Home Inspection Report
646 Johnson Dr, Carmel, IN 46033Inspection Date:
Tuesday, April 7, 2015
Prepared For:Ryan Lewis
Prepared By:Jason Thompson
, 3177014637
Report Number:040715
Inspector:Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 2
Report SummaryItems Not Operating
None apparent
Major ConcernsNone apparent
Potential Safety HazardsOpen joints or cracks in firebrick recommend properly sealing
Deferred Cost ItemsWater heater that is 5+ years.
Improvement ItemsFirewall protection recommended on access to attic. Recommend cleaning moss and mold off of the roof. Recommend having flue cleaned and reexamined.
Items To MonitorRoof coverings appeared overall satisfactory, but will need minor maintenance. (Moss)
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 3
Report OverviewHouse in Perspective
Well Built/Maintained
Scope of InspectionAll components designated for inspection in the ASHI Standards of Practice are inspected, except as may be noted in the "Limitations of Inspection" sections within this report. It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind.Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.
Main Entrance FacesEast
State of OccupancyOccupied
Weather ConditionsCloudy
Recent RainYes
Ground CoverDamp
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
Receipt/InvoiceJason Thompson
, 3177014637
Date: Tue. Apr. 7, 2015 8:13 Inspection Number: 040715
Inspected By: Jason Thompson
Client: Ryan Lewis
Inspection FeeHome Inspection $350.00
Total $350.00
646 Johnson Dr Carmel, IN 46033 Page 5
GroundsService Walks
None Not VisibleMaterial X Concrete Flagstone Gravel Brick OtherCondition X Satisfactory Marginal Poor Trip hazard X Typical cracks Pitched towards home
Settling cracks Public sidewalk needs repairCommentsPhotos
Driveway/ParkingNone Not Visible
Material Concrete X Asphalt Gravel/Dirt Brick OtherCondition Satisfactory X Marginal Poor Settling Cracks Typical cracks Pitched towards home
Trip hazard Fill cracks and sealCommentsPhotos
PorchX None Not Visible
Condition Satisfactory Marginal Poor Railing/Balusters recommendedSupport Pier Concrete Wood OtherFloor Satisfactory Marginal Poor Safety HazardComments
Stoops/StepsNone
Material X Concrete Wood Other Railing/Balusters recommendedCondition X Satisfactory Marginal Poor Safety Hazard Uneven risers Rotted/Damaged
Cracked SettledComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 6
Photos
PatioNone
Material X Concrete Flagstone Kool-Deck X Brick brick paver on concreteCondition X Satisfactory Marginal Poor Settling cracks Trip hazard
Pitched towards home (see remarks) Drainage provided Typical cracksComments SW GFCI recepticle has no power.
Recepticle on exterior brick wall has no power. Recommend repair and should be GFCI protected. Recommend replacing light switch operated wall recepticle with light. See photo
Photos
Deck/BalconyX None Not Visible
Material Wood Metal Composite Railing/Balusters recommendedCondition Satisfactory Marginal Poor Wood in contact with soilFinish Treated Painted/Stained Other Safety Hazard Improper attachment to house
Railing loose Not ApplicableComments
Deck/Patio/Porch CoversNone
Condition X Satisfactory Marginal Poor Posts/Supports need Repair Earth to wood contactMoisture/Insect damage
Recommend Metal Straps/Bolts/Nails/Flashing Improper attachment to house X NoneComments
Fence/WallNot evaluated X None
Type Brick Block Wood Metal Chain Link Rusted VinylCondition Satisfactory Marginal Poor Typical cracks Loose Blocks/CapsGate N/A Satisfactory Marginal Poor Planks missing/damaged Operable: Yes NoComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 7
GroundsLandscaping affecting foundation
X N/ANegative Grade East West North South X Satisfactory Recommend additional backfill
Recommend window wells/covers X Trim back trees/shrubberiesWood in contact with/improper clearance to soil
CommentsPhotos
Retaining wallX None
Material Brick Concrete Concrete block Railroad ties Timbers OtherCondition Satisfactory Marginal Poor Safety Hazard Leaning/cracked/bowed
Drainage holes recommendedComments
Hose bibsN/A
Condition X Satisfactory Marginal Poor No anti-siphon valve Recommend Anti-siphon valveOperable X Yes No Not Tested Not OnComments 50psi
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 8
RoofGeneralVisibility None X All Partial OtherInspected From X Roof Ladder at eaves Ground With Binoculars
Style of RoofType X Gable Hip Mansard Shed Flat OtherPitch Low X Medium Steep FlatRoof #1 Type:
