Project: SAIGON CENTRE PHASE 2&3 PHASE 1 A&A WORK
RESPONSE TO INSTRUCTION OF CONSULTANT RE: BROKEN BEAM SOFFIT
Comment #1
HBCs response:
-
Page 2
Comment #2
HBCs response:
- We conducted testing for one bolt at top (out of 4 bolts).
- There is not any crack found after testing.
- Testing result:
+ The connection passed the test (required testing tensile force 85% strength of M16 8.8 106.7 kN)
+ Concrete is not broken or cracked
Figure 1. Location of tested bolt
Figure 2. Site quick report of testing for bolt #3
-
Page 3
Comment #3
HBCs response:
- There is not any crack line found.
Bottom side
Side 1 face
Side 2 face
-
Page 4
Comment #4
HBCs response:
We have already conducted UPV test.
Test result:
- Horizontal direction: average pulse velocity 3.28 km/s (distance 40 cm, concrete grade C30)
- Vertical direction: average pulse velocity 3.32 km/s (distance 60 cm, concrete grade C30)
(See Appendix 2 for detail data).