– 1 – ISA–TR105–CDR052016
DRAFT RECOMMENDED PRACTICE
ISA-dRP105.00.01-201XCD16
Management of a Calibration Program For Monitoring And Control Systems
Approved xx month xxxx
Copyright 2016 ISA. All rights reserved.
123456789
10111213141516171819202122232425
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
ISA–TR105 CDR052016 – 2 –
ISA-dRP105.00.01-201X
Quality Management System for Implementation and Maintenance of an Industrial Calibration Program
ISBN:
Copyright © 201X by ISA, the International Society of Automation. All rights reserved. Not for resale. Printed in the United States of America. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means (electronic mechanical, photocopying, recording, or otherwise), without the prior written permission of the Publisher.
ISA67 Alexander DriveP.O. Box 12277Research Triangle Park, North Carolina 27709USA
Copyright 2016 ISA. All rights reserved.
43
44454647484950515253545556575859
– 3 – ISA–TR105–CDR052016
Preface
This preface, as well as all annexes, is included for information purposes and is not part of ISA-dRP105.00.01-201X.
This document has been prepared as part of the service of ISA toward a goal of uniformity in the field of instrumentation. To be of real value, this document should not be static but should be subject to periodic review. Toward this end, the Society welcomes all comments and criticisms and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67 Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-8411; Fax (919) 549-8288; E-mail: [email protected].
The ISA Standards and Practices Department is aware of the growing need for attention to the metric system of units in general, and the International System of Units (SI) in particular, in the preparation of instrumentation standards. The Department is further aware of the benefits to USA users of ISA standards of incorporating suitable references to the SI (and the metric system) in their business and professional dealings with other countries. Toward this end, this Department will endeavor to introduce SI-acceptable metric units in all new and revised standards, recommended practices, and technical reports to the greatest extent possible. Standard for Use of the International System of Units (SI): The Modern Metric System , published by the American Society for Testing & Materials as IEEE/ASTM SI 10-97, and future revisions, will be the reference guide for definitions, symbols, abbreviations, and conversion factors.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals and interests in the development of ISA standards, recommended practices, and technical reports. Participation in the ISA standards-making process by an individual in no way constitutes endorsement by the employer of that individual, of ISA, or of any of the standards, recommended practices, and technical reports that ISA develops.
CAUTION — ISA DOES NOT TAKE ANY POSITION WITH RESPECT TO THE EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS ASSERTED IN CONNECTION WITH THIS DOCUMENT, AND ISA DISCLAIMS LIABILITY FOR THE INFRINGEMENT OF ANY PATENT RESULTING FROM THE USE OF THIS DOCUMENT. USERS ARE ADVISED THAT DETERMINATION OF THE VALIDITY OF ANY PATENT RIGHTS, AND THE RISK OF INFRINGEMENT OF SUCH RIGHTS, IS ENTIRELY THEIR OWN RESPONSIBILITY.
PURSUANT TO ISA’S PATENT POLICY, ONE OR MORE PATENT HOLDERS OR PATENT APPLICANTS MAY HAVE DISCLOSED PATENTS THAT COULD BE INFRINGED BY USE OF THIS DOCUMENT AND EXECUTED A LETTER OF ASSURANCE COMMITTING TO THE GRANTING OF A LICENSE ON A WORLDWIDE, NON-DISCRIMINATORY BASIS, WITH A FAIR AND REASONABLE ROYALTY RATE AND FAIR AND REASONABLE TERMS AND CONDITIONS. FOR MORE INFORMATION ON SUCH DISCLOSURES AND LETTERS OF ASSURANCE, CONTACT ISA OR VISIT WWW.ISA.ORG/STANDARDSPATENTS.
OTHER PATENTS OR PATENT CLAIMS MAY EXIST FOR WHICH A DISCLOSURE OR LETTER OF ASSURANCE HAS NOT BEEN RECEIVED. ISA IS NOT RESPONSIBLE FOR IDENTIFYING PATENTS OR PATENT APPLICATIONS FOR WHICH A LICENSE MAY BE REQUIRED, FOR CONDUCTING INQUIRIES INTO THE LEGAL VALIDITY OR SCOPE OF PATENTS, OR DETERMINING WHETHER ANY LICENSING TERMS OR CONDITIONS PROVIDED IN CONNECTION WITH SUBMISSION OF A LETTER OF ASSURANCE, IF ANY, OR IN ANY LICENSING AGREEMENTS ARE REASONABLE OR NON-DISCRIMINATORY.
ISA REQUESTS THAT ANYONE REVIEWING THIS DOCUMENT WHO IS AWARE OF ANY PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE DOCUMENT NOTIFY THE ISA STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER.
Copyright 2016 ISA. All rights reserved.
60
616263646566676869707172737475767778798081828384858687888990919293949596979899
100101102103104105106107108109110111112113
ISA–TR105 CDR052016 – 4 –
ADDITIONALLY, THE USE OF THIS DOCUMENT MAY INVOLVE HAZARDOUS MATERIALS, OPERATIONS OR EQUIPMENT. THE DOCUMENT CANNOT ANTICIPATE ALL POSSIBLE APPLICATIONS OR ADDRESS ALL POSSIBLE SAFETY ISSUES ASSOCIATED WITH USE IN HAZARDOUS CONDITIONS. THE USER OF THIS DOCUMENT MUST EXERCISE SOUND PROFESSIONAL JUDGMENT CONCERNING ITS USE AND APPLICABILITY UNDER THE USER’S PARTICULAR CIRCUMSTANCES. THE USER MUST ALSO CONSIDER THE APPLICABILITY OF ANY GOVERNMENTAL REGULATORY LIMITATIONS AND ESTABLISHED SAFETY AND HEALTH PRACTICES BEFORE IMPLEMENTING THIS DOCUMENT.
THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE IMPACTED BY ELECTRONIC SECURITY ISSUES. THE COMMITTEE HAS NOT YET ADDRESSED THE POTENTIAL ISSUES IN THIS VERSION.
The following people served as members of ISA Committee ISA105:
NAME COMPANY
This recommended practice was approved for publication by the ISA Standards and Practices Board on __________.
NAME COMPANY
Copyright 2016 ISA. All rights reserved.
114115116117118119120121122123124125126127128129130
131132133134135136
137138139140
– 5 – ISA–TR105–CDR052016
Table of ContentsIntroduction........................................................................................................................................... 6
Purpose.......................................................................................................................................... 6Organization.................................................................................................................................. 7
1 Scope............................................................................................................................................. 8
1.1 General Applicability...........................................................................................................81.2 Inclusions and exclusions..................................................................................................8
2 Normative References.................................................................................................................. 8
3 Definition of Terms and Acronyms..............................................................................................8
3.1 Terms................................................................................................................................... 83.2 Acronyms........................................................................................................................... 10
4 Establishing a calibration program............................................................................................10
4.1 General.............................................................................................................................. 104.2 Calibration program concepts.........................................................................................104.3 Calibration program..........................................................................................................114.4 Device calibration.............................................................................................................114.5 Loop calibration................................................................................................................. 114.6 Test equipment................................................................................................................. 124.7 Competency.......................................................................................................................12
5 Calibration Program Planning....................................................................................................12
5.1 General.............................................................................................................................. 125.2 Loops and components in the calibration program.......................................................125.3 Component and loop criticality determination...............................................................125.4 Establishing required loop tolerance..............................................................................135.5 Calculating theoretical loop tolerance............................................................................135.6 Calibration Confirmation Intervals..................................................................................145.7 Calibration equipment......................................................................................................155.8 Calibration record system................................................................................................165.9 Calibration procedures.....................................................................................................165.10 Calibration personnel.......................................................................................................175.11 Responsibilities................................................................................................................. 17
6 Loop and Component Performance Verification......................................................................18
6.1 General.............................................................................................................................. 187 Calibration program management.............................................................................................18
7.1 Control............................................................................................................................... 187.2 Assurance..........................................................................................................................187.3 Improvement......................................................................................................................18
8 Examples..................................................................................................................................... 19
Annex A – Example Documentation................................................................................................24
Copyright 2016 ISA. All rights reserved.
141142
143144145
146147148
149
150151152
153154155156157158159160
161162163164165166167168169170171172
173174
175176177178
179
180181
ISA–TR105 CDR052016 – 6 –
IntroductionPurposeThe purpose of this recommended practice is to provide the basic framework for developing and maintaining a consistent calibration program for industrial automation and control systems, including instrumentation used in safety instrumented systems. The recommended practice provides guidance on methodologies for verification and calibration of monitoring and control systems by considering the accuracy of each loop required by the process and then adjusting loop component(s) to achieve the desired loop or component accuracy.
Accurate, reliable, and repeatable operation of loops in monitoring and control systems is vital to maintaining the safety and reliability of a facility. A well-considered calibration program, properly implemented and maintained, can directly contribute to the assurance of the desired operation of the monitoring or control system for the facility. A calibration establishes periodic assessments to be performed to monitor performance of instrumentation over time. Data acquired during these assessments not only aids in the establishment of future calibration intervals, but also is critical in the allocation of capital and operational resources. Clearly defined policy and procedures support the efforts of maintenance planners to schedule adequate labor and equipment for calibration both during and between facility outages. Following calibration procedures reduces the likelihood of human errors due to improper practices, ensures the desired results of the calibration efforts, and promotes the proper operation of monitoring and control systems.
In automation systems, more hardware faults occur in measuring instrumentation, transmitters, and control valves than in the control/logic systems. A calibration program can aid in early detection of failures. Reduction or elimination of instrument and control system calibration and maintenance of instrumentation and control systems may increase the likelihood of system problems, including:
Inaccuracy of measurements and control
System not responding correctly or as desired
Reduced awareness of instrument performance and actual need for calibration and maintenance
Potential for incorrect reporting of environmental data
However, targeted reduction, or increase, using data derived from an instrument asset management program can both reduce maintenance costs and improve reliability/safety.
Various definitions of the term calibration can be found:
The formal definition of calibration by the International Bureau of Weights and Measures is the following: "Operation that, under specified conditions, in a first step, establishes a relation between the quantity values with measurement uncertainties provided by measurement standards and corresponding indications with associated measurement uncertainties (of the calibrated instrument or secondary standard) and, in a second step, uses this information to establish a relation for obtaining a measurement result from an indication."
NIST Handbook 150:2001: 1.5.8 Calibration: Set of operations that establish, under specified conditions, the relationship between values of quantities indicated by a measuring instrument or measuring system, or values represented by a material measure or a reference material, and the corresponding values realized by standards.
