Human Perception of Comfort Level BScience

download Human Perception of Comfort Level BScience

of 48

Transcript of Human Perception of Comfort Level BScience

  • 8/13/2019 Human Perception of Comfort Level BScience

    1/48

    1

    BUILDING SCIENCE 1 (ARC 2412)

    Project 1:

    Human Perception of Comfort Level

    The Report

    Muhammad Naim Ahmad Mukif 0303348

    Arif Zakwan Abdul Hamid 0303736

    Muhammad Arif Shafii 0303005

    Sonia Gala Alai Mariam Gerawat 0304827

    Oh Keng Yee 0312501

    Siti Munirah Zazarin 0312710

  • 8/13/2019 Human Perception of Comfort Level BScience

    2/48

    2

    Table of Contents

    Summary.. 3

    Introduction4

    Methodology. 5

    Site Introduction. 8

    Orthographic

    Projections 9

    Results and Analysis

    Raw Data 12

    Bioclimatic Chart.. 17

    Thermal Balance...18

    Ventilation... 22

    Thermal Analysis. 24

    Conclusion.. 43

    References. 44

    Appendix45

  • 8/13/2019 Human Perception of Comfort Level BScience

    3/48

    3

    Summary

    In this project, we are to find the thermal comfortof inhabitants of a certain space. Thermal

    comfort is defined as a feeling of well -being.1To determine this state of well-being, one is affected by

    several factors which can be categorized into personal, measurable environmental, as well as

    psychological influences. In other words, the data collected are both quantitative as well as qualitative.

    A bedroom in an apartment is chosen as the site for this experiment. The quantitative data such as

    temperature and relative humidity (RH) are recorded in the respective room using a thermohygrometer.

    This information is then interpreted into a bioclimatic chart to determine whether or not the resident is

    living in comfort. Other factors used to analyze thermal comfort include human activity and clothing.

    The inhabitants response towards the site (qualitative data) will also be taken into consideration. Apart

    from that, diagrams which illustrate the sun path, wind rose, heat gain and heat loss are also used to

    assist in coming up with a conclusion regarding thermal comfort. Throughout this project, the analyses

    made are all done in reference to the MS 15252; a code of practice evaluating the energy efficiency of a

    building, as well as the Uniform Building By-Laws (UBBL)3.

    1T. Grondzik, W., Stein, B., G. Kwok, A. and S. Reynolds, J. 2010. Mechanical and Electrical Equipment for Buildings. 11th ed. New Jersey: J. Wiley

    & Sons, p. 91-92

    2http://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-System

    3https://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-

    aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=A

    SszZwdsaF3KtxaK

    http://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-System
  • 8/13/2019 Human Perception of Comfort Level BScience

    4/48

    4

    Introduction

    Our chosen site is a bedroom in an apartment unit on the ground floor of Block A, Mutiara

    Perdana located in PJS7, Bandar Sunway. We used a Data Logger to measure the indoor temperature

    and relative humidity levels of chosen room, in which measurements were taken for three consecutive

    days (13thto 16thSeptember). Though the data logger records the temperature and relative humidity

    continuously, for the purpose of this report, we are to analyse the data between 10pm to 6 am for the

    respective days. We then use the results to plot the point of thermal comfort in a bioclimatic chart.

    According to the Malaysian Standard 1525 act, thermal comfort is the condition of mind which

    expresses satisfaction with the thermal environment. Our task is toevaluate the current conditions of

    thermal comfort and propose different strategies that could improve it. Thermal comfort is quite

    difficult to be given an exact value to as it differs from person to person - each person may experience

    comfort at different humidity or temperature levels. Nevertheless, the data and analysis collected in this

    report will surely improve our understanding of thermal comfort, hence allowing us to adapt sustainable

    design strategies.

    Hypotheses

    In this research, we predict and will either prove or disprove that:

    The relationship between temperature and relative humidity is inversely proportional. The chosen unit is cooler than the upper floors and is within the comfort level due to it being on

    the ground floor (prediction based on the idea of shadow cast from upper floors and that the

    fact that hot air rises)

    Limitations

    Human error in handling the data logger Sudden weather change Limited time frame of data collection, hence less variation in data

  • 8/13/2019 Human Perception of Comfort Level BScience

    5/48

    5

    Methodology

    In completing this project, several methods of investigation are carried out. These range from

    sourcing material available online to measuring the data manually.

    Data Logger

    Figure 1: Data Logger

    This instrument is normally used to record several factors which affect thermal comfort (such as, but not

    limited to: air temperature, surface temperature, air motion and relative humidity levels).

