GV2 & GV3
-
Upload
thongtn2007 -
Category
Documents
-
view
77 -
download
8
Transcript of GV2 & GV3
3/0
Contents 0
3
3 - Protection componentsMotor circuit-breakers
TeSys protection components for the motor protection
Thermal-magnetic motor circuit-breakersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/2
b General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6
b GV2 ME and GV2 P
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/8
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/22
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/45
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/62
b GV3 ME
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/10
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/26
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/47
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65
b GV7 R
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/11
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/29
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/48
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65
b GV2 RT
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/34
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/49
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/64
b Accessories
v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/59
v For circuit-breakers GV3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55
v For circuit-breakers GV7. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/57 and 3/61
Magnetic motor circuit-breakersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/4
b GV2 LE and GV2 L
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/12
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/35
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/50
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/70
b GK3
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/14
v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/41
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/51
v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/72
b Accessories
v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/53 and 3/59
v For circuit-breakers GK3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55
3/1
3
Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/74
b Thermal-magnetic circuit-breaker GB2 for the protection of industrial equipment
control circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/76
v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/77
v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/80
v Dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/81
3/2
3
Selection guide 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers
Applications Protection of motors
Tripping threshold on short-circuit 13 In on average
Standard motor power ratings in AC-3, 415 V Up to 15 kW Up to 37 kW
Operational current at 415 V 0.1…32 A 1…80 A
Breaking capacity at 415 V (Icu) to IEC 60947-2 10…100 kA 35…100 kA
Door interlock mechanism Without With Without
Circuit-breaker type GV2 ME GV2 P GV3 ME
Pages 3/45 and 3/46 3/45 3/47
3/3
3
33
Protection of motors with high current peak on starting
20 In on average
7.5…110 kW Up to 11 kW
12…220 A 0.25…23 A
35 and 36 kA 70 kA 15…100 kA
With With
GV7 RE GV7 RS GV2 RT
3/48 3/49
3/4
3
Selection guide 3 TeSys protection components 3
Magnetic motor circuit-breakers
Applications Protection of motorsMagnetic circuit-breakers provide short-circuit protection. They must be combined with thermal overload relays to provide motor overload protection.
Tripping threshold on short-circuit 13 In on average
Standard motor power ratings in AC-3, 415 V Up to 15 kW
Operational current at 415 V 0.4…32 A
Breaking capacity at 415 V (Icu) to IEC 60947-2 10…100 kA 35…100 kA
Door interlock mechanism With
Device type GV2 LE GV2 L
Pages 3/50
3/5
3
33
6…14 In 8…13 In 6.3…12.5 In
11…37 kW 0.37…250 kW
40…80 A 1.5…500 A
35 and 50 kA 25.7 and 150 kA 35.7…150 kA 45.7…150 kA
GK3 EF NS 80 NS 100 toNS 250
NS 400 and NS 630
3/51 Please consult the Merlin Gerin catalogue - Low Voltage Distribution
3/6
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers
EnvironmentCircuit-breaker type GV2 ME GV2 P GV3 ME GV7 R
Conforming to standards IEC 60947-1, 60947-2, 60947-4-1, EN 60204, UL 508, CSA C22-2 n° 14, NF C 63-650, 63-120, 79-130, VDE 0113, 0660
IEC 60947-2, 60947-4-1, NF EN, BS EN, DIN EN 60 947.
IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, EN 60947-4-1, NF C 63-650, NF C 63-120, 79-130,VDE 0113, 0660
Product certifications CSA, CEBEC, GOST, TSE, UL, BV, GL, LROS , DNV, PTB, EZU, SETI, RINA,
CSA, UL, PTB, EZU, GOST, TSE, DNV, LROS, GL, BV, RINA
CSA, UL, LROS DNV, UL
Protective treatment “TH” “TC” “TC”
Degree of protectionconforming to IEC 60529
Open- mounted
IP 20 IP 20 IP 405with terminal shields
In enclosure GV2 Mp01: IP 41 GV2 Mp02: IP 55
– GV3 CE01: IP 55 –
Shock resistanceconforming to IEC 60068-2-27
30 gn -11 ms 22 gn -20 ms 30 gn -11 ms
Vibration resistanceconforming to IEC 60068-2-6
5 gn (5…150 Hz) 2.5 gn (0…25 Hz) 2.5 gn (25 Hz)
Ambient air temperature Storage °C - 40…+ 80 - 40…+ 80 - 40…+ 80 - 55…+ 95
Operation Open- mounted
°C - 20…+ 60 - 20…+ 60 - 20…+ 60 - 25… + 70
In enclosure °C - 20…+ 40 – - 20…+ 40 –
Temperature compensation Open- mounted
°C - 20…+ 60 - 20…+ 60 - 20…+ 60 - 25… + 55 (1)
In enclosure °C - 20…+ 40 – - 20…+ 40 –
Flame resistanceconforming to IEC 60695-2-1
°C 960 960 960
Maximum operating altitude m 2000 3000 2000
Suitable for isolationconforming to IEC 60947-1 § 7-1-6
Yes – Yes
Resistance to mechanical impact J 0.5 0.5 0.5 0.5
In enclosure: 6 – – –
Sensitivity to phase failure Yes, conforming to IEC 60947-4-1 § 7-2-1-5-2
Technical characteristicsCircuit-breaker type GV2
MEGV2 P
GV2 RT
GV3 ME06…ME25
GV3 ME40…ME63
GV3 ME80
GV7 Rp20... Rp100
GV7 Rp150
GV7 Rp220
Utilisation category Conforming to IEC 60947-2 A A A
Conforming to IEC 60947-4-1 AC-3 AC-3 AC-3
Rated operational voltage (Ue) conforming to IEC 60947-2
V 690 690 690
Rated insulation voltage (Ui)
Conforming to IEC 60947-2 V 690 690 750
Conforming to CSA C22-2 n° 14, UL 508
V 600 600 (B600) 600
Rated operational frequencyconforming to IEC 60947-2
Hz 50/60 50/60 50/60
Rated impulse withstand voltage (U imp) conforming to IEC 60947-2
kV 6 6 8
Total power dissipated per pole W 2.5 3 6 8 5 8.7 14.5
Mechanical durability(C.O.: Closing - Opening)
C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000
Electrical durabilityfor AC-3 duty
440 V In/2 C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000
440 V In C.O. – – – – 30 000 20 000 10 000
Duty class (maximum operating rate) C.O./h 25 25 25
Maximum conventional rated thermal current (Ith) conforming to IEC 60947-4-1
A 0.16… 32
0.16… 32
0.40… 23
1.6… 25
40… 63
80 12… 100
150 220
Rated duty conforming to IEC 947-4-1 Continuous duty
(1) For operation up to 70 °C, please consult your Regional Sales Office.
References :pages 3/44 to 3/49
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/7
3
Characteristics (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers
Mounting characteristicsOperating positionWithout derating, in relation to normal vertical mounting plane
Side view Front view
GV3 ME: preferably vertical
Connection characteristicsCircuit-breaker type GV2 ME GV2 P GV3 ME06…ME20 GV3 ME25…ME80
Connection to screw clamp terminalsNumber of conductors and c.s.a.
Min. Max. Min. Max. Min. Max. Min. Max.Solid cable mm2 2 x 1 2 x 6 2 x 1 2 x 6 2 x 1 2 x 6 1 x 2.5 1 x 35
Flexible cable without cable end
mm2 2 x 1.5 2 x 6 2 x 1.5 2 x 6 2 x 1 2 x 6 1 x 2.5 2 x 16
Flexible cable with cable end
mm2 2 x 1 2 x 4 2 x 1 2 x 4 2 x 1 2 x 4 1 x 2.5 2 x 16
Tightening torque N.m 1.7 1.7 1.7 1.7 1.7 1.7 5 5
Connection to spring terminalsNumber of conductors and c.s.a.
Solid cable mm2 2 x 1 (1) 2 x 6 – – – – – –
Flexible cable without cable end
mm2 2 x 1.5 (1) 2 x 4 – – – – – –
Connection to bars,cables with lugs or bare cables
Circuit-breaker type GV7 Rp20...Rp100 GV7 Rp150 GV7 Rp220Pitch Without spreaders mm 35 35 35
With spreaders mm 45 45 45
Bars or cables with lugs e mm y 6 y 6 y 6
L mm y 25 y 25 y 25
d mm y 10 y 10 y 10
Screws M6 M8 M8
Tightening torque N.m 10 15 15
Bare cables (copper or aluminium)with connectors
Height (h) mm 20 20 20
C.s.a. mm2 1.5...95 1.5...95 1.5...185
Tightening torque N.m 15 15 15
(1) For cross-sections 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.
e
d
L
d
L
h
References :pages 3/44 to 3/49
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/8
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakersGV2 ME and GV2 P
Breaking capacity of GV2 ME and GV2 PCircuit-breaker type GV2 ME GV2 P
01 to 06
07 08 10 14 16 20 21 & 22
32 01 to 06
07 08 10 14 16 20 21 & 22
32
Rating A 0.1 to 1.6
2.5 4 6.3 10 14 18 23 & 25
32 0.1 to 1.6
2.5 4 6.3 10 14 18 23 & 25
32
Breaking capacityconforming to IEC 60947-2
230/240 V Icu kA g g g g g g g 50 50 g g g g g g g g g
Ics % (1) g g g g g g g 100 100 g g g g g g g g g
400/415 V Icu kA g g g g g 15 15 15 10 g g g g g g 50 50 50
Ics % (1) g g g g g 50 50 40 50 g g g g g g 50 50 50
440 V Icu kA g g g 50 15 8 8 6 6 g g g g g 50 20 20 20
Ics % (1) g g g 100 100 50 50 50 50 g g g g g 75 75 75 75
500 V Icu kA g g g 50 10 6 6 4 4 g g g g 50 42 10 10 10
Ics % (1) g g g 100 100 75 75 75 75 g g g g 100 75 75 75 75
690 V Icu kA g 3 3 3 3 3 3 3 3 g 8 8 6 6 6 4 4 4
Ics % (1) g 75 75 75 75 75 75 75 75 g 100 100 100 100 100 100 100 100
Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2
230/240 V aM A g g g g g g g 80 80 g g g g g g g g g
gG A g g g g g g g 100 100 g g g g g g g g g
400/415 V aM A g g g g g 63 63 80 80 g g g g g g 100 100 100
gG A g g g g g 80 80 100 100 g g g g g g 125 125 125
440 V aM A g g g 50 50 50 50 63 63 g g g g g 50 63 80 80
gG A g g g 63 63 63 63 80 80 g g g g g 63 80 100 100
500 V aM A g g g 50 50 50 50 50 50 g g g g 50 50 50 50 50
gG A g g g 63 63 63 63 63 63 g g g g 63 63 63 63 63
690 V aM A g 16 25 32 32 40 40 40 40 g 20 25 40 40 50 50 50 50
gG A g 20 32 40 40 50 50 50 50 g 25 32 50 50 63 63 63 63
g > 100 kA.(1) As % of Icu.
R e f e r e n c e s :p a g e s 3 / 4 4 t o 3 / 4 9
D i m e n s i o n s :p a g e s 3 / 6 2 t o 3 / 6 7
S c h e m e s :p a g e s 3 / 6 8 a n d 3 / 6 9
3/9
3
Characteristics (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakersGV2 ME and GV2 P
Breaking capacity of GV2 ME and GV2 P (used in association with current limiter GV1 L3)Circuit-breaker type GV2 ME
01 to 06 07 08 10 14 16 20 21 22 32Rating A 0.1 to
1.62.5 4 6.3 10 14 18 23 25 32
Breaking capacityconforming to IEC 60947-2
230/240 V Icu kA g g g g g g g g g g
Ics % (1) g g g g g g g g g g
400/415 V Icu kA g g g g g 100 100 100 100 100
Ics % (1) g g g g g 50 50 40 40 40
440 V Icu kA g g g g g 50 20 20 20 20
Ics % (1) g g g g g 75 75 75 75 75
500 V Icu kA g g g g 50 42 10 10 10 10
Ics % (1) g g g g 100 100 75 75 75 75
Circuit-breaker type GV2 P01 to 06 07 08 10 14 16 20 21 22 32
Rating A 0.1 to 1.6
2.5 4 6.3 10 14 18 23 25 32
Breaking capacityconforming to IEC 60947-2
230/240 V Icu kA g g g g g g g g g g
Ics % (1) g g g g g g g g g g
400/415 V Icu kA g g g g g g g g g g
Ics % (1) g g g g g g g g g g
440 V Icu kA g g g g g 100 100 100 100 100
Ics % (1) g g g g g 50 50 50 50 50
500 V Icu kA g g g g 100 100 100 100 100 100
Ics % (1) g g g g 50 50 50 50 50 50
690 V (3) Icu = Ics kA g 50 50 50 50 50 50 50 50 50
Circuit-breaker type GV2 ME01 to 06 07 08 10 14 16 20 21 22 32
Rating A 0.1to 1.6
2.5 4 6.3 10 14 18 23 25 32
Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables)
Minimum c.s.a. protected at 40 °C at Isc max.
1 mm2 p p p y 10 kA y 6 kA (2) (2) (2) (2) (2)
1.5 mm2 p p p y 20 kA y 10 kA (2) (2) (2) (2) (2)
2.5 mm2 p p p p p p p p p (2)
4…6 mm2 p p p p p p p p p p
g > 100 kAp Cable c.s.a. protected(1) As % of Icu(2) Cable c.s.a. not protected(3) With limiter LA9 LB920
References :pages 3/44 to 3/49
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/10
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME
Breaking capacity of GV3 MECircuit-breaker type GV3 ME
06 & 07 08 10 14 20 25 40 63 80Rating A 1.6 & 2.5 4 6 10 16 25 40 63 80
Breaking capacityconforming to IEC 60947-2
230/240 V Icu kA 100 100 100 100 100 100 100 100 100
Ics % (1) 100 100 100 100 100 100 100 100 100
400/415 V Icu kA 100 100 100 100 100 100 35 35 15
Ics % (1) 100 100 100 100 50 50 50 50 50
440 V Icu kA 100 100 100 25 25 25 25 25 10
Ics % (1) 100 100 100 100 60 60 60 60 60
500 V Icu kA 100 100 100 8 8 8 8 8 4
Ics % (1) 100 100 100 100 100 100 75 75 100
690 V Icu kA 100 4 4 4 4 4 4 4 2
Ics % (1) 100 100 100 100 100 100 75 75 100
Associated fuses, if requiredif lsc > breaking capacity Icu
230/240 V aM A g g g g g g g g g
gG A g g g g g g g g g
400/415 V aM A g g g g g g 250 315 315
gG A g g g g g g 315 400 400
440 V aM A g g g 125 160 200 250 315 315
gG A g g g 160 200 250 315 400 400
500 V aM A g g g 80 100 125 160 200 200
gG A g g g 100 125 160 200 250 250
690 V aM A g 40 50 80 100 125 160 200 200
gG A g 50 63 100 125 160 200 250 250
g Fuse not required: breaking capacity Icn > Isc.(1) As % of Icu.
