GV2 & GV3

82
3/0 Contents 0 3 3 - Protection components Motor circuit-breakers TeSys protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/2 b General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6 b GV2 ME and GV2 P v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/8 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/22 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/45 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/62 b GV3 ME v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/10 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/26 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/47 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65 b GV7 R v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/11 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/29 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/48 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65 b GV2 RT v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/34 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/49 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/64 b Accessories v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/59 v For circuit-breakers GV3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55 v For circuit-breakers GV7. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/57 and 3/61 Magnetic motor circuit-breakers Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/4 b GV2 LE and GV2 L v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/12 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/35 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/50 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/70 b GK3 v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/14 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/41 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/51 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/72 b Accessories v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/53 and 3/59 v For circuit-breakers GK3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55

Transcript of GV2 & GV3

Page 1: GV2 & GV3

3/0

Contents 0

3

3 - Protection componentsMotor circuit-breakers

TeSys protection components for the motor protection

Thermal-magnetic motor circuit-breakersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/2

b General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6

b GV2 ME and GV2 P

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/8

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/22

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/45

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/62

b GV3 ME

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/10

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/26

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/47

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65

b GV7 R

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/11

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/29

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/48

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65

b GV2 RT

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/34

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/49

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/64

b Accessories

v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/59

v For circuit-breakers GV3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55

v For circuit-breakers GV7. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/57 and 3/61

Magnetic motor circuit-breakersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/4

b GV2 LE and GV2 L

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/12

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/35

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/50

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/70

b GK3

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/14

v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/41

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/51

v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/72

b Accessories

v For circuit-breakers GV2. . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/53 and 3/59

v For circuit-breakers GK3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55

Page 2: GV2 & GV3

3/1

3

Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformersSelection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/74

b Thermal-magnetic circuit-breaker GB2 for the protection of industrial equipment

control circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/76

v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/77

v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/80

v Dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/81

Page 3: GV2 & GV3

3/2

3

Selection guide 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers

Applications Protection of motors

Tripping threshold on short-circuit 13 In on average

Standard motor power ratings in AC-3, 415 V Up to 15 kW Up to 37 kW

Operational current at 415 V 0.1…32 A 1…80 A

Breaking capacity at 415 V (Icu) to IEC 60947-2 10…100 kA 35…100 kA

Door interlock mechanism Without With Without

Circuit-breaker type GV2 ME GV2 P GV3 ME

Pages 3/45 and 3/46 3/45 3/47

Page 4: GV2 & GV3

3/3

3

33

Protection of motors with high current peak on starting

20 In on average

7.5…110 kW Up to 11 kW

12…220 A 0.25…23 A

35 and 36 kA 70 kA 15…100 kA

With With

GV7 RE GV7 RS GV2 RT

3/48 3/49

Page 5: GV2 & GV3

3/4

3

Selection guide 3 TeSys protection components 3

Magnetic motor circuit-breakers

Applications Protection of motorsMagnetic circuit-breakers provide short-circuit protection. They must be combined with thermal overload relays to provide motor overload protection.

Tripping threshold on short-circuit 13 In on average

Standard motor power ratings in AC-3, 415 V Up to 15 kW

Operational current at 415 V 0.4…32 A

Breaking capacity at 415 V (Icu) to IEC 60947-2 10…100 kA 35…100 kA

Door interlock mechanism With

Device type GV2 LE GV2 L

Pages 3/50

Page 6: GV2 & GV3

3/5

3

33

6…14 In 8…13 In 6.3…12.5 In

11…37 kW 0.37…250 kW

40…80 A 1.5…500 A

35 and 50 kA 25.7 and 150 kA 35.7…150 kA 45.7…150 kA

GK3 EF NS 80 NS 100 toNS 250

NS 400 and NS 630

3/51 Please consult the Merlin Gerin catalogue - Low Voltage Distribution

Page 7: GV2 & GV3

3/6

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers

EnvironmentCircuit-breaker type GV2 ME GV2 P GV3 ME GV7 R

Conforming to standards IEC 60947-1, 60947-2, 60947-4-1, EN 60204, UL 508, CSA C22-2 n° 14, NF C 63-650, 63-120, 79-130, VDE 0113, 0660

IEC 60947-2, 60947-4-1, NF EN, BS EN, DIN EN 60 947.

IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, EN 60947-4-1, NF C 63-650, NF C 63-120, 79-130,VDE 0113, 0660

Product certifications CSA, CEBEC, GOST, TSE, UL, BV, GL, LROS , DNV, PTB, EZU, SETI, RINA,

CSA, UL, PTB, EZU, GOST, TSE, DNV, LROS, GL, BV, RINA

CSA, UL, LROS DNV, UL

Protective treatment “TH” “TC” “TC”

Degree of protectionconforming to IEC 60529

Open- mounted

IP 20 IP 20 IP 405with terminal shields

In enclosure GV2 Mp01: IP 41 GV2 Mp02: IP 55

– GV3 CE01: IP 55 –

Shock resistanceconforming to IEC 60068-2-27

30 gn -11 ms 22 gn -20 ms 30 gn -11 ms

Vibration resistanceconforming to IEC 60068-2-6

5 gn (5…150 Hz) 2.5 gn (0…25 Hz) 2.5 gn (25 Hz)

Ambient air temperature Storage °C - 40…+ 80 - 40…+ 80 - 40…+ 80 - 55…+ 95

Operation Open- mounted

°C - 20…+ 60 - 20…+ 60 - 20…+ 60 - 25… + 70

In enclosure °C - 20…+ 40 – - 20…+ 40 –

Temperature compensation Open- mounted

°C - 20…+ 60 - 20…+ 60 - 20…+ 60 - 25… + 55 (1)

In enclosure °C - 20…+ 40 – - 20…+ 40 –

Flame resistanceconforming to IEC 60695-2-1

°C 960 960 960

Maximum operating altitude m 2000 3000 2000

Suitable for isolationconforming to IEC 60947-1 § 7-1-6

Yes – Yes

Resistance to mechanical impact J 0.5 0.5 0.5 0.5

In enclosure: 6 – – –

Sensitivity to phase failure Yes, conforming to IEC 60947-4-1 § 7-2-1-5-2

Technical characteristicsCircuit-breaker type GV2

MEGV2 P

GV2 RT

GV3 ME06…ME25

GV3 ME40…ME63

GV3 ME80

GV7 Rp20... Rp100

GV7 Rp150

GV7 Rp220

Utilisation category Conforming to IEC 60947-2 A A A

Conforming to IEC 60947-4-1 AC-3 AC-3 AC-3

Rated operational voltage (Ue) conforming to IEC 60947-2

V 690 690 690

Rated insulation voltage (Ui)

Conforming to IEC 60947-2 V 690 690 750

Conforming to CSA C22-2 n° 14, UL 508

V 600 600 (B600) 600

Rated operational frequencyconforming to IEC 60947-2

Hz 50/60 50/60 50/60

Rated impulse withstand voltage (U imp) conforming to IEC 60947-2

kV 6 6 8

Total power dissipated per pole W 2.5 3 6 8 5 8.7 14.5

Mechanical durability(C.O.: Closing - Opening)

C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000

Electrical durabilityfor AC-3 duty

440 V In/2 C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000

440 V In C.O. – – – – 30 000 20 000 10 000

Duty class (maximum operating rate) C.O./h 25 25 25

Maximum conventional rated thermal current (Ith) conforming to IEC 60947-4-1

A 0.16… 32

0.16… 32

0.40… 23

1.6… 25

40… 63

80 12… 100

150 220

Rated duty conforming to IEC 947-4-1 Continuous duty

(1) For operation up to 70 °C, please consult your Regional Sales Office.

References :pages 3/44 to 3/49

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 8: GV2 & GV3

3/7

3

Characteristics (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers

Mounting characteristicsOperating positionWithout derating, in relation to normal vertical mounting plane

Side view Front view

GV3 ME: preferably vertical

Connection characteristicsCircuit-breaker type GV2 ME GV2 P GV3 ME06…ME20 GV3 ME25…ME80

Connection to screw clamp terminalsNumber of conductors and c.s.a.

