CIGRÉ Training Day 2 nd December 2015 EI, Dublin Slide 1 CIGRÉ - Irish National Committee How measured data is being used to help Operate the transmission network Ciarán Geaney EirGrid | Power System Protection & Metering

Transcript of How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation...

Page 1: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 1 CIGRÉ - Irish National Committee

How measured data is being used to help Operate

the transmission network

Ciarán Geaney

EirGrid | Power System Protection & Metering

Page 2: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 2 CIGRÉ - Irish National Committee

• Introduction

• Phasor Measurement Unit

• Timelines & Statistics

• System Overview

• Current Uses & Analyses

• Potential Uses

• Events Detected

• December 2014 Oscillation

Introduction

Page 3: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 3 CIGRÉ - Irish National Committee

Phasor Measuring Unit

eMSNI sub.net Disturbance Recorder

• Meets IEEE C37.118 Synchrophasor Standard

• Streams 3 Voltage Phasors, 3 Current Phasors &

Frequency @ 50 samples/second (20ms / 50Hz)

• Data is GPS time stamped with microsecond accuracy

• Communication is via Ethernet connection to secure

comms network.

• Each device can monitor 2 circuits/feeders

• PMUs installed on high accuracy EirGrid energy

metering cores (0.2% accurate)

• Calibration/Certification process in place

Page 4: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 4 CIGRÉ - Irish National Committee

Timelines & Statistics

• Pilot project completed in 2011

• Tendered solution installed Jan 2013

• In use in Control Centres by Jan 2014

• 39 PMUs actively streaming

Three-phase currents, voltages, frequency at 50 Hz

27 in EirGrid at 19 locations

12 PMUs in SONI at 5 locations

• All streaming PMUs are installed on revenue metering

check cores. CTs, VTs and PMUs are all revenue

metering-class (0.2% accurate)

• PMU calibration/certification process in place

• Two-years of historical data available on-line

(terrabytes of data)

• Many generator oscillations, wide-area events

detected

• Currently have a further 40+ PMUs installed and

operating as standalone disturbance recorders PMU

Standalone Disturbance Recorder

Page 5: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 5 CIGRÉ - Irish National Committee

System Overview

Databases Client Tools Interface Nodes

Comms Networks

Data Sources

Dedicated Display Viewer & Builder

Web Browser

Viewer

MS Excel Add-In

Analysis & Notifications Toolbox

Data Historian PMU’s

Private WAN #1

Private WAN #2

Private WAN #3 Data Collector #2

Data Collector #1

Asset Database

Private WAN #4

PMU’s

PMU’s

PMU’s

Voltage, Current & Frequency

sampled at 50 Hz.

GPS time-stamped.

Data transmitted to central PDC

(IEEE C37.118)

Concentrated data stored in

corporate servers

Power calculations executed

Data stored for ~ 2 years

(> 2.5 GB / day)

Client tools for viewing &

crunching the data

Page 6: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 6 CIGRÉ - Irish National Committee

• Generator oscillation detection & notification

Fourier analysis on real power output from each monitored unit

• Frequency oscillation detection & notification

Fourier analysis on frequency at a Dublin location & Cork location (backup)

Fourier analysis on frequency at location in SONI

• Phase angle monitoring

• Frequency event detection & notification

• Island detection & notification

• Voltage dip detection and notification

• Model validation

• Post event fault analysis

Current Uses & Analyses

Page 7: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 7 CIGRÉ - Irish National Committee

• Generator Testing

Currently ongoing but could be expanded

• Blackstart Testing

• Near Real-time calculations

Performance Monitoring Applications

Live Trends of Generator Response Vs. Expected/Ideal Response

• System Separation/Synchronisation Events

Real-time phase angle difference

• Automated Customer Reporting following events

• Integration with SCADA/EMS for smarter analyses

Potential Uses

Page 8: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 8 CIGRÉ - Irish National Committee

• Transfomer Energisation at 17:24:42

• Voltage dipped from 235 kV to 224 kV due to inrush

• CCGT unit reacted and began oscillating ~200 MW at 1.2 Hz

Events Detected (1)