References :pages 3/44 to 3/49
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/11
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakersGV7 R
Breaking capacity of GV7 RCircuit-breaker type GV7
RE20…RE100 RS20…RS100 RE150 RS150 RE220 RS220Rating A 12…20 to 60…100 90…150 90…150 132…220 132…220
Breaking capacityconforming to IEC 60947-2
230/240 V lcu kA 85 100 85 100 85 100
Ics % (1) 100 100 100 100 100 100
400/415 V Icu kA 36 70 35 70 35 70
Ics % (1) 100 100 100 100 100 100
440 V Icu kA 36 65 35 65 35 65
Ics % (1) 100 100 100 100 100 100
500 V Icu kA 18 50 30 50 30 50
Ics % (1) 100 100 100 100 100 100
690 V Icu kA 8 10 8 10 8 10
Ics % (1) 100 100 100 100 100 100
Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables)
Minimum c.s.a. protected at 40 °C at Isc max.
4 mm2 y 6 kA y 6 kA (2) (2) (2) (2)
6 mm2 p y 25 kA (2) (2) (2) (2)
10…50 mm2 p p p p p p
p Cable c.s.a. protected.
(1) As % of Icu.(2) Cable c.s.a. not protected.
References :pages 3/44 to 3/49
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/12
3
Characteristics 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 LE and GV2 L
EnvironmentType GV2 LE GV2 L
Conforming to standards IEC 60947-1, 60947-2, EN 60204, NF C 63-650, NF C63-120, 79-130, VDE 0113, 0660, UL 1077.
Product certifications UL, CSA BV, GL, LROS, DNV, RINA, UL, CSA
Protective treatment “TH” “TH”
Shock resistance Conforming to IEC 60068-2-27 30 gn 30 gn
Vibration resistance Conforming to IEC 60068-2-6 5 gn (5 to 150 Hz) 5 gn (5 to 150 Hz)
Ambient air temperature Storage °C - 40…+ 80 - 40…+ 80
Operation °C - 20…+ 60 - 20…+ 60
Flame resistance Conforming to IEC 60695-2-1 °C 960 960
Maximum operating altitude m 2000 2000
Operating position
CablingNumber of conductors and c.s.a.
Max. Min. Max. Min.Solid cable mm2 2 x 6 2 x 1 2 x 6 2 x 1
Flexible cable without cable end mm2 2 x 6 2 x 1.5 2 x 6 2 x 1.5
Flexible cable with cable end mm2 2 x 4 2 x 1 2 x 4 2 x 1
Suitable for isolation Conforming to IEC 60947-1 § 7-1-6
Yes Yes
Tightening torque N.m 1.7 1.7
Resistance to mechanical impact J 0.5 0.5
Utilisation category Conforming to IEC 60947-2 A A
Conforming to IEC 60947-4-1 AC-3 AC-3
Rated operational voltage (Ue)
Conforming to IEC 60947-2 V 690 690
Rated insulation voltage (Ui)
Conforming to IEC 60947-2 V 690 690
Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60
Rated impulse withstand voltage (U imp)
Conforming to IEC 60947-2 kV 6 6
Total power dissipated per pole W 1.8 1.8
Mechanical durability(C.O. : Closing - Opening)
C.O. 100 000 100 000
Electrical durability For AC-3 duty C.O. 100 000 100 000
Duty class(maximum operating rate)
C.O./h 40 40
Rated duty Conforming to IEC 60947-4-1 Continuous duty Continuous duty
References :pages 3/50 and 3/51
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/13
3
Characteristics (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 LE and GV2 L
Breaking capacity of GV2 LE and GV2 LType GV2 LE GV2 L
03 to 06
07 08 10 14 16 20 22 32 03 to 06
07 08 10 14 16 20 22 32
Rating A 0.4 to 1.6
2.5 4 6,3 10 14 18 25 32 0.4 to1
2.5 4 6,3 10 14 18 25 32
Breaking capacityconforming to IEC 60947-2
230/240 V Icu kA g g g g g g g 50 50 g g g g g g g 50 50
Ics % (1) g g g g g g g 100 100 g g g g g g g 100 100
400/415 V Icu kA g g g g g 15 15 15 10 g g g g g 50 50 50 50
Ics % (1) g g g g g 50 50 40 50 g g g g g 50 50 50 50
440 V Icu kA g g g 50 15 8 8 6 6 g g g g 20 20 20 20 20
Ics % (1) g g g 100 100 50 50 50 50 g g g g 75 75 75 75 75
500 V Icu kA g g g 50 10 6 6 4 4 g g g g 10 10 10 10 10
Ics % (1) g g g 100 100 75 75 75 75 g g g g 100 75 75 75 75
690 V Icu kA g 3 3 3 3 3 3 3 3 g 4 4 4 4 4 4 4 4
Ics % (1) g 75 75 75 75 75 75 75 75 g 100 100 100 100 100 100 100 100
Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2 amendment 1
230/240 V aM A g g g g g g g 80 80 g g g g g g g 100 100
gG A g g g g g g g 100 100 g g g g g g g 125 125
400/415 V aM A g g g g g 63 63 80 80 g g g g g 80 100 100 100
gG A g g g g g 80 80 100 100 g g g g g 100 125 125 125
440 V aM A g g g 50 50 50 50 63 63 g g g g 50 63 80 80 80
gG A g g g 63 63 63 63 80 80 g g g g 63 80 100 100 100
500 V aM A g g g 50 50 50 50 50 50 g g g g 50 50 50 50 50
gG A g g g 63 63 63 63 63 63 g g g g 63 63 63 63 63
690 V aM A g 16 25 32 32 40 40 40 40 g 20 25 40 40 50 50 50 50
gG A g 20 32 40 40 50 50 50 50 g 25 32 50 50 63 63 63 63
Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables) Minimum c.s.a. protected at 40 °C and at Isc max.
1 mm2 kA p p p y10 y 6 (2) (2) (2) (2) p p p y10 y 6 (2) (2) (2) (2)
1.5 mm2 kA p p p y20 y 10 (2) (2) (2) (2) p p p y20 y10 (2) (2) (2) (2)
2.5 mm2 p p p p p p p p (2) p p p p p p p p (2)
4…6 mm2 p p p p p p p p p p p p p p p p p p
g > 100 kApCable c.s.a. protected
(1) As % of Icu(2) Cable c.s.a. not protected
References :pages 3/50 and 3/51
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/14
3
Characteristics 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
EnvironmentConforming to standards IEC 60947-2. EN 60-204
Protective treatment “TC”
Degree of protection Conforming to IEC 60529
GK3 EF basic unit: IP 20
Shock resistance Conforming to IEC 60068-2-27
22 gn for 20 ms
Vibration resistance Conforming to IEC 60068-2-6
2.5 gn (0…25 Hz)
Flame resistance Conforming to IEC 60695-2-1
Conforms for 960 °C
Ambient air temperature Storage °C - 40…+ 80
Operation °C - 20… + 70 open-mounted
Maximum operating altitude m 3000
Operating position Any
Cabling Solid cable mm2 1 x 2.5 to 35 conductor
Flexible cable without cable end
mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors
Flexible cable with cable end
mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors
Tightening torque N.m 5
Suitable for isolation Yes, conforming to IEC 60947-1§7-1-6
Technical characteristicsRated insulation voltage (Ui)
Conforming to IEC 60947-2 V 750
Rated impulse withstand voltage (U imp)
Conforming to IEC 60947-2 kV 10
Rated operational voltage (Ue)
Conforming to IEC 60947-2 V 690
Rated operational frequency Hz 50…60
Electrical durability for AC-23/400 V duty(C.O.: Closing - Opening)
C.O. 1500
Mechanical durability C.O. 20 000
Maximum operating rate C.O./h 40
Operating threshold of magnetic trips
About 13 times the rating of the GK3 EF selected (non adjustable threshold)
Utilisation category Conforming to IEC 60947-2 A
References :pages 3/50 and 3/51
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/15
3
Characteristics (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Type GK3 EF40 GK3 EF65 GK3 EF80Breaking capacity of the circuit-breaker only or of thecircuit-breaker combined with a thermal overload relay
230/240 V Icu kA 100 50 50
Ics % (1) 20 40 40
400/415 V Icu kA 50 35 35
Ics % (1) 30 25 25
440 V Icu kA 30 25 25
Ics % (1) 30 30 30
500 V Icu kA 20 15 15
Ics % (1) 30 30 30
690 V Icu kA 6 6 6
Ics % (1) 60 50 50
Associated fuses (if required) for use with circuit-breaker only or circuit-breaker combined with a thermal overload relayif lsc > breaking capacity
230/240 V aM A 160 200 200
gG A 250 315 315
400/415 V aM A 160 200 200
gG A 200 250 250
440 V aM A 160 160 160
gG A 200 250 250
500 V aM A 125 160 160
gG A 160 200 200
690 V aM A 100 125 125
gG A 125 160 160
Use of circuit-breakers without fuses Minimum cable length (in metres) limiting the maximum short-circuit current to 35 kA maximum, so enabling breakers GK3 EF to be used without fuses
Cable c.s.a. mm2 y 25 35 50 70 95 120
Isc (rms) 3-phase, incoming (Ue = 400 V)
50 kA m 5 6 8 10 13 15
45 kA m 5 5 7 8 10 12
40 kA m 5 5 5 5 8 9
37 kA m 5 5 5 5 5 5
(1) As % of Icu
References :pages 3/50 and 3/51
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/16
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic and magnetic motor circuit-breakers GV2Auxiliary contacts
Type of contacts Instantaneous auxiliary GV AN, GV AD
Fault signalling GV AD, GV AM11 (1)
Instantaneous auxiliary GV AE
Rated insulation voltage (Ui) (associated insulation coordination)
Conforming to IEC 60947-1 V 690 690 250 (690 in relation to main circuit)
Conforming to CSA C22-2 n° 14and UL 508
V 600 300 300
Conventional thermal current (Ith)
Conforming to IEC 60947-5-1 A 6 2.5 2.5
Conforming to CSA C22-2 n° 14and UL 508
A 5 1 1
Mechanical durability(C.O. : Closing - Opening)
C.O. 100 000 1000 100 000
Operational power and currentconforming to IEC 60947-5-1 a.c. operation
AC-15/100 000 C.O. AC-14/1000 C.O. AC-15/100 000 C.O.
Rated operational voltage(Ue)
V 48 110 127
230 240
380 415
440 500 690 24 48 110 127
230 240
24 48 110 127
230 240
Operational power,normal conditions
VA 300 500 720 850 650 500 400 36 48 72 72 48 60 120 120
Occasional breaking and making capacities, abnormal conditions
kVA 3 7 13 15 13 12 9 0.22 0.3 0.45 0.45 0.48 0.6 1.27 2.4
Rated operational current(Ie)
A 6 4.5 3.3 2.2 1.5 1 0.6 1.5 1 0.5 0.3 2 1.25 1 0.5
Operational power and currentconforming to IEC 60947-5-1 d.c. operation
DC-13/100 000 C.O. DC-13/1000 C.O. DC-13/100 000 C.O.
Rated operational voltage(Ue)
V 24 48 60 110 240(2)
– – 24 48 60 – 24 48 60 –
Operational power,normal conditions
W 140 240 180 140 120 – – 24 15 9 – 24 15 9 –
Occasional breaking and making capacities, abnormal conditions
W 240 360 240 210 180 – – 100 50 50 – 100 50 50 –
Rated operational current(Ie)
A 6 5 3 1.3 0.5 – – 1 0.3 0.15 – 1 0.3 0.15 –
Low level switching reliability of contact GV A: number of failures for “n” million operating cycles(17 V-5 mA): = 10-6
Minimum operational conditionsd.c. operation
V 17
mA 5
Short-circuit protection By GB2 CBpp circuit-breaker (rating according to operational current for Ue y 415 V) or by gG fuse 10 A max
GB2 CB06 or gG fuse, 10 A max
Cabling, screw clamp terminals
Number of conductors 1 2Solid cable mm2 1…2.5 1…2.5
Flexible cable without cable end mm2 0.75…2.5 0.75…2.5
Flexible cable with cable end mm2 0.75…1.5 0.75…1.5
Tightening torque N.m 1.4 max 1.4 max
Cabling, spring terminals GV AN only
Flexible cable without cable end mm2 0.75…2.5 0.75…2.5 – 0.75…1.5
Operation of instantaneous auxiliary contacts Operation of fault signalling contacts
GV AM11Change of state following tripping on short-circuit.
GV AD10pp and GV AD01ppChange of state following tripping on short-circuit. overload or undervoltage.
(1) For application example of fault signalling contact and short-circuit signalling contact, see page 3/68.(2) Add an RC circuit type LA4 D to the load terminals, see page 24511/5.
0 1
FF
FO
O
O
F
F
F
F
O
F
Power pole
Contact openContact closed
References :page 3/53
Dimensions, schemes :pages 3/62 to 3/73
3/17
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 MEAuxiliary contacts
Type of contacts Instantaneous auxiliary contactsGV3 A01…A07
Fault signalling contacts GV3 A08 and A09
Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 690
Conforming to CSA C22-2 n° 14, UL 508
V 600 (B600) 600 (B600)
Conventional rated thermal current (Ith)
Conforming to IEC 60947-5-1 A 6 6
Conforming to CSA C22-2 n° 14, UL 508
A 5 (B600) 5 (B600)
Mechanical durability(C.O.: Closing - Opening)
C.O. 100 000 1000
Operational power and currentconforming to IEC 60947-5-1 a.c. operation
Rated operational voltage(Ue)
V 48 110 127
220 240
380 415
440 500 690 48 110 127
220 240
380 415
440 500 690
Operational power AC-11/100 000 C.O. AC-11/1000 C.O.
VA 350 500 800 850 700 700 400 240 460 800 850 450 450 200
Occasional breaking and making capacities
kVA 4 12 20 20 15 15 10 2.4 8 12 15 12 12 8
Operational current (Ie) A 6 4.5 3.5 2.2 1.5 1.5 0.6 5 3.6 3.5 2.2 1 1 0.3
Operational power and currentconforming to IEC 60947-5-1 d.c. operation
Rated operational voltage(Ue)
V 24 48 60 110 220 24 48 60 110 220
Operational power DC-11/100 000 C.O. DC-11/1000 C.O.
