Heating And Ventilation

1
TOILETS ATRIUM SPACE OFFICES 1 RESTAURANT OFFICES 12 OFFICES 23 PLANT ROOM PARKING LOT EXISTING OLD CORK CITY HALL OFFICES 7 OFFICES 18 OFFICES 29 1400 1400 TOILETS TOILETS INLET OUTLET HEAT RECOVERY STAIRWAY 1 PLANT ROOM INLET OUTLET BOILER STORAGE TANK SERVICE VOID BEHIND STACK EFFECT A.O.V FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FIRE DAMPER AT EACH FLOOR COLD AIR BROUGHT VENTED IN TO CAR PARK, SEPARATE FROM BUILDING VENTILATION AIR VENTED IN TO OFFICES THROUGH FLOOR PLENUM AND VENTED OUT DOUBLE FACADE AIR VENTED IN TO OFFICES THROUGH FLOOR PLENUM AND VENTED OUT THOUGH SUSPENDED CEILING VENTILATION VENTED OUT THOUGH SUSPENDED CEILING VENTILATION IF NEEDED AIR VENTED IN TO ROOMS THROUGH FLOOR PLENUM AND VENTED OUT THOUGH SUSPENDED CEILING VENTILATION VENTS OPEN DURING SUMMER AIR BEING PUSHED UP BY FAN AND TAKE AIR OUT OF OFFICES AIR BEING VENTED IN PARAPIT AND TAKING BACK TO PLANT ROOM AND LET STRAIGHT OUT NON SEGMENTED DOUBLE FACADE BUFFER ZONE HEAT RECOVER NOT USED ALL DURRING SUMMER INLET VENT OUTLET VENT EXHAUST AIR EXHAUST AIR CONDITIONED AIR OPENING WINDOWS FOR RAPID VENTILATION OPENING WINDOWS FOR RAPID VENTILATION OPENING WINDOWS FOR RAPID VENTILATION HEAT PUMP Summer Ventilation: The building uses a combination of mechanical supply and natural extract during the summer months. Fresh air supply is collected at roof level using vents in wall of plant room, The cool fresh air is supplied by mechanical ventilation via large vertical ducts adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the office areas raised floor plenums. Office occupants may adjust floor diffusers and open perimeter windows to avail of more fresh air. Double facade designed as a exhaust facade and also acts as a buffer for wind and city noise, the double facade allows staff to open perimeter windows during windy weather. Using displacement ventilation the stale exhaust air moves through permanent vents from the office areas to the plant room. Motor opening vents in curtain walling to let air out of offices in to double facade and brought back to plant room. The full height atrium has automatic opening vents to let air out. Summer Cooling: The main cooling is provided using a ground water heat exchange, via a closed loop of glycol fluid pumped through pipes embedded in the exposed concrete floors (Active Structure System). The pipes feed the heat pump, which is reversed during summer months. Atmospheric heat is absorbed from the fresh air moving over the exposed concrete soffits by the pipes and transferred into the ground water. Excess warm air in the atrium is vented out in to the atrium linked to the building management system (BMS). The air is let out by automatic opening vents at top of atrium. The outer glazed double facade has blinding's given shading from the solar gain. Winter Ventilation: The building uses a combination of mechanical supply and extract with a heat recovery ventilation unit during the winter months. Fresh supply air is collected at roof level using vents in wall of plant room. The cold fresh air is pre-heated by recovered heat from the building. The fresh air is then supplied by mechanical ventilation via large vertical ducts adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the office areas raised floor plenums. Office occupants may adjust floor diffusers and open perimeter windows to avail of more fresh air.Double facade designed as a exhaust facade and also acts as a buffer for wind and city noise, the double facade allows staff to open perimeter windows during windy weather. Using displacement ventilation the stale exhaust air moves through permanent vents from the office areas to the plant room. Motor opening vents in curtain walling to let air out of offices in to double facade and brought back to plant room. The full height atrium has automatic opening vents to let air out. Exhaust air is expelled from the building after recovering about 60% of the ventilation heat with the HRV units. Winter Heating: The main space heating is provided using a ground water heat pump, via a closed loop of glycol fluid pumped through pipes embedded in the exposed concrete floors (Active Structure System). The pipes feed the heat pump, which exchanges heat to the embedded pipes. Additional heat is transferred to the supply fresh air moving over the heated concrete structure in the floor plenums, thus further distributing the heat to the offices. Operable windows at the top of the atrium are closed during the winter, linked to the building management system (BMS). TOILETS ATRIUM SPACE OFFICES 1 RESTAURANT OFFICES 12 OFFICES 23 PLANT ROOM PARKING LOT EXISTING OLD CORK CITY HALL OFFICES 7 OFFICES 18 OFFICES 29 1400 1400 TOILETS TOILETS INLET OUTLET HEAT RECOVERY STAIRWAY 1 PLANT ROOM INLET OUTLET HEAT RECOVERY BOILER STORAGE TANK SERVICE VOID BEHIND STACK EFFECT A.O.V FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FLOOR PLENUM FIRE DAMPER AT EACH FLOOR COLD AIR BROUGHT VENTED IN TO CAR PARK, SEPARATE FROM BUILDING VENTILATION AIR VENTED IN TO OFFICES THROUGH FLOOR PLENUM AND VENTED OUT DOUBLE FACADE AIR VENTED IN TO OFFICES THROUGH FLOOR PLENUM AND VENTED OUT THOUGH SUSPENDED CEILING VENTILATION VENTED OUT THOUGH SUSPENDED CEILING VENTILATION IF NEEDED AIR VENTED IN TO ROOMS THROUGH FLOOR PLENUM AND VENTED OUT THOUGH SUSPENDED CEILING VENTILATION VENTS CLOSING AND OPENING DURING WINTER AIR BEING PUSHED UP BY FAN AND TAKE AIR OUT OF OFFICES AIR BEING VENTED IN PARAPIT AND TAKING BACK TO HEAT RECOVERY NON SEGMENTED DOUBLE FACADE BUFFER ZONE INLET VENT OUTLET VENT EXHAUST AIR EXHAUST AIR CONDITIONED AIR OPENING WINDOWS FOR RAPID VENTILATION OPENING WINDOWS FOR RAPID VENTILATION OPENING WINDOWS FOR RAPID VENTILATION HEAT PUMP Project: Client: Project No. Drawing No. Rev. Subject: File Ref. Paper size: CTB file: LTScale: ONOM File Path: Drawn by: Scale: Drawing Purpose: Checked by: Date: Gerard Nicholson 27 OF 32 B DESIGN DETAIL STUDIES 1:100 CORK MIXED-USE PROJECT HEATING AND VENTILATION G.M.I.T ARCHITECTURAL TECHNOLOGY 29/04/10 GERARD N.

