Intertenancy Boundary Aged CareZeroLot
IMPORTANT NOTES1. This design guide must be read in conjunction with the relevant and current James Hardie product install guides and relevant building code and regulations
2. The specifier or other responsible party for a project must ensure the information in this guide is appropriate for the application you are planning and that you undertake specific design and detailing for areas which fall outside the scope of these specifications.
3. Failure to install, finish or maintain these products in accordance with applicable building codes, regulations, standards and James Hardie’s written application instructions may lead to personal injury, affect system performance, violate local building codes, and void James Hardie’s product warranty.
4. HardieFire™ Insulation must be used as the frame cavity infill and must be compressed 5mm at a minimum in both vertical and horizontal directions (I.e. Batt size must be at a minimum 5mm wider and longer than frame stud bay). Ensure there are no gaps in the installation; please refer to design considerations section.
5. Make sure your information is up to date. When specifying or installing James Hardie® products, ensure you have the current manual or guide. If in doubt, or you need more information, visit www.jameshardie.com.au or Ask James Hardie® on 13 11 03.
SYSTEM INFORMATION
HARDIESMART™ INTERTENANCY WALL SYSTEM
FRL (minutes) Timber Stud Size (mm) Maximum stud spacing (mm)#
Min. Wall thickness (mm)
Max. Stud height (mm)*
Acoustic performance Rw (Rw+Ctr)
Thermal Performance (R-value)+
Bracing Performance (kN/m)^Depth Width
60/60/60 -/60/60
90 35^^ 450~ 223 3,000 60 (51)** 5.5 4.0 –10.0
90 45 600 3,300
TABLE NOTES:
* For increased heights, stud size may need to be increased. Where the height of an external wall exceeds 3.3m, the stud size must be increased to meet fire resistance requirements
# Stud spacing is based on a load bearing capacity of 5 kN/stud. The stud spacing may be reduced in accordance to wind pressure installation requirements for the selected external cladding product, please refer to the relevant and respective literature for more information. The loadbearing capacities of the timber-framed walls must be determined in accordance with AS1684 ‘Residential timber-framed construction’ and AS1720.1 ‘Timber structures’
† Thermal value is based on using a single reflective vapour permeable membrane (e.g. HardieWrap™ weather barrier) with an emissivity of 0.16. The total R-values for common systems are in accordance with AS4859.1:2002 and Amendment 1:2006 Materials for Thermal Insulation of Buildings. Note that the R-value will be reduced in cavities that are ventilated.
^ Additional fastener and design considerations may be required. Refer to James Hardie Structural Bracing Application guide for more information.~ Stud spacing may be increased to 600mm centres with a reduced loadbearing capacity of 3.4 kN/stud. Please note that if specifying 600mm centres, cutting of
HardieFire™ Insulation will be required as sizes have been optimised for 45mm studs at 600mm and 35mm studs at 450mm centres. It is recommended to install 560mm batts horizontally to minimise cutting. Ensure a 5mm compression throughout and no gaps.
^^ A larger minimum timber stud size may be required, Please refer to framing section under design considerations.** When an acoustic rating of Rw+Ctr of 46 or less is required, 6mm Villaboard® lining may be used in lieu of 9mm Villaboard® lining.
HARDIESMART™ INTERTENANCY WALL SYSTEM
Design GuideAustralia | December 2015
SCOPEThis design guide contains product information, technical specification, construction details and design considerations for HardieSmart™ Intertenancy wall system when used in multi-residential applications.
ACCESSORIESPlease refer to the respective cladding and lining products for required accessories. In addition, the following components may be required.
PROVIDED BY JAMES HARDIE®
HardieFire™ InsulationMineral wool insulation specifically designed for use in fire applications with HardieSmart™ systems.
Batt Sizes: 1160 x 560 x 85 mm (for 600mm spaced studs, 45mm wide)1160 x 420 x 85mm (for 450mm spaced studs, 35 or 45mm wide)
No. of pieces: 5 per pack
Pack weight: 22.1 Kg approx. (for 560 x 1160 x 85mm)16.6 Kg approx. (for 420 x 1160 x 85mm)
Product Code:
305790 (for 560 x 1160 x 85mm)305791 (for 420 x 1160 x 85mm)
Density: 80 Kg/m3
R Value: 2.5 m2.K/W
Coverage per pack:
3.6 m2 (for 560 x 1160 x 85mm)2.7 m2 (for 420 x 1160 x 85mm)
All dimensions and masses provided are approximate only and subject to manufacturing tolerances. Masses are based on equilibrium moisture content of product.
