[IEEE 2013 2nd International Conference on Electric Power Equipment - Switching Technology...
Transcript of [IEEE 2013 2nd International Conference on Electric Power Equipment - Switching Technology...
2013 2nd International Conference on Electric Power Equipment - Matsue, Japan
Research on Interference Characteristics of Secondary Cables Due to Lightning Strol<e in
Grounding Grid of Substation LI Bingl,2 and XU Jianyuan 1,2
lSchool of Electrical Engineering, Shenyang University of Technology, Shenyang, 110870, Liaoning Province, China 2Liaoning Province Key Laboratory of Safe Operation and Monitoring of Power Grid, Shenyang, 1 10870, Liaoning
Province, China
Abstract- The lightning current might inject grounding
grid through the grounding lead when the arrester
suffered a lightning wave in substation. Then the ground
potential difference(the difference of ground potential
can/may) generated interference voltage on secondary
cables due to earth potential rising. The interference
voltage might lead secondary equipments misoperation
and even damage. To analysis the problems mentioned
above, a equivalent circuit model was established. The
transient voltage caused by ground potential difference to
secondary cables could be (can be or is) calculated by
EMTP-ATP. As a validation. the impulse voltage
generator was used as voltage source to simulate that
substation encountered with the lightning, and to measure
the interference voltage at cable terminal as well. Both
experiment and computer simulation had been taken to
analysis the influencing factors of the interference voltage
on secondary cables and the ports of secondary
equipments. The factors included the lightning current
injection point and the soil resistivity rate. The analysis
would provide a reasonable reference for wiring cables to
improve anti-jamming capability of secondary equipments
in substation.
Key words-lightning strike, ground potential difference,
secondary cable, interference voltage
1. INTRODUCTION
The ground potential of grounding resistance would
rise when the substation were struck by lightning and
lightning current injected into the grounding grid
through grounding lead. In addition, the area of
grounding grid was generally larger, this would cause
ground potential to distribute unevenly. These factors
leaded to ground potential difference[11. The ground
potential of two ground points was different when the
cable shield was grounded at both ends. The current that
flowed through cable shield would generate interference
on cable core through transfer impedance or transfer
admittance between cable shield and core [21.
During this paper, the experiment was set up with the
impulse voltage generator as the source of interference.
The experiment simulated that ground potential
difference interfered with secondary cable when the
lightning current injected into grounding grid. At the
same time, equivalent circuit was set up by ATP, and
compared the results of simulation and actual
measurement. Exhaustive papers analyzed the
interference voltage on cable core in some factors such
as the different lightning current injection points and
different soil resistivity rate. We could forecast the
interference voltage on secondary cable through the
combination of computer simulation and experiment,
and it also helped us to fmd out weak points of
secondary system. The analysis could be as a reference
to design secondary system of substation.
II. EQUIVALENT MODEL OF GROUNDING GRID
A. Model of Grounding Unit
The impedance characteristic of grounding electrode
under the impulse current was different from the power
current's. It was mainly due to the amplitude and
frequency of impulse current, which were both higher
than power current's. The grounding electrode were
resistive (conductive), inductive, capacitive when the
impulse current flowed through grounding electrode.
The length of grounding electrode and wave head of
lightning impulse was about same (the length of wave
head was calculated under the speed of light), so we
should consider wave to propagate along with
grounding electrode and the equivalent parameters of
grounding grid were distributed.
We should dispose grounding unit as loss of long
wire, and the figure 1 was equivalent circuit.
Rdx Ldx
---1 Cdx �Y""-1 I
I I
I
I Fig. I. The equivalent circuit diagram of distributed parameter
of grounding unit
Among the figure 1, the R , L , C and G respectively
represented resistance, inductance, both capacitance and
conductance to zero potential. Their formulas were as
following [5, 61.
L = jJl [In 21 -1] 27r r
C=cpG The grounding electrode was horizontal:
G _
27r 1-
12 p[ln - - 0.61]
2hr
The grounding electrode was vertical:
27r GJ =
41 p[ln--l] 2r
(Him) ( 1)
(F/m) (2)
(S/m) (3)
(S/m) (4)
Among the formulas, I , r and h respectively
represented length, radius and buried depth of
grounding unit, the unit was meter; E was the
permittivity of soil, the value was 9*8.86* 1 0-12; J.1 was
the permeability of soil, the value was 47r x 1 0-7, P was the resistivity of soil.
The R was ignored because R « L when high
frequency characteristic of lightning was considered [71. Not only self-inductance bus also mutual inductance
should be considered when the two grounding
electrodes were parallel. Otherwise, the mutual
inductance was approximate to zero. The following was
the formula of mutual inductance between two parallel
grounding electrodes.
Among the formula, the d was the distance of two parallel grounding elelctrodes and other parameters were same to the formulas from (1) to (4). The value of d should be not less than S meters, and when the value of d was greater than or equal to 10 meters, the mutual inductance could be ignored when it's value was less than S% of self-inductance's.
