    HVAC Energy AuditHarlan Labs, Wyton

    1

    HVAC Compliance and Energy Audit Report

    for

    Harlan Laboratories, Wyton

    NAME: Mir Ali

    Date: 18/06/2012

    Project No. 12070

    Rev R1

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    2/45

    HVAC Energy AuditHarlan Labs, Wyton

    2

    1 Contents

    1.0 Executive Summary .......... ........... .......... .......... ........... .......... .......... ........... .......... ........... ........... . 3

    2.0 Introduction and General Systems Overview ....................................................................... 9

    3.0 Energy Performance Benchmarks .......................................................................................... 154.0 Assessment Findings and Observations ............................................................................... 20

    5.0Summary Condition Appraisal, Filtration and Maintenance Overview ............... ..... 25

    6.0 Documentation, Maintenance, Cleaning & Metering ....................................................... 27

    7.0 Project Recommendations and Capital Investment Opportunities ........... ........... ..... 29

    Recommended Energy Projects ...................................................................................................... 29

    Regulatory Projects: ............................................................................................................................ 29

    Low Cost Projects: ................................................................................................................................ 31

    Medium Cost Projects: ........................................................................................................................ 32

    Sustainability Projects: ....................................................................................................................... 36

    Building fabric improvement Projects: ........................................................................................ 38

    9. Conclusions ........................................................................................................................................ 41

    10.0 Action Plan / Way Forward .................................................................................................. 44

    11. Sample FRS (Functional Requirement Specification) ..................................................... 45

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    3/45

    HVAC Energy AuditHarlan Labs, Wyton

    3

    1.0

    Executive Summary

    Harlan Laboratories is a leading provider of essential, pre-clinical and non-clinical contract research,research models, lab animal diets, and services to the pharmaceutical, biotech, medical device,

    agrochemical, and chemical industries and other research organisations.

    Harlan Labs provide customers with products and services to optimize the discovery and safety of new

    medicines and compounds.

    The client had requested us to undertake a Building Energy and Sustainability Feasibility Assessment for

    Harlan UK, Wyton, Huntingdon, Cambridgeshire. This is in response to reducing the energy consumption

    of the facility in recognition of increased policy compliance legislation, operational cost optimisation and a

    continuing business driver to deliver improved building operational performance.

    Taking into account the design and age of the building and plant deployed the inspection has identified

    significant opportunities of improving HVAC system performance. These include improved maintenance

    schedules, optimising the operation of HVAC plant, control strategy optimisation and implementation of

    improved building systems energy and process operational metering, monitoring and targeting.

    Cognisance should be made of European revised legislation to future proof the facilities.

    During inspection it was observed that the site does not currently meet the Government and Industry

    stipulated Guidelines in some areas. The Wyton site (Beagles) does not have any form of cooling which

    would be needed to meet maximum temperature requirements. Based on the site visit, there are

    operational problems with the heating only AHUs due to the age of the plant. Based on the Home Office

    (HO) Code of Practice for the housing and care of animals in designated breeding and supplyingestablishments, and HO Animals (scientific procedures) Act 1986 Pg 31 requires some form of cooling to

    be provided in order to attain temperatures between 15-24 Deg C for beagles to deal with extremes of

    temperature.

    It was also noted that the site lacks an air filtration philosophy, On Site a minimum of F7 filtration is

    generally recommended to ensure operator safety, studies conducted in the US by the Environmental

    Epidemiology Program, Department of Environmental Health provide direct correlation between PM2.5

    particles and increased incidence of cancer and respiratory ailments. (The Concentration-Response

    Relation between PM2.5 and Daily Deaths by Joel Schwartz et al) carried out over six U.S. cities. There

    may also be a risk to the product as a result of poor air filtration.

    As the site is an animal research facility, we would expect that protection of pure breeds from

    contamination and outside pollutants is a primary goal. We would highly recommend that a filtration

    philosophy be developed at site, as the site may be susceptible to airborne viruses from the nearby

    testing facility within site which could wipe out existing stocks and poses a business continuity risk.

    Due consideration should be made to comply with European regulations when Directive 2010/63/EU will

    take full effect from 1 January 2013, these regulations prescribe the temperature, relative humidity, space

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    4/45

    HVAC Energy AuditHarlan Labs, Wyton

    4

    ventilation, lighting, and noise levels within these spaces, which require a provisional 1520 ACPH.

    Stocking densities should be taken into account when selecting air change rates.

    The survey covered the Inspection of HVAC systems, assessing the performance of fans, and associatedheating and cooling electrical/gas loads, in order compare performance with industry standards and to

    identify energy savings whilst maintaining their minimum performance requirements. A key observation

    was the lack of effective controls at site; it would appear that only Building 3 is connected on the BMS

    with out of range alarms with the outstation located at Hillcrest. Operational problems are being logged

    by the site personnel with no means of viewing control parameters at site, it is highly recommended that

    the site incorporate a BMS outstation with all plant operations on a BMS outstation to have effective

    control of critical monitoring parameters to ensure HO compliance for recording temperature and

    humidity.

    While reviewing the onsite records, there were no Operational and Maintenance manuals, Commissioning

    Data for the Mechanical plant including commissioning results ( including flow rates) for the AHUs werenot found with the O&M Manuals. The As Built record drawings and subsequent amendments were not

    available at site. Planned Preventative Maintenance Records indicating the frequency of maintenance /

    schedules and building log book were not made available during the visit.

    We would recommend that the site carry out a re-commissioning exercise in order to validate air flow

    rates in order to check for compliance with HO regulation.

    The site currently has 5KW cooling capacity to the Archives room, which does not warrant an Air

    conditioning inspection.

    In summary the existing HVAC system chilled water operation at Harlan UK, Wyton, Huntingdon,Cambridgeshire would benefit from optimisation to enable ongoing operational efficiencies to be realised.

    Replacement of AHUs in 1,2a,2b,4,5,11,12,24,25,25a,26,27,28 which have a heating only AHU should be

    considered as soon as possible to ensure Regulatory compliance and plant security.

    Buildings 16,17,18,19,20,21 housing whelping do not have an AHU, but rely on a rudimentary wall

    mounted supply and extract fan with a local gas fired heater in the space coupled with infra red localised

    heating in the cages to provide a temperature of 26-28 Deg C to comply with Home office regulations. It is

    not clear whether adequate air changes and temperatures needed are being attained. It is recommended

    that these areas be reviewed for compliance.

    Electrical supplies to the site is via 2 Nos feeds, the top side (Admin areas, Buildings 1,2a,2b,3) andbottom side (4,5,11,12,16,17,18,19,20,21,24,25,25a,26,27,28). The top side is served via a 400A main

    breaker whereas the back side is served via a 200A main breaker. The site also has a backup generator

    provision, the top side being served via a 100KVA generator, while the bottom side served via a 200KVA

    generator.

    It would appear that the generator serving the top side is clearly undersized for its duty and requires an

    upgrade, while the bottom side generator appears to currently meet the loadings. We would recommend

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    5/45

    HVAC Energy AuditHarlan Labs, Wyton

    5

    a full electrical audit to review the existing electrical infrastructure at site with a view to incorporate

    additional cooling loads going forward.

    A separate lighting study will follow this report.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    6/45

    HVAC Energy AuditHarlan Labs, Wyton

    6

    We have provided a breakdown of the various energy efficiency measures with a priority listing to enable the client to make a judgement for

    considering various energy efficiency measures needed to run the plant in an optimum and energy efficient manner.

