GXT Family

4
SPECIFICATIONS 700-3000 VA Liebert ® UPStation ® GXT™ While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 1998 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. SLE GXT FAM E.1 Printed in Italy LIEBERT PRODUCTS ARE AVAILABLE FROM MiniTower models RackTower models Model No. GXT700MT-120 GXT1000MT-120 GXT1000RT-120 GXT1000RTE-120 GXT1500RT-120 GXT2000RT-120 GXT3000RT-120 VA/Watts (max.) 700/490 1000/700 1000/700 1000/700 1500/1050 2000/1400 3000/2100 Input Voltage Range 120 VAC nominal; variable based upon output load 100-90% Loading 80-83 VAC to 134-138 VAC 90-93 VAC to 134-138 VAC 90-70% Loading 80-83 VAC to 134-138 VAC 80-83 VAC to 134-138 VAC 70-30% Loading 70-73 VAC to 134-138 VAC 70-73 VAC to 134-138 VAC 30-0% Loading 60-62 VAC to 134-138 VAC 60-62 VAC to 134-138 VAC Input Plug NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-20P NEMA L5-30P Output Voltage 100V, 110V, 120V or 127V, user selectable, ±3%; sinewave Output Receptacles (6) NEMA 5-15R (6) NEMA 5-15R (4) NEMA 5-15R (4) NEMA 5-15R (8) NEMA 5-15R (8) NEMA 5-15R (8) NEMA 5-15R (2) NEMA 5-20R (1) NEMA L5-30R Battery Time (FL/HL) 6 min./18 min. 7 min./25 min. 7 min./25 min. 17 min./49 min. 7 min./18 min. 10 min./26 min. 6 min./19 min. Dimensions: mm WxDxH 162 x 430 x 225 162 x 430 x 225 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 Weight: kg 13.6 16.6 26.0 33.2 29.1 39.3 41.6 MiniTower models RackTower models Model No. GXT700MT-230 GXT1000MT-230 GXT1000RT-230 GXT1000RTE-230 GXT1500RT-230 GXT2000RT-230 GXT3000RT-230 VA/Watts (max.) 700/490 1000/700 1000/700 1000/700 1500/1050 2000/1400 3000/2100 Input Voltage Range 230 VAC nominal; variable based upon output load 100-90% Loading 160-163 VAC to 273-276 VAC 184-187 VAC to 273-276 VAC 90-70% Loading 160-163 VAC to 273-276 VAC 160-163 VAC to 273-276 VAC 70-30% Loading 140-143 VAC to 273-276 VAC 140-143 VAC to 273-276 VAC 30-0% Loading 120-122 VAC to 273-276 VAC 120-122 VAC to 273-276 VAC Input Socket IEC320-10A IEC320-10A IEC320-10A EC320-10A IEC320-10A IEC320-10A IEC320-16A Output Voltage 208V, 220V, 230V or 240V, user selectable, ±3%; sinewave Output Receptacles (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (1) IEC320-16A Battery Time (FL/HL) 6 min./18 min. 6 min./18 min. 6 min./18 min. 17 min./49 min. 5 min./15 min. 11 min./27 min. 6 min./15 min. Dimensions: mm WxDxH 162 x 430 x 225 162 x 430 x 225 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 Weight: kg 13.6 16.6 26.0 33.2 29.1 39.3 41.6 RackTower models Model No. GXT1800RT-208 1 GXT2700RT-208 1 GXT1800RT-208 1 GXT2700RT-208 1 VA/Watts (max.) 1800/1260 2700/1890 2000/1400 3000/2100 Input Voltage Range 208 VAC nominal; variable based upon output load 240 VAC nominal; variable based upon output load 100-90% Loading 184-187 VAC to 273-276 VAC 184-187 VAC to 273-276 VAC 90-70% Loading 160-163 VAC to 273-276 VAC 160-163 VAC to 273-276 VAC 70-30% Loading 140-143 VAC to 273-276 VAC 140-143 VAC to 273-276 VAC 30-0% Loading 120-122 VAC to 273-276 VAC 120-122 VAC to 273-276 VAC Input Socket NEMA L6-15P NEMA L6-20P NEMA L6-15P NEMA L6-20P Output Voltage 208 VAC, +/-3%; sinewave 240 VAC, +/-3%; sinewave Output Receptacles (2) NEMA L6-15R (2) NEMA L6-15R (2) NEMA L6-15R (1) NEMA L6-20R (2) NEMA L6-15R (1) NEMA L6-20R Battery Time (FL/HL) 11 min./31 min. 5 min./15 min. 11 min./31 min. 5 min./15 min. Dimensions: mm WxDxH 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 Weight: kg 39.3 41.6 39.3 41.6 UPStation ® GXT-208 VAC Models UPStation ® GXT-230 VAC Models, 50 Hz UPStation ® GXT-120 VAC Models, 60 Hz L IEBERT C ORPORATION 1050 DEARBORN DRIVE P.O. BOX 29186 COLUMBUS, OHIO 43229 USA TEL: +1 614 888 0246 F AX: +1 614 841 6022 L IEBERT W EB S ITE http://www.liebert.com L IEBERT E UROPE VIA G. ROSSINI 6 20098 S. GIULIANO MILANESE (MI) ITALY TEL: +39 02 982501 F AX: +39 02 9844633 L IEBERT UK GLOBE P ARK, MARLOW BUCKINGHAMSHIRE, SL7 1YG UNITED KINGDOM TEL: +44 (0)1628 403200 F AX: +44 (0)1628 403203 1 Power rating is variable, based on output voltage selected by customer.