HardieFire™ Insulation
20-30mm cavity
90mm twin timber frame
9mm Villaboard® lining**
Designed for semi-detached common walls between tenancies in multi-residential developments, townhouses and terraces; requiring a Fire Resistance Level (FRL) of up to 1 hour and an acoustic rating Rw +Ctr ≥ 50. This integrated solution will also provide you with excellent energy efficiency and bracing performance.
NOT PROVIDED BY JAMES HARDIE®
James Hardie recommends the following products for use in conjunction with HardieSmart™ Systems. James Hardie does not supply these products. Please contact the component manufacturer for information on their warranties and further information on their products.
Fire and Acoustically rated sealant: Suitable and tested sealant for fire- and acoustically-rated construction and HardieSmart™ Systems. Used to fill control joints, penetrations and any wall gaps to maintain acoustic and fire integrity. The sealant may need to be water resistant if required in a wet area.
Reciprocating Saw or Hand Saw: Used to cut HardieFIre™ Insulation when required. Refer to safety and handling section.
Fire Resisting Mineral Wool: Used to maintain FRL of the selected wall system at junctions where relevant. Please see construction details for applications. It must be installed in accordance with manufacturer recommendations.
PAGE 2 OF 8 | HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE
SYSTEM PERFORMANCE1. FIRE RESISTANCE LEVEL (FRL): The fire resistance level (FRL) test
reports and Letters of Opinion in this guide have been certified by the CSIRO Division of Building Construction and Engineering and the Building Research Association of New Zealand (BRANZ).
Fire resistance testing to determine the FRL of a wall (in the form of a specimen) has been conducted to the Australian Standard AS 1530 Part 4: ‘Fire Resistance Tests of Elements of Building Construction’. The standard follows the basic principles and provisions contained in ISO-834 ‘Fire Resistance Tests – Elements of Building Construction’. For more information on fire performance in buildings, please refer to James Hardie Fire and Acoustically rated walls Application Guide.
2. ACOUSTIC PERFORMANCE: The acoustic test reports in this manual have been certified by the RMIT. Systems used in building construction are tested under laboratory conditions to establish their sound insulation characteristics. The method of measurement is described in AS1191 ‘Acoustics – method for laboratory measurement of airborne sound transmission loss of building partitions’. 3.5.2 Acoustic modelling. Based on the test results indicated above, acoustic modelling for HardieSmart™ wall systems was undertaken by SLR Acoustics Pty Ltd. For more information on acoustic performance in buildings, please refer to James Hardie Fire and Acoustically rated walls Application Guide.
3. THERMAL PERFORMANCE: This guide outlines a range of certified modelled total R-values for HardieSmart™ wall systems. This information will assist in both satisfying the minimum deemed to satisfy Building Code of Australia (BCA) thermal resistance requirements or used with verification software tools across Australia..
4. BRACING PERFORMANCE: To achieve the necessary bracing requirements, this guide must be read in conjunction with James Hardie Structural Bracing Application Guide. It has been designed in accordance with AS 1684 ‘Residential Timber Framed Construction’ (‘the code’), and gives fixing details and bracing capacity for James Hardie products. All design capacities quoted are Ultimate Limit State (ULS) figures and have been certified by consulting engineers, Cardno (NSW) Pty Ltd.
DESIGN CONSIDERATIONS1. INTERNAL LINING: Villaboard® lining (9mm in thickness) is recommended
when using and specifying HardieSmart™ Intertenancy wall system. Villaboard® lining may be replaced by Versilux® lining (9mm).
NOTES: If Architectural™ Invibe or Inraw™ panels are used, 6mm Villaboard® lining must be fixed behind these panels to maintain fire rating. Villaboard lining must be fixed in accordance with the installation guide current at the time of installation.
