[IEEE 2010 4th International Power Engineering and Optimization Conference (PEOCO) - Shah Alam,...
-
Upload
mohd-fahmi -
Category
Documents
-
view
214 -
download
0
Transcript of [IEEE 2010 4th International Power Engineering and Optimization Conference (PEOCO) - Shah Alam,...
Abstract - Power transfer through a short transmission line is
mainly limited by thermal rating. Accurate determination of
thermal rating can maximize power transfer which
subsequently saves utility from building new lines. Thermal
rating normally is set to a certain conductor temperature which
during operation the transmission line will not has problem
with ground clearance and the conductor material properties
will remain in its original state. The conductor temperature
varies with weather parameters and loading and it has close
relationship with line sag or line ground clearance. The
conductor temperature can be determined by monitoring the
line ground clearance and weather parameters and the actual
thermal rating can be calculated. Monitoring of the line ground
clearance can be done in real time using laser distance
measurement sensor with data logger and real time monitoring
and calculation software. Index Terms-- thermal rating, conductor temperature,
ground clearance, weather parameter.
I. INTRODUCTION
Nowadays resources such as right of way (ROW) are
scarce, materials for building transmission line are more
expensive and to build new transmission lines are sometimes
almost impossible, power utility companies has to find ways
to fully utilize their assets especially transmission lines.
Power transfer through a short transmission line which is
less than 80 km is mainly limited by thermal rating and for
long transmission line it is limited by voltage drop limit and
stability limit [1]. In normal practice, short transmission
lines are normally loaded according to static thermal rating.
The static thermal rating is calculated based on conservative
assumption of weather parameters [2]. However in actual
condition the weather parameters may differ from the
assumption hence there is opportunity to increase the rating
when the actual rating is known. To determine the actual
thermal rating of the transmission line, real time
measurement on the weather parameter or conductor
temperature is required.
There are a few techniques can be used to determine the
actual thermal rating of transmission line. The techniques
can be divided into 2 categories; using weather model and
conductor temperature model. This paper discusses on both
models and for conductor temperature model the conductor
temperature is determined using line ground clearance
technique. Dynamic thermal rating (DTR) monitoring
system also will be discussed.
TNB is a biggest power utility company in Malaysia.
II. DYNAMIC THERMAL RATING MONITORING SYSTEM
There are 3 main components to form the Dynamic
Thermal Rating (DTR) system that is remote monitoring
station, communication system and system computer. The
overview of system is shown in Figure 1. Remote monitoring
station gathers information on the environment in which the
transmission lines are located and also information on the
line clearance. The remote monitoring station includes
weather sensors and laser distance measurement (LDM)
sensors. The LDM sensors are used for measuring the line
ground clearance. The weather sensors consist of wind speed
and direction sensors, pyranometer and temperature sensor.
The remote monitoring station is placed at a critical location
along the transmission line where the wind cooling is
minimal or where there is an increased probability of contact
between the conductor and objects on the ground.
Figure 1- Dynamic thermal rating (DTR) system block
diagram
Remote monitoring station consists of a data logger, weather
sensors and 2 units of laser distance measurement sensor. The
function of this station is to gather weather data and line clearance
data in a defined interval and transmit it through a serial
connection to the system computer whenever dial-up connection is
established. Data obtained from the remote monitoring system will
be used for thermal rating calculation by the thermal rating
calculation software in the system computer. All sensors are
connected to the logger through its analog input terminals. The
connection of sensors to the data logger is shown in Figure 2.
Figure 2 - Components integration block diagram of the
Dynamic Thermal Rating (DTR) system
Weather sensors are used to measure weather data such
as wind speed and direction, ambient temperature and solar
Thermal Rating Monitoring of the TNB
Overhead Transmission Line using Line Ground
Clearance Measurement and Weather
Monitoring Techniques Azlan Abdul Rahim, Izham Zainal Abidin, Faris Tarlochan, Mohd Fahmi Hashim
The 5th
Student Conference on Research and Development –SCO
11-12 December 2007, Malaysia The 4th International Power Engineering and Optimization Conference (PEOCO2010), Shah Alam, Selangor, MALAYSIA. 23-24 June 2010.