    For the purpose of this experiment, the data logger was used to obtain data in the following areas:

    - Relative Humidity (RH) Indoors- Temperature Indoors

  • 8/13/2019 Human Perception of Comfort Level BScience

    6/48

    6

    Its usage is fairly straightforward and steps were taken as follows:

    Figure 2: placement of Data Logger

    1) Set the data logger to the current date and time2) Set to record data at one-hour intervals3) Select to record indoor temperature and relative humidity levels4) Place device in the center of the room at a height of 1m from ground level5) Retrieve data after a period of three days

    Additional data required such as temperature of the site and the relative humidity levels outdoors was

    obtained from meteorological data available on the internet.

    Visual Presentation of Data

    Visual aids were used to clarify the relationship between the data collected. Methods used are as

    follows:

    - Line graphs- Diagrams

  • 8/13/2019 Human Perception of Comfort Level BScience

    7/48

    7

    Figure 3 : Data collected from the Data Logger

    Mainly line graphs were used with the help of tables to compare the data collected across the three day

    period. These graphs were plotted with the data collected both by the data logger and those found

    from meteorological sites online. It is especially effective in conveying the correlation or relationship

    between the different fields of data.

    Figure 4 : Wind Rose Diagram & Heat Loss/Gain Diagram

    For more complex data like the sun path in the area of the site as well as the wind speed, various

    diagrams were used to show the data collected. With regards to the sun path, diagrams produced with

    the program Ecotect proved most effective. When showing wind speed throughout the month, the

    clearest way was to show it through a wind rose diagram.

  • 8/13/2019 Human Perception of Comfort Level BScience

    8/48

    8

    Orthographic Drawings

    The site chosen is a rented unit and as such had no plans available to us. To overcome this, we measured

    the site and produced sketches and drawings to further aid in explaining our results.

    Figure 5 : Site Context & Orthographic Drawings

    Items drawn range from plans to sections as well as elevations.

    Miscellaneous

    Other data without numerical values such as human activities and items of clothing worn were noted

    down to ensure all parts of the experiment were covered.

  • 8/13/2019 Human Perception of Comfort Level BScience

    9/48

    9

    Site Introduction

    The site that we have chosen is located in PJS 7/15,

    Bandar Sunway. PJS is a residential area in an urban

    environment, consisting of mainly flats, apartments and

    terrace houses. Apart from that, there are also schools and

    shop lots to cater for the residents of the area. Due to it

    being of walking-distance to a nearby university, it is an ideal

    choice for student accommodation.

    Looking at Mutiara Perdana apartment specifically, it

    is considered a high-density living space as most of the units

    are occupied.

    Site Context

    The highlighted area in the diagram above illustrates our chosen area of research.

  • 8/13/2019 Human Perception of Comfort Level BScience

    10/48

    10

    Macroclimate

    Malaysia, being an equatorial country experiences high humidity and temperature, with average annual

    temperature of 27C and receives an average rainfall of 2500mm. Having this tropical climate, buildings,

    of course must be designed to suit the climate in order to achieve maximum thermal comfort. Due to it

    being warm all-year round, it is an ideal design consideration to keep the building cool, rather than to

    heat it. Without doubt, electrical methods of cooling such as air-conditioning or using a fan are effective

    ways to cool a space. However, natural factors such as wind ventilation, smart choices of building

    materials can help buildings offer better comfort in hot climates more sustainably.

    Microclimate

    The following table displays site-specific climate information.

    Day1 2 3

    Highest Lowest Mean Highest Lowest Mean Highest Lowest Mean

    Outdoor RH (%) 100 94 95.3 100 84 92.4 94 74 86.2

    Indoor RH (%) 74.4 72.8 73.8 74.4 74.1 74.2 71.6 43.4 54.6

    Outdoor Temperature (C) 26 25 25.4 25 24 24.6 27 24 25.4

    Indoor Temperature (C) 29.6 28.9 29.3 30.4 29.1 29.7 29.4 25.6 27.5

    From this table, we can see that indoor temperature is always higher than the temperature outside. On

    the other hand, the indoor relative humidity is lower than that of the outdoors.As mentioned earlier,

    Malaysia has an average annual temperature of 27C. In this table, however, it is observed that mean

    outdoor temperature is 25C. This will be further analyzed in the report.

    Meteorological data of PJS7, Bandar Sunway, Subang Jaya

  • 8/13/2019 Human Perception of Comfort Level BScience

    11/48

    11

    Orthographic Projections

    The following are orthographic

    projections generated to assist us inanalyzing thermal comfort.

