EXPERION PKS RELEASE 516 IEC 61850 SCADA Configuration Guide EPDOC-X375-en-516A August 2020

Transcript of IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6...

Page 1: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

EXPERION PKSRELEASE 516

IEC 61850 SCADA Configuration GuideEPDOC-X375-en-516A

August 2020

Page 2: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

DisclaimerThis document contains Honeywell proprietary information. Information contained herein is to beused solely for the purpose submitted, and no part of this document or its contents shall bereproduced, published, or disclosed to a third party without the express permission of HoneywellInternational Sàrl.

While this information is presented in good faith and believed to be accurate, Honeywell disclaimsthe implied warranties of merchantability and fitness for a purpose andmakes no expresswarranties except as may be stated in its written agreement with and for its customer.

In no event is Honeywell liable to anyone for any direct, special, or consequential damages. Theinformation and specifications in this document are subject to change without notice.

Copyright 2020 - Honeywell International Sàrl

- 2 -

Page 3: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Contents 3

Chapter 1 - About this guide 61.1 Revision history 6

1.2 Intended audience 6

Chapter 2 - Introduction 72.1 About IEC 61850 7

2.1.1 About IEC 61850 7

2.1.2 IEC 61850 features 7

2.2 IEC 61850system interface in 7

2.2.1 Configuration A: Integration of small systems using LAN 8

2.2.2 Configuration B: Integration of small systems using PRP/HSR 9

2.2.3 Configuration C: Integration of larger systems using data concentrators(PRP/HSR and LAN) 10

2.2.4 Configuration D: Integration of larger systems using data concentrators(PRP/HSRand PRP/HSR) 10

2.2.5 Configuration E: Integration of Process Control System and Electrical ControlSystem. 11

2.3 Alternate supported topologies 12

2.4 Overview 14

2.5 Terms and definitions 16

2.6 Package information 18

Chapter 3 - Installation and upgrades 193.1 Hardware requirements 19

3.1.1 Hardware requirements for server grade machines 19

3.1.2 Hardware requirements for industrial grade machines 19

3.2 Software requirements 19

3.2.1 Prerequisite for Server node 19

3.2.2 Prerequisites for Flex Server node (data concentrator) 19

3.3 Prerequisites 20

3.3.1 To enable the IEC 61850client interface 20

3.4 Installation 20

3.5 Upgrades 21

Chapter 4 - Configuration 224.1 About SLD Generator tool 22

4.1.1 Prerequisites for SLD Generator tool 23

- 3 -

Page 4: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.2 Dual home configurations for SCADA server 23

4.2.1 To verify IP routing is disabled 23

4.2.2 To disable Microsoft Windows Client and File Sharing for the IEC 61850 portson the SCADA server 24

4.2.3 To change the TCP/IPv4 interface metric and disable netBIOS 25

4.3 System configuration 25

4.3.1 Configuring the firewall settings 26

4.3.2 Configuring the IEC 61850system interface 29

4.3.3 Configuring file replication 31

4.4 IED Configuration 32

4.4.1 Starting the IEC 61850 system configurator 32

4.4.2 Adding IED 33

4.4.3 Removing IED 35

4.4.4 Cloning IED 36

4.4.5 Exporting IED 37

4.4.6 Importing IED 40

4.4.7 Scan Period 42

4.4.8 File Services 43

4.4.9 Log Control Block (LCB) 44

4.4.10 Settings Groups Control Block (SGCB) 49

4.5 IEC 61850 points configuration 51

4.5.1 Configurig Assets, Alarms and SOE 51

4.5.2 Downloading points 52

4.5.3 Deleting points 53

4.6 Assigning Report Control Blocks 53

4.6.1 To enable reports 54

4.7 Configuring control parameters 54

4.7.1 To exceute direct execute/direct execute with enhanced security control 54

4.7.2 To execute select before operate control 55

4.7.3 To execute select before operate with enhanced security control 55

4.8 Synchronizing servers 57

4.8.1 Prerequisites 57

4.8.2 To synchronize servers 57

4.9 Embedding a point in custom display 57

Chapter 5 - Operations 595.1 Alarms 59

5.2 Trend group 59

- 4 -

Page 5: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

5.3 System status display 60

5.4 system detailed display 60

5.4.1 IED detail display 61

5.4.2 IED summary display 62

5.5 IEC 61850 Diagnostics tool 64

5.5.1 Launching the IEC 61850 Diagnostics tool 65

5.5.2 The IEC 61850DCT user interface 66

Chapter 6 - Troubleshooting and maintenance 686.1 OPC Data Connection status is 'Not connected' 68

6.2 OPC Notification status is ‘Connecting’ 68

6.3 Other issues 68

Chapter 7 - Performance parameters and limitations 727.1 Server performance 72

- 5 -

Page 6: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

ABOUT THIS GUIDE

This document provides information about configuring and operating the IEC 61850systeminterface in Experion.

1.1 Revision history

Revision Date Description

A August 2020 Initial release of the document.

1.2 Intended audience

This guide is intended for Project Engineers andMaintenance Engineers who are responsible forconfiguring IEC 61850system interface in Experion.

l Familiar with working in a Microsoft Windows operating environment.

l Familiar with Experion system topology and using Experion applications.

l Familiar with using Configuration Studio.

l Familiar with IEC 61850 standards.

You may also refer to the following related documents.

Document Description

Communication networks and systems in substations - Part 1–10

Publication date: 2004-05

Document for IEC 61850standards.

Communication networks and systems in power utility automations-Part 1–10(IEC 61850 Edition 2)

Publication date: 2011-07

Document for IEC 61850standards Edition 2.

- 6 -

CHAPTER

1

Page 7: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

INTRODUCTION

This chapter provides information about IEC 61850 SCADA configuration you must know beforeconfiguring it in an network.

l About IEC 61850

l IEC 61850 system interface in Experion

l Alternate supported topologies

l Overview

l Terms and definitions

l Package information

2.1 About IEC 61850

This section gives an overview about IEC 61850 and lists the available IEC 61850 standards.

2.1.1 About IEC 61850

IEC 61850 is a standard for the design of electrical substation automation, prepared andpublished by the International Electrotechnical Commission (IEC).

IEC 61850 is the standard protocol used for communication between Data Acquisition (SCADA)and Intelligent Electronic Device (IED) in the transmission and distribution industries forsubstation automation. IEC 61850 utilizes TCP/IP networks or substation LAN using high speedswitched Ethernet to obtain the necessary response times for protective relaying.

The IEC 61850 standards specification document is available in the IEC website(http://www.iec.ch).

2.1.2 IEC 61850 features

Some of the features of IEC 61850 include.

l Enables use of multi-vendor electrical devices on a common bus network facilitatingintegration, device engineering and fast response.

l Ensures easy introduction of newer devices into the electrical network without the need forremoving the older devices.

l Supports large number of diagnostic parameters.

l Reduces costs of installation, commissioning andmaintenance.

2.2 IEC 61850system interface in

This section gives an overview of the integration and topology of IEC 61850system interface inand its usage in the environment.

- 7 -

CHAPTER

2

Page 8: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Using IEC 61850 client interface in , monitoring and control of industrial process electrificationsystem can be done as described in the topologies below.

In smaller industrial systems with less than 200 IEDs, the following topologies are supported.

l Configuration A: Integration of small systems LAN

l Configuration B: Integration of small systems using PRP/HSR

In larger industrial systems with more than 200 IEDs, the following topologies are supportedwhere multiple substations are monitored individually using data concentrators and overall plantmanagement is done at remote control centres. Data concentrators can integrate up to 200 IEDs,by converting IEC 61850MMS data from IEDs to DSA. Thus, enabling the monitoring and controlof overall plant from remote control centre. You can integrate as many as IEDs based on thistopology without crossing the DSA limits.

l Configuration C: Integration of larger systems using data concentrators (PRP/HSR and LAN )

l Configuration D: Integration of larger systems using data concentrators (PRP/HSR andPRP/HSR)

When one has to integrate both Electrical Control System and Process Control System, Experionsupports the following topologies where one can communicate the IEDs , Controllers (C300) andExperion Process Control Server as below.

l Configuration E: Integration of Process Control System and Electrical Control System.