NOTE 1 The result of a calibration permits either the assignment of values of measured to the indications or the determination of corrections with respect to indications.
NOTE 2 A calibration may also determine other metrological properties such as the effect of influence quantities.
Copyright 2016 ISA. All rights reserved.
182
183
184185186187188189
190191192193194195196197198199200
201202203204205
206
207
208209
210
211
212213
214
215216217218219220
221222223224
225226
227
– 7 – ISA–TR105–CDR052016
NOTE 3 The result of a calibration may be recorded in a document, sometimes called a calibration certificate or a calibration report.
According to standards ISO 9001:2008 7.6 and ANSI/NCSL Z540.3-2006, calibration is a comparison of the device being tested against a traceable reference instrument (calibrator) and documentation of this comparison. Although calibration does not formally include any adjustments, in practice, adjustments are possible and often included in the calibration process.
Maintenance practices for devices such as gauges and indicators, unfortunately, may occur only when the error in reading becomes large enough to be obvious to the operator or technician. Maintenance personnel routinely make decisions based on these devices. A faulty indication on such a device could lead to the release of energy or other unsafe action. A well-considered calibration program that periodically measures actual loop accuracy can drive the calibration intervals for these devices.
Instrumentation based on newer technology, e.g. “smart” devices, is more accurate than older technology devices and more stable, requiring less frequent calibration monitoring. A calibration program should also accommodate these types slightly differently, such as calibration check frequency and accuracy of calibration equipment required.
Companies striving to maintain a safe working environment while ensuring the reliability of their facilities may use calibration as a means of verifying the functionality and accuracy of their equipment.
Like other aspects of maintenance, there are many things to consider when establishing a company calibration program. Certainly, this is the case with the calibration of monitoring and control loops in a control system. This document presents a recommended approach to developing, implementing and maintaining a calibration program that is intended to lead to increased accuracy and reliability of monitoring and control systems, decreased production costs, and quality control improvements. More important, this approach is also intended to lead to increased safety of operation as the result of increased accuracy and reliability of the instrumentation.
This approach to calibration has proven successful when companies have adhered to the concepts set forth in these guidelines, enabling those companies to realize the full benefits from a standardized approach to calibration.
The intended audience for this document is any company or industry that utilizes instrumentation in the monitoring and control of a process or facility.
OrganizationThis recommended practice is organized to provide recommendations on:
Establishing a calibration program
Calibration program activities
Calibration program management
Copyright 2016 ISA. All rights reserved.
228229
230231232233
234235236237238239
240241242243
244245246
247248249250251252253254
255256257
258259
260
261
262
263
264
265
266
ISA–TR105 CDR052016 – 8 –
1 Scope1.1 General ApplicabilityThe recommended practice detailed in this document defines a baseline definition and model of a quality management system that can be utilized to implement and maintain a calibration program for industrial monitoring and control systems. It is applicable to all industrial monitoring and control systems.
1.2 Inclusions and exclusions1.2.1 Manufacturer specific calibration proceduresThis document does not provide or recommend manufacturer-specific calibration procedures for specific instruments as these are established by the instrument manufacturer and are outside the scope of this document.
1.2.2 BPCS and SIS functionalityThis document does not include any consideration for how instrumentation and control signals are handled within the BPCS (Basic Process Control System) or /SIS (Safety Instrumented System) other than including indication of the signal in loop accuracy calculations.
1.2.3 Control value calibrationThis document does not cover control valve maintenance.
1.2.4 Regulatory requirementsRegulatory requirements related to loop/instrument accuracies are not included in this RP.
1.2.5 SIS instrument calibrationThe calibration of monitoring and control loops that are part of safety instrumented systems is included in the scope of this recommended practice. The documentation and management of these instruments as part of safety instrumented systems is excluded. For more information, see ANSI/ISA 84 and all its parts.
1.2.6 Instrument criticalityThis document mentions criticality as it applies to a calibration program. This document does not modify any guidelines for establishing criticality provided in ISA TR91.00.02.
1.2.7 Control loop performanceThe performance of final control elements and the tuning of control loops are excluded from the scope of this recommended practice.
2 Normative References NIST Handbook 150:2001
ISA TR91.00.02-2003 Criticality Classification Guideline for Instrumentation
ANSI\ISA 5.1-2009 Instrumentation Symbols and Identification
3 Definition of Terms and Acronyms3.1 Terms3.1.1accuracythe degree of conformity of a device’s output to its actual input value
Copyright 2016 ISA. All rights reserved.
