Hardware and Engineering DV6-340- Vector Frequency Inverters · 2010. 10. 16. · 1 Contents About...
Transcript of Hardware and Engineering DV6-340- Vector Frequency Inverters · 2010. 10. 16. · 1 Contents About...
-
Hardware and Engineering
DV6-340-...Vector Frequency Inverters
01/02 AWB8230-1415GB1st published 2002, edition 01/02
© Moeller GmbH, Bonn
Authors: Holger Friedrich, Jörg RandermannEditor: Michael KämperTranslator: Dominik Kreuzer
All brand and product names are trademarks or registered trademarks of the owner concerned.
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm or any otherprocess) or processed, duplicated or distributed by means of electronic systems without written permission of Moeller GmbH, Bonn.
Subject to alterations without notice.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Moe
llerG
mbH
Safe
ty in
stru
ctio
nsWarning!Dangerous electrical voltage!
Before commencing the installation
• Disconnect the power supply of the device.
• Ensure that devices cannot be accidentally restarted.
• Verify isolation from the supply.
• Earth and short circuit.
• Cover or enclose neighbouring units that are live.
• Follow the engineering instructions (AWA) of the device concerned.
• Only suitably qualified personnel in accordance with EN 50 110-1/-2 (VDE 0105 Part 100) may work on this device/system.
• Before installation and before touching the device ensure that you are free of electrostatic charge.
• The functional earth (FE) must be connected to the protective earth (PE) or to the potential equalisation. The system installer is responsible for implementing this connection.
• Connecting cables and signal lines should be installed so that inductive or capacitive interference do not impair the automation functions.
• Install automation devices and related operating elements in such a way that they are well protected against unintentional operation.
• Suitable safety hardware and software measures should be implemented for the I/O interface so that a line or wire breakage on the signal side does not result in undefined states in the automation devices.
• Ensure a reliable electrical isolation of the low voltage for the 24 volt supply. Only use power supply units complying with IEC 60 364-4-41 (VDE 0100 Part 410) or HD 384.4.41 S2.
• Deviations of the mains voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation.
• Emergency stop devices complying with IEC/EN 60 204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause restart.
• Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings.
• Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented.
• Wherever faults in the automation system may cause damage to persons or property, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks etc.).
• According to their degree of protection frequency inverters may feature during operation live, bright metal, or possibly moving, rotating parts or hot surfaces.
• The impermissible removal of the necessary covers, improper installation or incorrect operation of motor or frequency inverter may cause the failure of the device and may lead to serious injury or damage.
• The relevant national regulations apply to all work carried on live frequency inverters.
• The electrical installation must be carried out in accordance with the relevant regulations (e. g. with regard to cable cross sections, fuses, PE).
• All work relating to transport, installation, commissioning and maintenance must only be carried out by qualified personnel. (IEC 60 364 and HD 384 and national work safety regulations).
• Installations fitted with frequency inverters must be provided with additional monitoring and protective devices in accordance with the relevant safety regulations etc. Modifications to the frequency inverters using the operating software are permitted.
IFor Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
II
• All shrouds and doors must be kept closed during operation.
• In order to reduce hazards to persons or equipment, the user must include in the machine design measures that restrict the consequences of a malfunction or failure of the drive (increased motor speed or sudden standstill of motor). These measures include:
– Other independent devices for monitoring safety-related variables (speed, travel, end positions etc.).
– Electrical or non-electrical system related measures (interlocks or mechanical interlocks).
– Live parts or cable connections of the frequency inverter must not be touched after it has been disconnected from the power supply due to the charge in capacitors. Appropriate warning signs must be provided.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
Contents
1
About this Manual 5Abbreviations and symbols 5Changes 5
1 About the DV6 frequency inverters 7System overview 7Type code 8Inspecting the package content 9Layout of the DV6 10– Features of the frequency inverters 11Selection criteria 11Intended use 12Service and guarantee 12
2 Engineering 13Performance features of the DV6 13Connecting to the mains 15– Mains configurations 15– Mains voltage, Mains frequency 15– Interaction with p.f. correction equipment 15– Fuses and cable cross-sections 15– Protection of persons and domestic animals with
residual-current protective devices 16– Mains contactor 16– Current peaks 16– Mains choke 17– Mains filters and radio interference filters 17EMC guidelines 18– EMC interference class 18
3 Installation 19Installing the DV6 19– Mounting position 19– Installation dimensions 19– Mounting the DV6 20EMC compliance 21– EMC compliant installation 21– Using the radio interference filter 22– EMC measures in the control panel 23– Earthing 24– Screening 24Electrical connection 26– Connecting the power section 28– Connecting the control signal terminals 38
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Contents 01/02 AWB8230-1415GB
2
4 Operating the DV6 45Initial startup 45LCD keypad 46Operation with LCD keypad 46– Menu overview 47– Changing display and Basic parameters 48– Changing the parameters of the extended
parameter groups 48Display after the supply voltage is applied 49Connection examples 50– Operation using an external potentiometer 50– Operation through an analog setpoint value 50– Operation with fixed frequencies 51Operational warnings 52
5 Programming the control signal terminals 53Overview 53Analog outputs – AM, AMI and FM 58– Voltage output (AM) 58– Current output (AMI) 59– Frequency output (FM) 59Analog inputs, terminals O, O2 and OI 61– Frequency setpoint definition 61– Matching of terminals O, O2 and OI 62– Analog setpoint value matching 63Programmable digital inputs 1 to 8 66– Start/stop 68– Fixed frequency selection (FF1 to FF4) 69– Bitwise fixed frequency selection (SF1 to SF7) 71– Analog input changeover (AT) 73– Second time ramp 2CH 74– Controller inhibit and coasting (free run stop – FRS) 75– External fault message (EXT) 76– Unattended start protection USP 77– Reset (RST) 78– Jog mode (JOG) 79– Change over vector parameters (CAS) 81– PTC/NTC thermistor input, terminal TH 82– Software protection (SFT) 83– Motor potentiometer functions: accelerate (UP) –
decelerate (DWN) – Reset frequency (UDC) 84– Use second and third parameter set (SET/SET3) 86– Activate DC braking DB 88– Change over current limit (OLR) 90– Heavy mains starting (CS) 91– Setpoint value through keypad (OPE) 93– Torque limitation (TL), torque selection (TRQ1 and TRQ2) 94– Three-wire control (STA – STP – F/R) 96– Activating/deactivating PID control (PID)
Resetting PID and integral component (PIDC) 97– Changeover from PI to P control (PPI) 98– Brake enable confirmation (BOK) 100
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Contents
3
Programmable digital outputs 11 to 15 101– Frequency arrival signal FA1/FA2/FA3/FA4/FA5 102– Run signal (RUN) 104– Overload signal OL, OL2 105– PID control deviation (OD) 106– Fault signal (AL) 107– Release brake (BRK) and brake fault (BER) 108– Zero frequency (ZS) 109– Torque exceeded (OTQ) 110– Torque limitation (TRQ) 111– Instant stop (IP) and undervoltage (UV) 113– Running time (RNT) and Mains On time (ONT) 114– Motor thermal overload (THM) 115– Digital fault message output 116Signalling relay terminals K11, K12, K14 117
6 Setting Parameters 119Setting the display parameters 120Basic functions 121– Input/display frequency value 121– Acceleration time 1 121– Deceleration time 1 122– Direction of rotation 122Setting the frequency and start signal parameters 123– Definition of frequency setpoint value 123– Start signal 123– Base frequency 125– Maximum end frequency 125Voltage/frequency characteristic and voltage boost 126– Boost 126– Voltage/frequency characteristics 126DC braking (DCB) 130Operating frequency range 132Acceleration pause 133PID controller 134– PID control 134– Structure and parameters of the PID controller 137– Example for setting Kp and Ti 143– Application examples 144Automatic voltage regulation (AVR) 146Energy-saving mode 147Time ramps 148Acceleration and deceleration characteristics 149Automatic restart after a fault 151Electronic motor protection 154– Tripping characteristics at increased overload protection 154– Tripping characteristic at normal overload protection 155– Tripping characteristic at adjustable overload protection 155Current limit 157Parameter protection 159Controlled deceleration 160
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Contents 01/02 AWB8230-1415GB
4
Other functions 162– Inhibit direction of rotation 162– Starting behaviour 162– Display mode 163– Pulse frequency 164– Initialization 165– Country version 165– Frequency factor for display through PNU d007 165– Inhibit of the OFF key 165– Motor restart after cancellation of the FRS signal 166– Controlling the built-in braking transistor 166– Type of motor stop 168– Fan control 168– Debug mode 168Controlling an external brake 169SLV and autotuning 171– SLV (sensorless vector control) 171– Autotuning 171PI controller 175User-defined parameters – parameter group U 176
7 Messages 177Fault messages 177– State of frequency inverter on fault message 177– Fault message display 177– Fault history register 178Other messages 180Warnings 181
8 Troubleshooting 183
Appendix 185Technical Data 185Weights and dimensions 193Cables and fuses 194Mains contactors 195Mains choke 196Radio interference filters 197Standard form for user defined parameter settings 199
Index 215
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
5
About this Manual
This manual describes the DV6 series frequency inverters.
