HIU Brochure - G3 G4 Eco - June 11

download HIU Brochure - G3 G4 Eco - June 11

of 20

Transcript of HIU Brochure - G3 G4 Eco - June 11

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    1/20

    Taking comfort control in

    apartments and multi-use

    dwellings to a higher level

    CourtesyofParkridge-www.d

    ickensheathvillage.com

    Giacomini Heat Interface Units(with optional Energy & Water Meters)

    G3 & G4 ECO

    G4 Eco Twin

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    2/201 T: 01454 311012 Fax: 01454 316345

    A range of models to suit every application

    G3 Twin Heat Exchanger 44kW and 58kW G3 Single Heat Exchanger 44kW

    G4 Eco Twin Heat Exchanger 44kW and 58kW G4 Eco Single Heat Exchanger 44kW

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    3/202

    Jig bracket supplied as standard

    First fix can be carried out without the heat

    interface unit being on site. Prevents site

    theft and site damage. No need to purchase

    unit until it is required, easing cash flow.

    Jig bracket is supplied as standard with

    all relevant isolating valves

    No hidden additional costs.

    Jig bracket comes with Y strainers

    supplied

    Stops any debris in the system entering the

    unit, preventing damage, blockages or any

    reduction of the efficiency of the plate heat

    exchangers.

    Jig bracket supplied as standard with Part

    L compliant WRAS approved filling loop.No hidden additional costs.

    Jig bracket available with a 50mm offset

    This leaves a 50mm void at the rear of the

    unit to enable pipework to run behind the

    main body of the unit, making installation

    faster, easier and aesthetically pleasing.

    Domestic hot water (DHW) and central

    heating (CH) circuits run in parallel

    No troublesome diverter valves, which are

    renowned for causing problems, are used or

    needed, giving a much simpler operation.

    Stainless steel heat exchangersLess likely to suffer from scale which can

    reduce efficiency and can, in extreme cases,

    block the waterway completely.

    Twin heat exchanger model gives both

    indirect CH and DHW

    Should the property develop a leak in the

    system, only the water inside the property

    would be expelled, lessening likely damage.

    Also instantaneous hot water availability, no

    storage or cylinder required.

    Single plate heat exchanger models ideal for

    direct DHW, where a cylinder or hot water

    storage is preferred, or where a cylinder is

    already in place, e.g. the replacement market.

    Optional energy meter

    Allows each tenant to be billed for the energy

    he or she consumes.

    Optional water meter

    Water meter can be housed securely inside

    the HIU when fitted outside the apartment.

    Built-in dynamic balancing and

    commissioning valve

    Balances the system throughout the

    apartment block when a large number of

    units are installed, maintaining optimum

    performance in each apartment.

    HIU housed in a metal, powder-coated

    casing, which is lockable

    Aesthetically pleasing and secure.

    Lightweight and compact

    Can be housed in a cupboard. Easy to handleand install.

    E: [email protected] W: www.giacomini.co.uk

    The New Giacomini G3 & G4 Eco Heat InterfaceUnits for communal heating systems

    Main Benefits AT A GLANCE

    Helping to minimise the heat source

    requirement and further reduce energy

    consumption

    The G4 Eco has, as standard, a motorized valve

    fitted that can shut off the heat exchanger for

    heating when not in use to save energy and cut

    fuel bills. It also has an option to fit a further

    motorized valve on the domestic hot water heat

    exchanger. This combination of valves

    minimizes the energy extracted from the

    primary flow, allowing a greater diversity factor

    and a smaller heat source requirement when

    sizing the boiler. This can result in significant

    energy savings, lower emissions and is ideal for

    use with renewable technologies, where the

    energy produced is limited.

    Additional Benefits of the G4 ECOG4 Eco Twin

    G3 Twin

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    4/203 T: 01454 311012 Fax: 01454 316345

    With no need for a gas supply, flues, or hot water cylinders,

    the new heat interface unit from Giacomini provides all the

    benefits of a combi boiler without the combustion.

    Compact in size and simple to install, this versatile unit

    controls and measures hot water and heating usage in

    apartments supplied from a communal boiler system. It

    delivers major benefits to everyone concerned, from the

    building contractor and installer to the tenants and

    landlords.