    A summary of projects identified are listed below:

    Elec

    KWHr / Yr

    Elec

    / Yr

    Fuel

    KWHr/ Yr

    Fuel

    / yr

    CAPEX

    Year Tons

    Project Title BudgetCostsSimple

    PaybackCO2

    Saving

    Regulatory:

    AHU Ductwork cleaning (Per Bldg) -- - - 1,500.00 - -

    Validation of HVAC System- - - - 15,000.00 - -

    DEC Site wide (not mandatory)- - - - 1200.00 - -

    Oil Tank Plinths- - - - 30,000.00 - -

    Asbestos Risk Register- - - - 30,000.00 - -

    Low Cost Projects:

    Energy Efficient Boilers for Admin

    Bldg-

    - 13,665 947.84 30,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    7/45

    HVAC Energy AuditHarlan Labs, Wyton

    7

    Gas Fired Burners per Bldg -- 41,621 2,525.16 12,000.00 - -

    DX Systems ( Regulatory) -- - - 50,000.00 - -

    BMS Upgrade 25,1333,141.73 196,624 11,951.21 200,000.00 13.25 Years 64.6

    Sustainability Projects:

    Gas based Heating / Cooling -- - - - - -

    Sun Pipes / Natural Daylighting per

    Bldg7,100

    897.63 - - 60,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    8/45

    HVAC Energy AuditHarlan Labs, Wyton

    8

    It was noted that the site has a negative image/ perception within the local community, there

    exists an opportunity to redress this image. We have identified a solution which could result in

    the site becoming a carbon neutral flagship site while also addressing local community

    cohesion and good local Public Relations.

    As the site is situated in a rural area surrounded by farmland with an opportunity to use local

    crop waste as fuel for heating / cooling and electricity generation, thereby helping the local

    community / farmers and improving community cohesion. There are government incentives in

    the form of ROCs (Renewable Obligation Certificates) for such projects.

    While this option is by far more expensive than others investigated, we believe this would

    help the site reduce the negative press / publicity it has attracted over sometime while

    helping to reduce energy consumption and result in becoming a carbon neutral site.

    An option to explore would be to set up an ESCO (Energy Supply Company) for the sites entire

    energy needs, there are ESCOs who would set up the plant providing the necessary

    infrastructure and capital funding for long term energy contracts.

    The client would benefit from savings on capital outlays and expenditure while benefitting

    from a carbon neutral operation, should local bio-mass and wood chip be sought, this would

    help improve the local community and improve the clients image within the community.

    We believe this represents a great opportunity for the client to reduce the negative image

    within the local community while upgrading to a carbon neutral flagship operation.

    We shall be happy to explore this in detail and provide budget costs should the client wish to

    progress this further.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    9/45

    HVAC Energy AuditHarlan Labs, Wyton

    9

    2.0 Introduction and General Systems Overview

    Harlan UK, Wyton, Huntingdon, Cambridgeshire PE28 2DX consists of several buildings in the campus. Thevarious blocks house the stock, brood and whelping along with an Office and Administration area. Each of

    the Blocks is generally self contained with an AHU, DHW provision with an oil tank / LPG connection. The

    site also houses Churchill Labs, a private research facility, access was not available to review that building

    an assessment has not been included in our report.

    Incoming services

    The incoming water services to site is via a single metered supply within the site premises with 6 Nos

    water manholes provided for its distribution. During the survey, we could not find a water treatmentfacility, we would assume that the water used for cage washing and consumption is the towns mains

    water.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    10/45

    HVAC Energy AuditHarlan Labs, Wyton

    10

    Electrical supplies to the site is via 2 Nos feeds, the top side (Admin areas, Buildings 1,2a,2b,3) and

    bottom side (4,5,11,12,16,17,18,19,20,21,24,25,25a,26,27,28). The top side is served via a 400A main

    breaker whereas the back side is served via a 200A main breaker. The site also has a backup generator

    provision, the top side being served via a 100KVA generator, while the bottom side served via a 200KVAgenerator.

    It would appear that the generator serving the top side is clearly undersized for its duty and requires an

    upgrade, while the bottom side generator appears to currently meet the loadings.

    The site is served by a number of Distribution boards located in the various buildings, some of the boards

    appear to be dated, it is recommended that a periodic inspection report of the electrical installation be

    carried out to achieve regulatory compliance.

    We would recommend that the site carry out a full electrical audit in order to review the electrical

    infrastructure at site.

    There is no gas supply in the area, the heating for the entire site is met via gasoil fired / LPG boilers

    located all around the site.

    The site is not connected to the mains sewer and operates a sewer /effluent treatment plant for soil

    waste.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    11/45

    HVAC Energy AuditHarlan Labs, Wyton

    11

    LPG Layout

    The site has an extensive network of LPG tanks and piping at site providing heating for the buildings,

    domestic hot water requirement is met via localised point of use water heaters.

    Offices and Admin Block

    The office areas are heated via 2 Nos oil fired boilers located within the building. DHW for the offices is

    provided via point of use electric heaters. There is generally no cooling at site, cooling is only being

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    12/45

    HVAC Energy AuditHarlan Labs, Wyton

    12

    provided to the archive room via a 5KW heat pump. The office and admin block heating is fed of a 2500

    Litre oil tank located in the courtyard. The oil tank is currently being supported on bricks, not consistent

    with DEFRA regulations which prescribe a proper foundation.

    Buildings 1,2a,2b,4,5,11,12,24,25,25a,26,27,28

    Buildings 1,2a,2b,4,5,11,12,24,25,25a,26,27,28 house the brood, and stock. These buildings are served

    via a primary Air Handling Unit (AHUs), these are constant volume systems providing fresh tempered air

    to the barriers. The Primary AHUs are aonce through type units with the extract air from the building

    vented through openable louvers. There is no HVAC control optimisation strategy e.g. Night setback,booster facility, and or free cooling on the AHU.

    The AHUs for these buildings are fairly basic, with air being heated by gasoil / LPG fired heaters. The

    centrifugal fan is housed within an enclosure, and connected to air socks which serve the barriers. It

    would appear that these AHUs do not have adequate level of filtration, a minimum of F7 is required for

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    13/45

    HVAC Energy AuditHarlan Labs, Wyton

    13

    air socks. It is important to have the extract air ducted as it could provide a possible path for

    contamination of the pure stock by airborne viruses.

    We would recommend that air quality / filtration be reviewed in order to comply with the European

    RegulationsDirective 2010/63/EU will take full effect from 1 January 2013.

    Buildings 3, 29

    Building 3 houses the Whelping puppies, the building AHU is served via 2 Nos modern AHUs. The air

    handling unit is made up of a supply and return air sections, this consists of an inlet louvre, a panel filter,

    Gas fired heater and a forward curve belt driven centrifugal fan driven by a 415V 3 phase motor.

    The AHU incorporates a recuperator before the air is discharged into the atmosphere. Air is extracted

    from the conditioned space via a centrifugal fan, driven by a 415V 3 phase motor. The AHUs are on an

    inverter. Heating for the Building 3 is provided via Gas fired heater batteries located in the AHU. Both the

    AHUs were running at 31 Hz during the survey. AHU-1 had control issues with temperature control

    ranging from 17-27 Deg C, while AHU-2 was performing satisfactorily within a deadband of 2 Deg C.

    The air-handling units operate under the control of a BMS system, which is located at Hillcrest.

    The AHU is interfaced with the fire alarm, in case of a fire, the Supply fan is shut down, and the extract fan

    is also shut down. The fire philosophy of the building is not well defined. The HVAC plant for the barriers is

    being operated continuously.