267
268
269270271272
273
274
275276277
278
279280281
282
283
284
285
286
287288289290
291
292293
294
295296
297
298
299
300
301
302
303304305
– 9 – ISA–TR105–CDR052016
3.1.2calibrationthe act of determining (by comparison with a standard) and, if necessary, adjusting a device to meet the standard within the device’s stated accuracy
3.1.3calibration work instructionsStep by step instruction for performing a calibration on a specific device or loop
3.1.4devicea piece of instrument hardware designed to perform a specific action or function
3.1.5device calibrationa calibration performed on only one device
3.1.6errorthe difference between an indicated value and the actual value
3.1.7instrument asset managementcoordinated work processes of an organization to ensure the intended capability of assets is available
3.1.8Loopcombination of two or more instruments or control functions arranged so that signals pass from one to another for the purpose of measurement, indication, or control of a process variable
3.1.9loop accuracythe degree of conformity of a loop’s measured or controlled variable indicated value to the variable’s actual value
3.1.10loop tolerancethe permissible limit of variation, from a known standard, in the loop indicated process measurement
3.1.11management programactivity that manages a group of related projects and/or work processes in a way that provides benefits and control not available by managing each activity individually and independently
3.1.12precisionthe repeatability of measurements over time
3.1.13proceduresequence of tasks with a defined beginning and end that is intended to accomplish a specific objective
Copyright 2016 ISA. All rights reserved.
306307308309
310311312
313314315
316317318
319320321
322323324325
326327328329
330331332333
334335336337
338339340341
342343344
345346347348
ISA–TR105 CDR052016 – 10 –
3.1.14repeatabilitythe variation in measurements of a device or loop under the same conditions, and over a period of time
3.1.15traceabilityThe property of the results of a measurement or the value of a standard whereby it can be related to a stated reference
Note 1: For example in the US, this is the National Institute of Standards and Technology or ILAC recognized laboratories.
3.1.16taska single piece of work that needs to be done and does not have interacting elements requiring management
3.1.17verificationthe act of checking the accuracy of a loop or loop component to determine whether it is performing within required tolerances
3.1.18work processset of interrelated or interacting procedure(s) which transforms inputs into outputs
3.2 Acronyms
NIST National Institute of Standards and Technology
ILAC International Laboratory Accreditation Cooperation
4 Establishing a calibration program4.1 GeneralA calibration Management program includes defined procedures, tasks and activities for the calibration of all the relevant instruments. On-going calibration is a fundamental part of instrument maintenance, which in turn is a fundamental part of the Plant’s / Facility’s maintenance. As such the management and scheduling of maintenance personnel, and other resources such as test equipment, to perform calibration activities is usually executed via Work Orders from the Plant’s / facility’s maintenance management system (computerized or otherwise). A broader reliability or Asset Management program in turn may guide this. Consequently, consideration should be given to how the calibration program interacts with other programs and systems in the Plant / Facility.
Where instrument and systems performance certification is mandated by regulating agencies, Federal, State or local, the owners should ensure that technicians involved in the calibration process are familiar with those requirements. Examples are EPA, NRC or CEMs permits for emissions and discharge to water bodies.
4.2 Calibration program conceptsMonitoring and control instrumentation and systems currently used in industry range from pneumatics to “smart” (microprocessor-based) digital electronics. These devices are as varied as the processes they monitor. Devices with moving parts require regular maintenance. These mechanical devices are much more susceptible to mechanical performance issues (e.g. binding and dragging due to environmental contamination) than are other automation instrumentation.
Copyright 2016 ISA. All rights reserved.
349350351352
353354355356
357358
359360361362
363364365366
367368369
370
371
372
373
374375376377378379380381382
383384385386
387
388389390391392
– 11 – ISA–TR105–CDR052016
Analog electronic instrumentation is subject to drift in settings and output. Digital instrumentation has multitudes of parameter settings that should be set properly to achieve desired operation. Devices not operating to their manufacturer’s specifications and/or not properly configured for the specific application can result in operational issues, such as off-spec quality, productivity issues, and safety issues. And then there is always the instrument failure. All of this results in a need for the loops important to safety, quality and correct operation of the facility to be periodically calibrated.
Understanding and adhering to the following guidelines, explained in the sections that follow, is required to achieve the full benefits of the recommended approach to a calibration program set forth in this document.
4.3 Calibration programA calibration program for an industrial monitoring and control system formalizes a methodology to periodically verify the performance accuracy of the components in that monitoring and control system and, when necessary, make adjustments to those components to bring them within their manufacturer rated accuracy and the loop within its required performance accuracy.
Each user company/facility is encouraged to establish a calibration program specific to its needs. This recommended practice discusses the essential features of a calibration program and provides guidance how to establish such a program.
This proposed approach to a calibration program for automation instrumentation and systems takes into consideration all known loop measurement errors and establishes calibration tolerances based on the process requirements. Successful implementation of this approach requires management commitment to make this a living process. Critical steps in the process include:
a) establish a loop/instrument tagging system,
b) develop a comprehensive list of loops and instrumentation equipment requiring calibration,
c) establish a loop criticality system and criticality ratings for each of those loops,
d) establish tolerance requirements for each loop,
e) establish loop calibration verification intervals (frequencies),
f) establish calibration equipment requirements,
g) establish loop/instrument calibration record forms and calibration record-keeping system,
h) establish necessary calibration procedures,
i) establish staff qualifications and training requirements,
j) perform calibration checks at required intervals and document results, and
k) establish a calibration program verification methodology
4.4 Device calibrationDevice calibration ensures that discrete components within the loop have been compared and
Device calibration ensures that discrete components within the loop have been compared and adjusted, if necessary, to a reference standard. This is typically done before the component or instrument is installed and is used as an initial benchmark to ensure accuracy and then is periodically checked to ensure device accuracy. The period, or calibration interval, may be set by the authority having jurisdiction, plant maintenance program, the manufacturer’s recommendation, or another agreed upon period. The shortest period should be used, except where environmental conditions require more frequent.
