HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter...

63
Date By Lee Eng Lock HVAC Talk

Transcript of HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter...

Page 1: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Date

By Lee Eng Lock

HVAC Talk

Page 2: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer2

• Chong Qing, • Hang Zhou, • Shen Zhen

in China

Psychometric Chart for Weather Data from:

Page 3: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer3

Location Map of the 3 cities

Page 4: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer4

Chong Qing Weather Data

2004 - 2006

2004 2006

Page 5: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer5

Hang Zhou Weather Data

2004 - 2006

2004 2006

Page 6: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer6

Shen Zhen Weather Data

2004 - 2006

2004 2006

Page 7: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer7

AHU ENERGY RETROFIT

New AHU Design Criteria

1. Low air velocity across filter and cooling coil2. Air pre-cool by 15 degC chilled water3. High efficiency Airfoil direct driven fan4. Super-E electric motor5. Variable speed drive6. Digital temperature Control7. Non flammable AHU panel8. High resistance of coil to corrosion (powder coating)

CASE STUDY 1. ST Microelectronics CASE STUDY 1. ST Microelectronics PtePte LtdLtd

Page 8: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer8

AHU ENERGY RETROFIT

New AHU Plan View

CASE STUDY 1. ST Microelectronics CASE STUDY 1. ST Microelectronics PtePte LtdLtd

Page 9: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer9

AHU ENERGY RETROFIT

New AHU Section

CASE STUDY 1. ST Microelectronics CASE STUDY 1. ST Microelectronics PtePte LtdLtd

Page 10: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer10

AHU ENERGY RETROFIT

CASE STUDY 1. ST Microelectronics CASE STUDY 1. ST Microelectronics PtePte LtdLtd

Executive SummaryOLD and NEW AHU PERFORMANCE

# AHU Parameter (100% fresh air): Unit OLD AHU NEW AHU

1 Total cooling capacity Ton refrigerant 340 354

2 Chilled water supply temperature Degree C 6

15-pre-cool,

6-final cooling

3 Chilled water temperature rise Degree C 5.5 11

4 Fan power consumption KW 35 7

5 Chiller power consumption KW 212 170

6 AHU efficiency KW/Ton 0.1 0.02

SAVINGS

# Savings (for 2 units): kW % $Sin/Year

1 Fan power consumption 56 80 72,800

2 Chiller power consumption 84 20 109,200

3 Total 140 182,000

Payback period of investments 1.9 years

Page 11: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer11

Existing Ultrasonic Flow Meter

Page 12: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer12

Newly Installed Ultrasonic Flow Meter

Header MF?

Page 13: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer13

Magnetic flow meter on condenser flow

Page 14: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer14

Magnetic flow meter on chilled water flow

Page 15: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer15

New USFOld USF on the vertical pipe

Three MFs on chilled side

Three MFs on condenser side

Page 16: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer16

UF installation

Page 17: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer17

MF installation

From OMEGA Engineering

Page 18: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer18

Flow measure comparison

Flow measurement comparison (GPM) 18Nov08

1000.00

1100.00

1200.00

1300.00

1400.00

1500.00

1600.00

1700.00

1800.00

1900.00

2000.00

7:0

0

8:0

0

9:0

0

10:0

0

11:0

0

12:0

0

13:0

0

14:0

0

15:0

0

16:0

0

17:0

0

18:0

0

time

gpm USFnew(header)

USFold(header)

MF existing(header)

1) Correctly mounted ultrasonic flow meter reading matches the existing magnetic flow reading

2) Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter and the existing magnetic flow meter

Page 19: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer19

Cooling load comparison

Cooling load comparison (tons) 18Nov08

400

500

600

700

800

900

1000

1100

7:00 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00

Cooling load (USF new)

Cooling load (USF old)

Cooling load (MF existing)

1) Equipment switched on at 7.30am, switched off at 6:pm

2) There is a cooling load spike in the early morning due to the heat accumulation during the night.