W 180 240 180 140 120 120 120 90 70 60
Occasional breaking and making capacities
W 240 360 240 210 180 180 180 135 105 90
Operational current (Ie) A 6 5 3 1.3 0.5 5 2.5 1.5 0.7 0.3
Short-circuit protection By GB2 CB08 circuit-breaker or gG fuse, 6A max
Cabling Number of conductors 1 2
Solid cable mm2 1…2.5 1…2.5
Flexible cable without cable end mm2 0.75…2.5 0.75…2.5
Flexible cable with cable end mm2 0.75…2.5 0.75…1.5
Contact operation GV3 A08 and A09 change state following tripping on short-circuit or overload0 1
OF
FF
FF
O
FF
F
FF
GV3 A01, A07
GV3 A02
GV3 A03
GV3 A05
GV3 A06
Power pole
Contact openContact closed
References :page 3/55
Dimensions, schemes :pages 3/62 to 3/73
3/18
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7Auxiliary contacts
Auxiliary contact characteristicsType of contacts GV7 AE11 GV7 AB11
Rated insulation voltage (Ui) (associated insulation coordination)
Conforming to IEC 60947-1 V 690 690
Conventional thermal current (Ith)
Conforming to IEC 60947-5-1 A 6 6
Mechanical durability(C.O.: Closing - Opening)
C.O. 50 000 50 000
Operational currentconforming to IEC 60947-5-1 a.c. operation
AC-12 or AC-15. 50 000 C.O. AC-12 or AC-15. 50 000 C.O.
Rated operational voltage (Ue)
V 24 48 110 230/ 240
380/ 415
440 690 24 48 110 230/ 240
380/ 415
440 690
Rated operational current (Ie)
AC-12 A 6 6 6 6 6 6 6 5 5 5 5 5 5 5
AC-15 A 6 6 5 4 3 3 0.1 5 5 4 3 2.5 2.5 0.1
Operational currentconforming to IEC 60947-5-1 d.c. operation
DC-12 or DC-14. 50 000 C.O. DC-12 or DC-14. 50 000 C.O.
Rated operational voltage (Ue)
V 24 48 110 250 24 48 110 250
Rated operational current (Ie)
DC-12 A 2.5 2.5 0.8 0.3 2 2 0.5 –
DC-14 A 1 0.2 0.5 0.03 0.5 0.1 0.25 –
Minimum operational conditions V 17 12
d.c. operation mA 5 5
Short-circuit protection By GB2 CBpp circuit-breaker(rating according to operational current for Ue y 415 V) or gG fuse, 10 A max.
Cabling Solid cable mm2 1 x 1.5 conductor 1 x 1.5 conductor
Flexible cable without cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor
Flexible cable with cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor
References :page 3/57
Dimensions, schemes :pages 3/62 to 3/73
3/19
3
Characteristics 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Characteristics of Start-Stop and fault signalling contactsRated insulation voltage (Ui)
Conforming to IEC 60947-1 V 500
Rated operational voltage (Ue)
Conforming to IEC 60947-1 V 500
Conventional thermal current (Ith)
Conforming to IEC 60947-5-1 A 6
Operational power and currentconforming to IEC 60947-5-1 a.c. operation(C.O.: Closing - Opening)
AC-15. 20 000 C.O.Rated operational voltage (Ue) V 48 110/127 220/240 380/415 440 500
Operational power VA 360 500 800 850 700 700
Occasional breaking and making capacities
VA 4000 12 000 20 000 20 000 15 000 15 000
Rated operational current (Ie) A 6 4.5 3.5 2.2 1.5 1.5
Operational power and currentconforming to IEC 60947-5-1 d.c. operation(C.O.: Closing - Opening)
DC-13. 1000 C.O.
Rated operational voltage (Ue) V 24 48 60 110 220
Operational power W 180 240 180 140 120
Occasional breaking and making capacities
W 240 280 240 210 180
Rated operational current (Ie) A 6 5 3 1.3 0.5
Short-circuit protection Conforming to IEC 60947-5-1 By GB2 CB08 circuit-breaker or gG fuse, 6A max
Cabling Solid cable mm2 1 x 1…4 conductor
Flexible cable without cable end mm2 1 x 2.5 conductor
Flexible cable with cable end mm2 1 x 1…2.5 conductor or 2 x 1…2.5 conductors
Tightening torque N.m 0.8
References :page 3/55
Dimensions, schemes :pages 3/62 to 3/73
3/20
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakersElectric trips
Characteristics of electric tripsType of circuit-breaker GV2 ME, GV2 P GV3 ME GV7 RType of trip GV AU GV AX (1) GV AS GV3 B GV3 D GV7 AU GV7 AS
Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 500 690 690 690 690 690
Conforming to CSA C22-2 n° 14, UL 508
V 600 – 600 600 (B600) 600 (B600) 600 600
Operational voltage Conforming to IEC 60947-1 V 0.85…1.1 Un 0.7…1.1 Un
0.8…1.1 Un 0.85…1.1 Un
0.7…1.1 Un
Drop-out voltage V 0.7…0.35 Un 0.75…0.2 Un
0.7…0.35 Un 0.35…0.7 Ue
0.2…0.75 Ue
Inrush consumption a VA 12 14 12 < 10
c W 8 10.5 7 < 5
Sealed consumption a VA 3.5 5 7 < 5
c W 1.1 1.6 2.5 < 5
Operating time Conforming to IEC 60947-1 From the moment the voltage reaches its operational value until opening of the circuit-breaker.
ms 10…15 10 15 < 50
On-load factor 100 % 100 % 100 %
Cabling Number of conductors 1 or 2 1 or 2 1
Solid cable mm2 1…2.5 1…2.5 1.5
Flexible cable without cable end mm2 0.75…2.5 0.75…2.5 1.5
Flexible cable with cable end mm2 0.75…1.5 0.75…2.5 1
Tightening torque N.m 1.4 max 1.2 1.2
Mechanical durability(C.O.: Closing - Opening)
C.O. 100 000 50 % of the mechanical durability of the circuit-breaker
(1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only, see page 3/68.
References :pages 3/53 to 3/57
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/21
3
Characteristics 3 TeSys protection components 3
Thermal-magnetic and magnetic motor circuit-breakers GV2Accessories
Characteristics of 3-pole busbars GV2 GpppRated insulation voltage (Ui)
Conforming to IEC 60947-1 V 690
Conventional thermal current (Ith)
Conforming to IEC 60439-1 A 63
Permissible peak current( I peak)
kA 11
Permissible thermal limit(I2t)
kA2s 104
Degree of protection Conforming to IEC 60529 IP 20
Characteristics of terminal blocks GV2 G05 and GV1 G09Rated insulationvoltage (Ui)
Conforming to IEC 60947-1 V 690
Conventional thermal current (Ith)
Conforming to IEC 60439-1 A 63
Degree of protection Conforming to IEC 60529 IP 20
Cabling Solid cable mm2 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 conductors
Flexible cable without cable end mm2 1 x 1.5 to 25 conductor or 2 x 2.5 to 10 conductors
Flexible cable with cable end mm2 1 x 1.5 to 16 conductor or 2 x 1.5 to 4 conductors
Tightening torque Connector N.m 2.2
Screw clamp N.m 1.7
Characteristics of current limiters (GV2 ME and GV2 P)Type GV1 L3 LA9 LB920
Rated insulation voltage (Ui)
Conforming to IEC 60947-1 V 690 690
Conventional thermal current (Ith)
Conforming to IEC 60947-1 A 63 63
Operating threshold rms current A 1500 (non adjustable threshold) 1000 (non adjustable threshold)
Cabling 1 conductor 2 conductors 1 conductor 2 conductors
Solid cable mm2 1.5…25 1.5…10 1.5…25 1.5…10
Flexible cable without cable end mm2 1.5…25 2.5…10 1.5…25 1.5…10
Flexible cable with cable end mm2 1.5…16 1.5… 4 1.5…16 1.5… 4
Tightening torque N.m 2.2
References :pages 3/53 and 3/59
Dimensions, schemes :pages 3/62 to 3/73
3/22
3
Curves 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
Thermal-magnetic tripping curves for GV2 ME and GV2 PAverage operating time at 20 °C related to multiples of the setting current:
1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state
0,001
0,1
1
10
100
0,01
1 1,5 10 100
1000
10 000
32
1
Time (s)
x the setting current (Ir)
References :pages 3/45 and 3/46
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/23
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
Current limitation on short-circuit for GV2 ME and GV2 P (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current2 24-32 A3 20-25 A4 17-23 A5 13-18 A6 9-14 A7 6-10 A8 4-6.3 A9 2.5-4 A10 1.6-2.5 A11 1-1.6 A12 Limit of rated ultimate breaking capacity on short-circuit of GV2 ME (14, 18, 23 and 25 A ratings)
1
6
5
4
3
7
8
9
10
11
2
100
10
1
0,10,1 1 10 100
cos
= 0
.95
= 0.
9
= 0.
8
= 0.
7=
0.5
= 0.
3
= 0.
25
15 (12)
Limited peak current (kA)
Prospective Isc (kA)
References :pages 3/45 and 3/46
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/24
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME
Thermal limit on short-circuit for GV2 METhermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 24-32 A2 20-25 A3 17-23 A4 13-18 A5 9-14 A6 6-10 A7 4-6.3 A8 2.5-4 A9 1.6-2.5 A10 1-1.6 A
100
10
1
0,1
0,010,1 1 10 100
345
6
7
8
9
10
21
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :pages 3/45 and 3/46
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/25
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakersGV2 P
Thermal limit on short-circuit for GV2 PThermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 24 -32 A1 20-25 A2 17-23 A3 13-18 A4 9-14 A5 6-10 A6 4-6.3 A7 2.5-4 A8 1.6-2.5 A9 1-1.6 A
100
10
1
0,1
0,010,1 1 10 100
123
4
5
6
7
8
9
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :pages 3/45 and 3/46
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/26
3
Curves 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME
Thermal-magnetic tripping curvesAverage operating time at 20 °C related to multiples of the setting current:
1 3 poles from cold state, 1.6…16 A rating2 3 poles from hot state, 1.6…16 A rating3 3 poles from cold state, 25…80 A rating4 3 poles from hot state, 25…80 A rating
0,001
0,1
1
10
100
0,01
1 10 100
1000
10 000
4
2
3
1
Time (s)
x the setting current (Ir)
References :page 3/47
Dimensions :page 3/65
Schemes :page 3/69
3/27
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME
Current limitation on short-circuit (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current2 56-80 A3 40-63 A4 25-40 A5 16-25 A6 10-16 A7 6-10 A8 4-6 A9 2.5-4 A10 1.6-2.5 A11 1-1.6 A
1
4
3
2
100
10
1
0,10,1 1 10 100
= 0.
9
= 0.
8
= 0.
7=
0.5
= 0.
3
= 0.
25
15
56
7
9
8
10
11
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/47
Dimensions :page 3/65
Schemes :page 3/69
3/28
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME
Thermal limit on short-circuitThermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 56 -80 A2 40-63 A3 25-40 A4 16-25 A5 10-16 A6 6-10 A7 4-6 A8 2.5-4 A9 1.6-2.5 A
100
10
1
0,10,1 1 10 10015
321
45
6
7
8
9
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :page 3/47
Dimensions :page 3/65
Schemes :page 3/69
3/29
3
Curves 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Thermal-magnetic tripping curves for GV7 RAverage operating time at 20 °C related to multiples of the setting current:
1 Cold state curve2 Cold state curve3 12…14 Ir
In the event of total phase failure, tripping occurs after 4 s ± 20 %
0,001
0,002
0,1
0,01
0,005
0,05
1
0,5
0,02
0,2
2
5
10
20
50
100
200
500
1000
2000
5000
10 000
102 3 4 7 10020 30 405 50 701
3
1
1,12
2
Time (s)
x the setting current (Ir)
References :page 3/48
Dimensions :pages 3/65 and 3/67
Schemes :page 3/69
3/30
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Current limitation on short-circuit (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc)
For GV7 RE only
1 GV7 RE2202 GV7 RE1503 GV7 RE100
For GV7 RS only
1 GV7 RS2202 GV7 RS1503 GV7 RS100
4102
5
7
60
20
10
50
100
30
3 4 6 10020 30 40 60
40
70
5 50
6
8
80
1
2
3
70
Limited peak current (kA)
Prospective Isc (kA)
4102
5
7
60
20
10
50
100
30
3 4 6 10020 30 40 60
40
70
5 50
1
2
3
6
8
80
70
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/48
Dimensions :pages 3/65 and 3/67
Schemes :page 3/69
3/31
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Thermal limit (3-phase 400/415 V)
Thermal limit
Sum of I2dt = f (prospective Isc)
For GV7 RE only
1 GV7 RE2202 GV7 RE1503 GV7 RE100
For GV7 RS only
1 GV7 RS2202 GV7 RS1503 GV7 RS100
2x104
102
3x104
5x104
2x106
2x105
105
106
107
5x106
3x105
3 4 6 10020 30 40 60
5x105
3x106
5 50 70
1
2
3
Sum of I2dt (A2s)
Prospective Isc (kA)
2x104
102
3x104
5x104
2x106
2x105
105
106
107
5x106
3x105
3 4 6 10020 30 40 60
5x105
3x106
5 50 70
1
2
3
Sum of I2dt (A2s)
Prospective Isc (kA)
References :page 3/48
Dimensions :pages 3/65 and 3/67
Schemes :page 3/69
3/32
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Current limitation on short-circuit (3-phase 690 V)
Dynamic stress
I peak = f (prospective Isc)
For GV7 RE only
1 GV7 RE2202 GV7 RE150 and GV7 RE100
For GV7 RS only
1 GV7 RS2202 GV7 RS150 and GV7 RS100
4102
5
6
30
10
8
20
50
40
3 4 6 205
12
7
9
Limited peak current (kA)
Prospective Isc (kA)
4102
5
6
30
10
8
20
50
40
3 4 6 205
12
7
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/48
Dimensions :pages 3/65 and 3/67
Schemes :page 3/69
3/33
3
Curves (continued) 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Thermal limit on short-circuit (3-phase 690 V)
Thermal stress limit
Sum of I2dt = f (prospective Isc)
For GV7 RE only
1 GV7 RE2202 GV7 RE150 and GV7 RE100
For GV7 RS only
1 GV7 RS2202 GV7 RS150 and GV7 RS100
102 3 4 6 205
2x106
2x105
105
106
3x105
5x105
3x106
1
2
8
Sum of I2dt (A2s)
Prospective Isc (kA)
102 3 4 6 205
2x106
2x105
105
106
3x105
5x105
3x106
1
2
Sum of I2dt (A2s)
Prospective Isc (kA)
References :page 3/48
Dimensions :pages 3/65 and 3/67
Schemes :page 3/69
3/34
3
Curves 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 RT
Thermal-magnetic tripping curves for GV2 RT
1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state
10
10 000
1
0,1
0,0011 10 100
1000
100
0,01
21
3
Time (s)
k x Ir
References :page 3/49
Dimensions :page 3/64
Schemes :page 3/68
3/35
3
Curves 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Tripping curves for GV2 L or GV2 LE combined with thermal overload relay LRD or LR2 KAverage operating time at 20 °C related to multiples of the setting current
1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state
10
10 000
1
0,1
0,0011 10 100
1000
100
0,01
32
1
Time (s)
x the setting current (Ir)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/36
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Current limitation on short-circuit for GV2 L and GV2 LE only (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current2 32 A3 25 A4 18 A5 14 A6 10 A7 6.3 A8 4 A9 2.5 A10 1.6 A11 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).