  • 8/13/2019 Human Perception of Comfort Level BScience

    12/48

    12

    Results and Analysis

    Raw Data Collected

    DAY 1Time Indoor RH (%) Outdoor

    RH (%)

    Indoor

    Temperature

    (C)

    Outdoor

    Temperature

    (C)

    External

    Conditions

    22:00:21 72.8 94 29.6 25 Passing

    clouds /

    warm

    23:00:24 73.2 100 29.5 25 Passing

    clouds /

    warm

    0:00:27 73.7 94 29.4 26 Passing

    clouds /warm

    1:00:30 73.9 100 29.4 26 Passing

    clouds /

    warm

    2:00:33 73.9 94 29.3 26 Passing

    clouds /

    warm

    3:00:36 74 94 29.2 26 Passing

    clouds /

    warm

    4:00:40 74.2 94 29.1 25 Passing

    clouds /

    warm

    5:00:43 74.4 94 29 25 Partly sunny

    / warm

    6:00:46 74.4 94 28.9 25 Partly sunny

    / warm

  • 8/13/2019 Human Perception of Comfort Level BScience

    13/48

    13

    DAY 2

    Time Indoor RH (%) Outdoor RH

    (%)

    Indoor

    Temperature (C)

    Outdoor

    Temperature (C)

    External Conditions

    22:00:35 74.2 84 30.4 25 Light rain

    23:00:38 74.3 84 30.1 25 Mostly cloudy /

    warm

    0:00:41 74.2 94 29.9 25 Partly cloudy /

    warm

    1:00:45 74.2 94 29.8 25 Partly cloudy /

    warm

    2:00:48 74.2 100 29.6 25 Partly cloudy /

    warm

    3:00:51 74.1 94 29.5 24 Partly cloudy / mild

    4:00:54 74.1 94 29.4 24 Partly cloudy / mild

    5:00:57 74.3 94 29.2 24 Partly cloudy / mild

    6:00:00 74.4 94 29.1 24 Passing cloud / mild

  • 8/13/2019 Human Perception of Comfort Level BScience

    14/48

    14

    DAY 3

    Time Indoor RH

    (%)

    Outdoor RH

    (%)

    Indoor Temperature

    (C)

    Outdoor

    Temperature

    (C)

    External Conditions

    22:00:50 71.6 74 29.4 27 Partly cloudy / warm

    23:00:53 66.3 79 27.7 27 Broken clouds /

    warm

    0:00:56 59.1 84 27.3 26 Partly cloudy / warm

    1:00:59 56.4 84 28.1 26 Partly cloudy / warm

    2:00:02 49.4 84 26.7 26 Partly cloudy / warm

    3:00:05 48.6 89 27.4 25 Partly cloudy / warm

    4:00:08 49.1 94 27.3 24 Partly cloudy / mild

    5:00:11 43.4 94 25.6 24 Partly cloudy / mild

    6:00:14 47.8 94 27.6 24 Partly cloudy / mild

  • 8/13/2019 Human Perception of Comfort Level BScience

    15/48

    15

    Based on the raw data collected, a graph is produced to observe the patterns of thermal comfort

    throughout the three days.

    Day 1 2 3Highest Lowest Mean Highest Lowest Mean Highest Lowest Mea

    Outdoor RH (%) 100 94 95.3 100 84 92.4 94 74 86.2

    Indoor RH (%) 74.4 72.8 73.8 74.4 74.1 74.2 71.6 43.4 54.6

    Outdoor Temperature (C) 26 25 25.4 25 24 24.6 27 24 25.4

    Indoor Temperature (C) 29.6 28.9 29.3 30.4 29.1 29.7 29.4 25.6 27.5

    An analysis of the data over the three days is fairly regular with the exception of the third day being an

    anomaly. Looking at the mean values calculated, it can be observed that the indoor humidity levels and

    temperature are affected by the state of humidity and temperature outside the room although they are

    not in direct correlation. There was rainfall recorded on the second day at roughly 01:00 hours. This

    accounts for the spike in humidity on the second day, and the subsequent decrease in relative humidity

    levels after. This will be further explained below.

  • 8/13/2019 Human Perception of Comfort Level BScience

    16/48

    16

    Based on various findings, rainfall leads to a drop in temperature but an increase in relative humidity

    levels. After the rain however, humidity levels tend to drop as moisture in the air evaporates, forming

    rainclouds. This subsequently leads to more rain. Of course this is only a very basic explanation on the

    effect of humidity levels on rain, there are many other factors to consider.

    Rainfall occurs on day two, in line with the spike in relative humidity levels outdoor. The temperature

    outdoor is also seen to drop during this time. After a whole day, the moisture in the air is assumed to

    have evaporated as the humidity levels drop drastically. This assumption is further reinforced by the

    increase in temperature, showing the absence of rain on day three.

    The trend of the graph for outdoor humidity is more erratic throughout the three days but the value

    maintains on the high side. This is not reflected on the indoor humidity levels as the graph shows a

    stable reading for the first two days. On the third day, the indoor humidity decreases drastically as the

    user spent less time in the room compared to the first two days. This also accounts for the drop in

    indoor temperature.

