Handbook - elec-engg.com
Transcript of Handbook - elec-engg.com
© A
BB
Gro
up -
3-
2-J
ul-18
AutoreclosingAuto reclosing Cycle
Fast
simultaneous
Fault clearing
OH-lines
High fault-rate
(80-90%)
© A
BB
Gro
up -
4-
2-J
ul-18
AutoreclosingAUTORECLOSING CYCLE
OH-lines
Intermittent faults
(80-90%)
Successful
AR-rate :
High (80-90%)
© A
BB
Gro
up -
5-
2-J
ul-18
Autoreclosing
Auto reclosing principles
95% of faults are transient type
3 Ph autoreclosing synchrocheck is used
Helps verify phase angles are not out of phase e.g: due to
heavy power swing
1 Ph autoreclosing needs identification of faulty phase
Phase identification is difficult for high resistance faults
© A
BB
Gro
up -
7-
2-J
ul-18
AutoreclosingAutoreclosure in a Line
bay
AR- Autorecloser
BFR- Breaker failure
relay
COM- Communication
COND-CB condition
DLC SC-Dead line check
and synchronism check
LP- Line protection
MAN- Manual CB control
PD- Pole discordance
relay
© A
BB
Gro
up -
8-
2-J
ul-18
Autoreclosing
Auto reclosing principles Protections that start autoreclosing
Main 1 protection
Main 2 protection
Protections that block autoreclosing
CB fail detected by Breaker fail relay & Pole discrepancy relay
CB not ready
Delayed tripping ( Zone2 or3 of distance relay , Back up relay)
Manual CB operation
Communication fail
Direct transfer trip receive , BB protection , O/V protection, Reactor protection
© A
BB
Gro
up -
9-
2-J
ul-18
Autoreclosing
Circuit-breaker Contact Travel
Con
tact
pos
itio
n
Time
Closed
Open
Closed
t t t t
tt 2 6
5431
© A
BB
Gro
up -
10
-
2-J
ul-18
AutoreclosingDead time for Automatic Reclosing Equipment
A B
Time
Con
tact
po
siti
on
t2 B
t2 A
t6 A
t6 B
t1 A
t1 B
t0
A
B
F
Open
Open
Closed
ClosedDead time
Interruption time
© A
BB
Gro
up -
11
-
2-J
ul-18
Autoreclosing
Single-pole Reclosing
A B C A B C
Single-Pole Reclosing
© A
BB
Gro
up -
12
-
2-J
ul-18
AutoreclosingTemporal Description of Automatic Reclosing
0.1 1 10 100 s
TD
3
HSR = High-Speed Automatic Reclosing
DR = Delayed Automatic Reclosing
R = Automatic Reclosing
SR = Slow Automatic Reclosing
R SR
DR
HSR
© A
BB
Gro
up -
13
-
2-J
ul-18
Autoreclosing
Classical Three-pole Reclosing
A B
Time
Con
tact
po
siti
on
t2 B
t2 A
t6 A
t6 B
t1 A
t1 B
t0
A
B
F
Open
Open
Closed
Closed
Dead time
Interruption time
© A
BB
Gro
up -
14
-
2-J
ul-18
Autoreclosing
Factors affecting extinction of Primary Arc
Fault current magnitude
Fault clearance time
Coupling from energized conductors
Closing or opening of resistors
Magnitude of reenergizing voltage
Point of wave for reenergizing
Magnetic forces on the fault current
Length of insulating string
Weather conditions
Shape of grading ring
© A
BB
Gro
up -
15
-
2-J
ul-18
AutoreclosingMinimum Dead Time (IEEE)
System Voltage Minimum deionization time [ms]
kV Based on Field and
Laboratory Tests
Based on Operating
Experience
23 110 180
46 120 200
69 130 210
115 150 230
132 160 240
230 210 280
345 260 340
400 280 370
500 330 420
© A
BB
Gro
up -
16
-
2-J
ul-18
AutoreclosingMinimum Dead Time for Three-pole Reclosing
Minimum Dead Time
Three-Pole Reclosing
System Voltage
100 200 300 400 500 600 kV
500
400
300
200
100
ms
Based on Opera-
ting Experience
Based on Field and
Laboratory Tests
© A
BB
Gro
up -
17
-
2-J
ul-18
Autoreclosing
Double Fault on a Double-circuit Line
L R
A B CA B CL1
L2
© A
BB
Gro
up -
18
-
2-J
ul-18
AutoreclosingCapacitive Coupling and Single-pole Tripping
L R
A B C A B CC p
C p C p
Ce
Ce
Ce
© A
BB
Gro
up -
19
-
2-J
ul-18
Autoreclosing
Secondary arc
Secondary arc is phasor sum of currents maintained by
capacitive and inductive coupling from the energised
phase conductors
© A
BB
Gro
up -
20
-
2-J
ul-18
Autoreclosing
Critical Line Lengths for Single-pole Reclosing
System Voltage Critical Line Length [miles]
kV Successful Range Doubtful Range
230 0-300 300-500
345 0-140 140-260
500 0-60 60-100
765 0-50 50-80
© A
BB
Gro
up -
21
-
2-J
ul-18
Autoreclosing
Artificial extinction of secondary arc
Where high-speed automatic reclosing is to be implemented,
secondary arcs must be artificially extinguished since they would
otherwise last too long.
