Developed for high pressure and high temperature Fast, secure metal-to-metal press fitting No welding - no sparks High performance fittings for industry, energy, district heating, industrial oils and gases * * Bursting pressure varies according to the pipe size (see table) Up to 600 bar Scan here for assembly video!

Transcript of High performance fittings for industry, energy, district ... · High performance fittings for...

Page 1: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

Developed for high pressure and high temperature

Fast, secure metal-to-metal press fitting

No welding - no sparks

High performance fittings for industry, energy, district heating, industrial oils and gases

*

* Bursting pressure varies according to the pipe size (see table)

Up to 600 bar

Scan here for assembly video!

Page 2: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

2nd seal(not pressed)

1st seal (not pressed)

Body of the fitting

Press ring (pressed)

1st seal(pressed)

2nd seal(pressed)

Pipe

XTRME FIX is the modern metal-to-metal press connection for industrial applica-tions

XTRME FIX, the modern metal-to-metal connection technology, is a real alternative to welding which is often dangerous and elaborate. No special training is required for the installer. No qualification for welding is required. The training is carried out by KE KELIT staff.

XTRME FIX is the problem solver when quick connections or repairs are required in existing or new systems, in areas where little space is available, during bad weather, or when the medium remains in the system. A perfect connection can be made in a few seconds.

A force of up to 50 tonnes is exerted to permanently press the metal-to-metal connection without any gaskets.XTRME FIX press tools guarantee that every press connection is of the same quality

Advantages

Safe and clean connection compared to welding

Press connection comple-ted in a few seconds

Metal-to-metal connection

Withstands high pressure and temperature

Work possible in any weather

Connection can be made without complete draining of the medium from the system

No special training required

Permanent connection, pressed with a force of 50 tonnes

Temperature range: -55°C to 400°C

Page 3: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

Applications

XTRME FIX can be used for a wide range of applications

Industrial process pipingLubricating and hydraulic oilSteam and condensatePublic utilities

Measuring pipes and control pipesPublic utilities, water, steamStorage tanks, refinery pipesCompressed air

Compressed air supplyHeat distributionTurbine constructionCO2 cooling /cooling agents

Propane and nitrogen Gas dryingGases: CO2, H2, N2High pressure fire extinguishing systems

Certified by the leading test institutes

Water Heating Cooling, CO2 Steam Compressed air Solar

Fire extinguishing Industry Vakuum Shipbuilding District heating

FW

≈ ≈ ≈

Fitting bodyCarbon

steelSleeve

Carbon steel XCC closed neutral neutral

Fitting bodyStainless

steel Sleeve

Stainless steel XNN open/

closedaggressive aggressive

Circuit Medium SurroundingsMaterial Material

Application and choice of material

XTRME FIX is certified by „ASME B31.1 Power Piping“ and „ASME B31.3 Process Piping“ and fulfills all the requirements of the IACS (International Association for the Classification of Ships), which is the most demanding industry certification in this sector.

In order to meet the requirements, XTRME FIX is continuously certified by various testing institutes, taking into account the respective require-ments of the application areas.

Page 4: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

Pipe specificationsSizing of the pipes and wall thickness:

The pipes are installed in accordance with DIN2413 or ANSI B31.3 using the pressure rating required for the individual application. For further specifications please contact the pipe manufacturer.

Size ODmaxA) ODmin

B) OD1nomC)

OD3nomC)

OD2nomC) smin smax

½“ 21.75 21.00 21.30 21.26 1.60 2.77

¾“ 27.30 26.50 26.90 26.67 2.11 3.91

1“ 34.20 33.25 33.70 33.41 2.60 4.55

1¼“ 42.90 41.90 42.40 42.16 2.60 5.08

1½“ 49.10 47.95 48.30 48.26 2.60 5.08

2“ 60.80 59.85 60.30 60.33 2.60 5.54

Wall thickness tolerances

A) ODmax = maximum permissible diameter

B) ODmin = minimum permissible diameter

C) ODxnom = nominal pipe diameter *Maximum standard diameter above ODmax is possible

Pipe outside diameter (inch)

pipe tolerances

Size ODmaxA) ODmin

B) OD1nomC) OD2nom

C) smin smax

18 18.30 17.70 18.00 18.00 1.50 3.0020 20.35 19.70 20.00 20.00 1.50 3.00

wall thickness tolerances

pipe tolerancesNominal outside

diameteraccording to standard

Metric pipe – outside diameter (in mm)

EN 253 (OD3)

Outside diameter D3* 21.3 (1/2") to 60.3 (2"): ±0.3mm ≥ 60.3: 0.005 x D3

Wall thickness T3* ±0.3mm pipes, s ≤ 3.2mm ±0.4mm pipes, s = 3.6mm ±0.5mm pipes, s ≥ 4 mm

EN ISO 1127 or EN 10220 (OD1)

Outside diameter D3* ±0.75% or min. ±0.3mm

Wall thickness T3* ±10% or min. ±0.2mm

Pipe tolerances

OvalityThe ovality tolerance is equal to the maximum outside diameter

Pipe hardnessUp to a maximum of 90 Rockwell B is permitted.