This manual contains information you need to install, configure and operate the DV6 frequency inverters. The features, parameters and functions are described in detail, with examples for the most important applications. All information applies to the specified hardware and software versions.
Abbreviations and symbols
The following abbreviations and symbols are used in this manual:
All measurements are in millimeters unless otherwise stated.
In some of the illustrations, the enclosure of the frequency inverter and other components affecting equipment safety have been omitted for improved clarity. However, the frequency inverter must always be operated with the enclosure and all necessary compon-ents that affect equipment safety correctly fitted.
Read the manual thoroughly before you install and operate the frequency inverter. We assume that you have a good knowledge of engineering fundamentals and that you are familiar with the electrical systems and the applicable principles and are able to read, interpret and apply the information contained in technical drawings.
X Indicates instructions to be followed
To improve legibility, the title of the current section is given at the top of each left-hand page and the current subsection at the top of each right-hand page, except on the title page of each section and the blank pages at the end of each section.
Changes
EMC Electro Magnetic Compatibility
ESD Electrostatic Discharge
HF High Frequency
IGBT Insulated Gate Bipolar Transistor
PES Positive Earth connection of the cable screen
PNU Parameter Number
WE Radio-frequency interference (RFI)h Indicates useful tips and additional information
Caution!Warns of the possibility of minor material damage.
Warning!Warns of the possibility of major material damage and minor injury.
Warning!Warns of the possibility of major material damage and serious or fatal injury.
Publication date Page Keyword New Change Omitted
01/02 202 PNU A042 to A343, default setting j
203 PNU A244, value 05 j
203 PNU A344, values 02 to 05 j
203 PNU A056 to A059, default setting j
211 PNU A029 instead of A027 after PNU A028 j
212 PNU C087, gain, terminal AMI instead of AM j
212 PNU C088, default setting j
214 to 215 Parameter group H j
215 Parameter group U j
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
6
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
7
1 About the DV6 frequency inverters
System overview
Figure 1: System overview
a DEX-DEY-10 external keypadb Expansion module, for example for PROFIBUS-DP connection: DE6-NET-DPc DV6 frequency invertersd DE6-LZ... RFI filtere Mains choke f Braking resistor
a
f
e
d
c
b
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
About the DV6 frequency inverters
01/02 AWB8230-1415GB
8
Type code
Type codes and type designations of the DV6 frequency inverters:
Example:
Figure 2: Type codes of the DV6 frequency inverters
DV6-340-11K The DV6 frequency inverters
Three-phase mains supply voltage: 400 V
Assigned motor rating: 11 kW at 400 V
DV6- x x x - yyyMotor rating codeIncoming supply: EU rated voltage 400 V
Version and model number0 = basic version1 = system devices2 = voltage code suffix
Supply connection, voltage code (EU rated value)4 = 400 V (342 V – 0 % to 506 V + 0 %)
Supply connection, phase code3 = three-phase
Series designation:Drives Vector frequency inverter, generation 6
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Inspecting the package content
9
Inspecting the package content
The DV6 frequency inverter has been carefully packaged and prepared for delivery. The device may be transported only in its original packaging with a suitable transport system (see weight details). Observe the instructions and the warnings on the side of the packaging. This also applies after the device is removed from the package.
Open the packaging with suitable tools and inspect the contents immediately on delivery to ensure that they are complete and undamaged. The package should contain the following items:
• one DV6 frequency inverter,• Installation instructions, AWA8230-1938,• one CD containing:
– this manual in PDF format and copies in other languages– the parameterization software
Hardware requirements: PC with Windows 95/98/ME/2000/NT and the DEX-CBL-2M0-PC connecting cable
Figure 3: Package content
h On the nameplate attached to the frequency inverter, check to ensure that the frequency inverter is the type which you have ordered.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
About the DV6 frequency inverters
01/02 AWB8230-1415GB
10
Layout of the DV6
Figure 4: Physical features of the DV6
a Keypadb Fanc Heat sinkd Interface connector for keypade Two slots for optional modulesf RS 485 interface
g Control signal terminalsh Power terminalsi Cable entryj Screw for opening the terminal shroudk Terminal shroudl Cover
a
b
d
e
f
g
h
i
c
l
k
j
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Selection criteria
1
1Features of the frequency inverters
The DV6 frequency inverters convert the voltage and frequency of an existing three-phase supply to a DC voltage and use this voltage to generate a three-phase supply with adjustable voltage and frequency. This variable three-phase supply allows infinitlely adjustable speed control of three-phase asynchronous motors.
a Supply through an interference suppressorMains voltage VLN (EU-rated voltages):3-phase 400 V AC, 50/60 Hz
b The bridge rectifiers convert the AC voltage of the electrical supply to a DC voltage.
c The DC link contains a charging resistor, smoothing capacitor and switched-mode power supply unit. It enables coupling of the DC bus voltage and the DC current supply:DC bus voltage (VZK) = W2 x mains voltage (VLN)
d IGBT power inverter:The power inverter converts the DC voltage of the internal DC link to a variable three-phase alternating voltage with variable frequency. In conjunction with an external braking resistor, the braking transistor allows braking of motors with a high moment of inertia or during extended regenerative operation.
e Output voltage (V2), motor connection: three-phase, variable AC voltage, 0 to 100 % of the input voltage (VLN)Output frequency (f2):variable frequency, 0 to 400 HzOutput rated current (I2N):2.5 to 260 A with about 1.5 times the starting current for 60 s, with a switching frequency of 5 kHz and at an ambient temperature of 40 °CMotor connection, assigned shaft output (P2):0.75 to 132 kW at 400 V
f Programmable control section with keypad and interface
Selection criteria
Select the frequency inverter according to the rated current of the motor. The rated output current of the frequency inverter must however, be greater than or equal to the rated current of the motor.
The following drive data is assumed to be known:
• Type of motor (three-phase asynchronous motor)• Mains voltage = supply voltage of the motor (e.g. 3 ~ 400 V)• Rated motor current (guide value, dependent on the circuit type
and the supply voltage)• Load torque (quadratic, constant, with 1.5 times the starting
torque)• Ambient temperature (maximum temperature 40 °C).
The rated output current of the frequency inverter can be found in the technical data in the appendix from Page 187.
Figure 5: Function chart of the frequency inverter
a
b c d
f
e
M3 ˜
h
h If several motors are connected in parallel to the output of a frequency inverter, the motor currents are subject to vector addition, i.e. the active in-phase current and reac-tive current components are added separately. When you select a frequency inverter, make sure that it can supply the total resulting current.
h If you connect a motor to an operational frequency inverter, the motor draws a multiple of its rated current. When you select a frequency inverter, make sure that the starting current plus the sum of the currents of the running motors will not exceed the rated output current of the frequency inverter.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
About the DV6 frequency inverters
01/02 AWB8230-1415GB
12
Intended use
The DV6 frequency inverters are not domestic appliances. They are designed only for industrial use as system components.
The DV6 frequency inverters are electrical apparatus for control-ling variable speed drives with three-phase motors. They are desi-gned for installation in machines or for use in combination with other components within a machine or system.
After installation in a machine, the frequency inverters must not be taken into operation until the associated machine has been confirmed to comply with the safety requirements of Machinery Safety Directive (MSD) 89/392/EEC and meets the requirements of EN 60204. The owner/operator of the equipment is responsible for ensuring that the machine is used in compliance with the relevant EU Directives.
The CE markings on the DV6 frequency inverter confirm that, when used in a typical drive configuration, the apparatus complies with the European Low Voltage Directive (LVD) and the EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/EEC, as amended by 93/68/EEC).
In the described system configurations, DV6 frequency inverters are suitable for use in public and non-public networks. Depending on their location of use, additional, external filtering may be necessary.
Connection to IT networks (networks without a ground potential reference point) is not permitted as the devices internal filter capacitors connect the network to the ground potential (enclo-sure). On earth free networks, this can lead to dangerous situa-tions or damage the device (isolation monitoring is required).
To the output of the frequency inverter (terminals U, V, W) you may not:
• connect a voltage or capacitive loads (e.g. phase compensation capacitor),
• connect multiple frequency inverters in parallel,• make a direct connection to the input (bypass).
Observe the technical data and terminal requirements. For additi-onal information, refer to the equipment nameplate or label and the documentation.
Any other usage constitutes improper use.