2. HARDIEFIRE™ INSULATION: It must be used as the frame cavity infill designed to be compressed 5mm or more in both vertical and horizontal directions (I.e. Batt size are cut 5mm wider and longer than frame stud bay). Ensure there are no gaps in the installation. Please refer to figure 1 for more information on installation. If cutting is required, it is recommended to cut outdoors. If indoors, please ensure that workspace is properly ventilated or HEPA vacuums/dust extractors are used.
a. Position cutting station so wind will blow dust away from the user or others in working area.
b. Use one of the following methods based on the required cutting rate: i. Reciprocating Saw ii. Mechanical Hand Saw
3. FRAMING:
■ Material type: Dry seasoned timber only. ‘Timber used for house construction must have the level of durability appropriate for the relevant climate and expected service life. Reference AS1684.2 ‘Residential Timber Framed Construction’. Steel frames are not suitable.
■ Minimum stud width: Studs that are 35mm in width may be used in accordance to system information section; however, depending on the James Hardie external cladding and internal lining product selected, where sheet jointing is required; the minimum stud width may be 38mm so as to properly accommodate the joint.
■ Stud spacing: 600mm maximum. Check whether the selected external cladding and/or internal lining require closer stud spacing for your site wind pressures and tile weight (only for tiled walls). It must be noted that HardieFire™ Insulation sizes have been optimised for 45mm studs at 600mm and 35mm studs at 450mm centres, cutting may be required otherwise.
■ Nogging: 1350mm maximum centres.
4. SLAB AND FOOTINGS: The slab and footings on which the building is situated must comply with AS 2870 ‘Residential slabs and footings – Construction’ and the requirements of the Building Code of Australia (BCA).
5. FIRE AND ACOUSTICALLY RATED SEALANT: Fire sealant in junctions and gaps as indicated in construction details to maintain fire and acoustic integrity of the system. E.g. Bostik FireBan One.
6. FASTENER TYPE: Brad nail and/or adhesive fixing are not recommended in fire and acoustically rated systems. Please refer to the respective product for alternative fixing methods.
7. PENETRATIONS: All penetrations require careful and comprehensive treatment to maintain Fire Resistance Level (FRL) of the system; therefore, they should be avoided. Generally, dealing with penetrations in fire and acoustically rated systems can be avoided by placing them in external non-fire rated systems, or by building false walls or box/bulkheads, creating pockets in the fire rated element. For more information contact James Hardie Engineering Solutions Team on 13 11 03.
8. PAINT/TEXTURE: Refer to the respective James Hardie internal installation manual for coating requirements. Please refer to coating manufacturer for
FIGURE 1 HARDIESMART™ INTERTENANCY WALL SYSTEM LAYOUT
HardieFire™ insulation5mm compression, ensure no gaps
9mmVillaboard®
lining
9mmVillaboard®
lining
Twin 90mm Timber frame20-30 mm cavity
300mm (Reduce to 200mm if tiled)
200mm
CONSTRUCTION DETAILS
Min 25mm cavity
90mm twin timber frame
9mmVillaboard®
lining
9mmVillaboard®
lining
Concrete Slab
HardieFire™ insulation
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity.
FIGURE 2 HARDIESMART™ INTERTENANCY WALL SYSTEM BASE TO SLAB
BASE DETAILS
suitability and specific requirements. When installing Villaboard® lining in areas that are not exposed and there is no concern of aesthetics such as roof cavities, James Hardie™ Top Coat and finishing coatings are not required to maintain FRL and acoustic performance. However, the joints must be sealed with an appropriate fire and acoustically rated sealant or alternatively James Hardie™ Base Coat.
SAFETY AND HANDLINGFor information refer to the respective products installation guide or data sheet and MSDS at www.jameshardie.com.au or www.accel.com.au; and the safe workplace government authority in your state.
DESIGN TOOLSJames Hardie® has developed online tools for easy specification. Please refer to www.accel.com.au for more information on estimation tools, CAD details, system selector, site specific recommendations and more.
HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE | PAGE 3 OF 8
Concrete Slab
90mm timber frame
HardieFire™ insulation
9mm Villaboard® lining
9mm Villaboard® lining
90mm twin timber frame with 20-30mm cavity (30mm recommended)
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity.