Copyright 2016 ISA. All rights reserved.
393394395396397398399
400401402
403
404405406407
408409410
411412413414415
416
417
418
419
420
421
422
423
424
425
426
427
428
429430431432433434435
ISA–TR105 CDR052016 – 12 –
Device calibration is used before loop calibration to verify that the instrument is within engineering tolerances. Device calibration covers the closest instrument to the process measurement, whereas loop calibration will take into account the communication means from the instrument to the measurement recorder, e.g. the PLC, DCS, or other.
adjusted, if necessary, to a reference standard. This is typically done before the component or instrument is installed and is used as an initial benchmark to ensure accuracy and then is periodically checked to ensure device accuracy.
Device calibration is also used when loop calibration is not practical.
[4.5] Loop calibrationA key concept of this recommended practice is establishing required tolerance and performing calibration of the entire loop, which may include multiple devices, where practical. The concept of loop calibration is when the loop indication is not within the desired loop tolerance, the devices in the loop are individually checked and adjusted as necessary to bring the loop indication within the desired tolerance.
For example, a temperature transmitter could be calibrated as a single device but when installed with the sensor and indicator, the loop indication might not be within the desired tolerance. The key parameter is whether the entire loop is providing a measurement within the tolerance needed for proper operation of the process. Each component in a loop has a rated accuracy. The inaccuracy or error of each component in the loop results in the total loop inaccuracy greater than that of any component.
4.5[4.6] Test equipmentThe test equipment used to validate and calibrate a loop or component should be of sufficiently greater accuracy (typically three to four times better accuracy) than that loop or component.
4.6[4.7] CompetencyProperly trained personnel are essential to the success of a calibration program. This includes understanding the process, regulatory requirements, calibration tools, and instrument\systems training required by the manufacturer.
5 Calibration Program Planning5.1 GeneralComponents and systems require periodic calibration to operate safely, efficiently, and in compliance with regulations. To ensure such calibrations occur as necessary, companies should have a structured calibration program, a formalized methodology that applies to all components and systems covered by the program, consisting of standards, procedures, tasks, and activities for verifying performance accuracy and adjusting or replacing deficient/defective components/systems as necessary to ensure operation occurs in accordance with manufacturer rated accuracy parameters and/or required performance tolerances.
5.2 Loops and components in the calibration programIf it does not already exist, an identification (tagging) system should be established which assigns a unique identification (tag) to each loop and component. This provides a uniform means of identifying a loop and each loop device, its inherent functions, and related system(s). The ANSI/ISA-5.1 standard for Instrumentation Symbols and Identification provides guidance for developing an identification system. Proper identification of the components in the calibration program is important to efficient and proper operation of the calibration program, including proper documentation and tracking of components.
Copyright 2016 ISA. All rights reserved.
436437438439
440441442
443
444
445446447448449
450451452453454455
456
457458
459
460461462
463
464
465466467468469470471
472
473474475476477478479
– 13 – ISA–TR105–CDR052016
Using the unique tags established, a comprehensive list of all loops and instrumentation in the facility to be included in the calibration program should be developed.
5.3 Component and loop criticality determinationIf it does not already exist, establish a loop criticality classification system for loops in the facility. The criticality of each loop is one of the driving factors for establishing calibration intervals. ISA technical report TR91.00.02 provides a structured technique for establishing criticality classifications. Classification examples from that document include safety, environmental, and asset protection.
Using the criticality classification system established, the applicable criticality classification for each component in the calibration program should be identified.
5.4 Establishing required loop toleranceEach loop should be evaluated against and calibrated to a specified tolerance, which is the permissible deviation from the actual value or loop tolerance.
The tolerance for each loop may be established in either of two ways: (1) by establishing the required accuracy of the loop necessary to meet safety, quality, and/or production requirements of the process, or (2) by establishing the theoretical tolerance of the loop based on the rated accuracies of all of its components. In both methods, the theoretical tolerance of the loop should be calculated to demonstrate whether the loop is capable of meeting the required accuracy (in method 1) or to establish the target tolerance for the loop (in method 2).
Establishing an acceptable tolerance for each loop:
a) Clearly defines the level of acceptable performance for each loop
b) Provides a defined measure to use in the periodic check of loop performance
c) Facilitates tracking of loop performance over time
d) Focuses calibration efforts to the areas that provide the most benefits
e) Provides management with a measure for auditing loop performance and calibration work (staff and equipment performance)
f) Clarifies loop performance expectations for operations and maintenance, including regulatory requirements where applicable
5.5 Calculating theoretical loop toleranceTheoretical loop tolerance is calculated by using the Root-Sum-Square (RSS) method, which combines the rated accuracy of each component in the loop. Each of the listed
Tolerance=√ (error 1 )2+(error 2)2 +(error3)2+(etc . error)2
effects on accuracy is squared and all squared terms are added together. The square root of this sum provides a combined uncertainty in either percentage or engineering units of the loop. Section 7 provides examples for calculating loop tolerance by using the manufacturers’ data and the RSS method.
The following influencing parameters of a device need to be considered when calculating loop tolerance:
a) hysteresis,
b) drift,
Copyright 2016 ISA. All rights reserved.