100
10
1
0,10,1 1 100
1
5
4
3
8
9
10
7
6
cos
= 0
.95
= 0.
9
= 0.
8=
0.7
= 0.
5
= 0.
3
= 0.
25
151011
2
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/37
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Current limitation on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 K (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current2 32 A3 25 A4 18 A5 14 A6 10 A7 6.3 A8 4 A9 2.5 A10 1.6 A11 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).
100
10
1
0,10,1 1 10 100
cos
= 0
.95
= 0.
9
= 0.
8
= 0.
7=
0.5
= 0.
3
= 0.
25
15 11
1
2
3
4
5
6
7
8
9
10
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/38
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Thermal limit on short-circuit for GV2 LE onlyThermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 32 A2 25 A3 18 A4 14 A5 10 A6 6.3 A7 4 A8 2.5 A9 1.6 A
100
10
1
0,1
0,010,1 1 10 100
1 2
3
4
5
6
7
8
9
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/39
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Thermal limit on short-circuit for GV2 L onlyThermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 25 A and 32 A2 18 A3 14 A4 10 A5 6.3 A6 4 A7 2.5 A8 1.6 A
100
10
1
0,1
0,010,1 1 10 100
1234
5
6
8
7
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/40
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Thermal limit on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 KThermal limit in kA2s in the magnetic operating zone
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 32 A (GV2 LE32)2 25 A and 32 A (GV2 L32)3 18 A4 14 A5 10 A6 6.3 A7 4 A8 2.5 A9 1.6 A10 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).
100
10
1
0,1
0,010,1 1 10 100
2
3
4
5
6
7
8
9
15
1
10
Sum of I2dt (kA2s)
Prospective Isc (kA)
References :page 3/50
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/41
3
Curves 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Tripping curves for GK3 combined with thermal overload relay LRD 33Average operating time at 20 °C without prior current flow
1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state
A Thermal overload relay protection zoneB GK3 protection zone
10
10 000
1
0,1
0,0011 10 100
1000
100
0,01
32
1
B
A
Time (s)
x the setting current (Ir)
References :page 3/51
Dimensions :page 3/72
Schemes :page 2457/5
3/42
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Current limitation on short-circuit for GK3 only (3-phase 400/415 V)
Dynamic stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V
1 Maximum peak current2 80 A3 65 A4 40 A
1
0,11 10 100
10
100
0,1
432
1
Limited peak current (kA)
Prospective Isc (kA)
References :page 3/51
Dimensions :page 3/72
Schemes :page 3/73
3/43
3
Curves (continued) 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Thermal limit on short-circuit for GK3 onlyThermal limit in A2s
Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
1 80 A2 65 A3 40 A
10
11 10 100
100
1000
0,1
3
2
1
Sum of I2dt (A2s)
Prospective Isc (kA)
References :page 3/51
Dimensions :page 3/72
Schemes :page 3/73
3/44
3
Presentation 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2, GV3 and GV7
GV2 ME, GV2 P, GV3 ME and GV7 R motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers specifically designed for the control and protection of motors, conforming to standards IEC 60947-2 and IEC 60947-4-1
These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2 ME can be supplied with spring terminal connections.These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact and is even more effective when conductors without cable ends are used. Each connection can take two independent conductors.
Control is manual and local when the motor circuit-breaker is used on its own.Control is automatic and remote when it is associated with a contactor.
Pushbutton control.Energisation is controlled manually by operating the Start button “I” 1.De-energisation is controlled manually by operating the Stop button “O” 2, or automatically by the thermal-magnetic protection elements or by a voltage trip attachment.
Control by rotary knob.
Control by rocker lever.Energisation is controlled manually by moving the knob or rocker lever to position “I” 1.De-energisation is controlled manually by moving the knob or rocker lever to position “O” 2.De-energisation due to a fault automatically places the knob or rocker lever in the “Trip” position 3. Re-energisation is possible only after having returned the knob or rocker switch to position “O”.
Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker.The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about 13 times the maximum setting current of the thermal trips.The thermal elements (overload protection) include automatic compensation for ambient temperature variations.The rated operational current of the motor is displayed by means of a graduated knob 4.
Personnel protection is also provided. All live parts are protected against direct finger contact.
The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltage condition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, since the Start button “I” has to be pressed to restart the motor.
With the addition of a shunt trip, de-energisation of the unit can be remotely controlled.
The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position “O” by up to 3 padlocks.
Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distance and indicate the actual position of the moving contacts by the position of the operators.
These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screw fixing or clip-on mounting on symmetrical, asymmetrical or combination rails.
Connection
Operation
IO 1
2
4
GV2 ME
O I12
4
GV3 ME
1
2
4
3
GV2 P
O 23
1
GV7 R
GV2 ME with screw clamp connections
5338
86
GV2 ME with spring terminal connections
5338
87
GV2 P
5338
88
GV3 ME
5338
89
GV7 R
5338
90
GV2 ME and GV3 ME
GV2 P
GV7 R
Protection of motors and personnel
Special features
Characteristics :pages 3/6 to 3/21
Dimensions :pages 3/62 to 3/67
Schemes :pages 3/68 and 3/69
3/45
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
Thermal magnetic circuit-breakers GV2 ME and GV2 P with screw clamp terminalsGV2 ME: pushbutton control, GV2 P: control by rotary knobStandard power ratings of 3-phase motors50/60 Hz in category AC-3
Setting rangeof thermaltrips (2)
Magnetic tripping currentId ± 20 %
Reference Weight
400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)
kW kA % kW kA % kW kA % A A kg– – – – – – – – – 0.1…0.16 1.5 GV2 ME01 0.260
or GV2 P01 0.350
0.06 g g – – – – – – 0.16…0.25 2.4 GV2 ME02 0.260or GV2 P02 0.350
0.09 g g – – – – – – 0.25…0.40 5 GV2 ME03 0.260
or GV2 P03 0.350
0.12 g g – – – 0.37 g g 0.40…0.63 8 GV2 ME04 0.260
or GV2 P04 0.350
0.18 g g – – – – – – 0.40…0.63 8 GV2 ME04 0.260or GV2 P04 0.350
0.25 g g – – – 0.55 g g 0.63…1 13 GV2 ME05 0.260
or GV2 P05 0.350
0.37 g g 0.37 g g – – – 1…1.6 22.5 GV2 ME06 0.260
or GV2 P06 0.350
0.55 g g 0.55 g g 0.75 g g 1…1.6 22.5 GV2 ME06 0.260or GV2 P06 0.350
– – – 0.75 g g 1.1 g g 1…1.6 22.5 GV2 ME06 0.260
or GV2 P06 0.350
0.75 g g 1.1 g g 1.5 3 75 1.6…2.5 33.5 GV2 ME07 0.260
0.75 g g 1.1 g g 1.5 8 100 1.6…2.5 33.5 GV2 P07 0.350
1.1 g g 1.5 g g 2.2 3 75 2.5…4 51 GV2 ME08 0.2601.1 g g 1.5 g g 2.2 8 100 2.5…4 51 GV2 P08 0.350
1.5 g g 2.2 g g 3 3 75 2.5…4 51 GV2 ME08 0.260
1.5 g g 2.2 g g 3 8 100 2.5…4 51 GV2 P08 0.350
2.2 g g 3 50 100 4 3 75 4…6.3 78 GV2 ME10 0.260
2.2 g g 3 g g 4 6 100 4…6.3 78 GV2 P10 0.350
3 g g 4 10 100 5.5 3 75 6…10 138 GV2 ME14 0.2603 g g 4 50 100 5.5 6 100 6…10 138 GV2 P14 0.350
4 g g 5.5 10 100 7.5 3 75 6…10 138 GV2 ME14 0.260
4 g g 5.5 50 100 7.5 6 100 6…10 138 GV2 P14 0.350
5.5 15 50 7.5 6 75 9 3 75 9…14 170 GV2 ME16 0.260
5.5 g g 7.5 42 75 9 6 100 9…14 170 GV2 P16 0.350
– – – – – – 11 3 75 9…14 170 GV2 ME16 0.260– – – – – – 11 6 100 9…14 170 GV2 P16 0.350
7.5 15 50 9 6 75 15 3 75 13…18 223 GV2 ME20 0.260
7.5 50 50 9 10 75 15 4 100 13…18 223 GV2 P20 0.350
9 15 40 11 4 75 18.5 3 75 17…23 327 GV2 ME21 0.260
9 50 50 11 10 75 18.5 4 100 17…23 327 GV2 P21 0.350
11 15 40 15 4 75 – – – 20…25 327 GV2 ME22 (3) 0.26011 50 50 15 10 75 – – – 20…25 327 GV2 P22 0.350
15 10 50 18.5 4 75 22 3 75 24…32 416 GV2 ME32 0.260
15 35 50 18.5 10 75 22 4 100 24…32 416 GV2 P32 0.350
Thermal magnetic circuit-breakers GV2 ME with lugsTo order termal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected above. Example: GV2 ME08 becomes GV2 ME086.
Thermal magnetic circuit-breakers GV2 ME with built-in auxiliary contact blockWith instantaneous auxiliary contact block (composition, see page 3/53):b GV AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE1TQ.b GV AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE11TQ.b GV AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AN11TQ.These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.(1) As % of Icu.(2) For use of GV2 ME in an enclosure, see page 2/10.(3) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office.g > 100 kA.
GV2 ME
5338
95
GV2 P
533
896
Characteristics :pages 3/6 to 3/9
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/46
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME
(1) For connection of conductors from 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.(2) As % of Icu.g > 100 kA.
Thermal magnetic circuit-breakers GV2 ME with spring terminal connections (1)
Pushbutton controlStandard power ratings of 3-phase motors 50-60 Hz in category AC-3
Setting rangeof thermaltrips
Magnetictripping currentId ± 20 %
Reference Weight
400/415 V 500 VP Icu Ics (2) P Icu Ics (2)
kW kA % kW kA % A A kg– – – – – – 0.1…0.16 1.5 GV2 ME013 0.280
0.06 g g – – – 0.16…0.25 2.4 GV2 ME023 0.280
0.09 g g – – – 0.25…0.40 5 GV2 ME033 0.280
0.120.18
gg
gg
– – – 0.40…0.63 8 GV2 ME043 0.280
0.250.37
gg
gg
0.37 g g 0.63…1 13 GV2 ME053 0.280
0.370.55
gg
gg
0.370.550.75
ggg
ggg
1…1.6 22.5 GV2 ME063 0.280
0.75 g g 1.1 g g 1.6…2.5 33.5 GV2 ME073 0.280
1.11.5
gg
gg
1.52.2
gg
gg
2.5…4 51 GV2 ME083 0.280
2.2 g g 3 50 100 4…6.3 78 GV2 ME103 0.280
34
gg
gg
45.5
1010
100100
6…10 138 GV2 ME143 0.280
5.5 15 50 7.5 6 75 9…14 170 GV2 ME163 0.280
7.5 15 50 9 6 75 13…18 223 GV2 ME203 0.280
911
1515
4040
11 4 75 17…23 327 GV2 ME213 0.260
11 15 40 15 4 75 20…25 327 GV2 ME223 0.260
Contact blocksDescription Mounting Maximum
numberType of contacts
Sold in lots of
Unit reference
Weightkg
Instantaneous auxiliary contacts
Front 1 N/O + N/C 10 GV AE113 0.030
N/O + N/O 10 GV AE203 0.030
LH side 2 N/O + N/C 1 GV AN113 0.060
N/O + N/O 1 GV AN203 0,060
AccessoryDescription Application Sold in
lots ofUnit reference
Weightkg
Cable end reducer For connection of conductors from 1 to 1.5 mm2
20 LA9 D99 –
GV2 MEpp3
5338
97
LA9 D99
Characteristics :pages 3/6 to 3/19
Dimensions :pages 3/62 to 3/64
Schemes :page 3/68
3/47
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME
(1) As % of Icu.(2) Recommended for use in association with a contactor.
Thermal magnetic circuit-breakers GV3 ME with screw clamp terminalsPushbutton controlStandard power ratings of 3-phase motors 50/60 Hz in category AC-3
Settingrange of thermal trips
Reference Weight
400/415 V 500 V 660/690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)
kW kA % kW kA % kW kA % A kg0.370.55
100100
100100
0.370.550.75
100100100
100100100
0.751.1
100100
100100
1…1.6 GV3 ME06 0.600
0.75 100 100 1.1 100 100 1.5 100 100 1.6…2.5 GV3 ME07 0.600
1.11.5
100100
100100
1.52.2
100100
100100
2.23
44
100100
2.5…4 GV3 ME08 0.600
2.2 100 100 3 100 100 4 4 100 4…6 GV3 ME10 0.600
34
100100
100100
45.5
88
100100
5.57.5
44
100100
6…10 GV3 ME14 0.600
7.5 100 50 9 8 100 911
44
100100
10…16 GV3 ME20 0.600
911
100100
5050
1115
88
100100
1518.5
44
100100
16…25 GV3 ME25 0.600
1518.5
3535
5050
18.522
88
7575
2230
44
7575
25…40 GV3 ME40 (2) 0.700
2230
3535
5050
3037
88
7575
3745
44
7575
40…63 GV3 ME63 (2) 0.700
37 15 50 45 4 100 55 2 100 56…80 GV3 ME80 (2) 0.700
GV3 ME20
5338
99
Characteristics :pages 3/6 to 3/10
Dimensions :page 3/65
Schemes :page 3/69
3/48
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
(1) As % of Icu.