FIGURE 3 HARDIESMART™ INTERTENANCY WALL SYSTEM BASE TO STEPPED SLAB
45mm sacrificialtimber block tomaintain FRL
45mm sacrificial timber block tomaintain FRL
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
Saw cut in flooring (optional)Suitable floor joistsperpendicular toseparating wall
Suitable floor joistparallel to the wall
9mm Villaboard® lining9mmVillaboard® lining
9mmVillaboard®
lining
9mmVillaboard®
lining
Skirting board
Structural flooring
HardieFire™
insulation 20-30mm cavity (30mm recommended)
Ant capping and damp proof course
ContinuousConcrete Slab
FIGURE 4 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH SUSPENDED GROUND FLOOR
FIGURE 5 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH UPPER STOREY FLOOR OPTION 1
Non fire-ratedceiling liningGap must not exceed 25mm and must be covered by cornice
HardieFire™ insulation
Cornice
Structural flooring
9mm Villaboard® lining
9mm Villaboard® lining
9mm Villaboard® lining9mm Villaboard® lining
Skirting board
Saw cut in flooring (optional)
HardieFire™ insulation
Min 25mm cavity
20-30mm cavity (30mm recommended)
Perpendicularsuitable timberjoist
45mm sacrificialtimber block tomaintain FRL
45mm sacrificialtimber block tomaintain FRL
Suitable floor joist parallel to the wall
HardieFire™ insulation
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity.
FLOOR JUNCTIONS
Non fire-ratedceiling lining
HardieFire™ insulationCornice
Structural flooring
9mm Villaboard® lining
9mm Villaboard® lining
Gap must not exceed 25mm and must be covered by cornice
9mm Villaboard® liningSkirting board
HardieFire™ insulation
20-30mm cavity (30mm recommended)
45mm sacrificial timber block to maintain FRL
45mm sacrificial timber block to maintain FRL
Suitable floor joist parallel to the wall
Perpendicular suitable timber joist
Saw cut in flooring (optional)
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity.
Blocking
Sacrificial solid timber blocking must be fitted tight
with minimal gapping. Use 45mm solidtimber blocks.
FIGURE 6B HARDIESMART™ INTERTENANCY WALL SYSTEM WITH UPPER STOREY FLOOR OPTION 2 (PLAN VIEW)
Floor Joists perpendicular to wall
Solid timber 45mm block to maintain FRL as indicatedabove
100
Solid and Continuous45mm timber block.Offset joints from firepockets 100mmminimum
FIGURE 6A HARDIESMART™ INTERTENANCY WALL SYSTEM WITH UPPER STOREY FLOOR OPTION 2 (SECTION VIEW)
FIGURE 7 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH UPPER STOREY FLOOR OPTION 3
Non fire-ratedceiling lining
Cornice
Structural flooring
9mm Villaboard® lining
9mm Villaboard® lining9mm Villaboard® liningSkirting board
20-30mm cavity (30mm recommended)
Perpendicularsuitable timberjoist
45mm Solid timber pole plate
Gap must not exceed25mm and must be covered by cornice
Lining may be continued through the floor junction
HardieFire™ insulation9mm Villaboard® liningNogging for support
HardieFire™ insulation
OPTION 2: DISCONTINUOUS WALL (NO JOIST HANGERS REQUIRED)
OPTION 1: DISCONTINUOUS WALL (JOIST HANGERS REQUIRED) OPTION 3: CONTINUOUS WALL
PAGE 4 OF 8 | HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE
Steel beam to engineer's detail
Structural FloorBottom plate
Top plate
Double floor joistssupported on wallframing below Double timber 90x45mm
studs to support above load and maintain FRL
Steel SHS Column
Steel, beam not fixed to SHS cap plate
Fill with fire resistant mineral wool to maintain FRL (HardieFire™ insulation not suitable)
FIGURE 8A HARDIESMART™ INTERTENANCY WALL SYSTEM TO STEEL BEAM POCKET (SECTION VIEW)
Fill gap with fire and acoustically rated sealant
Steel beam toengineer's detail
Timber blockingsupported on wallframing below
Fill with fire resistantmineral wool to maintainFRL (HardieFire™ insulation not suitable)
Steel beam not fixed to cap plate
Timber blockingsupported onframing below
Nailing plate
9mm Villaboard® liningHardieFire™ insulation
9mm Villaboard® lining
20-30mm cavity (30mm recommended)
Non fire-rated ceiling lining