    In terms of temperature, however, the outdoor temperature was constant, hovering around the 25C

    mark all three days. The indoor temperature was significantly higher indoors, a good 4C increase

    compared to the temperature outside the building. The windows of the building were noted to be open

    during the day and closed during the night, which is the period the experiment was conducted. The

    closed windows prevented cross ventilation and could be the cause of increased indoor temperature.

    The users room is located on the ground floor and the building it is located in is surrounded by various

    other buildings, so the wind flow is limited compared to those on a higher floor. This could have also

    contributed to the increase in indoor temperature.

    Indoor

    Temperature

    (C)

    Indoor

    Relative

    Humidity

    (RH) (%)

    Outdoor

    Temperature

    (C)

    Outdoor

    Relative

    Humidity (RH)

    (%)

    DAY 1 29.27 73.83 25.44 95.33

    DAY 2 29.67 74.22 24.56 92.44

    DAY 3 27.46 54.63 25.44 86.22

    Mean 28.8 67.56 25.15 91.33

  • 8/13/2019 Human Perception of Comfort Level BScience

    17/48

    17

    Bioclimatic Chart

    Indoor Bioclimatic Chart

    From the intersection of the line, it is understood that the inhabitant is outside the comfort zone most

    of the time probably due to high humidity percentage and temperature. The cause of such conditions

    could be the low efficiency of the rooms ventilation system, asthe room is only fitted with one window.

    Other factors include the furnishing and the building materials used in the room. The window was shut

    and covered by a curtain throughout the data recordings. The window is fitted with tempered glass - thiskeeps heat from escaping, therefore slows down heat loss. This is one of the contributing factors to the

    high indoor temperature. Humidity levels are moderately high due to the fact that is not well-ventilated

    (i.e. closed windows) during the night. Nevertheless, in the MS 1525, it is stated that the RH for indoor

    comfort condition should not exceed 70%. Based on this requirement, the RH in the room is tolerable

  • 8/13/2019 Human Perception of Comfort Level BScience

    18/48

    18

    Sun Path Analysis

    Site Plan N.T.S

    As seen in the site plan, the building selected is surrounded by other buildings and parking lots. The lack

    of nature in this scenario contributes to the high indoor temperature readings obtained by the data

    logger. However, the surrounding buildings provide a certain amount of shade at various times during

    the day.

    Figure E: Sun path simulation of building at 09:00 hours, September 15th

    , 2013

    Chosen Unit

  • 8/13/2019 Human Perception of Comfort Level BScience

    19/48

    19

    Figure E shows that the shadow casts provided by the surrounding blocks at 09:00 hours are mainly for

    the side of the building. The length of shadow cast is fairly short but sufficient to shade the various

    openings.

    There are openings located on the North-West, North-East and South-West side of the building. The

    frequencies of these openings are the same for every floor. The South side is attached to the

    neighboring block and as such has no visible openings. This prevents heat from entering from this

    direction but also blocks any heat from escaping from here.

    The morning sun does not reach any of the openings of the unit. The unit in front of and adjacent to the

    chosen site is protected and hence is not subjected to the morning sun. Hence, it is assumed that theunit is not affected by the morning sun.

    Figure F : Sun path and shadows at 12:00 hours, September 15th2013

    The unit is exposed to more sunlight as the sun peaks at mid-day. The South-West wall of the room is

    exposed to the full blast of the afternoon sun. The intensity of the afternoon sun penetrates the walls

    and will cause an increase in the indoor temperatures of the room. The North-Western wall however

    has slight coverage from the presence of an awning.

  • 8/13/2019 Human Perception of Comfort Level BScience

    20/48

    20

    North Western wall

    Figure G : Sun Path and shadowing of unit at 16:00 hours, September 15th

    2013

    At 16:00 hours, the chosen unit is exposed to direct sun light on the north western wall which contains a

    window and a small awning. The presence of said awning cuts down the amount of sunlight penetrating

    the building at the given time. Due to its location, the kitchen sits in the shadow of the surrounding

    buildings.

  • 8/13/2019 Human Perception of Comfort Level BScience

    21/48

    21

  • 8/13/2019 Human Perception of Comfort Level BScience

    22/48

    22

    Sun Path Diagrams throughout the Year

    March 15

    th

    9am March 15

    th

    12pm March 15

    th

    4pm

    July 15th

    9am

    July 15th

    12pm

    July 15th

    4pm

    September 15th

    9am

    September 15th

    12pm

    September 15th

    4pm

  • 8/13/2019 Human Perception of Comfort Level BScience

    23/48

    23

    Wind Analysis

    Based on the diagram, throughout the month of

    September, typical wind speed varies from 10 km/h to

    55 km/h. The lowest wind speed is at 10km/h with a

    high frequency that occurred for less than an hour. As

    for the highest wind speed, it is 55km/h with also a

    high frequency. According to the highest wind speed,

    the wind flows from two directions North West to

    South East and North to South. The average of wind

    speed is about 30km/h. Prevailing North West to South

    East, the wind flows directly into the unit through the

    entrance facing the West and the wind movement

    escapes through the back where the toilet is facing the

    East.

