House Inspection Specialists
Sum Insured Home Rebuild Cost Appraisals
Pre Purchase Inspections
Mobile: 0274 522 159
Work: 09 5334521
www.fchi.co.nz
NZS 4306-2005 Full Indemnity Insurance
Date of inspection 10/04/2014
House inspection Mr and Mrs Smith
Address: 123 Sample St
Auckland
Pre purchase - Condition report
Agent Present: N/A
Buyer Present: Yes
Weather at time of Inspection Dry
Approximate age of house: 1995
Bedrooms: 4 Plus Study
Cladding: Brick veneer & Fibrolite textured – No cavity on fibrolite
Roof: Corrugated Profile
Publication and Use Neither the whole nor any part of this Report or any other report (whether verbal or written) or any reference to this Report or any such other report may be: included in any published document, circular or statement, whether hardcopy or electronic; transferred to any person other than the Customer; or distributed or sold, in each case without first obtaining the written approval of the Company. The Report is not to be used in any litigation except with the prior written approval of the Company
CONTENTS
KITCHEN ...................................................................................................................................................... 4
LIVING ROOMS............................................................................................................................................ 5
BEDROOMS ................................................................................................................................................. 7
BATHROOMS –WET AREAS .......................................................................................................................10
GARAGE ....................................................................................................................................................13
EXTERIOR ......................................................................................................................................................14
EXTERIOR CLADDING & JOINERY ..............................................................................................................14
SITE ...........................................................................................................................................................17
SUB-FLOOR CONSTRUCTION ....................................................................................................................18
ROOF .........................................................................................................................................................19
ROOF SPACE ..............................................................................................................................................19
ELECTRICAL ...............................................................................................................................................21
PLUMBING ................................................................................................................................................22
SUMMARY .....................................................................................................................................................24
DISCLAIMER / LIMITATIONS OF THIS REPORT ..............................................................................................25
FUTURE ISSUES A MUST READ ......................................................................................................................28
CERTIFICATE OF INSPECTION IN ACCORDANCE WITH NZS 4306 2005 .........................................................31
Page 4
COMMENTS: Photo
KIT
CH
EN
Oven 2 Working at time of inspection- Handle loose
Walls 3 No water ingress issues found
Ceiling 3 No water ingress issues found
Floor Covering 3 No issues found
Windows 3 Aluminium - No water ingress issues found
Cabinetry 2 Water damage on kitchen doors K1
Bench tops 3 No issues found
Cook Top 3 Working at time of inspection
Waste disposal 3 Working at time of inspection - No leaks
Range hood 3 Working at time of inspection
Ventilation N/A
Photo K1
Water damaged kitchen doors on front of sink unit
Any additional comments: Action Required
MAINTENANCE
Page 5
COMMENTS: Photo
LIV
ING
RO
OM
S
Doors 3 All hardware working - Doors line up with frame
Walls 2 Elevated moisture readings found L1
Ceiling 3 No water ingress issues found
Floor Coverings 3 No issues found
Windows 3 Water ingress issues left side of window L4
Fireplace 3 Fireplace needs to be checked by approved person L3
Ventilation Fitted and working at time of inspection
Air-Conditioning N/A
Lighting 3 No issues found
Photo L1
Elevated readings below the window above skirting’s
This appears to have come in via the pergola direct fixing to the cladding system
This is known as a high risk area where the bolts are bolted into the framing
Photo L2