Thermal magnetic circuit-breakers GV7 R with screw clamp terminalsControl by rocker leverStandard power ratings of 3-phase motors 50/60 Hz in category AC-3
Settingrange of thermal trips
Reference Weight
400/415 V 500 V 660/690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)
kW kA % kW kA % kW kA % A kg7.59
3636
100100
911
1818
100100
1115
88
100100
12…20 GV7 RE20 2.010
7.59
7070
100100
911
5050
100100
1115
1010
100100
12…20 GV7 RS20 2.010
911
3636
100100
1115
1818
100100
1518.5
88
100100
15…25 GV7 RE25 2.010
911
7070
100100
1115
5050
100100
1518.5
1010
100100
15…25 GV7 RS25 2.010
18.5 36 100 18.522
1818
100100
22 8 100 25…40 GV7 RE40 2.010
18.5 70 100 18.5 50 100 22 10 100 25…40 GV7 RS40 2.010
22 36 100 30 18 100 30 8 100 30…50 GV7 RE50 2.015
22 70 100 30 50 100 30 10 100 30…50 GV7 RS50 2.015
37 36 100 4555
1818
100100
55 8 100 48…80 GV7 RE80 2.040
37 70 100 4555
5050
100100
55 10 100 48…80 GV7 RS80 2.040
45 36 100 – 18 100 75 8 100 60…100 GV7 RE100 2.040
45 70 100 – 50 100 75 10 100 60…100 GV7 RS100 2.040
5575
3535
100100
7590
3030
100100
90110
88
100100
90…150 GV7 RE150 2.020
5575
7070
100100
7590
5050
100100
90110
1010
100100
90…150 GV7 RS150 2.020
90110
3535
100100
110132160
303030
100100100
160200
88
100100
132…220 GV7 RE220 2.350
90110
7070
100100
110132160
505050
100100100
160200
1010
100100
132…220 GV7 RS220 2.350
GV7 RE
5339
00
GV7 RS
5339
01
Characteristics :pages 3/6 to 3/11
Dimensions :page 3/65
Schemes :page 3/69
3/49
3
References 3 TeSys protection components 3
Thermal-magnetic circuit-breakersGV2 RT
(1) Other accessories such as mounting, cabling and marking accessories are identical to those used for GV2 ME motor circuit-breakers, see page 3/59.
For motors with high current peak on startingControl by rocker leverStandard power ratings of 3-phase motors 50-60 Hz in category AC-3
Setting rangeof thermal trips
Magnetic tripping currentId ± 20 %
Reference Weight
220/230 V
400/415 V
440 V 500 V 690 V
kW kW kW kW kW A A kg0.06 0.09 0.09
0.12– – 0.25…0.40 8 GV2 RT03 0.350
– 0.120.18
0.18 – 0.37 0.40…0.63 13 GV2 RT04 0.350
0.090.12
0.250.37
0.250.37
0.37 0.55 0.63…1 22 GV2 RT05 0.350
0.180.25
0.370.55
0.370.55
0.370.550.75
0.751.1
1…1.6 33 GV2 RT06 0.350
0.37 0.75 0.751.1
1.1 1.5 1.6…2.5 51 GV2 RT07 0.350
0.550.75
1.11.5
1.5 1.52.2
2.23
2.5…4 78 GV2 RT08 0.350
1.1 2.2 2.23
3 4 4…6.3 138 GV2 RT10 0.350
1.52.2
34
4 45.5
5.57.5
6…10 200 GV2 RT14 0.350
2.23
5.5 5.57.5
7.5 911
9…14 280 GV2 RT16 0.350
4 7.5 7.59
9 15 13…18 400 GV2 RT20 0.350
5.5 911
11 11 18.5 17…23 400 GV2 RT21 0.350
For primaries of 3-phase transformersControl by rocker leverStandard power ratings Setting range
of thermal trips
Magnetic tripping currentId ± 20 %
Reference Weight
230/240 V 400/415 V 440 V 500 V 690 VkW kW kW kW kW A A kg
– – – – – 0.25…0.40 8 GV2 RT03 0.350
– – – – – 0.40…0.63 13 GV2 RT04 0.350
– – 0.63 0.63 1 0.63…1 22 GV2 RT05 0.350
0.4 0.63 1 1 – 1…1.6 33 GV2 RT06 0.350
0.63 1 – 1.6 1.62
1.6…2.5 51 GV2 RT07 0.350
1 1.62
1.62
22.5
2.5 2.5…4 78 GV2 RT08 0.350
1.62
2.5 2.54
4 456.3
4…6.3 138 GV2 RT10 0.350
2.5 45
5 56.3
– 6…10 200 GV2 RT14 0.350
4 6.3 6.3 – 1012.5
9…14 280 GV2 RT16 0.350
56.3
10 10 1012.5
10 13…18 400 GV2 RT20 0.350
Accessory (1)Description Reference Weight
kgPadlockable external operator (IP 54)black handle, blue legend plate
GV2 AP03 0.280
GV2 RT
5339
02
Characteristics :pages 3/6 to 3/21
Dimensions :page 3/64
Schemes :page 3/68
3/50
3
References 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 LE and GV2 L
Magnetic circuit-breakers GV2 LE and GV2 L with screw clamp terminalsGV2 LE: control by rocker lever, GV2 L: control by rotary knobStandard power ratings of 3-phase motors50/60 Hz in category AC-3
Magnetic protection rating
Tripping currentId ± 20 %
Use in association with thermal overload relay
Reference Weight
400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)
kW kA kW kA kW kA A A kg0.06 g g – – – – – – 0.4 5 LR2 K0302 GV2 LE03 0.330
0.09 g g – – – – – – 0.4 5 LR2 K0304 GV2 LE03 0.330
or LRD 03 GV2 L03 0.3300.12 g g – – – 0.37 g g 0.63 8 LR2 K0304 GV2 LE04 0.330
or LRD 04 GV2 L04 0.330
0.18 g g – – – – – – 0.63 8 LR2 K0305 GV2 LE04 0.330
or LRD 04 GV2 L04 0.330
– – – – – – 0.55 g g 1 13 LR2 K0305 GV2 LE05 0.330
or LRD 05 GV2 L05 0.3300.25 g g – – – – – – 1 13 LR2 K0306 GV2 LE05 0.330
or LRD 05 GV2 L05 0.330
– – – – – – 0.75 g g 1 13 LR2 K0306 GV2 LE05 0.330
or LRD 06 GV2 L05 0.330
0.37 g g 0.37 g g – – – 1 13 LR2 K0306 GV2 LE05 0.330
or LRD 05 GV2 L05 0.3300.55 g g 0.55 g g 1.1 g g 1.6 22.5 LR2 K0307 GV2 LE06 0.330
or LRD 06 GV2 L06 0.330
– – – 0.75 g g – – – 1.6 22.5 LR2 K0307 GV2 LE06 0.330
or LRD 06 GV2 L06 0.330
0.75 g g 1.1 g g 1.5 3 75 2.5 33.5 LR2 K0308 GV2 LE07 0.330
0.75 g g 1.1 g g 1.5 4 100 2.5 33.5 LRD 07 GV2 L07 0.3301.1 g g – – – – – – 2.5 33.5 LR2 K0308 GV2 LE07 0.330
or LRD 08 GV2 L07 0.330
1.5 g g 1.5 g g 3 3 75 4 51 LR2 K0310 GV2 LE08 0.330
1.5 g g 1.5 g g 3 4 100 4 51 LRD 08 GV2 L08 0.330
– – – 2.2 g g – – – 4 51 LR2 K0312 GV2 LE08 0.330
or LRD 08 GV2 L08 0.3302.2 g g 3 50 100 4 3 75 6.3 78 LR2 K0312 GV2 LE10 0.330
2.2 g g 3 g g 4 4 100 6.3 78 LRD 10 GV2 L10 0.330
3 g g 4 10 100 5.5 3 75 10 138 LR2 K0314 GV2 LE14 0.330
3 g g 4 10 100 5.5 4 100 10 138 LRD 12 GV2 L14 0.330
4 g g 5.5 10 100 – – – 10 138 LR2 K0316 GV2 LE14 0.330
or LRD 14 GV2 L14 0.330– – – – – – 7.5 3 75 10 138 LRD 14 GV2 LE14 0.330
– – – – – – 7.5 4 100 10 138 LRD 14 GV2 L14 0.330
– – – – – – 9 3 75 14 170 LRD 16 GV2 LE16 0.330
– – – – – – 9 4 100 14 170 LRD 16 GV2 L16 0.330
5.5 15 50 7.5 6 75 11 3 75 14 170 LR2 K0321 GV2 LE16 0.330
5.5 50 50 7.5 10 75 11 4 100 14 170 LRD 16 GV2 L16 0.3307.5 15 50 9 6 75 15 3 75 18 223 LRD 21 GV2 LE20 0.330
7.5 50 50 9 10 75 15 4 100 18 223 LRD 21 GV2 L20 0.330
9 15 40 11 4 75 18.5 3 75 25 327 LRD 22 GV2 LE22 0.330
9 50 50 11 10 75 18.5 4 100 25 327 LRD 22 GV2 L22 0.330
11 15 40 15 4 75 – – – 25 327 LRD 22 GV2 LE22 0.330
11 50 50 15 10 75 – – – 25 327 LRD 22 GV2 L22 0.33015 10 50 18.5 4 75 22 3 75 32 416 LRD 32 GV2 LE32 0.330
15 35 50 18.5 10 75 22 4 100 32 416 LRD 32 GV2 L32 0.330
(1) As % of Icu.g > 100 kA.
GV2 LE
534
101
GV2 L
5341
02
Characteristics :pages 3/12 and 3/13
Dimensions :pages 3/70 to 3/72
Schemes :page 3/73
3/51
3
References 3 TeSys protection components 3
Magnetic motor circuit-breakers GK3
Magnetic circuit-breakers GK3 with screw clamp connectionsControl by rotary knobStandard power ratings of 3-phase motors 50-60 Hz in category AC-3
Associated equipment Circuit-breakerContactor minimum size
Thermal overload relay
Short-circuit protection
400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1) Reference Reference Rating (1) Reference WeightkW kA kW kA kW kA A kg
15 50 30 18.5 20 30 – – – LC1 D32 LRD 32 40 GK3 EF40 0.710
– – – – – – 22 6 60 LC1 D40 LRD 3353 40 GK3 EF40 0.710
18.5 50 30 22 20 30 30 6 60 LC1 D40 LRD 3355 40 GK3 EF40 0.710
22 35 25 30 15 30 – – – LC1 D50 LRD 3357 65 GK3 EF65 0.790
– – – – – – 37 6 50 LC1 D65 LRD 3357 65 GK3 EF65 0.790
30 35 25 37 15 30 – – – LC1 D65 LRD 3359 65 GK3 EF65 0.790
30 35 25 37 15 30 – – – LC1 D65 LRD 3361 65 GK3 EF65 0.790
– – – – – – 45 6 50 LC1 D80 LRD 3359 65 GK3 EF65 0.790
37 35 25 45 15 30 – – – LC1 D80 LRD 3361 80 GK3 EF80 0.795
37 35 25 55 15 30 – – – LC1 D80 LRD 3363 80 GK3 EF80 0.795
(1) Associated current limiter or fuses, where required. See characteristics page 3/15.
GK3 EF
534
103
Characteristics :pages 3/14 and 3/15
Dimensions :page 3/72
Schemes :page 3/73
3/52
3
33
GV2 AK00GV1 L3
GV AD
GV AM11
GV AM11
GV AN
GV AN
GV2 P
GV2 ME
GV AX
GV AU
GV AS
GV AE1
GV AE1
GV AE11, AE20
GV2 L
GV2 LE
3/53
3
References 3 TeSys protection components 3
Thermal-magnetic and magnetic motor circuit-breakers GV2 with screw clamp connectionsAccessories
Contact blocksDescription Mounting Maximum
numberType of contacts
Sold in lots of
Unit reference
Weightkg
Instantaneous auxiliary contacts
Front (1) 1 N/O or N/C (2) 10 GV AE1 0.015N/O + N/C 10 GV AE11 0.020
N/O + N/O 10 GV AE20 0.020
Side (LH) 2 N/O + N/C 1 GV AN11 0.050
N/O + N/O 1 GV AN20 0.050
Fault signalling contact + instantaneous auxiliary contact
Side (3)(LH)
1 N/O (fault) + N/O 1 GV AD1010 0.055
+ N/C 1 GV AD1001 0.055N/C (fault) + N/O 1 GV AD0110 0.055
+ N/C 1 GV AD0101 0.055
Short-circuit signalling contact
Side(LH)
1 C/O common point 1 GV AM11 0.045
Electric tripsMounting Voltage Reference Weight
kg
Undervoltage or shunt trips (4)
Side(1 block on RH side of circuit-breaker)
24 V 50 Hz GV Ap025 0.105
60 Hz GV Ap026 0.10548 V 50 Hz GV Ap055 0.105
60 Hz GV Ap056 0.105
100 V 50 Hz GV Ap107 0.105
100…110 V 60 Hz GV Ap107 0.105
110…115 V 50 Hz GV Ap115 0.105
60 Hz GV Ap116 0.105120…127 V 50 Hz GV Ap125 0.105
127 V 60 Hz GV Ap115 0.105
200 V 50 Hz GV Ap207 0.105
200…220 V 60 Hz GV Ap207 0.105
220…240 V 50 Hz GV Ap225 0.105
60 Hz GV Ap226 0.105380…400 V 50 Hz GV Ap385 0.105
60 Hz GV Ap386 0.105
415…440 V 50 Hz GV Ap415 0.105
415 V 60 Hz GV Ap416 0.105
440 V 60 Hz GV Ap385 0.105
480 V 60 Hz GV Ap415 0.105500 V 50 Hz GV Ap505 0.105
600 V 60 Hz GV Ap505 0.105
Undervoltage trip, INRS (can only be mounted on GV2 ME)Safety device for dangerous machines conforming to INRS and VDE 0113
Side(1 block on RH side of circuit-breaker GV2 ME)
110…115 V 50 Hz GV AX115 0.110
60 Hz GV AX116 0.110
127 V 60 Hz GV AX115 0.110220…240 V 50 Hz GV AX225 0.110
60 Hz GV AX226 0.110
380…400 V 50 Hz GV AX385 0.110
60 Hz GV AX386 0.110
415…440 V 50 Hz GV AX415 0.110
440 V 60 Hz GV AX385 0.110
Add-on contact blocksDescription Mounting Maximum
numberReference Weight
kgVisible isolation block (5) Front (1) 1 GV2 AK00 0.150Limiters At top
(GV2 ME and GV2 P)1 GV1 L3 0.130
Independent 1 LA9 LB920 0.320
(1) Mounting of a GV AE contact block or a GV2 AK00 visible isolation block on GV2 P and GV2 L(2) Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted.(3) The GV AD is always mounted next to the circuit-breaker.(4) To order an undervoltage trip: replace the dot (p) in the reference with a U, example: GV AU025.
To order a shunt trip: replace the dot (p) in the reference with an S, example: GV AS025.(5) Visible isolation of the 3 poles upstream of circuit-breaker GV2 P and GV2 L.
