![Page 1: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/1.jpg)
1 | Corporate Presentation, September 20, 2016
Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR)
QIUWEI WU/Associate ProfessorCenter for Electric Power and Energy (CEE)
Technical University of Denmark (DTU) 15th September 2016
![Page 2: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/2.jpg)
Outline• PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 3: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/3.jpg)
PowerLab Combines Experimental Facilities in a Unique Platform
Stakeholders:
Supported by:
Investment:18 million Euro
TECHNOLOGY DEVELOPMENT TESTING TRAINING DEMONSTRATION
Lyngby & Ballerup Campus Risø Campus
Flexible multi-purpose laboratories
The Island Bornholm
Large-scale test system
Full-scale real-lifeenergy system
40,000 people33% wind power50% renewable energyIslanding capability
![Page 4: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/4.jpg)
Bornholm - Full-scale Living Laboratory with 40,000 Inhabitants and 50% Renewable Energy Penetration
Bornholm
Resources:- Wind power- Biomass - Biogas- District heating- Combined heat and power- Solar power- eMobility- Active demand
Features:- Nord Pool market- Islanding capability
TECHNOLOGY DEVELOPMENT TESTING TRAINING DEMONSTRATION
![Page 5: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/5.jpg)
Intelligent Control Lab - Test-bed for Integrated Experiments
Grid in Lab
w. 22LabCells
Full-scalecontrol room
Real-time digital simulator
Power amplifier 150 kW (1.2 MW)
SCADAsystem
Models
Power hardwaretest in lab
Onlinedata
LabGrid with 21 LabCells
Onlinecontrol/
data
Online control/data
Power
Power
I/O
Blade Center(power market/controllers)
Online control/data
Real worldControl hardware
test in labI/O
![Page 6: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/6.jpg)
Outline• Intelligent control lab of PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 7: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/7.jpg)
Year 2014Danish wind power generation: 39.1% of the electricity consumption
January 2014Danish wind power generation: 63.3% of the electricity consumption
December 21th 2013Danish wind power generation: 102% of the electricity consumption
Single hour July 9th 2015Danish wind power generation: 140% of the electricity consumption
March 11th 2014only 9 MW wind power generated out of installed 4,900 MW
but 480 MW out of 580 MW solar units supplied the grid
Wind Power in Denmark
![Page 8: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/8.jpg)
0
1000
2000
3000
4000
5000
6000
7000
MW
h/h
201225% wind power
DemandWind Power
202050% wind power
DemandWind Power
Wind Power in Denmark
![Page 9: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/9.jpg)
Outline• Intelligent control lab of PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 10: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/10.jpg)
DFR Control Logic
The DFR control logic type I disconnects and reconnects electric appliances to the grid when the system frequency falls below and recovers above , respectively
offf
onf
![Page 11: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/11.jpg)
DFR Control LogicThe DFR control logic type II is customized for switching thethermostatically controlled loads by adjusting the nominaltemperature set points and .normal
lowT
0( )normalhigh highT T kf f f= + −
0( )normallow lowT T kf f f= + −
normalhighT
![Page 12: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/12.jpg)
Outline• Intelligent control lab of PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 13: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/13.jpg)
Heat Pump Model• The dynamics of a direct air heating system can be sufficiently
described by three thermal masses.• The ambient air of the building interior has smaller storage
volume, and defines a faster dynamics of the system.• the larger storage volume of the building envelope, or structure,
describes a slower dynamics of the system
( ) ( )1 1i e i a i H w s
i ie ia
IT T T T T Q AC R R
= − + − + + Φ
( ) ( )1 1e a e e e s
e ea iei
IT T T T T AC R R
= − + − + Φ
![Page 14: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/14.jpg)
Outline• Intelligent control lab of PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 15: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/15.jpg)
HIL Test
![Page 16: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/16.jpg)
HIL Test
00:00:00 00:10:00 00:20:00 00:30:0019.5
20
20.5
21
o C
On/off control
Tinside
Tstructure
00:00:00 00:10:00 00:20:00 00:30:000
5
10
kW
Pelectricity
Pheat
00:00:00 00:10:00 00:20:00 00:30:004
5
6
Time (HH:MM:SS)
o C
Toutside
![Page 17: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/17.jpg)
HIL Test
![Page 18: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/18.jpg)
HIL Test
(a)
(b)
![Page 19: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/19.jpg)
Outline• Intelligent control lab of PowerLabDK
• Wind power in Denmark
• DFR control logics
• Heat pump model
• HIL test
• Conclusions
![Page 20: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/20.jpg)
• The DFR technology has been developed to utilize the demandside resources to provide fast reserves needed in the futurerenewable based power system.
• The DFR technology has been tested by offline simulations in theprevious work.
• The real time HIL tests were conducted to verify the effectivenessof the DFR technology.
• The HIL test results show that the DFR technology cansuccessfully arrest the system frequency and illustrate the efficacyof the SmartBox.
Conclusions
![Page 21: Hardware-in-the-loop (HIL) Test of Demand as Frequency ......Hardware-in-the-loop (HIL) Test of Demand as Frequency controlled Reserve (DFR) QIUWEI WU/Associate Professor Center for](https://reader035.fdocuments.us/reader035/viewer/2022070221/6135501adfd10f4dd73c4b02/html5/thumbnails/21.jpg)
21 | Corporate Presentation, September 20, 2016
Thank you for your attention