480481
482
483484485486487
488489
490
491492
493494495496497498
499
500
501
502
503
504505
506507
508
509510
511
512
513514515516
517518
519
520
ISA–TR105 CDR052016 – 14 –
c) effects of influencing parameters
d) resolution,
e) maximum permissible error,
f) dead band.
g) range,
h) bias,
i) repeatability,
j) stability, and
k) measurement uncertainty.
As an example, a manufacturer lists the following parameters for their differential pressure transmitter:
long term stability
line pressure effect per 1000 psi (68,95 bar)
ambient temperature effect per 50oF (28oC)
mounting position effect
vibration effect
power effect, and
electromagnetic compatibility (EMC).
5.6 Calibration Confirmation Intervals The calibration confirmation interval for a particular component or loop is a function of (a) criticality of the component/loop, (b) the performance history of the component/loop, (c) the ruggedness of the component(s), and (d) the operating environment. Effective calibration programs base calibration intervals on these factors and on historical verification data for the loop or component. The user must determine the applicable verification frequency for each component/loop. Historical performance information and/or Instrument Asset Management diagnostics maintained by the user can be very helpful in this effort.
Records obtained using statistical data techniques for measurement frequency etc. can be useful in determining whether or not to modify calibration confirmation interval. Initial frequencies may consider manufacturer’s recommendations if no other data is available and then be adjusted as calibration performance data is obtained. Shown below is an illustrative example of a calibration intervals using criticality ranking. The example is not intended to be used directly.
Copyright 2016 ISA. All rights reserved.
521
522
523
524
525
526
527
528
529
530
531532
533
534
535
536
537
538
539
540
541
542543544545546547548
549550551552553
554
– 15 – ISA–TR105–CDR052016
Table 1. Example Criticality Ranking
5.7 Calibration equipmentEquipment used to measure a loop’s tolerance or to calibrate a device should be:
a) Certified, typically by the manufacturer or a third party on a regular, fixed period (annually or otherwise as recommended by the manufacturer) to be operating properly and within all manufacturers’ specifications. A sticker should be affixed to the equipment documenting the most recent date of re-certification. For calibration equipment, the device’s calibration should be traceable to a national or other acceptable standard.
b) At least a factor of three times better than the specified tolerance of the loop/component being calibrated (For example, if the loop tolerance is 3%, the aggregate calibration equipment accuracy should be 1% or less. If the component accuracy is 0.25%, the aggregate calibration equipment accuracy should be less than 0.08%. If multiple calibration equipment components are used, the aggregate accuracy should be calculated using the RSS method.)
c) Properly corrected for the effects of local conditions (e.g. ambient temperature, atmospheric pressure, etc.)
Control of Access to Calibration Adjustments - Access to adjusting means on devices after they have been confirmed or calibrated, whose setting affects the performance, should be sealed or otherwise safeguarded to prevent unauthorized changes. Seals or safeguards should be designed and implemented such that tampering will be detected. The calibration process procedures should include actions to be taken when seals or safeguards are found damaged, broken, bypassed or missing.
Copyright 2016 ISA. All rights reserved.
555556
557
558
559
560561562563564
565566567568569570
571572
573574575576577578
579
ISA–TR105 CDR052016 – 16 –
The following is a list of common test equipment:
a) digital multimeter (voltage, resistance, current)
b) digital thermocouple, millivolt simulators (may be included in a))
c) thermostatically controlled temperature bath
d) digital frequency meter/timer(may be included in a))
e) special test equipment required by the vendor of the device being tested/calibrated
f) stabilized DC power supply
g) dead weight tester
h) precision pressure gauge
i) current and/or voltage generator
j) precision wire wound resistor decade box
k) sine wave generator
l) wobulator
m) stop watch
n) digital manometer
o) digital pneumatic pressure calibrators(may be included in a))
p) portable manually operated pneumatic pump
q) vacuum pumps (manually operated)
r) sets of standard (precision) mercury-in-glass thermometers, and
s) inclined manometer.
5.8 Calibration record systemA calibration record system is necessary to provide documentation of when calibration activities have been undertaken on which pieces of equipment, what the results were, and what (if any) corrective action was taken. The system should include forms to be used to record the calibration activities and the method for storage of all calibration records to facilitate future access. This system may be paper- or electronic-based. The calibration service record (CSR) provides essential information on a particular loop/component. This includes the calibration points with the acceptable loop/component tolerances. Using the CRS allows staff to capture the “as found” and “as left” data, which highlights how much drift has occurred in the loop/component since the last calibration. An example of a CSR is provided in the Annex.
5.9 Calibration proceduresTo promote consistent methodology and results, calibration procedures, or calibration work instructions, should be established for each loop/component. These procedures should detail the method and equipment to be used to check and perform calibration. The procedure includes the following:
description of the component or loop to be calibrated
overview of the tasks to be performed
equipment and personnel requirements, and
procedure to be followed for the calibration.
Copyright 2016 ISA. All rights reserved.
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602603604605606607608609610
611
612
613614615616
617
618
619
620
– 17 – ISA–TR105–CDR052016
Operating personnel & instrument technicians should huddle before calibration procedure begins. All data should be recorded in a centralized location for easy review and audit.