Service and guarantee
In the unlikely event that you have a problem with your Moeller frequency inverter, please contact your local sales office.
Please have the following data and information about your frequency inverter to hand:
• Exact frequency inverter type designation (a nameplate)• Date of purchase• Detailed description of the problem which has occurred with the
frequency inverter
If some of the information printed on the nameplate is not legible, please state only the information which is clearly legible.
Information concerning the guarantee can be found in the Moeller General Terms and Conditions of Sale.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
3
12 Engineering
This section describes the “Performance features of the DV6“ and the requirements and directives concerning the following:
• Connecting to the mains• EMC guidelines
Performance features of the DV6
Ambient temperatures
Operation1) Ta = –10 to +40 °C at rated current Ie without derating,up to +50 °C at reduced pulse frequency of 2 kHz and output current reduced to 80 % Ie
Storage Ta = –20 to +65 °C
Transport Ta = –25 to +70 °C
Permissible environmental conditions
Resistance to vibration Impact and vibration:• DV6-340-007 to DV6-340-2K2: up to 5.9 m/s2 (0.6 g) at 10 to 55 Hz• from DV6-340-4K0: up to 2.94 m/s2 (0.3 g) at 10 to 55 Hz
Degree of pollution VDE 0110 Part 2, pollution degree 2
Packaging Dust proof packaging (DIN 4180)
Climatic conditions Class 3K3 according to EN 50178 (non-condensing, average relative humidity 20 to 90 %)
Installation altitude Up to 1000 m above sea level
Mounting position Vertically suspended
Free surrounding areas 100 mm above and below device
Electrical data
Emitted interference IEC/EN 61800-3 (EN 55011 group 1, class B)
Noise immunity IEC/EN 61800-3, industrial environment
Insulation resistance Overvoltage category III according to VDE 0110
Leakage current to PE Greater than 3.5 mA according to EN 50178
Degree of protection IP20
Protection against direct contact Finger and back-of-hand proof (VBG 4)
Protective isolation against switching circuitry
Safe isolation from the mains. Double basic isolation according to EN 50178
Protective measures Overcurrent, earth fault, overvoltage, undervoltage, overload, overtemperature, electronic motor protec-tion: I 2t monitoring and PTC input (thermistor or temperature contacts)
Open-/closed-loop control
Modulation method Pulse width modulation (PWM), V/f characteristics control (linear, quadratic)
Switching frequency 5 kHz (default), adjustable from 0.5 to 15 kHz
Torque At start 1.5 x MN for 60 s at assigned motor rating, every 600 s, 2 x MN for 0.5 s
Output frequency
Range 0.1 to 400 Hz
Frequency resolution 0.1 Hz, at digital setpoint, maximum frequency/1000 with analog setpoint value
Error limit at 25 °C g10 °C Digital setpoint definition g0.01 % of the maximum frequency
Analog setpoint definition g0.2 % of the maximum frequency
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Engineering 01/02 AWB8230-1415GB
14
Relay
Changeover contact • Contacts K11-K14– 250 V AC, 2 A (resistive load)– 250 V AC, 0.2 A (inductive load, p.f. = 0.4)– 100 V AC, minimum 10 mA– 30 V DC, 8 A (resistive load)– 30 V DC, 0.6 A (inductive load, p.f. = 0.4)– 5 V DC, minimum 100 mA
• Contacts K11-K12– 250 V AC, 1 A (resistive load)– 250 V AC, 0.2 A (inductive load, p.f. = 0.4)– 100 V AC, minimum 10 mA– 30 V DC, 1 A (resistive load)– 30 V DC, 0.2 A (inductive load, p.f. = 0.4)– 5 V DC, minimum 100 mA
Internal voltages
Control 24 V DC, maximum 30 mA
Setpoint definition 10 V DC, maximum 10 mA
Analog and digital actuation
Analog inputs • 1 input, 0 to 10 V, input impedance 10 kO• 1 input, 4 to 20 mA, load impedance 250 O• 1 input, +10 to –10 V, input impedance 10 kO
Digital inputs/outputs 8 inputs, user-configurable
5 outputs, open collector (up to 27 V DC, 50 mA), user-configurable
Analog outputs • 1 output for motor frequency or current, 10 V, up to 1.2 mA• 1 output, 0 to 10 V, up to 2 mA, user-configurable• 1 output, 4 to 20 mA, user-configurable
Keypad (built-in)
Operation 6 function keys for controlling and parameterizing the DV6
Display Four-digit, 7-segment display and ten LEDs (for status signals)
Potentiometer Setpoint definition (0 to 270°)
1) If the frequency inverter is to be installed in a control panel, enclosure or similar installation, the temperature within the enclosure or control panel is considered to be ambient temperature Ta. The use of fans should be considered to ensure that the ambient temperature remains within permissible limits.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Connecting to the mains
5
1Connecting to the mains
The DV6 frequency inverters can not be used in every network configuration without limitations (network configuration accor-ding to IEC 364-3).
Mains configurations
Networks with earthed centre point (TT/TN networks):
• DV6 frequency inverters can be used without limitations in TT and TN networks. The ratings of the DV6 frequency inverters must, however, be observed.
Networks with earthed centre point (IT networks):
• The use of DV6 frequency inverters in IT networks is only permissible to a limited extent. In this case, a suitable device (isolation monitor) to monitor earth faults and isolates the frequency inverter from the mains must be used.
Mains voltage, Mains frequency
The ratings of the DV6 frequency inverters cover European and American standard voltages:
• 400 V, 50 Hz (EU) and 460 V, 60 Hz (USA)
The permissible mains voltage range is:
• 380/480 V: 342 V – 0 % to 528 V + 0 %
The permissible frequency range is 47 Hz – 0 % to 63 Hz + 0 %.
The motor rating to mains voltage assignments are listed in the appendix, Section “Technical Data“, Page 185.
Interaction with p.f. correction equipment
The DV6 frequency inverters absorb only a small fundamental reactive power from the AC supply. A p.f. correction is therefore not necessary.
Fuses and cable cross-sections
The fuse ratings and cable cross-sections required for the network connection depend on the rating of the frequency inverter and the the drive’s operating mode.
The recommended fuses and their assignment to the DV6 frequency inverters are listed in the appendix, Section “Cables and fuses“, Page 194.
The national and regional standards (e.g. VDE 0113, EN 60204) must be observed and any required approvals (e.g. UL) at the site of installation must be fulfilled.
When the device is operated in a UL-approved system, only UL-approved fuses, fuse bases and cables must be used.
The leakage currents to ground (according to EN 50178) are greater than 3.5 mA. The PE terminal and the enclosure must be connected to the earth-current circuit.
Caution!In the event of an earth fault in an IT system, the capaci-tors of the frequency inverter which are switched to earth are subjected to a very high voltage, and safe operation of the frequency inverter is no longer guaranteed. To over-come this problem,fit additional isolating transformer to the frequency inverter’s supply and earth the trans-former’s secondary side at its centre point to form, in effect, an individual TN network for the frequency inverter.
Caution!Operation of DV6 series frequency inverters on the mains with p.f. correction equipment is only permitted when this equipment is dampened with chokes.
Caution!When selecting the cable cross-section, take the voltage drop under load conditions into account. Compliance to further standards (e.g. VDE 0113, VDE 0289) is the responsibility of the user.
Caution!The prescribed minimum cross-sections of PE conductors (EN 50178, VDE 0160) must be observed. Use a PE conductor whose cross-section is as least as large as the terminal capacity of the power terminals.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Engineering 01/02 AWB8230-1415GB
16
Protection of persons and domestic animals with residual-current protective devices
Residual-current circuit breakers (RCCBs; also called earth-leakage circuit breakers or ELCBs). Universal current sensitive RCCBs according to EN 50178 and IEC 755.
The frequency inverter has a built-in mains rectifier. When a frame fault occurs, a DC fault current can block the trip of the alternating current sensitive or pulse current sensitive residual-current circuit breaker, thereby preventing its protective function. We therefore recommend the use of:
• Universal RCCBs with a rated fault current f 300 mA.
The approximate fault current values of the DV6 frequency inver-ters and their assigned radio interference filters are listed in the appendix, Section “Radio interference filters“, Page 197.
Spurious tripping of a residual-current circuit breaker can be caused by the following:
• capacitive compensation currents in the cable screens, particu-larly with long, screened motor cables,
• simultaneous connection of multiple frequency inverters to the mains supply,
• the use of additional chokes and filters (radio interference filters, line filters).
Mains contactor
The mains contactor is connected to the mains side input cables L1, L2, L3 and allows the DV6 frequency inverter on the supplying network to be switched on and off during operation and to be disconnected in the event of a fault.
Mains contactors and their assignment to the DV6 frequency inverters are listed in the appendix, Section “Mains contactors“, Page 195.