    Wind rose diagram on site map

    The Wind Rose Diagram

  • 8/13/2019 Human Perception of Comfort Level BScience

    24/48

    24

    The figure above indicates that the major wind flows from two directions which are, from North West to

    South East and from North to South. As the direction of the wind flows from the main entrance and the

    security guard post, the wind tends to be warmer coming from the main road near the main entrance.

    However, the wind is less warm from the security guard post towards Block A whilst the guard post is

    partly surrounded by trees and shrubs.

    Wind flow around site

  • 8/13/2019 Human Perception of Comfort Level BScience

    25/48

    25

    Ventilation

    The presence of opening at different sections of the unit promotes air movement, which, in turn,

    increases thermal comfort of a user. This is due to the replacement of air that occurs during crossventilation.

    Cross Ventilation in the unit shown on plan

    As a new batch of cool air enters the unit from one side of the unit, the stale, warmer air is pushed out

    another, usually located opposite the window fresh air entered. This exchange causes movement in the

    air, thereby reducing humidity significantly and causing an increase in human thermal comfort.

  • 8/13/2019 Human Perception of Comfort Level BScience

    26/48

    26

    Section showing the flow of air with the red arrow representing warm air, and the blue, cold.

    The basic gist of things is that hot air rises. There will always be a certain amount of air that is warmer in

    relation to its surroundings, hence, air movement will always occur. The key in determining thermal

    comfort is the degree of air movement in a given place. The movement of hot air to the top and cold to

    the bottom is commonly known as heat convection. This phenomenon is further promoted by air

    movement. In general, the higher the degree of air movement, the higher the degree of heat convection,

    and in turn this contributes to an increase in thermal comfort.

    Due to the lack of air movement in the case study, thermal comfort is on the lower end of the spectrum

    as the speed at which heat convection occurs is low. The hot air rises at a slow pace and heat is dispelled

    out of the unit slower. This causes a rise in temperature inside the unit.

  • 8/13/2019 Human Perception of Comfort Level BScience

    27/48

    27

    The opening in the kitchen facing East is the main opening of the unit. However, due to the positioning

    of the building, air flow is blocked by the surrounding buildings and as such air movement is hindered.

    This causes poor air circulation even though the window is left open.

    LeftRight : Opening located in kitchen. Opening located in bathroom.

    While the window in the bathroom is also left open most of the time, the bathroom door is closed. This

    is a fairly common practice amongst Malaysians today as doors are kept closed whenever possible due

    to safety reasons. These shut doors become and obstacle for air movement and prevent optimal cross

    ventilation to occur. The result is a stuffy home, one that is humid and slightly warm. Thermal comfort is

    at a low point.

  • 8/13/2019 Human Perception of Comfort Level BScience

    28/48

    28

    Thermal Balance

    To be in a state of thermal balance, the heat loss must equate to the heat gained by the occupant. Of

    course one must take into account the psychrometric qualities that affect thermal comfort but for thepurpose of this section, they will be assumed to be constant for all.

    Thermal Heat Transfer

    Solar Radiation

    Heat is transferred to an occupant through various ways. In the tropical climate of Malaysia, solar

    radiation is a major factor of heat transfer. It is essentially electromagnetic energy that travels in the

    form of light and heat. In the case study, the window in the kitchen faces East. This causes the kitchen to

    receive the full brunt of the morning sun. Despite the presence of awnings, the temperature in the unit

    increases due to exposure to direct sunlight. The lack of casement windows also contribute to overall

    hermal discomfort in the unit, especially from 08:00 hours to 12:00 hours

  • 8/13/2019 Human Perception of Comfort Level BScience

    29/48

    29

    Thermal Radiation

    This is the heat produced by objects while being in use. These objects radiate heat that add to the

    thermal heat transfer equation. Everyday items, especially those of electronic nature, causes heat gain

    to the occupant of the unit.