Page 20: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer20

Efficiency comparison (kw/ton) (18Nov08)

0.60

0.70

0.80

0.90

1.00

1.10

1.20

7:00

7:30

8:00

8:30

9:00

9:30

10:0

010

:30

11:0

011

:30

12:0

012

:30

13:0

013

:30

14:0

014

:30

15:0

015

:30

16:0

016

:30

17:0

017

:30

18:0

018

:30

Efficiency (USF new)

Efficiency (USF old)

Efficiency (MF existing)

Efficiency comparison

Page 21: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer21

Efficiency comparison

Efficiency comparison (kw/ton) (18Nov08)

0.00

0.20

0.40

0.60

0.80

1.00

1.20

7:00

7:30

8:00

8:30

9:00

9:30

10:0

010

:30

11:0

011

:30

12:0

012

:30

13:0

013

:30

14:0

014

:30

15:0

015

:30

16:0

016

:30

17:0

017

:30

18:0

018

:30

Efficiency (USF new)

Efficiency (USF old)

Efficiency (MF existing)

Page 22: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer22

Spot measurement

Chill plant power: 421.8 kw

Chiller plant flow rate: 2441gpm

Chiller Chw temp in: 52.34F (11.3 C)

Chiller Chw temp out: 46.22F(7.9C)

The resultant plant efficiency: 0.6776 kw/ton

The measurement time is around 9:30am to 10:30amComparing with the logging graph, the spot measured efficiency is lower than logging data which is 0.71-0.88kw/ton based on UF new and MF existing flow measurement, but acceptable

Page 23: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer23

• The sampling rate is 1 minute

• The readings from correctly mounted ultrasonic flow meter matches well those from magnetic flow meter mounted on the header

• Due to the improper mounting of the old ultrasonic ( air accumulation), the readings from old UF is 15% lower than new correctly mounted UF, which causes the higher efficiency deviation

• During the equipment switching on and off period, unsteady operating condition affects the flow meter reading greatly

• Chiller plant average efficiency from 8:am to 6pm on Nov.18, 2008 is 0.79kw/ton, which is meet the GreenMark baseline minimum efficiency requirement 0.85kw/ton

• There is big room to improve chiller plant efficiency:

Page 24: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer24

Page 25: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer25

Figure 3a

Page 26: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer26

Figure 3b

Page 27: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer27

Figure 3c

Page 28: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer28

Page 29: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer29

Page 30: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer30

Insert subtitle here

Figure 5a

Page 31: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer31

Figure 5b

Page 32: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer32

Figure 5c

Page 33: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer33

Figure 5d

Page 34: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer34

Page 35: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer35

Page 36: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer36

Figure 6a

Page 37: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer37

Figure 6b

Page 38: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer38

Figure 6c

Page 39: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer39

Figure 6d

Page 40: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer40

Page 41: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer41

Figure 7a

Page 42: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer42

Figure 7b

Page 43: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer43

Low Face VelocityAn Energy Conservation Option

forMake-Up Air Units

Presented by:Greg Owen, PE

[email protected]

October 4, 2000

Page 44: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer44

Cleanroom facility design decisions must be economically

justified.

FACT:

Low Face Velocity

Page 45: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer45

• Unit CFM - 43,500 CFM

• Site Elevation - 1500 Ft

• Summer Conditions - 96oF / 65oF

• Winter Conditions - -20oF

• Chilled Water - 39oF / 51oF

• Hot Water - 180oF / 150oF

• Supply Air Conditions - 55oF / 48.6oF

Make-Up Unit Design Conditions

Low Face Velocity

Page 46: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer46

Elements That Affect Make-up Air Unit Energy Consumption

CoilSize

FilterSize

Fan CFM, Motor Hp

oF &RH%of OA

Under the control ofthe Design Engineer

oF &RH%

Low Face Velocity

Page 47: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer47

FACE VELOCITIES CONSIDERED

• Unit CFM

Face Area

500FPM

350FPM

425

FPM

300FPM

Low Face Velocity

Page 48: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer48

Low face velocities reduce air handling unit coil and filter static

pressure and result in lower energy consumption by the unit.