AsphaltLayers:1 LayerAge:5-10+Location:Main roof
Roof #2 NoneType:AsphaltLayers:1 LayerAge:5-10+Location:Over garage area
Roof #3 NoneType:AsphaltLayers:1 LayerAge:1-5+Location:Covered patio roof
Comments
Ventilation SystemNone N/A
Type X Soffit Ridge X Gable X Roof Turbine Powered OtherCommentsPhotos
FlashingMaterial Not Visible X Galv/Alum Asphalt Copper Foam Rubber Lead Other
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 9
RoofFlashing cont.Condition Not Visible X Satisfactory Marginal Poor Rusted Missing
Separated from chimney/roof Recommend Sealing OtherComments
ValleysN/A
Material X Not Visible Galv/Alum Asphalt Lead Copper OtherCondition Not Visible X Satisfactory Marginal Poor Holes Rusted Recommend SealingCommentsPhotos
Condition of Roof CoveringsRoof #1 Satisfactory X Marginal Poor Curling Cracking Ponding Burn Spots
Broken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles X Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Roof #2 N/A X Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Roof #3 N/A X Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Comments Recommend cleaning moss and mold off of the roof.Photos
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 10
RoofSkylights
X N/A Not VisibleCondition Cracked/Broken Satisfactory Marginal PoorComments
Plumbing VentsNot Visible Not Present
Condition X Satisfactory Marginal PoorCommentsPhotos
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 11
ExteriorChimney(s)
NoneLocation(s) Middle of Roof
North Viewed From X Roof Ladder at eaves Ground (Inspection Limited) With BinocularsRain Cap/Spark Arrestor X Yes No RecommendedChase X Brick Stone Metal X Blocks FramedEvidence of Holes in metal X Cracked chimney cap Loose mortar joints X Flaking Loose brick Rust
No apparent defectsFlue X Tile Metal Unlined Not VisibleEvidence of Scaling Cracks Creosote X Not evaluated X Have flue(s) cleaned and re-evaluated
Recommend Cricket/Saddle/Flashing No apparent defectsCondition X Satisfactory Marginal Poor Recommend RepairComments Chimney flue was not evalutated.Photos
Recommend sealing/repairing crack in chimney cap
Gutters/Scuppers/EavestroughNone
Condition X Satisfactory Marginal Poor Rusting Downspouts needed Recommend repair/replaceNeeds to be cleaned
Material Copper Vinyl/Plastic X Galvanized/Aluminum OtherLeaking Corners Joints Hole in main run X No apparent leaksAttachment Loose Missing spikes Improperly sloped X SatisfactoryExtension needed North South East West X N/AComments Gutters were in overall adequate condition.
SidingMaterial Stone Slate Block/Brick Fiberboard Fiber-cement Stucco EIFS* Not Inspected
Asphalt Wood X Metal/Vinyl Other Typical cracks Peeling paint MonitorWood rot Loose/Missing/Holes
Condition X Satisfactory Marginal Poor Recommend repair/paintingComments
TrimMaterial X Wood Fiberboard Aluminum/Steel X Vinyl Stucco Recommend repair/painting
Damaged wood OtherCondition X Satisfactory Marginal PoorComments Recommend repairing broken shutter on 2 nd floor east window
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 12
Photos
SoffitNone
Material X Wood Fiberboard Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other
Condition X Satisfactory Marginal PoorComments
FasciaNone
Material X Wood Fiberboard Aluminum/Steel Vinyl Stucco X Recommend repair/paintingDamaged wood Other
Condition X Satisfactory Marginal PoorComments
FlashingNone
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other
Condition X Satisfactory Marginal PoorComments
CaulkingNone
Condition X Satisfactory Marginal PoorRecommend around windows/doors/masonry ledges/corners/utility penetrations
Comments
Windows/ScreensCondition X Satisfactory Marginal Poor Wood rot Recommend repair/painting
Recommend repair/replace damaged screens Failed/fogged insulated glassMaterial Wood Metal X Vinyl Aluminum/Vinyl cladScreens Torn Bent Not installed X SatisfactoryComments
Storms WindowsX None Not installed
Condition Satisfactory Broken/cracked Wood rot Recommend repair/paintingMaterial Wood Clad comb. Wood/Metal comb. MetalPutty Satisfactory Needed N/AComments
Slab-On-Grade/FoundationFoundation Wall Concrete block X Poured concrete Post-Tensioned concrete Not Visible OtherCondition X Satisfactory Marginal Monitor Have Evaluated Not Evaluated
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 13
ExteriorSlab-On-Grade/Foundation cont.Concrete Slab X N/A Not Visible Satisfactory Marginal Monitor Have EvaluatedComments