    These items include, but are not limited to:

    - Wifi Routers- Desktop Computers- Lighting units

  • 8/13/2019 Human Perception of Comfort Level BScience

    30/48

    30

    Cross-Ventilation

    Based on the wind rose diagram, it is observed that the location of the building causes the bedroom to

    receive maximum wind exposure as the highest wind velocities come from the north-west (which is the

    direction the bedroom window faces). To evaluate the effect of cross-ventilation on thermal comfort,

    the MS 1525 is referred to. Clause 4.6.1 states the following design recommendations:

    a) Orientate the building to maximize surface exposure to prevailing winds

    b) Provide inlets on the windward side (pressure zone) and outlets on the

    leeward side (suction zone).

    c) Use architectural features like wing walls and parapets to create positive

    and negative pressure areas to induce cross ventilation.

    d) Provide openings on opposite walls for optimum cross ventilation

    effectiveness. However, if this is not possible, openings can be placed on

    adjacent walls.

    e) Make openings easily accessible and operable by the occupants.f) Avoid obstructions between inlets and outlets

    g) Have equal inlet and outlet areas to maximize airflow

    h) Make outlet openings slightly larger than inlet openings to produce higher

    air velocities

    i) Locate outlet openings on the windward side at the occupied level

    inlet

    outlet

  • 8/13/2019 Human Perception of Comfort Level BScience

    31/48

    31

    Looking at the recommendations above, there are some factors that are present in the chosen bedroom,

    and there are factors that are not. For instance, clause 4.6.1(a) mentions the orientation of the building

    to achieve maximum thermal comfort. Based on our wind rose diagram, this is successfully achieved.

    Clause 4.6.1(d) is also successfully represented in the room, which is that openings should be placed onopposite walls. In our case, the bathroom window is parallel to the bedroom window, hence increases

    thermal comfort.

    An example where the design features of the room do not coincide with MS 1525 is in clause 4.6.1(h). It

    is recommended that outlet openings should be slightly larger than inlet openings to increase thermal

    comfort. In the case of the chosen room, it is the other way round. Thus, a design proposal to increase

    thermal comfort would be to increase the number of inlets and outlets to maximize airflow in the room.

  • 8/13/2019 Human Perception of Comfort Level BScience

    32/48

    32

    Material Analysis

    Table 1.0 : Thermal Conductivity of Materials in the Room

    The different materials used in the room depict different thermal performances (Table 1) that can

    affect the thermal condition of the space within the building. Processes of heat transfer such as

    conduction, convection and radiation in materials are explained as follows.

    Materials

    Component Material Thermal Conductivity (W/mK)

    Walls Concrete (general) 1.28

    Windows Laminated Glass 0.93

    Window Frames Aluminium 237

    Tiles Ceramic 1

    Door Plywood 0.16

    Ceiling Gypsum 0.16

  • 8/13/2019 Human Perception of Comfort Level BScience

    33/48

    33

    K-Value : Thermal Conductivity

    A value that measures the speed of thermal conductivity across any given material. This is

    affected by the density of the material.

    The denser a material, the higher the K-Value.

    A higher K-Value translates to being a good conductor of heat. Conversely, materials with low K-

    Values are said to be good insulators of heat.

    Based on the collected information and what is understood of the K-Value, it is seen that the component

    in the room that conducts the most heat are the aluminium window frames with a K-Value of 237,

    followed by the masonry walls with a K-Value of 1.28. The components which conduct the least heat are

    the plywood door and gypsum ceiling which both have a K-Value of 0.16.

    From this information, it can be concluded that aluminium is not the best material choice due to its high

    conductivity, which decreases thermal comfort. A design proposal to improve thermal comfort would be

    to use a less conductive material, such as a PVC window frame.

    It is worth noting that the furnishings used in the room, such as a bamboo mat and polyester curtains

    may have affected thermal comfort, though not greatly.

    R-Value : Thermal Resistance

    A value used to measure the thermal resistance of a particular material.In general, the higher the R-value of a material, the higher the thermal insulation it provides.

    R = X/K

    SI unit = m2K/W

    R = Thermal Resistance (m2K/W)

    X= Thickness of the Materials (m)

    K = Thermal Conductivity of the Materials

    Materials

    Component Material R-Value

    Walls Concrete (general) 0.12

    Windows Laminated Glass 0.02

    Window Frames Aluminum 0.0003

    Tiles Ceramic 0.01

  • 8/13/2019 Human Perception of Comfort Level BScience

    34/48

    34

    A quick tabulation of the R-Value of building materials used show how well these materials resist

    heat. In line with our findings when calculating the K-Value, aluminum is not the best choice forwindow frames in terms of thermal resistance. The R-Value of aluminum is incredibly low,

    highlighting its vulnerability in absorbing, and conversely, dispelling heat to the environment.

    From the table it is seen that the laminated glass and ceramic are in the same category in terms of

    providing thermal insulation whereas plywood and concrete prove to be more efficient in this

    category. The highest value, however, goes to gypsum with a staggering 1.875 R-Value.