FIGURE 8B HARDIESMART™ INTERTENANCY WALL SYSTEM TO STEEL BEAM POCKET (FRONT VIEW)
FIGURE 9 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH PERPENDICULAR ROOF TRUSSES
Gap must not exceed25mm and must be covered by cornice
Cornice
45mm sacrificialtimber block tomaintain FRL
6mm Villaboard® lining (joints do not require to be set or sealed)
20-30mm cavity (30mm recommended)
90mm twin timber frame
Roofing with sarkinginstalled in accordancewith manufacturer
Fill with fire resistantmineral wool to maintain FRL of wall system
9mm Villaboard® lining
6mm Villaboard® lining(joints do not require to be set or sealed)
HardieFire™ insulation
Non-fire ratedceiling lining
ROOF JUNCTIONS
OPTION 1: PERPENDICULAR ROOF TRUSS (INSULATION BOTH SIDES)
OPTION 2: PERPENDICULAR ROOF TRUSS (INSULATION BOTH SIDES)
Cornice
Gap must not exceed 25mm andmust be coveredby cornice
Non-fire ratedceiling lining
Roofing with sarkinginstalled in accordancewith manufacturer
Fill with fire resistantmineral wool to maintain FRL of wall system
Suitable spacing to allow for lining insulation
Timber batten forperimeter support
9mm Villaboard® lining9mm Villaboard® lining
HardieFire™ insulation
6mm Villaboard® lining(joints do not require to be set or sealed)
6mm Villaboard® lining(joints do not require to be set or sealed)
90mm twin timberframe with 20-30mm cavity (30mm recommended)
FIGURE 11 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH PARALLEL ROOF TRUSSES
FIGURE 10 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH PERPENDICULAR ROOF TRUSSES
NOTE: Please note that this option requires increasing frame cavity to 30mm.
Gap must not exceed25mm and must be covered by cornice
Cornice
45mm sacrificialtimber block tomaintain FRL
90mm twin timber frame with 30mm cavity
Roofing with sarkinginstalled in accordancewith manufacturer
Fill with fire resistantmineral wool to maintain FRL of wall system
9mm Villaboard® lining
200m
m
9mm Villaboard® lining
6mm Villaboard® lining(joints do not require to be set or sealed)
HardieFire™ insulation
HardieFire™ insulation
Non-fire ratedceiling lining
Required acousticinsulation minimum75mm R1.5
Required acousticinsulation minimum75mm R1.5
No HardieFire™ insulation required
OPTION 1: PARALLEL ROOF TRUSS (INSULATION BOTH SIDES)
CorniceNon-fire ratedceiling lining Timber batten forperimeter support
Gap must not exceed25mm and must becovered by cornice.9mm Villaboard® lining 9mm Villaboard® liningHardieFire™ insulation
HardieFire™ insulation
6mm Villaboard® lining(joints do not require to be set or sealed)
Required acoustic insulation minimum 75mm R.15
6mm Villaboard® lining(joints do not require to be set or sealed)
90mm twin timberframe with 30mmcavity
200m
m
Roofing with sarkinginstalled in accordancewith manufacturer
Fill with fire resistantmineral wool to maintain FRL of wall system
Suitable spacing to allow for lining insulation
HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE | PAGE 5 OF 8
FIGURE 12 HARDIESMART™ INTERTENANCY WALL SYSTEM WITH PARALLEL ROOF TRUSSES
NOTE: Please note that this option requires increasing frame cavity to 30mm.
FIGURE 13 HARDIESMART™ INTERTENANCY WALL SYSTEM TO PARAPET ROOF WITH PARALLEL ROOF TRUSSES
Suitable parapet capping
Suitable corrosionresistant metal flashing installed as wall claddingto protect lining
Roofing withsarking installed in accordance with manufacturer
CorniceGap must not exceed25mm and must be covered by cornice
Non-fire ratedceiling lining
9mm Villaboard® lining9mm Villaboard® lining
6mm Villaboard® lining(joints do not require to be set or sealed)
6mm Villaboard® lining(joints do not require to be set or sealed)
Timber battenfor perimeter support
HardieFire™ insulation 90mm twin timber frame with 20-30mm cavity (30mm recommended)
FIGURE 14 HARDIESMART™ INTERTENANCY WALL SYSTEM TO PARAPET ROOF WITH PARALLEL ROOF TRUSSES
NOTE: Please note that this option requires increasing frame cavity to 30mm.