2.2.1 Configuration A: Integration of small systems using LAN

In industrial systems where there are less than 200 IEDs in the system, you can integrate IEC61850 systems into servers by enabling IEC 61850 license. If the IEDs are not PRP-enabled, thenthe supported network topology is LAN.

The following figure explains IEC 61850 in with LAN network topology.

The following figure explains IEC 61850 in with dual LAN network topology.

- 8 -

Chapter 2 - Introduction

Page 9: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 2 - Introduction

2.2.2 Configuration B: Integration of small systems using PRP/HSR

In industrial systems where there are less than 200 IEDs in the system, you can integrate IEC61850 systems into servers by enabling IEC 61850 license. If the IEDs are PRP-enabled, then thesupported network topology is PRP.

- 9 -

Page 10: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

ATTENTION

You can connect non-PRP IEDs and GPS as singly attached node (SAN) or doubly attachednodes (DAN) using a REDBOX.

2.2.3 Configuration C: Integration of larger systems using dataconcentrators (PRP/HSR and LAN)

If the DSA network is on LAN and IEC 61850MMS network is on PRP, then the following topology issupported.

ATTENTION

In similar manner, IEDs can be connected in HSR topologies.

2.2.4 Configuration D: Integration of larger systems using dataconcentrators (PRP/HSRand PRP/HSR)

If both DSA network and IEC 61850MMS network is on PRP, then the following topology issupported.

- 10 -

Chapter 2 - Introduction

Page 11: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 2 - Introduction

ATTENTION

In similar manner, IEDs can be connected in HSR topologies.

2.2.5 Configuration E: Integration of Process Control System andElectrical Control System.

Experion support the following three different network topologies.

Figure 2.1 Non-redundant Ethernet ring topology

- 11 -

Page 12: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Figure 2.2 HSR topology

Figure 2.3 PRP topology

2.3 Alternate supported topologies

This section describes additional topologies supported by IEC 61850system interface in Experion.

- 12 -

Chapter 2 - Introduction

Page 13: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 2 - Introduction

Figure 2.4 Non-redundant Ethernet ring topology model

Figure 2.5 HSR topology model

- 13 -

Page 14: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Figure 2.6 PRP topology model

2.4 Overview

The IEC 61850 system configurator tool is used for configuring the following:

l IEDs in substations.

l Electrical point tag names, state descriptors, alarms, priorities, SOE, trends, groups, andhistory.

l IEC 61850 Report Control Blocks.

After configuring the system, you can download the points to to see them in the Station andupload the changes done in Station back to the database.

IEC 61850 service is authorized to allow certain roles, so that it cannot be misused by non-IECapplications. The following users from these roles/user groups are authorized to use the service:

1. Local Engineers

2. Local Supervisors

3. Product Administrators.

This tool also provides information about the following IEC 61850 parameters.

l Data model

l Dataset

l Report Control Blocks of the IEDs

The tool consists of four views as shown below.

Toolbar view

Use the Toolbar view to launch actions that the tool can perform. All the operations can beperformed only from the Toolbar view.

- 14 -

Chapter 2 - Introduction

Page 15: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 2 - Introduction

l Add IED

l Delete IED

l Download point

l Upload point

l Delete point

l Clone IED

l Export IEDs

l Import IEDs

l Archive IEDs

l Restore IEDs

l Save (configuration)

l Export ICD

Tree view

Use the Tree view to browse data model of the IEDs and understand the structure of the IEDs. TheTree view also filters points displayed in the List view by displaying only points that belong to theselected category.

List view

Use the List view to see points and IEDs based on their selection in the Tree view. The followingfilters can be used in the List view.

l Dataset: Only points that are present in the dataset of the IEDs are displayed.

l Downloaded: Displays points that are downloaded to .

l Not downloaded: Displays points that are not downloaded to .

ATTENTION

The default filter displayed is the dataset. The icons are in blue color when they are notdownloaded to and in green color when they are downloaded to .

Tab view

Use the Tab view to configure points and IED properties.

ATTENTION

After modifying the parameters, you are prompted to save the changes when the focusmoves to other points.

- 15 -

Page 16: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Figure 2.7 Views in IEC 61850 System Configurator tool

2.5 Terms and definitions

This section provides information about the terms and definitions associated with IEC 61850system interface in used in the document.

- 16 -

Chapter 2 - Introduction

Page 17: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 2 - Introduction

Terminology Description

Asset

Assets represent entities such as fixed plant equipment, materials, and buildings.The Asset Model provides a hierarchical structure that more closely resembles yourorganization.

The points in your system belong to assets. For example, you might have an assetthat represents a furnace in your plant. All the points associated with the physicalfurnace (analog points measuring the temperature, status points controlling valvesor pumps associated with the furnace) might belong to the asset that represents thefurnace.

The part of the system for which you are responsible can be controlled by assignedassets to you or the Station you are using. In addition, where assets have beenassigned to you, the tasks that you can perform can be restricted. For example, youmay have View access to an asset in your system. In this case, you can only viewitems associated with the asset, you cannot make any changes, such asacknowledging alarms or changing a point parameter.

Channel The communications port used by the server to connect to an IED.

DAI Instantiated Data Attribute

Display

Station uses displays to present information to operators in a manner that they canunderstand. The style and complexity of displays varies according to the type ofinformation being presented. Displays are sometimes called pages, a term which isused for Web pages.

Dual homeDual-home/ dual homing is a network topology where a network device is built withmore than one network interface.

Faceplate

A specialized popup that shows a subset of the details shown on the matching pointdetail (or template) display. It typically shows the point's run-time values and controlsettings. A faceplate appears when an operator clicks an object that is linked to apoint.

IEC International Electrotechnical Commission.

IED

Intelligent Electronic Device

An intelligent control andmessaging device used for interfacing substationautomation controllers and networks to target electrical equipment such as relays,circuit breakers, and so on.

IEDtechnicalname

The IED name configured by the vendor. It is also known as IED network name.

Integrityperiod

The Period in milliseconds (ms) at which the Report Control Blocks (RCB) arerequired to report in regular intervals.

BR Buffered Reports

RP Unbuffered Reports

Parameter

Each item of information about a point is called a parameter. The main parametersstore:

l The current value or state of the point (sometimes referred to as ProcessVariable or PointValue/PointState).

l The uncalibrated value of the point (sometimes referred to as output orOutputValue/OutputState).

l The control state of the point, that is, whether the point is being automaticallycontrolled or manually controlled (sometimes referred to as Mode orModeState).

Point

A point is a collection of information about a particular part of your system. Forexample, a point representing a motor would include:

l A Point name, which uniquely identifies the motor.

l A description.

- 17 -

Page 18: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

l A full item name.

l The current state (off or on). The desired state. This is applicable if you areallowed to control the point. For example, if current state of the motor is "On"you can change the real state of the motor to "Off" using the display.

PointParameter

A unit of information about a point. For example, an analog point includesparameters such as: process variable parameter (PointValue) and output parameter(OutputValue).

Point Server

A high-level interface that allows to exchange data with another application orsubsystem without the need for separately defining points in .

The database structure of a point on a point server (called a flexible point) isdetermined by the application/subsystem, rather than by .

PointValue The process variable parameter of a standard point.

REDBOX

Redundancy box

Redbox is a switch that enables non-HSR or non-PRP nodes like the 850M toconnect to an HSR or PRP network.

SOE Indicates the Sequence Of Events.

SLDGenerator

SLD Generator tool (Single Line Diagram Generator tool) creates single-linediagrams (SLD) for electrical substations from substation configuration description(SCD) and substation specification description (SSD) files.

2.6 Package information

The IEC 61850media contains two folders.

l IEC 61850 software installation – This contains the setup.exe file required to install IEC 61850.

l PRP MUX software installation – This contains the setup.exe file required to install PRP driver.

- 18 -

Chapter 2 - Introduction

Page 19: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

INSTALLATION AND UPGRADES

3.1 Hardware requirements

The hardware requirements for installing the IEC 61850 are same as those for installing Experion.

3.1.1 Hardware requirements for server grade machines

NOTERefer to the Experion standards for latest hardware requirements for server grademachines.