Please get the fireplace checked by a certified installer before use
Page 6
Photo L3
Other than the window in the picture no other water ingress issues were found in this area
Photo L4
Water damaged window jamb
This is very common for this type of window
This will need the extrusion beads popped and re siliconed on the exterior along with the butt glass re sealed
Any additional comments: Action Required
MAINTENANCE
Page 7
COMMENTS: Photo
BED
RO
OM
S
Doors 3 N/A
Walls 2 Elevated moisture readings found BR2 BR4 BR7
Ceiling 3 No water ingress issues found
Floor Coverings 3 No issues found
Windows 2 Water ingress issues left side of window BR6
Wardrobe 3 All hardware working - Doors line up with frame
Fan N/A
Air-conditioning Working at time of inspection
Air movement system
Working at time of inspection
Lighting 3 No issues found
Photo BR1
Water ingress issues below this window as described below
Photo BR2
Water damaged area on internal wall in bedroom one
This has come in via the exterior cladding detail finishing where the gutter and flashings meet the wall cladding as shown in photo R2
Further investigation is required to establish if there is any long term rot to the timber structure
Page 8
Photo BR3
Water ingress issues below window as described in photo BR2
Photo BR4
Water damaged area
Elevated readings on left side of wall under window
The entry point of water penetration appears to be from the flashing and gutter junctions as described in the photo BR2
Further investigation is required to establish if there is any long term rot to the timber structure
Photo BR5
No water ingress issues found
Page 9
Photo BR6
Window as described below
Photo BR7
Water penetration issues below the window
Elevated moisture readings are very high on the wall and skirting and the damage is visible on the swollen skirtings
This is common for water leaks due to the style of window
Further investigation is required to establish if there is any long term rot to the timber structure
Photo BR8
No water ingress issues found
Any additional comments: Action Required
YES
Page 10
COMMENTS: Photo
BA
THR
OO
MS –W
ET A
REA
S
Doors 3 All hardware working - Doors line up with frame
Walls 2 Elevated moisture readings found B4
Ceiling 3 No water ingress issues found
Floor Coverings 3 No issues found
Shower 1 Both showers need maintenance B2 B4
Windows 3 Aluminium - No water ingress issues found
Vanity 2 Old water damaged found B5
Ventilation N/A
Toilet 3 Cistern working - No leaks found
Bath 3 Tapware working - No issues found
Heated towel rail N/A
Laundry tub 3 Tapware working - Waste pipes checked - No leaks
Laundry ducting N/A
Tap pressure 3 N/A
Photo B1
No water ingress issues found below windows
Page 11
Photo B2
Shower is leaking behind the walls on each corner
Given the age of the shower this will have to be removed and a new one installed
This is common for 70% of these showers installed due to the style of drainage systems relying on silicone to divert water away from behind the wall linings
Photo B3
Main Bathroom
Photo B4
This shower has been replaced recently given the new style of drainage system
Unfortunately this has not been set up properly and it is allowing water to flow out the right side end panel when tested
Water damage to wall and skirting and particle board flooring were visible and high readings on the trotec 650 meter
Page 12
Photo B5
Wash basin has had water overflow at some stage and damage to the side panel was visible
Photo B6
No water ingress issues found
Any additional comments: Action Required
MAINTENANCE
Page 13
COMMENTS: Photo
GA
RA
GE
Doors 3 Doors line up with frame - Hardware working
Walls 3 No water ingress issues found
Ceiling 3 No water ingress issues found
Floor Coverings 3 No issues found
Windows N/A
Garage Door 3 Garage doors runs freely - Motor working at time of inspection
Photo G1
No water ingress issues found
Any additional comments: Action Required
NONE
Page 14
Exterior
COMMENTS: Photo
EXTE
RIO
R C
LAD
DIN
G &
JO
INER
Y
Cladding Style Brick veneer – Monolithic cladding – No cavity
Cracks must be repaired by grinding back joints and re taping and texturing
X2
Roof to wall junctions
No issues found
Surface Coating Recently painted 3 years ago – Repairs needed X2
Cladding to Roof Junction
No issues found
Cladding to Wall Junctions
No issues found
Vertical Relief Joints
N/A
Horizontal Relief Joints
N/A
Windows type Aluminum window needs attention - Leaking BR6
Window Head flashing
Head flashings need to be fitted above garage door X1
Window sill flashing
N/A
Drainage holes windows
No issues found
Cavity System Fibrolite No cavity system needed at time of construction
Photo X1
No head flashings fitted above the garage door
This will allow wicking under the door head and under the cladding and will cause long term damage to the framing
It is possible damage to the framing may have already occurred
Further investigation is required to establish if there is any long term rot to the timber structure