Min. Max. Min. Max. Min. Max. Min. Max.Solid cable mm2 2 x 1 2 x 6 2 x 1 2 x 6 2 x 1 2 x 6 1 x 2.5 1 x 35

Flexible cable without cable end

mm2 2 x 1.5 2 x 6 2 x 1.5 2 x 6 2 x 1 2 x 6 1 x 2.5 2 x 16

Flexible cable with cable end

mm2 2 x 1 2 x 4 2 x 1 2 x 4 2 x 1 2 x 4 1 x 2.5 2 x 16

Tightening torque N.m 1.7 1.7 1.7 1.7 1.7 1.7 5 5

Connection to spring terminalsNumber of conductors and c.s.a.

Solid cable mm2 2 x 1 (1) 2 x 6 – – – – – –

Flexible cable without cable end

mm2 2 x 1.5 (1) 2 x 4 – – – – – –

Connection to bars,cables with lugs or bare cables

Circuit-breaker type GV7 Rp20...Rp100 GV7 Rp150 GV7 Rp220Pitch Without spreaders mm 35 35 35

With spreaders mm 45 45 45

Bars or cables with lugs e mm y 6 y 6 y 6

L mm y 25 y 25 y 25

d mm y 10 y 10 y 10

Screws M6 M8 M8

Tightening torque N.m 10 15 15

Bare cables (copper or aluminium)with connectors

Height (h) mm 20 20 20

C.s.a. mm2 1.5...95 1.5...95 1.5...185

Tightening torque N.m 15 15 15

(1) For cross-sections 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.

e

d

L

d

L

h

References :pages 3/44 to 3/49

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 9: GV2 & GV3

3/8

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakersGV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 PCircuit-breaker type GV2 ME GV2 P

01 to 06

07 08 10 14 16 20 21 & 22

32 01 to 06

07 08 10 14 16 20 21 & 22

32

Rating A 0.1 to 1.6

2.5 4 6.3 10 14 18 23 & 25

32 0.1 to 1.6

2.5 4 6.3 10 14 18 23 & 25

32

Breaking capacityconforming to IEC 60947-2

230/240 V Icu kA g g g g g g g 50 50 g g g g g g g g g

Ics % (1) g g g g g g g 100 100 g g g g g g g g g

400/415 V Icu kA g g g g g 15 15 15 10 g g g g g g 50 50 50

Ics % (1) g g g g g 50 50 40 50 g g g g g g 50 50 50

440 V Icu kA g g g 50 15 8 8 6 6 g g g g g 50 20 20 20

Ics % (1) g g g 100 100 50 50 50 50 g g g g g 75 75 75 75

500 V Icu kA g g g 50 10 6 6 4 4 g g g g 50 42 10 10 10

Ics % (1) g g g 100 100 75 75 75 75 g g g g 100 75 75 75 75

690 V Icu kA g 3 3 3 3 3 3 3 3 g 8 8 6 6 6 4 4 4

Ics % (1) g 75 75 75 75 75 75 75 75 g 100 100 100 100 100 100 100 100

Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2

230/240 V aM A g g g g g g g 80 80 g g g g g g g g g

gG A g g g g g g g 100 100 g g g g g g g g g

400/415 V aM A g g g g g 63 63 80 80 g g g g g g 100 100 100

gG A g g g g g 80 80 100 100 g g g g g g 125 125 125

440 V aM A g g g 50 50 50 50 63 63 g g g g g 50 63 80 80

gG A g g g 63 63 63 63 80 80 g g g g g 63 80 100 100

500 V aM A g g g 50 50 50 50 50 50 g g g g 50 50 50 50 50

gG A g g g 63 63 63 63 63 63 g g g g 63 63 63 63 63

690 V aM A g 16 25 32 32 40 40 40 40 g 20 25 40 40 50 50 50 50

gG A g 20 32 40 40 50 50 50 50 g 25 32 50 50 63 63 63 63

g > 100 kA.(1) As % of Icu.