3.1.2 Hardware requirements for industrial grade machines

System Configuration Standard Performance

Processor i –series Quad Core Processor (minimum i5)i –series Quad Core

Processor (minimum i7)

Minimum RAM 8GB 16GB

Networking 100Mbps Ethernet Networking 100Mbps Ethernet

Operating System Microsoft Windows 10 Professional (64 bit)

Hard Drive80 GB available

500 GB+ recommended

80 GB available

500 GB+ recommended

CAUTIONExperion L2 network cables, switches and devices should be in the protected environment(locked), so that the network cannot be accessed by the unknown user.

3.2 Software requirements

3.2.1 Prerequisite for Server node

Experion R510.1 server node is installed with the IEC 61850 system interface option is enabled.

3.2.2 Prerequisites for Flex Server node (data concentrator)

Experion R510.1 Flex Server node is installed with the IEC 61850 system interface option isenabled.

- 19 -

CHAPTER

3

Page 20: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

3.3 Prerequisites

The IEC 61850 system interface license should be enabled before you begin installation.

ATTENTIONEnsure that there is no folder with share name as IEC61850.

3.3.1 To enable the IEC 61850client interface

1. Procure a license as mentioned in section "Software requirements" on the previous page.

2. Change the license.

3. Verify if all the necessary license options are enabled.

3.4 Installation

IEC 61850 system interface software components are installed while installing Experion. Thesecomponents are installed on Experion nodes supporting IEC 61850 system interface software.

Before you begin installation, check for IEC 61850 system interface license by performing thefollowing steps.

1. Start Station and then click Configure > Server License Details.

The Server License Details page appears.

2. Click the Interfaces tab.

3.

Verify the status for the IEC 61850 System Interface.

l Green LED before the component indicates that you have the license option enabled.

l Black LED before the component indicates you do not have the license.

- 20 -

Chapter 3 - Installation and upgrades

Page 21: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 3 - Installation and upgrades

3.5 Upgrades

IEC 61850 system interface software upgrade is performed along with Experion server upgrade.For information about upgrade, refer to the ExperionMigration guides.

- 21 -

Page 22: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

CONFIGURATION

l About SLD Generator tool

l Dual home configurations for SCADA server

l System configuration

l IED Configuration

l IEC 61850 points configuration

l Assigning Report Control Blocks

l Configuring control parameters

l Synchronizing servers

l Embedding a point in custom display

4.1 About SLD Generator tool

The SLD Generator tool (Single Line Diagram Generator tool) creates single-line diagrams (SLD)for electrical substations from substation configuration description (SCD) and substationspecification description (SSD) files. This tool assists you to create Experion HMIWeb DisplayBuilder graphics pages by showing the information on how electrical power systems areconnected and helps managing electrical network.

SLD Generator tool parses SCD/SSD files and generates/updates the graphic that can be viewedin Station/ HMI Web Display Builder.

The following figure explains the working process of the SLD Generator tool.

- 22 -

CHAPTER

4

Page 23: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.1.1 Prerequisites for SLD Generator tool

According to the IEC 61850 standards, the SCD file must have the following information togenerate a single-line diagram.

l Voltage levels

l Bays

l Conducting Equipments

l Connectivity nodes

l Co-ordinates

4.2 Dual home configurations for SCADA server

l Ensure that the lower MAC address is selected for FTE network installation. As the Dell serverslike Dell 320 have four built-in NIC interfaces, ensure to use the first two NICs for FTEconnection and other two NICs for IEC 61850 network connections. If you have installedadditional dual NICs on two NIC built-in type server, ensure that lower MAC address NIC isselected for FTE. With this setup, installation automatically selects the lower MAC interfaces(first two interface of built-in NICs) for FTE and systemmanagement and also sets properbinding order that FTEMUX is on top .

l Disable the IP routing between the FTE interfaces and the IEC 61850 interfaces.

l Disable Microsoft Windows Client and File Sharing for the IEC 61850 ports on the SCADAserver.

l Change the TCP/IPv4 interface metric on both the IEC 61850 interfaces to 5 and 10, anddisable netBIOS on both IEC 61850 interfaces.

l Do not include a gateway address on either IEC 61850 interface with an assumption thatgateway address is already defined on the FTEMUX.

4.2.1 To verify IP routing is disabled

1. Choose Start > All Programs > Honeywell Experion PKS > Server > Diagnostic Tools > ExperionCommand Prompt.

The Experion Command Prompt window appears.

2. Type ipconfig /all and press ENTER.

The IP configuration details are listed.

3. In the Windows IP Configuartion section, ensure that the value of IP Routing Enabled is set asNo.

- 23 -

Chapter 4 - Configuration

Page 24: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

4.2.2 To disable Microsoft Windows Client and File Sharing for theIEC 61850 ports on the SCADA server

1. Choose Start > Control Panel.

The Control Panel window is displayed.

2. Perform one of the following depending upon your operating system.

Option Description

Windows 7

Click Network and Internet > Network and sharing Center > Change AdapterSettings.

WindowsServer2008

Click Network and sharing Center > Manage Network Connections.

The Network Connections window is displayed.

3. Right-click the network connections and choose Properties.

The User Account Control dialog box is displayed.

4. Click Continue.

5. In the Networking tab, disable the following options.

l Client for Microsoft Networks

l File and printer sharing for Microsoft Networks

6. Click OK.

- 24 -

Page 25: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.2.3 To change the TCP/IPv4 interface metric and disable netBIOS

1. Choose Start > Computer.

2. Right-click Network and choose Properties.

3. Right-click on the DHEB Network connection and choose Properties.

4. Select Internet Protocol (TCP/IP) and choose Properties.

5. Click the Advanced button on the Internet Protocol (TCP/IP) Properties window.

6. In the Interface Metric box, specify 5 for one IEC 61850 interface.

7. Click the WINS tab.

8. Click Disable NetBIOS over TCP/IP and then click OK.

9. Click OK on the Internet Protocol (TCP/IP) Properties dialog box.

10. Click OK on the DHEB Network Properties dialog box.

11. Repeat the above steps to change the TCP/IPv4 interface metric on the other IEC 61850interface to 10.

4.3 System configuration

This section includes tasks to configure the system for IEC 61850.

- 25 -

Chapter 4 - Configuration

Page 26: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

l Configuring the firewall settings

l Configuring the IEC 61850 system interface

l Configuring file replication4.3.1 Configuring the firewall settings

1. Click Start > Control Panel > System and Security > Windows Firewall, or Start > Control Panel >Administrative Tools> Windows Firewall with Advanced Security.

The Windows Firewall with Advanced Security page appears.

2. Click the Inbound Rules in the left pane and then click New Rule in the right pane to add thenew rule.

The New Inbound Rule Wizard, with the Rule Type page appears.

3. On the Rule Type page, select the Port option.

4. Click Next.

The Protocols and Ports page appears.

- 26 -

Page 27: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Perform the following:

l Select the TCP option button.

l Select the Specific local ports option button.

l Type 1010.

- 27 -

Chapter 4 - Configuration

Page 28: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

5. Click Next.

The Action page appears.

6. On the Action page, select the Allow the connection option and then click Next.

The Profile page appears.

- 28 -

Page 29: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

7. On the Profile page, select the following check boxes.

l Domain

l Private

l Public

8. Click Next.

The Name page appears.

9. Enter the name of the wizard and Click Finish to close the New Inbound Rule Wizard for TCPport 1010.

10. Repeat the same procedure to add the following to ensure communication through Windowsfirewall.

l Inbound Rule of TCP port 1011

l Outbound Rule of TCP port 1010

l Outbound Rule of TCP port 1011

4.3.2 Configuring the IEC 61850system interface

Prerequisites

You must have mngr access level to configure the system interface.

- 29 -

Chapter 4 - Configuration

Page 30: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

To configure the IEC 61850system interface

1. Start the Station.

2. Click Configure>System Hardware>System Interfaces.

The Configuration Summary page appears.

Figure 4.1 Figure 1. Configuration Summary page

3. From the Type drop-down list, select .

4. In the Alias column, click IEC 61850.

The OPC Server Configuration page appears.

5. Select the Status tab, and click the Enabled check box, to enable Notifications.

ATTENTION

Notifications connection status LED appears Green only after at least one IED isconfigured. Refer to the section Removing IED.