Service EntryLocation X Underground OverheadCondition X Satisfactory Marginal Poor Weather head/mast needs repair Overhead wires too lowExterior receptacles X Yes No Operable: X Yes No Condition: X Satisfactory Marginal PoorGFCI present X Yes No Operable: X Yes No Safety Hazard Reverse polarity Open ground(s)
Recommend GFCI ReceptaclesComments
Building(s) Exterior Wall ConstructionType X Not Visible Framed Masonry OtherCondition X Not Visible Satisfactory Marginal PoorComments
Exterior DoorsMain Entrance N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace
Door condition: X Satisfactory Marginal PoorPatio N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace
Door condition: X Satisfactory Marginal PoorRear door X N/A Weatherstripping: Satisfactory Marginal Poor Missing Replace
Door condition: Satisfactory Marginal PoorOther door X N/A Weatherstripping: Satisfactory Marginal Poor Missing Replace
Door condition: Satisfactory Marginal PoorComments
Exterior A/C - Heat pump #1Unit #1 N/A
Location:Exterior rear wallBrand:TraneModel #:4TWR3042B1000ABSerial #: 14491H314FApproximate Age:Mfr date 12/2014
Condition X Satisfactory Marginal Poor Cabinet/housing rustedEnergy source X Electric Gas OtherUnit type X Air cooled Water cooled Geothermal Heat pumpOutside Disconnect X Yes No Maximum fuse/breaker rating (amps): 45 Fuses/Breakers installed (amps): 50
X Improperly sized fuses/breakersLevel X Yes No Recommend re-level unitCondenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line X SatisfactoryInsulation Yes X No ReplaceImproper Clearance (air flow) Yes X NoComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 14
Photos
Exterior A/C - Heat pump #2Unit #2 X N/A
Location:Brand:Model #:Serial #: (null)Approx. Age:
Energy source Electric Gas OtherUnit type Air cooled Water cooled Geothermal Heat pumpOutside Disconnect Yes No Maximum fuse/breaker rating (amps): (null) Fuses/Breakers installed (amps): (null)
Improperly sized fuses/breakersLevel Yes No Recommend re-level unitCondenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line SatisfactoryInsulation Yes No ReplaceCondition Satisfactory Marginal Poor Cabinet/housing rustedImproper Clearance (air flow) Yes NoComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 15
Garage/CarportType
NoneType X Attached Detached 1-Car X 2-Car 3-Car 4-Car CarportComments
Automatic OpenerNone N/A
Operation X Operable InoperableComments
Safety ReverseNone N/A
Operation X Operable Not Operable Need(s) adjusting Safety hazardX Photo eyes and pressure reverse tested
Comments
RoofingMaterial X Same as house
Type:Approx. age: (null) Approx. layers: (null)
Comments
Gutters/EavestroughCondition X Satisfactory Marginal Poor X Same as houseComments
SidingN/A
Material X Same as house Wood Metal Vinyl Stucco Masonry Slate FiberboardCondition X Satisfactory Marginal Poor Recommend repair/replace Recommend paintingComments
TrimN/A
Material X Same as house Wood Aluminum VinylCondition X Satisfactory Marginal Poor Recommend repair/replace Recommend paintingComments
FloorMaterial X Concrete Gravel Asphalt Dirt OtherCondition X Satisfactory X Typical cracks Large settling cracks Recommend evaluation/repair
Safety hazardSource of Ignition within 18" of the floor N/A Yes X NoComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 16
Photos
Sill PlatesNone X Not Visible
Type Floor level ElevatedCondition Rotted/Damaged Recommend repairComments
Overhead Door(s)N/A
Material X Wood Fiberglass Masonite Metal Recommend repairCondition Satisfactory X Marginal Poor Hardware loose Safety Cable Recommended
Weatherstripping missing/damaged Loose/missingRecommend Priming/Painting Inside & Edges X Yes NoComments Recommend repair/replace wood rot on overhead door. See photoPhotos
Exterior Service DoorNone
Condition X Satisfactory Marginal Poor Damaged/RustedComments
Electrical ReceptaclesX Yes No Not Visible Operable: X Yes No
Reverse polarity Yes X NoOpen ground Yes X No Safety HazardGFCI Present Yes X No Operable: Yes No Handyman/extension cord wiring
X Recommend GFCI ReceptaclesComments
Fire Separation Walls & CeilingN/A X Present Missing Recommend repair
Condition X Satisfactory Recommend repair X Holes walls/ceiling Safety hazard(s)
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 17
Garage/CarportFire Separation Walls & Ceiling cont.Moisture Stains Present Yes X NoTypical Cracks X Yes NoFire door X Not verifiable Not a fire door Needs repair SatisfactorySelf closure X N/A Satisfactory Inoperative MissingComments Firewall protection recommended on access to attic.