Current peaks
In the following cases, a relatively high peak current can occur on the primary side of the frequency inverter (i.e. on the supply voltage side), which, under certain conditions, can destroy the input rectifier of the frequency inverter:
• Imbalance of the voltage supply greater than 3 %.• The maximum power output of the point of supply must be at
least 10 times greater than the maximum frequency inverter rating.
• If sudden voltage dips in the supply voltage are to be expected, e.g. :– a number of frequency inverters are operated on a common
supply voltage– a thyristor system and a frequency inverter are operated on a
common supply voltage– power factor correction devices are switched on or off
In these cases, a mains choke with about 3 % voltage drop at rated operation should be installed.
Identification on the residual-current circuit-breakers
Logo
Model
Alternating current sensitive (RCCB, Type AC)
Pulse current sensitive (RCCB, Type A)
Universal current sensitive (RCCB, Type B)
Caution!Residual-current circuit breakers must be installed only on the primary side between the incoming supply and the frequency inverter.
Warning!To prevent the risk of fire, use only cables, residual-current circuit breakers and contactors with the specified rating.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Connecting to the mains
7
1Mains choke
The mains choke (also called commutating choke or line reactor) is connected to the mains side input cables L1, L2, L3. It reduces the harmonics and therefore reduces the apparent mains current by up to 30 %.
A mains choke also limits any current peaks caused by potential dips (e.g. caused by p.f. correction equipment or earth faults) or switching operations on the mains.
The mains choke increases the lifespan of the internal DC link capacitors and therefore the lifespan of the frequency inverter. Its use is also recommended:
• with derating (temperatures above +40 °C, sites of installation more than 1000 m above sea level),
• with parallel operation of multiple frequency inverters on a single mains supply point,
• with DC link coupling of multiple frequency inverters (intercon-nected operation).
Mains chokes and their assignment to the DV6 frequency inverters are listed in the appendix, Section “Mains choke“, Page 196.
Mains filters and radio interference filters
Mains filters are a combination of mains chokes and radio interfe-rence filters in a single enclosure. They reduce the current harmo-nics and dampen high frequency radio interference levels.
Radio interference filters only dampen high frequency radio inter-ference levels.
Caution!The mains phase failure detection (PNU b006) does not operate correctly when a radio interference filter is installed.
Caution!When line filters or radio interference filters are used, the leakage current to earth increases. Observe this point when installing residual-current circuit breakers.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Engineering 01/02 AWB8230-1415GB
18
EMC guidelines
The limit values for emitted interference and immunity for variable speed drives are described in the IEC/EN 61800-3 Product Stan-dard.
If you use DV6 frequency inverters in European Union (EU) coun-tries, you must observe the EMC Directive 89/336/EEC. The follo-wing conditions must be observed to comply with this Directive:
Supply voltage (mains voltage) for the frequency inverter:
• Voltage fluctuation g10 % or less• Voltage imbalance g3 % or less• Frequency variation g4 % or less
If one of the conditions listed here cannot be fulfilled, you must install an appropriate mains choke (a Section “Mains choke“ in the appendix, Page 196).
EMC interference class
Installed according to the “EMC guidelines“ in Kapitel „Installa-tion“, Page 21 and with the use of a radio interference filter, the DV6 frequency inverters conform to the following standards:
• Emitted interference:IEC/EN 61800-3 (EN 55011 group 1, class B)
• Noise immunity:EN 61800-3, industrial environment
With frequency inverters, performance related and emitted interfe-rence increases with the pulse frequency. The frequency at which performance-related interference occurs also increases with longer motor cables. When the assigned radio interference filter is used, the EN 61800-3 standard is complied to as follows:
Noise immunityUsed with the assigned radio interference filters, the DV6 frequency inverters meet the interference immunity requirements of the EMC Product Standard IEC/EN 61800-3 for industrial envi-ronments (second environment) and for domestic use (first envi-ronment).
A “domestic environment” is defined here as a connection point (transformer feeder) to which domestic households are also connected.
For industrial systems, the EMC Directive requires electromagnetic compatibility with the environment as a whole. The Product Stan-dard regards a typical drive system as a complete unit, i.e. the combination of frequency inverter, cables and motor.
Emitted interference and radio interference suppressionUsed with the assigned radio interference filters, the DV6 frequency inverters meet the requirements of the EMC Product Standard IEC/EN 61800-3 for domestic use (first environment) and therefore also for the higher limit values of industrial environments (second environment).
To ensure compliance to the limit values, observe the following points:
• Reduction of performance related interference with line filters and/or radio interference filters including mains chokes
• Reduction of the electromagnetic emission interference by screening motor cables and signal cables
• Compliance with installation requirements (EMC-compliant installation).
Conformity
General Limited
First environment (public mains network)
Up to 10 m motor cable length at 15 kHz (maximum pulse frequency)
Up to 50 m1)
Up to 20 m motor cable lengths with a switching frequency of up to 5 kHz
Second environ-ment (industrial)
Up to 50 m Up to 50 m
1) This is a product with limited conformity as efined by IEC/EN 61800-3. This product can cause radio-frequency interference in domestic environments. In this case appropriate protection measures must be implemented by the user.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
9
13 Installation
The DV6 frequency inverters should be installed in a control panel or in a metal enclosure (e.g. IP54).
Installing the DV6
The DV6 frequency inverters must be mounted vertically on a non-flammable background.
Mounting position
Weights and dimensions of the DV6 are listed in the appendix in Section “Weights and dimensions“, Page 193.
h During installation or assembly operations on the frequency inverter, all ventilation slots and openings should be covered to ensure that no foreign bodies can enter the device.
Figure 6: Mounting position
F 30˚F 30˚
F 30˚F 30˚
Figure 7: Installation dimensions
f 1
00f
100
f 50f 50
f 1
00f
100
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
20
Mounting the DV6
Mount the DV6 frequency inverter as shown in Fig. 8 and tighten the screws to the following torque values (a Table 1):
Table 1: Tightening torques of the fixing screws
Figure 8: Mounting the DV6
1
2
3
1
2
o[mm]
Nm ft lb
6 M5 4 3.07 M6 4.9 3.610 M8 8.8 6.5
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB EMC compliance
1
2The fixing screw sizes are listed in the table below:
Table 2: Fixing screw sizes
EMC compliance
EMC compliant installation
The frequency inverters operate with fast electronic switching devices e.g. transistors (IGBT). For this reason, radio interference can occur on the frequency inverter’s output, which may effect other electronic devices in the direct vicinity, such as radio recei-vers or measurement instruments. To protect against this radio frequency interference (RFI), the devices should be screened and installed as far away as possible from the frequency inverters.
For an EMC-compliant installation, we recommend the following measures:
• Installation of the frequency inverter in a metallic, electrically conducting enclosure with a good connection to earth.
• Installation of a radio interference filter on the input of and immediately adjacent to the frequency inverter.
• Use of screened motor cables (short cable lengths).
X Earth the metallic enclosure using a cable which is as short as possible (a Fig. 9).
DV6-340-... a b
0751K52K24K05K5
130 241
11K 189 246
15K18K522K
229 376
30K 265 510
37K45K55K
300 520
75K90K
300 510
110K132K
380 760
Figure 9: DV6 and radio interference filters in an insulated metal enclosure
Z1: RFI filterG1:Frequency invertera Screened motor cable
Z1 G1
6
Uh
EM3h
E
a
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
22
Using the radio interference filter
The RFI filter should be installed immediately adjacent to the frequency inverter. The connection cable between the frequency inverter and filter should be as short as possible. If cables are longer than 30 cm, use screened cables.
The mounting surfaces for the frequency inverter and radio inter-ference filter should be as free as possible from paint and oil residue.
Up to size DV6-340-22K frequency inverters, the assigned DE6-LZ... radio interference filters (a Section “Radio interference filters“, Page 197) are mounted underneath the inverter (footprint mounting).
With the DV6-340-30K to DV6-340-132K frequency inverters, fit the radio interference filters on the side next to the device (book-type mounting). You can fit the RFI filter either to the left or the right of the frequency inverter.
Radio interference filters produce leakage currents which, in the event of a fault (phase failure, load unbalance), can be larger than the rated values. To prevent dangerous voltages, the filters must therefore be earthed before use. As the leakage currents are high-frequency interference sources, the earthing connections and cables must have a low resistance and large contact surfaces.
Figure 10: Footprint mounting
Figure 11: Book-type mounting (on right side in the example)
Figure 12: Earthing measures
Z1: RFI filterG1:Frequency inverter
M3h
E
L1L2L3
UV
W
R2S2T2
L1L2L3
L1
Z1 G1
L2L3
PE
Ee
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB EMC compliance
3
2With leakage currents f 3.5 mA, VDE 0160 and EN 60335, one of the following conditions must be fulfilled:
• the protective conductor has a cross-section f 10 mm2,• the protective conductor is monitored to ensure continuity, or• an additional protective conductor is installed.