R e f e r e n c e s :p a g e s 3 / 4 4 t o 3 / 4 9

D i m e n s i o n s :p a g e s 3 / 6 2 t o 3 / 6 7

S c h e m e s :p a g e s 3 / 6 8 a n d 3 / 6 9

Page 10: GV2 & GV3

3/9

3

Characteristics (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakersGV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 P (used in association with current limiter GV1 L3)Circuit-breaker type GV2 ME

01 to 06 07 08 10 14 16 20 21 22 32Rating A 0.1 to

1.62.5 4 6.3 10 14 18 23 25 32

Breaking capacityconforming to IEC 60947-2

230/240 V Icu kA g g g g g g g g g g

Ics % (1) g g g g g g g g g g

400/415 V Icu kA g g g g g 100 100 100 100 100

Ics % (1) g g g g g 50 50 40 40 40

440 V Icu kA g g g g g 50 20 20 20 20

Ics % (1) g g g g g 75 75 75 75 75

500 V Icu kA g g g g 50 42 10 10 10 10

Ics % (1) g g g g 100 100 75 75 75 75

Circuit-breaker type GV2 P01 to 06 07 08 10 14 16 20 21 22 32

Rating A 0.1 to 1.6

2.5 4 6.3 10 14 18 23 25 32

Breaking capacityconforming to IEC 60947-2

230/240 V Icu kA g g g g g g g g g g

Ics % (1) g g g g g g g g g g

400/415 V Icu kA g g g g g g g g g g

Ics % (1) g g g g g g g g g g

440 V Icu kA g g g g g 100 100 100 100 100

Ics % (1) g g g g g 50 50 50 50 50

500 V Icu kA g g g g 100 100 100 100 100 100

Ics % (1) g g g g 50 50 50 50 50 50

690 V (3) Icu = Ics kA g 50 50 50 50 50 50 50 50 50

Circuit-breaker type GV2 ME01 to 06 07 08 10 14 16 20 21 22 32

Rating A 0.1to 1.6

2.5 4 6.3 10 14 18 23 25 32

Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables)

Minimum c.s.a. protected at 40 °C at Isc max.

1 mm2 p p p y 10 kA y 6 kA (2) (2) (2) (2) (2)

1.5 mm2 p p p y 20 kA y 10 kA (2) (2) (2) (2) (2)

2.5 mm2 p p p p p p p p p (2)

4…6 mm2 p p p p p p p p p p

g > 100 kAp Cable c.s.a. protected(1) As % of Icu(2) Cable c.s.a. not protected(3) With limiter LA9 LB920

References :pages 3/44 to 3/49

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 11: GV2 & GV3

3/10

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME

Breaking capacity of GV3 MECircuit-breaker type GV3 ME

06 & 07 08 10 14 20 25 40 63 80Rating A 1.6 & 2.5 4 6 10 16 25 40 63 80

Breaking capacityconforming to IEC 60947-2

230/240 V Icu kA 100 100 100 100 100 100 100 100 100

Ics % (1) 100 100 100 100 100 100 100 100 100

400/415 V Icu kA 100 100 100 100 100 100 35 35 15

Ics % (1) 100 100 100 100 50 50 50 50 50

440 V Icu kA 100 100 100 25 25 25 25 25 10

Ics % (1) 100 100 100 100 60 60 60 60 60

500 V Icu kA 100 100 100 8 8 8 8 8 4

Ics % (1) 100 100 100 100 100 100 75 75 100

690 V Icu kA 100 4 4 4 4 4 4 4 2

Ics % (1) 100 100 100 100 100 100 75 75 100

Associated fuses, if requiredif lsc > breaking capacity Icu

230/240 V aM A g g g g g g g g g

gG A g g g g g g g g g

400/415 V aM A g g g g g g 250 315 315

gG A g g g g g g 315 400 400

440 V aM A g g g 125 160 200 250 315 315

gG A g g g 160 200 250 315 400 400

500 V aM A g g g 80 100 125 160 200 200

gG A g g g 100 125 160 200 250 250

690 V aM A g 40 50 80 100 125 160 200 200

gG A g 50 63 100 125 160 200 250 250

g Fuse not required: breaking capacity Icn > Isc.(1) As % of Icu.

References :pages 3/44 to 3/49

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 12: GV2 & GV3

3/11

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakersGV7 R

Breaking capacity of GV7 RCircuit-breaker type GV7

RE20…RE100 RS20…RS100 RE150 RS150 RE220 RS220Rating A 12…20 to 60…100 90…150 90…150 132…220 132…220

Breaking capacityconforming to IEC 60947-2

230/240 V lcu kA 85 100 85 100 85 100

Ics % (1) 100 100 100 100 100 100

400/415 V Icu kA 36 70 35 70 35 70

Ics % (1) 100 100 100 100 100 100

440 V Icu kA 36 65 35 65 35 65

Ics % (1) 100 100 100 100 100 100

500 V Icu kA 18 50 30 50 30 50

Ics % (1) 100 100 100 100 100 100

690 V Icu kA 8 10 8 10 8 10

Ics % (1) 100 100 100 100 100 100

Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables)

Minimum c.s.a. protected at 40 °C at Isc max.