James Hardieexternal cladding
HardieWrap™
weather barrier
Suitable corrosionresistant parapet capping
Fill with fire resistantmineral wool to maintainFRL of wall system
Fill with fire resistantmineral wool to maintainFRL of wall system
200mm
90mm twin timber frame with 30mm cavity
Non-fire ratedceiling lining
Non-fire ratedceiling lining Cornice
6mm Villaboard® lining(joints do not require to be set or sealed)
9mm Villaboard® lining9mm Villaboard® lining
Timber battenfor perimetersupport
Gap must not exceed25mm and must be covered by cornice
HardieFire™ insulation
Required acoustic insulation minimum 75mm R1.5
6mm Villaboard® lining(joints do not require to be set or sealed)
Roofing with sarking installed in accordancewith manufacturer
Corrosion resistantmetal flashing withmin. 75 mm upstand
FIGURE 15 HARDIESMART™ INTERTENANCY WALL SYSTEM TO HARDIESMART™ BOUNDARY WALL SYSTEM ABOVE
NOTE: Please note that this detail requires increasing the cavity to 30mm.
FIGURE 16 HARDIESMART™ INTERTENANCY WALL SYSTEM TO BOX GUTTER WITH PERPENDICULAR ROOF TRUSSES
Gap must not exceed25mm and must be covered by cornice
Cornice45mm sacrificialtimber block tomaintain FRL
Timberbattensupport
Trussperpendicularto wall
20-30mm cavity (30mm recommended)
Non-fire ratedceiling lining
Roofing with sarkinginstalled in accordancewith manufacturer
9mm Villaboard® lining
HardieFire™ insulation
Suitable parapet capping
Suitable corrosionresistant metal flashing installed as wall claddingto protect lining
Roofing withsarking installed in accordance with manufacturer
CorniceNon-fire ratedceiling lining
9mm Villaboard® lining9mm Villaboard® lining
Timber battenfor perimeter support
HardieFire™ insulation 90mm twin timber frame with 30mm cavity
200m
m Required acoustic insulation minimum 75mm R.15Gap must not exceed25mm and must be covered by cornice
6mm Villaboard® lining(joints do not require to be set or sealed)
6mm Villaboard® lining(joints do not require to be set or sealed)
No HardieFire™ insulation requiredHardieFire™ insulation
OPTION 2: PARALLEL ROOF TRUSS (INSULATION ONE SIDE)
OPTION 1: PARAPET WALL (INSULATION BOTH SIDES)
OPTION 2: PARAPET WALL (INSULATION ONE SIDE)
PAGE 6 OF 8 | HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE
FIGURE 19 HARDIESMART™ INTERTENANCY WALL SYSTEM TO NON-FIRE-RATED EXTERNAL CLADDING WALL IN A CAVITY
9mm Villaboard® lining
HardieFire™ insulation
non-fire ratedinternal lining
non-fire ratedinternal lining
Selected cladding installed in accordance with manufacturer
HardieWrap™
weather barrier
Dampproofcourse
Fire resisting Mineral wool to maintain FRL (HardieFire™ insulation not sutable)
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
20-30mm cavity (30mm recommended)
45mm sacrificialtreated timber block to maintain FRL
FIGURE 20 HARDIESMART™ INTERTENANCY WALL SYSTEM EXTERNAL PROJECTION TO LIGHTWEIGHT FAÇADE
Non-fire ratedinternal lining
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
Non-fire ratedinternal lining
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
HardieFire™ insulation9mm Villaboard® liningMin 25mm cavity
9mm Villaboard® lining
HardieWrap™ weather barrier
45mm sacrificial timberblock to maintain FRL
Selected James Hardieexternal cladding
Corner detail and accessoryinstalled in accordancewith selected cladding
HardieFire™ insulation
For frameprojection limit referto project engineer
WALL JUNCTIONS
FIGURE 18 HARDIESMART™ INTERTENANCY WALL SYSTEM TO NON-FIRE-RATED EXTERNAL CLADDING WALL
9mm Villaboard® liningHardieFire™ insulation
Selectedexternalcladding
HardieWrap™ weather barrier
non-fire ratedinternal lining
non-fire ratedinternal lining
45mm sacrificialtimber block tomaintain FRL
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
20-30mm cavity (30mm recommended)
Non-fire ratedinternal lining
Non-fire ratedinternal lining
HardieWrap™
weather barrier
90mm twin timber framewith 20-30mm cavity (30mm recommended)y