391.88

MW

50.03

Hz

Real Power Frequency

17:25:10 17:25:05 17:25:00 17:24:45 17:24:40 17:24:35

15/01/2014 17:25:15Real Power (green) Vs Frequency (blue)

250.00

300.00

350.00

400.00

450.00

500.00

550.00

49.98

50.00

50.02

50.04

50.06

50.08

50.10

-28.83

MVAr

1.07

Reactive Power %..\..\.%

17:25:10 17:25:05 17:25:00 17:24:45 17:24:40 17:24:35

15/01/2014 17:25:15Reactive Power (green) Vs pu Voltage (blue)

-60.00

-40.00

-20.00

0.00

20.00

40.00

60.00

1.01

1.02

1.03

1.05

1.06

1.07

1.08

Page 9: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 9 CIGRÉ - Irish National Committee

• CCGT tripped from 400 MW near Dublin

• Frequency dipped to 49.25 Hz and returned to 49.9 Hz within six seconds

• Another CCGT provided correct MW reserve, but large MVAr swing

• Dublin voltage was ok, Cork Voltage swung from 236 kV to between 223 kV and

252 kV

• Synchrosphasor System summarised the event and issued email notifications

Events Detected (2)

219.997

MW

49.88

Hz

Real Power Frequency

4:10:25 4:10:20 4:10:15 4:10:10 4:10:05 4:09:55 4:09:50 4:09:45 4:09:40 4:09:35

06/05/2013 04:10:30Active Power (green) Vs Frequency (blue)

180

190

200

210

220

230

240

49.2

49.35

49.5

49.65

49.8

49.95

50.1

115.949

MVAr

1.07704

Reactive Power

4:10:25 4:10:20 4:10:15 4:10:10 4:10:05 4:09:55 4:09:50 4:09:45 4:09:40 4:09:35

06/05/2013 04:10:30Reactive Power (green) Vs pu Voltage (blue)

-50

0

50

100

150

200

250

1

1.02333

1.04667

1.07

1.09333

1.11667

1.14

Page 10: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 10 CIGRÉ - Irish National Committee

• 2½ hour trend on Wednesday 12th of February 2014 showing ~95 trips

during the heights of Storm Darwin.

238.3

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Longpoint 220 kV

150.0

190.0

210.0

250.0 283.7

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Coolkeeragh 275 kV

280.0

282.0

283.0

284.0

286.0

401.8

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Moneypoint 400 kV

375.0

385.0

395.0

405.0

415.0 115.6

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Shannonbridge 110 kV

104.0

109.0

114.0

118.0

287.1

kV L-L

13:30 13:00 12:30 12:00

Ballycronan More 275 kV

282.0

284.0

286.0

289.0

235.5

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Irishtown 220 kV

222.0

227.0

232.0

240.0

282.2

kV L-L

13:30 13:00 12:30 12:00

12/02/2014 14:00:00Louth 275 kV

274.0

278.0

280.0

282.0

286.0

1.04

1.03

1.08

1.07

1.04

13:30 12:00

12/02/2014 14:00:00Per Unit Vol tages

0.65

0.85

0.95

1.15

Events Detected (3)

Page 11: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 11 CIGRÉ - Irish National Committee

• Suspect device

discovered under

Louth – Tandragee

275 kV tower

• Systems were split

in a planned

manner as a

precaution.

• Frequencies were

balanced with

SONI slightly

higher than

EirGrid

• Sync Scheme at

Tandragee worked

as planned

System Separation &

Re-Synchronisation

Page 12: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 12 CIGRÉ - Irish National Committee

Oscillation & Trip

• Generator oscillation and consequent tripping due to issue with a gas valve

-5.41026

MW

49.9846

Hz

Real Power Frequency

4:44 4:43 4:42 4:41 4:40 4:38 4:37 4:36 4:35 4:34

17/06/2014 04:45:00Active Power (green)

-60

-40

-20

0

20

40

60

80

100

49.88

49.9

49.92

49.94

49.96

49.98

50

50.02

50.04

Page 13: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 13 CIGRÉ - Irish National Committee

