HL Series Centrifugal Fire Pumps
Installation Instructions
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Operational Limits .................................................................................... 2
Available Pump Models ........................................................................... 2
Installation Instructions ........................................................................... 3
Pump Lifting Points ................................................................................ 3
Pump Mounting ...................................................................................... 4
Pump Intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Low Pressure Discharge ........................................................................ 5
High Pressure Discharge ....................................................................... 5
High Pressure Inlet Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
High Pressure Relief Valve .................................................................... 5
Read through the installation Thermal Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
instructions carefully before
installing your Waterous HL Series Fire Pump.
Piston Primers ....................................................................................... 6
Lubrication ............................................................................................. 7
Pedestal (Primer Housing) Fill and Drain ........................................... 7
K Series Transmission Fill and Drain . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Pump Water Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NOTE: Instructions subject to change without notice Tachometer Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Optional Items ...................................................................................... 10
Solenoid Valve for PIV (Priming Isolation Valve) . . . . . . . . . . . . . . . 10
RTP Foam Systems: ....................................................................... 11
Installed on Pump at Factory ....................................................... 11
Mounted Remotely from Pump .................................................... 11
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Final Checks ........................................................................................... 13
Lubrication ........................................................................................... 13
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
F-1031, Section 3032 (Rev: 9/5/17)
Waterous Company, 125 Hardman Avenue South, South St. Paul, Minnesota 55075 USA (651) 450-5000
www.waterousco.com
![Page 2: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/2.jpg)
F−1031, Section 3032 Page 2 of 13
Introduction
This instruction covers the typical installation of any HL Series pump regardless of the model or intake and discharge.
General Description
The HL series are pedestal mounted fire pumps designed to operate in two modes:
Low Pressure Mode
Pump only low pressure water.
High Pressure Mode
Simultaneously pump low and high pressure water.
Three performance levels are available:
Before operating the HL pump, read the following instructions carefully.
Operational Limits
Maximum Low Pressure
Control the speed of the pump so that the maximum low pressure is limited to 17 bar.
Maximum High Pressure
The maximum high pressure is internally limited by the high pressure relief valve not to exceed 55 bar.
Maximum Angle of Inclination
The maximum angle of inclination for pump operation is 15 degrees.
Maximum Pump Speed
The pump has a maximum operating speed of 3450 rpm. Do not exceed this speed.
Maximum Priming Speed
When priming, the pump speed should be limited to 2600 rpm.
Low Pressure High Pressure Model Series
2000 L/min @ 10 bar 400 L/min @ 40 bar HL200
3000 L/min @ 10 bar 400 L/min @ 40 bar HL300
4000 L/min @ 10 bar 400 L/min @ 40 bar HL400
Available Pump Models
![Page 3: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/3.jpg)
F−1031, Section 3032 Page 3 of 13
Installation
Pump Lifting Points
Direct Drive Models HL200D, HL300D, HL400D
Gear Drive Models HL200K, HL300K, HL400K
![Page 4: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/4.jpg)
F−1031, Section 3032 Page 4 of 13
Pump Mounting
Select a mounting location that will make the pump and its accessories readily available for maintenance. Provide room around the pump for all intended piping, instrumentation and drive system.
Pump Mounting Flange
For mounting holes are located on the pump pedestal that are to be used to secure the pump to a mounting plate (plate not supplied by Waterous). The mounting plate should be designed with the four mounting holes (see diagram below for dimensions).
The plate should also provide clearance for the volute flange as identified in the diagram below.
Attach the pump to the mounting plate and secure to the vehicle with M16 bolts.
Driveline Connection
The pump mounting location should be such that the drive line shaft length and angles are in accordance with the drive line manufacturer's specification.
Connect the driveline to the companion flange provided on the pump input shaft. use appropriate fasteners and torque following the driveline manufacturer's specification.
NOTICE
Tighten fasteners to the following specifications: 176-190 • (130-140 lb-ft).