    Building 29 is served via 2 Nos modern AHUs, this building was being constructed during the survey; no

    details of the AHUs were available for review.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    14/45

    HVAC Energy AuditHarlan Labs, Wyton

    14

    Buildings 16,17,18,19,20,21

    Buildings 16,17,18,19,20,21 houses the Whelping puppies, ventilation for these buildings is provided via

    rudimentary supply and extract wall mounted fans coupled with a gas fired heater located within thebuildings along with localised infra-red heaters in the cages. Home Office regulation for puppies requires a

    local environmental temperature of 26-28 Deg C for at least the first 5-10 days of life. It is not clear how

    these parameters are being recorded / monitored at site.

    AHUs for buildings apart from Building 3 and 29, do not have an extract ductwork but rely on gravity

    louvres for extract, this has resulted in increased gas energy consumption at site

    Asbestos roofing

    It would appear that Buildings 11,12,16,17,18,19,20,21,22,23,24,25,25a,26,27,28 have asbestos roofing, it

    would appear that the roofing due to age has become extremely fragile. Consideration should be made toupgrade the roofing to improve energy performance of the building.

    Building Fabric

    Harlan Labs, Wyton was constructed in the 1980s; the thermal elements and standards reflect the

    building regulations level of compliance at the time of construction in 1980. This building has not

    undergone any significant re-development works over the years and the services match the age of the

    building. The car park was later added to the main building.

    The construction of Harlan Labs, Wyton is based on a concrete frame and floors with block cladding walls

    with corrugated insulated panel roofing. The windows are generally double glazed with Aluminium frames

    which are part of the original installation.

    Building Fabric for Buildings 1,2,2a,3,4,5 appears to be sound, we would recommend that an air

    permeability test be carried out in order to determine their air tightness. Buildings

    11,12,16,17,18,19,20,21,22,23,24,25,25a,26,27,28 have a poor building fabric which appears to be in

    excess of 30 years old, consideration should be made to upgrade the building fabric to improve the air

    tightness and hence energy performance of the buildings.

    Site Energy Consumption data

    Actual electricity consumption during 2011 was 359,055 kWhs costing 44,881.87 based on an electricity

    tariff of 12.65 pence/kWh (Inclusive of VAT at 17.5%), the site uses Gasoil Class A2 32 Sec1 as a heating

    medium along with LPG, unfortunately there is no consumption data available to carry out an energy

    benchmarking.

    Projected energy savings and costs are based on 2011 energy prices.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    15/45

    HVAC Energy AuditHarlan Labs, Wyton

    15

    3.0 Energy Performance Benchmarks

    The building consumes significant amounts of gasoil, LPG and electricity for its operation to provide forheating, ventilation, lighting, small power and DHWS services.

    The table below relates to the energy consumption of the building, unfortunately treated floor area of

    each building including total production areas are currently unavailable for carrying out an energy

    performance benchmarking assessment. Electrical Costs below are based on 12.65p / KWHr for Electricity.

    While this data is generally accurate to an extent, we would recommend an AMR (Automatic Meter reading)

    for the Gasoil meter, so as to enable a more accurate degree day regression analysis be carried out for the

    site.

    LPG is used for heating the barrier / production areas, while gasoil is limited to the Office / Admin block andused as generator fuel.

    Table 1Harlan Labs, Wyton Building Energy Use 2011 (based on datasheet provided by client)

    Utility Annual Energy &

    Water Consumption

    Annual Cost CO2

    emissions1

    kWHr/year % /year % tonnes

    Electricity 359,055 11.3 44,881.87 20.8 195.6

    LPG 2,774,751 87.6 168,362.00 78.1 717.93

    Gasoil * 34,164 1.1 2,369.60 1.1 9.51

    Total Utility 3,167,970 215,613.47 100% 923.04

    Total CO2 Emitted for utilities (tonnes) 923.04

    1. Carbon Dioxide conversion factors based on carbon Trust.

    Gasoil estimated at 70% of total consumption based on discussions with the client as gasoil is also being

    used as generator fuel.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    16/45

    HVAC Energy AuditHarlan Labs, Wyton

    16

    Site wide Energy Split

    As is evident from the picture, LPG heating for the barriers constitutes a major energy load at site.

    29,121 29,181

    31,807

    29,84730,376

    29,15729,446 29,198

    28,589

    30,176 30,122

    32,035

    Electricity Consumption- 2011Electricity (KWHr)

    11%

    88%

    1%

    Site Energy Consumption

    Electricity LPG Gasoil *

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    17/45

    HVAC Energy AuditHarlan Labs, Wyton

    17

    Regression Analysis

    The degree day plot allows us with a comparison with weather related measure and is a powerful tool for

    energy managers to evaluate the performance of buildings. This shows the relationship between the

    actual external temperatures and the electrical consumption on site.

    Based on the data provided by the client, it would appear that the electrical consumption at site is fairly

    accurate. There are no individual meters monitoring oil consumption, Gasoil and LPG consumption is

    based on monthly / quarterly receipts. Unfortunately, these do not provide adequate granularity to carry

    out an accurate regression analysis. As months with no oil / LPG deliveries would not be adequately

    represented on the assessment.

    The nearest weather station with a good dataset available was the Ramsey station in Cambridgeshire andhas been used in the assessment.

    The degree day plot allows a comparison with weather related measure. This shows the

    relationship between the actual external temperatures and the gas consumption on site.

    In the equation within the graph:

    The R2 regression value represents the degree of scatter about the line of best fit. The R2 value

    for a perfectly controlled system would be unity (R2=1) and anything above 0.9 is reasonable.

    The y-intercept shows the energy needed by the building regardless of the external

    y = 1645.8x - 15107

    R = 0.9193

    0

    100000

    200000

    300000

    400000

    500000

    600000

    700000

    0 100 200 300 400

    LPGConsumption

    Degree Days

    2011 LPG Consumption KWHr

    2011 LPG ConsumptionKWHr

    Linear (2011 LPG

    Consumption KWHr)

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    18/45

    HVAC Energy AuditHarlan Labs, Wyton

    18

    temperature. This is known as the weather unrelated demandfor instance boiler losses and

    hot water.

    The slope of the line shows extra kWh required for each unit increase in degree day value, or

    increase due to lower external temperatures.

    The scatter of the graph (an R2 value of 0.91) suggests a reasonably good controlled heating system

    and would indicate room for improvement with the control of the system.

    The slope of the characteristic line indicates a weather-related demand of about 1645.8 kWh per

    degree day. It would appear that this is unusually high for a site which is maintaining a wide dead

    band of 15-24 Deg C in temperature control in the barriers. We would recommend that this be

    investigated further.

    The site also uses Gasoil for heating in the office block and for the generators. Gasoil constitutesabout 1.2% of the total heating fuel consumed at site and does not represent a major energy

    load.

    Based on the information provided by the client with regards to gasoil consumption, we have

    carried out a regression analysis for the office area. Unfortunately, we have a poor dataset for

    Gasoil consumption at site. As expected, there is poor correlation and regression due to the

    quality of data available.

    y = 15.998x + 1279.3

    R = 0.1797

    0

    2000

    4000

    6000

    8000

    10000

    12000

    0 100 200 300

    GasOilConsumption

    Degree Days

    Office Gasoil Consumption KWHr

    2011 Gasoil

    Consumption KWHr

    Linear (2011 Gasoil

    Consumption KWHr)

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    19/45

    HVAC Energy AuditHarlan Labs, Wyton

    19

    Energy Benchmarking:

    This compares the energy performance for Harlan Labs, Wyton delivered energy in KWHr/M2/year of

    treated floor area. Current performance has been calculated on invoice data and hour hourly data

    provided by the client.

