IEC 60870-5-101 Requirement for RLDC
-
Upload
skmandilwar -
Category
Documents
-
view
26 -
download
4
description
Transcript of IEC 60870-5-101 Requirement for RLDC
![Page 1: IEC 60870-5-101 Requirement for RLDC](https://reader031.fdocuments.us/reader031/viewer/2022020102/55cf99f6550346d0339fe7dd/html5/thumbnails/1.jpg)
IEC 60870-5-101 Interoperability profile for NRLDC, NERLDC , ERLDC (ALSTOM EMS/SCADA system)
Page 9 of 10 Rev.1
2. ADDITIONAL INFORMATION ON IEC 60870-5-101 FOR NRLDC, NERLDC AND ERLDC
A. Telemetred Data and ASDU mapping
The following table explains the type of the telemetered data and corresponding ASDUs used to transmit this data as per IEC 60870-5-101 protocol. These are same for all the above three RLDCs.
Type of Data Data Unit type as per IEC
Description as per IEC
Data polling method
Interrogation group
Transmitted after Class-X request
Info Obj. Addressrange
Analog inputs (P,Q, V, f)
ASDU-11 Measured value scaled value
As cyclic data on Class 2 polls
Class 2 8848-
ASDU-1 Single point information
By exception (spontaneous) and on periodic Group scan
Group-1 Class 1 after exception, Class 1 after Group 1 scan
392- Digital inputs –Single status (Isolators, Protection signals)
ASDU- 2 (for SOE)
Single point information with time tag
By exception (spontaneous) and on periodic Group scan
Group-1 Class 1 after exception, Class 1 after Group 1 scan
Digital inputs –Double status (Circuit breakers)
ASDU-4 Double point information with time tag
By exception (spontaneous) and on periodic Group scan
Group-1 Class 1 after exception, Class 1 after Group 1 scan
256-
Pulse accumulators ASDU-15 Integrated totals By periodic counter interrogation
Group-1 (counter interrogation)
Class 2 12544-
Analog Outputs (Setpoint)
ASDU-48 Set point command Normalized value
37120
Digital Control command (CB
ASDU 46 Double command 33024-