LA9 LB920
Characteristics :pages 3/16, 3/20 and 3/21
Dimensions, schemes :pages 3/62 to 3/73
3/54
3
33
GV3 A08GV3 A09
GV3 A01...A07
3/55
3
References 3 TeSys protection components 3
Motor circuit-breakers, thermal-magnetic GV3 ME and magnetic GK3 with screw clamp connectionsAccessories
For thermal-magnetic motor circuit-breakers GV3 MEContact blocksDescription Type of standard
early break contactsReference Weight
kg
Instantaneous auxiliary contact blocks (1 per circuit-breaker)
N/C + N/O GV3 A01 0.060N/O + N/O GV3 A02 0.060
N/C + N/O + N/O GV3 A03 0.070
N/O + N/O + N/O GV3 A05 0.070
N/O + N/O + 2 volt-free terminals GV3 A06 0.070
N/C + N/O + 2 volt-free terminals GV3 A07 0.070
Fault signalling contacts (1) N/C GV3 A08 0.030
N/O GV3 A09 0.030
Electric tripsDescription Voltages Reference Weight
50 Hz 60 Hz kgUdervoltage trips (1) 110, 120, 127 V 120, 127 V GV3 B11 0.070
220, 240 V 277 V GV3 B22 0.070
380, 415 V 440 V, 480 V GV3 B38 0.070
Shunt trips (1) 110, 120, 127 V 120, 127 V GV3 D11 0.070
220, 240 V 277 V GV3 D22 0.070
380, 415 V 440 V, 480 V GV3 D38 0.070
AccessoryDescription Sold in
lots ofUnit reference
Weightkg
Padlocking device, for locking the start button (on open-mounted product)
5 GV1 V02 0.010
For magnetic circuit-breakers GK3Contact blocksDescription Composition Reference Weight
kgAuxiliary contact blocks for On-Off signalling and “control circuit test” function (1 or 2 blocks per device) mounted on RH side of GK3 EF
N/O GK2 AX10 0.025N/O + N/O GK2 AX20 0.031
N/C + N/O GK2 AX50 0.031
Instantaneous fault signalling contact blocks (1 or 2 blocks per device)mounted on LH side of GK3 EF
N/O GK2 AX12 0.025
N/O + N/O GK2 AX22 0.031N/C + N/O GK2 AX52 0.031
AccessoriesDescription Reference Weight
kgPadlocking device for padlocking the operator, using up to 3 padlocks(padlocks not supplied)
GK3 AV01 0.020
External operator for mounting on the enclosure door.Red Ø 40 pushbutton on yellow plate. Can be locked in position "O" by means of up to 3 padlocks, with door locked in position "I" and door locked in position "O" when padlocked.
GK3 AP03 0.300
(1) 1 voltage trip OR 1 fault signalling contact to be fitted inside the motor circuit-breaker.
Other versions 24 to 690 V, 50 or 60 Hz voltage trips for circuit-breakers GV3 ME.Please consult your Regional Sales Office.
Characteristics :pages 3/16 and 3/20
Dimensions, schemes :pages 3/62 to 3/73
3/56
3
33
GV7 RE, RS
GV7 AE11, AB11
GV7 AU, AS
12
34
3/57
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connectionsAccessories
Add-on auxiliary contactsThey allow remote indication of the circuit-breaker contact states. They can be used for signalling, electrical locking, relaying, etc. Two versions are available: standard and low level. They include a terminal block and the auxiliary circuits leave the circuit-breaker through a hole provided for this purpose.They perform the following functions, depending on where they are located in the circuit-breaker:
Location Function Application1 and/or 4 C/O contact Indicates the position of the circuit-breaker poles2 Trip indication Indicates that the circuit-breaker has tripped due to an
overload, a short-circuit, a differential fault or the operation of a voltage trip (undervoltage or shunt trip) or of the “push to trip” test button. It resets when the circuit-breaker is reset.
3 Electrical fault indication Indicates that the circuit-breaker has tripped due to an overload, a short-circuit or a differential fault. It resets when the circuit-breaker is reset.
Type Reference Weightkg
Standard GV7 AE11 0.015
Low level GV7 AB11 0.015
Fault discrimination devicesThey make it possible to:b either differentiate a thermal fault from a magnetic fault,b or open the contactor only in the event of a thermal fault.
Voltage Reference Weightkg
a 24...48 and c 24…72 V GV7 AD111 (1) 0.100
z 110…240 V GV7 AD112 (1) 0.100
Electric tripsThese allow the circuit-breaker to be tripped via an electrical control signal.
b Undervoltage trip GV7 AUv Trips the circuit-breaker when the control voltage drops below the tripping threshold, which is between 0.35 and 0.7 times the rated voltage.v Circuit-breaker closing is only possible if the voltage exceeds 0.85 times the rated voltage.Circuit-breaker tripping by a GV7 AU trip meets the requirements of IEC 60947-2.
b Shunt trip GV7 ASTrips the circuit-breaker when the control voltage rises above 0.7 times the rated voltage.
b Operation (GV7 AU or GV7 AS)v When the circuit-breaker has been tripped by a GV7 AU or AS, it must be reset either locally or by remote control. (For remote control, please consult your Regional Sales Office).v Tripping has priority over manual closing: if a tripping instruction is present, manual action does not result in closing, even temporarily, of the contacts.v Durability: 50 % of the mechanical durability of the circuit-breaker.
Type Voltage Reference Weightkg
Undervoltage trip 48 V, 50/60 Hz GV7 AU055 (1) 0.105110…130 V, 50/60 Hz GV7 AU107 (1) 0.110
200…240 V, 50/60 Hz GV7 AU207 (1) 0.110
380…440 V, 50/60 Hz GV7 AU387 (1) 0.105
525 V, 50 Hz GV7 AU525 (1) 0.100
Shunt trip 48 V, 50/60 Hz GV7 AS055 (1) 0.105
110…130 V, 50/60 Hz GV7 AS107 (1) 0.110
200…240 V, 50/60 Hz GV7 AS207 (1) 0.110
380…440 V, 50/60 Hz GV7 AS387 (1) 0.105
525 V, 50 Hz GV7 AS525 (1) 0.100
(1) For mounting of a GV7 AD or a GV7 AU or AS.
Characteristics :pages 3/16, 3/20 and 3/21
Dimensions :pages 3/65 to 3/67
Schemes :page 3/69
3/58
3
33
O
TRIP.
RESET RESET
3/59
3
References 3 TeSys protection components 3
Thermal-magnetic and magnetic motor circuit-breakers GV2 with screw clamp connectionsAccessories
AccessoriesDescription Application Sold in
lots of Unit reference
Weightkg
Adapter plates For mounting a GV2 ME or GV2 LE by screw fixing
10 GV2 AF02 0.021
For mounting a GV2 ME or GV2 P and contactor LC1 D09…D38 with front faces aligned
1 LAD 311 0.040
Height compensation plate 7.5 mm 10 GV1 F03 0.003
Combination blocks Between GV2 and contactor LC1 K or LP1 K
10 GV2 AF01 0.020
Between GV2 and contactor LC1 D09…D38
10 GV2 AF3 0.016
Between GV2 mounted on LAD 311 and contactor LC1 D09…D38
10 GV2 AF4 0.016
Motor starter adapter plate With 3-pole connection for mounting a GV2 and a contactor LC1 D09…D25
1 GK2 AF01 0.120
Description Application Pitch Reference Weightmm kg
Sets of 3-pole busbars63 A
2 tap-offs 45 GV2 G245 0.036
54 GV2 G254 0.038
72 GV2 G272 0.042
3 tap-offs 45 GV2 G345 0.058
54 GV2 G354 0.060
4 tap-offs 45 GV2 G445 0.07754 GV2 G454 0.085
72 GV2 G472 0.094
5 tap-offs 54 GV2 G554 0.100
Description Application Sold in lots of
Unit reference
Weightkg
Protective end cover For unused busbar outlets 5 GV1 G10 0.005
Terminal block for supply to one or more GV2 G busbar sets
Connection from the top 1 GV1 G09 0.040Can be fitted with current limiter GV1 L3 (GV2 ME and GV2 P)
1 GV2 G05 0.115
Cover for terminal block For mounting in modular panels 10 LA9 E07 0.005
Flexible 3-pole connection for connecting a GV2 to acontactor LC1-D09…D25
Centre distance between mounting rails: 100…120 mm
10 GV1 G02 0.013
Set of connections upstream/downstream
For connecting GV2 ME to a printed circuit board 10 GV2 GA01 0.045
Clip-in marker holders (supplied with each circuit-breaker)
For GV2 P, GV2 L, GV2 LE and GV2 RT (8 x 22 mm)
100 LA9 D92 0.001
Padlockable external operatorsDescription Reference Weight
kgFor GV2 P and GV2 L (150 to 290 mm)
Padlocking in “On” and “Off” positionBlack handle, blue legend plate, IP 54
GV2 AP01 0.200
Padlocking in “Off” positionRed handle, yellow legend plate, IP 54
GV2 AP02 0.200
For GV2 LE Padlocking in “On” and “Off” positionBlack handle, blue legend plate, IP 54
GV2 AP03 0.280
Padlocking deviceDescription Reference Weight
kgFor all GV2 devices For use with up to 4 padlocks (not supplied),
Ø 6 mm shank max.GV2 V03 0.092
Dimensions :pages 3/62 to 3/72
3/60
3
33
ON
OFFO
ON
OFFO
ON
OFFO
OFFO
ON
ON
OFFO
GV7 RE, RS
GV7 AP03
OFFO
ON
GV7 AP04
GV7 AP01, AP02
GV7 V01
GV7 AP05
GV7 RE, RS
GV7 AC01
GV7 AC03 GV7 AC01
GV7 AC04
GV7 AC04
3/61
3
References 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connectionsAccessories
Cabling accessoriesDescription Application For
contactorSold in lots of
Unit reference
Weight
kgClip-on connectors for GV7 R
Up to 150 A, 1.5…95 mm2 – 3 GV7 AC021 0.300
Up to 220 A, 1.5…185 mm2 – 3 GV7 AC022 0.350
Spreader 3-pole (1)
To increase the pitch to 45 mm – 1 GV7 AC03 0.180
Terminal shields IP 405 (1)
Supplied with sealing accessory
– 1 GV7 AC01 0.125
Phase barriers Safety accessories used when fitting of shields is impossible
– 2 GV7 AC04 0.075
Insulating screens Ensure insulation between the connections and the backplate
– 2 GV7 AC05 0.075
Kit for combination with contactor (2)
Allowing link between the circuit-breaker and the contactor. The cover provides protection against direct finger contact.
LC1 F115…F185 1 GV7 AC06 0.550
LC1 F225 and F265 1 GV7 AC07 0.550
LC1 D115 and D150
1 GV7 AC08 0.550
Direct rotary handleReplaces the circuit-breaker front cover; secured by screws. It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). A conversion accessory allows the direct rotary handle to be mounted on the enclosure door. In this case, the door cannot be opened if the circuit-breaker is in the “ON” position. Circuit-breaker closing is inhibited if the enclosure door is open.
Description Type Degree of protection Reference Weightkg
Direct rotary handle Black handle, black legend plate IP 40 GV7 AP03 0.205
Red handle, yellow legend plate IP 40 GV7 AP04 0.205
Adapter plate (3) Four mounting direct rotary handle on enclosure door
IP 43 GV7 AP05 0.100
Extended rotary handleAllows a circuit-breaker installed in the back of an enclosure to be operated from the front of the enclosure. It comprises:b a unit which replaces the circuit-breaker front cover; secured by screws,b an assembly (handle and front plate) to be fitted on the enclosure door,b an extension shaft which must be adjusted (distance between the mounting surface and the door: 185 mm minimum, 600 mm maximum). It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). This prevents the enclosure door from being opened.
Description Type Degree of protection Reference Weightkg
Extended rotary handle Black handle, black legend plate IP 55 GV7 AP01 0.775
Red handle, yellow legend plate IP 55 GV7 AP02 0.775
Locking deviceAllows circuit-breakers not fitted with a rotary handle to be locked in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied).
Description Application Reference Weightkg
Locking device For circuit-breaker not fitted with a rotary handle GV7 V01 0.100
(1) Terminal shields cannot be used together with spreaders.(2) The kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker.(3) This conversion accessory makes it impossible to open the door if the device is closed and prevents the device from being
closed if the door is open.