Transcript of Heating And Ventilation

Page 1: Heating And Ventilation

TOILETS

ATRIUM SPACE

OFFICES 1

RESTAURANT

OFFICES 12

OFFICES 23

PLANT ROOM

PARKING LOT

EXISTING OLD CORK CITY HALL

OFFICES 7

OFFICES 18

OFFICES 29

1400 1400

TOILETS

TOILETS

INLET

OUTLET

HEAT RECOVERY

STAIRWAY 1 PLANT ROOM

INLET

OUTLET

BOILER

STORAGE

TANK

SERVICE VOID

BEHIND

STACK EFFECT

A.O.V

FLOOR PLENUM

FLOOR PLENUM

FLOOR PLENUMFLOOR PLENUM

FLOOR PLENUM

FLOOR PLENUM

FIRE

DAMPER AT

EACH FLOOR

COLD AIR BROUGHT VENTED IN

TO CAR PARK, SEPARATE FROM

BUILDING VENTILATION

AIR VENTED IN TO OFFICES

THROUGH FLOOR PLENUM

AND VENTED OUT DOUBLE

FACADE

AIR VENTED IN TO OFFICES

THROUGH FLOOR PLENUM

AND VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION

VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION IF NEEDED

AIR VENTED IN TO ROOMS

THROUGH FLOOR PLENUM

AND VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION

VENTS OPEN DURING SUMMER

AIR BEING PUSHED UP BY FAN

AND TAKE AIR OUT OF OFFICES

AIR BEING VENTED IN PARAPIT

AND TAKING BACK TO PLANT

ROOM AND LET STRAIGHT OUT

NON SEGMENTED DOUBLE

FACADE BUFFER ZONE

HEAT RECOVER NOT USED ALL

DURRING SUMMER

INLET VENT

OUTLET VENT

EXHAUST AIR

EXHAUST AIR

CONDITIONED AIR

OPENING WINDOWS FOR RAPID

VENTILATION

OPENING WINDOWS FOR RAPID

VENTILATION

OPENING WINDOWS FOR RAPID

VENTILATION

HEAT

PUMP

Summer Ventilation:

The building uses a combination of mechanical supply and natural extract during the

summer months. Fresh air supply is collected at roof level using vents in wall of plant room,

The cool fresh air is supplied by mechanical ventilation via large vertical ducts

adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the office

areas raised floor plenums. Office occupants may adjust floor diffusers and open perimeter

windows to avail of more fresh air. Double facade designed as a exhaust facade and also

acts as a buffer for wind and city noise, the double facade allows staff to open perimeter

windows during windy weather.