- 30 -

Page 31: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Figure 4.2 Figure 2. Enabling notifications for IEC 61850system interface

6. Repeat the steps for the remaining four interfaces.

4.3.3 Configuring file replication

ATTENTION

This section is required only for the redundant server.

- 31 -

Chapter 4 - Configuration

Page 32: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

To configure file replication

1. Start Station.

2. Click Configure>File Replication.

The File Replication Summary page is displayed.

3. Click an unconfigured slot and then configure the file replication for IEC 61850, as displayed inthe following figure.

4.4 IED Configuration

This section includes tasks to configure the IED and points belonging to the IED.

l Starting the IEC 61850 system configurator

l Adding IED

l Removing IED

l Cloning IED

l Exporting IED

l Importing IED

l Scan Period Support

l File Service

l Log Control Block (LCB)

l Settings Groups Control Block (SGCB)

4.4.1 Starting the IEC 61850 system configurator

Using the Configuration Studio, you can configure IEC 61850system interface in . The system andnodes connected to the system and server are listed when the Configuration Studio is launched.

Prerequisites

To log on, you must be a member of the Administrator group.

- 32 -

Page 33: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

To start the IEC 61850 system configurator

1. Log on to the server.

2. Choose Start > All Programs > Honeywell Experion PKS > Configuration Studio.

3. Right-click Configuration Studio and then click Run as administrator.

The Connect dialog box appears.

4. In the list of systems and servers, click the system or specific server that you want to connectto and click Connect.

The Login to Server dialog box appears.

5. Log on to Configuration Studio with the required privileges.

6. On the Configuration Studio, click the IEC 61850 icon in the left pane.

IEC 61850 appears in the right pane.

7. Click Configure IEC 61850.

The IEC 61850 System Configurator tab appears next to the Configuration Explorer tab.

4.4.2 Adding IED

You can add IEDs into system by importing the IED configuration from SCL files or by importingvalues from the IED.

CAUTIONSCL files should be stored in properly access controlled location. Only administrator cancopy the vendor supplied SCL files.

- 33 -

Chapter 4 - Configuration

Page 34: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

TIP

As a best practice, it is recommended to add IED using SCL file. If the SCL file provided isinvalid or no SCL file is available, add the IED using Import from IED option.

To import from SCL files

1. In the Toolbar, click the icon to begin adding the IED.

The Add IED(s) dialog box appears.

2. Select Import from SCL file option and then click button.

3. Browse for the applicable SCL file, and navigate to the location of the required file and thenclick Open.

ATTENTION

The file is validated against the edition-1 or edition-2 schema to check if any errorsare displayed.

4. Click OK.

5. Change the IED name to the required reference name.

6. Select the interface in which IEDs are needed to be added.

The IED(s) are imported from the SCL file.

7. You can re-import the SCL file by selecting the Update option.

ATTENTIONl While importingmodified SCL file, IEDs are updated based on the IED Network

name. So, importing a modified SCL file with IED name change is considered asa new IED.

l Duringmodified SCL import, IED Network name should not be swapped acrossIEDs.

l For RCBs that do not end with an index, such as RCBA01, RCBA02 and so on,you must add the indexed= false tag in the RCB definition in the SCL file asfollows:

<ReportControl name="URCB_NOTINDEX" rptID="URCB_MX_notindex"indexed="false" confRev="1" bufTime="100" datSet="PgroupST1"intgPd="5000">

- 34 -

Page 35: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

To import from IED

1. In the Toolbar, click the icon to begin adding the IED.

The Add IED(s) dialog box appears.

2. Select the option Import from IED.

3. Specify the following details.

l IED name: name of the IED.

l IED network name: name as configured in the IED.

l IP Address: IP addresses of the remote device.

l Set the Edition value.

l Set Redundant value as Yes if you have a redundant IED, and enter the IP address of theredundant IED in the IP address field.

4. Select the interface in which IEDs must be added.

5. To addmore IED, click on the + symbol on left pane.

6. Click OK.

IEDs are added successfully.

7. You can re-configure the IEDs by selecting the Update option.

ATTENTIONl If IEC 61850 System Configurator tool is launched on nodes apart from primary

server, and adding the IEDs using Import from IED option, it will affect theoperation in other nodes. You should repoen the IEC 61850 SystemConfigurator tool.

l IEDs added using Import from IED option cannot be updated using SCL file.

l Logs of Import from IED option are found only in primary server nodes.

l IED Network name is case sensitive.

4.4.3 Removing IED

This sections describes tasks to remove IEDs.

To remove IED

1. In the Toolbar, click the icon to remove the IED.

A warningmessage is displayed, asking for confirmation to delete the IED.

2. Click OK to delete the IED.

A progress bar appears, displaying the progress of deletion.

After the IED is deleted successfully, the Tree view in the left pane no longer displays the IED.

ATTENTION

Removing the IED deletes all the points related to that IED.

- 35 -

Chapter 4 - Configuration

Page 36: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

4.4.4 Cloning IED

As there are identical bays in the substation, their IED configuration may also be identical. You canchoose to configure one typical IED and clone them as required.

Considerations

l You can clone a maximum of 50 IEDs at a time.

l Ensure to have a list of IED network names before you begin cloning.

To clone IED

1. In the Toolbar, click the icon to clone the IED.

The Clone IED dialog box appears.

2. In the Cloning options section, enter the following details.

l Number of IEDs to be cloned in the Number of clones drop down box.

l IED name

l IED network name

l OPC server

l IP address

ATTENTIONl Ensure that you specify the IED name and OPC server before you begin

cloning IEDs.

l IED Network name must be provided appropriately for IEDs that are addedusing Import from IED option, to ensure that these IEDs can be cloned.

l IED Network name is case sensitive.

3. Click Clone.

AWarningmessage is displayed asking for confirmation to clone.

4. Click OK.

Cloning begins. The status of the clone is displayed in the Status column.

- 36 -

Page 37: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

5. Repeat the previous steps to clone other IEDs. Click Close to exit.

The IEDs are displayed in the Tree view in the left pane, under their respective servers.

ATTENTION

Cloning is not supported for edition-2 IEDs where the logical device name is not asubset of IED Network name

NOTEAs a best practice, while adding IEDs using SCL file, add only the distinct IEDs andclone them later. This ensures that there is no reconfiguration.

4.4.5 Exporting IED

This section describes tasks to export IED configuration details into Microsoft Excel spreadsheet tofacilitate the user configure their system offline.

To export IED

1. In the Toolbar, click the icon to export IED.

The Export IEDs dialog box appears and the IED(s) are listed in the IED Selection List section.

2. Click the button to navigate to the path where the IED details must be exported.

The Browse For Folder dialog box appears.

3. If the Microsoft Excel spreadsheet exists in the selected folder, it is overwritten when theOverwrite Existing Files option is selected.

4. By default, only the points present in dataset are exported and you must uncheck the optionExport points in dataset to export all points.

- 37 -

Chapter 4 - Configuration

Page 38: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

5. In the IED Selection List section, select the IED(s) you want to export.

a. View the IED(s).

l Choose the server in the Server Name drop down box.

l Choose All option in the Server Name drop down box to view all IED(s) in the system.

b. Select the IED(s) by checking the check box next to the IED Name column.

6. Click Export

Amessage appears after the IEDs are successfully exported.