    For the building contractor and the installer, the advantages

    are simplicity of installation; theres no need for a gas supply,

    flue or hot water cylinder and little or no servicing

    requirement once installed. With no need for hot water

    storage, Giacominis neat and compact heat interface unit

    its just 450mm wide by 670mm high and 200mm in depth

    also saves on valuable space, compared to a conventional

    individual heating system.

    For the tenants and the landlord there are major advantages.

    The new heat interface unit meets the need to control and

    monitor the heating and sanitary water consumption of

    tenants in flats, apartments or multi-dwelling buildings,

    according to their individual needs.

    Monitoring energy consumptionOne of the key advantages for the tenant is the direct linking

    of their energy bill to personal consumption. For the landlord,

    the key advantage is the ability to remotely monitor and

    analyse the energy consumption of both individual users and

    the overall system through a special interface fitted within the

    unit. This uses the latest M-BUS communications technology,

    standardised throughout Europe.

    The principal difference between the heat interface unit and a

    conventional individual boiler is that the usual heating source

    is replaced with a heat exchanger fed from a central

    communal hot water supply. A primary plate heat exchanger is

    used for the provision of heating and a secondary plate heatexchanger for domestic hot water production. These are

    configured as a sealed system in the heat interface unit,

    together with an expansion tank, safety valve and filling loop.

    The result gives each Giacomini unit the effectiveness and

    flexibility of a combi boiler, without the need for individual

    combustion.

    Accurate measurement of energy usage is obtained via

    compact volumetric meters, which are of a single jet turbine

    type that provide high precision and reliability in compliance

    with standard EN 1434. Well engineered, all components are

    installed in a durable zinc-plated casing, supplied with fittings

    for easy wall mounting.

    Advantages for the building contractor

    Simplicity of installation no gas supply, no flues and

    no cylinders

    Jig Bracket, Valves, Y Strainer and WRAS approved Filling

    Loop supplied as standard (see page 5)

    Saves space no hot water cylinder required

    Lower servicing costs

    Advantages for the tenant

    The tenant is aware that bills are linked directly to personalconsumption

    Optional energy metering display allows tenants to see how

    much energy is being consumed and to individually adapt to

    changing circumstances

    Greater efficiencies for individual users lowers both costs

    and emissions

    Advantages for the landlord

    Through remote monitoring, Giacomini heat interface units

    provide the landlord with comprehensive data for analysis

    with a consequent major energy saving opportunity Possibility of central conversion to other kinds of fuel,

    without major cost implications for satellite units

    Adaptable for remote heating control

    More secure and less intrusive, through centralised

    data collection

    Maintenance costs shared across all residents

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    5/204E: [email protected] W: www.giacomini.co.uk

    Data centralisation

    The direct reading of measured data is possible on each

    metering device, using an analogue or digital display. However,

    this may not conform to tenants privacy agreements, where

    metering units are installed in common areas or outside

    apartments.

    Additionally, direct reading of individual meters is time

    consuming, subject to human error and requires installation

    of metering units in positions easy to access. For these

    reasons, Giacomini metering modules and heat interface units

    are provided with metering devices fitted with a special

    interface for M-BUS communication, the European standard

    for remote reading of energy meters. All data is detected

    electronically so that it can be sent via the communication

    M-BUS.

    A concentrator periodically interrogates all M-BUS devices,

    collecting consumption data and making it available locally

    or remotely, for sharing and analysis. Data reading becomes

    fast, convenient and possible at all times, even when tenants

    are out.

    All the benefits of a

    combi boiler without

    the combustion

    Optional accessories

    Sanitary water meter (M-BUS)

    For the monitoring of water consumption via M-BUS to central

    collection point.

    Other meter options, such as wireless / pre-pay meters, are

    available on request.

    Energy meter (M-BUS)

    For the monitoring of energy consumption sending data to a

    central collection point via M-BUS.

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    6/20

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    7/206E: [email protected] W: www.giacomini.co.uk

    1 Energy meter (optional)

    1a = volumetric reader

    1b = meter display

    2 Sanitary water meter (optional)

    3 Insulation in expanded PEx (optional)

    4 Electrical motor for the zone valve for DHW

    production (optional)

    5 Jig with interception valves

    Insulation panel

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    8/207 T: 01454 311012 Fax: 01454 316345

    G4 Single

    G4 Twin

    G3 TwinG3 Single

    Operation

    Technical data - All models - G3 & G4

    Maximum working temperature of the primary circuit and

    secondary circuits (heating and sanitary): 90C

    Maximum working pressure of the primary circuit and

    secondary sanitary: 10 bar

    Maximum working pressure of the heating secondary circuit:

    3 bar (safety valve setting)

    Nominal primary flow: 1000 1250 L/h (depending on the

    required sanitary power and the type of heating, by radiant

    floor or by radiators)

    Versions and part numbers

    Part number Type Heat exchanger

    nominal power

    G3 Single Heating 44kW

    G3 Twin Heating and DHW production 44kW

    G3 Twin Heating and DHW production 58kW

    G4 Eco Single Heating 44kW

    G4 Eco Twin Heating and DHW production 44kW

    G4 Eco Twin Heating and DHW production 58kW

    Table 1 Codes

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    9/208E: [email protected] W: www.giacomini.co.uk

    Sanitary:cold inlet (Pages 9/10: Fig.5-C), cold outlet (Fig.5-D),

    hot outlet (Fig.5-E). In place of the spacer (Fig.5-9), a sanitary

    water meter can be installed.

    Heating:inlet (Fig.5-F) and outlet (Fig.5-G). The circuit is

    simply composed of exchanger and circulator. As it deals with

    a closed circuit, the equipment is completed by: expansion

    vessel, safety valve, manometer.

    Primary:flow (Fig.5-B) and return (Fig.5-A). The energy meter

    can be installed in place of the spacer (Fig.5-8, installing the

    inlet temperature probe in the appropriate housing (Fig.5-10).

    For G3-G4 single, the primary circuit operates only for the

    heating circuit; the primary circuit is composed of a balancing

    valve and a differential pressure controller that work togetherto perform automatic balancing (see Figure 3 below); the heat

    exchanger and the thermostatic valve with remote bulb

    regulate the power for the heating circuit. The zone valve can

    manage the heating by means of a chrono-thermostat.

    For G3-G4 twin, the primary circuit is divided in two

    symmetrical arms: one is for the heating handling, the other is

    for the production of hot sanitary water. These two arms are

    completed by: heat exchanger, thermostatic valve with remote

    bulb, the balancing valve, and differential pressure controller.

    The balancing valve and a differential pressure controller

    valve work together to perform the automatic balancing (see

    Figure 3). The zone valve can manage the holiday function(motor of the zone valve is optional).

    Figure 4 Balancing devices

    Differential pressure controllerNOTE: Setting scale in RED

    Static balancing valve

    NOTE: Setting scale in WHITE

    Figure 3 Automatic balancing operation for the primary

    circuit.

    (QA = Primary flow rate; QB = Secondary flow rate;

    QC = Bypass flow rate)

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    10/209 T: 01454 311012 Fax: 01454 316345

    Components G3

    Table 2 Components (see Figure 5)

    Figure 5 Components

    A = Primary outlet

    B = Primary inlet

    C = Cold water inlet

    D = Cold water outlet

    E = Hot water outlet

    F = Heating inlet

    G = Heating outlet

    1 Heat exchanger, heating

    function

    2 Manual air vent, primary

    circuit

    3 Expansion vessel, heating

    circuit

    4 Primary balancing -

    differential pressure

    controller valve

    5 Primary balancing staticbalancing valve

    6 Heat exchanger, sanitary

    hot water function

    7 Backflow preventer

    8 Spacer pipe for energy

    meter

    9 Spacer pipe for sanitary

    water meter

    10 Flow temperature probe

    housing for energy meter

    11 Manual air vent, heating

    circuit

    12 Thermostatic valve, heating

    function

    13 Electric box

    14 Primary balancing for

    heating circuit static

    balancing valve

    15 Thermostatic valve sensor

    heating function

    16 Thermostatic valve,

    sanitary hot water function

    17 Circulator, heating function

    18 Thermostatic valve,sanitary hot water function

    19 Manometer heating

    function

    20 Safety valve, heating

    circuit

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    11/2010E: [email protected] W: www.giacomini.co.uk

    Components G4 Eco

    Figure 5 Components

    Table 2 Components (see Figure 5)