For DV6 frequency inverters, use the assigned DV6-LZ... filters.
EMC measures in the control panel
To ensure an EMC-compliant setup, connect all metallic compon-ents of the devices and of the control cabinet with each other using a large cross-section conductor with good HF conducting properties. Do not make connections to painted surfaces (Eloxal, yellow-passivized). If there is no alternative, use contact and scraper washers to ensure contact with the base metal. Connect mounting plates to each other, and the cabinet doors with the cabinet, using contacts with large surface areas and short HF wires.
An overview or all EMC measures can be seen in the following figure.
Figure 13: EMC-compliant setup
PESPES
PES
W2 U2 V2
U1 V1 W1
PE
PE
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
24
Fit additional RFI filters or mains filters and frequency inverters as closely as possible to each other and on a single metal mounting plate.
Lay cables in the control cabinet as near as possible to the earth potential. Cables that hang freely act as antennae.
To prevent transfer of electromagnetic energy, lay interference-suppressed cables (e.g. the mains supply line before the filter) and signal lines as far away as possible (at least 10 cm) from HF-conducting cables (e.g. mains supply cable after a filter, motor power cable). This applies especially where cables are routed in parallel. Never use the same cable duct for interference-suppressed and HF cables. Where crossovers are unavoidable, cables should always cross at right angles to each other.
Never lay control or signal cables in the same duct as power cables. Analog signal cables (for measured values, setpoints and correction values) must be screened.
Earthing
Connect the base plate (mounting plate) with the protective earth using a short cable. lay all conducting components (frequency inverter, mains filter, motor filter, mains choke) with an HF wire, and the protective conductor in a star configuration from a central earthing point. This achieves the best results.
Make sure that the earthing measures have been correctly imple-mented (a Fig. 14). No other device which has to be earthed should be connected to the earthing terminal of the frequency inverter. If more than one frequency inverter is used, the earthing cables should not form a closed loop.
Screening
Unscreened cables behave like antennae, i.e. they act as transmit-ters and receivers. To ensure EMC-compliant connection, screen all interference-emitting cables (frequency inverter/motor output) and interference-sensitive cables (analog setpoint and measured value cables).
The effectiveness of the cable screen depends on a good screen connection and a low screen impedance. Use only screens with tinned or nickel-plated copper braiding, braided steel screens are unsuitable. The screen braid must have an overlap ratio of at least 85 percent and an overlap angle of 90°.
Figure 14: Star-type point-to-point earthing
e
PE
Z1G1 Gn Zn
PE
PE
M1
PE PE
M 3h
Mn
M 3h
Figure 15: Sample motor cable
a Copper screen braidb PVC outer sheathc Drain wire (copper)d PVC core insulation
3 x black, 1 x green/yellowe Textile braid and PVC inner
ba
e dc
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB EMC compliance
5
2The screened cable between frequency inverter and motor should be as short as possible. Connect the screen to earth at both ends of the cable using a connection with a large contact surface.
Lay the cables for the supply voltage separately from the signal cables and control cables.
Never unravel the screening or use pigtails to make a connection.
If contactors, maintenance switches, motor protection relays, motor chokes, filters or terminals are installed in the motor cabling, interrupt the screen near these components and connect it to the mounting plate (PES) using a connection with a large contact surface. The free, unscreened connecting cables should not be longer than about 100 mm.
Example: Maintenance switch
In an EMC-compliant control cabinet (metal-enclosed, damped to about 10 dB), the motor cables do not need to be screened provided that the frequency inverter and motor cables are spatially separated from each other and arranged in a separate partition from the other control system components. The motor cable scree-ning must then be connected with a large surface area connection at the control cabinet (PES).
The control cable and signal (analog setpoint and measured value) cable screens must be connected only at one cable end. The screen connection must have a large contact surface a low impedance. Digital signal cable screens must be connected at both cable ends, also with large-surface, low-resistance connections.
Figure 16: Inadmissible screen grounding (pigtails)
Figure 17: Maintenance switch, e.g. T… in an enclosure
a Metal plateb Insulated PE terminal
PES
PES
a
b
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
26
Electrical connection
This section describes how to connect the motor and the supply voltage to the power terminals, and the signal cables to the control terminals and the signalling relay.
The following illustration shows an overview of the connections.
Warning!Carry out the wiring work only after the frequency inverter has been correctly mounted and secured. Otherwise, there is a danger of electrical shock or injury.
Warning!Carry out wiring work only under zero voltage conditions.
Warning!Use only cables, residual-current circuit breakers and contactors with a suitable rating. Otherwise there is a danger of fire.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
7
2Figure 18: Power connection
a Network configuration, mains voltage, mains frequencyInteraction with p.f. correction systems
b Fuses and cable cross-sectionsc Protection of persons and domestic animals with residual-current circuit
breakersd Mains contactore Mains choke, radio interference filter, line filterf Mounting, installation
Power connectionEMC measuresExample of circuits
g Motor filterdu/dt filterSinusoidal filter
h Motor cables, cable lengthi Motor connection
Parallel operation of multiple motors on a single frequency inverterj Braking resistors, braking units
DC link couplingDC supply
c
b
a
L13 h 400 V, 50/60 Hz
L2L3PE
e
d
g
j
i
h
f
FI
T1 T2 PE L1 L2
PE U V W CM1 TH
L3 PE
2 DC+ BR
K14 K12 K11
1
DE4-BR1...
M3 i˜
i
PES PES PES
PES
#
I > I > I >
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
28
Connecting the power section
To connect the supply voltage, the motor cables and the signal relay terminals, open the front cover.
Opening the terminal shroudX Loosen the screw.
h Complete the following steps with the specified tools and without the use of force.
Figure 19: Loosening the screw
1
1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
9
2X Pull the terminal shroud upwards to remove it.
Power terminal arrangement
Table 3: Description of the power terminals
Figure 20: View of the power and control signal terminals
a Power terminalsb Control signal terminals
Terminal designation
Function Description
L1, L2, L3 Supply voltage (mains voltage)
Three-phase mains voltage: Connection to L1, L2, L3
U, V, W Frequency inverter output
Connection of a three-phase motor
L+, DC+ External DC choke Normally, the terminals L+ and DC+ are fitted with a jumper. If a DC link choke is used, remove this jumper.
DC+, DC– DC link These terminals are used for connecting an optional braking resistor and for DC linking and supplying DC power to multiple frequency inverters.
BR, DC+ External braking resis-tance
These terminals are used for connecting an optional external braking resistor.
R0, T0 Control electronics supply voltage
The voltage supply for the control electronics is provided internally through connector J51 by tapping off L1 and L3. The control electronics can also be supplied externally.
e, PE Earthing Enclosure earthing (prevents dangerous voltages on the enclosure in the event of a malfunction)
L3L2L1 U V W
M3 h
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
30
The arrangement of the power terminals is shown in the figure below.
Table 4: Arrangement of the power terminals
DV6-340-075toDV6-340-5K5
DV6-340-7K5DV6-340-11K
DV6-340-15KtoDV6-340-55K
DV6-340-75KtoDV6-340-132K
a Internal connection. Remove if a DC link choke is used.
L+ DC+ BR PE PEDC–
L2 L3L1T0R0
U V W
a
e e
L+ DC+ BR PE PEDC–
L2 L3L1T0R0
U V W
a
e e
L+L3L2L1 DC+ U V W PEDC–
T0R0
a
PEe e
L+L3L2L1 DC+ U V W
PE
DC–
T0R0
aPEe e
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
1
3Power terminal connection
Laying the cablesLay the cables for the power section separately from the signal cables and control cables.
The connected motor cables must be screened. The maximum cable length must not exceed 50 m. With larger cable lengths, a motor choke is required for du/dt limitation
If the cable leading from the frequency inverter to the motor is longer than about 10 m, the fitted thermal overload relays (bime-tallic relays) may malfunction due to high frequency harmonics. Install a motor filter on the output of the frequency inverter in this case.
Tightening torques and conductor cross-sections
X Tighten the cable connections according to Table 5.
Warning!Select a frequency inverter according to the available supply voltage (a Section “Appendix“, Page 185):
• DV6: Three-phase 400 V (342 to 528 V g 0 %)
Warning!Never connect mains voltage to the output terminals U, V and W. Danger of electrical shock or fire.
Warning!Each phase of the supply voltage for the frequency inverter must be protected with a fuse (danger of fire).
Warning!Make sure that all power cables are correctly tightened in the power section.
Warning!The frequency inverter must be earthed. Danger of elec-trical shock or fire.
Warning!To prevent inadvertent loosening, tighten the screws on the terminals sufficiently (a Table 5).