Transcript of GXT Family

Page 1: GXT Family

SPECIFICATIONS 700-3000 VA

Liebert®

UPStation® GXT™

While every precaution has been taken to ensure accuracy and completeness in this brochure,Liebert Corporation assumes no responsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.

© 1998 Liebert Corporation. All rights reserved throughout the world.Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks of their respective owners.

SLE GXT FAM E.1 Printed in Italy

LIEBERT PRODUCTS ARE AVAILABLE FROM

MiniTower models RackTower modelsModel No. GXT700MT-120 GXT1000MT-120 GXT1000RT-120 GXT1000RTE-120 GXT1500RT-120 GXT2000RT-120 GXT3000RT-120VA/Watts (max.) 700/490 1000/700 1000/700 1000/700 1500/1050 2000/1400 3000/2100Input Voltage Range 120 VAC nominal; variable based upon output load100-90% Loading 80-83 VAC to 134-138 VAC 90-93 VAC to 134-138 VAC90-70% Loading 80-83 VAC to 134-138 VAC 80-83 VAC to 134-138 VAC70-30% Loading 70-73 VAC to 134-138 VAC 70-73 VAC to 134-138 VAC30-0% Loading 60-62 VAC to 134-138 VAC 60-62 VAC to 134-138 VACInput Plug NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-15P NEMA 5-20P NEMA L5-30POutput Voltage 100V, 110V, 120V or 127V, user selectable, ±3%; sinewaveOutput Receptacles (6) NEMA 5-15R (6) NEMA 5-15R

(4) NEMA 5-15R (4) NEMA 5-15R (8) NEMA 5-15R (8) NEMA 5-15R (8) NEMA 5-15R (2) NEMA 5-20R (1) NEMA L5-30RBattery Time (FL/HL) 6 min./18 min. 7 min./25 min. 7 min./25 min. 17 min./49 min. 7 min./18 min. 10 min./26 min. 6 min./19 min.Dimensions: mm WxDxH 162 x 430 x 225 162 x 430 x 225 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430Weight: kg 13.6 16.6 26.0 33.2 29.1 39.3 41.6

MiniTower models RackTower modelsModel No. GXT700MT-230 GXT1000MT-230 GXT1000RT-230 GXT1000RTE-230 GXT1500RT-230 GXT2000RT-230 GXT3000RT-230VA/Watts (max.) 700/490 1000/700 1000/700 1000/700 1500/1050 2000/1400 3000/2100Input Voltage Range 230 VAC nominal; variable based upon output load100-90% Loading 160-163 VAC to 273-276 VAC 184-187 VAC to 273-276 VAC90-70% Loading 160-163 VAC to 273-276 VAC 160-163 VAC to 273-276 VAC70-30% Loading 140-143 VAC to 273-276 VAC 140-143 VAC to 273-276 VAC30-0% Loading 120-122 VAC to 273-276 VAC 120-122 VAC to 273-276 VACInput Socket IEC320-10A IEC320-10A IEC320-10A EC320-10A IEC320-10A IEC320-10A IEC320-16AOutput Voltage 208V, 220V, 230V or 240V, user selectable, ±3%; sinewaveOutput Receptacles (4) IEC320-10A

(4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (4) IEC320-10A (1) IEC320-16ABattery Time (FL/HL) 6 min./18 min. 6 min./18 min. 6 min./18 min. 17 min./49 min. 5 min./15 min. 11 min./27 min. 6 min./15 min.Dimensions: mm WxDxH 162 x 430 x 225 162 x 430 x 225 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430Weight: kg 13.6 16.6 26.0 33.2 29.1 39.3 41.6

RackTower modelsModel No. GXT1800RT-2081 GXT2700RT-2081 GXT1800RT-2081 GXT2700RT-2081