4 mm2 y 6 kA y 6 kA (2) (2) (2) (2)

6 mm2 p y 25 kA (2) (2) (2) (2)

10…50 mm2 p p p p p p

p Cable c.s.a. protected.

(1) As % of Icu.(2) Cable c.s.a. not protected.

References :pages 3/44 to 3/49

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 13: GV2 & GV3

3/12

3

Characteristics 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 LE and GV2 L

EnvironmentType GV2 LE GV2 L

Conforming to standards IEC 60947-1, 60947-2, EN 60204, NF C 63-650, NF C63-120, 79-130, VDE 0113, 0660, UL 1077.

Product certifications UL, CSA BV, GL, LROS, DNV, RINA, UL, CSA

Protective treatment “TH” “TH”

Shock resistance Conforming to IEC 60068-2-27 30 gn 30 gn

Vibration resistance Conforming to IEC 60068-2-6 5 gn (5 to 150 Hz) 5 gn (5 to 150 Hz)

Ambient air temperature Storage °C - 40…+ 80 - 40…+ 80

Operation °C - 20…+ 60 - 20…+ 60

Flame resistance Conforming to IEC 60695-2-1 °C 960 960

Maximum operating altitude m 2000 2000

Operating position

CablingNumber of conductors and c.s.a.

Max. Min. Max. Min.Solid cable mm2 2 x 6 2 x 1 2 x 6 2 x 1

Flexible cable without cable end mm2 2 x 6 2 x 1.5 2 x 6 2 x 1.5

Flexible cable with cable end mm2 2 x 4 2 x 1 2 x 4 2 x 1

Suitable for isolation Conforming to IEC 60947-1 § 7-1-6

Yes Yes

Tightening torque N.m 1.7 1.7

Resistance to mechanical impact J 0.5 0.5

Utilisation category Conforming to IEC 60947-2 A A

Conforming to IEC 60947-4-1 AC-3 AC-3

Rated operational voltage (Ue)

Conforming to IEC 60947-2 V 690 690

Rated insulation voltage (Ui)

Conforming to IEC 60947-2 V 690 690

Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60

Rated impulse withstand voltage (U imp)

Conforming to IEC 60947-2 kV 6 6

Total power dissipated per pole W 1.8 1.8

Mechanical durability(C.O. : Closing - Opening)

C.O. 100 000 100 000

Electrical durability For AC-3 duty C.O. 100 000 100 000

Duty class(maximum operating rate)

C.O./h 40 40

Rated duty Conforming to IEC 60947-4-1 Continuous duty Continuous duty

References :pages 3/50 and 3/51

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 14: GV2 & GV3

3/13

3

Characteristics (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 LE and GV2 L

