TODAY’S AGENDA

• Life Safety Dampers - What are they???

• A Couple of Hot Videos

• Codes / Where are the dampers???

• Unique Products and Special

applications

• Accessories

Page 3: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 3/51

Fire Damper A device used to restrict the passage of flame through the duct work

of an air system. A fire damper is installed in a fire rated wall or 

floor and closes automatically to maintain the integrity of thatpartition.

STATIC RATED:

DYNAMIC RATED:

Acceptable for penetrations rated less than 3 hours

No Airflow Through Damper 

With Airflow Through Damper 

1 ½ Hr :

3 Hr : Acceptable for penetrations rated 3 hours or greater 

Page 4: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 4/51

 B style C style – Most Free Area

O style –Oval Duct

 R style – Round Duct

FD / FSD STYLES

 BC Style

Page 5: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 5/51

Smoke Damper A device used to restrict the spread of smoke in an

HVAC system which shut down in the event of a fire.

Leakage Class I – 8 cfm @ 4” w.g.

Leakage Class II – 20 cfm @ 4” w.g.Leakage Class III – 80 cfm @ 4” w.g.

Velocity Ratings start at 2000 fpm @ 4” w.g. and increase at 1000

fpm and at 2” w.g.

Temperature Rating 250° or 350°

Page 6: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 6/51

Smoke Control Systems

• Engineered Smoke Control

Strategically located fireand smoke dampers open

or close to channel HVAC

air into selected areas -creating high and low

pressures

• Passive Smoke Control

Close upon detection of 

smoke

Page 7: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 7/51

Smoke detector Actuator 

Smoke Barrier 

24” max.

from wall

Typical Smoke Damper Application 

TS 150Firestst

Page 8: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 8/51

Combination Fire/Smoke Damper 

A device which functions as both a fire damper, and a smoke

smoke damper.

Page 9: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 9/51

Mounting angles

Break away connections

Sleeve

Damper within the plane of fire barrier 

Typical Combination 

Fire & Smoke Damper 

Application 

Fire barrier 

Page 10: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 10/51

Break away connections

Sleeve

Damper in fire barrier 

Typical Combination 

Fire & Smoke Damper 

Application 

Mounting angles

EFL

(Electronic Fuse Link)

Page 11: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 11/51

Ceiling Damper (aka Radiation Damper) A device used to protect the HVAC opening in in a fire rated horizontally

rated ceiling assembly. A ceiling damper closes automatically to restrict the

passage of flame and heat.

Protected area

Page 12: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 12/51

Ruskin CFD7 (R)T

Design L-586

Square or Round Available

Page 13: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 13/51

Fire Smoke Damper1 hr. Rated

Dampers

Corridor Damper 

Combination Fire/Smoke dampers

used specifically

for tunnel corridor construction

When the walls and

ceiling form a tunnel,

the wall fire rating

need not extend

above

the top of the rated

ceiling assembly

Page 14: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 14/51

Dynamic Closure under Higher Velocities and Pressures 

Minimum operational requirements for Fire Dampers, Smoke Dampersand Combination Fire Smoke Dampers: 2000 fpm @ 4” wg

Max. size- 72 X 48 or 48 X 72

Max. Size- 64 X 96 or 120 X 48

Max. Size- 120 X 96 w/ elec. Act / 144 X 96 w/ pneu. actuators

4000 FPM / 4” wg –  Max. Size 24 X 24

Fire Damper - curtain type 

Fire Damper – multi blade type 

4000 FPM / 8” wg –  Max. Size 64 X 48

3000 FPM / 4” wg – Max. Size 120 X 36

4000 FPM / 4” wg – Max. Size 48 X 24

4000 FPM / 8” wg – Max. Size 24 X 24

Combination Fire/Smoke Damper 

Page 15: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 15/51

Page 16: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 16/51

Fire Test Video

Page 17: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 17/51

Ceiling Fire

Dampers

Smoke

Damper 

Fire Damper 

Exterior Wall

FSDHorizontal (in concrete)

Bottom of Shaft

FSD in Shaft Walls

Fire Barrier 

CODES and

STANDARDS

Page 18: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 18/51

FIRE AND SMOKE PROTECTION(Minimum Code Requirements)

• Fire Walls

• Fire Barriers

• Shaft Enclosures

• Fire Partitions

• Corridors

• Smoke Barriers

• Horizontal Assemblies

Page 19: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 19/51

FIRE DAMPERS –Where are they used?