Selected cladding installedin accordance with manufacturer
Fire resistant mineral wool to maintain FRL(HardieFire™ insulation not suitable)
9mm Villaboard® lining
9mm Villaboard® lining
HardieFire™ insulation
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
FIGURE 21 HARDIESMART™ INTERTENANCY WALL SYSTEM TO EXTERNAL BRICK RETURN
FIGURE 17A HARDIESMART™ INTERTENANCY WALL SYSTEM TO EAVES BLOCKING FRONT ELEVATION VIEW
FIGURE 17B HARDIESMART™ INTERTENANCY WALL SYSTEM TO EAVES BLOCKING SIDE ELEVATION VIEW
Fill with fireresistant mineralwool to maintain FRL (HardieFire™ insulationnot suitable)
James Hardie™ lining to extend through eaves (min 4.5mm in thickness)
Fill with fire resistant mineralwool to maintain FRL(HardieFire™ insulationnot suitable)
External non-fire rated wall frame
HardieSmart™ Intertenancy wall system
HardieSmart™ Intertenancy wall system
Non-fire rated and sound rated linings
Refer to side elevation view
Fill with fire-resistant mineralwool to maintain FRL (HardieFire™
insulation not suitable)
HardieSmart™ Intertenancywall system
James Hardie lining to extend through eaves (min 4.5mm in thickness)
Soffit bearer
Rafter or Truss
EAVES SEPARATION
HARDIESMART™ INTERTENANCY WALLS – DESIGN GUIDE | PAGE 7 OF 8
HardieFire™ insulationSuitable wet
area sealant6mm Villaboard® lining
Batten to suit penetration depth
Batten to suit penetration depth
90mm twin timber frame
Suitable tiles with recommendedwaterproofing membrane
FIGURE 25 HARDIESMART™ INTERTENANCY WALL SYSTEM PLUMBING PIPE PENETRATION – PLAN
FIGURE 26 HARDIESMART™ INTERTENANCY WALL SYSTEM PLUMBING PIPE PENETRATION – SECTION
Batten to suit penetration depth
Adequate horizontal support for taps
Suitable wet area sealant
HardieFire™ insulation
6mm Villaboard® lining
9mm Villaboard® lining
Suitable tiles with recommendedwaterproofing membrane (forwet areas)
90mm timber frame
WARRANTYHardieSmart™ Intertenancy wall system has a James Hardie product warranty. The period varies for the selected system components. For terms and conditions of product warranty, refer to www.jameshardie.com.au or www.accel.com.au
CODEMARK CERTIFIEDThis product is marked with the CodeMark Scheme Mark of Conformity. This indicates that the conformity of our product is based upon technical documentation and review of our manufacturing and quality control process to monitor our ability to consistently produce the product in compliance with the requirements of Clauses B1.2 and B1.4 in respect of structural capacity of the walls, A2.3, C1.10, F5.5,J1.2 inter alia J1.5, NTF5.5, QLD J1.2 interalia J1.5 BCA 2009 and BCA 2010, 1.2.3, 3.8.6.2, NT 3.8.6.2, 3.12.1.1 interalia 3.12.1.4, NT 3.12.1.1 interalia 3.12.1.4 BCA 2005 of the BCA.’
PENETRATIONS
FIGURE 22 HARDIESMART™ INTERTENANCY WALL SYSTEM TO NON-FIRE-RATED INTERNAL PARTITION WALL
9mmVillaboard®
lining
9mmVillaboard®
lining
Non-fire-rated lining
45mm sacrificialtimber block tomaintain FRL
HardieFire™
insulation
Recommend sealing gap with suitable fire and acoustically rated sealant to maintain acoustic integrity
HardieFire™
insulation
FIGURE 24 FIRE-RATED SWITCH PLATE OR GENERAL POWER OUTLET (GPO) ELEVATION
9mmVillaboard®
lining
Fire rated switchbox as supplied by manufacturer
Switch plate bracket
Switch plate
Gap sealed with fire and acoustically rated sealant
HardieFire™ insulation
9mmVillaboard®
lining
HardieFire™ insulation
NOTE: It is recommended to pin the cable on the side of the stud for ease of insulation installation. Ensure power points are offset 300mm minimum horizontally at each side of the wall.
FIGURE 23 VILLABOARD® LINING CONTROL JOINT IN HARDIESMART™ INTERTENANCY WALL SYSTEM
22mm backing rod9mmVillaboard®
lining
9mmVillaboard®
lining
HardieFire™
insulation
HardieFire™
insulation
Gap sealed with suitable fire and acoustically rated sealant
Suitable tiles with recommendedwaterproofing membrane (for wet areas)
CONTROL JOINTS