7. Click OK.

The IEC 61850 client interface configuration details are exported into a Microsoft Excelspreadsheet.

l Offline configuration

Offline configuration

The details of parameters in the Microsoft Excel spreadsheet are listed as follows:

- 38 -

Page 39: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Page Non-editable fields Editable fields

Analog_Points

l IEDName

l LogicalDevice

l LogicalNode

l PointID

l PointName

l Description

l Asset

l AssociatedDisplay

l DetailDisplay

l GroupFaceplateTemplateDisplay

l ScanningEnabled

Analog_Parameters

l Parent Item Name

l LogicalDevice

l LogicalNode

l ParameterName

l ExperionMappingParameter

l FunctionalConstraint

l PointID

l AlarmType0

l AlarmPriority0

l AlarmLimit0

l AlarmType1

l AlarmPriority1

l AlarmLimit1

l AlarmType2

l AlarmPriority2

l AlarmLimit2

l AlarmType3

l AlarmPriority3

l AlarmLimit3

l AlarmDisable

l RangeLow

l RangeHigh

l Deadband

Status_Points

l IEDName

l LogicalDevice

l LogicalNode

l PointID

l PointName

l Description

l Asset

l AssociatedDisplay

l DetailDisplay

l GroupFaceplateTemplateDisplay

Status_Parameters

l Parent Item Name

l LogicalDevice

l LogicalNode

l ParameterName

l ExperionMappingParameter

l FunctionalConstraint

l AlarmEnableState0

l AlarmDescriptorState0

l AlarmPriority0

l AlarmEnableState1

l AlarmDescriptorState1

l AlarmPriority1

l AlarmEnableState2

l AlarmDescriptorState2

l AlarmPriority2

l AlarmEnableState3

l AlarmDescriptorState3

l AlarmPriority3

l AlarmDisable

- 39 -

Chapter 4 - Configuration

Page 40: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

l EnableSOE

Reports

l Dataset

l ReportID

l Domain

l SelectReport

l IntergrityPeriod

l SequenceNo

l ReportTimeStamp

l ReasonForInclusion

l DataSetOption

l DataReference

l BufferOverflow

l EntryID

l ConfigurationRevision

l Segementation

l DataChange

l QualityChange

l DataUpdate

l Intergrity

l GI

Guidelines for modifying IED values in the Microsoft Excel spreadsheet

l You can modify only existing IEDs.

l You cannot add a new IED (new row).

l Ensure that you do not copy paste content in the editable fields in the Microsoft Excelspreadsheet. Validations are not performed on copy-pasted content.

l Ensure that you do not change the non-editable fields. Though Microsoft Excel spreadsheetallows you to make changes, these changes are not imported.

l You can modify the name of the Microsoft Excel spreadsheet.

l Ensure that the entries in the DetailDisplay and GroupFaceplateTemplateDisplay end with.htm/.html.

4.4.6 Importing IED

This section describes tasks to import IED configuration details from a Microsoft Excel spreadsheet.

- 40 -

Page 41: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

To import IED

1. In the Toolbar, click the icon to import IED.

The Import IED(s) dialog box appears and the IED(s) are listed in the IED Selection Listsection.

2. Click the button to navigate to the path where the IED details are located.

The Browse For Folder dialog box appears.

3. Browse to the required folder, select the Microsoft Excel spreadsheet, and click OK.

The path where the Microsoft Excel spreadsheet is present appears in the Directory field.

4. Select the IED(s) you want to import by checking the check box next to the IED Name column.

ATTENTION

Ensure that you import the updatedMicrosoft Excel spreadsheet. Otherwise, theconfiguration done in the UI is lost. As a best practice, you can have a commondirectory to export all the Microsoft Excel spreadsheets, modify them and importback.

5. Click Import.

A message appears after the IEDs are successfully imported.

6. Click OK.

The IEC 61850 client interface configuration details are imported into a Microsoft Excelspreadsheet and displayed in the Tree view in the left pane, under the individual servers.

- 41 -

Chapter 4 - Configuration

Page 42: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

4.4.7 Scan Period

Scan Period Configuration

The Scan Period is used to read the data for Dataset and Non Dataset points based on theconfigured periodicity . By default, the point will be set to Scan Period as 0. If Scan Period is setother than 0, then the read operation happens from the device at the specified scan period.

Figure 4.3 Scan Period Configuration

NOTEThe point is already part of Dataset that is mapped to a report and enabled. ConfiguringScan Period for these points, will lead to send additional read requests for same point valuemapped in the report.

- 42 -

Page 43: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.4.8 File Services

CAUTIONLoad shedding files and Disturbance recording files should be stored in properly accesscontrolled location. Only administrator can copy the vendor supplied Load shedding filesand Disturbance recording files.

Manual File Services

The user can perform below File Services using IED point detailed display:

1. Read file

2. Delete file

3. Transfer file.

Read file

This operation is used to read the file content from the IED to the client (Experion server).

To read file, perform the below steps:

1. Select Read filefrom Command drop-down list.

2. Select a file from Remote file name drop-down list.

3. Type the preferred local file name in Local file name text box.

4. Click Send command.

5. Retrieved file is stored in the Output path.

Delete file

This operation allows the user to delete a file from the IED.

To delete file, perform the below steps:

1. Select Delete filefrom Command drop-down list.

2. Select a file from Remote file name drop-down list.

3. Click Send command.

Transfer file

This operation allows the user to transfer file from the client (Experion server) to IED.

To transfer file, perform the below steps:

1. Select Transfer filefrom Command drop-down list.

2. Browse and select the local file.

3. Type the Remote file name.

4. Click Send command

NOTEEnsure that the file exist in the File Transfer folder.

- 43 -

Chapter 4 - Configuration

Page 44: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

Automatic retrieval of COMTRADE file

The COMTRADE file can be retrieved from IED automatically by monitoring RcdMade data objectunder RDRE logical Node. When the COMTRADE file recorded in IED, then IED will set theRcdMade data attribute to 1.

The Point Scripts needs to be created for RcdMade SCADA point to retrieve the COMTRADE fileautomatically when the file is recorded in IED using FileServiceQuery and FileServiceCommandparameters available under IED SCADA point.

Below steps needs to be implemented as a part of point scripts on value change of RcdMadeSACADA point :

1. To retrieve COMTRADE file Name:

a. Write value "1" to FileServiceCommand parameter.

b. COMTRADE file name will be retrieved and updated in FileServiceQuery parameter.

2. To retrieve COMTRADE file Content:

a. Write value <COMTRADE_FILE_NAME, LOCAL_FOLDER_FILE_NAME> to FileServiceQueryparameter.

b. Write value "4" to FileServiceCommand parameter.

The COMTRADE file will be copied to server local folder.

NOTEl Make sure RcdMade data object is part of Reports or configure scan rate to 1sec for

RcdMade SCADA point to read the attribute value periodically.

l Alarm can be configured for RcdMade SCADA point for State 1, when COMTRADE fileis recorded by IED and alarm will be reported.

4.4.9 Log Control Block (LCB)

This feature allows the user to retrieve the historical values of data objects. To retrieve thehistorical values, IED must be capable to support Log Control Block.

To configure the LCB, perform below steps:

1. Select the IED from List view.

2. In the Control Blocks tab, under CB Type select CONFIGURED for LCB.

3. Click on Save Control Block Settings and download the IED.

Figure 4.4 Configure and download LCB

- 44 -

Page 45: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

To configure LCB point, perform below steps:

1. Select the IED from List view and expand.

2. Go to LLN0 logical node in the List view and expand.

3. Under LLN0 logical node, select LG Functional Constraint and configure the point.

4. Under LG Functional Constraint, select the LCB data object .

5. Configure and download the LCB data object with appropriate assets, names, etc.

The user can perform below options to retrieve the historical data from IED using LG point detaileddisplay. LCB performs the following two operations:

1. Read Parameters

2. Read Log

Read Parameters

This operation reads LCB configuration data and parameters from the IED.

To read the LCB parameters, perform the below steps:

1. Open Station and open the IED Detail Display.

2. Enable the LCB in IED Detail Display.

3. Open the LCB Point Detail Display in station. The LOG control block page appears.

- 45 -

Chapter 4 - Configuration

Page 46: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

4. Select Read_Parameters from the Query type drop-down list.

5. Click Query.

Figure 4.5 Read Parameters

Read Log

This operation reads the historical data for specified time intervals.

To read log perform the following steps:

1. Select Read Log from the Query type drop-down list.

2. Once you select Read Log, the following options are listed:

a. ByTime

b. ByLogEntry

ByTime

This allows user to retrieve a range of historical data based on time ranges (Start time and Endtime). To read log ByTime select required Start time and End time and click Query. The historicaldata recorded between the user specified start time and end time is retrieved from the IED.

Figure 4.6 Read Log - ByTime

- 46 -

Page 47: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

NOTETo report SOE events of the historical data in the user specified time interval, select EnableSOE option before Query. Also, SOE option to be enables at point level.

Figure 4.7 Read Log - ByTime with SOE enabled

The SOE events of the historical data are updated as shown in following figure.