Page 15
Photo X2
The crack under the window will need to be repaired by a certified repairer
Cracks like this will allow water ingress into the dwelling wall space given the cladding is only 7.5mm thick and has no drainage systems in place to deal with excess water and no air flow behind the cladding system
Further investigation is required to establish if there is any long term rot to the timber structure
Photo X3
Window extrusion will need to be siliconed where it has cracked as these windows only rely on silicone for a weather tight seal
Photo X4
High risk area of water ingress as there is no flashings to stop water getting in behind the cladding system
Further investigation is required to establish if there is any long term rot to the timber structure
Page 16
Photo X5
No capillary breaks where the cladding system meets the concrete ledge at the base of the dwelling
If water is trapped behind the cladding it cannot get out and can rot out the timber framing long term
It is possible this may have already happened
Further investigation is required to establish if there is any long term rot to the timber structure
Photo X6
Pergola is directly fixed to the cladding system and this could have a high risk of water ingress damage to the framing
Any penetrations into the cladding system even if there was a cavity system is a high risk for water entry points
Photo X7
No soffits
The barge board trim has been nailed directly into the cladding system
This is a very high risk area of water ingress issues from this method of construction
Having no soffits will increase the risk of water ingress issues due to no weather protection above the windows and flashings
Any additional comments: Action Required
YES
Page 17
COMMENTS: Photo
SITE
Slope No excess water found near dwelling
Fencing Normal movement for age
Paths/driveway Normal cracks from movement
Surface water None at time of inspection
Gates No issues found
Retaining wall No movement found
Pergola Pergola is direct fixed to the wall cladding - High risk area
Photo ST1
Direct fixing to the wall cladding system as described in exterior wall claddings
Any additional comments: Action Required
YES
Page 18
COMMENTS: Photo
SUB
-FLO
OR
CO
NST
RU
CTI
ON
Materials Timber and concrete base
Piles Posts into ground - Minimal movement
Joists-Bearers Timber - No rot found
Flooring Particle board flooring - No water damage seen at time of inspection
Ventilation Air movement vents fitted
Ground condition Ground condition dry
Ground clearance 150mm from the top of the floor to the paved surface- This did not happen in the courtyard area and will need an invasive test carried out
Foil paper N/A
Photo SF1
Ground dry
Insulation fitted to sub floor
Any additional comments: Action Required
YES
Page 19
COMMENTS: Photo
RO
OF
Materials Galvanised corrugated roof
Slope Roof materials correct for pitch of roof
Flashings Flashings rusty - Maintenance needed R3
Fixings No issues found
Penetrations N/A
Coating and Surface
Good condition
Soffits Minimal soffits for weather protection
Barge Boards, Facia
Wooden barge boards - No rot found
Gutters Plastic gutter - No leaks at time of inspection
Down pipes Plastic - No leaks found
Valley No issues found
Hip and Ridges No issues found
Chimney N/A
RO
OF
SPA
CE
Construction Timber framing - No rot seen at time of inspection
Dampness None seen at time of inspection
Insulation Insulation was present on inspection- This is not a statement as to the efficency or rating of the insulation
Insect & Pests None seen at time of inspection
Rotting Timbers None seen at time of inspection
Page 20
Photo R1
Roofing iron is in good condition
Photo R2
This junction has had issues with water leaks from when the dwelling was built
This area is responsible for two rooms leaking
This area must be modified by a LBP builder and flashings must be upgraded
Further investigation is required to establish if there is any long term rot to the timber structure
Photo R3
Rusty flashing along two walls above the pergola needs replacing
Any additional comments: Action Required
MAINTENANCE
Page 21
COMMENTS: Photo
ELEC
TRIC
AL
Wiring TPS Wiring is a current wiring system - No issues found what could be seen
Fitting All lights checked - No wall sockets checked
Distribution panel Trip switches fitted - Cover fitted
Ceiling Fans N/A
Air conditioning Working at time of inspection
Outdoor Lights/power points
Working at time of inspection
Main Panel No issues found
Gas Supply N/A
Alarm All working at time of inspection
Smoke Detector Smoke detectors need to be fitted
Heating Systems Working at time of inspection
Venting Systems Working at time of inspection
Central Vac N/A
Spa N/A
Pool N/A
Photo EL1
No issues found
Page 22
COMMENTS: Photo
PLU
MB
ING
Feed Pipes Mixture of pipe feeds fitted - No issues found
Taps & Fittings All taps working - No leaks
Waste Pipes No leaks found
