I9-089B R30 R40

download I9-089B R30 R40

of 124

Transcript of I9-089B R30 R40

  • 7/27/2019 I9-089B R30 R40

    1/124

    Instruction Manual

    R30, R40 Series Line Recorders

  • 7/27/2019 I9-089B R30 R40

    2/124

  • 7/27/2019 I9-089B R30 R40

    3/124

    HANDLING OF ELECTRONIC EQUIPMENT

    A person's normal movements can easily generate electrostatic potentials of several thousand volts.Discharge of these voltages into semiconductor devices when handling electronic circuits can cause

    serious damage, which often may not be immediately apparent but the reliability of the circuit will have

    been reduced.

    The electronic circuits of ALSTOM T&D Protection & Control Ltd products are completely safe from

    electrostatic discharge when housed in the case. Do not expose them to the risk of damage by

    withdrawing modules unnecessarily.

    Each module incorporates the highest practicable protection for its semiconductor devices. However, if it

    becomes necessary to withdraw a module, the following precautions should be taken to preserve the high

    reliability and long life for which the equipment has been designed and manufactured.

    1. Before removing a module, ensure that you are at the same electrostatic potential as the equipment

    by touching the case.

    2. Handle the module by its front-plate, frame, or edges of the printed circuit board.

    Avoid touching the electronic components, printed circuit track or connectors.

    3. Do not pass the module to any person without first ensuring that you are both at the same

    electrostatic potential. Shaking hands achieves equipotential.

    4. Place the module on an antistatic surface, or on a conducting surface which is at the same

    potential as yourself.

    5. Store or transport the module in a conductive bag.

    More information on safe working procedures for all electronic equipment can be found in BS5783 and

    IEC 60147-0F.

    If you are making measurements on the internal electronic circuitry of an equipment in service, it is

    preferable that you are earthed to the case with a conductive wrist strap.Wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap is not

    available, you should maintain regular contact with the case to prevent the build up of static.

    Instrumentation which may be used for making measurements should be earthed to the case whenever

    possible.

    ALSTOM T&D Protection & Control Ltd strongly recommends that detailed investigations on the electronic

    circuitry, or modification work, should be carried out in a Special Handling Area such as described in

    BS5783 or IEC 60147-0F.

    Instruction Manual

    R30, R40 Series Line Recorders

  • 7/27/2019 I9-089B R30 R40

    4/124

    Page 4

    CONTENTS

    SAFETY SECTION

    1. INTRODUCTION 12

    1.1 General information 12

    1.2 Qualified person 121.3 Warning information 12

    1.4 Approved use 13

    2 APPLICATION 14

    2.1 Purpose 14

    2.2 Standard 14

    2.3 Designs 14

    2.4 Options 15

    2.5 Delivery 15

    2.6 Conversion 15

    2.7 Environmental protection 15

    3 DESIGN AND MODE OF OPERATION 16

    3.1 Summary 16

    3.2 Recorder components 17

    3.2.1 Housing 17

    3.2.2 Measuring module 17

    3.2.3 Central processing unit 18

    3.2.4 Power supply 18

    3.2.4.1 AC 230V or AC 115V 18

    3.2.4.2 DC 24V 183.2.4.3 AC 24V 18

    3.2.5 Chassis 19

    3.2.5.1 Chassis support 19

    3.2.5.2 Control PCB 19

    3.2.5.3 Clock backup 19

    3.2.5.4 Recording system 19

    3.2.5.5 Chart carriage 19

    3.2.5.6 User interface 19

    3.3 Mode of operation 21

    3.4 Scope of delivery 21

    3.5 Accessories, consumable materials 21

    3.6 Options 21

    3.6.1 Digital input/ output 21

    3.6.2 DC 24V output 22

    4 PREPARATION FOR OPERATION 22

    4.1 Recorder identification 22

    4.1.1 Rating plate 22

    4.1.2 Object version 22

    4.1.3 Module release version 23

    4.1.4 Firmware version 23

  • 7/27/2019 I9-089B R30 R40

    5/124

    Page 5

    4.2 Installation guidelines 25

    4.3 Mechanical preparation of recorder for operation 26

    4.4 Connection of power supply 26

    4.4.1 Connection to ac 230V or ac 115V 27

    4.4.2 Connection to ac 24V or dc 24V 27

    4.4.3 Selection of 50/ 60Hz 284.5 Connection of analog channels 28

    4.5.1 Labels 31

    4.5.2 DC U 31

    4.5.3 DC I 31

    4.5.5 Direct thermocouple connection 31

    4.5.6 Indirect thermocouple connection, constant cold junction temperature 32

    4.5.7 Indirect thermocouple connection, variable cold junction temperature 32

    4.5.8 RTD, R 33

    4.5.9 Two-wire measurement of thermoelectric resistance and standard resistance 33

    4.5.10 Three-wire measurement of thermoelectric resistance and standard resistance 334.5.11 Three-wire measurement of potentiometers 34