- 47 -

Chapter 4 - Configuration

Page 48: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

Figure 4.8 SOE events of the historical data (Read Log - ByTime)

ByLogEntry

This allows user to retrieve historical data from the referenced ID that are after the Start time andEntry. To read log ByLogEntry select required Log id, Start time and then click Query. This readsthe data from entered Log id and start time till the latest data. The historical data recordedbetween the user specified start time and Log id is retrieved from the IED.

Figure 4.9 Read Log - ByLogEntry

- 48 -

Page 49: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

NOTETo report SOE events of the historical data in the user specified start time and Log id, selectEnable SOE option before Query. Also, SOE option to be enables at point level.

Figure 4.10 Read Log - ByLogEntry with SOE enabled

The SOE events of the historical data are updated as shown in following figure.

Figure 4.11 SOE events of the historical data (Read Log - ByLogEntry)

4.4.10 Settings Groups Control Block (SGCB)

The Settings Groups Control Block (SGCB) is used to modify and edit the settings groups.

To configure settings groups control block, perform the below steps:

- 49 -

Chapter 4 - Configuration

Page 50: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

1. Select the IED from List view and expand.

2. Go to LLN0 logical node in the List view and expand.

3. Under LLN0 logical node, select SP Functional Constraint.

4. Under SP Functional Constraint, select SGCB data object for Setting Group Control Block.

5. Configure the SGCB with assigned assets and download the data object.

Figure 4.12 Configure and download settings groups

6. Open Station and call SGCBPoint Detail Display.

7. Once SG block is called, then the below parameters are updated:

a. SGCB point

b. Number of setting groups

c. Active setting group

To change the active setting group, select the group from the Active setting group drop-down list.

To edit the setting group, select the group from the Edit setting group drop-down list, using thirdparty tool modify the required parameters, and enable Confirm Edit Setting Group check box toload the new setting group values.

Figure 4.13Modify and edit settings groups

- 50 -

Page 51: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.5 IEC 61850 points configuration

This section provides the information on the steps to configure the analog and digital points.

Configuring IEC 61850 points consists of the following steps:

l Configurig Assets, Alarms and SOE

l Downloading points

l Deleting points

l Configurig Assets, Alarms and SOE

l Downloading points

l Deleting points

4.5.1 Configurig Assets, Alarms and SOE

This section describes the steps to configure alarms and SOE for the IEDs.

To configure assets, alarms and SOE

1. Expand the IED in the Tree view, and then browse until the required point.

2. In the Tab view, configure the following parameters.

- 51 -

Chapter 4 - Configuration

Page 52: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

Tab Configuration

Maintab

l ID

l Name

l Description

l Asset

l CDC type

ATTENTIONCDC type is populated from SCL file by default. For IEDs added using Import fromIED option, CDC type is populated as per standard and for non-standard points,CDC type is unknown, which you can change based on your requirements.

Displaytab

l Group Number

l Position in Group

l Associated Display

l Point Detail display

l Group Faceplate Template Display

AlarmHistory&Trendtab

l Select the parameter for which you want to configure the alarms.

l Specify the parameter descriptor, state description and severity.

l Configure the history and trend numbers in the History Options, Group and TrendOptions sections.

l In the Alarm Options section, select Field Timestamp check box if you require fieldtimestamp for alarms.

ATTENTIONFor points that have more than 4 states, you can change the number of states to 8and provide State Descriptor as None for states which are not applicable. Forexample, to configure mode of the logical node point which has 5 states, you haveto change the number of states to 8 and provide descriptors for state 0,6 and 7 asNone.

4.5.2 Downloading points

Considerations

l Point name must be as per Experion standards.

l If the IED properties or point properties are updated, these IEDs must be downloaded again.

l Point must be assigned to Assets for a successful download.

To download points using the List view

1. Download the IEDs.

2. In the List view, select the points you want to download. To select multiple points, hold theSHIFT key and then select the points.

3. .Download the points by clicking the Download button in the Tool Bar view.

The downloading of points begins. The downloaded points icon appears green.

- 52 -

Page 53: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.5.3 Deleting points

1. Select the required points to be deleted in the List view.

2. Click Delete points in the toolbar. The selected points are deleted, and a success messageappears at the bottom of Delete Points dialog box.

4.6 Assigning Report Control Blocks

To support hot standby redundancy feature, the Report Control Blocks of IEDs must be assigned toprimary and backup servers. For each dataset, you must ensure that the reports are assignedcorrectly, so that data is reported in parallel to both the servers.You can select the followingoptions for Report Control Blocks.

l None

l Non-redundant

l ServerA

l ServerB

Guidelines for enabling reports

l Identify the dataset that contains the downloaded points to find out in which dataset the pointsare present, by referring to the Dataset Values tab.

l Identify the list of reports that contain the required dataset names.

l To enable hot redundancy, ensure that two instances of reports are configured for ServerAand ServerB respectively.

l If instance reports are not supported by IEDs, then configure them as non-redundant.

l For non-redundant systems, configure reports as non-redundant.

ATTENTION

The report assignment must be done for both ServerA and ServerB for hot standbyredundancy to work as intended.

Enabling history backfill

You can enable history backfill for buffered reports(BRCB). Ensure to check the History Backfillcheck box for the required buffered reports.

ATTENTION

You cannot enable history backfill for unbuffered reports.

Considerations

You should enable reports for data set that contain the downloaded points. You can also referDataset Values tab for information about the downloaded point.

Default settings for reports

- 53 -

Chapter 4 - Configuration

Page 54: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

Datasettype

Report control blocktype

Trigger options Optional fieldsIntegrityperiod

Analog BufferedPeriodic, GI & no datachange

l Sequence number

l Report Time Stamp

l Dataset

l Buffer overflow (forbuffered reports only)

l EntryID (for bufferedreports only)

l Configuration revision

1000

UnbufferedPeriodic, GI & no datachange

1000

Digital BufferedData Change & GI andno periodic

0

UnbufferedData Change & GI andno periodic

0

4.6.1 To enable reports

1. Select the IED from the list view.

2. In the Reports tab, select the required reports that should be enabled. You can change thevalue if the following fields, if required.

l Select Report

l Optional fields

l Trigger options

l Integrity period

l History Backfill

3. Click Save Report Settings.

4.7 Configuring control parameters

Experion supports the following IEC 61850 control.

l direct execute

l select before operate

l direct execute with enhanced security

l select before operate with enhanced security

4.7.1 To exceute direct execute/direct execute with enhancedsecurity control

1. Use Operate service to execute the command by writing Oper with high value along with theother parameters of Oper service with the required values according to the table below.

2. Use Cancel service to cancel the command by writing Cancel with high value along with theother parameters of cancel service with the required values according to the table below.

- 54 -

Page 55: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

4.7.2 To execute select before operate control

1. Use Select service to select the desired control operation by writing SBO with high value alongwith the other parameters of SBO service with the required values according to the tablebelow.

2. Use Operate service to execute the command by writing Oper with high value along with theother parameters of Oper service with the required values according to the table below.

3. Use Cancel service to cancel the command by writing Cancel with high value along with theother parameters of cancel service with the required values according to the table below.

4.7.3 To execute select before operate with enhanced securitycontrol

1. Use Select service to select the desired control operation by writing SBOw with high valuealong with the other parameters of SBOW service with the required values according to thetable below.

2. Use Operate service to execute the command by writing Oper with high value along with theother parameters of Oper service with the required values according to the table below.

3. Use Cancel service to cancel the command by writing Cancel with high value along with theother parameters of cancel service with the required values according to the table below.