    The site has a total area of XXX M2, with a total production area of XXX M2 consuming 359,055 KWHr of

    electricity and 2,808,915 KWHr of LPG and Gasoil for its operation. The Energy cost per M2 for the

    production area is

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    20/45

    HVAC Energy AuditHarlan Labs, Wyton

    20

    4.0 Assessment Findings and Observations

    HVAC systems at site could be broadly divided into two categories, one catering for the broodand stock and the other catering to the whelping puppies.

    4.1AHUs serving Buildings 1,2a,2b,4,5,11,12,24,25,25a,26,27,28

    Buildings 1,2a,2b,4,5,11,12,24,25,25a,26,27,28 house the brood, and stock. These buildings are served

    via a primary Air Handling Unit (AHU), these are constant volume systems providing fresh tempered air to

    the barriers. The Primary AHUs are a once through type units with the extract air from the building

    vented through openable louvers. Unfortunately, there is no recorded information at site to enable us to

    carry out an assessment of air flow rates / energy consumption of these buildings.

    The AHUs for these buildings are fairly basic, with air being heated by gasoil / LPG fired heaters. The

    centrifugal fan is housed within an enclosure, and connected to air socks which serve the barriers. This

    arrangement results in high eddy losses and is not recommended. It would appear that thes e AHUs do

    not have adequate level of filtration. There is no data available at site indicating air flow rates of these

    AHUs, air socks was found to be damaged in building 2a, many of the air socks were dirty needing a

    cleanup.

    Based on Home Office regulations, some form of cooling is required to provide temperatures between 15-

    24 Deg C for beagles to deal with extreme ambient temperatures. Based on the site operational log, the

    gas fired burners are 30 years old well past their recommended life and are showing signs of increasing

    failure, this has resulted in an inability to meet the HO recommended peak temperatures.

    4.2 Ventilation and heating for buildings 16,17,18,19,20,21

    Buildings 16,17,18,19,20,21 houses the Whelping puppies, ventilation for these buildings is provided via

    rudimentary supply and extract wall mounted fans coupled with a gas fired heater located within the

    buildings along with localised infra-red heaters in the cages. Home Office regulation for puppies requires a

    local environmental temperature of 26-28 Deg C for at least the first 5-10 days of life. Unfortunately,

    there is no recorded information at site to enable us to carry out an assessment of air flow rates / energy

    consumption of these buildings.

    It is not clear how these parameters are being recorded / monitored at site.

    4.3 Admin Building

    The admin building is served via an LPHW radiator system with natural ventilation, there is no cooling in

    the admin / security building apart from the cooling provided by the heat pump in the archive room.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    21/45

    HVAC Energy AuditHarlan Labs, Wyton

    21

    4.4 DX Systems

    The site has a DX system providing heating and cooling for the Archive room, the units runs continuously

    (24/7) and is locally controlled. No documented records were available regarding maintenance of filters.

    The refrigerant used in the units is R410A. On inspection there was no evidence of leakage and the units.

    The areas around the condensing coil were generally free of debris and obstructions.

    4.5 Boilers

    The site has gas fired boilers providing Heating and DHW to the small admin offices located within each

    building all across the site. These boilers are on a time clock and controller. During the survey, it was

    noted that these are not being optimally used, consideration should be made to incorporate weather

    compensation to improve energy efficiency.

    DHW for male and female change areas in some buildings is provided via a point of use standalone

    electric water heater.

    4.6 Oil Tanks

    As the site does not have a mains gas supply, all heating and DHW services are via Oil tanks and LPG tanks

    located at the following locations:

    During the survey, it was noticed that the LPG tanks had a proper concrete plinth, the oil tank bunding for

    the admin block was not compliant with the Oil storage regulations. Failure to comply is a criminal

    offence. The site could be fined up to 5,000.

    DEFRA can serve a notice under section 161A Water Resources Act 1991 (works notice) to make the site

    improve the oil storage standards. Failure to comply with a notice is a criminal offence and may result in

    prosecution.

    4.7 Domestic Hot Water Provision

    Domestic hot water is provided by gas fired DHWS generators providing heating and hot water to the

    various blocks, employing a decentralised system. These boilers have a centralised controller, some of

    the timers on these controllers were out by 1 hour suggesting that they have not been changed to British

    Summer time. The hot water is circulated within the building to its points of use thereby minimising

    heating losses. The site has hard water with large calcium carbonate deposits and has maintained rigorous

    water softening maintenance policy.

    It is recommended that all tanks be de-scaled annually as part of the L8 service.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    22/45

    HVAC Energy AuditHarlan Labs, Wyton

    22

    4.8 Asbestos roof

    Buildings 11,12,16,17,18,19,20,21,22,23,24,25,25a,26,27,28 have asbestos roofing, it would appear that

    the roofing due to age has become extremely fragile. An asbestos register could not be identified at site,it is a legal requirement under the Control of Asbestos Regulations 2006 (Regulation 4).Consideration

    should be made to upgrade the roofing to improve energy performance of the building.

    4.9 Water consumption

    The sites water demand is met through a single water mains supply, it has a large demand of water

    namely for cleaning the cages, and for consumption by animals. During the survey, a Reverse Osmosis

    (RO) plant could not be identified, we would assume that the water is currently not being additionally

    treated. Water saving devices like spray taps can help reduce water demand at site. We would

    recommend that the site carry out a water audit to determine water consumption / savings.

    4.10 Lighting

    Lighting at site is generally in good order with a combination of Fluorescent T5 light fittings in the barriers,

    and office areas. The Lux levels in the office areas were between 380 Lux and 600 Lux in some areas,

    which is quite acceptable for an office environment and complies with the CIBSE Lighting Guide (LG7)

    regulations, Lighting Guide 7 (2005): Office lighting and the BS EN 12464-1:2002 Light and lighting -

    Lighting of work places - Part 1: Indoor work places.

    Lighting in the production areas consists of T5 Fluorescent Light fittings. Lux levels measured in the

    production areas were within an acceptable range.

    We would recommend that the lighting in the offices be integrated with Energy efficient lighting controls

    with PIR occupancy switches with daylight linked dimming thereby reducing energy bills further. We

    would recommend these lighting controls; they have a simple payback of less than 2 years.

    Lighting for the production areas and stores are recommended to be changed from the existing T8

    Fluorescent lighting toHF T5 tubes along with intelligent control to take diurnal / seasonal patterns of the

    rodents.

    A lighting survey had been undertaken, the results of the audit have been enclosed as separate report.

    4.11 Building Management Systems

    The site does not have a BMS and was found lacking of an effective control strategy at site, it would

    appear that only Building 3 is connected on the BMS with out of range alarms with the graphic front end

    located at Hillcrest. Operational problems are being indicated by the site personnel with no means of

    viewing control parameters at site, it is highly recommended that the site incorporate a BMS outstation

    with all plant operations on a BMS outstation to have effective control of critical monitoring parameters

    to ensure HO compliance.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    23/45

    HVAC Energy AuditHarlan Labs, Wyton

    23

    4.12 Building Fabric

    Building Fabric at site presents a legacy picture, with some buildings constructed recently having a sound

    building fabric and U values, while others which were constructed in the 1980s have a poor buildingfabric and U values, the roofs of the older buildings had asbestos which appears fragile and in need of an

    upgrade. Consideration should be made to upgrade the building fabric and improve the air tightness and

    hence energy performance of the buildings which appears to be in excess of 30 years old. An Asbestos

    Risk register for the site is recommended in order to adequately monitor and control asbestos at site.