    4.6 Digital input/ output 34

    4.7 DC 24V output 37

    4.8 Starting up the recorder 38

    5 OPERATION 38

    5.1 Display and control elements 39

    5.2 Display elements 40

    5.3 Levers 40

    5.3.1 Functions of service lever and lever 2 41

    5.3.1.1 Service lever Releasing the chassis 415.3.1.2 Lever 2 Releasing the chart carriage 41

    5.3.2 Functions of Levers 1, 3 and 4 in recording mode 41

    5.3.2.1 Lever 1 Zero adjustment 41

    5.3.2.2 Lever 1 PAUSE ON 42

    5.3.2.3 Lever 3 PROG menu ON 42

    5.3.2.4 Lever 3 42

    5.3.2.5 Lever 4 TEST menu ON 42

    5.3.3 Functions of Levers 1, 3 and 4 in the PAUSE status 43

    5.3.3.1 Lever 1 PAUSE OFF 43

    5.3.3.2 Lever 3 PROG menu ON 435.3.3.3 Lever 3 Chart feed 43

    5.3.3.4 Lever 4 TEST menu ON 43

    5.3.4 Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu 44

    5.3.4.1 Lever 1 DEC 44

    5.3.4.2 Lever 1 INC 44

    5.3.4.3 Lever 3 PROG menu OFF 44

    5.3.4.4 Lever 3 ENTER 44

    5.3.4.5 Lever 4 44

    5.3.5 Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu 45

    5.3.5.1 Lever 1 DEC 45

  • 7/27/2019 I9-089B R30 R40

    6/124

    Page 6

    5.3.5.4 Lever 3 ENTER 45

    5.3.5.5 Lever 4 TEST menu OFF 45

    5.4 Settings via PROG menu 46

    5.4.1.1 P[0], P[10] Chart speeds A, B 47

    5.4.1.2 P[5], P[15] Condition 47

    5.4.1.3 Event-dependent chart speed 485.4.1.5 Example 49

    5.4.2 Measured-value table (only R40 version) 49

    5.4.2.1 P[20] Measured-value table 49

    5.4.2.2 Printing the measured-value table 49

    5.4.3 Parameterizing the Analog Channels 50

    5.4.3.1 P[25] Analog channel 50

    5.4.3.2 P[30] Mode 51

    5.4.3.3 P[35] Measuring range 52

    5.4.3.4 P[40] Sensor 52

    5.4.3.6 TC 535.4.3.7 RTD, R, Pot. 53

    5.4.3.9 P[60] Open-circuit 57

    5.4.3.10P[65] Damping 57

    5.4.4 Parameterizing the digital channel (only R40 version) 58

    5.4.4.1 P[70] Channel (digital) 58

    5.4.5 Alarm 59

    5.4.5.1 P[80] Alarm 59

    5.4.5.2 P[85] Mode 59

    5.4.5.3 P[90] Channel 60

    5.4.5.4 P[95] Value 605.4.6 Print (only R40 version) 61

    5.5 Settings using TEST menu 61

    5.5.1 Measuring mode 62

    5.5.1.1 T[0] Measuring mode 62

    5.5.2 Diagram 63

    5.5.2.1 T[5] Diagram (only R40 version) 63

    5.5.2.2 Start line (only R40 version) 63

    5.5.2.3 T[10] Cycle 64

    5.5.2.4 Time marker 64

    5.5.2.5 T[15] Grid (only R40 version) 645.5.3 Text (only R40 version) 65

    5.5.3.1 T[20] Text, T[25] Editing, T[30] Condition 65

    5.5.3.2 Programming text 65

    5.5.3.3 Instrument text 66

    5.5.3.4 Event text 66

    5.5.4 Clock (only R40 version) 66

    5.5.4.1 T[35] Clock: Mode, T[40] Hours: hh, T[45] Minutes: mm, T[50] Day: DD, T[55]Month: MM, T[60] Year: YY 66

    5.5.5 Control input DI4 67

    5.5.5.1 T[65] Control input DI4 67

  • 7/27/2019 I9-089B R30 R40

    7/124

    Page 7

    5.5.5.2 Chart feed 67

    5.5.5.3 Time marker 68

    5.5.5.4 Clock sync. 3:00 (only R40 version) 68

    5.5.5.5 Summer time (MESZ) (only R40 version) 68

    5.5.5.6 TEST locking 68

    5.5.6 Language (only R40 version) 695.5.6.1 T[70] Language 69

    5.5.7 PROG Locking 69

    5.5.7.1 T[75] PROG locking 69

    5.6 Parameterization examples 70

    5.6.1 Setting the chart speed 70

    5.6.2 Setting the output of the measured-value table 71

    5.6.3 Parameterizing the analog channel 71

    5.6.4 Parameterizing the digital channel 74

    5.6.5 Parameterizing the alarms 74

    5.6.6 Parameterizing the measuring mode 755.6.7 Parameterizing the diagram (only R40 version) 76

    5.6.8 Parameterizing texts (only R40 version) 76

    5.6.9 Parameterizing the time 78

    5.6.10 Parameterizing the control input DI4 80

    5.6.11 Parameterizing the language (only R40 version) 80

    5.6.12 Parameterizing the PROG locking 81

    6 MEASURING AND RECORDING MODE 81

    6.1 Chart formatting (only R40 version) 81

    6.1.1 Main time line (only R40 version) 82

    6.1.2 Instrument text (only R40 version) 826.1.3 Switch-on text (only R40 version) 82

    6.1.4 Event text (only R40 version) 82

    6.1.5 Start line (only R40 version) 83

    6.1.6 Time markers (only R40 version) 83

    6.1.7 Limit line and alarm markers (only R40 version) 83

    6.1.8 Measured-value table (R40 version) 84

    6.1.9 Grid (only R40 version) 84

    6.1.10 Priorities of text outputs 85

    6.1.11 Configuration data (only R40 version) 85

    6.1.12 Error messages and Status messages (only R40 version) 876.2 Example recording with explanations 87

    7 SERVICING AND MAINTENANCE 89

    7.1 Removing the chart carriage 89

    7.2 Inserting the chart carriage 90

    7.3 Setting the main time line 90

    7.4 Removing a fanfold pack 91

    7.5 Inserting a fanfold pack 91

    7.6 Removing a chart roll 92

    7.7 Inserting a chart roll 93

  • 7/27/2019 I9-089B R30 R40

    8/124

    Page 8

    7.8 Moving chassis into maintenance position 95

    7.9 Returning chassis from maintenance position 96

    7.10 Removing chassis from housing 96

    7.11 Inserting chassis into housing 97

    7.12 Removing the guide tongue 97

    7.13 Inserting the guide tongue 987.14 Labelling and inserting the measuring-point label 98

    7.15 Replacing the pens for the analog channels 98

    7.16 Replacing the pen for alphanumeric text (only R40 version) 99

    7.17 Replacing the scale 99

    7.18 Replacing the battery (only R40 version) 99

    7.19 Adjustment, test prints, carriage/ text positions 100

    7.19.1 Adjustment 100

    7.19.1.1T[80] Adjustment: Range, T[85] Channel 100

    7.19.2 Carrying out the adjustment 102

    7.19.3 Test print 1027.19.3.1T[90] Test print 102

    7.19.4 Maintenance 104

    7.19.4.1T[95] Maintenance 104

    7.19.4.2Setting example for text channel 105

    7.19.5 Service 105

    7.19.5.1T[100] Service 105

    8 TECHNICAL DATA 106

    Measuring functions general data 106

    R30 version 107

    R40 version 1088.1 Operation, displays 110

    8.2 Recording 110

    8.3 Digital input/ output (option) 111

    8.4 DC 24V output (option) 112

    8.5 Power supply 112

    8.6 Ambient conditions 112

    8.7 Mounting position 112

    8.8 Degree of protection 112

    8.9 Electric safety 112

    8.10 Electromagnetic compatibility 1138.11 Dimensions, mounting 114

    8.12 Weight 114

    8.13 Explanation of error data 114

    9 SCOPE OF DELIVERY, OPTIONS, ACCESSORIES 116

    9.1 Scope of delivery 116

    9.2 Available accessories and consumable material 117

    9.3 Available options 118

    REPAIR FORM 119

  • 7/27/2019 I9-089B R30 R40

    9/124

    Page 9

    SAFETY SECTION

    This Safety Section should be rea d be fore commencing a ny w ork on the equipm ent.

    Health and safety

    The information in the Safety Section of the product documentation is intended toensure that products are properly installed and handled in order to maintain them ina safe condition. It is assumed that everyone who will be associated with theequipment will be familiar with the contents of the Safety Section.

    Explanation of symbols and labels

    The meaning of symbols and labels which may be used on the equipment or in theproduct documentation, is given below.

    Caution: refer to product documentation Caution: risk of electric shock

    Protective/ safety *earth terminal

    Functional *earth terminal.

    Note: this symbol may also be used for a protective/safety earth terminal if that terminal is part of a

    terminal block or sub-assembly eg. power supply.

    *Note: The term earth used throughout the product documentation is the direct equivalent of

    the North American term ground.

    Installing, Commissioning and Servicing

    Equipment connections

    Personnel undertaking installation, commissioning or servicing work on this

    equipment should be aware of the correct working procedures to ensure safety.The product documentation should be consulted before installing, commissioning orservicing the equipment.

    Terminals exposed during installation, commissioning and maintenance may presenta hazardous voltage unless the equipment is electrically isolated.

    If there is unlocked access to the rear of the equipment, care should be taken by allpersonnel to avoid electric shock or energy hazards.

    Voltage and current connections should be made using insulated crimp terminationsto ensure that terminal block insulation requirements are maintained for safety. Toensure that wires are correctly terminated, the correct crimp terminal and tool for the

    wire size should be used.

  • 7/27/2019 I9-089B R30 R40

    10/124

    Page 10

    Before energising the equipment it must be earthed using the protective earthterminal, or the appropriate termination of the supply plug in the case of plugconnected equipment. Omitting or disconnecting the equipment earth may cause asafety hazard.

    The recommended minimum earth wire size is 2.5 mm2, unless otherwise stated in

    the technical data section of the product documentation.Before energising the equipment, the following should be checked:

    Voltage rating and polarity;

    CT circuit rating and integrity of connections;

    Protective fuse rating;

    Integrity of earth connection (where applicable)

    Equipment operating conditions

    The equipment should be operated within the specified electrical and environmentallimits.

    Current transformer circuits

    Do not open the secondary circuit of a live CT since the high voltage producedmay be lethal to personnel and could damage insulation.

    External resistors

    Where external resistors are fitted, these may present a risk of electric shock orburns, if touched.

    Battery replacement

    Where internal batteries are fitted they should be replaced with the recommendedtype and be installed with the correct polarity, to avoid possible damage to theequipment.

    Insulation and dielectric strength testing

    Insulation testing may leave capacitors charged up to a hazardous voltage. At theend of each part of the test, the voltage should be gradually reduced to zero, todischarge capacitors, before the test leads are disconnected.

    Insertion of modules and pcb cards

    These must not be inserted into or withdrawn from equipment whilst it is energised,since this may result in damage.

    Fibre optic communication

    Where fibre optic communication devices are fitted, these should not be vieweddirectly. Optical power meters should be used to determine the operation or signallevel of the device.

  • 7/27/2019 I9-089B R30 R40

    11/124

    Page 11

    Decommissioning and Disposal

    Decommissioning: The auxiliary supply circuit in the relay may include capacitorsacross the supply or to earth. To avoid electric shock or energyhazards, after completely isolating the supplies to the relay(both poles of any dc supply), the capacitors should be safelydischarged via the external terminals prior to decommissioning.

    Disposal: It is recommended that incineration and disposal to watercourses is avoided. The product should be disposed of in a safemanner. Any products containing batteries should have themremoved before disposal, taking precautions to avoid shortcircuits. Particular regulations within the country of operation,may apply to the disposal of lithium batteries.

  • 7/27/2019 I9-089B R30 R40

    12/124

    Page 12

    Section 1. INTRODUCTION

    1.1 General information

    This Manual contains the information required for approved use of the productsdescribed in it. It is directed at technically qualified personnel who are speciallytrained or have appropriate knowledge in the field of instrumentation and control,referred to below as automation technology

    Knowledge of the safety information and warnings present in this Manual and theirtechnically correct application are requirements for safe installation andcommissioning as well as safe operation and repair of the described products.Only qualified personnel in the sense of Section 1.2 have the required specialistknowledge in order to correctly interpret the general safety information and warningspresent in this document for a specific case, and to apply them appropriately.

    For organizational reasons, this Manual must be ordered separately. For clarityreasons, the manual does not cover all details on all types of the described products,

    and cannot describe every possible case in connection with installation, operation ormaintenance. Should you require further information, or should particular problemsoccur which are not handled in sufficient depth in this Manual, help can be requestedthrough your local ALSTOM T&D Protection & Control office or representative.

    Your attention is additionally drawn to the fact that the contents of this InstructionManual are not part of a previous or existing agreement, commitment or statutoryright and do not change these. All commitments on the part of ALSTOM T&DProtection & Control are contained in the respective sales contract which alsocontains the complete and solely applicable warranty conditions. These warrantyconditions in the contract are neither extended nor limited by the contents of thisManual.

    1.2 Qualified person

    Unqualified interventions in the devices or the non-observance of the warningspresent in this Manual or on the devices may lead to severe personal injury ordamage to property. Therefore only suitably qualified personnel may work on thesedevices:

    q Configuring personnel familiar with the safety concepts of automation technology

    q Operating personnel instructed in the handling of equipment for automationtechnology and acquainted with the contents of this Manual which are importantfor operation

    q

    Commissioning and servicing personnel who are trained to repair suchautomation technology equipment or who are authorized to energize, earth andtag circuits and devices in accordance with established safety practices.

    1.3 Warning information

    Warning information with the following meanings is used in this Instruction Manualand in the warning information on the products:

    Danger

    means that death, severe personal injury or substantial damage to property will occurif the appropriate safety precautions are not observed.

  • 7/27/2019 I9-089B R30 R40

    13/124

    Page 13

    Warning

    means that death, severe personal injury or substantial damage to property can occurif the appropriate safety precautions are not observed.

    Caution

    means that slight personal injury or damage to property can occur if the appropriatesafety precautions are not observed.

    Note: is important information on the product, its handling or the respective part ofthe documentation to which particular attention should be paid.

    1.4 Approved use

    q The devices must only be used for applications described in the Catalog and theInstruction Manual, and only in conjunction with other devices and componentsrecommended by or approved of by ALSTOM T&D Protection & Control.

    q The products have been developed, manufactured, tested and documented in

    accordance with the appropriate safety standards. If the handling guidelines andsafety information are observed during configuring, assembly, approved use andmaintenance, the products do not therefore present a danger in the normal casewith respect to property or the health of persons.

    Warning

    q Following removal of the housing or the guard, certain parts of these devices areaccessible which may carry dangerous voltages.

    q Only suitably qualified personnel should work on these devices.

    q These should be thoroughly familiar with all sources of danger and maintenancemeasures according to the information in this Manual.

    q Correct and safe operation of the products is dependent on proper transport,storage, installation and assembly as well as careful operation and maintenance.

    Documentation

    In addition to this Instruction Manual - which can be used by all target groups - thefollowing relevant technical documentation is also available for the devices:

    q Leaflet "Parameterization a concise overview".Explains in visual form the basic operation and parameterization as well as thePROG and TEST menus. Target group: configuring and maintenance personnel.

  • 7/27/2019 I9-089B R30 R40

    14/124

    Page 14

    Section 2. APPLICATION

    2.1 Purpose

    The devices

    q line recorder, referred to below as R30 version, andq line recorder with alphanumeric output, referred to below as R40 version,

    can be used to measure, record and monitor analog and digital values.

    2.2 Standard

    The recorders can be used to cyclically measure the following variables :

    q DC voltage (DC U)

    q direct current (DC I)

    and also with the R40 version

    q thermocouple connection (TC)q thermoelectric resistance, resistance and potentiometer connection (RTD, R)

    to process these and to document them on chart paper. As a result of the short cycletime, the recorders are also suitable for recording fast, dynamic process parameters.

    Even when delivered according to customer-specific requirements, the recorders canstill be subsequently and easily adapted to requirements within the input, measuringand recording ranges.

    The recorders can be equipped with up to three coloured pens for the analogrecording of measured values connected via channels #1 to #3.

    The R40 version has an additional pen for a text channel for the output ofalphanumeric characters and the recording of up to two digital channels d#1 andd#2.

    The recorder functions can be set manually using levers.

    2.3 Designs

    The recorders vary with respect to their recording systems, measuring ranges andpower supplies:

    q R30 version: no alphanumeric text

    q R40 version: with alphanumeric text

    q Standard measuring rangesq Universal measuring ranges

    q Power supply ac 230V

    q Power supply ac 115V

    q Power supply ac 24V

    q Power supply dc 24V

  • 7/27/2019 I9-089B R30 R40

    15/124

    Page 15

    2.4 Options

    The recorders can be equipped with the following options:

    q Digital input/ output

    q DC 24V output

    The Digital input/ output provides four inputs (DI1 to DI4) for control functions andsix outputs (DO1 to DO6) for alarms, status signals or control signals. The inputs andoutputs are electrically isolated from the recorder circuits. Two different outputs canbe selected:

    q Digital input/ output, electronic version with semiconductors

    or

    q Digital input/ output, relay version with changeover contacts.

    The option DC 24V output provides a power output for external devices or optionsto a limited extent such as eg. a transmitter or digital input/ output.

    Design R30 version R40 version

    Recording

    Alphanumeric q

    Measuring ranges

    Standard q

    Universal q

    Power supply

    AC 230V or q q

    AC 115V or q q

    AC 24V or q q

    DC 24V q q

    Options

    Digital input/ output, electronic v v

    Digital input/ output, relay v v

    DC 24V output v v

    q Included in standard delivery v Possible options

    Table 1 Summary of recorder versions and options

    2.5 Delivery

    The recorders are delivered as standard designs, or manufactured, parameterizedand prepared for operation in the factory according to the customers order.

    2.6 Conversion

    Conversions to the recorders such as eg. changing the power supply or subsequentlyinstalling options must only be carried out by the certified servicing department.

    2.7 Environmental protection

    Only environmentally-friendly materials have been used for the packaging system of

    the recorders.

  • 7/27/2019 I9-089B R30 R40

    16/124

    Page 16

    Section 3. DESIGN AND MODE OF OPERATION

    The following chapter describes the mechanical and electrical design as well as therecorder components.

    3.1 Summary

    The recorders are designed as panel mounted instruments with a format 144 mm x144 mm.

    Installation without interspacing is possible in panels and mosaic systems withsufficient ventilation.

    The modern recorders have digital data processing. Measured values are recordedserially in channels and with solid state technology.

    As a result of the exclusive use of step motors, the drive system for recording operatescompletely without contacts. This technology permits a wide range of applicationsand high functional reliability.

    Fig. 1 and Fig. 2 show views of the recorder. The mode of operation of the recordersis explained down to the block diagram level using Fig. 3.

    1. Door 4. (Not used)

    2. Chart carriage 5. LEDs

    3. Levers 6. Visual operating aids

    Fig. 1 Front view of R30, R40 versions

  • 7/27/2019 I9-089B R30 R40

    17/124

    Page 17

    1. Earth connection 5 Connection of power supply

    2. Terminals for dc 24V output 6. Fuse F2

    3. Connection of digital input/ output 7. Window of measuring point allocations

    4. (Not used) 8. Input terminals

    Fig. 2 Rear view of R40 version (ac 115/ 230V design)

    3.2 Recorder components

    3.2.1 Housing

    The housing is made of sheet-steel. The chassis and the chart carriage are present at

    the front; the measuring module, the central processing unit, parts of the powersupply and the options are located at the rear. The housing is mounted in the panel,mosaic system or desk upright panel using the supplied, standardized mountingelements.

    3.2.2 Measuring module

    The measuring module has up to three channels, a multiplexer with semiconductorrelays and an analog-to-digital converter. The input ranges are set specifically foreach channel using jumpers. The channels are electrically isolated from one anotherby staggered control of the semiconductor relays.

    Control is handled by the central processing unit. All channels to be measured during

    a cycle are connected to the input amplifier in succession via the individual

  • 7/27/2019 I9-089B R30 R40

    18/124

    Page 18

    semiconductor relays. The amplified signal is applied to an analog-to-digitalconverter which operates according to the dual-slope procedure.

    In order to permit equally accurate measurements in sensitive ranges, referencemeasurements are carried out cyclically in the recorder version with universalmeasuring ranges. A cyclic check is also carried out for open-circuits.

    The terminal block also contains a sensor for measuring the terminal temperaturewhen carrying out temperature measurements using thermocouples.

    3.2.3 Central processing unit

    The central processing unit is the heart of the electronics. It contains a microprocessoras well as the program memory (EPROM), main memory (RAM) and non-volatilememory (EEPROM) for configuration data.

    Central component of the processing section is a microprocessor system withfirmware. This is used, inter alia, for:

    q Sequence control

    q Calculation of measured values

    q Positioning of pen assemblies

    q Evaluation of input commands

    q Use of PC interface.

    The central processing unit permits control of the module Digital input/ output.

    A crystal-controlled calendar/ clock with external synchronization facility provides thedate and time as a reference for sets of measured values and the chart.

    The central processing unit is located at the rear of the housing and is accessiblefrom the front following removal of the chassis. It contains the plugs for connection of

    the other modules.

    3.2.4 Power supply

    The recorders have different designs on the input side as a result of the four differentpower supplies which can be ordered.

    3.2.4.1 AC 230V orAC 115V

    The mains power supply is connected to the recorder via an appliance plug withsubsequent fuses, filter and transformer. The stepped down ac voltage is rectified,filtered and applied to dc/ dc converters which generate the required internal dcvoltages.

    Note: The recorder must only be connected to the envisaged power supply.Observe the corresponding note on the rear of the recorder.

    3.2.4.2 DC 24V

    The dc 24V supply connected via the terminals is applied via a fuse to a powerinverter whose output is connected to a transformer. The secondary side of thetransformer is connected as in the recorder version with a mains power supply.

    3.2.4.3 AC 24V

    The ac 24V supply connected via the terminals is applied via a fuse to the primaryside of the transformer. The secondary side is connected as in the recorder versionwith a mains power supply.

  • 7/27/2019 I9-089B R30 R40

    19/124

    Page 19

    3.2.5 Chassis

    The chassis contains the chassis support, control PCB, recording system, userinterface, PC interface and chart carriage. The chassis is connected to the centralprocessing unit via a multi-conductor ribbon cable with plug. The cable length is suchthat the chassis can be completely removed from the housing without loosening the

    connection.3.2.5.1 Chassis support

    This is the support for the motors of the recording system, the control PCB, userinterface and PC interface. The chart carriage latches into the chassis support andcan be removed at any time using lever 2, eg. to replace the chart.

    3.2.5.2 Control PCB

    The control PCB contains the power electronics for the step motors of the drives aswell as the light barrier for detection of the carriage zero points. It also contains amicroswitch for recognizing the end of the chart paper, and several microswitcheswhich are activated using the levers.

    3.2.5.3 Clock backup

    Only R40 version: the clock backup consists of a backup battery and capacitor. If abattery is not present, or if the chassis is separated from the central processing unit,the capacitor buffers the internal clock for approx. 5 minutes. The status of the clockbuffer is checked when the power supply is switched on.

    The support for the backup battery is present on the control PCB and accessiblefollowing removal of the chassis.

    3.2.5.4 Recording system

    The recording system consists of up to seven step motors depending on the recorder

    version. These are used for:q Chart drive

    q Positioning of the three coloured pens in the xdirection

    q Pen lift

    q R40 version: positioning of pen for text channel in x and ydirections

    3.2.5.5 Chart carriage

    The chart carriage permits fanfold packs or rolls to be used as the chart paper.A take-up spool is required when using rolls. In addition, the chart carriage must beadapted when changing from fanfold paper to rolls. The required operations are

    described in Section 7 Servicing and Maintenance.

    3.2.5.6 User interface

    The user interface consists of four levers and two LEDs underneath the chart carriage.A further lever is present on the side of the chassis and is only visible when thechassis is in maintenance position.

    Mechanical operations are directly activated by two of the four levers underneath thechart carriage. The other two levers can be used for two different actions each bymoving the respective lever to the left or right. The TEST menu can be activated andswitched off again using the switch which is accessible on the side of the chassis.

    Green and red LEDs indicate different recorder statuses depending on how they areactivated (on, off, flashing).

  • 7/27/2019 I9-089B R30 R40

    20/124

    Page 20

    Fig. 3 Block diagram of R30, R40 versions

    Measuring module

    Only R40 version

    Recording system for33 analog channels

    and 2 digital channels

    2x

    5x

  • 7/27/2019 I9-089B R30 R40

    21/124

    Page 21

    3.3 Mode of operation

    As a result of the many different possible uses, the recorders are delivered preset tothe basic setting of 4 to 20mA.

    Customer-specific presetting is also possible as required. The recorder can then beused immediately following installation and commissioning.

    The values measured cyclically by the recorder are amplified, digitized andprocessed further by a microprocessor system.

    In addition to processing of the measured values, the microprocessor system isresponsible for sequence control, self-test, event processing, control of the step motorsof the recording system, feedbacks from the recording system and the user interface.

    The microprocessor system converts the measured value into positioning commandsfor the recording system. The pens draw a continuous line on the chart paperaccording to the measured signal. You can adjust the measuring and recordingranges such that the signal is recorded with an optimum resolution and display.It is also possible to define limits which are constantly recorded in the R40 version as

    vertical lines. The recorders can output an alarm text if the limit is violated.The number of limits and the alarm function can be parameterized within wideranges. If the recorder is equipped with the digital input/ output option, the alarmscan be output for further processing.

    The R40 version can output a measured-value table, event text and recorder textcyclically or event-controlled. The texts must be entered previously via the user whensetting up the recorder. The outputs are made depending on the recorder parameters.

    3.4 Scope of delivery

    The scope of delivery is listed in Section 9.1.

    3.5 Accessories, consumable materials

    The accessories and consumable materials are listed in Section 9.2.

    3.6 Options

    The following options are available:

    q Digital input/ output with 4 inputs and 6 outputs

    q DC 24V output

    3.6.1 Digital input/ output

    The input signals (DI1 to DI4) of the four digital inputs are applied to the basicelectronics via opto isolators and processed further on the central processing unit.

    The output signals (DO1 to DO6) of the digital outputs are externally available at theinterface electrically isolated either via opto isolators orrelays depending on theversion.

    q Electronic version: the output signals are generated by short-circuit-resistantsemiconductor switches. The switches are controlled via opto isolators.

    The semiconductor switches must be powered via an external voltage source sincethey are electrically isolated from the basic device.

    q Relay version: the electrical isolation is provided by relays whose changeovercontacts are externally available.

  • 7/27/2019 I9-089B R30 R40

    22/124

    Page 22

    3.6.2 DC 24V output

    The dc 24V output option can be used for the following purposes:

    q Power supply to external transmitters

    q Power supply to digital input/ output, electronic version

    The dc 24V output module is powered by the rectified and filtered internal dcvoltage. The floating output is available as a bipolar terminal on the rear of therecorder. Refer to Section 9.2 for the ordering data.

    Section 4. PREPARATION FOR OPERATION

    The following chapter describes all preparations necessary for operation of therecorders.

    4.1 Recorder identification

    The recorders and modules can be identified with respect to their application and

    release version by means of various labels:

    q Rating plate with object version for recorder

    q Part No. with release version for modules

    4.1.1 Rating plate

    The rating plate (Fig. 4) provides information on:

    q Recorder type

    q Serial number

    q Object version

    q Channel assignments (only rating plate on rear).

    There are three rating plates on the recorder:

    q On the rear (eg. Fig. 8),

    q On the left inside the housing (visible after removing the chassis),

    q On the left side of the chassis (eg Fig. 63)

    If the input ranges are changed, a blank label can be inscribed using a water-resistant felt pen and adhered to the part of the rating plate which is no longer valid.

    4.1.2 Object version

    The object version (Fig. 4) of the recorder can be read from the rating plate.The digit marked with a cross identifies the hardware release of the recorder.The Instruction Manual references the object version. This Manual is valid for theobject version 1 shown in Fig. 4.

  • 7/27/2019 I9-089B R30 R40

    23/124

    Page 23

    Fig. 4 Example of rating plate for R40 version

    4.1.3 Module release version

    The release version (Fig. 5) documents the hardware release of modules. The releaseversion is indicated on the following relevant modules:

    q Central processing unit with power supply (bottom right, visible following removalof chassis)

    q Chassis (bottom right, visible following removal of chassis)

    Record the release version of the modules in your instrument passport so that you canpass this information on to the servicing department if necessary.

    Fig. 5 Release version (example)

    4.1.4 Firmware version

    The release version of the firmware can be read on a label adhered to the EPROM.

    The release version can be read on the EPROM label following removal of thechassis.

    The Instruction Manual references the firmware release. This Manual is valid for the

    release version shown in Fig. 6.Record the release version of the firmware in your instrument passport so that you canpass this information on to the servicing department if necessary.

    1 2 3 4 5 6 7 8 9 10 11

    Line Recorder DC U/ISerial No H6-966

    X 2 3 4 5 6 7 5 9 10 11

    CHANNEL

    1: 4....20mA

    2: 4....20mA

    3: 4....20mA

    Made in France

  • 7/27/2019 I9-089B R30 R40

    24/124

    Page 24

    Fig. 6 Positions of EPROM and jumper for 50/ 60Hz on moduleCentral processing unit

    1 Cut-out prepared for digital input/ output

    2 Fuse F13 Power supply connection

    4 Grip for cable detensioning

    5 Window with channel inscriptions for setting of input ranges(design for standard measuring ranges)

    6 Input terminals

    7 Cut-out prepared for dc 24V output

    Fig. 7 Rear view of R30 version (dc 24V design)

    DC24V81+82

    1

    2

    2

    3

    4

    5

    6

  • 7/27/2019 I9-089B R30 R40

    25/124

    Page 25

    1 Earth connection

    2 DC 24V output (option)

    3 Digital input/ output (option)

    4 Transformer with rating plate

    5 Fuse F1

    6 Power supply connection with mains supply

    7 Fuse F2

    8 Window with channel inscriptions for setting of input ranges(design for universal measuring ranges)

    9 Input terminals for channel #1 bis #3

    Fig. 8 Rear view of R40 version (ac 115/ 230V design)

    4.2 Installation guidelines

    Insert the recorder into the prepared panel cut-out (see Fig. 9 for dimensions), inserttwo clamps into the corresponding positions on the housing, and tighten the screws.Special clamps must be used when fitting in a 72mm mosaic system.

    The permissible ambient temperature according to the technical data must beobserved at the mounting position. This must be particularly observed when installingwithout interspacing.

    Note When installing, observe the safety guidelines in Section 1.

    The following information is generally applicable to installation:

    q No special requirements are placed on power supply, measuring and controlcables which do not carry a dangerous contact potential.

    q Voltages which are not dangerous to contact are up to dc 50V or ac 25V if theyare generated by safety transformers, batteries etc. and are not connected to

    other circuits (low-voltage networks with safe isolation).

    3

    2

    1

    2

    6

    7

    8

    9

  • 7/27/2019 I9-089B R30 R40

    26/124

    Page 26

    q The isolation of power cables with a dangerous contact potential must be selectedaccording to the max. voltage.

    q The cross-section of the protective earth conductor must be selected at least aslarge as the largest cross-section of the power cable.

    q The connection between the protective earth connection and the protective earth

    conductor must be made before any other connections.

    Fig. 9 Dimensions for installation of R30, R40 versions

    4.3 Mechanical preparation of recorder for operation

    Note Only use recorders with the scales and pens fitted.

    The following points refer to the mechanical preparation of the recorders, and mustbe carried out in the defined sequence prior to starting up:

    1. Remove chart carriage (Section 7.1)

    2. Insert recording system (Section 7.15)

    3. Insert roll or fanfold pack (Section 7.7, Section 7.5)

    4. Insert chart carriage (Section 7.2)

    4.4 Connection of power supply

    Depending on the recorder design, the connection is for

    q AC 230V or

    q AC 115V or

    q AC 24V or

    q DC 24V.

  • 7/27/2019 I9-089B R30 R40

    27/124

    Page 27

    Before connecting, check that the technical data (Fig. 10) for the power supply asspecified by the manufacturer on the recorder agrees with the data of the powersupply to be connected.

    Note The data for the power supply must lie within the values specified for thisdesign in the technical data.

    Fig. 10 Power supply information on recorder

    4.4.1 Connection to ac 230V or ac 115V

    The connection to an ac 230V mains supply is made using the supplied applianceplug. The correct connection for ac 230V and ac 115V is identical and shown inFig. 11.

    Fig. 11 Connection of mains supply

    4.4.2 Connection to ac 24V or dc 24V

    The connection inscriptions depend on the recorder design. The connection must bemade to the provided screw terminals according to the defined inscriptions.

    The cable must be secured using a grip to reduce the strain (Fig. 12).

    F1 =F2 =T0, 125/250C

  • 7/27/2019 I9-089B R30 R40

    28/124

    Page 28

    Fig. 12 Connection of ac 24V or dc 24V

    4.4.3 Selection of 50/ 60Hz

    The measured values are recorded according to an integrated measuring procedure.In order to suppress interferences (hum), the measuring period (integration time) mustbe matched to the mains frequency. The basic setting is 50Hz.

    The setting can be changed using a jumper on the module "Central processing unit"(Fig. 6). If the recorder is powered via a dc supply, the frequency of the surroundingac supply must be set.

    The chassis must be removed from the housing in order to check or change thejumper setting (Section 7.10).

    4.5 Connection of analog channels

    The following types of measurement are possible for each channel:

    q DC U or

    q DC I or

    q TC (only recorder design with universal measuring ranges) or

    q RTD, R (only recorder design with universal measuring ranges)

    The type of measurement is set using jumpers.

    In order to set the jumpers, you must first remove the window for setting the inputranges (Fig. 13). The transparent plastic part can be easily removed by inserting asmall screwdriver at the side.

    Fig. 13 Connection of analog channels #1 to #3 to recorder design with universal

    measuring range

    Earth Earth

  • 7/27/2019 I9-089B R30 R40

    29/124

    Page 29

    Jumper positions Input ranges Measuring ranges

    Direct connection TC/ RTD/ R/ Pot./ U(only recorder withuniversal range)

    1V DC U0/ 1V0.2/ 1V1V

    10V DC U0/ 10V2/ 10V10V

    20mA DC I0/ 20mA

    4/ 20mA20mA

    Fig. 14 Jumper settings

    Fig. 15 Basic connections for channel inputs with R30 version

  • 7/27/2019 I9-089B R30 R40

    30/124

    Page 30

    Fig. 16 Basic connections for channel inputs with R40 version

  • 7/27/2019 I9-089B R30 R40

    31/124

    Page 31

    4.5.1 Labels

    A label with information (Fig. 17 or Fig. 18) on the possible connections of theanalog channels is adhered on the transformer (Fig. 8 or Fig. 7) above the windowfor setting the input ranges.

    Fig. 17 Possible connections for analog channels in design with standardmeasuring ranges

    4.5.2 DC U

    The connection is made according to Fig. 17 and the jumper settings according toFig. 14. The parameters are set according to Section 5.5.3.

    4.5.3 DC I

    The connection is made according to Fig. 17 and the jumper settings according toFig. 14. The parameters are set according to Section 5.5.3.

    Fig. 18 Label with information on the possible connections for the analog channelsin design with universal measuring range

    4.5.4 TC

    Thermocouples can be connected as follows:

    q Directly with an internal cold junction

    q Indirectly with an external cold junction at constant temperatureq Indirectly with an external cold junction at any temperature

    The basic connections are shown in the following Figs. The jumpers of the inputchannels are set according to Fig.14 and the parameters according to Section 5.5.3.

    4.5.5 Direct thermocouple connection

    (Internal cold junction)

    The connections of the thermocouples or the associated equalizing conductors mustbe connected directly to the recorder terminals. The temperature of the terminal block(reference temperature) is measured by the recorder and compensated.

    The connection is made as in Fig. 19.

  • 7/27/2019 I9-089B R30 R40

    32/124

    Page 32

    Fig. 19 Thermocouple connection

    4.5.6 Indirect thermocouple connection, constant cold junction temperature

    (External cold junction at constant temperature)

    The connections of the thermocouple are connected via a cold junction, eg.thermostat. The temperature of the cold junction must be entered. The cables betweenthe external cold junction and the recorder terminals can be made using anyconductors with the same material (usually Cu). The connection is made according to

    Fig. 18.

    Fig. 20 Thermocouple connection to external cold junction at constant temperature

    4.5.7 Indirect thermocouple connection, variable cold junction temperature

    (External cold junction at variable temperature)

    The connections of the thermocouple are connected via a cold junction at anytemperature. The temperature of the cold junction must be measured using anotherchannel and is calculated internally. Thermocouples as well as resistancethermometers are possible for recording the cold junction temperature.

    The connection is made according to Fig. 21.

    Fig. 21 Thermocouple connection to external cold junction at any temperature

  • 7/27/2019 I9-089B R30 R40

    33/124

    Page 33

    4.5.8 RTD, R

    Thermoelectric resistors as well as standard resistors can be connected as follows:

    q Two-wire measurement

    q Three-wire measurement

    4.5.9 Two-wire measurement of thermoelectric resistance and standard resistance

    This type of connection is preferably selected for a short distance between the sensorand the recorder. It is necessary to either select the cables with such a low resistancethat an error in measurement does not occur (Fig. 22), or they must be adjusted to10 (Fig. 23).

    Fig. 22 Two-wire system without additional line compensation

    Fig. 23 Two-wire connection with line compensation (RA) to 10

    4.5.10 Three-wire measurement of thermoelectric resistance and standard resistance

    This type of connection presupposes that the resistances of the cables between thesensor and terminals 12 and 13 on the recorder are of equal magnitude.

    The connection is made according to Fig. 24.

    Fig. 24 Three-wire system

  • 7/27/2019 I9-089B R30 R40

    34/124

    Page 34

    4.5.11 Three-wire measurement of potentiometers

    The resistances of the three cables between the sensor and the recorder must also beof equal magnitude with this measurement.

    The setting is made according to the Section Selecting the type of connection.Two methods are basically possible.

    1. The cables have such a low resistance that no errors in measurement occur.

    Fig. 25 Connection for potentiometer measurement

    2. The total of the full-range resistance of the potentiometer and the cable resistanceis adjusted to 10 using additional external line compensation.

    Fig. 26 Connection for potentiometer measurement with additional linecompensation (RA2, RA3) to 10

    4.6 Digital input/ output

    A 25-pin subminiature plug (Fig. 8) is present on the rear of the recorder for theoption Digital input/ output. See Section 3.6 for technical details.

    In the electronic version, the semiconductor switches which are isolated from thebasic electronics by opto isolators must be powered by an external 24V supply.If the recorder is equipped with a dc 24V output (option), it is alternatively possible touse this source, taking into account the technical data (Fig. 27).

    A 25-pin subminiature plug for connection of the digital input/ output is included inthe delivery. The pin assignments are shown in Table 2 and Table 3.Parameterization of the digital input/ output is described in Section 5.7.4.

  • 7/27/2019 I9-089B R30 R40

    35/124

    Page 35

    Plug pin Input Parameterizable functions Remarks

    24 Input DI1 Measuring mode normal on/ off Low off, High on

    Measuring mode fast - on/ off Low off, High on

    Measuredvalue table 1) Edge following High outputEvent text 1) Edge following High output

    Digital channel 1) Recording of time characteristic

    12 Input DI2 Chart feed A on Edge following High on

    Chart feed B on Edge following High on, only ifcondition for A is not fulfilled

    Measuredvalue table 1) Edge following High output

    Event text 1) Edge following High output

    Digital channel 1) Recording of time characteristic 2)

    25 Input DI3 Measured-value table 1) Edge following High output

    Event text 1) Edge following High output

    Digital channel 1) Recording of time characteristic 3)

    13 Input DI4 Control input for

    Chart feed 10mm to 100mm Edge following High acc. to feed

    Time marker Edge following High zero adj.

    Clock synchronization 3:00 Edge following Highsynchronization

    Summer time (MESZ) Low MEZ, High MESZ 3)

    TEST locking Low on, High off

    Measured-value table 1) Edge following High output

    Event text 1) Edge following High output

    Digital channel 1) Recording of time characteristic 2)

    11 Reference

    potential0V (DI)

    1) Only R40 version

    2) Max. two channels

    3) MEZ Central European time

    MESZ Central European summer time

    Table 2 Pin assignments Digital input/ output (DI1 to DI4)

  • 7/27/2019 I9-089B R30 R40

    36/124

    Page 36

    Plug pin Assignments for Assignments for

    electronic version relay version

    14 Output DO1 Output DO1: NO contact

    2 Common point

    15 NC contact

    3 Output DO2 Output DO2: NO contact

    16 Common point

    4 NC contact

    17 Output DO3 Output DO3: NO contact

    5 Common point

    18 NC contact

    6 Output DO4 Output DO4: NO contact

    19 Common point

    7 NC contact

    20 Output DO5 Output DO5: NO contact

    8 Common point

    21 NC contact

    9 Output DO6 Output DO6: NO contact

    22 Common point

    10 NC contact

    23 Ext. power supply 24V (DO)

    1 Ext. power supply 0V (DO)

    Table 3 Pin assignments "Digital input/ output" (DO1 to DO6)

  • 7/27/2019 I9-089B R30 R40

    37/124

    Page 37

    Fig. 27 Example of connection for digital input/ output

    4.7 DC 24V output

    Following installation of the option dc 24V output, a bipolar terminal (Fig. 28) isavailable at the rear of the recorder with a floating output for the supply of externalcomponents. The following connections are permissible since the current output islimited to max. 75mA:

    Up to three two-wire transmitters with a current consumption of25mA each

    Digital input/ output

    Note If several two-wire transmitters are powered, these must be connectedtogether on one side and are thus not electrically isolated from one another.For noise reasons (differences in potential), this arrangement is onlymeaningful for transmitters which are close together.

    DIGIN/O UT

    11

    13

    81+

    82+

    OV (DI)

    D14

    To pin 11

    To pin 13

    OV {DI}

    24VSynchronization 3:00 hours

    81+

    82+To pin 14

    To pin 1

    To pin 23 24V {D0}

    0V (DO)

    DO1

    24V (D0)

    OV (DI)

    D14

    11

    13

    1

    14

    23DIGIN/O UT

    Digital input/ output electronic version

    Time synchronization 3:00 hours Lamp triggering via DO1 Supply of digital input/ output via DC 24 V output

  • 7/27/2019 I9-089B R30 R40

    38/124

    Page 38

    Fig. 28 Example of connection for two-wire transmitter to the dc 24V output option(R30 version, dc 24V design)

    4.8 Starting up the recorderAll recorder settings have already being made in the factory if the recorder has beendelivered according to customer specifications.

    The standard settings have been made for recorders delivered without customerspecifications. The standard settings are listed in Section 5 Operation in therespective subsections.

    If you are not acquainted with the recorder, it is recommended to start with simplemeasurements after working through Sections 2 to 5. Measurements with thestandard settings are most appropriate initially.

    Section 5. OPERATION

    The following chapter describes how to operate the recorders.

    Note Replacing the chart and the battery for backing up the clock are described inSection 7.

    You are guided by menus when operating the recorders. The menus provideinformation in the form of a table on the respective functions or values for an input(leaflet Parameterization a concise overview).

    The input menus consist of several elements which are comprised in turn of menu

    code numbers and designations.

  • 7/27/2019 I9-089B R30 R40

    39/124

    Page 39

    In the first input step (selection of row) you decide which function or parameter is tobe called. The red LED lights up.

    In the second step (selection of column) you can define or modify the correspondingsetting of the recorder. The red LED flashes.

    The input of a menu code number is terminated by ENTER.

    You can scroll through the menu using the INC/ DEC functions.

    5.1 Display and control elements

    Operation is carried out using four horizontal levers located below the chart carriage(Fig. 29). A further lever is present on the side of the chassis. Two coloured LEDswhich are also located below the chart carriage serve to support you when setting upthe recorders and for the output of status messages. In the R40 version statusmessages are additionally printed on the chart paper by means of the text channel(Section 6).

    1. Scale channel 3 5 Lever 3 9 Lever 1

    2 Pen channel 1 6 LED, green 10 (Not used)

    3 Pen channel 2 7 Lever 2 11 Service lever

    4 Pen channel 3 8 LED, red 12 Parameterization scale

    Fig. 29 Display and control elements at front

  • 7/27/2019 I9-089B R30 R40

    40/124

    Page 40

    Fig. 30 Chassis in maintenance position, activation of lever 4

    5.2 Display elements

    The recorders are equipped with two colored LEDs whose combined statuses (on, off,flashing, fast flashing) indicate status messages. Table 4 lists a summary of the statusmessages assigned to the LED statuses.

    Table 4 Summary of LED status messages

    5.3 Levers

    The levers have different effects. The black service lever and lever 2 act directly onthe mechanics. The other levers act on microswitches whose signals are processed bythe central processing unit. The levers are used for recording, START, STOP or PAUSEOFF, PAUSE ON, high chart speed and recorder settings via the PROG and TESTmenus.

  • 7/27/2019 I9-089B R30 R40

    41/124

    Page 41

    Feedbacks for the user when setting up the recorders are via the LEDs and thepositions of the pens. The rows and columns of the PROG and TEST menus designedin tabular form directly correspond to the value of the parameterization scale, ie. ascale value of 15% corresponds to row 15 or column 15 depending on the status ofthe red LED.

    The levers are assigned different functions during operation, PAUSE and when settingup the recorder. Fig. 31 shows a summary of the lever functions. These functions aredescribed in detail in the following sections.

    Fig. 31 Summary of lever functions

    5.3.1 Functions of service lever and lever 2

    5.3.1.1 Service lever Releasing the chassis

    The service lever is used to release the chassis. The chassis must be moved to themaintenance position in order to change the pens or scales. To do this, briefly movethe service lever to the left, and simultaneously pull out the chassis until this latches inthe maintenance position. The chassis must be returned to its original positionfollowing the required operations. To do this, move the service lever to the left again,and simultaneously push in the chassis until it latches in place.

    The chassis can be completely removed from the housing in order to replace thebattery for backing up the clock (only R40 version). To do this, release the chassis inthe maintenance position using the service lever, and pull out the chassis to the front.When inserting the chassis again, you must again release it at the maintenanceposition using the service lever.

    Section 7 describes the above operations in detail.5.3.1.2 Lever 2 Releasing the chart carriage

    Lever 2 is used to release the chart carriage from the chassis. This is necessary inorder eg. to replace the chart.

    Section 7 describes the above operations in detail.

    5.3.2 Functions of Levers 1, 3 and 4 in recording mode

    5.3.2.1 Lever 1 Zero adjustment

    Briefly moving lever 1 (labelled 1) to the left starts a zero adjustment withoutmarking. The pens are moved to the right edge and carry out an adjustment.

    Recording mode is subsequently continued.

  • 7/27/2019 I9-089B R30 R40

    42/124

    Page 42

    5.3.2.2 Lever 1 PAUSE ON

    Briefly moving lever 1 to the right stops recording (PAUSE ON). The recording systemis lifted up, and the pens move to the maintenance position (text channel: approx.15%, bottom pen: approx. 40%, middle pen: approx. 60%, top pen: approx. 85%).All instrument functions apart from recording remain active.

    5.3.2.3 Lever 3 PROG menu ON

    Briefly moving lever 3 to the left activates the PROG menu. The following actionsidentify the transition to the parameterization state:

    1. Recording system lifts up.

    2. All pens are driven to the 100% mark and carry out an adjustment there.

    3. Channel 1 moves to the code number position for the PROG/ TEST menu andwrites a mark which must correspond to the version number of the PROG/ TESTmenu (cf. data in leaflet Parameterization a concise overview, version: codenumber n).

    4. The pen for channel 1 moves to the 0% position and thus indicates Row 0,PROG menu. The red LED lights up, the green LED is off.

    The recorder is now in the parameterization status. All parameters can be set whichare available in the PROG menu.

    Note The function PAUSE ON (lever 1 ) is not required in order to enter theparameterization status.

    The PROG menu is switched off by moving the lever again. The red LED goes out, thegreen LED lights up. The recorder is switched back to its original status. Individualactions:

    1. The recording system is lifted up.

    2. An adjustment of the pens is carried out at the 100% mark.

    3. The pens move to the measured values.

    4. The recording system is lowered, and recording is continued.

    5.3.2.4 Lever 3

    The lever 3 has no function in recording mode.

    5.3.2.5 Lever 4 TEST menu ON

    The chassis must first be moved to the maintenance position before lever 4 can be

    activated.

    Lever 4 is used to activate the TEST menu. Lever 4 is accessible on the side of thechassis and can be moved down eg. using a ball-point pen (Fig. 30).

    The mechanical sequences of the recording system correspond to those whenactivating Lever 3 .

  • 7/27/2019 I9-089B R30 R40

    43/124

    Page 43

    Table 5 Lever functions in recording mode

    5.3.3 Functions of Levers 1, 3 and 4 in the PAUSE status

    Recording is not carried out in the PAUSE status. The pens are lifted up and arelocated in the maintenance position. The measurements are continued, and themeasured values stored in a buffer to a limited extent. The measured values and textoutputs (only R40 version) are written when returning to recording mode.

    5.3.3.1 Lever 1 PAUSE OFF

    Termination of PAUSE. Brief activation of lever 1 leads to adjustment of the recordingsystem and continuation of recording.

    5.3.3.2 Lever 3 PROG menu ON

    The procedure is described in Section 5.3.2. Reactivation of lever 3 returns to thePAUSE status.

    5.3.3.3 Lever 3 Chart feed

    The chart is moved forward at maximum speed as long as lever 3 is held pressed tothe right.

    5.3.3.4 Lever 4 TEST menu ON

    The procedure is described in Section 5.3.2. Reactivation of lever 4 returns to thePAUSE status.

  • 7/27/2019 I9-089B R30 R40

    44/124

    Page 44

    Table 6 Lever functions in the PAUSE status

    5.3.4 Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu

    5.3.4.1 Lever 1 DEC

    The PROG menu is organized as a matrix with rows and columns. In theparameterization status, the row or column number can be decremented, ie. switchedby one digit in the zero direction with each activation. If the lever is activated whenthe pen is positioned at zero, this moves to the maximum row or column value (menucode number).

    5.3.4.2 Lever 1 INC

    As DEC, except that adjustment of the next higher menu code number is possible(incrementing (INC)).

    5.3.4.3 Lever 3 PROG menu OFF

    The red LED must light up (selection of row): the PROG menu is switched off, and therecorder returns to the original operating status.

    5.3.4.4 Lever 3 ENTER

    The number of the row or column selection currently marked by the pen is confirmedand entered. A switch is simultaneously made to the next selection level. Two cases

    are possible:

    1. Parameterization commences with selection of the row. ENTER is used to switch toselection of the column, and the currently set value is displayed. Activating ENTERagain switches over to selection of the row again. Whether you are positioned inselection of a row or column is indicated by lighting-up or flashing of the red LED.

    2. A subsequent input, eg. text input (only R40 version), is provided in the same rowfor the function to be parameterized, this status is indicated by fast flashing of thered LED.

    5.3.4.5 Lever 4

    Lever 4 has no functions with the PROG menu activated.

  • 7/27/2019 I9-089B R30 R40

    45/124

    Page 45

    Table 7 Lever functions with PROG menu activated

    5.3.5 Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu

    5.3.5.1 Lever 1 DEC

    The TEST menu is organized as a matrix with rows and columns. In theparameterization status, the row or column number can be decremented, ie. switchedby one digit in the zero direction with each activation. If the lever is activated whenthe pen is positioned at zero, this moves to the maximum row or column value (menucode number).

    5.3.5.2 Lever 1 INCAs DEC, except that adjustment of the next higher menu code number is possible(incrementing (INC)).

    5.3.5.3 Lever 3

    Lever 3 has no functions with the TEST menu activated.

    5.3.5.4 Lever 3 ENTER

    The number of the row or column selection currently marked by the recording systemis confirmed and entered. A switch is simultaneously made to the next selection level.

    Two cases are possible:

    1. Parameterization commences with selection of the row. ENTER is used to switch toselection of the column, and the currently set value is displayed. Activating ENTERagain switches over to selection of the row again. Whether you are positioned inselection of a row or column is indicated by lighting-up or flashing of the red LED.

    2. A subsequent input, eg. text input (only R40 version), is provided in the same rowfor the function to be parameterized, this status is indicated by fast flashing of thered LED.

    5.3.5.5 Lever 4 TEST menu OFF

    The red LED must light up (selection of row): the TEST menu is switched off, and therecorder is reset to the original operating status.

    Releasing of chassis

    Red LED lit: decrement menu row (DEC)

    Red LED flashes: decrement menu column (DEC)

    Red LED lit: increment menu row (INC)Red LED flashes: increment menu column (INC)

    Chart carriage released

    Red LED lit: switch off PROG menuRed LED flashes: none

    None

    1. Red LED lit: confirm row selection(every activation leads to change between 1. and 2.)2. Red LED flashes: confirm column selection

    Service lever

    Lever 1

    Lever 1

    Lever 2

    Lever 3

    Lever 3

    Lever 3

    DEC

    INC

    PROG

    TEST

    ENTER

    RecorderparameterizationusingPROGmenu

  • 7/27/2019 I9-089B R30 R40

    46/124

    Page 46

    Table 8 Lever functions with TEST menu activated

    5.4 Settings via PROG menu

    The following sections explain the settings which can be achieved using the PROGmenu by means of text, figures and examples.

    You can call and modify all recording, measurement and alarm settings in the PROGmenu.

    Access to the PROG menu can be protected by two interlocking steps.With interlocking step 1, only the chart feed A can change, with stage 2, the PROG

    menu is completely disabled.

    Note You can orientate yourself using the cross-references, eg. P[0] (means PROGmenu, row 0), and the associated PROG menu table (leafletParameterization a concise overview).

    Releasing of chassis

    Red LED lit: decrement menu row (DEC)

    Red LED flashes: decrement menu column (DEC)

    Red LED lit: confirm row section (INC)Red LED flashes: increment menu column (INC)

    Chart carriage released

    None

    None

    1. Red LED lit: confirm row section(every activation leads to change between 1. and 2.)2. Red LED flashes: confirm column selection

    Service lever

    Lever 1

    Lever 1

    Lever 2

    Lever 3

    Lever 3

    Lever 4

    DEC

    INC

    TEST

    ENTER

    RecorderparameterizationusingTE

    STmenu

  • 7/27/2019 I9-089B R30 R40

    47/124

    Page 47

    Section 5.5.1

    Section 5.5.1

    Section 5.5.2

    Section 5.5.3

    Section 5.5.4

    Section 5.5.5

    Section 5.5 6

    Fig. 32 Summary of PROG menu, rows

    5.4.1 Chart speed

    5.4.1.1 P[0], P[10] Chart speeds A, B

    The parameters for chart speed A or B can be used to define two combinable speedsfor the chart paper. The selectable values are listed in Fig. 33.

    5.4.1.2 P[5], P[15] Condition

    Chart speed A and/ or B can be linked to a condition if required so that the chartspeed changes dependent on an event. The possible conditions are shown in Fig.33.

    Chart speed B

    Chart speed A

  • 7/27/2019 I9-089B R30 R40

    48/124

    Page 48

    5.4.1.3 Event-dependent chart speed

    The recorder selects chart speed A when switched on. The event sources are alsoprocessed even if recording is switched off. The currently active status is retained ifno conditions are fulfilled for chart feeds A and B or if both conditions are fulfilledsimultaneously. A change is made to chart speed B if the condition set for it is

    fulfilled. The same applies to a change from B to A.If the alarm of a channel is used as the condition, if Mode OFF is selected for theassociated channel.

    See Section 5.6.1 for setting example.

    Fig. 33 Programmable parameter Chart speed

    5.4.1.4 Details on selection of chart speed

    Switching over commences with a marker in the form of small horizontal lines on the

    curves and a fast feed of at least 7mm such that a setting on the main time lines - ifset - is retained. Small horizontal lines are then again drawn on the curves, and therecording commences with the new chart speed. At the same time, the text channel ofthe R40 version starts to write a chart switching line.

    Note If the chart speed is switched over too frequently in succession, the recordingsystem would be overloaded and the measured values lost. Therefore therecorder switches over again at the earliest after approx. 30s.

    The following example clarifies the mode of operation of chart speeds A and B withcondition.

  • 7/27/2019 I9-089B R30 R40

    49/124

    Page 49

    5.4.1.5 Example

    Chart speed A is set to 20mm/ h [P0.30]. The condition is present at Input DI2[P5.70].

    Chart speed B is set to 120mm/ h [P10.40]. The condition is at / Input DI2[P15.75].

    Result:

    The chart speed is 20mm/ h in measuring mode if the signal at input DI2 is High.The chart speed is switched over to 120mm/ h if the signal changes to Low.This status is retained until DI2 changes to High again. The chart speed then returnsto 20mm/ h.

    5.4.2 Measured-value table (only R40 version)

    5.4.2.1 P[20] Measured-value table

    The R40 version prints a measured-value table (Fig. 56 Example recording for R40version as required with the following information, if relevant:

    q Date and time

    q Channel number

    q Measured value

    q Dimension

    q Symbol for open-circuit

    q Status of alarms assigned to the channel.

    Printing can be triggered cyclically or event-controlled.

    Parameterization is carried out according to Fig. 34.

    5.4.2.2 Printing the measured-value table

    The graphic recording is not interrupted when printing the measured-value table, ie.the 2nd and 3rd lines are only printed if the chart feed has reached a full line heightsince the last line. If a further trigger function for a measured-value table or an eventtext arrives whilst a table is being printed, this is only commenced when the table hasbeen completely printed and the chart feed has reached a full line height since thelast line.

    The printout of the measured-value table always coincides with a time mark if it iscarried out cyclically. The first line of the measured-value table is omitted in this case.

    The minimum distance between two cyclic printouts is 10 mm.

    The measured values at the printed time are stored in intermediate memory beforebeing output. Only those channels are printed out for which Measuring orRecording has been selected.

    See Section 5.6.2. for setting example.

  • 7/27/2019 I9-089B R30 R40

    50/124

    Page 50

    Fig. 34 Summary of parameters Measured-value table

    5.4.3 Parameterizing the Analog Channels

    The channel-specific variables are set using the parameters for channel (analog),

    mode, measuring range, sensor, connection, left value, right value, open-circuit anddamping.

    5.4.3.1 P[25] Analog channel

    This is used to select the number of the analog channel you wish to parameterize.The channel number is preceded by the symbol # in the printouts, eg. #1.

    The recorders have one to three analog channels: #1, #2, #3. The associated pen isactivated following selection of the channel.

    The following table lists the channel assignments:

    Channel #1 Channel #2 Channel #3

    Position in Bottom Centre Toprecording system

    Table 9 Characteristics of analog channels #1 to #3

    The possible setting parameters are shown in Fig. 35.

  • 7/27/2019 I9-089B R30 R40

    51/124

    Page 51

    Fig. 35 Summary of parameter Channel (analog)

    See Section 5.6.3 for setting example.

    5.4.3.2 P[30] Mode

    You can use this parameter to select the Measure or Recording mode for theselected channel (Section 5.5.3). Select Off if the measuring and recording modesare to be switched off. In Measure and Recording modes, the associatedchannel is scanned cyclically. The alarm is generated by comparing the measuredvalue with the set alarm value.

    In Recording mode, the measured values are additionally recorded by therecording system.

    Fig. 36 Summary of parameter Channel (analog), Mode

    See Section 5.6.3 for setting example.

  • 7/27/2019 I9-089B R30 R40

    52/124

    Page 52

    5.4.3.3 P[35] Measuring range

    The measuring ranges are selected according to the set input range (Section 4.5).

    The recording range (left value, right value) is fixed to the measuring range limits forcertain standard ranges (Fig. 37) and cannot be changed.

    With the other measuring ranges, you can enter the start-of-scale and full-scale valuesyourself within the range limits. Table 10 shows the possible values for the setranges.

    Fig. 37 Summary of parameter Channel (analog), Measuring range

    See Section 5.6.3 for setting example.

    5.4.3.4 P[40] Sensor

    The parameter Sensor is used to define the type of sensor when usingthermocouples or resistor thermometers. The associated linearization values areautomatically taken into account during measured-value processing.

    The appropriate operating range of the sensor must be selected when using resistors,potentiometers or sensors with a voltage output.

    The possible settings are shown in Fig. 38.

  • 7/27/2019 I9-089B R30 R40

    53/124

    Page 53

    Fig. 38 Summary of parameter Channel (analog), Sensor

    See Section 5.6.3 for setting example.

    5.4.3.5 P[45] Connection

    This parameter is used to select the input for the reference temperature whenmeasuring with thermocouples. Select the desired reference point from Fig. 39.

    5.4.3.6 TC

    With the setting Ref.: internal, the temperature of the input terminals is used as thereference.

    Select the setting Ref.: 0C to Ref.: 70C if the external reference point is heldstable at one of the corresponding temperatures. The reference point can bemeasured via a further input if the temperature varies.

    In this case, select the settings Ref.: #1 to Ref.: #6.

    5.4.3.7 RTD, R, Pot.

    You can select either a three-wire or two-wire connection (Section 5) formeasurements via resistance thermometers, resistors and potentiometers.

    Select RL: 10 in the case of a two-wire system with adjustment of the lineresistance to 10 .

    Select RL: 0 if the line resistance is negligibly small.

  • 7/27/2019 I9-089B R30 R40

    54/124

    Page 54

    Fig. 39 Summary of parameter Channel (analog), Connection

    See Section 5.6.3 for setting example.

    5.4.3.8 P[50] Left value P[55] Right value

    The recording range can be set within limits using the parameters Left value andRight value, apart from certain standard measuring ranges (Fig. 40).

    The factory-set recording ranges are listed in Table 10 (default settings for left value/right value).

    The recording range is set numerically for the inputs Left value and Right value.The input refers to the set measuring range and is set in a uniform manner. The signis entered first, followed by 4 digits separated by a decimal point. If modificationsare necessary, only the associated digits or the sign are overwritten. If illegal inputsare made, adaptation is automatically made according to the measuring range.

  • 7/27/2019 I9-089B R30 R40

    55/124

    Page 55

    Fig. 40 Summary of parameter Channel (analog), Left value and Right value

    See Section 5.6.3 for setting example.

  • 7/27/2019 I9-089B R30 R40

    56/124

    Page 56

    Measuring Dimen- Setting range Presetrange sion

    Start End Left Rightvalue value

    0/ 20mA mA +00.00 +20.004/ 20mA mA +04.00 +20.000/ 1V V +0.000 +1.0000.2/ 1V V +0.200 +1.0000/ 10V V +00.00 +10.002/ 10V V +02.00 +10.00

    20mA mA 22.00 +22.00 20.00 +20.001V V 1.100 +1.100 1.000 +1.00010V V 21.00 +21.00 10.00 +10.00

    U: 40mV mV 44.00 +44.00 44.00 +44.00U: 100mV mV 110.0 +110.0 100.0 +100.0

    U: 400mV mV 440.0 +440.0 400.0 +400.0U: 1000mV mV 1100. +1100. 1000. +1000.

    R: 300 030.0 +330.0 +000.0 +300.0R: 1000 0100. +1100. +0000. +1000.

    Pot: 300 % 010.0 +110.0 +000.0 +100.0Pot: 1000 % 010.0 +110.0 +000.0 +100.0

    RTD: Pt 100 C 0273. +2000. +0000. +0500.RTD: Ni 100 C 0273. +2000. +0000. +0500.

    TC: J C 0273. +2000. +0000. +0500.TC: L C 0273. +2000. +0000. +0500.

    TC: T C 0273. +2000. +0000. +0400.TC: U C 0273. +2000. +0000. +0500.TC: K C 0273. +2000. +0000. +0500.TC: N C 0273. +2000. +0000. +0500.TC: E C 0273. +2000. +0000. +0500.TC: S C 0273. +2000. +0800. +1500.TC: R C 0273. +2000. +0800. +1500.TC: B C 0273. +2000. +0800. +1500.

    Table 10 Setting of recording range

  • 7/27/2019 I9-089B R30 R40

    57/124

    Page 57

    5.4.3.9 P[60] Open-circuit

    Only R40 version. Monitoring is carried out for an open-circuit in the mV measuringranges and the TC, RTD, R and Pot. ranges based on them.

    As soon as the internal resistance of the sensor exceeds a certain value, therecording is continued on the left of the 0% line in the case of the setting < 0%

    (Fig. 41), and on the right of the 100% line in the case of >100%. The R40 versionadditionally outputs the event Open-circuit in the measured-value table (Section5.4.2) printed on the chart paper.

    An open-circuit is not detected in the setting OFF.

    Fig. 41 Summary of parameter Channel (analog), Open-circuit

    See Section 5.6.3 for setting example.

    Fig. 42 Example of display with open-circuit

    5.4.3.10P[65] Damping

    The damping is determined by the time constant of a 1st order low-pass via which thesignal connected to the input terminals of the recorder is filtered. The output signal ofthe low-pass is an exponential function following a jump in the signal at the input.

    The time constant defines how long it takes until the output signal has attained 63.2%of the stationary final value. Set 0s for output of unfiltered measured values.

    The damping must be set individually for each channel. With the setting auto, the

    damping is automatically adapted to the chart speed. The basic setting is 0s.

  • 7/27/2019 I9-089B R30 R40

    58/124

    Page 58

    The following Figure shows the parameterizable time constants.

    Fig. 43 Summary of parameter Channel (analog), Damping

    See Section 5.6.3 for setting example.

    5.4.4 Parameterizing the digital channel (only R40 version)

    5.4.4.1 P[70] Channel (digital)

    The recorder has two digital channels in addition to the three analog channels.An alarm (Section 5.4.5) or a digital input (Section 5.6) can be selected as the

    source. The binary signals of the digital inputs are displayed as a square-wave signalat defined chart positions (Table 11):

    Channel #1d Channel #2d

    Logical 0 (Low) 81% 91%

    Logical 1 (High) 89% 99%

    Table 11 Chart positions of channels (digital)

    The digital channels are recorded by the mechanical system of the text channel.Edges from logical 0 to 1 and logical 1 to 0 as well as peaks are recorded ascontinuous lines. Constant signal sequences are recorded as dashed lines. The linesare spaced at 10 mm with low chart speeds, and at 20mm with high chart speeds(see Fig. 56 Example recording for R40 version).

    Fig. 44 shows the possible parameters.

    See Section 5.6.4 for setting example.

  • 7/27/2019 I9-089B R30 R40

    59/124

    Page 59

    Fig. 44 Summary of parameter Channel (digital)

    5.4.5 Alarm

    The recorder permits the programming of up to six alarms, each of which is assignedto a fixed output of the digital input/ output (option) (Table 3). A set alarm becomesactive in Measure or Recording mode if the set limit is violated.

    The assignments of the alarms to the individual channels, mode and alarm value arefreely selectable. The settings always commence with selection of an alarm.

    See Section 5.6.5 for setting example.

    5.4.5.1 P[80] Alarm

    The parameter Alarm is used to select one of the available alarms A1 to A6 towhich the mode, channel and value apply in a subsequent setting.

    5.4.5.2 P[85] Mode

    The parameter Mode can be used to define whether the alarm is to be triggeredwhen MIN is fallen below or MAX exceeded.

    With the R40 version, limit lines can be drawn parallel to the time axis. These linesare vertical and approx. 1mm long. The spacing between the individual lines is

    reduced by half if the limit is violated. The lines are drawn by the mechanical systemof the text channel. The alarm symbol, the associated alarm number, the channelnumber or the character (with the setting All channels) are written cyclically nextto the limit lines. The limit line can be set for each alarm using the parameter MINwith line or MAX with line.

    In the setting Status (only available in recorders with option Digital input/ output),recorder readiness is signalled if all of the following conditions are fulfilled:

    q Power supply present

    q PROG menu not switched on

    q TEST menu not switched on

    1) Only R30 version

  • 7/27/2019 I9-089B R30 R40

    60/124

    Page 60

    q Recording started

    q Chart paper present

    q Last adjustment of recording system fault-free.

    Use of the status message is particularly meaningful if the recorder cannot be directly

    viewed.A control signal is output in the position Time marker (only available in recorderswith option Digital input/ output) at the start of the zero adjustment. This signal canbe used to synchronise the cyclic zero adjustment of several recorders using this oneas the master.

    An alarm is not output in the position OFF. All alarms are switched off in the basicsetting.

    5.4.5.3 P[90] Channel

    The 6 alarms can be freely assigned to the individual analog channels. The basicsetting is as follows:

    q Alarms A1 and A2 to channel 1

    q Alarms A3 and A4 to channel 2

    q Alarms A5 and A6 to channel 3

    A further possibility is the assignment of a common alarm to the channels in thesetting All channels and applies to the channels for which Measure orRecording mode has been selected. The alarm is triggered if the value is exceeded(max) or fallen below (min) for at least one of the channels.

    5.4.5.4 P[95] Value

    The setting Alarm, Value is used to define the percentage with respect to the

    recording range at which the alarm to be triggered. The selectable range of values isidentical to the recording range and can be set in steps approx. 0.1%.

  • 7/27/2019 I9-089B R30 R40

    61/124

    Page 61

    Fig. 45 Summary of parameter Alarm

    5.4.6 Print (only R40 version)

    Printing of the configuration data is triggered by the parameter Print.

    The color of the text channel is black. A different color setting is not possible.

    Note: All printing operations triggered via the input menu can be aborted usingENTER

    5.5 Settings using TEST menu

    The following sections explain the settings which can be achieved using the TESTmenu by means of text, figures and examples.

    Note You can orientate yourself using the cross-references, eg. T[0], in theassociated TEST menu table (leaflet Parameterization - a concise overview).

    85: Condition

  • 7/27/2019 I9-089B R30 R40

    62/124

    Page 62

    Section 5.5.1

    Section 5.5.2

    Section 5.5.3

    Section 5.5.4

    Section 5.5.5

    Section 5.5.6

    Section 5.5 7

    Section 7.19

    Section 7.19.3

    Section 7.19.4

    Section 7.19.5

    Fig. 46 Summary of TEST menu, rows

    5.5.1 Measuring mode5.5.1.1 T[0] Measuring mode

    Five settings are possible for the parameter Measuring mode. No acquisition ofmeasured values is carried out in the position OFF, ie. all other associatedfunctions such as chart speed and alarm monitoring are also switched off.

    The setting Normal or Fast determines the cycle time. The resolution of measuredvalues is higher with the setting Normal. The cycle times can also be switched onor off via the option Digital input/ output with DI1. Measuring mode is carried outwith the set cycle time as long as input DI1 remains at High. Measuring mode isterminated if the signal changes to Low.

  • 7/27/2019 I9-089B R30 R40

    63/124

    Page 63

    Fig. 47 Summary of parameter Measuring mode

    See Section 5.6.6 for setting example.

    5.5.2 Diagram

    5.5.2.1 T[5] Diagram (only R40 version)

    The parameter Diagram is used to select the chart formatting. All texts are output ifrecording is switched on with the setting Alphanumeric ON. These texts include:

    q Start line when starting recording

    q Chart switching line when changing the chart speed

    q Text with PAUSE ON

    q Date/ time marker and instrument text

    q Event texts

    q Inscription of limit lines.

    These texts are suppressed in the setting Alphanumeric OFF.Output of the time at the left edge of the chart is suppressed in the setting TimeOFF. The underline character is still output. The date is still printed out every 12h.

    The following texts are suppressed with the setting Status line OFF:

    q Start line when starting recording

    q Chart switching line when changing the chart speed

    q Text with PAUSE ON

    (see Fig. 56 Example recording for R40 version ).

    See Section 5.6.7 for setting example.

    5.5.2.2 Start line (only R40 version)

    The printout of the start line and the graphic recording commence simultaneously, ie.the arrangement of the pens means the start line appears in the chart (see Fig. 56Example recording for R40 version).

    The start line consists of the word START, the date, time, active chart speed andmeasuring cycle. The graphic recording commences together with printing of the startline.

    An abbreviated start line is printed when the chart speeds A and B are changed.This line consists of the time and the active chart speed.

    0.0: OFF

    0.15: DI1 normal

    0.5: ON normal

    0.10: ON fast

    0.20: DI1 fast

  • 7/27/2019 I9-089B R30 R40

    64/124

    Page 64

    5.5.2.3 T[10] Cycle

    This menu item can be used with the line recorders to set the time between two timemarkers. The possible settings are shown in the following Figure. A time marker is notoutput in the position OFF. Only a zero adjustment is carried out