    A = Primary outlet

    B = Primary inlet

    C = Cold water inlet

    D = Cold water outlet

    E = Hot water outlet

    F = Heating inlet

    G = Heating outlet

    1 Heat exchanger, heating

    function

    2 Manual air vent, primary

    circuit

    3 Primary balancing for

    heating circuit static

    balancing valve

    4 Primary balancing -

    differential

    5 Primary balancing static

    balancing valve

    6 Heat exchanger, sanitary

    hot water function

    7 Backflow preventer

    8 Spacer pipe for energy

    meter

    9 Spacer pipe for sanitary

    water meter

    10 Flow temperature probe

    housing for energy meter

    11 Manual air vent, heating

    circuit

    12 Thermostatic valve, heating

    function

    13 Electric box

    14 Motorized zone valve

    heating function pressure

    controller valve

    15 Expansion vessel, heating

    circuit

    16 Thermostatic valve sensor

    heating function

    17 Zone valve for DHW

    production isolation

    18 Thermostatic valve,

    sanitary hot water function

    19 Circulator, heating function

    20 Thermostatic valve sensor

    sanitary hot water function

    21 Manometer heating

    function

    22 Safety valve, heating

    circuit

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    12/2011 T: 01454 311012 Fax: 01454 316345

    Heating

    Adjust the heating temperature through the thermostatic

    head (Fig.5-12).

    Warning!

    Provide for a safety thermostat for the lowtemperature heating applications.

    If you note that the rating temperature of the heating is

    higher than the set value, the flow of the primary may be

    too high and the thermostatic head is not able to close. In

    this case, open the differential pressure controller valve

    (Fig.5-4). About the regulation, see Page 8, Figure 4.

    To balance the heating production functions, you may work

    with the static balancing valve (Page 9 Fig.5-5, Page 10

    Fig.5-3) and the primary balancing valve (Fig.5-5) but the

    latter also affects the hot water production.

    Finally it is possible to change the heating power by

    modifying the circulator speed that has 3 speeds (Page 9

    Fig.5-17, Page 10 Fig.5-19).

    Controls and maintenance

    Heating circuit pressure

    Periodically adjust the pressure of the heating circuit by

    means of the manometer (Page 9 Fig.5-19, Page 10 Fig.5-21).

    The pressure value must be maintained over 1 bar (pressure

    values under 1 bar can damage the circulator by cavitation).

    A device for filling is supplied (the satellite has no internal

    filling loop). During the filling, the safety valve may activate

    (Page 9 Fig.5-20, Page 10 Fig.5-22).

    Warning: danger of burns.

    In order to eliminate the air in the heating circuit, use themanual air vent (Fig.5-2 and Fig.5-11).

    Safety valve

    Periodically work the manual hand wheel of the safety valve

    (Page 9 Fig.5-20, Page 10 Fig.5-22) for a good service of the

    valve. Be careful to check for leakage of the water from the

    discharge.

    Warning: danger of burns.

    Warning!

    The set value represents the rating value; the

    thermostatic head is not as precise as a

    thermostatic mixer and in transitory phases (unexpected

    openings) does not guarantee the precise set value, youmay have even +/-15C as regards to the set value, for a

    short period of time.

    Adjustments

    Sanitary hot water temperatureAdjust the temperature of the sanitary hot water using the

    thermostatic head (Fig.5-12):

    Position 23 34 45 56 67 Fully Open

    Temperature 23C 34C 45C 56C 67C Maximum

    Position 23 34 45 56 67 Fully Open

    Temperature 23C 34C 45C 56C 67C Maximum

    Warning!

    Danger of burns. The thermostatic head for

    the regulation of the sanitary hot watertemperature serves to set the temperature

    rating value.

    To avoid burns, provide for a thermostatic mixer

    downstream of the satellite.

    If you note that the rating temperature of the sanitary hot

    water is higher than the set value, the flow of the primary

    may be too high and the thermostatic head is not able to

    close. In this case, open the differential pressure controller

    valve (Fig.5-4). About the regulation, see Page 8, Figure 4.

    To balance the sanitary hot water production functions,

    you may work with the primary balancing valve (Fig.5-5).

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    13/2012E: [email protected] W: www.giacomini.co.uk

    Wiring for G3 modelsWiring for G4 models

    Electrical connections

    On top right of the satellite there is an electrical box IP55 (see

    Fig.5-13) containing the terminals (see Figure 7 below) for the

    electrical connections for the M-BUS (optional) devices and for

    the control and supply of the circulator (Page 9 Fig.5-17, Page

    10 Fig.5-19).

    Technical data

    Supply voltage for circulator: 230V +10% / -15%: 50Hz 5%

    Maximum electrical power for the circulator on the three

    speeds = 132W, 92W, 62W.

    Maximum electrical power for one electrical motor of the

    zone valve = 3.5W (1A).