Gulley Traps Lids fitted - Waste flowing
Hot Water Cylinder
Electric - No leaks - Strap fitted
Toilets All cisterns working - No leaks found
Water toby No lid fitted
Plumbing exterior penetrations
All penatrations are sealed at time of inspection
Water tanks N/A
Septic tank N/A
Photo P1
No leaks found
Page 23
Photo P2
Some of the plumbing appears to be very cheap plastic fittings and are known to become very brittle over time
Page 24
SUMMARY
1994 dwelling
Two levels
Brick veneer and block and fibrolite with no cavity system needed on the fibrolite textured board at time of construction
Aluminium windows
Galvanised colour steel roof
My concerns with this dwelling is that there are no soffits for weather protection on the windows or cladding system and given there are already a few leaks in the dwelling, what is the condition of the framing behind the cladding in these areas
We have not had much rain over the last few months and given the moisture content and damaged skirting’s on these areas of concern, there may already be long term damage to the framing
These types of cladding systems do not have any spacing’s between the cladding and framing and this will allow rot into the framing if water enters the wall space
This dwelling is built up on the hill which will be more susceptible to wind and heavy rain on the cladding system and this makes this style of dwelling more vulnerable to leaks given the design and flashing systems and capillary breaks that have not been installed
If you wish to proceed with this dwelling it will require an invasive test which will have a series of holes drilled through the exterior and samples of the timber sent to a lab for tests to see if there is any rot present
The dwelling will also need a considerable amount of upgrading with flashings etc to try and minimise the risks of water ingress issues in the future or the other alternative is to re-clad the fibrolite areas on a cavity system and a new cladding material fitted
All areas of concern are highlighted in my report and most will need a LBP builder to do the repairs
Any questions please call
Mark Muller
25 Years building experience
15 Years water ingress issues
Small Claims Building Investigator for the Courts
Page 25
FIRST CHOICE HOUSE INSPECTIONS
DISCLAIMER / LIMITATIONS OF THIS REPORT
Terms and Conditions Applicable to Residential Building Inspection Reports Purpose The building inspection report (“Report”) is prepared by First Choice House Inspections Limited (“FCHL”) for the specific purposes of assessing the general condition of the building and identifying defects that are readily apparent at the time of inspection based on the limited visual, non-invasive inspection as further described below in the Scope and Limitations & Exclusions sections. No responsibility is accepted in the event that the Report is used for any other purpose. Scope The Report is based on a limited visual, above ground, non-invasive inspection of the standard systems and components of the building. FCHL does not open up, uncover or dismantle any part of the building as part of the inspection or undertake any internal inspection of the building. The procedure for the inspection will be conducted in accordance with NZS 4306:2005. New Zealand Standard; Residential Property Inspection.
Report Limitations & Exclusions
The Report is a guide only (as per New Zealand Standards) and not a guarantee or warranty as to the state of the building or any product, system or feature in the building.
Areas of the building that the inspector believes to be potential problem areas for moisture ingress are checked with a non-invasive moisture meter. Rotting of timber framing and/or the presence of toxic moulds however, can only be determined by invasive testing which requires the removal of wall linings. This cannot be done without the written consent of the owner and is outside the scope of the Report. The Report is not a specialist weathertightness report. FCHL accepts no responsibility or liability for any omission in its inspection or the Report related to defects or irregularities which are not reasonably visible at the time of the inspection or which relate to components of the building:
- which are below ground or which are concealed or closed in behind finished surfaces (such as plumbing, drainage, heating, framing, ventilation, insulation or wiring);
- which required the moving of anything which impeded access or limited visibility (such as floor coverings, furniture, appliances, personal property, vehicles, vegetation, debris or soil) – FCHL does not move owner/occupier items for the purposes of the inspection;
- to which access is not reasonably and safely available to carry out a visual inspection. This may include roofs, subfloor areas and ceiling cavities and high, constricted or dangerous areas for which inspection is not permitted by Occupational Safety and Health regulations.