VA/Watts (max.) 1800/1260 2700/1890 2000/1400 3000/2100Input Voltage Range 208 VAC nominal; variable based upon output load 240 VAC nominal; variable based upon output load100-90% Loading 184-187 VAC to 273-276 VAC 184-187 VAC to 273-276 VAC90-70% Loading 160-163 VAC to 273-276 VAC 160-163 VAC to 273-276 VAC70-30% Loading 140-143 VAC to 273-276 VAC 140-143 VAC to 273-276 VAC30-0% Loading 120-122 VAC to 273-276 VAC 120-122 VAC to 273-276 VACInput Socket NEMA L6-15P NEMA L6-20P NEMA L6-15P NEMA L6-20POutput Voltage† 208 VAC, +/-3%; sinewave 240 VAC, +/-3%; sinewaveOutput Receptacles (2) NEMA L6-15R (2) NEMA L6-15R

(2) NEMA L6-15R (1) NEMA L6-20R (2) NEMA L6-15R (1) NEMA L6-20RBattery Time (FL/HL) 11 min./31 min. 5 min./15 min. 11 min./31 min. 5 min./15 min.Dimensions: mm WxDxH 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430 177 x 522 x 430Weight: kg 39.3 41.6 39.3 41.6

UPStation® GXT-208 VAC Models

UPStation® GXT-230 VAC Models, 50 Hz

UPStation® GXT-120 VAC Models, 60 Hz

L I E B E R T C O R P O R A T I O N

1050 DEARBORN DRIVE

P.O. BOX 29186

COLUMBUS, OHIO 43229

USA

TEL: +1 614 888 0246

FAX: +1 614 841 6022

L I E B E R T W E B S I T E

http://www.liebert.com

L I E B E R T E U R O P E

VIA G. ROSSINI 6

20098 S. GIULIANO MILANESE (MI)

ITALY

TEL: +39 02 982501

FAX: +39 02 9844633

L I E B E R T U K

GLOBE PARK, MARLOW

BUCKINGHAMSHIRE, SL7 1YGUNITED KINGDOM

TEL: +44 (0)1628 403200FAX: +44 (0)1628 403203

1Power rating is variable, based on output voltage selected by customer.

Page 2: GXT Family

N E T W O R K P O W E R P R O T E C T I O N

Liebert®

UPStation® GXT™ Family

VERSATILE, HIGH PERFORMANCEUPS FOR NETWORK AND

TELECOMMUNICATIONAPPLICATIONS

TRUE ON-LINE

POWER FOR YOUR

MISSION CRITICAL SYSTEMS

Reliance on sensitive electronic equipment is at an alltime high, as is the cost of downtime. When yourcritical systems demand reliable power protection, theUPStation GXT delivers the power back-up andconditioning you need.

The UPStation GXT units offer true on-line powerprotection, the best available technology forprotecting mission critical systems.

The GXT features easy to operate controls, user-installable slide-in communications options andbattery upgrades.

But simplicity is only the start...on-line design meanssuperior power quality even under the worst conditionssuch as sags, surges and even frequency deviations.

■ True on-line design

■ Protection against all power threats

■ Internal SNMP communications and other

monitoring options

■ Extended battery options

■ User replaceable internal

batteries up to 3kVA

■ Hot swappable external battery

packs up to 3kVA

■ Rack mount or tower configuration

up to 3kVA

■ Two-year warranty as standard

ON-LINETECHNOLOGY

UTILITY

BATTERY

LOADINVERTERSURGESUPPRESSION

BYPASS

POWER FACTORCORRECTION/RECTIFIER

CHARGER

Page 3: GXT Family

The Liebert UPStation GXT uses true on-linetechnology to meet the most exacting equipmentpower requirement of modern network andtelecommunication equipment. Unlike other UPSdesigns, it provides precise sinewave power, to ensureprotection against all types of power disturbances,including lightning strikes and surges, voltage sags,harmonics and power outages. It also offers thecommunications capability and flexibility that is vitalto the continuous operation of today’s complexdistributed computing systems.

The on-line technology at the heart of the highperformance UPStation GXT gives superior powerquality compared with other UPS topologies.Whatever the condition of the utility power supply,the UPS output will meet the requirements ofdelicate and sensitive electronic equipment.

A basic off-line UPS will reduce the impact of spikes,surges and sags in the supply by clipping the peaksand valleys, boosting the power or switching tobattery backup. In fact, within the track of anelectrical sinewave, most power problems will be leftuncorrected.

But the on-line UPStation GXT completelyregenerates the sinewave, rather than merelyconditioning the incoming mains supply. It alsoprovides the frequency regulation which is essentialwhen using backup generator systems.