Recommend repair of small hole in garage ceiling drywall
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 18
Garage/DetachedType
NoneType Attached X Detached 1-Car X 2-Car 3-Car 4-Car CarportComments
Automatic OpenerNone N/A
Operation X Operable InoperableComments
Safety ReverseNone N/A
Operation X Operable Not Operable Need(s) adjusting Safety hazardX Photo eyes and pressure reverse tested
Comments
RoofingMaterial Same as house
Type:AsphaltApprox. age: 3 years Approx. layers: 1
Comments
Gutters/EavestroughCondition X Satisfactory Marginal Poor Same as houseComments
SidingN/A
Material Same as house Wood Metal X Vinyl Stucco Masonry Slate FiberboardCondition X Satisfactory Marginal Poor Recommend repair/replace Recommend paintingCommentsPhotos
TrimN/A
Material Same as house X Wood Aluminum VinylCondition X Satisfactory Marginal Poor Recommend repair/replace Recommend paintingComments
FloorMaterial X Concrete Gravel Asphalt Dirt OtherCondition X Satisfactory X Typical cracks Large settling cracks Recommend evaluation/repair
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 19
Garage/DetachedFloor cont.Condition cont. Safety hazardSource of Ignition within 18" of the floor X N/A Yes NoComments
Sill PlatesNone Not Visible
Type Floor level X ElevatedCondition Rotted/Damaged Recommend repair X SatisfactoryComments No issues noted
Overhead Door(s)N/A
Material Wood Fiberglass Masonite X Metal Recommend repairCondition X Satisfactory Marginal Poor Hardware loose Safety Cable Recommended
Weatherstripping missing/damaged Loose/missingRecommend Priming/Painting Inside & Edges Yes X NoComments
Exterior Service DoorNone
Condition X Satisfactory Marginal Poor Damaged/RustedComments
Electrical ReceptaclesX Yes No Not Visible Operable: X Yes No
Reverse polarity Yes X NoOpen ground Yes X No Safety HazardGFCI Present Yes X No Operable: Yes No Handyman/extension cord wiring
X Recommend GFCI ReceptaclesComments
Fire Separation Walls & CeilingX N/A Present Missing Recommend repair
Condition Satisfactory Recommend repair Holes walls/ceiling Safety hazard(s)Moisture Stains Present Yes NoTypical Cracks Yes NoFire door Not verifiable Not a fire door Needs repair X SatisfactorySelf closure N/A Satisfactory Inoperative MissingComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 20
KitchenCountertopsCondition X Satisfactory Marginal Recommend repair/caulkingComments New granite countersPhotos
CabinetsCondition X Satisfactory Marginal Recommend repair/adjustmentComments
PlumbingFaucet Leaks Yes X NoPipes leak/corroded Yes X NoSink/Faucet X Satisfactory Corroded Chipped Cracked Recommend repairFunctional drainage X Satisfactory Marginal PoorFunctional flow X Satisfactory Marginal PoorCommentsPhotos
Walls & CeilingCondition X Satisfactory Marginal Poor Typical cracks Moisture stainsComments
Heating/Cooling SourceX Yes No
Comments
FloorCondition X Satisfactory Marginal Poor Sloping SqueaksComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 21
KitchenAppliancesDisposal N/A Not tested Operable: X Yes NoOven N/A Not tested Operable: X Yes NoRange N/A Not tested Operable: X Yes NoDishwasher N/A Not tested Operable: X Yes NoTrash Compactor X N/A Not tested Operable: Yes NoExhaust fan N/A Not tested Operable: X Yes NoRefrigerator N/A Not tested Operable: X Yes NoMicrowave N/A Not tested Operable: X Yes NoOther : Na Operable: Yes NoDishwasher airgap X Yes NoDishwasher drain line looped X Yes NoReceptacles present X Yes No Operable: X Yes NoGFCI X Yes No Operable: X Yes No Recommend GFCI Receptacles: X Yes No
X Potential Safety Hazard(s)Open ground/Reverse polarity: Yes X No Potential Safety HazardComments Appliances only tested for operation, working or not. Quality or extent of operation not part of testing or
inspection Recommend all countertop recepticle to be GFCI protected recepticle.
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 22
Laundry RoomLaundryLaundry sink X N/AFaucet leaks Yes X NoPipes leak Yes X No Not VisibleCross connections Yes X No Potential Safety HazardHeat source present X Yes NoRoom vented X Yes NoDryer vented N/A X Wall Ceiling Floor Not vented Plastic dryer vent not recommended
Not vented to exterior Recommend repair Safety hazardElectrical Open ground/reverse polarity: Yes X No Safety hazardGFCI present Yes X No Operable: Yes No X Recommend GFCI ReceptaclesAppliances X Washer X Dryer Water heater Furnace/BoilerWasher hook-up lines/valves X Satisfactory Leaking Corroded Not VisibleGas shut-off valve X N/A Yes No Cap Needed Safety hazard Not VisibleComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 23
1/2 BathroomBathLocation First floor half bathSinks Faucet leaks: Yes X No Pipes leak: Yes X NoTubs X N/A Faucet leaks: Yes No Pipes leak: Yes No Not VisibleShowers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not VisibleToilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaksWhirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes No
GFCI RecommendedShower/Tub area X Ceramic/Plastic Fiberglass Masonite Other
Condition: X Satisfactory Marginal Poor Rooted floorsCaulk/Grouting needed: Yes X NoWhere:
N/ADrainage X Satisfactory Marginal PoorWater flow X Satisfactory Marginal PoorMoisture stains present Yes X No Walls Ceilings CabinetryDoors X Satisfactory Marginal PoorWindow None X Satisfactory Marginal PoorReceptacles present X Yes No Operable: X Yes NoGFCI X Yes No Operable: X Yes No Recommend GFCIOpen ground/Reverse polarity Yes X No Potential Safety HazardHeat source present X Yes NoExhaust fan X Yes No Operable: X Yes No NoisyComments 1/2 bath is also laundry room
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 24
Basement Bathroom BathLocation Basement half bathSinks Faucet leaks: Yes X No Pipes leak: Yes X NoTubs X N/A Faucet leaks: Yes No Pipes leak: Yes No Not VisibleShowers X N/A Faucet leaks: Yes No Pipes leak: Yes No Not VisibleToilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaksWhirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes No
GFCI RecommendedShower/Tub area Ceramic/Plastic Fiberglass Masonite Other
Condition: Satisfactory Marginal Poor Rooted floorsCaulk/Grouting needed: Yes NoWhere:X N/A
Drainage X Satisfactory Marginal PoorWater flow X Satisfactory Marginal PoorMoisture stains present Yes X No Walls Ceilings CabinetryDoors X Satisfactory Marginal PoorWindow X None Satisfactory Marginal PoorReceptacles present X Yes No Operable: X Yes NoGFCI X Yes No Operable: X Yes No Recommend GFCIOpen ground/Reverse polarity Yes X No Potential Safety HazardHeat source present X Yes NoExhaust fan X Yes No Operable: X Yes No NoisyComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 25
2nd Floor BathroomBathLocation Second floor bathSinks Faucet leaks: Yes X No Pipes leak: Yes X NoTubs N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not VisibleShowers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not VisibleToilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaksWhirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes No
GFCI RecommendedShower/Tub area X Ceramic/Plastic Fiberglass Masonite Other
Condition: X Satisfactory Marginal Poor Rooted floorsCaulk/Grouting needed: Yes X NoWhere:
N/ADrainage X Satisfactory Marginal PoorWater flow X Satisfactory Marginal PoorMoisture stains present Yes X No Walls Ceilings CabinetryDoors X Satisfactory Marginal PoorWindow None X Satisfactory Marginal PoorReceptacles present X Yes No Operable: X Yes NoGFCI X Yes No Operable: X Yes No Recommend GFCIOpen ground/Reverse polarity Yes X No Potential Safety HazardHeat source present X Yes NoExhaust fan X Yes No Operable: X Yes No NoisyComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 26
Master Bathroom BathLocation Master bathSinks Faucet leaks: Yes X No Pipes leak: Yes X NoTubs X N/A Faucet leaks: Yes No Pipes leak: Yes No Not VisibleShowers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not VisibleToilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaksWhirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes No
GFCI RecommendedShower/Tub area X Ceramic/Plastic Fiberglass Masonite Other
Condition: X Satisfactory Marginal Poor Rooted floorsCaulk/Grouting needed: Yes X NoWhere:
N/ADrainage X Satisfactory Marginal PoorWater flow X Satisfactory Marginal PoorMoisture stains present Yes X No Walls Ceilings CabinetryDoors X Satisfactory Marginal PoorWindow None X Satisfactory Marginal PoorReceptacles present X Yes No Operable: X Yes NoGFCI X Yes No Operable: X Yes No Recommend GFCIOpen ground/Reverse polarity Yes X No Potential Safety HazardHeat source present X Yes NoExhaust fan X Yes No Operable: X Yes No NoisyComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 27
Family RoomRoomLocation First floor
North Type FAMILY ROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan X None Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted X N/A Yes NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareCommentsPhotos
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 28
1st Floor BedroomRoomLocation First floor
North Type BEDROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan None X Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted N/A Yes X NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 29
Master BedroomRoomLocation Second floor
North Type MASTER BEDROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan None X Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted N/A Yes X NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 30
Bedroom 1RoomLocation Second floor
NE Type BEDROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan None X Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted N/A Yes X NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 31
Bedroom 2RoomLocation Second floor
SE Type BEDROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan None X Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted N/A Yes X NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 32
Bedroom 3RoomLocation Second floor
SW Type BEDROOMWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor X Squeaks Slopes Tripping hazardCeiling fan None X Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted N/A Yes X NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 33
InteriorFireplace
NoneLocation(s) Family roomType Gas X Wood Solid fuel burning stove Electric VentlessMaterial X Masonry Metal (pre-fabricated) Metal insert Cast IronMiscellaneous Blower built-in Operable: Yes No Damper operable: X Yes No