    4.13 Automated Metering / Monitoring and Targeting

    The site does not have adequate sub metering on any buildings, individual auxiliary plant serving the

    building do not have a dedicated energy input or hours run meter. Meter readings are read and recorded

    on a regular basis and this data was provided by the client prior to attending site. Additionally this setup isnot ideal as it does not reward energy efficiency in anyway.

    It is recommended that the scope of metering be reviewed to install appropriate metering at least to the

    more significant energy consuming air conditioning plant, and subsequently to record the consumption on

    a regular basis.

    it is preferable to automate the Utility consumption of major ancillary loads in order to identify individual

    energy consumption patterns and thereby seek energy reduction, by various options available to the

    client which include installation of AMR (Automated Meter Reading) to capture half hourly Energy

    consumption data in order to monitor energy consumption and to gather real time energy profile data as

    part of the drive to reduce energy and running costs.

    We would recommend that monitoring & targeting system be introduced to the site to allow a more

    detailed review of energy use on the site.

    A good M&T system would enable the following:

    establish current consumption

    compare current consumption with historical data and benchmarks

    set future targets

    compare current consumption with the targets

    identify trends in consumption

    Produce exception reports when targets are exceeded.

    Accurate apportioning of utility costs for the different tenants

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    24/45

    HVAC Energy AuditHarlan Labs, Wyton

    24

    It is estimated that there is a 5% reduction in energy consumption due to an effective M & T

    system.

    4.13 Auxiliary Services

    In addition to heating, lighting and hot water, the admin building uses electricity for powering the building

    IT systems, printers, photocopiers, computer workstations, kitchen and tea room preparation areas.

    These Auxiliary services should be switched off when not in use to conserve energy.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    25/45

    HVAC Energy AuditHarlan Labs, Wyton

    25

    5.0Summary Condition Appraisal, Filtration and Maintenance Overview

    The AHUs serving the building are rudimentary and do not incorporate adequate level of airfiltration in them, the air socks in building 2a was found to be torn, air flow rates of these units are

    unknown it is not clear whether current home office regulation of 10-12 ACPH are being achieved.

    Some of the AHU fan section had foliage and debris in them indicating no filters were present, a

    minimum of F6 level of filtration would be needed to protect the fans and air socks from airborne

    dirt and debris.

    In general, the majority of plant and equipment is in operation, although a number of issues

    observed whilst on site need to be addressed and these are commented on in paragraphs to follow.

    Based on the Code of practice as advised by the Home Office for the housing of animals in designated

    breeding and supplying establishments which were prepared in consultation with Laboratory Animals

    Breeders Association (LABA) Guidelines on the care and housing of animals bred for scientific

    purposes, the Association of the British Pharmaceutical Industry (ABPI), British Laboratory Animal

    Veterinary Association (BLAVA), Institute of Animal Technology (IAT), and the Laboratory Animal

    Science Association (LASA), the ventilation rate of the room is related to stocking density and to the

    heat generated by animals and equipment in the room (thermal load).

    In order to maintain suitable air quality 10-12 changes of fresh or air conditioned air per hour

    distributed throughout the room would normally be adequate for rooms with high stocking densities

    eg dogs etc. It is highly recommended that the ventilation system complies with European

    regulations Directive 2010/63/EU which will take full effect from 1 January 2013.

    At present it would appear that none of the AHUs are capable of meeting the 15-20 ACHP criteria

    laid down by the code of practice.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    26/45

    HVAC Energy AuditHarlan Labs, Wyton

    26

    Buildings 16,17,18,19,20,21 housing the Whelping puppies, have uncontrolled ventilation provided

    via rudimentary supply and extract wall mounted fans coupled with a gas fired heaters along with

    localised infra-red heaters in the cages. Home Office regulation for puppies requires a local

    environmental temperature of 26-28 Deg C for at least the first 5-10 days of life. It is not clear howthese parameters are being recorded / monitored at site. These buildings do not have any filtration,

    thereby rendering all these buildings susceptible to airborne particulate matter / airborne viruses, a

    virus strain from the nearby testing facility could wipe out the entire stock of Whelping puppies and

    poses a business continuity risk.

    Evidence provided at the time of inspection, suggests that a comprehensive planned preventative

    maintenance (PPM) regime is needed at site, which includes an effective reactive maintenance

    regime supported by onsite maintenance personnel.

    Filtration

    As is evident from the above pictures, it would appear that air filtration at site is very poor. As the

    site operates an animal research facility with emphasis on breeding pure breeds, we would

    recommend that consideration should be made towards setting up a filtration standard at site. It is

    recommended that air filtration at site be upgraded to F9 or F13 depending on the level of protection

    to prevent airborne viruses / pathogens from contaminating the pure breed being bred at site.

    The site also houses a private research facility, Churchill Labs where it is presumed, where critical

    research takes place. It is recommended that consideration be made to review air filtration / extract

    at the facility in order to safe guard operations downstream.

    The site does not have extract ductwork which could provide a possible path for airborne viruses and

    contaminants to enter site, it is important that the entire ventilation philosophy be reviewed at site.

    We envisage that this is critical to the operations at site and presents a business continuity risk.

    Specific Fan Power

    Whilst on site, power consumed by all large supply and extract fans (including losses through

    switchgear VSDs) was measured in order that Specific Fan Power (SFP) of each system may be

    determined and compared with current levels recommended in the Non- domestic Heating, Cooling

    and Ventilation Compliance Guide.

    Specific Fan Power of the AHUs could not be calculated due to lack of data available regarding their

    flow rates. The AHUs currently do not meet the required specific fan power detailed in the Non-

    domestic Heating, Cooling and Ventilation Compliance Guide. Consideration should be made to

    review the air flow rates by re-visiting the ventilation design and BMS philosophy is also

    recommended.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    27/45

    HVAC Energy AuditHarlan Labs, Wyton

    27

    6.0 Documentation, Maintenance, Cleaning & Metering

    All documentation required to compile this report was either provided prior to attending site by theFMT, whilst on site. The following list of documentation was requested during the site inspection:

    Operation and Maintenance manuals

    Plant Installation drawings

    Planned Preventative Maintenance Records

    Floor Plans (used for the calculation of ventilation air change rates)

    While reviewing the onsite records, there were no Operational and Maintenance manuals,

    Commissioning Data for the Mechanical plant including commissioning results ( including flow rates)for the AHUs, were not found with the O&M Manuals. TheAs Built record drawings and subsequent

    amendments were not available at site, probably due to the fact that there are no records available

    at site due to the age of the building. Planned Preventative Maintenance Records indicating the

    frequency of maintenance / schedules and building log book were not available during the visit.

    It is recommended that the site carry out a complete re-commissioning of all the blocks, in order to

    validate air flows, water flows, fan ESPs and ACHP rates across various barriers in the various blocks.

    The indicated service frequency should comply with normal practice and the recommendations of

    HVCA SG20 (Standard Maintenance Specification for Mechanical Services in Buildings - Section 9

    Packaged Chillers), indicating that work has been untaken and no details of the content of the service

    visit i.e. major or minor. A separate service report sheet is recommended to confirm the detail of the

    work undertaken.

    Duct Cleaning

    It would appear that the ductwork serving the Buildings has never been cleaned and disinfected, this

    problem is compounded by the fact that there is inadequate levels of air filtration while we would

    advise that these systems be periodically cleaned and disinfected to prevent build up of debris, thus

    encouraging microbial growth. The client has stated his concern of long downtimes and an increased

    exposure for revenue generating processes.