In addition, the customer accepts that FCHL will not detect some defects because: the defect may only occur intermittently; the defect has been deliberately concealed; or FCHL has been given incorrect information by the customer or any third party. If you believe that any of these circumstances apply then you should immediately contact FCHL in order to try and resolve. Any area, system or component of the building or any item, feature or system not specifically identified in the Report as having been inspected was not included in the scope of the inspection. This includes the condition and location of any special features or services, underground services drainage or of any systems including electrical, plumbing, gas or heating except as otherwise may be described in the Report.
Page 26
On request, specialist inspections can be arranged of weathertightness or structure or of any systems including electrical, plumbing, gas or heating. Descriptions in the Report of systems or appliances relate to the existence of such systems or appliances only and not the adequacy, efficiency or life expectancy of such systems or appliances. The Report:
- is not a structural survey, engineer’s report, weathertightness inspection or a report on the building’s seismic safety. FCHL can assist with arranging such arranging such specialist third party inspections upon request;
- does not assess compliance with the requirements of any legislation (including, any act, regulation, code or by-law) unless otherwise stated;
- is not a geotechnical, site or environmental report. FCHL makes no representation as to the existence or absence of any or “hazard” (as defined in the Health and Safety in Employment Act) or any “hazardous substance”, “natural hazard” or “contaminant” (as those terms are defined in the Resource Management Act) in the building or property;
Title and Local Authority Records FCHL has not undertaken any title search and assumes all improvements are within the legal boundaries of the property. No survey of the property or any search of information held by the territorial authority or any other relevant authority has been undertaken. It is recommended that the customer conducts its own Land Information Memorandum or Council property file search. Unit Title Properties If the property is a Unit Title property, the inspection and Report is limited to the actual unit and any accessory unit(s) and does not extend to the remainder of the building or the common areas. FCHL recommends the customer obtain a copy of the financial statements and minutes from meetings of the Body Corporate to establish the history of the inspected property under such Body Corporate. Responsibility to Third Parties Our responsibility in connection with this Report is limited to the customer to whom the Report is addressed and to that customer only. We disclaim all responsibility and will accept no liability to any other party without first obtaining the written consent of FCHL and the author of the Report. FCHL reserves the right to alter, amend, explain or limit any information given to any other party. Publication Neither the whole nor any part of the Report (or any other report provided by FCHL, whether written or verbal) may be published or included in any published document, circular or statement whether in hard copy or electronic form or otherwise disseminated or sold without the prior written approval of FCHL and the inspector. Claims & Disputes
Should any dispute arise as a result of the inspection or the Report, it must be submitted to FCHL in writing as soon as practically possible but in any case, within ten working days of discovery. The customer agrees that in the event of a dispute, the contents of the Report may not be used to satisfy any terms of a sale and purchase agreement until the disagreement/dispute has been resolved. In the event the customer nevertheless enters into an unconditional agreement for purchase of the subject property or makes an existing agreement
Page 27
unconditional prior to resolution of the dispute, the customer shall be deemed to have waived the customer’s rights to continue with and/or make any future claim against FCHL in relation to that matter.
Any claim relating to the accuracy of the Report, in the form of errors or omissions is limited to the failure on the part of FCHL to follow the Standards of Practice of the New Zealand Standard; NZS 4306:2005 Residential Property Inspection (a copy can be made available for viewing if required).
Except in the case of an emergency, the customer further agrees not to disturb, repair, replace or alter anything that may constitute evidence relating to the dispute or claimed discrepancy before FCHL has had an opportunity to re-inspect and investigate the claim. The Customer understands and agrees that any failure to notify FCHL or permit FCHL to re-inspect as stated above shall be deemed to be a waiver of the customer’s rights to continue with and/or make any future claim against FCHL in relation to that matter.
Limitation of Liability
The customer acknowledges and agrees that the director(s) and employee(s) of FCHL shall not be held liable to the customer.
