HV CIRCUIT BREAKER DEAD TANK TYPE

download HV CIRCUIT BREAKER DEAD TANK TYPE

of 4

Transcript of HV CIRCUIT BREAKER DEAD TANK TYPE

  • 7/28/2019 HV CIRCUIT BREAKER DEAD TANK TYPE

    1/4

    Customer Benefits

    Explosion-proof design

    Special accuracy classes:TPS, TPX, TPY, TPZ, PR

    Mineral & synthetic oil-filled;PCB free

    Low maintenance

    Extensive experience in highly

    active seismic regions

    Compact construction

    Built for long life

    Non-corrosive hardware

    Hermetically sealed for long life

    Stable accuracy over a long

    period of time

    CTHCurrent Transformers72.5 to 765 kV

    T&D

    INSTRUMENT TRANSFORMERS

    For years, tens of thousands of CTH have been

    installed all over the world. In all types of climates

    and under even the most severe conditions, our

    units give complete satisfaction to the most

    exacting customers.

    The CTH operates both as a sensor and an

    essential interface between the high voltage

    transmission network and the low voltage systems.

    The great success of this series is the achievement

    of a very careful design entirely focused towards

    addressing two major goals: security and long life.

    > Metering - Relaying

    > Performance: Un: 72.5 to 765 kV

    In: up to 4800 A

    In short-circuit : up to 80 kA1 (Isc dyn: 200 kA peak)Secondary cores : from 4 to 8

    > Characteristics : High quality paper-oil insulation

    Top core design with metal head

    Oil expansion by stainless steel bellows

    Bellows position indicator

    Secondary cores in aluminum boxSingle, double or triple ratio at the primary side depending

    of the voltage level

    > Compliance with IEC, ANSI / IEEE or equivalent standards

    LIFE TIME

    Excellent field experience confirms the soundness of our technical concepts, and

    our clients have expressed their total satisfaction with our products.

    CTH have been designed for a 30 year life-time but many well out-live this service life.

  • 7/28/2019 HV CIRCUIT BREAKER DEAD TANK TYPE

    2/4

  • 7/28/2019 HV CIRCUIT BREAKER DEAD TANK TYPE

    3/4

    CTH maintains accuracy with minimal maintenance

    during a life-time of at least 30 years.

    INSULATOR

    The head of the current transformer is mounted abovea porcelain insulator suitable for the required voltage

    and environment.

    The standard CTH resists medium intensity seismic

    events. For highly active seismic regions, the design isadapted accordingly (special porcelain insulators,

    damping device at the base of the transformer).

    Custom design options also include the utilization of

    composite insulators which can be quoted on request.

    EXPLOSION-PROOF DESIGN

    In case of an exceptional catastrophic failure (direct

    lightning strike for instance), the CTH current

    transformers reduce considerably the consequences ofsuch failure, thanks to the following designarrangements:

    > Reduced oil volume,

    > Internal ground conductors with sufficient cross

    section for handling the fault current,

    > Tank head designed to prevent projection of parts in

    case of fault,

    > Special design to prevent the transmission, inside

    the porcelain insulator, of the over-pressure wave

    that originates in the head at the time of the fault.

    The efficiency of this design has been tested in various

    laboratories and the porcelain remains intact.

    MAINTENANCE

    The CTH current transformer is a reliable apparatusthat requires only a limited amount of maintenance

    operations. Its role of sensor and interface is essential

    for effective and secure network operation. However,preventive maintenance carried out by experts is

    recommended to ensure the longevity of your

    installations and the safety of your personnel.

    We offer you a full range of services, from preventive

    maintenance, to corrective maintenance to" la carte maintenance" or replacement of material.

    As instrument transformer experts for many decades,you can always count on our expertise and our spare

    parts stock.