There are several methods to extinguish artificially the secondary
arc:
Fixed Four-Reactor Scheme
Switched Four-Reactor Scheme
High speed Earthing Switch Scheme
© A
BB
Gro
up -
22
-
2-J
ul-18
AutoreclosingFixed Four-reactor Scheme
L R
A B C A B C
L p L p L p
L n
© A
BB
Gro
up -
23
-
2-J
ul-18
AutoreclosingSecondary Arcing Time (Haubrich)
s Tsa
Is
A50 100 150
0.5
1.0
1.5
2.0
Secondary Arcing Time
Haubrich 1971
© A
BB
Gro
up -
27
-
2-J
ul-18
Autoreclosing
Special problems
Memory Circuit
Priority circuit
Autoreclosure out of service
© A
BB
Gro
up -
29
-
2-J
ul-18
Autoreclosing
ULine UBus
SYNC-BLOCK
UBus
ULine
Fuse fail
1-ph
3-ph (or 1-ph)
UBus
ULineUHigh > 50-120% Ur
ULow < 10-100% Ur
PhaseDiff < 5-75
UDiff < 5-50% Ur
FreqDiff < 50-300 mHzo
Synchronism and Energizing check
© A
BB
Gro
up -
31
-
2-J
ul-18
Auto ReclosingCBIP manual on Protection
of Generators, generator
transformers and 220kV
and 400 kV networks
© A
BB
Gro
up -
32
-
2-J
ul-18
Autoreclosing1.0 GENERAL
• The auto-reclosing of power lines has become a generally accepted
practice.
• Reports from different parts of the world show that in
certain networks in region subject to a high lightening intensity only
about 5% of the faults are permanent.
• Auto reclosing therefore provides significant advantages.
• Outage times will be short compared to where station personnel
have to re-energize the lines after a fault.
• In interconnected networks auto-reclosing helps in maintaining
system stability
© A
BB
Gro
up -
33
-
2-J
ul-18
Autoreclosing1.1 Recommendations for provisions of auto-reclosing
• Presently 1 phase high speed auto-reclosure (HSAR) at 400kV and
220kV level is widely practised including on lines emanating from
Generating Stations and the same is recommended for adoption.
• If 3-phase auto-reclosure is adopted in future the application of the
same on lines emanating from generating stations should be studied
and decision taken on case to case basis.
© A
BB
Gro
up -
34
-
2-J
ul-18
Autoreclosing2.0 SETTING CRITERIA
2.1 Dead Time
• Auto- reclosing requires a dead time which exceeds the de-ionising
time
• Time required for the de-ionising of the fault path depends on:- arcing
time, fault duration, wind conditions, circuit voltage, capacitive
coupling to adjacent conductors, etc.
• Single phase dead time of 1.0 sec is recommended for both 400kV
and 220kV system.
© A
BB
Gro
up -
35
-
2-J
ul-18
Autoreclosing2.2 Reclaim Time
• The time during which a new start of the auto-reclosing equipment is
blocked.
• If reclosing shot has been carried out and the line is energized and a
new fault occurs before the reclaim time has elapsed, the auto-reclosing
equipment is blocked and a signal for definite tripping of the breaker is
obtained.
• After the reclaim time has elapsed, the auto-reclosing equipment
returns to the starting position and a new reclosing sequence can occur.
• The reclaim time must not be set to such a low value that the intended
operating cycle of the breaker is exceeded, when two faults incidents
occur close together.
© A
BB
Gro
up -
36
-
2-J
ul-18
Autoreclosing• If the breaker is closed manually, the auto reclosing equipment is
blocked and cannot start again until the reclaim time has elapsed.
• For the breaker to be used for auto-reclosing, it is essential that it
has the operating mechanism and breaking capacity necessary for
it to be able to perform the auto-reclosing sequences required.
© A
BB
Gro
up -
37
-
2-J
ul-18
Autoreclosing2.3 Circuit Breaker Requirement
• According to IEC Publication 56.2, a breaker must be capable of
withstanding the following operating cycle with full rated breaking
current:
O + 0.3 s + CO + 3 min + CO
• The recommended operating cycle at 400kV and 220kV is as per the
IEC standard.
• Reclaim time of 25 sec is recommended.