Recommended settings for control parameters

- 55 -

Chapter 4 - Configuration

Page 56: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

parameters IEC 61850 service Recommended value

OperCheck Operate

l 01: check interlock

l 10: checksynchrocheck

l 11: check both

l 00: nocheck

OperT can be blank

OperTestl 0: no test

l 1: perform control in Test Mode

OperctlNum can be blank

OperctlVall 0: open

l 1: close

Oper 1: execute Oper command

OperoriginorCat 2

OperoriginorIdent can be blank

CancelT Cancel can be blank

CancelTestl 0: no test

l 1: perform control in Test Mode

CancelctlNum can be blank

CancelctlVall 0: open

l 1: close

Cancel 1: execute Cancel command

CanceloriginorCat 2

CanceloriginorIdent can be blank

SBO Select1: execute Selectcommand

SBOCtrll 0: open

l 1: close

SBOwCheck SelectwithValue

l 01: check interlock

l 10: checksynchrocheck

l 11: check both

l 00: nocheck

SBOwT can be blank

SBOwTest0- No test, 1- Perform control in TestMode

SBOwctlNum can be blank

SBOwctlVal 0-Open, 1 -Close

SBOwWrite 1 to Exceute Select with valuecommand

SBOworiginorCat 2

SBOworiginorIdent can be blank

- 56 -

Page 57: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

ATTENTION

If Select, Cancel, Operate or Select with value operations fail, the value ofSBO,Oper,cancel,SBOW contains value -1.

TIPl Use Operate and Cancel services for direct control / direct control with enhanced

security control.

l Use Select, Operate and Cancel services for select before operate control.

l Use SelectwithValue, Operate and Cancel services for select before operate withenhanced security control.

4.8 Synchronizing servers

This section includes tasks to synchronize servers for IEDs from the IEC 61850 configuration.Servers must be synchronized when configuration changes should be reflected in the system.

4.8.1 Prerequisites

To synchronize servers, you must be a member of the Administrator group.

4.8.2 To synchronize servers

1. In the Toolbar view, click on the server icon which must be synchronized.

The Synchronize dialog box appears.

2. The Synchronize dialog box asks for a confirmation to synchronize. Click Yes.

The selected server is restarted.

4.9 Embedding a point in custom display

This section includes tasks to embed an analog point in a custom display.

1. Open the HMIWeb Display Builder.

2. Click Start > All Programs > Honeywell Experion PKS > Server > HMIWeb Display Builder.

TIP

The IED and points must be downloaded.

3. Open a new display.

4. Drag a text box on the display and then drag the alphanumeric object on the display.

5. Double-click the object and then click the Data tab.

6. Click the Browse button corresponding to the Point drop-down list.

- 57 -

Chapter 4 - Configuration

Page 58: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 4 - Configuration

7. In Point Browser, double-click the required point to be displayed in the Point text box.

ATTENTION

Only the downloaded points are listed in the Point Browser.

8. Select the required parameter from the Parameter drop-down list.

The following figure displays an example of a display.

9. Save the display with a name in the abstract folder.

TIP

The abstract folder is located at:

C:\ProgramData\Honeywell\ ExperionPKS\Client.

10. Open Station.

11. Change the security level to MNGR.

12. Type the display name in the command line and then press ENTER.

- 58 -

Page 59: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

OPERATIONS

l Alarms

l Trend group

l System status display

l Experion system detailed display

l IEC 61850 Diagnostics tool

l Log Control Block detailed display

5.1 Alarms

Alarm can be viewed on the station. You can process the alarms (acknowledge, shelve, and so on)like a normal CDA or a SCADA point alarm.

5.2 Trend group

In the station, you can create and operate a trend group like any normal operation.

- 59 -

CHAPTER

5

Page 60: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

5.3 System status display

The System Status display page displays the domain status of the IEC 61850 device.

5.4 system detailed display

The detailed display page displays the status of the IED device.

- 60 -

Chapter 5 - Operations

Page 61: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 5 - Operations

5.4.1 IED detail display

You can view the IED detail display in the Station using IED point and perform the followingoperations

l Enable/Disable IED

l Enable/Disable Reports

l Status of IED/Reports

l ConfiguringMarginal and Fail limits

l View the current communication retry count

1. Open the Station.

2. Choose Configure > System Hardware > Point Servers.

The System Interfaces display appears.

3. Select the type of interface, from the Type list box.

4.

Click the IEC 61850IEDs link.

The Point Server Configuration Display appears.

l Network name represents the point server’s computer name. This can be the localhost orthe network name of a stand-alone point server computer, but cannot be an IP address.Enter the appropriate name of the computer where the point server is configured inNetwork name.

l Server alias represents the name the server uses for the point server. This name appearsin the alarm and event summaries. Enter an appropriate name in alias.

- 61 -

Page 62: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

5.4.2 IED summary display

- 62 -

Chapter 5 - Operations

Page 63: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 5 - Operations

- 63 -

Page 64: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

5.5 IEC 61850 Diagnostics tool

The IEC 61850 Diagnostics tool helps in offline and online diagnosis of IEC 61850 interface. Thistool can increase/decrease the debug levels of devices configured and also capture theconfiguration and log files’ dump.

The main page of the IEC 61850 Diagnostics tool is as shown in the following image.

- 64 -

Chapter 5 - Operations

Page 65: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 5 - Operations

5.5.1 Launching the IEC 61850 Diagnostics tool

1. Click Start > All Programs > Honeywell Experion PKS > IEC 61850 > IEC 61850 Diagnostics.

2. If the User Account Control dialog box appears, click Yes.

The IEC 61850DCT page appears.

- 65 -

Page 66: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

l The IEC 61850DCT user interface

5.5.2 The IEC 61850DCT user interface

You can perform the following operations in the IEC 61850DCT page.

l Save diagnostics package data on your system.

l View/modify logs.

To save the diagnostics package data on your system

1.

On the IEC 61850DCT page, click the Save Diagnostic Package button.

The Save As dialog box appears.

2. Navigate to an appropriate path on your system.

3. Specify the package name, and click Save.

- 66 -

Chapter 5 - Operations

Page 67: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 5 - Operations

To view/modify logs

1.

On the IEC 61850DCT page, click the Advanced button.

The diagnostics details appears in the IEC 61850DCT page.

2. To view the diagnostics details, perform one of the following:

Option Description

Server tab Select the server whose details you want to view.

Refresh Refresh the diagnostic detail view.

Adjust Debug levels Adjust the level of log information to be collected for a server.

3. To adjust debug levels, perform one of the following:

Option Description

Increase/decreasedebug

Adjust the scale in the Adjust Debug section to increase/decreasedebug levels.

Restore all defaults Restore the default debug levels for all IEDs.

Restore defaults Restore the default debug levels for selected IEDs.

- 67 -

Page 68: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

TROUBLESHOOTING AND MAINTENANCE

This section provides general information on troubleshooting the typical problems faced whileusing the IEC 61850 interface.

l OPCData Connection status is 'Not connected'

l OPCNotification status is ‘Connecting’

l Other issues

6.1 OPC Data Connection status is 'Not connected'

Problem

The OPC data connection display status appears as ‘Not connected’, on the Statustab.

Also, the connection status does not appear in Green.

Cause NA

ResolutionTo view the status as Connected on the Status tab perform the following:

l Click the Configuration tab or the Tuning tab and then click the Status tab again.

6.2 OPC Notification status is ‘Connecting’

ProblemThe OPC data connection display status appears as ‘Connecting’, on the Status tab.

Also, the connection status does not appear in Green.

Cause No IEDs are configured.

ResolutionTo view the status as Connected on the Status tab, perform the following:

l Ensure that at least one IED is configured.

6.3 Other issues

IEDs are not displayed after opening the IEC 61850 System Configurator tool

Problem IEDs are not displayed after opening IEC 61850 system configurator tool.

Cause NA.

Resolution Close the tool and open it again.

IEDs are not added through SCL file

- 68 -

CHAPTER

6

Page 69: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Problem IEDs are not added through SCL file

Cause The Schema for the SCL file is invalid and not according to the standard.

Resolution

1. Check for the Schema errors while adding the SCL file by clicking on viewdetails.

2. Open view logs or navigate to configuration logs folder inC:\ProgramData\Honeywell\Experion

PKS\IEC61850\Log\Configuration and open SCLParsing.logfile and navigate to last to the lastly added IED.

If SCl_Parse_Res value is one then SCL xml structure is invalid.

l SCL_DT_Create_Res value is one then IED data model is incorrect.

l SCL_LD_Create_Res value is one then dataset contents or RCBs are invalid.

IEDs are not added through "Import from IED" option

Problem IEDs are not added through "Import from IED" option.

CauseThe IEDs are not communicating or the IED returned a negative response to the MMSrequest.

Resolution

1. Check that IED is communicating andMMS services are enabled in the IED.

2. View logs or navigate to configuration logs folder underC:\ProgramData\Honeywell\ExperionPKS\IEC61850\Log\Configuration and open 61850Config.log file andfind whether IED returned negative response to the MMS request.