    We would recommend that while the AHUs are being replaced, a temporary Air Sock be installed

    which would form part of a standby system and connected to the AHU, while the ductwork is being

    cleaned. This would help in minimising downtime.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    28/45

    HVAC Energy AuditHarlan Labs, Wyton

    28

    Metering

    No individual items of plant serving this building has its own dedicated energy input or hours run

    meter. Meter readings are read and recorded on a regular basis and this data was provided by theclient prior to attending site.

    It is recommended that the scope of metering be reviewed to install appropriate metering at least to

    the more significant energy consuming air conditioning plant, and subsequently to record the

    consumption on a regular basis. CIBSE TM39: Building energy metering provides guidance on

    developing a metering plan and should be consulted for best practise and advice.

    It is also recommended that AMR (Automatic Meter Reading) for all the tenants is introduced, this

    would automate the billing process, it also includes trends in consumption etc which would help the

    tenant to identify wastage in energy and help reduce energy consumption. As a general rule, a 5%

    energy saving is expected by incorporating an AMR.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    29/45

    HVAC Energy AuditHarlan Labs, Wyton

    29

    7.0 Project Recommendations and Capital Investment Opportunities

    Recommended Energy Projects

    The Audit-identified projects have been grouped into 4 different categories namely Statutory /

    Regulatory requirements, Low cost options, medium cost (Infrastructure upgrade) and Sustainability

    projects which are discussed below. All costs included here are budget costs (25% subject to detailed

    design):

    Note: Regulatory Projects may not be energy reductions, but EECO2 will ensure energy efficient solutions

    are proposed to minimise increases.

    Regulatory Projects:

    1. AHU Ductwork Cleaning: The Supply air socks on the AHUs were found to be dirty. It would

    appear that there is poor air filtration regime at the air intakes at the heaters. Existing ductwork

    has not undergone a cleaning regime. Airborne particulate matter present at site clearly presents

    a health hazard.Minimum F7 requirement for protection, along with yearly washing should be

    carried out, recommend a spare set of socks to allow for cleaning.

    Budget Cost:1500 for cleaning and disinfecting per AHU to provide a hygiene and safety deepclean.

    2.

    Measurement of HVAC System: Based on the Code of practice for the housing of animals indesignated breeding and supplying establishments, Laboratory Animals Breeders Association

    (LABA) Guidelines on the care and housing of animals bred for scientific purposes. The Industry

    (Home Office) Guidelines specify 10-12 changes of fresh or air conditioned air per hour

    distributed throughout the room for dogs. It would appear that the air flow rates in the Buildings

    currently do not meet the regulatory standards mentioned therein. It is advisable that the

    ventilation system be validated in all the Blocks as part of the Home Office regulatory

    compliance.

    Budget Cost:We would recommend that a budget Capex of 15K be set aside for carrying outmeasuring and checking of the HVAC systems at site in order to determine current air changes

    being achieved.

    3. Energy Performance Certificate (EPC) / Display Energy Certificate (DEC): An

    Energy Performance Certificate (EPC) is a statutory requirement in order to comply with the

    Energy Performance of Buildings Directive and UK National legislation. While, it is not mandatory

    for the site currently as it is privately owned, and would be needed while buying and selling the

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    30/45

    HVAC Energy AuditHarlan Labs, Wyton

    30

    premises. The client might wish to have an EPC certificate in order to determine the buildings

    asset rating.

    Display Energy Certificate (DEC) while not mandatory, shows the actual energy usage of abuilding, the Operational Rating, and help the public see the energy efficiency of a building.The

    DEC should be clearly displayed at all times and clearly visible to the public.A DEC is valid for 12

    months and needs to be updated annually. The accompanying Advisory Report is valid for 7

    years. The client might wish to carry out a DEC for public display in order to improve Public

    Relations (PR) in the local community.

    Budget Cost: A Budget cost would be 3K for carrying out an EPC and report, while a DECwould cost about 1200. As CIBSE accredited Energy Assessors, we can carry out the above works.

    4.

    Oil Tank plinths:During the survey, it was noticed that the oil tank plinths was not compliantwith the Oil storage regulations, some of the oil tanks were mounted on bricks, this is not as per

    DEFRA guidelines for oil storage. Failure to comply is a criminal offence. The site could be fined

    up to 5,000 by DEFRA.

    Budget Cost: We would assume that the cost of Civil works for providing adequate plinthsincluding providing an adequate concrete base for the Oil tanks located in the Admin courtyard

    and other areas at site would be 30K. We shall be happy to review this to make it DEFRA

    compliant.

    5. Asbestos Risk Register: During the survey, it was noticed that Buildings

    11,12,16,17,18,19,20,21,22,23,24,25,25a,26,27,28 have asbestos roofing, it would appear thatthe roofing due to age has become extremely fragile. An asbestos register could not be identified

    at site.

    The duty to manage asbestos is a legal requirement under the Control of Asbestos Regulations

    2006 (Regulation 4). It applies to the owners and occupiers of commercial premises (such as

    shops, offices, industrial units etc) who have responsibility for maintenance and repair activities.

    In addition to these responsibilities, they also have a duty to assess the presence and condition

    of any asbestos-containing materials. If asbestos is present, or is presumed to be present, then it

    must be managed appropriately. Failure to comply is a criminal offence; exposure to asbestos

    can lead to lung cancer and other respiratory ailments rendering the company liable to

    negligence.

    Budget Cost: We would assume that the cost of carrying out an asbestos survey at siteincluding preparing an asbestos risk register at site would be 30K. We shall be happy to review

    this in more detail should the client wishes to pursue this further.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    31/45

    HVAC Energy AuditHarlan Labs, Wyton

    31

    Quick Wins:As part of the assessment, a number of quick wins or JDIs (just Do it) were reviewed. These included:

    Boiler optimisation,

    Adding weather compensation to the office boilers, Insulating the heating system and DHWS system.

    Unfortunately, these measures are not viable as the boiler is showing increasing signs of deterioration

    due to its age. The heating and DHWS system at site is highly decentralised with a standalone boiler

    for the offices in the barriers, DHWS is provided via standalone combi boilers and/ or point of use

    electric heaters.

    Low Cost Projects:

    6.

    Energy Efficient Boilers for the Admin Block: The existing oil fired boilers in theAdmin block were installed in the 1980s is in a poor condition, it is well past the CIBSErecommended design life expectancy of 15 years. Due to their present age, there is insufficient

    combustion of the boilers resulting in acrid smoke in the offices during start up. The frequency of

    maintenance has increased many fold. These boilers have an efficiency of 60-70%.

    We would recommend that these be replaced with energy efficient Boilers which have an

    efficiency greater than 95%, the boilers selected shall be fully modulating, have weather

    compensation and incorporate an intelligent boiler controller for energy optimised operation.

    This would reduce energy consumption in excess of 30%.

    Energy Savings Identified for Oil Fired Boilers in Admin Block:

    Admin Block Potential Savings

    KWHr/pa 13,665

    GBP Saving/pa 947.84

    CO2 te/pa 3.80

    Simple Payback Period < 3 years*Budget Costs 30,000

    *Admin Block Boiler in poor condition, in need of a replacement. Energy

    efficient boiler is 2-2.5K more expensive than a standard boiler. Payback

    based on cost comparison.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    32/45

    HVAC Energy AuditHarlan Labs, Wyton

    32

    7. Water Saving Devices:The sites water demand is met through a single water mains supply,with a large water demand namely for cleaning the cages, and for consumption by animals.