Breaking capacity of GV2 LE and GV2 LType GV2 LE GV2 L

03 to 06

07 08 10 14 16 20 22 32 03 to 06

07 08 10 14 16 20 22 32

Rating A 0.4 to 1.6

2.5 4 6,3 10 14 18 25 32 0.4 to1

2.5 4 6,3 10 14 18 25 32

Breaking capacityconforming to IEC 60947-2

230/240 V Icu kA g g g g g g g 50 50 g g g g g g g 50 50

Ics % (1) g g g g g g g 100 100 g g g g g g g 100 100

400/415 V Icu kA g g g g g 15 15 15 10 g g g g g 50 50 50 50

Ics % (1) g g g g g 50 50 40 50 g g g g g 50 50 50 50

440 V Icu kA g g g 50 15 8 8 6 6 g g g g 20 20 20 20 20

Ics % (1) g g g 100 100 50 50 50 50 g g g g 75 75 75 75 75

500 V Icu kA g g g 50 10 6 6 4 4 g g g g 10 10 10 10 10

Ics % (1) g g g 100 100 75 75 75 75 g g g g 100 75 75 75 75

690 V Icu kA g 3 3 3 3 3 3 3 3 g 4 4 4 4 4 4 4 4

Ics % (1) g 75 75 75 75 75 75 75 75 g 100 100 100 100 100 100 100 100

Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2 amendment 1

230/240 V aM A g g g g g g g 80 80 g g g g g g g 100 100

gG A g g g g g g g 100 100 g g g g g g g 125 125

400/415 V aM A g g g g g 63 63 80 80 g g g g g 80 100 100 100

gG A g g g g g 80 80 100 100 g g g g g 100 125 125 125

440 V aM A g g g 50 50 50 50 63 63 g g g g 50 63 80 80 80

gG A g g g 63 63 63 63 80 80 g g g g 63 80 100 100 100

500 V aM A g g g 50 50 50 50 50 50 g g g g 50 50 50 50 50

gG A g g g 63 63 63 63 63 63 g g g g 63 63 63 63 63

690 V aM A g 16 25 32 32 40 40 40 40 g 20 25 40 40 50 50 50 50

gG A g 20 32 40 40 50 50 50 50 g 25 32 50 50 63 63 63 63

Cable protection against thermal stress in the event of short-circuit(PVC insulated copper cables) Minimum c.s.a. protected at 40 °C and at Isc max.

1 mm2 kA p p p y10 y 6 (2) (2) (2) (2) p p p y10 y 6 (2) (2) (2) (2)

1.5 mm2 kA p p p y20 y 10 (2) (2) (2) (2) p p p y20 y10 (2) (2) (2) (2)

2.5 mm2 p p p p p p p p (2) p p p p p p p p (2)

4…6 mm2 p p p p p p p p p p p p p p p p p p

g > 100 kApCable c.s.a. protected

(1) As % of Icu(2) Cable c.s.a. not protected

References :pages 3/50 and 3/51

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 15: GV2 & GV3

3/14

3

Characteristics 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

EnvironmentConforming to standards IEC 60947-2. EN 60-204

Protective treatment “TC”

Degree of protection Conforming to IEC 60529

GK3 EF basic unit: IP 20

Shock resistance Conforming to IEC 60068-2-27

22 gn for 20 ms

Vibration resistance Conforming to IEC 60068-2-6

2.5 gn (0…25 Hz)

Flame resistance Conforming to IEC 60695-2-1

Conforms for 960 °C

Ambient air temperature Storage °C - 40…+ 80

Operation °C - 20… + 70 open-mounted

Maximum operating altitude m 3000

Operating position Any

Cabling Solid cable mm2 1 x 2.5 to 35 conductor

Flexible cable without cable end

mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors

Flexible cable with cable end

mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors

Tightening torque N.m 5

Suitable for isolation Yes, conforming to IEC 60947-1§7-1-6

Technical characteristicsRated insulation voltage (Ui)

Conforming to IEC 60947-2 V 750

Rated impulse withstand voltage (U imp)

Conforming to IEC 60947-2 kV 10

Rated operational voltage (Ue)

Conforming to IEC 60947-2 V 690

Rated operational frequency Hz 50…60

Electrical durability for AC-23/400 V duty(C.O.: Closing - Opening)

C.O. 1500

Mechanical durability C.O. 20 000

Maximum operating rate C.O./h 40

Operating threshold of magnetic trips

About 13 times the rating of the GK3 EF selected (non adjustable threshold)

Utilisation category Conforming to IEC 60947-2 A

References :pages 3/50 and 3/51

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 16: GV2 & GV3

3/15

3

Characteristics (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Type GK3 EF40 GK3 EF65 GK3 EF80Breaking capacity of the circuit-breaker only or of thecircuit-breaker combined with a thermal overload relay

230/240 V Icu kA 100 50 50

Ics % (1) 20 40 40

400/415 V Icu kA 50 35 35

Ics % (1) 30 25 25

440 V Icu kA 30 25 25

Ics % (1) 30 30 30

500 V Icu kA 20 15 15

Ics % (1) 30 30 30

690 V Icu kA 6 6 6

Ics % (1) 60 50 50

Associated fuses (if required) for use with circuit-breaker only or circuit-breaker combined with a thermal overload relayif lsc > breaking capacity