Modified SCD file import is getting failed

Problem Modified SCD file import is getting failed.

Cause Incorrect SCL files schema in the modified SCL file.

Resolution Correct the SCL file as per schema.

Auto Point save is provoked only for some points

Problem Auto Point save is provoked only for some points.

CauseAuto Point save is provoked for points that contains SR Functional Constraint in themand it doesn’t have any impact.

Resolution Click on save and proceed.

Points are not getting downloaded

Problem Points are not getting downloaded.

Cause

Points downloadmay fail in the following scenarios.

l If the point name is already assigned or present in the system.

l Experion Switchover while System Configuration tool is opend.

Resolutionl Change the point name and try to download again.

l Reconnect to the primary server by relaunching the configuration studio.

Unhandled exception appears while opening the IEC 61850 System Configurator tool

Problem Unhandled exception appears while opening the IEC 61850 System Configurator tool.

CauseThe configuration files are corrupted due to improper closing of the IEC 61850 SystemConfigurator tool or Configuration Studio.

ResolutionCheck for the correct schema for config.xml, if something is corrupted then rectify thesame.

File being used by other process

- 69 -

Chapter 6 - Troubleshooting andmaintenance

Page 70: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Chapter 6 - Troubleshooting andmaintenance

Problem File being used by other process.

Cause The File replication is taking longer time due to network constrains.

Resolution

1. Check the network for speed and duplex settings and ensure file replicationhappens successfully.

2. Close the configuration studio and reopen the same and perform the lastoperation being processed.

Point Save operations fails

Problem Point Save operations fails.

Cause Improper handling of multiple project scenarios.

ResolutionEnsure that while performing Import from IED from non- primary server node needsthe System Configuration tool to be closed and reopened in other nodes.

Unhandled exception while performing operations

Problem Unhandled exception while performing operations.

Cause Corrupted database XMLs.

ResolutionWhenever Unhandled exception comes it is advised to quit the configuration studioand reopen them, still the error is there then delete the IED and reconfigure thesame.

IEC 61850 Diagnostics tool live logs are not displayed

Problem IEC 61850 Diagnostics tool live logs are not displayed.

Cause The tool is open for a long time.

Resolution Relaunch the tool.

Report Control Blocks are not enabled

Problem Report Control Blocks are not enabled.

Cause

l Report is enabled by third party simulator or external clients.

l RCB-write fails.

l You cannot write the Report Setting options such as Trgops, Optflds, buftm, rptID.

Resolution

l Close all third party clients.

l Check for Server logs in C:\ProgramData\Honeywell\ExperionPKS\IEC61850\Log\HCI.IEC6850.X.

l Check with vendor the reason the write operation fails and correct the Reportsettings in config xml if you cannot perform write operation.

Data is not updated

Problem Data is not updated.

CausePoints are not present in dataset, if they are present then the corresponding Reportscontrol blocks are not selected properly for Server A and Server B

Resolution

l Close all third party clients.

l Check for Server logs in C:\ProgramData\Honeywell\ExperionPKS\IEC61850\Log\HCI.IEC6850.X.

l Check with vendor the reason the write operation fails and correct the Reportsettings in config xml if you cannot perform write operation.

Alarms are not getting raised

- 70 -

Page 71: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

Problem Alarms are not getting raised.

Causel Notifications are not being enabled.

l The points are not reported by the IED using RCB's.

Resolutionl Enable the notification under IEC 61850 system interface.

l Check that the points are part of dataset and corresponding RCBs are enabled.

Control model of the point has a mismatch with the IED

Problem Control model of the point has a mismatch with the IED.

Cause Control model of the respective point is changed after the IED association.

ResolutionDisabled the IED and enabled the IED so that control model can re-read from theIEDs.

Control of the point failure

Problem Control of the point failure.

Causel Control model of the respective point is different from that of the IED.

l IED is giving the negative feedback command for the control.

Resolution Resync the control model.

Incorrect Control Type for points

Problem Incorrect Control Type for points.

Cause

The various supported control types are Boolean, Enum and Integer. These are basedon the CDC type provided in SCL files. For a particular CDC type if the control typeprovided for the point in SCL file is different than the control type as defined by thestandard, then control type mismatch occurs.

Resolution Provide control from the custom displays.

Parameters are not displayed in Faceplate

Problem Parameters are not displayed in Faceplate.

CauseIf the concatenation of names of parameters of the point exceeds Experion limit of255 Charcters.

Resolution Configure the points in custom displays.

"Data Limit Exceeded" warning appears in system alarms

Problem "Data Limit Exceeded" warning appears in system alarms.

CauseThe Number of parameters per second reported from the IEDs exceeds the limit of15000.

ResolutionControl the rate at which the parameters are reported from the IEDs by changing thedead band for the analog points.

- 71 -

Chapter 6 - Troubleshooting andmaintenance

Page 72: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

PERFORMANCE PARAMETERS AND LIMITATIONS

7.1 Server performance

NOTEThis specification is the combination of Reports and Scan Period.

Performance Capacity

Number of IEDs 200

Number of system interfaces 5

Number of IEDs per system interface 40

Number of IEC 61850 SCADA points 17000

Number of logical devices per IED 64

Number of logical nodes per logical device 255

Number of parameters per logical node 4068

Number of Active Alarms 3600

Number of Events (burst condition) 1000

History Sizing (Fast\ Standard\ Extended) 1000/ 2000/ 5000

SOE 9999

Number of events supported for the History backfill 10000

Number of data attributes reported per second per instance 15000

- 72 -

CHAPTER

7

Page 73: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

NoticesTrademarks

Experion®, PlantScape®, SafeBrowse®, TotalPlant®, and TDC 3000® are registered trademarks ofHoneywell International, Inc.

ControlEdge™ is a trademark of Honeywell International, Inc.

OneWireless™ is a trademark of Honeywell International, Inc.

Matrikon® andMatrikonOPC™ are trademarks of Matrikon International. Matrikon International isa business unit of Honeywell International, Inc.

Movilizer® is a registered trademark of Movilizer GmbH. Movilizer GmbH is a business unit ofHoneywell International, Inc.

Other trademarksMicrosoft and SQL Server are either registered trademarks or trademarks of Microsoft Corporationin the United States and/or other countries.

Trademarks that appear in this document are used only to the benefit of the trademark owner,with no intention of trademark infringement.

Third-party licensesThis product may contain or be derived frommaterials, including software, of third parties. Thethird party materials may be subject to licenses, notices, restrictions and obligations imposed bythe licensor. The licenses, notices, restrictions and obligations, if any, may be found in thematerials accompanying the product, in the documents or files accompanying such third partymaterials, in a file named third_party_licenses on the media containing the product, or athttp://www.honeywell.com/ps/thirdpartylicenses.

Documentation feedbackYou can find the most up-to-date documents on the Honeywell Process Solutions support websiteat: http://www.honeywellprocess.com/support

If you have comments about Honeywell Process Solutions documentation, send your feedback to:[email protected]

Use this email address to provide feedback, or to report errors and omissions in thedocumentation. For immediate help with a technical problem, contact your local HoneywellProcess Solutions Customer Contact Center (CCC) or Honeywell Technical Assistance Center(TAC).

How to report a security vulnerabilityFor the purpose of submission, a security vulnerability is defined as a software defect or weaknessthat can be exploited to reduce the operational or security capabilities of the software.

Honeywell investigates all reports of security vulnerabilities affecting Honeywell products andservices.

To report a potential security vulnerability against any Honeywell product, please follow theinstructions at:

https://www.honeywell.com/product-security

Support

- 73 -

Page 74: IEC61850SCADAConfigurationGuide€¦ · Contents 3 Chapter1-Aboutthisguide 6 1.1 Revisionhistory 6 1.2 Intendedaudience 6 Chapter2-Introduction 7 2.1 AboutIEC61850 7 2.1.1 AboutIEC61850

For support, contact your local Honeywell Process Solutions Customer Contact Center (CCC). Tofind your local CCC visit the website, https://www.honeywellprocess.com/en-US/contact-us/customer-support-contacts/Pages/default.aspx.