    Water saving devices like spray taps/ flow restrictors can help reduce water demand at site. We

    would recommend that the site carry out a water audit to determine water consumption /

    savings.

    Energy Savings Identified for Water Saving Devices:

    Water Saving Devices Potential Savings

    Water in M3/pa* 225

    GBP Saving/pa** 450

    CO2 te/pa N/A

    Simple Payback Period

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    33/45

    HVAC Energy AuditHarlan Labs, Wyton

    33

    9. Energy Efficient AHUs:AHUs at site could be broadly classified into 2 categories, namelythe brood and stock housing and the Whelping Puppies building.

    The AHUs serving Buildings 1,2a,2b,3,4,5,11,12,24,25,25a,26,27,28 are more than 30 years old

    and showing signs of failure, it is our considered opinion to replace the se with Low Energy AHUs

    capable of providing 10-12 AHCP for these Buildings, while incorporating system redundancy to

    allow the AHUs to function during downtime.

    Buildings 16,17,18,19,20,21 housing whelping do not have an AHU and relies on wall mounted

    fans for achieving the air change rates, It is recommended that these areas be reviewed for

    compliance.

    Due to the fact that the AHUs serving the buildings are more than 30 years old and showing

    signs of failure, along with the fact that these AHUs are not capable of providing 15-20 AHCP as

    mandated by the European directive which comes into effect in 2013.

    There are two options available for review:

    A Twin Fan system, operating at 50% duty each, capable of ramping up to design duty during

    maintenance of a single system.

    Incorporating a Fan Wall Technology system, with a 2N redundant system. The benefits of Fan

    Wall Technology include:

    Dramatically Shorter Footprint

    Quiet Operation and Low Vibration

    Optimized Performance and Energy Efficiency by providing more uniform airvelocities across filters and coils.

    Redundancy by Protecting critical assets and minimizing downtime exposure

    for revenue generating processes

    Lower Maintenance Costs

    It is worth noting that the current AHU does not appear to comply with the Home Office regulations,

    or the proposed EU regulations. Current levels of filtration on the AHUs arenot adequate.

    The energy savings shown below are a cost comparison between a standard AHU and an energy

    efficient AHU when considering an upgrade.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    34/45

    HVAC Energy AuditHarlan Labs, Wyton

    34

    Traditional Air Handling Unit

    AHU Fan Consumption kWh Fan Power Cost

    Capital

    Cost

    Building 2a 192,687 13,102.69 19,250.00

    Part L Compliant Air Handling Unit

    AHU Fan Consumption kWh Fan Power Cost

    Capital

    Cost

    Building 2a 146,382 9,953.98 25,000.00

    Saving 3,148.71 ROI 1.83

    Budget Costs for Energy Efficient AHU:100K- 200K

    10.Heating and Cooling Provision for the Energy Efficient AHUs:Heating for the site iscurrently provided via Gas fired burners, there is no cooling at site. In order to meet the Home

    office criteria and to comply with the proposed EU regulations, it is advisable that cooling be

    incorporated.

    a) Gas Fired BurnersThe Gas fired burners have operational problems at site indicate a very high frequency of failure

    of the gas fired heaters, primarily due to the age of the plant. It is also worth noting that these

    burners have a poor efficiency of around 55-60%. It is recommended that these be replaced by

    energy efficient burners along with an effective control strategy including weather

    compensation.

    Energy Savings Identified for Gas Fired Burners:

    Water Saving Devices Potential Savings

    KWHr/pa 41,621

    GBP Saving/pa 2,525.16

    CO2 te/pa 80.5

    Simple Payback Period 4.75 YearsBudget Costs 12,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    35/45

    HVAC Energy AuditHarlan Labs, Wyton

    35

    b) DX UnitsDX units present a less expensive alternative to incorporate cooling at site. However, it should be

    noted that the electrical supplies at site are stretched thereby requiring exploring alternatives

    including reinforcing the electrical supply to site.

    There exists an alternative approach to this problem which has been included as a sustainability

    project. Please refer to Project 12 for more details.

    Energy Savings Identified for DX System:

    DX System Potential Savings

    KWHr/pa *See Note

    GBP Saving/pa

    CO2 te/pa

    Simple Payback Period

    Budget Costs 50,000.00

    Budget Costs for DX System per building

    *currently there is no cooling, needed for achieving regulatory compliance.

    11.BMS Upgrade: The site does not have a BMS and was found lacking of an effective controlstrategy at site; it would appear that only Building 3 is connected on the BMS with out of range

    alarms with the outstation located at Hillcrest. Operational problems are being indicated by the

    site personnel with no means of viewing control parameters at site, it is highly recommendedthat the site incorporate a BMS outstation with all plant operations on a BMS outstation to have

    effective control of critical monitoring parameters to ensure HO compliance.

    It is estimated that there is a 5-7 % reduction in energy consumption due to an effective BMS

    system.

    Energy Savings Identified for BMS:

    BMS Potential Savings

    KWHr/pa 221,757GBP Saving/pa 15,092.94

    CO2 te/pa 64.6

    Simple Payback Period 13.25 Years

    Budget Costs 200,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    36/45

    HVAC Energy AuditHarlan Labs, Wyton

    36

    Sustainability Projects:

    Sustainability projects have been included with a view to address some shortcomings at site namelylack of spare provision in the electrical infrastructure at site, thereby requiring expensive electrical

    infrastructure upgrades. We have also looked at options where fuel could be locally sourced within

    the local community thereby resulting in better community cohesion / PR. It would also result in the

    site being carbon neutral.

    12.Gas Based Heating and cooling

    As the site is considering installing cooling to comply with home office regulation along with the fact

    that the heaters are in excess of 30 years old and in need replacement, it is therefore recommendedthat a gas based heat pump solution providing heating and cooling be explored thereby providing both

    heating and cooling at site.

    It is worth noting that the electrical infrastructure at site is stretched, any additional cooling demands

    for compliance would require additional electrical reinforcements at site. This solution does not

    require expensive electrical infrastructure upgrades.

    We can provide budget costs of a Gas based heat pump once treated floor areas of these buildings are

    made available.

    As part of the assessment, we have also explored an option for a Trigeneration CHP plant at site. Thesite is situated in a rural area surrounded by farmland with an opportunity to use crop waste as fuel,

    thereby helping the local community and improving community cohesion. There are government

    incentives in the form of ROCs (Renewable Obligation Certificates).

    A ROC is the green certificate issued for eligible renewable electricity generated within the United

    Kingdom and supplied to customers in the United Kingdom by a licensed supplier. Co-firing of crop

    waste results in 1.5 ROC per MW produced, each ROC is worth approximately 40 per MW produced.

    While this option is by far more expensive than others investigated, we believe this would help the site

    reduce the negative press / publicity it has attracted over sometime while helping to reduce energy

    consumption and result in becoming a carbon neutral site. We shall be happy to review this in detail

    and provide budget costs should the client wish to progress this further.

    An option to explore would be to seek services of an Energy Supply Company (ESCO), who would set

    up the proposed plant and infrastructure while seeking long term energy contracts from the site. This

    would result in the client saving on capital outlays and expenditure while benefitting from a carbon

    neutral operation.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    37/45

    HVAC Energy AuditHarlan Labs, Wyton

    37

    Energy Savings Identified for Gas based Heating & Cooling:

    Gas based Heating & CoolingPotential SavingsKWHr/paGBP Saving/pa

    CO2 te/pa

    Simple Payback Period

    Budget Costs

    Budget Costs for Gas based Heating & Cooling: Subject to detailed assessment.