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
32
Table 5: Tightening torques and conductor cross-sections for the power terminals
Connecting the supply voltageX Connect the supply voltage to the power terminals L1, L2, L3
and PE:
Connecting external supply voltage for the control electronics
If you also want to program the DV6 frequency inverter with the power supply switched off, connect an external power supply (L1 and L3) to terminals R0 and T0. Tis is done as follows:
L1, L2, L3L+, DC+, DC–, BRU, V, W, PE
DV6-340- mm2 AWG mm O Nm Nm
075 1.5 20 < 13 M4 4.5 1.5 1 –
1K5 2.5 18
2K2 16
4K0 14
5K5 M5 5.5 2.5
7K5 4 10 < 17
11K 6 8 M6 6.5 4.9
15K 10 6
18K5 16 6 < 18
22K 4
30K 25 3 < 23
37K 35 1
45K M8 8.5 – – 8.8
55K 2 x 35 1/0
75K 2 x 1 (75 °C) < 29
90K 2 x 50 M10 10.5 13.7
110K 2 x 70 2 x 1/0 < 40
132K 2 x 2/0
w
wo
Figure 21: Cable connection to the power terminals
PES
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
3
3X Remove the screws on terminals R0 and T0 and remove connector J51.
X Remove the ferrite rings from both cables.
X Push the ferrite rings onto both of the external supply voltage cables (L1 and L3).
X Screw on the cables of the external voltage supply to the termi-nals R0 and T0.
R0, T0
mm2 AWG mm Nm
DV6-340-... 1.5 to 2.5 16 to 14 8 to 10 9 M4 1.2 to 1.38 1
w
Figure 22: Remove the connection of J51 to R0 and T0
Figure 23: Remove the ferrite rings
R0 T0
J51
Figure 24: Push on the ferrite rings
Figure 25: Connecting the external supply voltage
R0 T0
J51
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
34
Connecting the motor cableX Connect the motor cable to the U, V, W and PE terminals:
The stator winding of the motor can be connected in a star or delta configuration in accordance with the rating data on the name-plate.
Figure 26: Power terminal connection
F1, Q1: Line protectionK1M: Mains contactorL1: Mains chokeZ1: RFI filter
PE
DV6-340
L1 L2 L3
L1L2L3PE
K1MQ1
F1
L1 L2 L3
L1 L2 L3
L1
Z1
J51
PE
PE
R0 T0
DC+ DC–L+ U V W PEBR
PES
PES
PES
PES
MM1
X1
3 ~
I II
Q1/F1
3 51
3 51
4 62
4 62
G1
h Observe the electrical connection data (rating data) on the rating label (nameplate) of the motor.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
5
3If you use a motor filter or a sinusoidal filter here, the rate of voltage rise can be limited to values of about 500 V/ms (DIN VDE 0530, IEC 2566).
By default, the DV6 frequency inverters have a clockwise rotation field. Clockwise rotation of the motor shaft is achieved by connec-ting the motor and frequency inverter terminals as follows:
With the DV6, the direction of rotation of the motor shaft can be reversed by:
• swapping two of the phase connections on the motor• actuating terminal FW (clockwise) or 8
(default: REV = anticlockwise)• applying a control command through the interface or fieldbus
interface connection
The speed of a three-phase motor is determined by the number of pole pairs and the frequency. The output frequency of the DV6 frequency inverter is indefinitely variable from 0.1 to 400 Hz.
Pole-changing three-phase motors (Dahlander pole-changing motors), rotor-fed three-phase commutator shunt motors (slipring rotor) or reluctance motors, synchronous motors and servo motors can be connected, provided they are approved for use with frequency inverters by the motor manufacturer.
Figure 27: Connection types
Figure 28: Example in motor star circuit
Figure 29: Example in motor delta circuit
Warning!If motors are used whose insulation is not suitable for operation with frequency inverters, the motor may be destroyed.
Motor DV6
U1V1W1
UVW
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2
/ 400 V230 38 / 22 A11S1 0.67ϕcoskW
rpm1410 50 Hz
U1 V1 W1
W2 U2 V2
/ 690 V400 22 / 13 A11S1 0.67ϕcoskW
rpm1410 50 Hz
Figure 30: Direction of rotation, change of direction
Warning!The operation of a motor at speeds above its rated speed (indicated on nameplate) can cause mechanical damage to the motor (bearings, unbalance) and the machinery to which it is connected and can lead to dangerous opera-ting conditions!
Caution!Uninterrupted operation in the lower frequency range (less than about 25 Hz) can lead to thermal damage (over-heating) of self-ventilated motors. Possible counterme-asures include over-dimensioning or external cooling independent of motor speed.
Observe the manufacturers recommendations for opera-ting the motor.
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2
FWD REV
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
36
Parallel connection of motors to a single frequency inverterDV6 frequency inverters can control several parallel-connected motors. If the motors are to run at different speeds, this must be implemented through the number of connected pole pairs and/or the gear transmission ratio.
Connecting motors inparallel reduces the load resistance at the frequency inverter output, reduces the total stator inductivity is and increases the leakage capacitance. As a result, the current distortion is larger than it is in a single-motor circuit. To reduce the current distortion, chokes or sinusoidal filters can be connected at the frequency inverter output.
If motors with widely differing ratings (for example 0.75 kW and 4.0 kW) are connected in parallel to the output of a frequency inverter, problems may arise during starting and at low speeds. Motors with a low rating may be unable to develop the required torque. This is due to the relatively high ohmic resistances of their stators. They require a higher voltage during the start phase and at low speeds.
Motor cableTo ensure electromagnetic compatibility, use only screened motor cables. The length of the motor cable and the associated use of further components has an influence on the motor control mode and the performance characteristics. In parallel operation (multiple motors connected to the frequency inverter output), the resulting cable lengths lres must be calculated:
lres = SlM x WnM
SlM: Sum of all motor cable lengthsnM: Number of motor circuits
Keep the motor cables as short as possible as it will positively influ-ence the drive’s characteristics.
Figure 31: Parallel connection of multiple motors
K1M
F1
M1
U1 V1 W1
K2M
F2
M2
U1 V1 W1
K3M
F3
M3
U1 V1 W1
M3 ˜
M3 ˜
M3 ˜
Caution!If a frequency inverter controls a number of motors in parallel, the contactors for the individual motors must be designed for AC-3 operation. Do not use the mains contactors listed in table in the appendix (Section “Mains contactors“, Page 195). These mains contactors are desi-gned only for the mains (primary) currents of the frequency inverter. If they are used in multiple-motor circuits, their contacts may weld.
h The current consumption of all connected motors must not exceed the rated output current I2N of the frequency inverter.
h Electronic motor protection can not be used when opera-ting the frequency inverter with a several connected motors. You must however, protect each motor with ther-mistors and/or overload relays.
h With long motor cables, the leakage currents caused by parasitic cable capacities can cause the “earth fault” message. In this case, motor filters must be used.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
7
3Motor choke, du/dt filters, sinusoidal filtersMotor chokes compensate for capacitive currents with long motor cables and with grouped drives (multiple connection of parallel drives to a single inverter).
The use of motor chokes is recommended (observe the manufac-turers instructions):
• for grouped drives• for the operation of three-phase current asynchronous motors
with maximum frequencies greater than 200 Hz,• for the operation of reluctance motors or permanently excited
synchronous motors with maximum frequencies above 120 Hz.
du/dt filters are used for limiting the rate of voltage rise at the motor terminals to values below 500 V/ms. They should be applied for all motors with unknown or insufficient insulation withstand voltage.
When sinusoidal filters are used, the motor supply voltage and current are almost sinusoidal.
Bypass operationIf you want to have the option of operating the motor with the frequency inverter or directly from the mains supply, the incoming supplies must be mechanically interlocked:
Caution!During the engineering phase, keep in mind that the voltage drop across motor filters and du/dt filters can be up to 4 % of the frequency inverter’s output voltage.
Caution!During the engineering phase, keep in mind that the sinu-soidal filter must be matched to the output voltage and to the frequency inverter’s pulse frequency.
The voltage drop on the sinusoidal filter can be up to 15 % of the frequency inverter’s output voltage.
Caution!A changeover between the frequency inverter and the mains supply must take place in a voltage-free state.
Warning!The frequency inverter outputs (U, V, W) must not be connected to the mains voltage (destruction of the device, risk of fire).
Figure 32: Bypass motor control
Q1
I> I> I>
K1M
S1
M1
G1
M 3h
L1 L2 L3
L1 L2 L3
U V W
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
38
Connecting the control signal terminals
The figure below shows the arrangement of the individual control signal terminals.