    Overall, most materials selected for the building has a low R-Value. This means that the building

    has low thermal insulation and is not efficient in terms of energy saving. Not only does this result

    in more energy spent to cool the place(with the use of fans and air-conditioning), it also causes a

    loss of uniformity in temperature from the floor to ceiling height.

    This in turn will cause a rise in temperature, increase in relative humidity levels and ultimately, a

    decrease in human thermal comfort.

    U-Value : Heat Transfer

    A value that measures the amount of heat transferred through a building over a pre-determined

    area.

    U=1/R

    SI unit = W/(m2K)

    Door Plywood 0.25

    Ceiling Gypsum 1.875

    Materials

    Component Material U-Value

    Walls Concrete (general) 8.33

    Windows Laminated Glass 50

    Window Frames Aluminium 3333.3

    Tiles Ceramic 100

    Door Plywood 4

    Ceiling Gypsum 0.53

  • 8/13/2019 Human Perception of Comfort Level BScience

    35/48

    35

    The U-Value is the inverse of the R-Values found earlier in the report. Thus, it can be concluded

    that the lower the U-Value, the better the thermal insulation provided by the material.

    Findings are in line with that of the R-value. The ranking of thermal insulation, with the worst

    lined first, is as follows:

    Aluminium < Ceramic < Laminated Glass < Concrete < Plwood < Gypsum

    However if we look at the data collectively, it can be assumed that the overall U-value of the

    building is on the higher end. This brings us to the conclusion that the building is not well

    insulated.

  • 8/13/2019 Human Perception of Comfort Level BScience

    36/48

    36

    Table 1.0 : Thermal conductivity and densities of common building materials.

  • 8/13/2019 Human Perception of Comfort Level BScience

    37/48

    37

    Convection

    The transfer of heat, applicable in the liquid and gaseous states. Particles in these two states

    travel in the Brownian Motion, ie, particles are free to move randomly and collide with one

    another. Heat is transferred from one molecule to another during these collisions.

    Conduction

    The transfer of heat, only applicable to solids. Heat transfers across molecules, generally from a

    cooler region to a warmer region when the particles vibrate against one another.

    Radiation

    The transfer of heat across a vacuum. Solar radiation is an example of this.

    The Stefan Boltzmann law is a formula that calculates radiation of a material.

    Q = (5.673x 10-8) x E x T4

    Q = Radiation emitted by the surfaceE= Emissivity (amount of radiation by a surface compared to a black body at same temperature)T= Surface temperature (

    oC)Constant = 5.673 x10-8 W/m

    2K4

    The radiation emitted by a material is directly proportional to the emissivity and temperature of a

    surface. In simpler terms, if the surface temperature and the emissivity is high, the material will

    radiate heat to its surroundings.

  • 8/13/2019 Human Perception of Comfort Level BScience

    38/48

    38

    Table 2.0 : Table showing the emissivity of various materials

    Thermal Capacity

    The measure of the amount of heat stored by a material from its surroundings.

    The higher the volume and density of a material, the higher its thermal capacity.

    Thermal Capacity =Volume .density . specific heat (J/kg.K)

    SI unit = J/K.m3

  • 8/13/2019 Human Perception of Comfort Level BScience

    39/48

    39

    Table 3.0 : Density, specific heat capacities and thermal conductivity of common building

    materials

  • 8/13/2019 Human Perception of Comfort Level BScience

    40/48

    40

    Other Factors Affecting Thermal Comfort

    Note: There were three occupants in the room on this day.

    Note: The inhabitant was not at home on this day.

    DAY 1

    Time Clothing

    Ensemble

    Clothing Value Human Activity Metabolic Rate

    (W/m2)

    22:00:21 Trousers, short-sleeve shirt

    0.57 Resting -Seated,quiet

    60

    23:00:24 Trousers, short-

    sleeve shirt

    0.57 Resting -

    Reclining

    45

    0:00:27 Trousers, short-

    sleeve shirt

    0.57 Resting -

    Reclining

    45

    1:00:30 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    2:00:33 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    3:00:36 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    4:00:40 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    5:00:43 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    6:00:46 Trousers, short-

    sleeve shirt

    0.57 Resting - Sleeping 40

    DAY 2Time Clothing

    Ensemble

    Clothing Value Human Activity Metabolic Rate

    (W/m2)

    22:00:35 - - - -

    23:00:38 - - - -

    0:00:41 - - - -

    1:00:45 - - - -

    2:00:48 - - - -

    3:00:51 - - - -

    4:00:54 - - - -

    5:00:57 - - - -

    6:00:00 - - - -

  • 8/13/2019 Human Perception of Comfort Level BScience

    41/48

    41

    As there was very little variation in the clothing ensemble and activities carried out, we felt

    that they do not highly affect our research.