Open joints or cracks in firebrick/panels should be sealed Fireplace doors need repairDamper modified for gas operation X N/A Yes No Damper missingHearth extension adequate X Yes NoMantel N/A X Secure Loose Recommend repair/replacePhysical condition Satisfactory Marginal Poor X Recommend having flue cleaned and re-examined
Not evaluatedComments
Stairs/Steps/BalconiesNone
Condition X Satisfactory Marginal Poor Loose/MissingHandrail X Satisfactory Marginal Poor Safety hazard Hand Rail/Railing/Balusters recommendedRisers/Treads X Satisfactory Marginal Poor Risers/Treads uneven Trip hazardComments
Smoke/Carbon Monoxide detectorsSmoke Detector X Present Not Present Operable: X Yes No Not tested Recommend additional
Safety HazardCO Detector Present X Not Present Operable: Yes No Not tested Recommend additional
Safety HazardComments Recommend changing smoke detectors batteries every 6 months
Attic/Structure/Framing/InsulationN/A
Access Stairs X Pulldown X Scuttlehole/Hatch No Access OtherInspected from X Access panel In the attic OtherLocation Hallway X Bedroom Closet X Garage OtherAccess limited by Small scuttle was partially blocked by clothing etcFlooring Complete Partial X NoneInsulation X Fiberglass Batts X Loose Cellulose Foam Other Vermiculite Rock wool
Depth: 12+ inches Damaged Displaced Missing CompressedRecommend additional insulation
Installed in Rafters/Trusses Walls X Between ceiling joists Underside of roof deck Not VisibleVapor barriers Kraft/foil faced Plastic sheeting X Not Visible Improperly installedVentilation X Ventilation appears adequate Recommend additional ventilation Recommend baffles at eavesFans exhausted to Attic: Yes X No Recommend repair Outside: X Yes No Not VisibleHVAC Duct N/A X Satisfactory Damaged Split Disconnected Leaking Repair/Replace
Recommend InsulationChimney chase N/A X Satisfactory Needs repair Not VisibleStructural problems observed Yes X No Recommend repair Recommend structural engineerRoof structure X Rafters Trusses X Wood Metal X Collar ties Purlins Knee wall Not Visible
OtherCeiling joists X Wood Metal Not VisibleSheathing X Plywood OSB Planking Rotted Stained DelaminatedEvidence of condensation Yes X NoEvidence of moisture Yes X NoEvidence of leaking Yes X NoFirewall between units X N/A Yes No Needs repair/sealingElectrical X No apparent defects Open junction box(es) Handyman wiring
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 34
InteriorAttic/Structure/Framing/Insulation cont.Electrical cont. Knob and tube covered with insulation Safety HazardComments Rafters appeared to be in overall adequate condition.
Roof sheathing, examined from the attic, showed no major defects or moisture damage. Insulation was sufficient for homes in this area. Ventilation was normal. Bathroom exhaust fans appeared to be vented to the exterior. Chimney section in attic appeared to be in satisfactory condition.
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 35
BasementStairsCondition X Satisfactory Marginal Poor Typical wear and tear Need repair Risers Uneven
Safety HazardHandrail X Yes No Condition: Satisfactory Loose X Handrail/Railing/Balusters recommendedHeadway over stairs X Satisfactory Low clearance Safety hazardCommentsPhotos
FoundationCondition Satisfactory Marginal Have evaluated Monitor X Not ElevatedMaterial ICF Brick Concrete block Stone Masonry X Poured concrete woodHorizontal cracks X None North South East WestStep cracks X None North South East WestVertical cracks X None North South East WestCovered walls None X North X South X East X WestMovement apparent X None North South East WestIndication of moisture Yes X No Fresh Old stainsComments Foundation walls were covered with paneling/drywall and were not visible.
FloorMaterial Concrete Dirt/Gravel X Not Visible OtherCondition X Satisfactory Marginal Poor Typical cracks Not VisibleComments Unfinished portions of the floor appeared to be in overall adequate condition.
Seismic boltsN/A X None visible
Condition Appear satisfactory Recommend evaluationComments
DrainageSump pump X Yes No X Working Not working Needs cleaning Pump not testedFloor drains X Yes Not Visible X Drains not testedComments
Girders/BeamsX Not Visible
Condition Satisfactory Marginal Poor Stained/RustedMaterial Steel Wood Concrete LVL Not VisibleComments
ColumnsNot Visible
Condition X Satisfactory Marginal Poor Stained/Rusted
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 36
BasementColumns cont.Material X Steel Wood Concrete Block Not VisibleComments
JoistsNot Visible
Condition X Satisfactory Marginal PoorMaterial X Wood Steel Truss Not Visible 2x8 X 2x10 2x12 Engineered I-Type
Sagging/altered joistsComments
SubfloorX Not Visible
Condition Satisfactory Marginal Poor Indication of moisture stains/rottingComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 37
Basement Recreation RoomLiving RoomLocation BasementWalls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan X None Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted X N/A Yes NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 38
Crawl SpaceCrawl space