FCHL shall have no liability to the customer for any indirect or consequential loss of whatever nature suffered by the customer or any other person and the customer hereby indemnifies FCHL in respect of any claims concerning any such loss.
Subject to any statutory provisions, if FCHL becomes liable to the customer for any reason, for any loss, damage, harm or injury in any way connected with the completion of the inspection and/or the Report, FCHL’s total liability shall be limited to a sum not exceeding $5,000.
Consumer Guarantees Act
Nothing contained in these terms and conditions shall be deemed to exclude or restrict any rights or remedies that the customer may have under the Consumer Guarantees Act 1993 or otherwise at law. Partial Invalidity
If any provision in these terms and conditions is illegal, invalid or unenforceable, such provision shall be deemed to be excluded or read down to the extent necessary to make the provision legal, valid or enforceable, and the remaining provisions of these terms and conditions shall not be affected.
“All our building inspections and reports are subject to our standard terms and conditions. This is an important legal document. Please take the time to read it before ordering any inspection or other services. Our standard terms and conditions exclude certain types of liability and limit our total liability to customers in the event of any problems.”
Page 28
FUTURE ISSUES A MUST READ
Recent court rulings as to how building and moisture inspections are reported are now required.
The rulings apply to all buildings not compliant with current codes.
This means if a building was compliant at the time of construction but methods materials along with flashings
and a new building code has changed since this dwelling was constructed. Inspectors must report on future
potential issues that are likely to adversely affect the buildings future durability in those areas in which the
specification has now been upgraded.
This is done regardless if there were no issues found on the day of inspection.
Should future issues occur they are more likely to happen around areas described as a high risk.
Most of these areas are proven to be flashings around windows and doors, internal guttering, eaves, external
fittings such as lighting, joins in sheets which crack and parapet capping’s
FCHIL advises that if moisture or building inspection was satisfactory on the day of inspection but the dwelling
was built prior to the current building code the following may occur.
Flashings around windows and doors. Current code ensures that if moisture gains access for whatever reason it
can get out without damaging the timber. Prior to the current codes, inspections of flashing installation and the
installation themselves were varied and sometimes unsatisfactory.
The guarantee therefore that if moisture gets in it can get out cannot be given for houses not currently
compliant. To minimize this risk it is recommended a yearly maintenance check to ensure there is no increased
moisture levels. FCHL past experience tells us that, should moisture levels rise it is in most cases due to the
comer miter join seals beginning to fail or the seal between the window cladding has broken.
These areas are easy to fix
Internal Guttering: If internal guttering becomes blocked and there are no insufficient overflows, water can
build up quickly and backflow into the soffit which fills up and then may flow into the frame. If there is no soffit
it may back flow directly into the frame. It is therefore essential that internal guttering is checked regularly for
blockages. Where there is internal guttering and a soffit, a simple fix is to install grills every 2 meters. This allows
any back flow that enters the soffit to exit via the grills before it reaches the frame.
Cladding Joins: Any cracks that appear increase the risk of moisture entering the frame. All cracks should be
raked and sealed.
Eaves: Eaves provide limited protection to exterior cladding, the windows and doors. As the size of the soffit
decrease, the risk of moisture entry increases because the water reaches the cladding, windows and doors more
often. In addition, if driving rain has forced water under the tiles or parapet flashing, it may enter the frame. In
the case of minimal eaves, the best protection is organising a method to prevent wind from forcing rain upwards
and ensuring regular maintenance around windows and doors and repairing cracks as they may show.
Page 29
Parapets: Where a building has parapets, they should be capped. If there is no capping the material used to
encase the frame may crack over time and allow moisture to enter the frame. A capping, usually metal, affords
good protection. The sides of the capping can lift under high winds allowing water to enter the top. If the top is
cracked, the water may then enter the frame. The fix is to regularly cast a visual eye to ensure no lifting of the
skirt and if so, arrange for it to be realigned and resealed.
Exterior Lights: The holes through which the cables pass to the external lights should be sealed. Water running
down the wall can pool inside the light fitting. When it’s sufficiently high it can reach the cable hole and flow
into the frame. The fix is to take down the lights, check the holes are sealed then replace. The screws used to
face the lights to the wall should be bound with silicon before replacing the unit.
Page 30
SUMMARY LIST OF FEATURES INSPECTED For any feature not present on the property, mark as N/A (not applicable).
Inspected
Y N N/A
SITE
Orientation of living spaces y
Site exposure, contour & vegetation y
Retaining walls y
Paths, steps, handrails & driveways y
Fencing y
Surface water control y
SUB
FLO
OR
Location of access point y
Accessibility y
Foundation type & condition y
Foundation walls y
Ground condition y
Ground vapour barrier y
Drainage y
Ventilation adequacy y
Pile type, instability & condition y
Pile to bear connections y
Obvious structural alteration y
Ground clearance of timber framing y
Floor type (timber or suspended concrete) y
Timber framing & bracing y
Insulation type, appropriate thickness, coverage & condition
y
Plumbing – material types, leakage & support y
Electrical – wiring type & support y
Insect and pest infestation y
Rotting timbers y
Debris y
EXTE
RIO
R Construction Type y
Cladding y
Chimneys n
Exterior stairs n
Balconies, verandahs, patios, etc. y
RO
OF
Roof material y
Roof condition y
Roof water collection y
Downpipes y
Eaves, fascia & soffits y
Y N N/A
INTE
RIO
R
Ceilings y
Walls y
Timber floors y
Concrete floors y
Doors & frames y
Electrical – operation of switches, etc. y
Heating systems y
Kitchen Bench top y
Cabinetry y
Sink y
Tiles y
Air extraction system y
Bathroom, WC, Ensuite y
Floor y
Cistern, pan & bidet y
Tiles y
Bath y
Shower y
Vanity/washbasin y
Ventilation y
Special features y
Laundry Location y
Floor y
Tubs/cabinet y
Tiles y
Ventilation y
Storage y
Stairs y
Exterior windows & doors y
SER
VIC
ES
Fire warning & control systems y
Heating systems y
Central vacuum systems n
Ventilation systems n
Security system n
Electricity services y
Gas services n
Water services y
Hot water services y
Foul water disposal y
Grey water recycling system n
Rainwater collection systems y
Solar heating n
Aerials & antennae n
Shading systems y
Telecommunications n
Lifts n
AN
CIL
LAR
Y S
PA
CES
Exterior claddings y
Floors y
Roofs y
Sub Floor y
RO
OF
SPA
CE
Accessibility y y
Roof cladding y
Thermal insulation type, clearances, approximate thickness & coverage
y n
Sarking n
Party walls, fire proofing n
Roof underlay & support y
Roof frame construction & connections y
Ceiling construction y
Obvious structural alteration y
Insect and pest infestation y
Rotting timbers y
Discharges into roof space y
Plumbing – material types, leakage & support y
Electrical – wiring type & support y
Tile fixings n
Inspected
Page 31
Ref No…501………..
CERTIFICATE OF INSPECTION IN ACCORDANCE WITH NZS 4306 2005
Client: Mr & Mrs Smith
Site address: 123 Sample St Auckland
Inspector:
Name: Mark Muller
Company: FCHI
Qualifications: Builder
Date of inspection: 10/04/2014
The following areas of the property have been inspected:
Yes No
(please tick)
(a) Site y
(b) Subfloor y
(c) Exterior y
(d) Roof Exterior y
(e) Roof Space y
(f) Interior y
(g) Services y
(h) Accessory units, ancillary spaces and buildings y Any limitations to the coverage of the inspection are detailed in the written report. Certification: I hereby certify that I have carried out the inspection of the property site at the above address in accordance with NZS 4306 2005 Residential Property Inspection – and I am competent to undertake this inspection.
Signature:
Date:10/04/2014
An inspection carried out in accordance with NZS 4306 2005 is not a statement that a property complies with the requirements of any Act, regulation or bylaw, nor is the report a warranty against any problems developing after the date of the property report. Refer to NZS 4306 2005 for full details.