Dimensions :pages 3/65 to 3/67
Schemes :page 3/69
3/62
3
Dimensions,mounting 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
GV2 ME GV AX GV AD, AM, AN, AU, AS, AX
GV AE
bGV2 MEpp 89
GV2 MEpp3 101(1) MaximumX1 Electrical clearance = 40 mm for Ue y 690 V
GV2 P GV AD, AM, AN, AU, AS GV2 AK00
(1) MaximumX1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V,or 120 mm for Ue = 500 and 690 VX2 = 40 mm
Mounting of GV2 MEOn 35 mm 5 rail On panel with adapter
plate GV2 AF02AM1 PA On pre-slotted mounting
plate On mounting rails DZ5 MB201
c = 78.5 on AM1 DP200 (35 x 7.5)c = 86 on AM1 DE200, ED200 (35 x 15)
Mounting of GV2 POn rail AM1 DE200, ED200 (35 x 15)
On panel On pre-slotted mounting plate AM1 PA
Adapter plate GK2 AF01
b
67,2
X1
46
15,7 X1
11
45=
=
44,5 16 9,3 9,3
81(1)
18
Block GV AD, AM, ANBlock GV AU, AS, AX 15
10
44,5 9,3 9,3
81(1)
1818
89
82
X1
5026
X2
15
6145
==
Block GV AD, AM, AN
Block GV AU, AS
9814
44,5
32
80
50/6
0
4,2
35c
==
AF1 EA4
35
50/6
0
356050
15
DZ5 MB201GV2 AF02
DZ5 ME8
13,5
84
44,5
44,5
106
45
35
54
105
±5
35 5
AF1 EA4
84
13,5 24
5545
135
9,5
Characteristics :pages 3/6 to 3/21
References :pages 3/44 to 3/46
Schemes :page 3/68
3/63
3
Dimensions,mounting (continued) 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P
GV2 AF01 GV2 AF3Combination GV2 ME + k contactor Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor
GV2 ME + LC1 D09…D18 LC1 D25 & D32 GV2 P + LC1 D09…D18 LC1 D25 & D32b 176.4 186.8 b 177.4 187.8
c1 88.65 94.95 c1 88.6 94.95
c 94.15 100.45 c 94.1 100.45
d1 91 91
d 96.8 96.8
GV2 AF4 + LAD 31 GV2 ME + GV1 L3 (current limiter)
Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor
X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue y 690 V
7.5 mm height compensation plate GV1 F03
GV2-ME + LC2 D09…D18 LC2 D25 and D32 GV2 P + LC2 D09…D18 LC2 D25 & D32b 188.6 199 b 169.1 199.5c1 92.7 99 c1 116.8 116.8
c 98.2 104.5 c 122.3 122.3
d1 98.3 98.3
d 103.8 103.8
Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 PDoor cut-out
79 45
152
c1
c
45
b
45
b
c1c
dd1
c1
c
d1
d
45
b
45
b
c1
c45
129
44,5
89
77
X1
X1
40
39
3513
1,5...5
7
53 135…284
65
5,2
= =
54
= =
==
54
Characteristics :pages 3/6 to 3/21
References :pages 3/44 to 3/46
Schemes :page 3/68
3/64
3
Dimensions,mounting (continued) 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P, GV2 RT
Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
l pGV2 G445 (4 x 45 mm) 179 45GV2 G454 (4 x 54 mm) 206 54
GV2 G472 (4 x 72 mm) 260 72
aNumber of tap-offs 5 6 7 8
GV2 G445 224 269 314 359GV2 G454 260 314 368 422
GV2 G472 332 404 476 548
Sets of busbars GV2 Gppp with terminal block GV1 G09 Sets of busbars GV2 G245, GV2 G254, GV2 G272
lGV2 G245 (2 x 45 mm) 89
GV2 G254 (2 x 54 mm) 98GV2 G272 (2 x 72 mm) 116
Sets of busbars GV2 G554 Sets of busbars GV2 G345 and GV2 G354
lGV2 G345 (3 x 45 mm) 134
GV2 G354 (3 x 54 mm) 152
Dimensions of GV2 RT Mounting of external operator GV2 AP03
X1 Electrical clearance = 40 mm for Ue < 690 V
Mounting of GV2 RTOn 35 mm 7 rail On panel with adapter
plate GV2 AF02On pre-slotted mounting plate AM1 PA
On mounting rails DZ5 MB
c = 80 on AM1 DP200 (35 x 7.5)c = 88 on AM1 DE200, ED200 (35 x 15)
63
l3
a
18
p
45
GV1 G09
30
l
260 l
89
66
X1
44167,5 X1
12,5
45=
=
44,5 1,5...5
13
53 133…282
65
6 = =
12,3
c
44,5
44,5
84,5
50/6
0
4,2
35
AF1 EA4
35
50/6
0
35
6050
15
DZ5 MB201GV2 AF02
DZ5 ME8
Characteristics :pages 3/6 to 3/21
References :pages 3/49 and 3/59
Schemes :page 3/68
3/65
3
Dimensions,mounting 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R
Motor circuit-breakers GV3 ME Mounting on rail AM1 DE200 or AM1 ED201
X1 Electrical clearance (ISC max) 40 mm for Ue < 500 V, 50 mm for Ue < 690 V
(1) Block GV3 A01…A07
MountingOn panel On pre-slotted mounting plate AM1 PA
Motor circuit-breakers GV7 R Motor circuit-breakers with terminal shields or phase barriersGV7 R + GV7 AC01 or AC04
(1) 126 for GV7 Rp220(2) Phase barriers: GV7 AC04
(3) Terminal shields: GV7 AC01
Combination of GV7 R and LC1 F with kit GV7 AC0p Minimum electrical clearance
a b cGV7 R + LC1 F115 or F150 + GV7 AC06
119 334 181
GV7 R + LC1 F185 + GV7 AC06
119 338 188
GV7 R + LC1 F225 + GV7 AC07
131 358 188
GV7 R + LC1 F265 + GV7 AC07
131 364 215
Minimum distance between 2 circuit-breakers mounted side-by-side = 0
x1 x2Painted or insulated metal plate,insulation or insulated bar
0 30
Bare metal plate
U y 440 V 5 35
440 V < U < 600 V 10 35U u 600 V 20 35
17,3
22 77,5
113
100…
110
120
5,5
X1
X1
4,5
70,4
(1)
122,5
113
100…
110
61,2
21,2
==
202020
100…
110
113 AF1 EA4
81
86
111 (1)
=
161
=
=
=
125
=
105
= =
35
=
=
321
=
81
=
=
==
==
161
==
357
(2)
(3)
ac
b
x1x1
x2x2
Characteristics :pages 3/6 to 3/21
References :pages 3/47 to 3/48
Schemes :page 3/69
3/66
3
Mounting 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7 R
Panel mounting Mounting on 2 mounting rails DZ5 MB201
Flush-mounting1 circuit-breaker GV7 R n circuit-breakers GV7 R
side-by-side
Combination of GV7 R and LC1 F with kit GV7 AC0p
E G HGV7 R + LC1 F115 + GV7 AC06 44 85 120GV7 R + LC1 F150 + GV7 AC06 46 85 120
GV7 R + LC1 F165 + GV7 AC06 48 85 120
GV7 R + LC1 F225 + GV7 AC07 57 85 120
GV7 R + LC1 F265 + GV7 AC07 60 85 120
35
=12
5
35 35
=
135
35
125
DZ5 ME5
15
=
29
=
29
47
76
88 83
==
108
= =
108
==
108
G
EH
Characteristics :pages 3/6 to 3/21
References :page 3/48
Schemes :page 3/69
3/67
3
Dimensions,mounting (continued) 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV7
Spreaders GV7 AC03 Cabling Smooth terminals Connectors
aGV7 Rp40…Rp150 19.5
GV7 Rp220 21.5
Direct rotary handle GV7 AP03, GV7 AP04Flush-mounting
Direct rotary handle GV7 AP03 or GV7 AP04 with conversion accessory GV7 AP05Front face cut-out Enclosure viewed from top
Door cut-outs require a minimum distance between the centre of the circuit-breaker and the door hinge point ∆ u 100 + (h x 5).
e = 1 to 3 max
Extended rotary handle GV7 AP01, GV7 AP02
l: 185 min, 600 maxThe shaft of the extended rotary handle GV7 AP01 or GV7 AP022 must be cut to length: l – 126 mm.
45 45
114
30 41
Z
X
X
7010
,5 Z
70
Z
X
19
a
73
4528
155
121
0
I
55
91
36 =
29
=
97
47
76
89
=
41
=
100
59
100
69
=
51
120
=
120
125 ±2
e
9
9,25
h
75
=
60
60
0
I
=
75
==
l
9
9,25
Characteristics :pages 3/6 to 3/21
References :page 3/48
Schemes :page 3/69
3/68
3
Schemes 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P and GV2 RT
GV2 MEpp and GV2 RT GV2 Ppp
Current limiter Front mounting add-on contact blocksInstantaneous auxiliary contacts
GV1 L3 GV AE1 GV AE11 GV AE20
Side mounting add-on contact blocksInstantaneous auxiliary contacts and fault signalling contactsGV AD0110 GV AD0101 GV AD1010 GV AD1001
Instantaneous auxiliary contacts Short-circuit signalling contactsGV AN11 GV AN20 GV AM11
Voltage tripsGV AUppp GV ASppp GV AXppp
Use of fault signalling contact and short-circuit signalling contact
Connection of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
1314 12
11or
1314 22
21 1314
2324
535496
95
5251
9695 97
98
5354
9798
5152
(62) 32
(61) 31 43 (73)
44 (74)
(64) 34
(63) 33 43 (73)
44 (74) 05
0608
D1
D2
C1
C2
D1
D2
E1
E2
GV AD10ppGV AM11
Short-circuit signalling
Trip signalling
N/C or N/O Start-Stop contact
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
D1
D2
E2
E1
10Agl max
Characteristics :pages 3/6 to 3/21
References :pages 3/45 to 3/47
Dimensions :pages 3/62 to 3/64
3/69
3
Schemes 3 TeSys protection components 3
Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R
Motor circuit-breakers Auxiliary contact blocksGV3 ME GV3 A01 GV3 A02 GV3 A03 GV3 A05 GV3 A06 GV3 A07
Fault signalling contacts Voltage tripsGV3 A08 GV3 A09 GV3 B GV3 D
Motor circuit-breakers Add-on auxiliary contacts according to their location (1)GV7 R GV7 AE11, GV7 AB11 Location 1
C/O contactLocation 2Trip indication
Location 3Electrical fault indication
Location 4C/O contact
A self-adhesive label, supplied with the contact, can be affixed to the front face of the circuit-breaker to allow personalised marking according to the function of the contact or contacts.
(1) See pages 3/18 and 3/57.
Electric tripsGV7 AUppp GV7 ASppp GV7 AD111, AD112
Recommended application schemes GV7 AD111, AD112Fault indication Contactor opening on overload
Associated componentsKA1: CA2 KN or CAD N
Associated componentsKA1: CAD N + LA6 DK10 or RHKKM1: LC1 D or LC1 F
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3 13
14 2221 13
14
2324
1314
2324 32
31 1314
2324
3334
1314
2324
3334
2324 32
311314
9695 97
98
D1
D2
U
C1
C2
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1114 12
9194 92
8184 82
2124 22
D1
D4
C1
C2
9897 50 ms
9897 50 ms
– KA1
2324
1314
– KA1
Reset
Overload fault
9897 50 ms
– KM1– KA1
A1
A2
A1
A2
B1
– KA1
2122
Reset
Characteristics :pages 3/6 to 3/21
References :pages 3/47 and 3/48
Dimensions :pages 3/65 to 3/67
3/70
3
Dimensions,mounting 3
TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
GV2 L GV AD, AM, AN, AU, AS GV2 AK00
X1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V, or 120 mm for Ue = 500 and 690 V.X2 = 40 mm.
(1) Maximum
Mounting of GV2 L Adapter plate GK2 AF01On rail AM1 DE200, AM1 ED200 (35 x 15)
On panel On pre-slotted mounting plate AM1 PA
7.5 mm height compensation plate GV1 F03
GV2 LE GV AD, AM, AN, AU, AS GV AE
X1 Electrical clearance = 40 mm for Ue y 690 V. (1) Maximum
Mounting of GV2 LEOn 35 mm 7 rail On panel with adapter plate GV2 AF02 On pre-slotted plate AM1 PA On rails DZ5 MB201
c = 80 on AM1 DP200 (35 x 7.5) and 88 on AM1 DE200, ED200 (35 x 15)
44,5 9,3 9,3
81 (1)
1818
89
82
X1
5026
X2
15
6145
==
Block GV AD, AM, AN
Block GV AU, AS9814
44,5
32
13,5
84
44,5
44,5
106
45
35
54
105±
5
35
Ø5,5
5
AF1 EA4
84
13,5 24
5545
135
9,5
39
3513
44
89
167,5
6612,5
X1
X1 44,5
45=
=
9,3 9,3 18
81 (1)
Block GV AD, AM, AN
Block GV AU, AS 15
10
c
44,5
44,5
84,54,2
35
50/6
0
AF1 EA4
35
50/6
0
15 35
50 60
DZ5 MB201GV2 AF02
DZ5 ME8
Characteristics :pages 3/6 to 3/21
References :page 3/50
Schemes :page 3/73
3/71
3
Dimensions,mounting (continued) 3
TeSys protection components 3
Magnetic motor circuit-breakers GV2 L and GV2 LE
Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 L
Mounting of external operator GV2 AP03 for GV2 LE
Door cut-out
Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
l pGV2 G445 (4 x 45 mm) 179 45GV2 G454 (4 x 54 mm) 206 54
GV2 G472 (4 x 72 mm) 260 72
aNumber of tap-offs 5 6 7 8
GV2 G445 224 269 314 359GV2 G454 260 314 368 422
GV2 G472 332 404 476 548
5,2
= =
1,5...5
7
53 6135…284
65
1,5...5
13
53 133…282
65
6 = =
12,3
54
= =
==
54
4xØ3,5 Ø43
63
l3
a
18
p
45
Characteristics :pages 3/12 and 3/13
References :page 3/50
Schemes :page 3/73
3/72
3
Dimensions,mounting 3
TeSys protection components 3
Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3
Sets of busbars GV2 Gppp with terminal block GV1 G09 Sets of busbars GV2 G245, GV2 G254, GV2 GR272
lGV2 G245 (2 x 45 mm) 89
GV2 G254 (2 x 54 mm) 98
GV2 G272 (2 x 72 mm) 116
Set of busbars GV2 G554 Sets of busbars GV2 G345 and GV2 G354
lGV2 G345 (3 x 45 mm) 134GV2 G354 (3 x 54 mm) 152
GK3 EF GK3 EF + 4 GK2 AX
Number of GK2 AX0 1 2 3 4
a 66 74.8 83.5 92.5 101
X1 Electrical clearance, 40 mm for Ue y 690 V.
MountingOn mounting rail AM1 EDpp or AM1 Dpppp On panel
Mounting of external operator GK3 AP03 Door cut-out
(1) 150 min, 305 max. with operating shaft, 97 without operating shaft
GV1 G09
30
l
260 l
70 4,515
120
X1
X1
105 38 28
45=
=
a
80
115,5115,5
=10
5=
=20=
4xØ4,5
(1)53
1,5…5
12065 =
=
54
4xØ3,5 Ø43
==
54
Characteristics :pages 3/12 to 3/15
References :pages 3/50 and 3/51
Schemes :page 3/73
3/73
3
Schemes 3 TeSys protection components 3
Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3
GV2 Lpp GV2 LEpp
Front mounting add-on contact blocksInstantaneous auxiliary contactsGV AE1 GV AE11 GV AE20
Side mounting add-on contact blocksInstantaneous auxiliary contacts and fault signalling contactsGV AD0110 GV AD0101 GV AD1010 GV AD1001
Instantaneous auxiliary contacts Short-circuit signalling contactsGV AN11 GV AN20 GV AM11
Voltage tripsGV AUppp GV ASppp
Motor circuit-breakers GK3 EF
Start-Stop signalling contact blocksGK2 AX10 GK2 AX20 GK2 AX50
Fault signalling contact blocksGK2 AX12 GK2 AX22 GK2 AX52
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1314 12
11
OR
1314 22
21 1314
2324
535496
95
5251
9695 97
98
5354
9798
5152
(62) 32
(61) 31 43 (73)
44 (74)
(64) 34
(63) 33 43 (73)
44 (74) 05
0608
D1
D2
C1
C2
2 4 6
– Q
1 3 5
1314
1314
2324 22
211314
9798
9798
0708
9798 06
05
Characteristics :pages 3/12 to 3/15
References :pages 3/50 and 3/51
Dimensions :pages 3/70 to 3/72
3/74
3
Selection guide 3 Protection components 3
Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformers
Applications Protection of industrial equipment control circuits and of single-phase loads
Tripping threshold on short-circuit 5…7 In 12…16 In
Operational current 0.5 and 1 A 0.5…20 A
Maximum operational voltage 415 V 250 V
Number of poles 1 1 + neutral
Breaking capacity (Icu) conforming to IEC 60947-2 50 kA at 415 V 1.5…50 kA at 415 V 1.5…50 kA at 250 V
Device type GB2 CS GB2 CB GB2 CD
Pages 3/81 3/80 3/80
3/75
3
33
Protection of transformers
Single-phase y 5000 VA/415 V 3-phase y 10 kVA/415 VPrimary Secondary
About 20 In
0.25…23 A
415 V 690 V
2 1 + neutral 3
1.5…50 kA at 415 V 1.5…50 kA at 250 V 15…100 kA at 415 V
GB2 DB GB2 DB GB2 CD GV2 RT
3/80 3/80 3/80 3/49
3/76
3
Presentation, selection 3 Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
GB2 thermal-magnetic circuit-breakers protect and isolate the control circuits of industrial equipment with contactor coils, transformers.…They protect and isolate single-phase auxiliary circuits such as solenoid valves, electro-brakes, battery chargers, supplied from the control circuit voltage.