N/AType Full crawlspace X Combination basement/crawl space/slabConditioned (heated/cooled) Yes X NoComments
AccessLocation Exterior Interior hatch/door X Via basement No accessInspected from X Access panel In the crawl spaceComments
Foundation wallsCondition X Satisfactory Marginal Have Evaluated Monitor Cracks MovementMaterial Concrete block X Poured concrete Stone ICF Wood BrickComments
FloorMaterial Concrete Gravel X Dirt OtherCondition Typical cracks X Not Visible Vapor barrier presentComments
Seismic boltsN/A X None visible
Condition Appear satisfactory Recommed evaluationComments
DrainageSump pump Yes X No Operable: Yes No Pump not testedStanding water Yes X No Not VisibleEvidence of moisture damage Yes X NoComments
VentilationX N/A
Location X Wall vents Power vents None apparentCondition Additional ventilation recommended Evidence of moisture damageComments No ventilation issues noted at time of inspection
Girders/Beams/ColumnsMaterial X Steel Wood MasonryCondition Satisfactory Marginal Poor X Not Visible Sagging/AlteredComments
JoistsMaterial X Wood Steel Truss Not Visible 2x8 2x10 X 2x12 Engineered I-Type
Sagging/Altered joistsCommentsCondition X Satisfactory Marginal Poor
SubfloorX Not Visible
Condition Indication of moisture stains/rottingComments
InsulationNone
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 39
Crawl SpaceInsulation cont.Type X Fiberglass Cellulose Rockwool Foam Not VisibleLocation X Walls Between floor joists OtherComments
Vapor barrierPresent X Yes No X Not Visible Improperly installedMaterial Kraft/foil faced X Plastic Not Visible OtherCondition X Satisfactory Marginal PoorComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 40
PlumbingWater serviceMain shut-off location Outside at curbside
Interior just inside crawl space access. Water entry piping Not Visible X Copper/Galv. PVC Plastic CPVC Plastic Polybutylene Plastic
PEX Plastic Lead PolyethyleneLead other than solder joints Yes No X Unknown Service entryVisible water distribution piping X Copper Galvanized PVC Plastic X CPVC Plastic Polybutylene Plastic
PEX Plastic OtherCondition X Satisfactory Marginal PoorFlow X Satisfactory Marginal Poor Water pressure over 80 psi Recommend plumber evaluate
Recommend pressure regulatorPipes Supply/Drain Corroded Leaking Valves broken/missing Dissimilar metal
Cross connection: Yes X No Safety Hazard Recommend repairRecommend a dielectric union X Satisfactory
Drain/Waste/Vent pipe Copper Cast iron Galvanized X PVC ABS BrassCondition X Satisfactory Marginal PoorSupport/Insulation N/A
Type:Metal strapping
Traps proper P-Type X Yes No P-traps recommendedDrainage X Satisfactory Marginal PoorInterior fuel storage system X N/A Yes No Leaking: Yes NoFuel line X N/A Copper Brass Black iron Stainless steel CSST Not Visible Galvanized
Recommend CSST be properly bondedCondition X Satisfactory Marginal Poor Recommend plumber evaluateComments
Main fuel shut-off locationX N/A
LocationComments
Well pumpX N/A
Type Submersible In basement Well house Well pit Shared wellPressure gauge operable Yes No Well pressure: (null) Not VisibleComments
Sanitary/Grinder pumpN/A Operable: X Yes No
Sealed Crock Sealed crock: X Yes NoCheck Valve Check valve: X Yes NoShut-off Valve Shut-off valve: X Yes NoVented X Yes NoComments
Water heater #1N/A
General Brand Name:WhirlpoolSerial #: 0438115094Capacity:50Approx. age:10-15+
Type Gas X Electric Oil LP Other
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 41
PlumbingWater heater #1 cont.Combustion air venting present Yes No X N/ASeismic restraints needed Yes No X N/ARelief valve X Yes No Extension proper: X Yes No Missing Recommend repair Improper materialVent pipe X N/A Satisfactory Pitch proper Improper Rusted Recommend repairCondition Satisfactory X Marginal PoorCommentsPhotos
Water heater #2X N/A
General Brand Name:Serial #: (null)Capacity:Approx. age:
Type Gas Electric Oil LP OtherCombustion air venting present Yes No N/ASeismic restraints needed Yes No N/ARelief valve Yes No Extension proper: Yes No Missing Recommend repair Improper materialVent pipe N/A Satisfactory Pitch proper Improper Rusted Recommend repairCondition Satisfactory Marginal PoorComments
Water softenerNone
Loop installed X Yes NoPlumbing hooked up X Yes NoPlumbing leaking Yes X NoComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 42
Heating SystemHeating systemUnit #1 Brand name:
TraneApprox. age:Installed 1-7-15
Unknown Model #: TEM3AOC42S41SAA Serial #: 13214NS2BV X Satisfactory MarginalPoor Recommended HVAC technician examine
Unit #2 X NoneBrand name:Approx. age:
UnknownModel #:Serial #: (null) Satisfactory Marginal Poor Recommended HVAC technician examine
Energy source Gas LP Oil X Electric Solid fuelWarm air system Belt drive X Direct drive Gravity Central system Floor/wall furnaceHeat exchanger N/A X Sealed X Not Visible Visual w/mirror Flame distortion Rusted
Carbon/soot buildupCarbon monoxide X N/A Detected at plenum Detected at register Not testedCO test Tester:
N/aCombustion air venting present X N/A Yes NoControls Disconnect: X Yes No X Normal operating and safety controls observed
Gas shut off valve: Yes NoDistribution X Metal duct Insulated flex duct X Cold air returns Duct board Asbestos-like wrap