5.10 Calibration personnel To ensure the safety and reliability of the measurement and control system, only competent personnel should be allowed to perform calibrations. Suggested areas of knowledge include:
a) general maintenance skills
1) operations and process safety
2) electrical safety
3) troubleshooting
b) instrument maintenance skills
1) instrumentation maintenance and repairs
2) loop checking
3) calibration
4) calibration record keeping
Confirming the qualifications of the personnel involved in calibration can be achieved through the completion of an internal certificate program or through an recognized independent third party certification program. Once complete, a subject matter expert should evaluate an individual’s ability to perform a specific type of calibration. Supervisors should keep a register of qualified individuals by component type. It is important to understand that someone may be fully qualified to calibrate one type of component and not another. In addition, certain regulatory requirements may establish qualification for personal performing calibrations. Requirements for periodic training and re-certification to ensure continued competency of personnel should also be established.
5.11 ResponsibilitiesPreferably, a calibration program definition should be an integral part of the initial design and build capital expenditure phases of the facility’s life cycle phase. Whether the calibration program is being created for the initial facility build or created/rejuvenated during the operation phase of the life cycle, given the number of loops in a typical industrial facility, fully implementing an automation and control system calibration program is a major undertaking. It may well be part of a broader scoped instrument asset management or reliability program. As with any significant program, for it to be successful, company management will need to provide sufficient support to the creation and on-going execution of the program. To ensure consistency, a project team should be created to manage the project. The project will require support from the facility technicians, engineers and, most important, senior management.
The management of the plant, facility, or automation system should be responsible for establishing and owning the program and ensuring compliance with the automation and control system calibration program. This would include establishing a process for auditing compliance with, and updating, the program.
All aspects of the calibration program should be completely documented for an effective calibration program, including, but not limited to:
c) calibration procedures (required method)
d) calibration equipment (required accuracies, re-certification frequency and procedures, personnel training)
e) personnel training and certification
f) personnel responsibilities and accountabilities
Copyright 2016 ISA. All rights reserved.
621622
623
624625
626
627
628
629
630
631
632
633
634
635636637638639640641642643
644
645646647648649650651652653654
655656657658
659660
661
662663
664
665
ISA–TR105 CDR052016 – 18 –
g) required loop tolerances
h) required forms
i) verification and calibration record keeping system, and
j) required verification frequencies
6 Loop and Component Performance Verification6.1 GeneralVerifications and calibrations should be made using the “loop” calibration method whenever possible. In those cases, where this is not possible, loop component accuracies should be verified and used to calculate loop accuracy, which is then compared to loop required accuracy.
The verification portion of the calibration procedure should define the steps necessary to check the performance of a type of loop. This should include a task list providing specific steps necessary to perform the check, including equipment and methodology.
If the calibration confirmation of a loop/component reveals that the loop/component is not within the required tolerance, a calibration adjustment may be required to one or more loop components according to defined procedures. The calibration procedure for that component defines the overall steps necessary to calibrate a type of device. A task list provides the specific steps necessary to calibrate a specific component. If the desired tolerance cannot be achieved, the component should be repaired or replaced.
Calibration confirmation is not achieved until and unless the fitness of the measuring equipment for the intended use has been demonstrated and documented. Calibration confirmation should include calibration and verification, any necessary adjustment or repair, and subsequent recalibration, comparison with the accuracy requirements for the intended use.
Software used in the calibration processes and calculations of results should be documented, identified and controlled to ensure suitability for continued use. Calibration Software - any revisions to it, shall be tested and/or validated prior to initial use, approved for use, and archived.
7 Calibration program management7.1 ControlAn effective calibration program should include a means to track calibrations by device/loop, define required interval, forecast calibrations due, document calibrations, and trend results. Many third party software applications exist that can help automate a calibration program.
7.2 AssuranceAn effective calibration program should be periodically monitored for compliance. This includes verification that loop calibration checks are being performed at the required intervals; all calibration activities are being properly documented; and calibration equipment is properly maintained and has current certification. Management should ensure that this periodic monitoring is consistently performed and results documented.
7.3 ImprovementCalibration programs should be evaluated and updated on a periodic basis or when significant modifications or projects are completed to ensure the program is evergreen. Audits should not only consider if the loops/devices have been added or removed, but should also include a review of the criticality rating, process conditions, accuracy capability and requirements for each device/loop.
Copyright 2016 ISA. All rights reserved.
666
667
668
669
670
671
672
673674675
676677678
679680681682683684
685686687688
689690691
692
693
694695696
697
698699700701702
703
704705706707708
– 19 – ISA–TR105–CDR052016
Periodically review results as trended over time to determine if drift performance is acceptable or if modified frequency of calibration or device technology should be considered in order to ensure desired loop performance is maintained.
8 Examples Calculating theoretical loop accuracy examples
Transmitter Accuracy 0.0750 0.0750System Accuracy 0.1000 0.1000Stability 0.0100 0.0100Ambient Temp Effect/oF 0.0036 0.0000 0.0036
Maximum Total Error 0.0886 0.1000 0.18860.0757 % 0.1000 % 0.1255 %2.27 PSI 3.00 PSI 3.76 PSI
Combined Uncertainties (±)
Transmitter Tolerance
Control System
Analog Input Card
Loop Combined Tolerance
Main Steam Pressure 0-3000 PSI
Calculating the theoretical tolerance using the RSS method, the loop is within calibration if the full-scale reading is between 2996.24 and 3003.75 PSI.