N m
Pump Mounting
![Page 5: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/5.jpg)
F−1031, Section 3032 Page 5 of 13
NOTICE
Install a suitable 1/2 in. fitting and tube or hose as sembly and route to one of the following locations:
To the holding tank, vehicle tank or to atmosphere (ground).
Pump Intake
If piping is to be attached to the pump intake, provisions must be made to allow the removal of the pump intake adapter while the pump remains in the vehicle. This is necessary to provide access to the pump for repairs and maintenance.
Low Pressure Discharge
Any piping connected to the low pressure discharge open ings on the pump discharge manifold must be properly sup ported and secured.
High Pressure Discharge
Any piping connected to the high pressure discharge open ing on the pump discharge manifold must be suitable for high pressure and properly supported and secured.
High Pressure Inlet Strainer
Pump installation should provide access as this is a main tenance item.
High Pressure Relief Valve
Pump installation should provide access as this is a main tenance item.
Thermal Relief Valve
The valve is designed to discharge water if the temperature of the pump water reaches 49° C. The discharged water must be diverted away from the pump operator.
Installation of Components
NOTICE
The piping must not be restricted in any way.
NOTICE
A suitable strainer should be installed in each intake opening on the pump.
![Page 6: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/6.jpg)
F−1031, Section 3032 Page 6 of 13
Clearance for Service
Piston Primers
Primer Discharge
The pump has (2) two automatic piston primers located on each side of the pump pedestal. Pump installation must provide 50 mm (2 in.) of space behind the primers to allow them to be removed for servicing.
During operation, the primers can discharge water. This wa ter exits through the primer discharge outlets. It is important that this water is not restricted in any way. Typically the water is discharged to the ground.
A suitable hose may be used to assist in directing the water to the ground, however, it is not recommended that any angled fittings be used as they will restrict the flow.
Piston Primers
NOTICE
The piping or hose must not be restricted in any way.
![Page 7: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/7.jpg)
F−1031, Section 3032 Page 7 of 13
Lubrication
Models HL200 and HL300D
Pedestal (Primer Housing) Fill and Drain - HL200D, HL300D
Models HL200K, HL300K, HL300D, HL400D
Pedestal (Primer Housing) and K Series Transmission Fill and Drain
See next page for K Series Transmission requirements.
NOTICE
Pump installation must provide for access to the lubrication fills and drains.
![Page 8: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/8.jpg)
F−1031, Section 3032 Page 8 of 13
Lubrication
Models HL200K, HL300K and HL400K Only
Transmission Mounted Vertically
NOTICE
Pump installation must provide for access to the lubrication fills and drains.
![Page 9: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/9.jpg)
NOTICE
All piping, fittings and valves must be suitable for pres sures that are present in the low and high pressure stages.
Pump Water Drains
The pump is provided with two (2) 3/8 in. BSPT taps to allow water to be drained. Once is located on the low pressure stage volute and one on the high pressure stage volute.
The drains should be fitted with valves and piping. The pip ing should be routed to a suitable draining location.
Tachometer Connection
If Optional Control Panel was not furnished:
The pump includes a magnetic pick-up installed in the pump pedestal which allows a tachometer to be connected. A 10 meter cable is included with the pump which mates with the magnetic pick-up (Amphenol connector part no. MS3106A-10SL-4S).
Wire the cable to the tachometer. Note that the magnetic pick-up produces four pulses per revolution of the pump shaft.
If Optional Control Panel was furnished:
The tachometer is included in the control panel and the wir ing to the magnetic pick-up was completed at the factory.