Safety HazardFlue piping X N/A Satisfactory Rusted Improper slope Safety hazard Recommend repair/replaceFilter X Standard Electrostatic X Satisfactory Needs cleaning/replacement Missing
Electronic (not tested)When turned on by thermostat X Fired Did not fire Proper operation: X Yes No Not testedHeat pump X N/A Supplemental electric Supplemental gasSub-slab ducts X N/A Satisfactory Marginal Poor Water/Sand Observed: Yes NoSystem not operated due to X N/A Exterior temperature OtherComments
Boiler systemX N/A
General Brand name:Approx. age:Model #:Serial #: (null)
Energy source Gas LP Oil Electric Solid fuelDistribution Hot water Baseboard Steam Radiator Radiant floorCirculator Pump Gravity Multiple zonesControls Temp/pressure gauge exist: Yes No Operable: Yes NoOil fired units Disconnect: Yes NoCombustion air venting present Yes No N/ARelief valve Yes No Missing Extension proper: Yes No Recommend repair/replaceOperated When turned on by thermostat: Fired Did not fireOperation Satisfactory: Yes No Recommend HVAC technician examine before closingComments
Other systemsX N/A
Type Electric baseboard Radiant ceiling cable Gas space heater Solid fuel burning stoveProper operation Yes NoSystem condition Satisfactory Marginal Poor Recommend HVAC Technician Examine
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 43
Electric/Cooling SystemMain panelLocation BasementCondition X Satisfactory PoorAdequate Clearance to Panel X Yes NoAmperage/Voltage Unknown 60a 100a 150a X 200a 400a 120v/240vBreakers/Fuses X Breakers FusesAppears grounded X Yes No Not VisibleGFCI breaker Yes X No Operable: Yes NoAFCI breaker Yes X No Operable: Yes No Not TestedMain wire Copper X Aluminum Not Visible Double tapping of the main wire
Condition: X Satisfactory Marginal PoorBranch wire X Copper Aluminum X Solid Branch Aluminum Wiring Not Visible Safety HazardBranch wire condition X Satisfactory Poor Recommend electrician evaluate/repair X Romex BX cable
Conduit Knob/Tube Double tapping Wires undersized/oversized breaker/fusePanel not accessible Not evaluated
Reason:Comments Branch breaker distribution appeared normal.
No signs of overheating were evident at the time of the inspection. Outlets were randomly tested and had correct polarity, except as noted.
Photos
Sub panel(s)None apparent
Location(s) Location 1:BasementLocation 2:Location 3:
Evaluation Panel not accessible Not evaluatedReason:N/a
Recommend separating/isolating neutrals Recommend electrician repair/evaluate boxBranch wire X Copper Aluminum Safety hazard Neutral/ground separated: X Yes No
Neutral isolated: X Yes NoCondition X Satisfactory Marginal PoorComments Recommend removing or properly terminating unused wires and breakers
Evaporator Coil Section Unit #1N/A
General X Central system Wall unitLocation:Basement utility roomAge: 12/2014 mfr date
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 44
Electric/Cooling SystemEvaporator Coil Section Unit #1 cont.General cont. Serial #: 14491H314FEvaporator coil Satisfactory X Not Visible Needs cleaning DamagedRefrigerant lines Leak/Oil present Damage Insulation missing X SatisfactoryCondensate line/drain To exterior To pump Floor drain sump pumpSecondary condensate line/drain Present: Yes X No Needed: Yes X No Primary pan appears clogged
Recommend technician evaluateOperation Differential: 30-40Condition X Satisfactory Marginal Poor Recommend HVAC technician examine/clean/service
Not operated due to exterior temperatureComments
Evaporator Coil Section Unit #2X N/A
General Central system Wall unitLocation:Age:Serial #: (null)
Evaporator coil Satisfactory Not Visible Needs cleaning DamagedRefrigerant lines Leak/Oil present Damage Insulation missing Satisfactory
Recommend/Replace damaged/missing insulationCondensate line/drain To exterior To pump Floor drain OtherSecondary condensate line/drain Present: Yes No Needed: Yes No Primary pan appears clogged
Recommend technician evaluateOperation Differential: (null)Condition Satisfactory Marginal Poor Recommend HVAC technician examine/clean/service
Not operated due to exterior temperatureComments
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 45
Living RoomLiving RoomLocation First floor
South Walls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan X None Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted X N/A Yes NoDoors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareCommentsPhotos
This confidential report is prepared exclusively for Ryan Lewis© 2015 Jason Thompson
646 Johnson Dr Carmel, IN 46033 Page 46
Dining RoomDining RoomLocation First floor
SW Walls & Ceiling X Satisfactory Marginal Poor Typical cracks DamageMoisture stains Yes X No
Where:Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazardCeiling fan X None Satisfactory Marginal Poor Recommend repair/replaceElectrical Switches: X Yes No X Operable Receptacles: X Yes No X Operable
Open ground/Reverse polarity: Yes X No Safety hazard Cover plates missingHeating source present X Yes No Holes: Doors Walls CeilingsBedroom Egress restricted X N/A Yes NoDoors X None Satisfactory Marginal Poor Cracked glass Broken/Missing hardwareWindows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glass
Broken/Missing hardwareComments