Page 1: HVAC INSTALLATION - AC SUPPLY CO....HVAC INSTALLATION TECH TIPS 8. Install outside air ventilation intakes at least 10 feet from any exhaust vent or stack. Coordinate bath fan exhaust

for Builders & TradesRecommended Practices for Optimized Energy Savings

COPYRIGHT ©2014 ADVANCED ENERGY. ALL RIGHTS RESERVED

SUCCESS WITH 2012 IECC TEXAS & OKLAHOMA

HVAC INSTALLATION

Page 2: HVAC INSTALLATION - AC SUPPLY CO....HVAC INSTALLATION TECH TIPS 8. Install outside air ventilation intakes at least 10 feet from any exhaust vent or stack. Coordinate bath fan exhaust

1.Seal all duct terminations to drywall and/or subfloor and all HVAC penetrations in the building envelope with foam, caulk or mastic. Use fire-rated sealants where applicable.

Mechanically fasten all metal duct work with screws. Attach the inner liner of flexible ducts with nylon/plastic straps and tighten with a manufacturer-approved tool.

3.2. Seal all HVAC components at all joints, seams and corners.

Seal all duct terminations to drywall and/or subfloor and all HVAC penetrations in the building envelope with foam, caulk or mastic. Use fire-rated sealants where applicable.

1.

Copyright ©2014 Advanced Energy. All Rights Reserved • Version 2014.1.A • Page 2

SUCCESS WITH 2012 IECC CODE

HVAC INSTALLATION

TECH TIPS

INSULATION SEAL

WRONG TAPE PLASTIC STRAPLOOSE SEAL BUCKET MASTIC

NONE MASTIC

Page 3: HVAC INSTALLATION - AC SUPPLY CO....HVAC INSTALLATION TECH TIPS 8. Install outside air ventilation intakes at least 10 feet from any exhaust vent or stack. Coordinate bath fan exhaust

5.Do not compress insulated flexible ducts more than the thickness of the insulation.

Support flexible duct (including spot ventilation) at least every 4 feet and do not bend greater than 90°.6. 6.

Support flexible duct (including spot ventilation) at least every 4 feet and do not bend greater than 90°.

Insulate all supply duct work in unconditioned attics to R-8. Insulate all other duct work outside ofconditioned space to R-6.

4.

Copyright ©2014 Advanced Energy. All Rights Reserved • Version 2014.1.A • Page 36

SUCCESS WITH 2012 IECC CODE

COMPRESSION NO COMPRESSION

NO SUPPORT SUPPORT GREATER THAN 90° LESS THAN 90°

UNINSULATED BOOT INSULATED BOOT

HVAC INSTALLATION

TECH TIPS

Page 4: HVAC INSTALLATION - AC SUPPLY CO....HVAC INSTALLATION TECH TIPS 8. Install outside air ventilation intakes at least 10 feet from any exhaust vent or stack. Coordinate bath fan exhaust

8.Install outside air ventilation intakes at least 10 feet from any exhaust vent or stack.

Coordinate bath fan exhaust duct direction with Electrical Contractor.9.

Terminate all exhaust ventilation ducts to the outside. Install screens where applicable.10. 11.

For heat pumps, install a heat strip outdoor temperature lockout that prevents supplemental heat operation and set it to the balance point.

Copyright ©2014 Advanced Energy. All Rights Reserved • Version 2014.1.A • Page 4

SUCCESS WITH 2012 IECC CODE

HVAC INSTALLATION

TECH TIPS

WRONG LOCATION RIGHT LOCATION WRONG DIRECTION RIGHT DIRECTION

WRONG TERMINATION RIGHT TERMINATION DISCONNECTED RIGHT INSTALLATION