IEEE Benchmark Year 2020 Results for 2019 Data 2020 … · 2020. 10. 20. · IEEE Benchmark Year...
Transcript of IEEE Benchmark Year 2020 Results for 2019 Data 2020 … · 2020. 10. 20. · IEEE Benchmark Year...
IEEE Benchmark Year 2020 Results for 2019 Data
2020 Distribution Reliability Working Group
Virtual Meeting
2
Background to IEEE DRWG Benchmark Study
1. Initiated in 2003, conducted annually
2. Participants are anonymous with key identifier to retain anonymity
3. Participation list is not revealed to anyone
4. Each participant can choose to share their results
5. No inference is made about good or bad reliability
6. Intended to provide information for users to assess their performance relative to peers
7. Called the 2020 Study (for 2019 Results)2
3
Benchmarking• Using annual key metrics (SAIDI, SAIFI and CAIDI) to assess
performance of a system may be useful, however, needs to be tempered
• DRWG Study attempts to identify various aspects that could cause a difference in reported metrics
• Data may not be directly comparable, since – Data collection & system differences exist
– Certain exclusion differences can occur, although we strive to have the differences minimized
• IEEE 1366-2003/2012 • addresses data issues by clearly defining the rules (i.e. what data should be
excluded)
• It DOES NOT address the data collection issues
• Companies may not report all forms of outages, due to data collection issues or other reasons
3
4
Region 0: Spans States or Unknown
Region 1: Northeast
Region 2: Mid-Atlantic
Region 3: Southeast
Region 4: Midwest
Region 5: Southwest
Region 6: South
Region 7: Northwest
Northwest: 8
Participants
Southwest: 12
Participants
Midwest: 18
Participants
South: 9
Participants Southeast : 4
Participants
Northeast: 6
Participants
Mid-Atlantic:
23 Participants
Regions represented by the participants
2020 Benchmark Study
Spans States or Other: 9
4
5
Respondents•About 260 companies have responded at some time
•2020 Survey: 89 entries responded
SAIDI ALL SAIDI IEEE SAIFI ALL SAIFI IEEE CAIDI ALL CAIDI IEEE
0 MIN 40 29 0.46 0.35 24 21
1 Q1 152 86 1.11 0.88 123 97
2 MEDIAN 233 126 1.44 1.12 181 116
3 Q3 403 178 1.67 1.39 251 133
4 MAX 1395 489 6.68 6.50 699 340
6
Respondents by Utility Size
Quartile Small 6 SAIDI ALL SAIDI IEEE SAIFI ALL SAIFI IEEE CAIDI ALL CAIDI IEEE
0 MIN 87 45 1.03 0.81 70 56
1 Q1 154 73 1.57 1.14 88 57
2 MEDIAN 169 103 1.68 1.32 99 71
3 Q3 479 174 2.20 1.46 173 113
4 MAX 672 281 3.41 2.28 349 172
Quartile Medium 48 SAIDI ALL SAIDI IEEE SAIFI ALL SAIFI IEEE CAIDI ALL CAIDI IEEE
0 MIN 40 29 0.46 0.35 24 21
1 Q1 153 102 1.14 0.97 117 101
2 MEDIAN 250 140 1.48 1.17 181 124
3 Q3 440 189 1.74 1.40 259 140
4 MAX 909 485 6.68 6.50 507 195
Quartile Large 34 SAIDI ALL SAIDI IEEE SAIFI ALL SAIFI IEEE CAIDI ALL CAIDI IEEE
0 MIN 83 48 0.79 0.63 62 53
1 Q1 156 85 1.07 0.85 143 103
2 MEDIAN 238 107 1.25 1.01 190 110
3 Q3 305 156 1.58 1.22 244 133
4 MAX 1395 489 2.55 2.18 699 340
7
Historic SAIDI-IEEE & Total
98105 109
103
8189 106 93
85 86 8197
7885 86
145 146 144155
116128
143
126115 115 115
124 120 123 126
192 198 200 196
167158
171163 158 159
166155
189
168178
75
125
175
225
2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019
Min
ute
s
2020 IEEE Benchmark: 2005 - 2019 IEEE SAIDI Quartiles
1st/2nd Qtrle IEEE SAIDI 2nd/3rd Qtrle IEEE SAIDI 3rd/4th Qtrle IEEE SAIDI
128 134 142178
106 125 202 153122 115 107 127 134 127 152
217 236 207
302
181211
310236
181 168 173 187222 209 233
366440
333
577
264
347
620
743
285 261 279 263
382 399 403
50
150
250
350
450
550
650
750
850
2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019
Min
ute
s
2020 IEEE Benchmark: 2005 - 2019 Total SAIDI Quartiles
1st/2nd Qtrle Total SAIDI
2nd/3rd Qtrle Total SAIDI
3rd/4th Qtrle Total SAIDI
8
Historic SAIFI-IEEE & Total
9
Historic CAIDI-IEEE & Total
10
Total (STD) SAIDI 2020
11
Total (STD) SAIFI 2020
12
Total (STD) CAIDI 2020
13
Major Event Excluded (IEEE SAIDI 2020)
14
Major Event Excluded (IEEE SAIFI 2020)
15
Major Event Excluded (IEEE CAIDI 2020)
16
We ask you a couple key questions
Trans Substation Breaker Recloser Fuses Svc Trans Customer 2 1/2 beta
Yes 83 85 85 85 84 84 68 60
No 6 4 4 4 5 5 21 29
% Yes 93% 96% 96% 96% 94% 94% 76% 67%
System Able to Record Outages at
Where do you record outages at?
Do you report using 2 ½ beta major events?
17
Questions
17