    External connections

    External power supply (230V~) should be connected to the

    terminal box to terminals 7 and 8, 10 and 11 in Figure 7. Use a

    two-conductor cable with 0.5mm2 section. No polarity need be

    complied with for the connection of the terminals.

    Functioning consent

    Concerning the connection of the functioning consents, the

    consent should be given through the normally open contact

    (N.O. contact, see Figure 7). For the connection of thefunctioning consent (terminals 6, 7 and 9, 10) use a two-

    conductor cable with 0.5mm2 section. No polarity should be

    complied with for the connections.

    M-BUS

    For the connection of the M-BUS data transmission cable to

    the concentrator use terminals 1 (RED conductor L1+) and to

    terminal 2 (GREEN conductor L2-) of the terminal box, see

    Figure 7.

    Figure 7 Electrical connections of the terminal box

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    14/2013 T: 01454 311012 Fax: 01454 316345

    Figure 10 Primary circuit for hot sanitary water production.

    Pressure losses depending on the setting of the static

    balancing valve (Fig.5-5). Legend. 1, 2, 3, 4, 5: see scale on the

    body by the handle of the valve (Page 8 Fig.4).

    Figure 11 Primary circuit for heating.

    Pressure losses depending on the setting of the static

    balancing valve (Page 9 Fig.5-14, Page 10 Fig.5-3) when the

    static balancing valve (Fig.5-5) is completely open.

    Legend. -1/2, -3/4, -1, -2 = number of revolutions starting from

    closed; f.o. = full open.

    Primary circuit - All models

    Heating

    Figure 8 Heating flow rate diagrams.

    Figure 9 Hydraulic data for hot and cold sanitary

    water circuits (Ref. See table 7)

    Sanitary circuit

    Table 7 Hydraulic data for hot and cold sanitary water circuits.

    Kv Decription Ref fig. 2

    1.85 Hot sanitary circuit C-D

    4.41 Cold sanitary circuit C-E

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    15/20

    Heating Radiators Flow Rate (l/h) and Primary Outlet

    Temperature (radiators 65-55C)

    circular flow rate power 80C 75C 70C

    speed m3/h (kW)

    I 1 11.6 430 580 975

    (56.6C) (57C) (59C)

    II 1.25 14.5 550 750 1320

    (57.2C) (58C) (60C)

    III 1.5 17.4 680 950 1750

    (67.8C) (59C) (61C)

    Table 6 Primary circuit and radiators heating for

    satellites with standard heat exchanger.

    Heating

    Heating - Radiant Floor Flow Rate (l/h) and Primary Outlet

    Temperature (radiant floor 45-39C)

    circular flow rate power 75C 70C 65C 60C

    speed m3/h (kW)

    I 1 7.0 240 300

    (39C) (39C)

    II 1.25 8.7 240 300 375

    (40C) (40C) (40C)

    III 1.5 10.5 290 350 450

    (40C) (40C) (40C)

    Table 7 Primary circuit and radiant floor heating for

    satellites with standard heat exchanger.

    Heating Radiators Flow Rate (l/h) and Primary Outlet

    Temperature (radiators 65-55C)

    circular flow rate power 80C 75C 70C

    speed m3/h (kW)

    I 1 11.6 410 525 780

    (55.4C) (55C) (57C)

    II 1.25 14.5 515 670 1010

    (55.6C) (56C) (57C)

    III 1.5 17.4 620 810 1250

    (55.8C) (56C) (58C)

    Table 8 Primary circuit and radiators heating for

    satellites with large heat exchanger.

    Heating

    Heating - Radiant Floor Flow Rate (l/h) and Primary Outlet

    Temperature (radiant floor 45-39C)

    circular flow rate power 75C 70C 65C 60C 55C

    speed m3/h (kW)

    I 1 7.0 220 280 380

    (39C) (39C) (39C)

    II 1.25 8.7 290 365 480

    (40C) (40C) (39C)

    III 1.5 10.5 300 350 430 590(39C) (40C) (39C) (39C)

    Table 9 Primary circuit and radiant floor heating for

    satellites with large heat exchanger.