SECTION 706 FIRE WALLS

“restricts the spread of fire and extends continuously from the foundation to or through

the roof , with sufficient structural stability under fire conditions to allow collapse of 

construction on either side without collapse of the wall”

Required to have 3 hour rating for most occupancies

2 hours for certain occupancies and 4 hours for 

hazardous

Protected openings when not on a lot line.

Opening size limited unless both buildings are

sprinkled

Ducts/ Air Transfer openings shall comply with Section 716 

Page 20: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 20/51

FIRE DAMPERS –Where are they used?

Section 707 FIRE BARRIERS

Continuous between floor levelsRating determined by occupancy

1, 2, 3, or 4 hours

Incidental use, Occupancy separations, Shafts,

Exits, Exit passageways & Fire areas

•SMOKE DAMPER required when fire barrier serves as a horizontal exit

Ducts/ Air Transfer openings shall comply with Section 716 

Page 21: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 21/51

FIRE DAMPERS –Where are they used?

SECTION 709 FIRE PARTITIONS

A vertical assembly of materials designed to restrict

the spread of fire in which openings are protected.

Not Continuous between f loor levels – vertical assemblies

Corridors, dwelling & sleeping unit separation, tenant separation in Malls & Elevatorlobby separation

Generally rated 1-2 hours depending on number of stories

•SMOKE DAMPER required for Corridors (exceptions)

Ducts/ Air Transfer openings shall comply with Section 716 

Page 22: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 22/51

FIRE and SMOKE DAMPERS –Where are they used?

SECTION 708 SHAFT ENCLOSURES

Shaft Enclosure – The wall or construction forming the boundaries of a shaft.

An enclosed space extending through one or more stories of a building,connecting vertical openings in successive floors, or floors and roof.

Used as vertical opening enclosures

Constructed as fire barriers or horizontalassemblies

Generally rated 1-2 hours depending onnumber of stories

cts/ Air Transfer openings shall comply with Section 716 

Page 23: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 23/51

SMOKE DAMPERS – Where are they Used?

SECTION 716 CORRIDOR ENCLOSURES

Corridor – An enclosed exit access compartment that definesand provides a path of egress travel to an exit.

Generally rated up to 1 hour

Ducts/ Air transfer openings are protectedand shall comply with section 716

Page 24: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 24/51

SMOKE DAMPERS- Where are they used?

Section 710 SMOKE BARRIERS

Smoke Barrier – A continuous membrane, either vertical or horizontal,

such as a wall, floor, or ceiling assembly, which is designedand constructed to restrict the movement of smoke.

Used in Institutional

1-hour rating required

Ducts/ Air Transfer openings shall comply

with Section 716

Smoke Barrier 

Page 25: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 25/51

Section 711 SMOKE PARTITIONS

SMOKE DAMPERS- Where are they used?

Smoke Partit ion – A continuous membrane, either vertical or horizontal,

such as a wall, floor, or ceiling assembly, which is designed and constructedto restrict the movement of smoke.

Corridor walls in I-2 (Hospitals, Nursing homes)

Not required to have a fire-resistance rating (unlessrequired elsewhere in the code)

Ducts/ Air Transfer openings shall comply with Section716

SmokePartition

Page 26: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 26/51

HORIZONTAL Assemblies(SECTION 712)

• General requirement mandates shaft enclosures foropenings in floor and roof systems (exceptions)

• Fire-resistance rating varies depending on building type of construction and occupancies being separated

• Ducts/ Air Transfer openings shall comply with Section 716• Through penetrations – FIRE DAMPER (exceptions)

• Membrane penetrations – CEILING FIRE DAMPER

(exceptions)• Non-fire resistance-rated assemblies – FIRE DAMPER(exception)

Horizontal Assembly – A fire-resistance-rated floor or roof assembly of materials designed to restrict the spread of fire in which continuity is maintained.