12 ratings are available, from 0.5 to 20 A, in single-pole (GB2 CB), single-pole + neutral (GB2 CD) and 2-pole (GB2 DB) versions.They have a magnetic tripping threshold set at between 12 and 16 In to withstand the current peaks generated by many industrial components.
2 ratings are available, 0.5 and 1 A, in single-pole version.The magnetic tripping threshold is set between 5 and 7 In.
Clip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick mounting plates.Upstream and downstream marking by means of AB1 clip-in markers.Clear indication of “I” and “O” positions on the operator.Tamper-proof device which requires no special maintenance (fixed magnetic and thermal tripping thresholds).
Single-phase transformers.Magnetising peak: 20 In.Operation of magnetic trips: 13 In.
(1) If the breaking capacity of the GB2 is insufficient, use a GV2 RT with 2 poles connected in series, see page 3/49.
Presentation
GB2 CB, GB2 CD, GB2 DB
GB2 CS
Functions, installation
Selection for the protection of circuits supplied by transformers
Power Primary (1) SecondaryVA 220/240 V 380/415 V 24 V 48 V 110 V 220 V
40 GB2 DB05 GB2 DB05 GB2 CD07 GB2 CD06 GB2 CD05 GB2 CD05
63 GB2 DB05 GB2 DB05 GB2 CD08 GB2 CD07 GB2 CD06 GB2 CD05
100 GB2 DB06 GB2 DB05 GB2 CD10 GB2 CD07 GB2 CD06 GB2 CD05
160 GB2 DB07 GB2 DB06 GB2 CD14 GB2 CD09 GB2 CD07 GB2 CD06
250 GB2 DB07 GB2 DB06 GB2 CD16 GB2 CD12 GB2 CD08 GB2 CD07
400 GB2 DB08 GB2 DB07 GB2 CD22 GB2 CD14 GB2 CD09 GB2 CD07
630 GB2 DB10 GB2 DB08 – GB2 CD21 GB2 CD12 GB2 CD08
1000 GB2 DB14 GB2 DB09 – – GB2 CD16 GB2 CD10
1600 GB2 DB20 GB2 DB14 – – – GB2 CD14
2000 GB2 DB21 GB2 DB14 – – GB2 CD22 GB2 CD16
2500 GB2 DB22 GB2 DB20 – – – GB2 CD20
3000 GB2 DB22 GB2 DB20 – – – GB2 CD21
4000 – GB2 DB21 – – – GB2 CD22
5000 – GB2 DB22 – – – –
Characteristics :pages 3/77 to 3/79
References :pages 3/80 and 3/81
Dimensions :page 3/81
Schemes :page 3/81
3/77
3
Characteristics 3 Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
Circuit-breaker type GB2 CB GB2 CD GB2 DB GB2 CS
EnvironmentConforming to standards IEC 60947-1, 947-2, EN 60947-1, 60947-2
Product certifications CSA, NEMKO, UL NEMKO, UL – –
Protective treatment “TC”Degree of protection Conforming to IEC 60529 IP 20
Shock resistance Conforming to IEC 60068-2-27 22 gn for 20 ms
Vibration resistance Conforming to IEC 60068-2-6 5 gn (5…110 Hz)
Ambient air temperature around the device
Storage °C - 40…+ 80
Operation °C - 20…+ 60
Flame resistance Conforming to IEC 60695-2-1 °C 960Maximum operating altitude m 3000
Operating position In relation to normal vertical mounting plane
GB2 CB,CD, CS GB2 DB
Cabling Minimum c.s.a. Maximum c.s.a.Solid cable mm2 1 x 0.75 1 x 6 or 2 x 4
Flexible cable with cable end mm2 1 x 0.75 1 x 4 or 2 x 2.5
Tightening torque N.m 1.2
Technical characteristicsUtilisation category Conforming to IEC 60947-2 A A A A
Rated operational voltage (Ue)
Conforming to IEC 60947-2 V 415 (1) 250 415 415 (1)
Conforming to CSA C22-2 Nr 14 and UL 1077
V 277 – 277 –
Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60 50/60 50/60Rated impulse withstand voltage (U imp)
Conforming to IEC 60947-2 kV 4 4 4 4
Total power dissipated per pole W 2 2 2 1.9
Mechanical andelectrical durability
C.O.: Closing - Opening C.O. 8000 8000 8000 8000
Operational current correction coefficient (a or c)
According to the permissible ambient temperature
°C - 20 - 10 0 + 10 + 20 + 30 + 40 + 50 + 60
Correction coefficient 1.2 1.15 1.1 1.05 1 0.95 0.90 0.85 0.80
Tripping threshold Of the magnetic trips 12…16 In 12…16 In 12…16 In 5…7 In
(1) One GB2 circuit-breaker on each live conductor.
Tripping curvesAverage operating time at 20 °C without prior current flow (cold state)
GB2 CB, GB2 CD, GB2 DB GB2 CS
1,051,5
2 3 4 5 6 810
1
52
2010
10050
1
52
2010
1
52
2010
60120
500200
100 x In1,051,5
2 3 4 5 6 810
1
52
2010
10050
1
52
2010
1
52
2010
60120
500200
100 x In
Mill
ise
cond
sS
econ
dsM
inu
tes
1,051,5
2 3 4 5 6 810
1
52
2010
10050
1
52
2010
1
52
2010
60120
500200
100 x In
Mill
ise
cond
sS
econ
dsM
inu
tes
Presentation, selection :page 3/76
References :pages 3/80 and 3/81
Dimensions :page 3/81
Schemes :page 3/81
3/78
3
Characteristics (continued) 3 Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
Circuit-breaker type GB2CB05 CB06 CB07 CB08 CB09 CB10 CB12 CB14 CB16 CB20 CB21 CB22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2 a 50/60 Hz
110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
400/415 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
Associated fuses, if requiredif Isc > breaking capacity Icu conforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
Circuit-breaker type GB2CD05 CD06 CD07 CD08 CD09 CD10 CD12 CD14 CD16 CD20 CD21 CD22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2 a 50/60 Hz
110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/ 240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
Associated fuses, if requiredif lsc > breaking capacity Icu conforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
Circuit-breaker type GB2DB05 DB06 DB07 DB08 DB09 DB10 DB12 DB14 DB16 DB20 DB21 DB22
Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20
Breaking capacityconforming to IEC 60947-2 a 50/60 Hz
110 V lcu kA 50 50 15 10 6 3 3 3 2 2 2 2
Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75
230/240 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5
Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75
400/415 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 75
Ics % (1) 25 25 25 50 50 75 75 75 75 75 1.5 75
Associated fuses, if requiredif lsc > breaking capacity Icu conforming to IEC 60947-2
110 V aM A g g 20 25 25 40 40 50 50 63 63 63
gG A g g 25 32 32 50 50 63 63 80 80 80
230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50
gG A g g 25 32 32 40 40 50 50 63 63 63
(1) As % of Icu.g Fuse not required. Breaking capacity Icu > lsc.
Presentation, selection :page 3/76
References :pages 3/80 and 3/81
Dimensions :page 3/81
Schemes :page 3/81
3/79
3
Characteristics (continued) 3 Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
Circuit-breaker type GB2pp05 pp06 pp07 pp08 pp09 pp10 pp12 pp14 pp16 pp20 pp21 pp22
Breaking capacity (lcu) conforming to IEC 60947-2c
24 V kA 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.548 V kA 1 1 1 1 1 1 1 1 – – – –
Operational currentconforming to IEC 60947-5-1 c
DC-12 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
48 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
DC-13 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20
48 V A 0.5 1 2 3 4 5 6 8 – – – –
Circuit-breaker type GB2CS05 CS06
Rating A 0.5 1
Breaking capacityconforming to IEC 60947-2 a 50/60 Hz
110 V lcu kA 50 50
lcs % (1) 100 100
230/240 V lcu kA 50 50
lcs % (1) 25 25
400/415 V (2)
lcu kA 50 50
lcs % (1) 25 25
Breaking capacity (lcu) conforming to IEC 60947-2c
24 V kA 1.5 1.5
48 V kA 1 1
Operational currentconforming to IEC 60947-5-1 c
DC-12 24 V A 0.5 1
48 V A 0.5 1
DC-13 24 V A 0.5 1
48 V A 0.5 1
Maximum permissible line length for star-delta starting (length of cable containing 2 or more conductors)
With contactors LCp D09 …D18
Operational voltage V 48 110 230 48 110 230
C.s.a. 060 mm2 m (3) 31 365 6 85 230
0.75 mm2 m (3) 39 460 8 110 290
1 mm2 m (3) 52 610 10 145 380
1.5 mm2 m (3) 78 910 15 220 570
2.5 mm2 m (3) 130 1520 26 360 9504 mm2 m (3) 200 2400 41 580 1500
With contactors LCp D25…D32
Operational voltage V 48 110 230 48 110 230
C.s.a. 0.60 mm2 m (3) (3) 230 (3) 56 230
0.75 mm2 m (3) (3) 290 (3) 70 290
1 mm2 m (3) (3) 390 (3) 95 380
1.5 mm2 m (3) (3) 580 (3) 140 570
2.5 mm2 m (3) (3) 970 (3) 230 950
4 mm2 m (3) (3) 1500 (3) 375 1500
With contactors LCp D40…D80
Operational voltage V 48 110 230 48 110 230
C.s.a. 0.60 mm2 m (3) (3) 46 (3) 13 1000.75 mm2 m (3) (3) 60 (3) 17 130
1 mm2 m (3) (3) 80 (3) 22 170
1.5 mm2 m (3) (3) 120 (3) 34 250
2.5 mm2 m (3) (3) 190 (3) 56 420
4 mm2 m (3) (3) 310 (3) 90 680
(1) As % of Icu.(2) One GB2 CS circuit-breaker on each live conductor.(3) Use relays.
Presentation, selection :page 3/76
References :pages 3/80 and 3/81
Dimensions :page 3/81
Schemes :page 3/81
3/80
3
References 3 Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
Circuit-breakers with magnetic tripping threshold: 12 to 16 InSingle-poleConventionalrated thermal current Ith (1)
Magnetictripping currentId ± 20 %
Sold in lots of
Unitreference
Weight
A A kg0.5 6.6 6 GB2 CB05 0.060
1 14 6 GB2 CB06 0.060
2 26 6 GB2 CB07 0.0603 40 6 GB2 CB08 0.060
4 52 6 GB2 CB09 0.060
5 66 6 GB2 CB10 0.060
6 83 6 GB2 CB12 0.060
8 108 6 GB2 CB14 0.060
10 138 6 GB2 CB16 0.06012 165 6 GB2 CB20 0.060
16 220 6 GB2 CB21 0.060
20 270 6 GB2 CB22 0.060
Single-pole + neutralConventional rated thermal current Ith (1)
Magnetic tripping current Id ± 20 %
Sold in lots of
Unit reference
Weight
A A kg0.5 6.6 6 GB2 CD05 0.0701 14 6 GB2 CD06 0.070
2 26 6 GB2 CD07 0.070
3 40 6 GB2 CD08 0.070
4 52 6 GB2 CD09 0.070
5 66 6 GB2 CD10 0.070
6 83 6 GB2 CD12 0.0708 108 6 GB2 CD14 0.070
10 138 6 GB2 CD16 0.070
12 165 6 GB2 CD20 0.070
16 220 6 GB2 CD21 0.070
20 270 6 GB2 CD22 0.070
2-poleConventional rated thermal current Ith (1)
Magnetictripping currentId ± 20 %
Sold in lots of
Unit reference
Weight
A A kg0.5 6.6 3 GB2 DB05 0.115
1 14 3 GB2 DB06 0.115
2 26 3 GB2 DB07 0.115
3 40 3 GB2 DB08 0.1154 50 3 GB2 DB09 0.115
5 66 3 GB2 DB10 0.115
6 83 3 GB2 DB12 0.115
8 108 3 GB2 DB14 0.115
10 138 3 GB2 DB16 0.115
12 165 3 GB2 DB20 0.11516 220 3 GB2 DB21 0.115
20 270 3 GB2 DB22 0.115
(1) Conforming to IEC 60947-1.
534
268
GB2 CBpp
5342
69
GB2 CDpp
5342
70
GB2 DBpp
Presentation, selection :page 3/76
Characteristics :pages 3/77 to 3/79
Dimensions :page 3/81
Schemes :page 3/81
3/81
3
References (continued),dimensions,schemes 3
Protection components 3
Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits
Circuit-breakers with magnetic tripping threshold: 5 to 7 InSingle-poleConventional rated thermal current Ith (1)
Magnetic tripping currentId ± 20 %
Sold in lots of
Unit reference
Weight
A A kg0.5 3.3 6 GB2 CS05 0.055
1 6 6 GB2 CS06 0.055
(1) Conforming to IEC 60947-1.
Accessories for circuit-breakers GB2 CB, DB and CSDescription Sold in
lots ofUnit reference
Weight
kgBusbar set for supply to 10 GB2 DB or 20 GB2 CB or GB2 CS with 2 connectors
1 GB2 G210 0.100
Supply connector 10 GB2 G01 –
DimensionsGB2 CBpp, GB2 CDpp, GB2 CSpp GB2 DBpp
Marking: up to twelve AB1 R clip-in markers.
SchemesGB2 CBpp GB2 CDpp GB2 DBpp GB2 CSpp
5342
71
GB2 CSpp
74
1582
82
75
79
67
30
74
85
85
78
82
70
2/T
11/
L1
2/T
11/
L1
3/L2
(13
) 4
/T2
( 14)
1/L1
3/L2
2/T
1
4/T
2
2/T
11/
L1
Presentation, selection :page 3/76
Characteristics :pages 3/77 and 3/79