230/240 V aM A 160 200 200

gG A 250 315 315

400/415 V aM A 160 200 200

gG A 200 250 250

440 V aM A 160 160 160

gG A 200 250 250

500 V aM A 125 160 160

gG A 160 200 200

690 V aM A 100 125 125

gG A 125 160 160

Use of circuit-breakers without fuses Minimum cable length (in metres) limiting the maximum short-circuit current to 35 kA maximum, so enabling breakers GK3 EF to be used without fuses

Cable c.s.a. mm2 y 25 35 50 70 95 120

Isc (rms) 3-phase, incoming (Ue = 400 V)

50 kA m 5 6 8 10 13 15

45 kA m 5 5 7 8 10 12

40 kA m 5 5 5 5 8 9

37 kA m 5 5 5 5 5 5

(1) As % of Icu

References :pages 3/50 and 3/51

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 17: GV2 & GV3

3/16

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic and magnetic motor circuit-breakers GV2Auxiliary contacts

Type of contacts Instantaneous auxiliary GV AN, GV AD

Fault signalling GV AD, GV AM11 (1)

Instantaneous auxiliary GV AE

Rated insulation voltage (Ui) (associated insulation coordination)

Conforming to IEC 60947-1 V 690 690 250 (690 in relation to main circuit)

Conforming to CSA C22-2 n° 14and UL 508

V 600 300 300

Conventional thermal current (Ith)

Conforming to IEC 60947-5-1 A 6 2.5 2.5

Conforming to CSA C22-2 n° 14and UL 508

A 5 1 1

Mechanical durability(C.O. : Closing - Opening)

C.O. 100 000 1000 100 000

Operational power and currentconforming to IEC 60947-5-1 a.c. operation

AC-15/100 000 C.O. AC-14/1000 C.O. AC-15/100 000 C.O.

Rated operational voltage(Ue)

V 48 110 127

230 240

380 415

440 500 690 24 48 110 127

230 240

24 48 110 127

230 240

Operational power,normal conditions

VA 300 500 720 850 650 500 400 36 48 72 72 48 60 120 120

Occasional breaking and making capacities, abnormal conditions

kVA 3 7 13 15 13 12 9 0.22 0.3 0.45 0.45 0.48 0.6 1.27 2.4

Rated operational current(Ie)

A 6 4.5 3.3 2.2 1.5 1 0.6 1.5 1 0.5 0.3 2 1.25 1 0.5

Operational power and currentconforming to IEC 60947-5-1 d.c. operation

DC-13/100 000 C.O. DC-13/1000 C.O. DC-13/100 000 C.O.

Rated operational voltage(Ue)

V 24 48 60 110 240(2)

– – 24 48 60 – 24 48 60 –

Operational power,normal conditions

W 140 240 180 140 120 – – 24 15 9 – 24 15 9 –

Occasional breaking and making capacities, abnormal conditions

W 240 360 240 210 180 – – 100 50 50 – 100 50 50 –

Rated operational current(Ie)

A 6 5 3 1.3 0.5 – – 1 0.3 0.15 – 1 0.3 0.15 –

Low level switching reliability of contact GV A: number of failures for “n” million operating cycles(17 V-5 mA): = 10-6

Minimum operational conditionsd.c. operation

V 17

mA 5

Short-circuit protection By GB2 CBpp circuit-breaker (rating according to operational current for Ue y 415 V) or by gG fuse 10 A max

GB2 CB06 or gG fuse, 10 A max

Cabling, screw clamp terminals

Number of conductors 1 2Solid cable mm2 1…2.5 1…2.5

Flexible cable without cable end mm2 0.75…2.5 0.75…2.5

Flexible cable with cable end mm2 0.75…1.5 0.75…1.5

Tightening torque N.m 1.4 max 1.4 max

Cabling, spring terminals GV AN only

Flexible cable without cable end mm2 0.75…2.5 0.75…2.5 – 0.75…1.5

Operation of instantaneous auxiliary contacts Operation of fault signalling contacts

GV AM11Change of state following tripping on short-circuit.

GV AD10pp and GV AD01ppChange of state following tripping on short-circuit. overload or undervoltage.

(1) For application example of fault signalling contact and short-circuit signalling contact, see page 3/68.(2) Add an RC circuit type LA4 D to the load terminals, see page 24511/5.