978-1-4244-7128-7/10/$26.00 ©2010 IEEE 274
radiation. The wind speed data is recorded in meter per
second and wind direction is in degrees counter clock wise
from north. Sensors used for wind speed and direction
measurement is a three-cup anemometer and a wind vane on
a single axis. The anemometer is a contact-type wind sensor
which, when rotated by the wind, triggers a series of
momentary switch closures that are directly related to wind
speed. The wind vane uses a potentiometer to sense
direction changes. Depending on the position of the
potentiometer wiper, the output is a voltage signal that
corresponds to the position of the vane. By orienting the
vane to North (0 degree) during installation, wind direction
can be easily calculated from the output voltage. The
resolution of the wind vane is 1 degree. Ambient
temperature is sensed using a thermistor element which
changes resistance in response to temperature fluctuations.
For maximum accuracy, the sensor is isolated from the
effects of sunlight which can cause misleading temperature
and humidity measurements. The solar radiation shield is
used to give this protection. Solar radiation sensor or
pyranometer is used to measure solar radiation. The sensor
output is in voltage which changes in response to solar
radiation fluctuations. The solar radiation measurement is
recorded in watts per meter2. A complete installation of the
weather sensors is as shown in Figure 3.
Figure 3 - Weather sensors installation next to the
transmission line
Laser distance measurement sensor utilize laser light for
distance measurement. It allows accurate and contact-less
distance measurement over a wide range using the reflection
of a laser beam. The sensor measurement range is from 0.2
meter to 200 meter and the accuracy is ±1.5 millimeter.
Verification of the measurement accuracy has been done
where measurement by the laser distance measurement
sensor is compared with measurement tape. The results
confirmed that the measurement accuracy was within
tolerance of ±1.5 millimeter. The laser distance
measurement sensor is used to measure the transmission line
clearance to the ground where the distant ranges from 12 to
16 meter. It was installed on the ground directly under the
transmission line at the middle of the span as shown in
Figure 4.
Figure 4 - Laser distance measurement sensor installation
The output from the sensor is a current signal which
varies in the range of 4 to 20 milliampere depending on
distance measured. In this thermal rating system, at the
monitoring point, the line ground clearance is in the range of
13.0 to 15.5 meter. The sensor output has a linear
relationship with the distance measured, whereby 4
milliampere corresponds to 13.0 meter and 20 milliampere
corresponds to 15.5 meter. For data logging and retrieving
by the system computer, the current output is connected to
the remote station data logger through one of its analog input
points. To enable continuous monitoring of the line
clearance, the sensor was set to operate in automatic mode
which will take measurement continuously at every one
minute interval. Data from remote monitoring system is
transmitted to system computer via a wireless data
communication system. The communication system used in
this real time thermal rating system is the GSM wireless data
call system. This communication system is more suitable for
use in the DTR system compared to fix line due to
connectivity issues and cost. The GSM wireless is easy to be
implemented; it is robust and suitable for use in the outdoor
environment. Data transfer from remote monitoring station
to system computer is based on dial-up connection at every
10 minutes interval. The system computer consists of 2
software modules that is thermal rating calculation module
and thermal rating display module. It has 2 primary
functions, namely to process the weather and line clearance
data then calculate the thermal rating of the line and to
display the thermal rating in real-time. There are two
methods used for the thermal rating calculation, by using
weather based calculation and line clearance based
calculation. Weather based calculation utilized weather data
that is wind speed and direction, ambient temperature and
solar radiation data from monitoring station at site. The
calculation of the thermal rating is based on thermal balance
energy equation as described in IEEE Std 738 [3].
Line clearance based calculation utilized line clearance
data, ambient temperature data, line load data and solar data
from the monitoring site. Weather based thermal rating
calculation process as shown in Figure 5. In the first step the
program read the input data on conductor parameter such as
the conductor resistance at low temperature and high
temperature, conductor diameter, conductor weight per
kilometer, number of aluminum strand, number of steel
strand, diameter of aluminum and steel strand. Data on
weather parameter at the monitoring site such as wind speed,
wind direction, ambient temperature, and solar radiation data
is read from the real time updated text file. The line load
data is read from the SCADA database.
275
Figure 5 - Weather based thermal rating calculation program
flowchart
Based on the input data, the program calculates the
convection heat loss qc of the conductor. The equation used
in the calculation depends on the wind speed condition, for
no wind condition, the natural convection equation (1) is
used, for available wind speed the force convection heat loss
equation (2) and (3) is used where the highest value is used
for the qc.
(1)
(2)
(3)
The program then calculates the conductor radiation
heat loss qr and solar heat gain qs using equation (4) and (5)
respectively. For explanation of the equations please refer
IEEE Std 738 [3]. Next the program calculates conductor
resistance at the maximum conductor temperature as defined
by the user. Finally the thermal rating of the conductor Ir is
calculated using equation (6).
(4)
(5)
(6)
Line ground clearance based thermal rating calculation
process is as shown in Figure 6. The line clearance data
input for this program is from the remote monitoring station.
The conductor temperature is then determined based on the
conductor temperature and line ground clearance
relationship. The equation produced from this relationship is
given in equation (7). The relationship was developed by a
calibration process where line clearance and conductor
temperature was measured. Then qc is determined using
equation (2) and (3), where the qr, R(Tc) is calculated at the
instantaneous conductor temperature, the Ir is the existing
line load current and qs is based on the solar radiation
measurement.
(7)
Figure 6 - Line ground clearance based thermal rating
calculation program flowchart
Based on the qc value determined previously, the
equivalent perpendicular wind speed is calculated using
equation (2) and equation (3), the lowest value is used for
the next calculation. Next the qc, qr is calculated based on
the maximum conductor temperature and the calculated
wind speed. Then with the latest value of qc, qr , R(Tc) and qs
the thermal rating Ir is calculated using equation (6).
III. GROUND CLEARANCE RELATIONSHIP WITH CONDUCTOR
TEMPERATURE
Ground clearance has direct relationship with line sag as
shown in Figure 7. The line sag can be calculated based on
equation (8) as suggested in EPRI Increased Power Flow
Guide Book [4]. To develop conductor temperature and line
sag relationship, actual transmission line section physical
dimension including span length is measured as shown in
Figure 7. The transmission line span is modeled into sag
calculation formula. The line sag for every 5ºC increase of
conductor temperature from 20ºC up to 120ºC is calculated
and plotted.
Figure 7 – The selected transmission line span physical
dimension
For a reference, at a known conductor temperature and
horizontal tension the line sag is given by equation (8).
(8)
276
Parameters Value Unit
Linear expansion coefficient, α 1.93 x 10-05 1/°C
Elastic coefficient 7033 kg/mm2
Length between towers 362 m
Weight per length 1.18246 kg/m
Tension at 25 °C 1758.3 kg
Table 1 - Input and calculated data for the Zebra conductor
sag calculation [5]
At 25°C, reference to the input data in Table 1, the
calculated sag given as follows.
Weight, w
= 1.18246 kg/m
Horizontal tension, H
= 1758.3 kg
Span length, S
= 362 m
Sag, D
= 11.01592 m
The actual conductor length L, at the correspondence
line sag is given by equation (9).
S
DSL
3
8 2
+=
(9)
Span length, S = 362 m
Sag, D = 11.01592 m
Conductor length, L
= 362.8939 m
Subsequently equation (10) and (11) are used to
calculate conductor length and the corresponding sag for a
each conductor temperature.
( )[ ]frTT TTLL
REF Re1 −+= α (10)
( )
8
3 SLSD T −
=
(11)
Table 2 shows the calculated line sag value for given
conductor temperature.
Conductor temperature,
Tc
(°C)
Conductor length, L
(m) Sag, D (m)
25 362.8939257 11.01592
26 362.9009296 11.05899
27 362.9079334 11.10189
28 362.9149373 11.14463
29 362.9219411 11.18720
30 362.9289450 11.22962
31 362.9359488 11.27187
32 362.9429527 11.31397
33 362.9499565 11.35591
34 362.9569604 11.39769
35 362.9639643 11.43932
36 362.9709681 11.48081
37 362.9779720 11.52214
38 362.9849758 11.56332
39 362.9919797 11.60436
Table 2 - Calculated line sag for a given conductor
temperature
The relationship between the conductor temperature and
the line sag is shown in Figure 8. The graph shows that the
relationship is almost linear for the temperature between
28ºC to 120 ºC. From this relationship the conductor
temperature and line ground clearance is determined.
Conductor Temperature vs Sag
0
20
40
60
80
100
120
140
11.0
1591
7
11.1
4462
8
11.2
7187
11.3
9769
2
11.5
2213
9
11.6
4525
7
11.7
6708
7
11.8
8766
8
12.0
0703
8
12.1
2523
4
12.2
4228
8
12.3
5823
3
12.4
7310
1
12.5
8692
12.6
9972
12.8
1152
6
12.9
2236
5
13.0
3226
2
13.1
4123
9
13.2
4932
13.3
5652
6
13.4
6287
9
13.5
6839
8
13.6
7310
3
13.7
7701
3
13.8
8014
4
13.9
8251
5
14.0
8414
1
14.1
8504
14.2
8522
6
14.3
8471
4
14.4
8351
8
Sag (m)
Co
nd
ucto
r te
mp
era
ture
(d
eg
C)
Figure 8 - Relationship between conductor temperature and
sag
For calibrating the temperature and line clearance
relationship curve, a site test was conducted by measuring
the test conductor temperature and measuring actual line
ground clearance using laser distance measurement sensor,
the test setup shown in Figure 9 and Figure 10. The test
conductor is the same type of conductor used for the real
transmission line and the test conductor was exposed to the
same weather condition as at site. The same amount of load
current was injected into the test conductor to simulate the
actual line condition. Thermocouple wires were used to
measure the conductor temperature and temperature data
logger was used to record the temperature. The line ground
clearance was measured using laser distance measurements
sensor and the measurement data was logged for every 1
minute.
Figure 9 - Test setup for calibrating the conductor
temperature and line ground clearance relationship
277
Figure 10 - Photograph of the site test setup
Based on the conductor temperature and sag data from
the calculation, the corresponding line clearance was
calibrated with line ground clearance measurement using
laser distance measurement. Then the calculated ground
clearance was plotted to form a relationship between the
conductor temperature and ground clearance. Additional
data from the actual line clearance measurement and
temperature measurement were plotted onto the same
calculation data plot to verify the relationship between
conductor temperature and line ground clearance produced
by calculation. The plot is shown in Figure 11.
Conductor temperature vs ground clearance
y = -0.0027x4 + 0.1156x3 - 1.0157x2 - 37.31x + 570.05
R2 = 1
0
20
40
60
80
100
120
140
12 12.5 13 13.5 14 14.5 15 15.5 16
ground clearance (m)
co
nd
ucto
r te
mp
(d
eg
C)
Experiment
Calculated
Poly. (Calculated)
Figure 11 - Relationship between conductor temperature and
line ground clearance verified by experiment
From the experiment, the relationship between
conductor temperature and line ground clearance is given as
follow;
05.57031.370157.11156.00027.0 234
+−−+−= xxxxy (12)
Where
y = conductor temperature in °C
x = line ground clearance in meter
IV. RESULT AND CONCLUSION
Use of dynamic thermal rating (DTR) technology can
lead to modest gains in power flow capacity, typically 5% –
20%. In this research, development of DTR system has been
carried out and the system has been installed at the TNB’s
275kV transmission lines particularly at the selected line
span. The selected line is a very important line which
carrying large power from big power generations to the
national grid and potential to be overloaded during tripping
of other lines. However the transfer capabilities of the lines
are limited by its static rating which is 683MVA (or 1434
Amperes per phase at 275kV) per line. The static rating is
calculated based on the assumption of ambient temperature
35°C, wind speed 0.4469 m/sec, 850W/m2 solar radiation
and 75°C maximum conductor temperature. The system
calculation results have been verified by series of testing
including laboratory testing and site testing. The result as
shown in Figure 12 shows that; the actual thermal rating is
almost always greater than the static rating and the measured
load is always significantly lower than the static rating.