Using displacement ventilation the stale exhaust air moves through permanent vents from

the office areas to the plant room. Motor opening vents in curtain walling to let air out of

offices in to double facade and brought back to plant room. The full height atrium has

automatic opening vents to let air out.

Summer Cooling:

The main cooling is provided using a ground water heat exchange, via a closed loop of

glycol fluid pumped through pipes embedded in the exposed concrete floors (Active

Structure System). The pipes feed the heat pump, which is reversed during summer months.

Atmospheric heat is absorbed from the fresh air moving over the exposed concrete soffits by

the pipes and transferred into the ground water.

Excess warm air in the atrium is vented out in to the atrium linked to the building

management system (BMS). The air is let out by automatic opening vents at top of atrium.

The outer glazed double facade has blinding's given shading from the solar gain.

Winter Ventilation:

The building uses a combination of mechanical supply and extract with a

heat recovery ventilation unit during the winter months. Fresh supply air is collected at roof

level using vents in wall of plant room. The cold fresh air is pre-heated by recovered heat

from the building. The fresh air is then supplied by mechanical ventilation via large vertical

ducts adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the

office areas raised floor plenums. Office occupants may adjust floor diffusers and open

perimeter windows to avail of more fresh air.Double facade designed as a exhaust

facade and also acts as a buffer for wind and city noise, the double facade allows staff to

open perimeter windows during windy weather.

Using displacement ventilation the stale exhaust air moves through permanent vents from

the office areas to the plant room. Motor opening vents in curtain walling to let air out of

offices in to double facade and brought back to plant room. The full height atrium has

automatic opening vents to let air out. Exhaust air is expelled from the building

after recovering about 60% of the ventilation heat with the HRV units.

Winter Heating:

The main space heating is provided using a ground water heat pump, via a closed loop of

glycol fluid pumped through pipes embedded in the exposed concrete floors (Active

Structure System). The pipes feed the heat pump, which exchanges heat to the embedded

pipes. Additional heat is transferred to the supply fresh air moving over the heated

concrete structure in the floor plenums, thus further distributing the heat to the offices.

Operable windows at the top of the atrium are closed during the winter, linked to the

building management system (BMS).

TOILETS

ATRIUM SPACE

OFFICES 1

RESTAURANT

OFFICES 12

OFFICES 23

PLANT ROOM

PARKING LOT

EXISTING OLD CORK CITY HALL

OFFICES 7

OFFICES 18

OFFICES 29

1400 1400

TOILETS

TOILETS

INLET

OUTLET

HEAT RECOVERY

STAIRWAY 1 PLANT ROOM

INLET

OUTLET

HEAT RECOVERY

BOILER

STORAGE

TANK

SERVICE VOID

BEHIND

STACK EFFECT

A.O.V

FLOOR PLENUM

FLOOR PLENUM

FLOOR PLENUMFLOOR PLENUM

FLOOR PLENUM

FLOOR PLENUM

FIRE

DAMPER AT

EACH FLOOR

COLD AIR BROUGHT VENTED IN

TO CAR PARK, SEPARATE FROM

BUILDING VENTILATION

AIR VENTED IN TO OFFICES

THROUGH FLOOR PLENUM

AND VENTED OUT DOUBLE

FACADE

AIR VENTED IN TO OFFICES

THROUGH FLOOR PLENUM

AND VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION

VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION IF NEEDED

AIR VENTED IN TO ROOMS

THROUGH FLOOR PLENUM

AND VENTED OUT THOUGH

SUSPENDED CEILING

VENTILATION

VENTS CLOSING AND OPENING

DURING WINTER

AIR BEING PUSHED UP BY FAN

AND TAKE AIR OUT OF OFFICES

AIR BEING VENTED IN PARAPIT

AND TAKING BACK TO HEAT

RECOVERY

NON SEGMENTED DOUBLE

FACADE BUFFER ZONE

INLET VENT

OUTLET VENT

EXHAUST AIR

EXHAUST AIR

CONDITIONED AIR

OPENING WINDOWS FOR RAPID

VENTILATION

OPENING WINDOWS FOR RAPID

VENTILATION

OPENING WINDOWS FOR RAPID

VENTILATION

HEAT

PUMP

Project:

Client:

Project No. Drawing No. Rev.

Subject:

File Ref.

Paper size: CTB file: LTScale:

ONOM File Path:

Drawn by:Scale:

Drawing Purpose:

Checked by:

Date:

Gerard Nicholson

27 OF 32 B

DESIGN DETAIL STUDIES

1:100

CORK MIXED-USE PROJECT

HEATING AND VENTILATION

G.M.I.T ARCHITECTURAL TECHNOLOGY

29/04/10

GERARD N.