AF2.APL16 ModuleDB\EirGrid|Frequency NCC

50.09

Hz

AF2.APL16 ModuleDB\EirGrid|Frequency CHCC

50.09

Hz

Frequency NCC Frequency CHCC

22:47 22:46 22:45 22:44 22:43 22:40 22:39 22:38 22:37 22:36

26/12/2014 22:47:45NCC and CHCC Frequency

49.60

49.70

49.80

49.90

50.00

50.10

50.20

December 2014 Oscillation (1)

Page 14: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 14 CIGRÉ - Irish National Committee

0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09

Osci llation Frequency (Hz)

Osci llation Ampli tude

(Peak-Peak mHz)

System Frequency (Hz)

Frequency Oscillation Amplitude (mHz)

Legend:

Live MeasurementsLast Five Minutes

22:49 22:48 22:47 22:46 22:45 22:40 22:39 22:38 22:37 22:36

0.00

50.00

100.00

150.00

200.00

250.00

Frequency NCC

22:49 22:48 22:47 22:46 22:45 22:44 22:41 22:40 22:39 22:38 22:37 22:36

49.60

49.70

49.80

49.90

50.00

50.10

50.20

0.0

50.0

100.0

150.0

200.0

December 2014 Oscillation (2)

• Very Low Frequency Oscillation

• 0.065 Hz oscillation mode with max pk-pk amplitude of ~ 350 mHz

• Root cause still under investigation

Page 15: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 15 CIGRÉ - Irish National Committee

How Measured Data is being used in Planning the

Transmission Network?

Brendan Kelly

EirGrid | Transmission Access Planning

Page 16: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 16 CIGRÉ - Irish National Committee

Page 17: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 17 CIGRÉ - Irish National Committee

Evolution in Planning Needs –

The Old meets the New

Connection Studies

Load Flow

Short Circuit

Dynamics Stability

EMT/TOV

Power Quality/Harmonics

Page 18: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 18 CIGRÉ - Irish National Committee

The need for Good Power Quality

Bound by Grid Code to ensure adequate Quality of Power for Customers as per IEC/TR 61000-3-6 at

IPP/DSO Point of Connection

Page 19: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 19 CIGRÉ - Irish National Committee

We’ve got you covered!

Page 20: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 20 CIGRÉ - Irish National Committee

Using Data for Power Quality Analysis

1. Predicting Future Harmonic Distortion using Existing Measurements

2. Trends – Is there a problem/Is it getting worse?

3. Monitoring Impacts of Wind, Demand, Outages, Cables, Filters and Improving Network Models

4. Using data to create more efficient study procedures

5. Combatting variability in measurements

Page 21: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 21 CIGRÉ - Irish National Committee

1. Predicting Future Harmonic Distortion

Measured

Harmonic

Distortion

Today

Calculation of Harmonic Limits for every future connecting customer

Page 22: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 22 CIGRÉ - Irish National Committee

2. #trending

Page 23: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 23 CIGRÉ - Irish National Committee

2b. Trends – Year on Year Change in

Incremental Harmonic Distortion

Page 24: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 24 CIGRÉ - Irish National Committee

2c. Correlation of Wind with Harmonic

Distortion

Page 25: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 25 CIGRÉ - Irish National Committee

3. Monitor/Benchmark Impact of

Cable Connections

Page 26: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 26 CIGRÉ - Irish National Committee

3b. Highlight Critical Contingencies

Page 27: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 27 CIGRÉ - Irish National Committee

4. Investigate Seasonal Demand

Correlations

- Cut Study Scenarios in Half! Measurements for January and June

Expected Significant

Damping from Load

Page 28: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 28 CIGRÉ - Irish National Committee

5. Variability of Measurements

Using Data to ensure Studies not detached from Reality

Page 29: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 29 CIGRÉ - Irish National Committee

Move towards an Interactive - Data

Transparent future?

Note: For Illustrative Purposes Only.

Real Measurement Data not included

Station A

Station B

Station C

Station D

Station E

Station F

Station G

Station H

Station I

Station J

Page 30: How measured data is being used to help Operate ... - Cigre · • December 2014 Oscillation Introduction . CIGRÉ Training Day 2nd December 2015 EI, Dublin Slide 3 CIGRÉ - Irish

CIGRÉ Training Day

2nd December 2015 EI, Dublin

Slide 30 CIGRÉ - Irish National Committee

Questions & Answers