Figure 12- Dynamic thermal rating profile of the study line
The probability density of the thermal rating for a
period of 2 months is plotted using kernel smoothing density
estimate function in Matlab as shown in Figure 13. The
graphs show that the load is always below the static rating.
Only during emergencies would the load exceed the normal
static rating. The dynamic thermal rating is mostly 20%
higher than the static rating which is shown by the tip of the
dynamic thermal rating probability density graph in Figure
13. These graphs also show that the dynamic thermal rating
is sometimes below the static rating but the probability is
small about 3% as given by the gray color area on the Figure
13. It is important to note that when this does occur and the
load is high, the sag limits may be exceeded. This does
happen on real lines, but most often no one knows it. In
fact, it is impossible to know this is happening without DTR
system. This is a hidden risk with the traditional static rating
method.
Conductor
under test
278
Figure 13 - Probability density plot of the dynamic thermal
rating and line loading
The reasons for limiting the current in a conductor is to
avoid excess sag, and damage (due to annealing) caused by
operating at too high a temperature. The operating
temperature of a Zebra conductor used in the study line is
limited to 75ºC due to the sag limit. Figure 14 shows the
probability density graph of the conductor temperature
calculated by the DTR system. Most of the time the
conductor temperature is around 30ºC and the maximum is
about 50ºC which is far below the limit. However the
conductor temperature is always higher than the ambient
temperature as shown in the graph.
Figure 14 - Probability density plot of the conductor and
ambient temperature
Figure 15 shows the recorded line ground clearance in a
day. This plot shows that the line ground clearance varies
from 14.6 meter to 15.1 meter in a day, this is corresponding
to about 10ºC variation of conductor temperature. The
lowest recorded ground clearance is around 12.00a.m. to
2.00p.m. and the highest ground clearance is during early
morning between 4.00a.m. to 6.30a.m.
Figure 15 - Daily line ground clearance at the monitoring
site
Solar radiation can increase the temperature of an
overhead conductor by up to 15ºC during the mid sunny day,
depending on conductor absorptivity, emissivity, wind speed
and direction. During Mac 2009, at the monitoring site of
the transmission line, daily solar starts at about 7.20 a.m. and
end at about 7.20 p.m. The maximum solar radiation
recorded was during mid day which was about 1050 W/m2
as shown in Figure 16.
Figure 16 - Typical daily solar radiation profile at the
monitoring site
Wind speeds below 1.5 m/s are quite variable in both
speed and direction. This is also reported by other
researchers [6,7,8,9,10]. Though it is common to calculate
static ratings for perpendicular wind, field measurements
verify that winds below 1.5 m/s are not persistent in
direction. Therefore low winds are only occasionally
perpendicular to the conductor. It would be more reasonable
to assume an average wind direction somewhere between
perpendicular and parallel. A conservative assumption
would be that the wind is more nearly parallel rather than
perpendicular. Wind speed typically increases during the day
but rapid large changes in speed and direction are common.
Figure 17 shows the wind speed recorded for 48 hours
duration at the monitoring site; it shows that during day time
the wind speed is mostly higher compared to night.
279
Figure 17 - Wind speed variation at the monitoring site
Based on the DTR system data, conclusion can be made
as follows;
The dynamic thermal rating is mostly 20% higher than
the static rating. It is above the static rating 97% of the time
but in some instances it is below the static rating.
Conductor temperature varies between 25 ºC to 52 ºC
with ambient temperature varies between 22 ºC to 32 ºC
throughout day and night but most of the time the conductor
temperature is around 30 ºC. The actual ambient is lower
compared to the assumption made in the static thermal rating
calculation which is 35 ºC. This is one of the reasons why
the actual thermal rating is higher than the static thermal
rating.
The ground clearance of the line bottom conductor at
the monitoring site varies between from 14.6 meter to 15.1
meter which is corresponding to about 10ºC variation of
conductor temperature.
Solar time and solar radiation pattern is almost same
throughout the 6 months monitoring period, about 5% of the
time the solar radiation is greater than the value used for
static thermal rating calculation which is 850W/m2
however
most of the time the solar radiation is less than 850W/m2.