Optional Items
F−1031, Section 3032 Page 9 of 13
Solenoid Valve for PIV (Priming Isolation Valve)
Drain Taps
Pump Water Drains
![Page 10: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/10.jpg)
F-1031, Section 3032 Page 10 of 13
Solenoid Valve for PIV (Priming Isolation Valve)
2.750
69.85
1.188
30.16
MOUNTING FLANGE : 1.563 i
·'":f-
19.84
39.69
2X M4 MOUNTING HOLE
I SOLENOID DIMENSIONS
AllDIMENSIONS SHOWN INCH ) AS INCH/MILLIMETER (MILLIMETER
GROMMET TWO 16 OR 18
AWG WIRES
CONNECTOR
HOUSING
SOLENOID
VALVE TERMINAL
SCREWS
NOTE: SOLENOID IS NOT
POLARITY SENSITIVE SOLENOID WIRING
AIR INLET CONNECTOR ON PUMP
PRIMING ISOLATION VALVE IPIVI.
CONNECT 6mm TUBING TO
PUSH-ON FITTING
TO PTO ACTUATOR
PTO SWITCH
6mm TUBING 16 OR 18 AWG WIRE
PRIMING VAL VE SOLENOID,
REMOTELY MOUNT IN CHASSIS
ISEE DIMENSION AND WIRING DETAILS!
FROM CHASSIS
AIR SUPPLY
6mm TUBE X 1/4
BSP FITTINGS
IL:9561
![Page 11: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/11.jpg)
F−1031, Section 3032 Page 11 of 13
RTP Foam System
(RTP Foam System is Optional)
Installed on Pump at Factory:
Install the Foam Suction Hose:
Install the barbed fitting in the tap located on the bottom of the Proportioner Valve.
Attach the hose and wand to the barbed fitting using the clamps provided.
Mounted Remotely from Pump:: See separate Installation Instructions F-1031, Section 2321.
RTP Foam System (Installed at Factory)
![Page 12: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/12.jpg)
F−1031, Section 3032 Page 12 of 13
Control Panel
(Control Panel is Optional)
Complete Electrical Connections for the fol lowing:
• Tachometer / Hourmeter
• Pump Overheat Module
• Pump Engaged Module
Complete Electrical Connections and Tank Connections for the following:
• Optional Tank Level Monitors
Control Panel
![Page 13: HL Series Centrifugal Fire Pumps Installation Instructions · F−1031, PageSection 3032 14of Final Checks Lubrication Before operating the pump, add the lubricants specified below](https://reader036.fdocuments.us/reader036/viewer/2022071015/5fce15dcdad6d814c02d0c64/html5/thumbnails/13.jpg)
F−1031, Section 3032 Page 13 of 13
Final Checks
Lubrication
Before operating the pump, add the lubricants specified below (see Pages 7 and 8 for fill locations.)
Models HL200D, HL300D and HL400D
Lubrication required for Pedestal (Primer Housing) Only
Pedestal (Primer Housing) Lubricant Capacity
SAE 10W-30 Motor Oil .95 Liter (1 Quart)
Models HL200K, HL300K and HL400K
Lubrication required for Pedestal (Primer Housing) and K Series Transmission
Pedestal (Primer Housing) Lubricant Capacity
SAE 10W-30 Motor Oil .95 Liter (1 Quart)
K Series Transmission Lubricant Capacity
SAE 80W-90 Gear Oil .95 Liter (1 Quart)
Testing Before operating the pump, check and verify all fasteners and connections (mounting, driveline, piping, etc.) are se cure.
To run the pump, follow instructions F-1031, Section 2408, HL Series Fire Pump Operation and Maintenance Instruc tions.
During the running of the pump, monitor for smoothness of operation, listen for unusual noises and check for leaks.
NOTICE
Failure to properly lubricate the pump may result in serious damage.
NOTICE
1. Capacities shown are approximate. Quantities listed vary based on ratio and /or mounting orientation.
2. Always fill to the marking on dipstick (pedestal) or bottom of the plug labeled “Oil Level” (K Series Transmission).
3. K Transmission breather may be removed and the hole used as the lubricant fill.
4. Synthetic oil substitutes are acceptable.