Heating And Ventilation
Transcript of Heating And Ventilation
TOILETS
ATRIUM SPACE
OFFICES 1
RESTAURANT
OFFICES 12
OFFICES 23
PLANT ROOM
PARKING LOT
EXISTING OLD CORK CITY HALL
OFFICES 7
OFFICES 18
OFFICES 29
1400 1400
TOILETS
TOILETS
INLET
OUTLET
HEAT RECOVERY
STAIRWAY 1 PLANT ROOM
INLET
OUTLET
BOILER
STORAGE
TANK
SERVICE VOID
BEHIND
STACK EFFECT
A.O.V
FLOOR PLENUM
FLOOR PLENUM
FLOOR PLENUMFLOOR PLENUM
FLOOR PLENUM
FLOOR PLENUM
FIRE
DAMPER AT
EACH FLOOR
COLD AIR BROUGHT VENTED IN
TO CAR PARK, SEPARATE FROM
BUILDING VENTILATION
AIR VENTED IN TO OFFICES
THROUGH FLOOR PLENUM
AND VENTED OUT DOUBLE
FACADE
AIR VENTED IN TO OFFICES
THROUGH FLOOR PLENUM
AND VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION
VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION IF NEEDED
AIR VENTED IN TO ROOMS
THROUGH FLOOR PLENUM
AND VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION
VENTS OPEN DURING SUMMER
AIR BEING PUSHED UP BY FAN
AND TAKE AIR OUT OF OFFICES
AIR BEING VENTED IN PARAPIT
AND TAKING BACK TO PLANT
ROOM AND LET STRAIGHT OUT
NON SEGMENTED DOUBLE
FACADE BUFFER ZONE
HEAT RECOVER NOT USED ALL
DURRING SUMMER
INLET VENT
OUTLET VENT
EXHAUST AIR
EXHAUST AIR
CONDITIONED AIR
OPENING WINDOWS FOR RAPID
VENTILATION
OPENING WINDOWS FOR RAPID
VENTILATION
OPENING WINDOWS FOR RAPID
VENTILATION
HEAT
PUMP
Summer Ventilation:
The building uses a combination of mechanical supply and natural extract during the
summer months. Fresh air supply is collected at roof level using vents in wall of plant room,
The cool fresh air is supplied by mechanical ventilation via large vertical ducts
adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the office
areas raised floor plenums. Office occupants may adjust floor diffusers and open perimeter
windows to avail of more fresh air. Double facade designed as a exhaust facade and also
acts as a buffer for wind and city noise, the double facade allows staff to open perimeter
windows during windy weather.
Using displacement ventilation the stale exhaust air moves through permanent vents from
the office areas to the plant room. Motor opening vents in curtain walling to let air out of
offices in to double facade and brought back to plant room. The full height atrium has
automatic opening vents to let air out.
Summer Cooling:
The main cooling is provided using a ground water heat exchange, via a closed loop of
glycol fluid pumped through pipes embedded in the exposed concrete floors (Active
Structure System). The pipes feed the heat pump, which is reversed during summer months.
Atmospheric heat is absorbed from the fresh air moving over the exposed concrete soffits by
the pipes and transferred into the ground water.
Excess warm air in the atrium is vented out in to the atrium linked to the building
management system (BMS). The air is let out by automatic opening vents at top of atrium.
The outer glazed double facade has blinding's given shading from the solar gain.
Winter Ventilation:
The building uses a combination of mechanical supply and extract with a
heat recovery ventilation unit during the winter months. Fresh supply air is collected at roof
level using vents in wall of plant room. The cold fresh air is pre-heated by recovered heat
from the building. The fresh air is then supplied by mechanical ventilation via large vertical
ducts adjacent to the atrium corridors. Branch ducts off the main vertical ducts supply the
office areas raised floor plenums. Office occupants may adjust floor diffusers and open
perimeter windows to avail of more fresh air.Double facade designed as a exhaust
facade and also acts as a buffer for wind and city noise, the double facade allows staff to
open perimeter windows during windy weather.
Using displacement ventilation the stale exhaust air moves through permanent vents from
the office areas to the plant room. Motor opening vents in curtain walling to let air out of
offices in to double facade and brought back to plant room. The full height atrium has
automatic opening vents to let air out. Exhaust air is expelled from the building
after recovering about 60% of the ventilation heat with the HRV units.
Winter Heating:
The main space heating is provided using a ground water heat pump, via a closed loop of
glycol fluid pumped through pipes embedded in the exposed concrete floors (Active
Structure System). The pipes feed the heat pump, which exchanges heat to the embedded
pipes. Additional heat is transferred to the supply fresh air moving over the heated
concrete structure in the floor plenums, thus further distributing the heat to the offices.
Operable windows at the top of the atrium are closed during the winter, linked to the
building management system (BMS).
TOILETS
ATRIUM SPACE
OFFICES 1
RESTAURANT
OFFICES 12
OFFICES 23
PLANT ROOM
PARKING LOT
EXISTING OLD CORK CITY HALL
OFFICES 7
OFFICES 18
OFFICES 29
1400 1400
TOILETS
TOILETS
INLET
OUTLET
HEAT RECOVERY
STAIRWAY 1 PLANT ROOM
INLET
OUTLET
HEAT RECOVERY
BOILER
STORAGE
TANK
SERVICE VOID
BEHIND
STACK EFFECT
A.O.V
FLOOR PLENUM
FLOOR PLENUM
FLOOR PLENUMFLOOR PLENUM
FLOOR PLENUM
FLOOR PLENUM
FIRE
DAMPER AT
EACH FLOOR
COLD AIR BROUGHT VENTED IN
TO CAR PARK, SEPARATE FROM
BUILDING VENTILATION
AIR VENTED IN TO OFFICES
THROUGH FLOOR PLENUM
AND VENTED OUT DOUBLE
FACADE
AIR VENTED IN TO OFFICES
THROUGH FLOOR PLENUM
AND VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION
VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION IF NEEDED
AIR VENTED IN TO ROOMS
THROUGH FLOOR PLENUM
AND VENTED OUT THOUGH
SUSPENDED CEILING
VENTILATION
VENTS CLOSING AND OPENING
DURING WINTER
AIR BEING PUSHED UP BY FAN
AND TAKE AIR OUT OF OFFICES
AIR BEING VENTED IN PARAPIT
AND TAKING BACK TO HEAT
RECOVERY
NON SEGMENTED DOUBLE
FACADE BUFFER ZONE
INLET VENT
OUTLET VENT
EXHAUST AIR
EXHAUST AIR
CONDITIONED AIR
OPENING WINDOWS FOR RAPID
VENTILATION
OPENING WINDOWS FOR RAPID
VENTILATION
OPENING WINDOWS FOR RAPID
VENTILATION
HEAT
PUMP
Project:
Client:
Project No. Drawing No. Rev.
Subject:
File Ref.
Paper size: CTB file: LTScale:
ONOM File Path:
Drawn by:Scale:
Drawing Purpose:
Checked by:
Date:
Gerard Nicholson
27 OF 32 B
DESIGN DETAIL STUDIES
1:100
CORK MIXED-USE PROJECT
HEATING AND VENTILATION
G.M.I.T ARCHITECTURAL TECHNOLOGY
29/04/10
GERARD N.