This is another reason why most of the time the actual
thermal rating is higher than the static thermal rating.
Wind speed is below 1.5m/s most of time but typically
increases during the day but rapid large changes in speed
and direction. DTR system data verify that winds below 1.5
m/s are not persistent in direction. However wind speed
value used in the static rating calculation is only 0.443 m/s at
30 degree angle toward the conductor axis which considered
conservative. This is another reason why the actual thermal
rating is higher than the static thermal rating.
V. REFERENCES
[1] Prabha Kundur "Power System Stability and Control", McGraw-Hill
1994.
[2] Black, W.Z. and Rehberg, R.L., Simplified Model for Steady State
and Real Time Ampacity of Overhead Conductors IEEE/PES Winter
Meeting, Paper No. 88 WM 236-5, 1985.
[3] IEEE Standard for Calculating the Current-Temperature Relationship
of Bare Overhead Conductors, IEEE Std 738-2006.
[4] R. Adapa, Technical Report – “Increased Power Flow Guidebook:
Increasing Power Flow in Transmission and Substation Circuits”,
EPRI, Palo Alto, CA, 2005.
[5] Cigre Working-group 22.12, The Thermal Behaviour of Overhead
Conductors, Section 3: Mathematical Model for Evaluation of
Conductor Temperature in The Unsteady State, Electra No.174
October 1997, pp. 59-69.
[6] Tapani 0. Seppa, Summer Thermal Capabilities of Transmission
Lines In Northern California Based on A Comprehensive Study of
Wind Conditions, IEEE Transactions on Power Delivery, Vol. 8. No.
3, July 1993.
[7] Patrick M. Callahan, D. A. Douglass. An Experimental Evaluation of
A Thermal Line Uprating by Conductor Temperature and Weather
Monitoring, IEEE Transactions on Power Delivery, vol. 3, NO. 4,
October 1988.
[8] Stephen D. Foss, Evaluation of An Overhead Line Forecast Rating
Algorithm, IEEE Transactions on Power Delivery, Vol. 7, No. 3, July
1992.
[9] Black, W.Z. and Rehberg, R.L., Simplified Model for Steady State
and Real Time Ampacity of Overhead Conductors IEEE/PES Winter
Meeting, Paper No. 88 WM 236-5, 1985.
[10] Dale A. Douglass, Field Studies of Dynamic Thermal Rating
Methods for Overhead Lines, 0-7803-5515-6/99, IEEE, 1999.
VI. BIOGRAPHIES
Azlan Abdul Rahim, received his Bachelor in Electrical & Electronic
Engineering from University Science of Malaysia in 1996. He joined TNB
Research Sdn. Bhd. in 1997. Currently, he is a senior researcher at Power
System Group, TNB Research Sdn. Bhd. and he is also a part time student
doing Master Degree at Universiti Tenaga Nasional. His research areas
include real time monitoring and control, dynamic thermal ratings of
electrical equipment, power system wide area measurement, fault detection
and location
Izham Zainal Abidin, received his Bachelor in Electrical Engineering
degree from Southampton University, UK in 1997. He obtained his PhD in
Electrical Engineering from the University of Strathclyde, Scotland, UK in
2002. Currently, he is an academic staff at Department of Electrical Power
Engineering, Universiti Tenaga Nasional Malaysia. His research interests
include voltage stability studies, artificial intelligence and fuzzy logic
application to Power Systems problems, and robotics
Faris Tarlochan, received his Bachelor in Mechanical Engineering and
Master in Science from Purdue University in 1998 and 2001 respectively
and obtained his PhD from Universiti Putra Malaysia in 2007. He joined
Universiti Tenaga Nasional 2007. Currently, he is an Associate Professor at
Universiti Tenaga Nasional. His research areas include finite element
analysis, optimization, design and applied mechanics
Mohd Fahmi Hashim, Mohd Fahmi Hashim received his Bachelor in
Electrical Engineering from University of Sheffield in 2003. Currently he
is a Researcher in TNBR. Prior to join TNBR, he works as a Research
Assistant in UTP since 2004. His research interests include fault location
and dynamic thermal rating
280