ASTM A213/A268/A269 (OD2)

Outside diameter D3* 13,72 to 38.1mm: ±0.13mm 38,1 to 88.9mm: ±0.25mm

Wall thickness T3*

±10%

* in EN ISO 1127

Nominal outside diameter

according to standard

Page 5: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

From -55°C to +400°C according to the material used. As the temperature in-creases the maximum operating pressure is reduced according to the table on the right.

Temp C°

Carbon Steel (CC)

Stainless Steel (NN)

50 0% 4%

100 10% 12%150 21% 15%200 31% 20%250 37% 25%

300 45% 30%350 33%400 35%

The coefficients for pressure losses are available on request.

Temperature range

Pipes which can be used: XTRME FIX can be used for thick wall carbon steel pipes conforming to EN253, EN10255 annealed stainless steel pipes conforming to EN10216-5, EN10217-7 and primed carbon steel pipes (see table)

Seamless welded and cold drawn pipes are per-mitted.

The pipe surface must be clean and free of any grooves and scratches (any scratches greater than 0.1mm are not allowed)

Rolling skin, scale and rust must be removed.

Hot rolled pipes or pipes with a scaly surface are not allowed.

The maximum and minimum diameter and wall thickness have to be within the limits of the spec-ification

Pipes made of carbon steel in accordance with EN253 and EN10255

Pipes made of stainless steel in accordance with EN10216-5 and EN10217-7

Size OD s (wall-

thickness)

PN1) (Nominal

pressure)

PN2) (Test

according to IACS)

Bursting pressure

test3)

½“ 21.3 2.0 400bar 200bar 800bar

¾“ 26.9 2.3 400bar 200bar 800bar

1“ 33.7 2.6 400bar 200bar 800bar

1¼“ 42.4 2.6 300bar 150bar 600bar

1½“ 48.3 2.6 300bar 150bar 600bar

2“ 60.3 2.6 300bar 150bar 600bar

Pipe outside diameter (inch)

Size OD s (Wall

thickness)

PN1) (Nominal pressure)

PN2) (Test accor-ding to IACS)

Bursting

pressure test3)

18 18 1.5 400bar 200bar 800bar20 20 2 400bar 200bar 800bar

Metric pipe – outside diameter (in mm)

1) Pressure for double security 2) Nominal pressure for shipbuilding3) Bursting pressure confirmed at four times the nominal pressure over 5 minutes

Outside diameter (OD) in metric units (mm)

Calculation internal pressureThe fittings, in metric and imperial sizes, are suited for the pressures mentioned below. The operating pressure of the system is calculated according to the materials used in the fittings, the dimensions and the operating temperature.

Page 6: High performance fittings for industry, energy, district ... · High performance fittings for industry, energy, district heating ... B31.3 Process Piping“ and fulfills all the requirements

KE KELIT Kunststoffwerk Gesellschaft m.b.H.A 4020 Linz, Ignaz-Mayer-Straße 17Austria, Europe

TELEFON +43 (0) 50 779FAX +43 (0) 50 779 318E-MAIL [email protected]

www.kekelit.com

STRAIGHT FITTING / SLIDING COUPLING

REDUCER

COUPLING WITH FEMALE / MALE THREAD

END CAP

90° ELLBOW

90° BEND

EQUAL T

MANIFOLD BLOCK 2 OUTLET / 4 OUTLET

Product range

1 2 3 4

5 6 7 8

1

2

3

4

5

6

7

8

Measure the pipe size and the wall thickness and check whether they are within the tolerances.

Cut the pipe at a right angle. If the pipes have been pre-insula-ted remove the insulation.

Chamfer the inside and outside of the pipe. Use a sanding belt to remove loose flakes of rust, scratches and dirt. Do not use an angle grinder.

Use the marking gauge to mark the pipe at the appropriate pla-ces. If necessary, mark the end of the un-pressed fitting so that a visual check of the joint can be made after pressing.

Insert the pipe into the full depth of the fitting.

Place the press tool on the fitting. Check that the pull ring in the tool fits to the nut of the fitting. Close the tool until it is locked into position.

The pressing procedure is started by pressing the button on the hydraulic unit. It stops automatically.

A perfect connection is achieved in a few seconds. A visual check of the connection is sufficient. The press ring should be aligned with the shoulder of the fitting and the marking should be visible.

1. Measuring

2. Cutting

3. Chamferring , sanding down

4. Marking

5. Connecting

6. Preperation

7. Pressing

8. Finished

Installation guidelines

XTR

ME

FIX

_6-S

eite

r_EN

_05

/2

01

7

Please observe the safety regulations and guidelines in the relevant standards!We are not liable for printing errors and re-serve the right to change technical details