Figure 33: Location of the control signal terminals
a Control signal terminals
a
h O2 AM FM TH FW 8 CM1 5 3 1 14 13 11 K14L O OI AMI P24 PLC CM1 7 6 4 2 15 CM2 12 K11 K12
ESD measuresDischarge yourself on an earthed surface before touching the frequency inverter and its accessories.This prevents damage to the devices through electrostatic discharge.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
9
3Function of the control signal terminals
Table 6: Meaning of the control signal terminals
No. Function Level WE Technical data, description
Supply voltages
h Setpoint voltage output +10 V H – Supply voltage for external setpoint potentiometer.Load carrying capacity: 20 mAReference potential: Terminal L
P24 Control voltage output +24 V H – Supply voltage for actuation of digital inputs 1 to 8 and FW.Load carrying capacity: 100 mAReference potential: Terminal CM1
Reference potentials
CM1 Reference potential 0 V – Reference potential terminals 1 to 8, FM, FW, TH and P24
CM2 External control voltage input
Up to 27 V – Connection: reference potential (0 V) of the external voltage source for the transistor outputs, terminals 11 to 15.Load carrying capacity: Up to 250 mA (sum of terminals 11 to 15)
L Reference potential 0 V – Reference potential, terminals AM, AMI, H, O, OI and O2
PLC Common connection, terminals 1 to 8 and FW
By default, the frequency inverters are supplied with a link between PLC and CM1, so that the potential on terminal PLC – and therefore on the digital inputs that are not energized – is 0 V (negative logic). If PLC is applied to P24, the control logic is positive.
Digital inputs
1 Digital input HIGH = +12 to +27 VLOW = 0 to +3 V
RST = reset PNP logic, configurable, Ri = 4.7 kO Reference potential: Terminal CM12 AT = analog input changeover
3 JOG = jog mode
4 FRS = controller inhibit
5 2CH = second parameter set
6 FF2 = fixed frequency 2
7 FF1 = fixed frequency 1
8 REV = anticlockwise operation
FW Digital input, clockwise operation
– Ri = 4.7 kO Reference potential: Terminal CM1
Analog inputs
O Analog input 0 to +10 V H Frequency setpoint value (0 to 50 Hz)
Ri = 10 kOReference potential: Terminal L
OI Analog input 4 to 20 mA Frequency setpoint value (0 to 50 Hz)
RB = 250 OReference potential: Terminal L
O2 Analog input frequency setpoint
–10 V to +10 V H – Resolution: 12 bitInput impedance: 10 kOReference potential: Terminal L
TH Thermistor input – Minimum thermistor rating: 100 mWReference potential: Terminal CM1
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
40
Control signal terminal wiringWire the control signal terminals as appropriate for their applica-tion. For instructions for changing the function of the control signal terminals, a Kapitel „Programming the control signal terminals“, Page 53.
Use twisted or screened cables for connecting to the control signal terminals. Earth the screen on one side with a large contact area connection near the frequency inverter. The cable length should not exceed 20 m. For longer cables, use a suitable signal amplifier.
Digital outputs
11 Transistor output Up to 27 V = CM2 Frequency setpoint reached Configurable, open collectorLoad carrying capacity: Up to 50 mA12 RUN (operation)
13 Overload alarm
14 Torque exceeded
15 Intermittent mains failure
Relay output
K11 Programmable relay output
AL = fault message Default settings:• Operating signal: K11-K14 closed.• Fault message or power supply off: K11-K12
closedCharacteristics of the relay contacts:• K11-K14
– Maximum 250 V AC/2 A (resistive) or 0.2 A (inductive, p.f. = 0.4); minimum 100 V AC/10 mA
– Maximum 30 V DC/8 A (resistive) or 0.6 A (inductive, p.f. = 0.4); minimum 5 V DC/100 mA
• K11-K12– Maximum 250 V AC/1 A (resistive) or
0.2 A (inductive, p.f. = 0.4); minimum 100 V AC/10 mA
– Maximum 30 V DC/1 A (resistive) or 0.6 A (inductive, p.f. = 0.4); minimum 5 V DC/100 mA
K12
K14
Analog outputs
AM Voltage output 0 to +10 V H Frequency actual value Resolution: 8 bitLoad carrying capacity: 2 mAReference potential: Terminal L
AMI Current output 4 to 20 mA Resolution: 8 bitRB F 250 OReference potential: Terminal L
FM Frequency output 0 to +10 V H Frequency actual value (0 to 50 Hz)
Configurable, monitored DC voltage; 10 V corres-ponds to set final frequency (50 Hz).Accuracy: g5 % from final valueLoad carrying capacity: 1.2 mAReference potential: Terminal CM1
No. Function Level WE Technical data, description
K12K11 K14
Caution!Never connect terminal P24 with terminals L, H, OI or FM.
Caution!Never connect terminal H with terminal L.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
1
4Actuating the digital inputsThe DV6 has eight digital inputs, which are connected internally with terminal PLC. By default, power is supplied through the internal 24 V supply. For this purpose, terminals PLC and CM1 are connected with a jumper. If the digital inputs are to be supplied from an external source, remove this jumper.
The digital inputs can be operated both with positive (default setting) and with negative logic. To set it to negative logic, remove the jumper between terminals PLC and CM1 and connect termi-nals PLC and P24 with this jumper. If you are using an external power supply, you can connect the negative pole (positive logic) or the positive pole (negative logic) with terminal PLC.
The figure below shows a sample protective circuit for the control signal terminals
Actuating the digital inputs with internal supply voltage and posi-tive logic (default)
Actuating the digital inputs with internal supply voltage and negative logic
Actuating the digital inputs with external supply voltage and positive logic
Actuating the digital inputs with external supply voltage and negative logic
87654321CM1PLCP24
87654321CM1PLCP24
87654321CM1PLCP24
+–
87654321CM1PLCP24
+–
Figure 34: Control terminal connection (factory setting)
8 FW P24H O L
ZB4-102-KS1
15
M4
PE
2Cu 2.5 mmPES
PES
1 2
3
M
R1 REV FWD
4K7M
F 2
0 m
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
42
If a relay is connected to one of the digital outputs 11 to 15 or 12, connect a free-wheel diode in parallel to the relay to prevent destruction of the digital outputs through the self-induced e.m.f. which results when the relay is switched off.
Figure 35: Relay with free-wheel diode
h Use relays that switch reliably at 24 V H and a current of about 3 mA.
h Route the control and signal cables separately from the mains and motor cables.
+ 24 V250 mA
CM2 1211 15
Figure 36: Crossover of signal and power cables
a Power cable: L1, L2, L3, U, V, W, L+, DC+, DC–, R0, T0b Signal cables: H, O, OI, O2, L, FM, AM, AMI,1 to 8, 11 to 15, CM1,
CM2, P24, TH, K11, K12, K14
f 100
b a
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Electrical connection
3
4Example for the protective circuit of the digital inputs using the internal P24 supply voltage or a separate external 24 V power supply:
Figure 37: Actuating the digital inputs
5
6
7
8
4
3
2
1
Q..
Q..
Q..
Q..
FWQ..
Q..
Q..
Q..
Q..
0 V L
P24 +24 V+24 V
24 V
DV6PLC
5
4
3
2
1
Q..
6Q..
7Q..
8Q..
FWQ..
Q..
Q..
Q..
Q..
0 V L
+24 V
+24 V24 V
DV6
PLC
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Installation 01/02 AWB8230-1415GB
44
Having made all cable connections, refit the terminal shroud on the frequency inverter and tighten the screw.
Figure 38: Close the terminal shroud
PESPEPES e
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB
5
44 Operating the DV6
This section describes how to take the DV6 frequency inverter into operation and what you should observe during its operation.
Initial startup
Observe the following points before you take the frequency inverter into operation:
• Make sure that the power lines L1, L2 and L3 and the frequency inverter outputs U, V and W are connected correctly.
• The control lines must be connected correctly.• The earth terminal must be connected correctly.• Only the terminals marked as earthing terminals must be
earthed.• The frequency inverter must be installed vertically on a non-
flammable surface (e.g. a metal surface).• Remove any residue from wiring operations – such as pieces of
wire – and all tools from the vicinity of the frequency inverter.• Make sure that the cables connected to the output terminals are
not short-circuited or connected to earth.• Ensure that all terminal screws have been sufficiently tightened.• Make sure that the frequency inverter and the motor are correct
for the mains voltage.• The configured maximum frequency must match the maximum
operating frequency of the connected motor.• Never operate the frequency inverter with opened power
section covers.
The control signal terminals are wired as follows.
X Switch on the supply voltage.
The POWER and Hz LEDs light up (keypad). The display should indicate 0.0.0.
X Close switch S1 (FW = clockwise operation).X With potentiometer R1, you can set the frequency and therefore
the motor speed.
The motor turns clockwise and the display indicates the set frequency.
X Open switch S1.
The motor speed is reduced to zero (display: 0.00).