    13.

    Sun Pipes: The Lighting system at site is generally good with ample Lux levels achieved withinthe barriers. The site has managed to replace nearly all of the T8 fluorescent light fittings with T5

    light fittings.

    Lighting at site represents a major load due to lack of cooling at site, consideration could be

    made to reduce electrical energy consumption by incorporating sun pipes and incorporating

    dimming features on the existing T5 light fittings, this would help reduce the need for procuring

    additional electrical supplies at site due to added cooling requirement to comply with the

    mandated regulatory requirements.

    Energy Savings Identified for Sun Pipes:

    Sun PipesPotential Savings*KWHr/pa 7100

    GBP Saving/pa 897.63

    CO2 te/pa 3.8

    Simple Payback Period

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    38/45

    HVAC Energy AuditHarlan Labs, Wyton

    38

    There exists an opportunity to reduce energy consumption by reviewing the process cooling

    loads at site. We would propose to review the process cooling loads at site and come up with a

    proposal to use evaporative cooling for the AHUs coupled with Bore Hole cooling thereby

    resulting in massive energy savings to be made. Typical ground water supply temperatures are in

    the range of 6-10C and typical re-injection temperatures 12-18C (subject to the requirements

    of the abstraction licence).

    Energy Savings Identified for Evaporative Cooling / Borehole cooling:

    EC / Borehole cooling Potential Savings *

    KWHr/pa

    GBP Saving/pa

    CO2 te/pa

    Simple Payback Period

    Budget Costs

    Budget Costs for EC / Borehole cooling : Subject to detailed assessment

    *It is difficult to put a Budget cost for this option, as a detailed study is required to look at

    Ground Water levels / Ground water abstraction for large yields. As a rough estimate, we would

    put it at 200K.

    Building fabric improvement Projects:

    15.Thermal Image Survey: Building fabric has been in existence for more than 30 years, which

    has resulted in high heat losses from the building. It is recommended that a thermal Image

    survey be carried out site wide in order to determine the leakage paths in the building fabric

    including windows, walls, roofing, piping, ductwork etc. This would help recommendations for

    building fabric U value improvement, relevant upgrade on leakage paths etc.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    39/45

    HVAC Energy AuditHarlan Labs, Wyton

    39

    Energy Savings Identified for Thermal Image Survey and Fabric report:

    Thermal Image Survey Potential Savings*KWHr/pa

    GBP Saving/pa

    CO2 te/pa

    Simple Payback Period

    Budget Costs 15,000.00

    *It is difficult to provide potential savings until information on the leakage paths and energy lost due

    to poor building fabric and air permeability levels are available.

    16.Building Fabric Improvement projects: Building fabric has been in existence for more

    than 30 years, which has resulted in high heat losses from the building. Consideration could be

    made in the future to improve the building fabric of the buildings by improving windows, walls

    and by adding additional insulation.

    It is worth noting that Buildings 11,12,16,17,18,19,20,21,22,23,24,25,25a,26,27,28 have asbestos

    roofing, which due to age has become extremely fragile, consideration should be made to

    upgrade the roofing in these buildings.

    Energy Savings Identified for Building Fabric Improvement projects:

    Fabric Improvement Potential Savings*

    KWHr/pa

    GBP Saving/pa

    CO2 te/pa

    Simple Payback Period

    Budget Costs for Building Fabric Improvement projects: subject to detailed

    assessment

    *This is a capital intensive project with low payback periods.It is difficult to put a Budget cost for

    this project, as a detailed study is required. This is complicated due to the fact that we have

    asbestos at site which requires removal and safe disposal.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    40/45

    HVAC Energy AuditHarlan Labs, Wyton

    40

    Enhanced Capital Allowance (ECA) and funding

    Enhanced Capital Allowances (ECAs) enable a business to claim 100% first-year capital allowances on

    their spending on qualifying plant and machinery.

    There are three schemes for ECA's

    Energy saving plant and equipment

    Low carbon dioxide emission cars and natural gas and hydrogen fuelling infrastructure

    Water conservation plant and machinery.

    Businesses can write off the whole of the capital cost of their investment in these technologies

    against their taxable profits of the period during which they make the investment. This can deliver a

    helpful cash flow boost and a shortened payback period.

    For products on the Energy Technology Product List, a claim can be made on the cost of the

    equipment itself, and other costs directly involved in installing it. These include:

    Direct Transportation the cost of getting equipment to the site.

    Direct Installation cranage (to lift heavy equipment into place), project management costs and

    labour, plus any necessary modifications to the site or existing equipment.

    Professional Fees if they are directly related to the acquisition and installation of the equipment.

    Any remote or indirect costs do not qualify for the ECA for example, staff time spent taken to

    select the right equipment. Only new equipment is eligible for an ECA used or second hand

    equipment does not qualify.

    All the plant selected falls under the Energy Technology product list, there by all the entire project

    costs could avail ECA benefit. Details of how to apply for ECA is available on the DECC website, we

    can also provide assistance towards applying for ECA benefit.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    41/45

    HVAC Energy AuditHarlan Labs, Wyton

    41

    9. Conclusions

    The report highlights the preliminary energy, operational and management issues associated withHarlan Labs, Wyton. it is advisable that a ventilation and filtration philosophy be incorporated in

    order to address business continuity risks and to meet regulatory compliance, it preferable to

    automate the Utility consumption of major ancillary loads in order to identify individual energy

    consumption patterns and thereby seek energy reduction, by various options available to the client

    which include installation of AMR (Automated Meter Reading) to capture half hourly Energy

    consumption data in order to monitor energy consumption and to gather real time energy profile

    data as part of the drive to reduce energy and running costs. A BMS system for plant automation /

    control is preferable to realise energy savings through incorporating energy optimisation schedules.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    42/45

    HVAC Energy AuditHarlan Labs, Wyton

    42

    A summary of projects identified are listed below:

    Elec

    KWHr / Yr

    Elec

    / Yr

    Fuel

    KWHr/ Yr

    Fuel

    / yr

    CAPEX

    Year Tons

    Project TitleBudget

    Costs

    Simple

    Payback

    CO2

    Saving

    Regulatory:

    AHU Ductwork cleaning (Per Bldg) -- - - 1,500.00 - -

    Validation of HVAC System- - - - 15,000.00 - -

    DEC Site wide- - - - 1200.00 - -

    Oil Tank Plinths- - - - 30,000.00 - -

    Asbestos Risk Register- - - - 30,000.00 - -

    Low Cost Projects:

    Energy Efficient Boilers for Admin

    Bldg-

    - 13,665 947.84 30,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    43/45

    HVAC Energy AuditHarlan Labs, Wyton

    43

    BMS Upgrade 25,1333,141.73 196,624 11,951.21 200,000.00 13.25 Years 64.6

    Sustainability Projects:

    Gas based Heating / Cooling -- - - - - -

    Sun Pipes / Natural Daylighting per

    Bldg7,100

    897.63 - - 60,000.00

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    44/45

    HVAC Energy AuditHarlan Labs, Wyton

    44

    10.0

    Action Plan / Way Forward

    Harlan Labs and EECO2 will develop a strategic plan to Identify and prioritise projects, confirm costbenefits, develop scope and budgets and produce an implementation plan for approval and budget

    allocation.

  • 8/12/2019 Harlan Labs Wyton HVAC Energy Audit R2

    45/45

    HVAC Energy AuditHarlan Labs, Wyton

    11. Sample FRS (Functional Requirement Specification)