PREMISE #1

Low Face Velocity

Page 49: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer49

FILTER DIFFERENTIAL PRESSURE

0

0.5

1

1.5

2

2.5

500 425 350 300(FPM)

Pre Filters Carbon Filters 95% Filters HEPA Filters

(INWG)

Low Face Velocity

Page 50: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer50

COIL DIFFERENTIAL PRESSURE

0

0.2

0.4

0.6

0.8

1

1.2

1.4

(INWG)

500 425 350 300(FPM)

Preheat Cooling Dehum Reheat

Low Face Velocity

Page 51: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer51

Energy savings from low face velocity systems reduce the operating costs of the units.

PREMISE #2

Low Face Velocity

Page 52: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer52

Component Cost Impact

Larger Casing Increase Capital Cost

Larger Coils Increase Capital Cost

Increased Filter Count Constant Life Cycle Cost

Smaller Fan Motors Decreased Capital Cost

Reduced Infrastructure Decreased Capital Cost

ECONOMIC IMPACT FOR LOW FACE VELOCITY COMPONENTS

Low Face Velocity

Page 53: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer53

MAKE-UP AIR UNIT MOTOR SELECTION

Static RPM Brake Hp

• 500 FPM 801 65.0

• 425 FPM 757 55.6

• 350 FPM 709 46.0

• 300 FPM 687 41.8

Low Face Velocity

Page 54: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer54

Includes

• Fan, Motor & Drives

• Coils

• Filter Racks

• Humidifier

• Housing & Inlet

• EE Infrastructure Impact

MAKE-UP AIR UNIT COST ESTIMATE

Excludes• Filter Media

• Installation Cost

• Building Space

Low Face Velocity

Page 55: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer55

Make-up Air Unit (MAU) Capital Cost Differential

• 500 FPM

• 425 FPM

• 350 FPM

• 300 FPM

• Base Cost

• +$4,820

• -$1,610

• +$9,450

Low Face Velocity

Page 56: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer56

Energy Cost

• High Average Industrial / Commercial Rate

– Boston Edison

– $0.097/kWHr

• Low Average Industrial / Commercial Rate

– Portland General Electric

– $0.0382/kWHr

Low Face Velocity

Page 57: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer57

• 425 FPM Unit $38,187 +37 Weeks (9.5 months)

MAU Electrical Operating Cost (High Rate)

• 500 FPM Unit $44,959 Base Condition

Pay Back PeriodUnit Size Cost/Yr.

• 350 FPM Unit $31,964 Immediate

• 300 FPM Unit $28,764 + 29 Weeks (7.25 months)

Low Face Velocity

Page 58: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer58

• 425 FPM Unit $15,039 +94 Weeks (23.5 months)

MAU Electrical Operating Cost (Low Rate)

• 500 FPM Unit $17,705 Base Condition

Pay Back PeriodUnit Size Cost/Yr.

• 350 FPM Unit $12,588 Immediate

• 300 FPM Unit $11,328 + 77 Weeks (19.2 months)

Low Face Velocity

Page 59: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer59

• Low face velocities do save energy & money.

• Return on Investment (ROI) is dependent on local energy rates.

• High tech companies generally require ROI’s of 12 months or less.

CONCLUSION

Low Face Velocity

Page 60: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Questions??

Low Face Velocity

Page 61: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer61

Questions??

Low Face Velocity

Questions??

Page 62: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply

Insert Footer62

Insert subtitle here

Page 63: HVAC Talk - · PDF fileSuper-E electric motor 5. ... Improperly mounted ultrasonic flow meter reading is 15% lower than correctly mounted ultrasonic flow meter ... 150 oF • Supply