    Sanitary Flow Rate (l/h) and Primary Outlet

    Temperature (sanitary 10-50C)

    l/min l/h kW 80C 75C 70C 65C 60C

    12 720 29 510 580 690 865 1210

    (22.9C) (25C) (27.9C) (31.4C) (36C)

    15 900 37 670 775 935 1200

    (25.7C) (28.1C) (31.1C) (34.8C)

    17 1020 41 785 920 1120 1480

    (27.5C) (30.2C) (33.2C) (37.1C)

    20 1200 49 975 1150 1430

    (30.2C) (32.9C) (36.1C)

    Sanitary Flow Rate (l/h) and Primary Outlet

    Temperature (sanitary 10-50C)

    l/min l/h kW 80C 75C 70C 65C 60C

    12 720 29 450 495 565 660 825

    (15.4C) (16.9C) (18.7C) (21.3C) (24.9C)

    15 900 37 575 640 730 870 1105

    (16.8C) (18.3C) (20.4C) (23.3C) (27.2C)

    17 1020 41 660 740 850 1010 1300

    (17.7C) (19.4C) (21.6C) (24.4C) (28.5C)

    20 1200 49 790 890 1030 1250

    (18.9C) (20.7C) (21.3C) (26.3C)

    24 1430 58 970 1100 1280

    (20.6C)(22.6C) (25.1C)

    E: [email protected] W: www.giacomini.co.uk 14

    Large heat exchanger

    Hot sanitary water production

    Table 4 Primary circuit and hot water production for

    satellites with standard heat exchanger

    Hot sanitary water production

    Table 5 Primary circuit and hot water production for

    satellites with large heat exchanger

    Small heat exchanger

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    16/2015 T: 01454 311012 Fax: 01454 316345

    A = Primary outlet

    B = Primary inlet

    C = Cold water inlet

    D = Cold water outlet

    E = Hot water outlet

    F = Heating inlet

    G = Heating outlet

    Dimensions - All models

    Figure 16 Dimensions (mm)

    670

    670

    200450

    W

    D

    200450

    Normative references

    UNI EN 1434

    Measuring Instruments Directive 2004/22/EC (MID) EN 60751

    EN 61107

    Ref. Fig. 5 Component Certificate number

    - Gaskets 0512513

    6 Heat exchanger 0712063

    8 Spacer 0507502

    7 Backflow preventer 0907056

    WRAS certifications

    Table 13 WRAS certifications.

    Thermal hydraulic performance

    Maximum working temperature of the primary circuit and

    secondary circuits (heating and sanitary): 90C

    Maximum working pressure of the primary circuit and

    secondary sanitary: 10 bar

    Maximum working pressure of the heating secondary circuit:3 bar (safety valve setting)

    Additional information

    For further information please contact the following website:

    www.giacomini.co.uk

    or contact the technical department:

    T: 01454 311012

    F: 01454 316345

    E: [email protected]

    This communication has an indicative value. Giacomini SpA reserves the

    right to make at any time, without notice, changes for technical or business

    reasons to the articles in this communication. The information contained in

    this technical communication does not exempt the user from following

    strictly the regulations and rules of good existing practice.

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    17/20E: [email protected] W: www.giacomini.co.uk 16

    Notes

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    18/2017 T: 01454 311012 Fax: 01454 316345

    Notes

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    19/20E: [email protected] W: www.giacomini.co.uk 18

    COMMERCIAL UNDERFLOOR HEATING

    Visit Giacominis

    NEW updated website

    www.giacomini.co.uk

    or call 01454 311012

    for an information pack

    We design it, manufacture it and then install it

    Single point responsibility for the whole system

    Pipework guaranteed for 50 years

    Brass components guaranteed for 10 years

    Full technical assistance at every stage

    All thecurves are

    in the rightplaces

    T O T A L U N D E R F L O O R H E A T I N G S O L U T I O N S

    Giacomini

    increase in life expectancycompared with conventional valves25%

    Up to

    Manufactured in Italy to the

    highest quality standards,

    the Giacomini lever ball

    valve range includes the

    revolutionary Dado Square

    Ball valve, which offers amassive 25% increase in

    life expectancy compared

    to conventional valves.

    DADO technology F x F full port ball valvesin sizes from 1/4 - 4

    C x C standard port in sizes from 15 - 28mm

    F x F standard port in sizes from 1/4 - 4

    All valves WRAS approved

    For use with water, oil and gas

    For a longer trouble-free working lifewith full traceability, nothing matchesGiacomini lever ball valves.

    LeverlastingBall

    Valves

  • 7/21/2019 HIU Brochure - G3 G4 Eco - June 11

    20/20