X Close switch S2 (REV = anticlockwise operation).X With potentiometer R1, you can set the frequency and therefore
the motor speed.
The motor turns anticlockwise and the display indicates the set frequency.
X Open switch S2.
The motor speed is reduced to zero (display: 0.00).
If both switches S1 and S2 are closed, the motor will not start. If you close both switches during operation, the motor speed is reduced to zero.
If a fault has occurred due to overcurrent or overvoltage, increase the acceleration or deceleration time (a Section “Acceleration time 1“, Page 121 and Section “Deceleration time 1“, Page 122).
By default, the ON key and the potentiometer on the keypad (a Fig. 40 and a Table 7) have no assigned function. For details about activating these devices, a Section “Setting the frequency and start signal parameters“, Page 123.
Caution!Do not carry out h.v. tests. Built-in overvoltage filters are fitted between the mains voltage terminals and earth, which could be destroyed.
h Sparkover voltage and insulation resistance tests (megger tests) have been carried out by the manufacturer.
Figure 39: Connecting the control signal terminals (default settings)
8L
S2
4K7M
REVR1
S1
OH
F 2
0 m
FW P24
PES
M
FWD
Caution!During or after intitial operation, check the following points to prevent damage to the motor:
• Was the direction of rotation correct?• Has a fault occurred during acceleration or decelera-
tion?• Was the frequency displayed correctly?• Did any unusual motor noise or vibration occur?
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Operating the DV6 01/02 AWB8230-1415GB
46
LCD keypad
The following illustration shows the LCD keypad of the DV6.
Table 7: Explanation of the operating and indication elements
Operation with LCD keypad
The functions of the DV6 are organized in parameter groups. The following sections describe how to set the parameter values and how the setting menu is structured.
For a detailed description of the parameters, a Kapitel „Setting Parameters“, Page 119.
Figure 40: Keypad view
For an explanation of each of the elements, a Table 7.
a b c
d
e
f
g
h
i
jkl
m
n
o
RUN
PRG
ALARMPOWER
HzVA%
kW
MIN MAX
PRG ENTER
Number Name Explanation
a RUN LED LED lights up in RUN mode if the frequency inverter is ready for operation or operational.
b 7 segment display
Display for frequency, motor current, fault messages, etc.
c POWER LED LED is lit when the frequency inverter has power.
d LED Alarm LED is lit when a fault has occurred.
e LED Hz Indication in b: Output frequency (Hz)
f, g LED V, A, kW Indication in b: Either output voltage (V) or output current (A) or a combined current and voltage factor (kW)
h LED % Indication in b: Torque in %
i Potentio-meter and LED
Frequency setpoint settingLED is lit when the potentiometer is activated.
j ENTER key This key is used for saving entered or changed parameters.
k Arrow keys Selecting functions, changing numeric values
Increase
Reduce
l PRG key Selecting and exiting the programming mode.
m OFF key Stop the running motor and acknow-ledge a fault message. Active by default, also when actuation is through terminals.
n On key and LED
Starts the motor in the specified direc-tion (not active by default).
o PRG LED LED is lit during parameterization.
ENTER
PRG
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Operation with LCD keypad
7
4Menu overview
The following figure shows the sequence in which the parameters appear on the display. Table 8 provides a brief description of the parameters.
Table 8: Explanation of the parameters
For a detailed description of the parameters, a Kapitel „Setting Parameters“, Page 119.
Figure 41: DV6 keypad menu structure
a The contents of this display depends on which display parameter (PNU d001 to d090) you have selected.
a
PRG
PRG
PRG
PRG
Display Explanation
Display parameter
d001 Output frequency display
d002 Output current display
d003 Direction of rotation display
d004 PID feedback display
d005 Digital inputs 1 to 8 status
d006 Status of digital outputs 11 to 15
d007 Scaled output frequency
d012 Motor torque
d013 Output voltage
d014 Electrical input power
d016 Running time
d017 Mains On time
d080 Total fault count
d081 First (most recent) fault
d082 Second fault
d083 Third fault
d084 Fourth fault
d085 Fifth fault
d086 Sixth fault
d090 Warning
Basic parameters
F001 Frequency setpoint adjustment
F002 Set acceleration time 1
F202 Set acceleration time 1 (second parameter set)
F302 Set acceleration time 1 (third parameter set)
F003 Set deceleration time 1
F203 Set deceleration time 1 (second parameter set)
F303 Set deceleration time 1 (third parameter set)
F004 Direction of rotation adjustment
Extended para-meter groups
A--- Extended functions group A
b--- Extended functions, group B
C--- Extended functions, group C
H--- Extended functions, group H
P--- Extended functions group P
U--- Extended functions group U
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Operating the DV6 01/02 AWB8230-1415GB
48
Changing display and Basic parameters
Press the PRG key to switch from display or RUN mode to programming mode. The PRG lamp lights up in this mode.
You can access the individual parameters or parameter groups with the UP and DOWN arrow keys (a Fig. 41).
To access the programming mode, press the PRG key. You can modify the parameter values with the arrow keys.Exceptions are the display parameters PNU d001 to d090. These parameters have no values. After you have selected a display para-meter with the arrow keys, you can return to the display mode with the PRG key. The display then shows the selected display para-meter (a Section “Setting the display parameters“, Page 120).
Parameter values can be accepted with the ENTER key or rejected with the PRG key.
To return to the display mode, press the PRG key in the display parameter range PNU d001 to d090.
Example for changing acceleration time 1: PNU F002The frequency inverter is in display mode and the RUN lamp is lit.
X Press the PRG key.
The frequency inverter changes to the programming mode, the PRG lamp lights up and d001 or the most recently modified para-meter appears on the display.
X Press the DOWN key until F002 appears on the display.X Press the PRG key.
The set acceleration time 1 in seconds appears on the display (default value: 30.00).
X To change the set value, use the UP and DOWN arrow keys.
There are now two possibilities:
X Accept the displayed value by pressing the ENTER key.X Reject the displayed value by pressing the PRG key.
The display shows F002.
X Press the UP key until d001 appears.X Press the PRG key.
The frequency inverter changes to the display mode and displays the set frequency.
Changing the parameters of the extended parameter groups
The following example illustrates how to change PNU A03 of the extended parameter group A. You can also change the parameter values of groups B, C, H, P and U as described in the example. For a detailed description of the extended parameter groups, see from Section “Setting the frequency and start signal parameters“, Page 123.
Example for changing the base frequency PNU A003X Press the PRG key to change to the programing mode.
The most recently modified parameter appears on the display and the PRG lamp lights up.
X Press the UP or DOWN key until the extended parameter group A--- appears on the display.
X Press the PRG key.
A001 appears on the display.
X Press the UP key twice until A003 appears on the display.X Press the PRG key.
The display shows the value entered under PNU A003 (default: 50.).
X To change the value, use the UP and DOWN arrow keys.
There are now two possibilities:
X Accept the displayed value by pressing the ENTER key.X Reject the displayed value by pressing the PRG key.
Figure 42: Change acceleration time 1
a Display dependent on the selected display parameter PNU d001 to d090
b Display of the most recently changed parameter
a
b
F02 = 29.99
F02 = 30.00
PRG PRG
PRG
PRG
ENTER
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
01/02 AWB8230-1415GB Display after the supply voltage is applied
9
4The display shows A003.
X Press the PRG key.
The display shows A---.
X Press the UP key until d001 appears.X Press the PRG key.
The frequency inverter changes to the display mode and displays the current frequency.
Display after the supply voltage is applied
After the supply voltage is switched on, the last screen which was visible before switch off will reappear (but not within the extended parameter groups).
Figure 43: Change the base frequency (example with default setting)
a Display dependent on the selected display parameter PNU d001 to d090b Display of the most recently changed parameter
a
b
A03 = 49.
A03 = 50.
PRG PRG
PRG
PRG
PRG
PRG
ENTER
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
-
Operating the DV6 01/02 AWB8230-1415GB
50
Connection examples
Operation using an external potentiometer
Configuration of the parameters
Method of operation You can start the frequency inverter in a clockwise direction with terminal FW and in an anticlockwise direction with terminal 8. If both terminals are closed simultaneously, a stop signal is issued.
With the externally connected potentiometer, the required frequency setpoint (voltage setpoint) can be defined.
You can use the measuring instrument to display the frequency (PNU C023 = 00) or the motor current (PNU C023 = 01). With PNU b081, you can match analog output FM to the measuring instrument’s measuring range (indication: frequency or current).
Operation through an analog setpoint value
Configuration of the parameters
Method of operationInputs FW and 8 function exactly as described in the previous example.
With digital input 3 (configured as AT), you can change over from a voltage setpoint value (0 to 10 V) to a current setpoint value (4 to 20 mA).
Instead of a fixed or switched connection on terminal 3, you can set PNU C013 to 01. Dig