B. The Parameters of Ground Grid
According to the laboratory's grounding grid, the
equivalent circuit was established by ATP. The
laboratory was established for experimenting on high
voltage equipments in my university. The figure 2 was
the laboratory's grounding grid.
Fig. 2. The diagram of grounding grid of laboratory
2
The material of horizontal grounding electrode was
hot dip galvanized flat steel and vertical grounding
electrode was hot dip galvanized steel pipe. The type of
former was 40 x S mm and the buried depth was 0.6Sm.
The diameter of later was SOmm and the length was 3m.
The material of grounding lead on the line was brass
and its type was 63 x 3.55 mm. The parameters of
grounding electrode unit were calculated according the
formulas from (1) to (4), which were used to establish
equivalent circuit in ATP.
III. EQUIVALENT MODEL OF CABLE
A. Interference Principle of Grounding Electrode to
Cable
The lightning current injected grounding grid through the grounding lead when the arrester operated under lightning. As shown in figure 3, the U AB was potential difference of two grounding points which connected grounding grid with both ends of the cable shield. ZAB was grounding impedance of two grounding points.
ground A UAI3
Fig. 3. The diagram of ground potential
The I was interference current, which flowed through
shield of cable by Zr. and then interfered cable core
by transfer impedance of Zt .If the amplitude of
interference voltage exceed its maximum withstand
voltage of secondary device port, it would influenced or
even destroyed secondary devices.
B. Equivalent Circuit of Shielded Cable
To make single-core shielded cable as an example,
equivalent circuit was shown in figure 4. The ground
potential difference would generate current excitation
source of iu in cable shield. Then the iu would
generate interference on cable core through transfer
impedance of Zt . In the end, we could calculate out the
voltage of cable core. The length of cable was unit
length. The ZI was impedance of cable core and Z2 ZI
r'···· ... .. I I I I I I
UG :e12 L12 : I I . . ._--- --- --
Ze12
Fig. 4. Equivalent circuit of single-core shielded cable
was impedance of cable shield. The Zt that included
L12 and C12 was transfer impedance between shield
and core of cable. The Zc was characteristic impedance
of shielded cable.
IV. EXPERIMENT AND SIMULATION
A. The Validation of Model
The experimental loop was established by impulse
voltage generator and its corollary equipments. The
highest amplitude of impulse voltage was 2400 kY. The experimental loop had simulated the interference of ground potential difference to secondary cable. During the experiment, the shield of cable was grounded at both ends, the grounding points were N33
and N37. The amplitude of impulse voltage was 400kV,
waveform parameter was 1.2/S0 IJS, and grounding
point of generator was N22. The oscilloscope was used
to measure the interference voltage of cable core at the
end of cable and its equivalent impedance was I MQ. At the same time, equivalent circuit of experiment was
established by ATP and then calculated out interference
voltage of cable core. The figure S showed the
compared result of actual measurement and simulation.
20�-�--�--------� -actual measurement
-simulation
10 20 30 40 50
Time (�s)
Fig. 5. The interference voltage curve of actual measurement
and simulation on cable core
According to actual measurement, the amplitude of
interference voltage on cable core was 17.2V,
peak-to-peak value was 33.2V The interference voltage
might cause secondary equipment that connected with
cable to misoperate, mistakenly measure and even be
damaged. The simulation value was slightly lower than
the actual measurement value. This was due to that
radiation interference from lightning current in the
grounding grid to secondary cable was not considered.
Meanwhile, the propagation process of electromagnetic
wave might be encountered wall or other devices, and
then the refractive or reflex electromagnetic wave
would be dispersive. This resulted in measurement
result attenuating faster than simulation result's. The
simulated interference voltage on cable core also
couldn't be ignored because the amplitude of
interference voltage was 13.43V and peak-to-peak value
was 23.64V The equivalent model could truly reflect
the actual situation. So it was convenient to further
study the influence of lightning current injection point
and soil resistivity on cable core.
B. The Influence of Different Lightning Current
3
Injection Points on Voltage of Cable Core
The simulated lightning impulse voltage injected at
different grounding points by ATP. They were NIl, N24
and N3S. The amplitude of impulse voltage was 400kV
and waveform parameter was 1.2/S0 IJS .Under the soil
resistivity was 100 n· m, we got the response cure of
voltage on cable core, as shown in figure 6.
From the figure 6, when the injection point of
lightning impulse voltage was N3S, the interference
voltage on cable core was lower 63.43% than the NIl's.
15 f� "n24
0
1 1 1 'I ' c35
5 1[ �l 'iI, o ll l l l'III .lIt,I ,II( '�" i ' :7;',,",'" {i./l C " . I r [ 1 11 JI I;rirj':t ,ji,
I I ·,
'III ilil ii; 1'1 I r
0
II 5'
10 15 20 25 30 35 40 45 50
Time (�s)
Fig, 6, The voltage curve on cable core under the different
injection points
Therefore, it was better to choose the center of
grounding grid as the grounding point of arrester so that
it could reduce the interference on secondary cable and
its attached equipments.