UNRIVALLED VERSATILITY & PERFORMANCE

P O W E R P R O T E C T I O N

L I E B E R T C O R P O R A T I O N

UPStation GXT Features include:

■ FlexibilityLiebert’s unique RackTower design allows units from1000VA to 3000VA to be installed either free-standingor rack-mounted, whilst the smaller MiniTower units areideal for desk-top applications.

■ Fault tolerance

A fail-safe bypass in the UPStationGXT ensures that thepower supply to the critical load is maintained evenduring UPS overload or fault conditions.

■ Battery back-up upgradingRackTower units can be upgraded using plug-in batterypacks to extend battery time. Extended batterycabinets are also available for the larger Tower units.

UPSTATION GXTPROVIDES PROTECTIONFOR CRITICALOPERATIONS:■ Large office telecommunications

systems.

■ Voicemail and E-Mail systems.

■ Networks: LANs and WANs.

■ Remote telecommunication units.

■ Test and diagnostic equipment.

■ Engineering network servers.

■ Factory floor protection of micro-processorcontrolled equipment.

■ Clustered network equipment: servers, hubs, routers,etc.

COMMUNICATION OPTIONS FORLIEBERT’S UPSTATIONGXTThe communications interface provided as standard,allows full UPS monitoring and control, when used withLiebert’s SiteNet software. All major platforms aresupported including Windows, UNIX, Novell, DEC and HP.

UPStation GXT is available in RackTower convertible models.

Rear view of the UPStation GXT MiniTower

Page 4: GXT Family

L I E B E R T C O R P O R A T I O N

SITNET® COMMUNICATION OPTIONS

■ Intellislot™SNMP Card

This user installable, hot-swap card enables the UPStationGXT to become a fully-interactive node on your SNMPnetwork, allowing consistent monitoring and control of allnetwork devices.Internal SNMP installation saves space, enhancesreliability, and is internally protected by the UPS.

■ SiteNet® Integrator™

Liebert’s SiteNet Integrator takes SNMP management onelevel further and adds environmental and userprogrammable monitoring to the UPS communication.

The MultiPort 4 communications card

■ SiteNet® 1

UPS monitoring and shutdown software which prevents un-expected server shutdowns by monitoring UPS activity andclosing down protected nodes if utility power remains off.

SPECIFICATIONS 6 AND 10 KVA

Model GXT6000T-208X GXT6000T-230 GXT6000T-230X GXT6000T-240X GXT10000T-208X GXT10000T-230 GXT10000T-230X GXT10000T-240X

VA/Watts (max.) 6000/4200 10000/7000

Input Voltage Range 208VAC nominal* 230 VAC nominal* 230 VAC nominal* 240 VAC nominal* 208 VAC nominal* 230 VAC nominal* 230 VAC nominal* 240 VAC nominal*

100%-90% Loading 184-187 VAC to 273-276 VAC 184-187 VAC to 273-276 VAC

90%-30% Loading 140-163 VAC to 273-276 VAC 140-163 VAC to 273-276 VAC

30%-0% Loading 120-122 VAC to 273-276 VAC 120-122 VAC to 273-276 VAC

Input Connector Terminal Block (hardwired) Terminal Block (hardwired)

Output Voltage Range 208/120 VAC; ±7% 230 VAC; ±3% 230 VAC; ±7% 240/120 VAC; ±7% 208/120 VAC; ±7% 230 VAC; ±3% 234 VAC; ±7% 240/120 VAC; ±7%

Output Waveform Sinewave Sinewave

Output Connector Terminal Block (hardwired) Terminal Block (hardwired)

Battery Time (FL/HL) 7 min./18 min. 10 min./25 min.

Dimensions WxDxH (mm) 260x558x800 340x640x965

Weight: (kg) 121 103 121 121 235 178 235 235

Note: Models with an “x” suffix contain isolation transformers. *Variable based on output load.

■ SiteNet® SNMP Manager

UPS monitoring software for Network ManagementSystems which provides a series of snap-in screens for NMSsoftware.

■ MultiPort 4 and MultiPort 8.

When used in conjunction with SiteNet software, theMultiPort multiplexer communicates the status of asingle UPS to as many as eight PCs, servers orworkstations.

■ SiteNet® 2

Power surveillance and shutdown management softwarewhich gives ongoing monitoring and control betweennetwork servers and system UPS via a two-way graphicalinterface.

■ SiteNet® MultiLink

This software allows single or multiple server shutdownthrough either a dedicated serial communicationsconnection, or across the network. It can be used acrossmixed operating platforms and network topologies,allowing your power protection software to expand as yournetwork develops.