Page 27: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 27/51

Other IBC Chapters

That Affect The Construction andRatings

• IBC Chapter 3“Use and Occupancy Classification”

• IBC Chapter 4“Special Use and Occupancy”

• IBC Chapter 9“Fire Protection System”

Page 28: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 28/51

International Mechanical Code

(IMC)

• SECTION 607 (DUCT AND AIR TRANSFER OPENINGS)

– Basically duplicates IBC requirements for dampers and/or refers back to IBC(same exceptions)

• HAZARD EXHAUST DUCTS – Fire dampers are prohibited

• CLOTHES DRYER EXHAUST – Fire dampers are prohibited• GREASE DUCT PENETRATION – Fire dampers are not used

• DUST COLLECTION – Fire dampers are not usually applicable

Page 29: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 29/51

NATIONAL FIRE PROTECTION

 ASSOCIATION¾ NFPA72 - National Fire Alarm and Signaling Code

¾ NFPA80 - Standard for Fire Doors and Other Opening Protective

¾ NFPA90A - Standard for the Installation of Air-Conditioning andVentilating Systems

¾ NFPA92A - Standard for Smoke-Control Systems Utilizing Barriers

and Pressure Differences

¾ NFPA92B - Standard for Smoke Management Systems in Malls,

Atria, and Large Spaces

¾ NFPA101 - Life Safety Code®

¾NFPA105 – Standards for Smoke Door Assemblies and OtherOpening Protectives

Page 30: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 30/51

Unique Products and FeaturesSpecial Applications

Page 31: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 31/51

True Round

Cinch Plate replaces Mounting Angles

UL approved one side

FSDR25 

Fire Damper / Smoke Damper / Combo Fire Smoke Damper 

FDR25 SDR25  

• 6” to 24” dia. • Lower pressure drop 

• Very Low installation costs 

Page 32: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 32/51

FLANGED SYSTEM

BREAKAWAYWARD / DUCTMATE / NEXUS / TDC / TDF

Unique Installations

Page 33: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 33/51

OUT OF WALL / FLOOR•Retrofi t Applications

•Through Penetration

•Duct Termination

Maintain

100%Free Area

Unique Installations

Page 34: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 34/51

8” Max.

For Shaft Applications

Page 35: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 35/51

“ GRILLE ACCESS” Models

FSD36FA/ 60FA

FSD35GA/ 36GA/ 60GA

For Shaft Applications

Page 36: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 36/51

FSDFA “ Front Access”•No retaining angles required• Allows for shortest sleeve possible

• Access to actuator & other components through the grille

•Thermal insulation on damper allows out of wall installation

Page 37: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 37/51

FSD60-BAL

3-Position “ Balancing” FSD

Built inpotentiometer to

20% to 100%

balance position

 Allows the damper to be SET at any

position for BALANCING AIRFLOW

under normal operations, open for 

SMOKE CONTROL and provides FIRE

protection simultaneously

No Control Signal

Required

Unique Installations

Page 38: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 38/51

Vertical Blade Fire Smoke Damper 

For applications where ducts runside by side and there is no roomfor actuator on the side of damper.

Unique Installations

FSD60V

Don’t try this with a normal damper! 

FSD60M

Page 39: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 39/51

FSD60MMODULATING Fire/Smoke Damper 

Responds from control signal

2 to10 VDC or 4 to 20mA

Proportional Modulating Actuator 

Page 40: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 40/51

FD / FSD

Many Options

I di h i i f h d bl dBl d P iti

Page 41: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 41/51

•Indicates the position of the damper blades

• Allows for other equipment to be turned on / off 

SPH2

SP 100

Blade Position

Indicating Switches

SP 200

TS150 Fi t t

Page 42: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 42/51

TS150 – FirestatFor Smoke Damper &

Combination Fire/Smoke Dampers

• Allows the damper to be reopened after the initial closure

for engineered smoke control.

• Equipped with blade position indicator

Page 43: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 43/51

Damper Test Switch - DTS

Momentarily interrupts power

Page 44: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 44/51

Duct Smoke Detectors

DSDF (Flow)

DSDN (No Flow)

Page 45: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 45/51

• Used to control, monitor, or testdampers remotely

MPC’s-Master Control Panels

Page 46: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 46/51

All your answers are here!

Page 47: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 47/51

Page 48: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 48/51

Page 49: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 49/51

Page 50: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 50/51

 Autodesk®Revit ®

Ruskin Revit ® files can be found at

•www.ruskin.com•http://seek.autodesk.com

Ruskin Dampers

• Life Safety Dampers• Air Control

• Industrial/ProcessRuskin Louvers

• Drainable• Wind-Driven Rain

• Hurricane• Sun ShadesRuskin ERV Units

Building Information Modeling

Page 51: HH FSD 8 10

7/30/2019 HH FSD 8 10

http://slidepdf.com/reader/full/hh-fsd-8-10 51/51

Thank You!