    We have the necessary resources to helpyou keep your installations operating efficiently,

    reliably and without risks for your employees

  • 7/28/2019 HV CIRCUIT BREAKER DEAD TANK TYPE

    4/4

    Available versions

    Our policy is one of continuous development. Accordinglythe design of our products may change at any time.Whi lstevery effort is made to produce up to date literature, thisbrochure should only be regarded as a guide and isintended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application of

    any product referred to in it. We cannot be heldresponsible for any reliance on any decisions taken on itscontents without specific advice.

    AREVA T&D Worldwide Contact Centre:

    http://www.areva-td.com/contactcentre/

    Tel.: +44 (0) 1785 250 070

    www.areva-td.com

    VIPREHVB-L3-CTH-GB--

    AREVA-2004.

    AREVA,

    theAREVAlogoandanyalternativeversionthereofaretradem

    arksandservicemarksofAREVA.

    A l l t d t d k t i d h i

    h t h i t d t t h t f t h i P

    i t d i B l i

    According to IEC 60044-1

    ( ) Other value on request.

    Owing to the flexibility of the range of models, there are various available size of the heads. Several metering or

    relaying cores can be accommodated with rated primary current up to 4800 A, and with short circuit withstand

    current up to 80 kA r.m.s. 1 sec. and 200 kA peak. Various type of insulators can be used according to the

    environmental conditions of the site.

    Indicatives values only - All indicated dimensions must be confirmed with order.

    ELECTRICAL CHARACTERISTICS

    Type

    CTH 72

    CTH 100/123

    CTH 145

    CTH 170

    CTH 245

    CTH 300

    CTH 362

    CTH 420

    CTH 550

    CTH 765

    Highest system voltage

    kV r.m.s.

    72,5

    100

    123

    145

    145

    170

    170

    245

    245

    300

    300

    362

    362

    420

    420525 (550)

    525 (550)

    765

    765

    Rated 1 min. 50/60 Hz

    withstand voltage

    kV r.m.s.

    140

    185

    230

    230

    275

    275

    325

    395

    460

    395

    460

    460

    510 (575)

    570

    630 (680)630

    680 (860)

    880

    975

    Rated lightning impulse test

    voltage (BIL) 1.2/50 s

    kV peak

    325

    450

    550

    550

    650

    650

    750

    950

    1050

    950

    1050

    1050

    1175 (1300)

    1300

    1425 (1550)1425

    1550 (1800)

    1950

    2100

    Switching impulse test

    voltage 250/2500 s

    kV peak

    -

    -

    -

    -

    -

    -

    -

    -

    -

    750

    850

    850

    950

    1050

    10501050

    1175

    1425

    1550

    DIMENSIONS

    Type

    CTH 72

    CTH 100CTH 123

    CTH 145

    CTH 170

    CTH 245

    CTH 300

    CTH 362

    CTH 420

    CTH 550

    CTH 765

    TotalHeight

    mm

    2385

    23852385

    2535

    2735

    3470

    3740

    4500

    4500

    5150

    7550

    TotalWeight

    kg

    375

    375375

    385

    380

    445

    475

    850

    850

    1200

    3540

    Oil

    l

    53

    5353

    54

    55

    88

    94

    190

    190

    300

    980

    Min. creepagedistance

    mm

    3075

    30753075

    3625

    4250

    6125

    8250

    10913

    10913

    13425

    19511

    INQUIRY CHECK LIST

    >Applicable standards

    > Rated frequency

    > Highest system voltage

    > Test voltages (power frequency,

    lightning impulse)

    > Primary/secondary rated currents

    > Short time current and duration

    > Core rating (burden, accuracy)

    > Environmental conditions (altitude,

    temperatures, pollution, seismicconditions)

    > Options:

    - Composite insulator

    - Surge arrester on secondary

    winding

    - Ground cable connector- Primary terminal- Damping devices for use in highly

    active seismic regions

    >Available accessories :

    - Tg F tap

    - OIl sampling valve

    - Lifting bar- Oil sampling tools kit

    - Shocks indicators during shipment