    DAY 3

    Time Clothing

    Ensemble

    Clothing Value Human Activity Metabolic Rate

    (W/m

    2

    )

    22:00:50

    Trousers, short-

    sleeve shirt

    0.57 House Cleaning 115-200

    23:00:53

    Trousers, short-

    sleeve shirt

    0.57 Reading, seated 60

    0:00:56

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    1:00:59

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    2:00:02

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    3:00:05

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    4:00:08

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    5:00:11

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

    6:00:00

    Trousers, short-

    sleeve shirt

    0.57 Resting -

    Sleeping

    40

  • 8/13/2019 Human Perception of Comfort Level BScience

    42/48

    42

    Standard Building Design

    In accordance with the Malaysian UBBL, the building design has to take into account the thermal

    comfort of occupants. The building chosen was analyzed to investigate if it fit into the standard building

    design highlighted in the UBBL. Findings are as follows:

    Clause 39 : Natural Lighting and Ventilation

    The number of openings in a building is dictated by its floor area. UBBL states that natural ventilation

    and lighting provided must be more than 10% of the total clear floor area. Such openings are also

    required to have an uninterrupted air flow no less than 5% of the floor area.

    Figure 3.11: Openings in Elevation

    Total area of windows and doors = 4.09 m2

    Area of clear floor with data logger = 7.5 m2

    Natural lighting and ventilation (%) = 4.09/7.5 X 100%

    = 54.5%

    Figure 3.13: Area of clear floor with

    data logger

  • 8/13/2019 Human Perception of Comfort Level BScience

    43/48

    43

    2. Clause 42 : Minimum area of rooms

    Using the UBBL as reference, the minimum width of a room has to be no less than 2 meters for it to be

    considered to be habitable.

    Note that the room chosen room has a width of 4.57m.

    3. Clause 44(1)(a) Height of rooms in residential buildings

    The minimum height of a room in residential buildings is 2.5 meters, as stated in the UBBL. The

    measured height of the chosen room is 2.8m, a clear 0.3m more than the minimum requirement.

  • 8/13/2019 Human Perception of Comfort Level BScience

    44/48

    44

    Conclusion

    To conclude the project, we have discovered that the inhabitant of the space is not living within the

    comfort zone. Based on bioclimatic chart and the MS 1525, it is evident that to achieve better thermal

    comfort, the indoor temperature as well as relative humidity has to be of a lower value. Ways that this

    can be achieved is by improving the cross-ventilation in the building. For example, the addition of

    windows may help achieve this. Also, the choice of materials can be improved. We suggest that PVC

    window frames to be used instead of the existing aluminium ones.

    A positive factor that contributes to thermal comfort is the positioning of the building. Based on our

    wind analysis, we have discovered that the buildings orientation allows maximum wind velocity to enter

    the room.

    There were several limitations to the project, especially in terms of data collection. Firstly, there was alack of human activities, thus it did not show much variation in data. A way in which we could have

    improved on this was to carry out different activities to show how the metabolic rate affects our

    investigation.

    During the days of data recording, we felt that the weather was not constant during the hourly intervals.

    For example, on the three days, there were thunderstorms, cloudy days and sunny days. These random

    occurrences may have affected the results. To add to that, the time frame given in this project was

    limited, which was from 10pm to 6am. We feel that if we had analyzed the whole day instead, more

    patterns of data can be obtained. Finally, we were not familiar with the use of the device; the data

    logger. We feel that our limited knowledge on the device may have delayed our progress during the

    research.

  • 8/13/2019 Human Perception of Comfort Level BScience

    45/48

    45

    References

    Aquino, M. (n.d.). Weather in Malaysia. Retrieved from

    http://goseasia.about.com/od/malaysia/a/wmalaysia.htm

    T. Grondzik, W., Stein, B., G. Kwok, A. and S. Reynolds, J. 2010. Mechanical and Electrical Equipment for

    Buildings. 11th ed. New Jersey: J. Wiley & Sons, p. 91-92

    http://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-

    System

    https://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-

    aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=138065827

    1&hash=ASszZwdsaF3KtxaK

    http://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttps://attachment.fbsbx.com/file_download.php?id=208902282617111&eid=ASu-aRbwshg2z2p9zETyZYMX1Ci5g7HRHIzCCbqEOb25q1EEDKdxXggiKagUk2zSP68&inline=1&ext=1380658271&hash=ASszZwdsaF3KtxaKhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-Systemhttp://www.docstoc.com/docs/37865664/GREEN-BUILDING-INDEX-MALAYSIA-MS-1525-2007-ACMV-System
  • 8/13/2019 Human Perception of Comfort Level BScience

    46/48

    46

    Appendix

  • 8/13/2019 Human Perception of Comfort Level BScience

    47/48

    47

  • 8/13/2019 Human Perception of Comfort Level BScience

    48/48