Tolerance=√ (0.0750 )2+(0.1000 )2 +( .0100 )2+ ( .0036 )2
Tolerance=±0.1255 %∨±3.76 PSI
Copyright 2016 ISA. All rights reserved.
709710711
712
713
714
715716
717
718
ISA–TR105 CDR052016 – 20 –
Transmitter Accuracy 0.2500 0.2500System Accuracy 0.1000 0.1000Stability 0.1000 0.1000Ambient Temp Effect/oF 0.0100 0.0022 0.0122
Maximum Total Error 0.3600 0.1022 0.4622
0.2694 % 0.1000 % 0.2875 %6.74 PSI 2.50 PSI 7.19 PSI
Combined Uncertainties (±)
First Stage Pressure 0-2500 PSI
Transmitter Tolerance
Data Logger Analog Input
Card
Loop Combined Tolerance
Transmitter Accuracy 0.0750 0.0750System Accuracy 0.5000 0.5000Stability 0.0100 0.0100 0.0200Ambient Temp Effect/oF 0.0036 0.0100 0.0136
Maximum Total Error 0.0886 0.5200 0.6086
0.0757 % 0.5001 % 0.5062 %1.89 PSI 12.50 PSI 12.65 PSI
First Stage Pressure 0-2500 PSI
Transmitter Tolerance
Control System
Analog Input Card
Loop Combined Tolerance
Combined Uncertainties (±)
Switch Repeatability 3.0000Temperature Effect per oF 0.0200Stability % per Year 0.0000
Maximum Total Error 3.0200
3.0001 %90.00 PSI
Combined Uncertainties (±)
Turbine EH System Pressure 200-3000 PSI
Switch Tolerance
Copyright 2016 ISA. All rights reserved.
719
720
721
– 21 – ISA–TR105–CDR052016
Gauge Accuracy 2.0000Temperature Effect per oF 0.1000Stability % per Year 1.0000
Maximum Total Error 3.1000
2.2383 %67.15 PSI
Boiler Feed Pump Turbine Pressure 0-3000 PSI
Combined Uncertainties (±)
Gauge Tolerance
These examples highlight the large differences in the uncertainties from system to system and from device to device. Far less accuracy is required to calibrate gauge (combined uncertainties 2.238%) than is required to calibrate loops on the inputs to a control system (combined uncertainties 0.1255%). It is important to note that there are actually more identifiable factors to uncertainty in the systems. However, none of these factors is significant enough to make a recognizable increase in the uncertainty of the loop.
Implementation example
o In 1995, the natural gas supplier started providing their technicians loop tolerances for all of the utility power plants. Shown below is March 2006 audit of the power plant meter run number one.
o Providing acceptable tolerance for each loop was a new concept for the natural gas supplier. Over time, the company realized the following benefits of this practice:
o Clearly defined levels of acceptable performance for each loop
o Focuses calibration efforts to the areas that provide the most benefits
o Provides management with a measurement for auditing the calibration work (staff and equipment performance)
Copyright 2016 ISA. All rights reserved.
722
723724725726727728
729
730
731732733
734
735736737
738
739
740741
ISA–TR105 CDR052016 – 22 –
Copyright 2016 ISA. All rights reserved.
742
743
744
745
746
747
748
– 23 – ISA–TR105–CDR052016
Bibliography
NIST (2001), Handbook 150:2001, Washington, National Institute of Standards and Technology
ISA (2009), 5.1-2009 Instrumentation Symbols and Identification, North Carolina, Inter-national Society of Automation
ISA (2003), TR91.00.02-2003 Criticality Classification Guideline for Instrumentation, North Carolina, International Society of Automation
Beamex (2009), Ultimate Calibration 2nd Edition, 2009, Finland, Beamex Oy Ab.
Cable, Mike (2005), Calibration: A Technician’s Guide, North Carolina, International Society of Automation
ISO 9001 (2015), Clause 7.6 Control of monitoring and measuring equipment, Switzerland, International Organization for Standards
ANSI/NCSL Z540.3-2006 (2006), Requirements for the Calibration of Measuring and Test Equipment, Boulder, Colorado, NCSL International
Copyright 2016 ISA. All rights reserved.
749
750
751752
753754
755
756757
758759
760761
762
ISA–TR105 CDR052016 – 24 –
This page intentionally left blank.
Copyright 2016 ISA. All rights reserved.
763
764
765
– 25 – ISA–TR105–CDR052016
Annex A – Example Documentation
Copyright 2016 ISA. All rights reserved.
766
767
ISA–TR105 CDR052016 – 26 –
Calibration Service Record
Copyright 2016 ISA. All rights reserved.
768769
– 27 – ISA–TR105–CDR052016
This page intentionally left blank.
Copyright 2016 ISA. All rights reserved.
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
ISA–TR105 CDR052016 – 28 –
Developing and promulgating sound consensus standards, recommended practices, and technical reports is one of ISA’s primary goals. To achieve this goal the Standards and Practices Department relies on the technical expertise and efforts of volunteer committee members, chairmen and reviewers.
ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers United States Technical Advisory Groups (USTAGs) and provides secretariat support for International Electrotechnical Commission (IEC) and International Organization for Standardization (ISO) committees that develop process measurement and control standards. To obtain additional information on the Society’s standards program, please write: