HVAC SYSTEM Presented By : Vishal Katiyar Quality Assurance A Seminar On…….

Transcript of hvac_basics

Page 1: hvac_basics

HVAC SYSTEM

Presented By :Vishal Katiyar

Quality Assurance

A Seminar On…….

Page 2: hvac_basics

2

HVAC DEFINITIONWhat is HVAC Full Form?Heating, Ventilation, Air Conditioning

PURPOSE In simple words –The system is used to provide heating and cooling services to buildings.

FUNCTION Control airborne particles, dust and micro-organisms Maintain room pressure & air changes per hour Temperature & RH

USE To prevent contamination To provide comfortable working conditions

Page 3: hvac_basics

3

MEANING OF WORDS USING IN HVAC

Page 4: hvac_basics

4

HVAC UNIT

Diagram of mechanical system on the blackboard

Secondary FILTER(5 micron)

FRESH AIR(10 to 20%)

HEPA FILTER(0.3 micron) Pre FILTER

(10,20,50 micron)

Page 5: hvac_basics

5

HVAC

Page 6: hvac_basics

6

AHU

Page 7: hvac_basics

7

HOW HVAC SYSTEM WORK

Page 8: hvac_basics

8

FILTER TYPE HEPA FILTER

SECONDARY FILTER

RETURN FILTER PRE FILTER

Page 9: hvac_basics

9

FILTER TYPE SPECIFICATION

HEPA FILTER

SECONDARY FILTER

PRE FILTER PreFilter -10,20,50 micron (Efficiency - Upto 80-95%)MOC : Metallic, SyntheticA filter's ability to remove large airborne particles from the air e.g dust,plant spores,fertilizer,household dust

Secondary Filter - 5 micron(Efficiency - Upto 99%)

MOC : Synthetic, HDPE(High-density polyethylene)A filter's ability to remove small airborne particles from the air e.g coal dust,House hold dust,Bacteria

HEPA Filter – 0.3 micron(Efficiency - Upto 99.97%)HEPA : “High Efficiency Particulate Air”MOC : Borosilicate microfibresA filter's ability to remove at least 99.97% of dust, pollen, mold, bacteria and any airborne particles with a size of 0.3 micrometres (μm)

Page 10: hvac_basics

10

Particle Size

Page 11: hvac_basics

11

DUCT

Page 12: hvac_basics

Validation of AHU/HVAC System

Temperature control test Humidity control test Filter integrity test Air velocity testAir flow pattern(Smoke test)Microbial test

12

Page 13: hvac_basics

1.Temperature control test:-

Test procedure:-Environment is divided by a gridSize of square- 60cm×60cm or moreSampling location- work heightResult compare with specification

60×60cm

Objective:- To demonstrate the ability of the HVAC system to control temperature.

Acceptance criteria:- Temp. 23±2ºC

13

Equipment- Thermometer

Page 14: hvac_basics

2.Humidity control test:-

Acceptance criteria:- Humidity: 60±5%

Data Logger

Objective:- To demonstrate the ability of the HVAC system to control humidity.Test procedure:-

Environment is divided by a gridSize of square- 60cm×60cm or moreSampling location- work heightResult compare with specification

60×60cm

14

Page 15: hvac_basics

3. Filter Integrity Test:-

Objective:- To provide evidence of the integrity of the HEPA filter

Acceptance criteria:- 99.97 efficiency- 0.03% particles of 0.3 µm 99.99 efficiency- 0.01% particles of 0.3 µm

100% 0.03%

HEPA filter

15

Page 16: hvac_basics

Air flow velocity and uniformity test:-

Test procedure:- Environment is divided by grid Measure by Airflow meter

Fig.- Airflow meter

Fig.- laminar air flow unit

Acceptance criteria:-Vertical flows 0.30 m/sec ± 20%Horizontal flows 0.45 m/sec ± 20%

Action: Deviation indicates blockage of filter Solution : Alteration of fan speed

HEPA filter replacement16

Page 17: hvac_basics

AIR FLOW SYSTEM (SMOKE TEST ) :-

Generate visible smoke upstream from the work zone

Establish the reference point

Videotape the direction of the flow in both case

Determine the direction

Test procedure:- (smoke test)

17

Page 18: hvac_basics

MICROBIOLOGICAL TESTS :-

Solid growth media

Sampling conditions

Sampling in the at rest condition may be continued at an agreed frequency to monitor baseline contamination levels.

The operational conditions and the activities being performed at the time of testing should be recorded.

Incubation conditions Incubation of samples, inverted, at 20 – 25C for at least 5 days is

suitable for the growth of mould and fungi.

Incubation of samples, inverted, at 30 - 35C for at least 2 days is suitable for the growth of bacteria.

18

Page 19: hvac_basics

1. Health-Care Facilities Residences

2. Educational Facilities 3. Laboratories4. Pharmaceutical

Industries5. Non Pharmaceutical

Industries6. Tall Buildings 7. Hotels 8. Places of Assembly 9. Nuclear Facilities 10. Commercial and Public

Buildings

APPLICATIONS OF HVAC

19

Page 20: hvac_basics

20