C The Influence of Different Soil Resistivities on Voltage of Cable Core
The injection point of lightning impulse voltage was
NIl, the amplitude of voltage was 400kV and
waveform parameter was l.2/S0 IJS . The soil resistivity
were lOOn· ill 500n· ill and 10000· ill , the
corresponding curves of voltage were shown in figure 7.
50
'I ' -sol' reslstl"'y100 , f -soil resistivity500
I' u: -soil resistivity1000
III i[11 , : ', UI, I." Irl, )1';' JI :1 '\ ',2'. to. .':
40
30
20
10 �
" if rill'] h' [';1<: ;1 l' 'f 'f \' r: "I E 0
� -10
·20
·30
'"'0
·50 o
, '1 11 11 11 , I il t ',I I
..
10 15 20 25
Time (�s)
Fig, 7, The voltage curve on cable core under the different soil
resistivity
The interference voltage on cable core was
significantly increased with increasing soil resistivity.
When the soil resistivity was 10000· ill , the amplitude
of interference voltage was 46.97V It was 3.S times to
the voltage under the resistivity was 1000· ill .
Therefore, the design of grounding grid should reduce
soil resistivity reasonably, thereby reducing the
grounding resistance to reduce the interference of
secondary cable.
V. CONCLUSION
According to analysis in this article, such conclusions
can be obtained as following:
(l)Under the lightning voltage with amplitude of
400kV and waveform parameter was 1.2/50 f1S , the
amplitude of interference voltage measured on cable
core was 17.2V and the peak-to-peak value was 33.2V,
when the grounding point of impulse voltage generator
was set to be N22 and both ends of the cable shield are
grounded.
(2) The equivalent circuit was established according
to the experiment by ATP. Through the simulation, the
amplitude of interference voltage on cable core was
13.43V and peak-to-peak value was 23.6y' The result
was close to the actual measurement. The equivalent
model could be used to analyze the influencing factors
on secondary cable. The influencing factors included the
injection point of lightning voltage, soil resistivity and
so on.
(3) The lowest amplitude of interference voltage on
cable core was 4.97V when the injection point of
lightning impulse voltage was N35. With the increasing
of soil resistivity, the interference voltage on cable core
was significantly increased. When the soil resistivity
was 10000· ill , the amplitude of interference voltage
on cable core was 46.97Y.
Through the experiment and simulation, the lightning
impulse voltage would lead to ground potential
difference and then interfered on secondary cable when
the shield of secondary cable was grounded at both ends.
The cable might introduce interference voltage into
secondary system and effect on the sampling circuit of
computer monitoring equipment, the control circuit, the
communication circuit and son on. It would cause the
logic confuse, computer freeze, chip damage and so on.
The grounding point of arrester, reactor and other
equipments should be selected near the center of
grounding grid. When we lay cables, we should try to
avoid the grounding point of these devices. In order to
reduce the interference on secondary cables, the laying
of grounding grid should be reasonable to reduce soil
resistivity of grounding grid.
ACKNOLEDGMENT
Department of Science and Technology of Liaoning
Program(20 1 12200 1 l);supported by NSFC(51 177104,).
REFERENCE
[1] Tao Rong, Li Jinglu, Lin Zhi, et al. Anti-interference analysis for the grounding methods of control cable shielding line[J]. Journal of Electric Technology, 2007.
[2] Chen Jian, Yang Wenbin, Hu Chang, et al. Computation of induced over-voltage on grounding grid in substation due to lightning strike[J].Power System Technology, 2008, 24(3).
4
[3] Yang Lin, Wu Guangning, Cao Xiaobin. Modeling of grounding electrode for lightning transient response analysis[J].Proceedings of the CSEE, 2011, 31(13).
[4] Xie Guangrun.Power system grounding techniques[M].8eijing: China Electric Power Press, 1996.
[5] Grcev L, Popov M. On high-frequency circuit equivalents of a vertical ground rod[J]. IEEE Trans. on Power Delivery, 2005, 20(2).
[6] Liu Yaqing, Zitnik M, Thottappillil R. An improved transmision-line model of grounding system[J].IEEE Trans. on Electromagnetic Compatibility, 2001, 43(3).
[7] Liu Jianping, Yu Mingyou, Jin Jianwei. Research on transient potential difference of lightning current on grounding grid[J]. Journal of Air Force Radar Academy, 2011, 25(5).
[8] Calculation and analysis of the grounding system of 500kV substation[D]. Shandong University, 2008.
[9] Zhang Gang.Analysis of coupling function from external transient electromagnetic field to shielded cables[D].Harbin Institute of Technology.
[10] GB/T 17626.5-2008, Electromagnetic compatibility. Testing and measurement techniques. Surge immunity test[S].8eijing: Standards Press of China,2008(in Chinese).
E-mailofauthors:[email protected]