0 1

FF

FO

O

O

F

F

F

F

O

F

Power pole

Contact openContact closed

References :page 3/53

Dimensions, schemes :pages 3/62 to 3/73

Page 18: GV2 & GV3

3/17

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 MEAuxiliary contacts

Type of contacts Instantaneous auxiliary contactsGV3 A01…A07

Fault signalling contacts GV3 A08 and A09

Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 690

Conforming to CSA C22-2 n° 14, UL 508

V 600 (B600) 600 (B600)

Conventional rated thermal current (Ith)

Conforming to IEC 60947-5-1 A 6 6

Conforming to CSA C22-2 n° 14, UL 508

A 5 (B600) 5 (B600)

Mechanical durability(C.O.: Closing - Opening)

C.O. 100 000 1000

Operational power and currentconforming to IEC 60947-5-1 a.c. operation

Rated operational voltage(Ue)

V 48 110 127

220 240

380 415

440 500 690 48 110 127

220 240

380 415

440 500 690

Operational power AC-11/100 000 C.O. AC-11/1000 C.O.

VA 350 500 800 850 700 700 400 240 460 800 850 450 450 200

Occasional breaking and making capacities

kVA 4 12 20 20 15 15 10 2.4 8 12 15 12 12 8

Operational current (Ie) A 6 4.5 3.5 2.2 1.5 1.5 0.6 5 3.6 3.5 2.2 1 1 0.3

Operational power and currentconforming to IEC 60947-5-1 d.c. operation

Rated operational voltage(Ue)

V 24 48 60 110 220 24 48 60 110 220

Operational power DC-11/100 000 C.O. DC-11/1000 C.O.

W 180 240 180 140 120 120 120 90 70 60

Occasional breaking and making capacities

W 240 360 240 210 180 180 180 135 105 90

Operational current (Ie) A 6 5 3 1.3 0.5 5 2.5 1.5 0.7 0.3

Short-circuit protection By GB2 CB08 circuit-breaker or gG fuse, 6A max

Cabling Number of conductors 1 2

Solid cable mm2 1…2.5 1…2.5

Flexible cable without cable end mm2 0.75…2.5 0.75…2.5

Flexible cable with cable end mm2 0.75…2.5 0.75…1.5

Contact operation GV3 A08 and A09 change state following tripping on short-circuit or overload0 1

OF

FF

FF

O

FF

F

FF

GV3 A01, A07

GV3 A02

GV3 A03

GV3 A05

GV3 A06

Power pole

Contact openContact closed

References :page 3/55

Dimensions, schemes :pages 3/62 to 3/73

Page 19: GV2 & GV3

3/18

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7Auxiliary contacts

Auxiliary contact characteristicsType of contacts GV7 AE11 GV7 AB11

Rated insulation voltage (Ui) (associated insulation coordination)

Conforming to IEC 60947-1 V 690 690

Conventional thermal current (Ith)

Conforming to IEC 60947-5-1 A 6 6

Mechanical durability(C.O.: Closing - Opening)

C.O. 50 000 50 000

Operational currentconforming to IEC 60947-5-1 a.c. operation

AC-12 or AC-15. 50 000 C.O. AC-12 or AC-15. 50 000 C.O.

Rated operational voltage (Ue)

V 24 48 110 230/ 240

380/ 415

440 690 24 48 110 230/ 240

380/ 415

440 690

Rated operational current (Ie)

AC-12 A 6 6 6 6 6 6 6 5 5 5 5 5 5 5

AC-15 A 6 6 5 4 3 3 0.1 5 5 4 3 2.5 2.5 0.1

Operational currentconforming to IEC 60947-5-1 d.c. operation

DC-12 or DC-14. 50 000 C.O. DC-12 or DC-14. 50 000 C.O.

Rated operational voltage (Ue)

V 24 48 110 250 24 48 110 250

Rated operational current (Ie)

DC-12 A 2.5 2.5 0.8 0.3 2 2 0.5 –

DC-14 A 1 0.2 0.5 0.03 0.5 0.1 0.25 –

Minimum operational conditions V 17 12

d.c. operation mA 5 5

Short-circuit protection By GB2 CBpp circuit-breaker(rating according to operational current for Ue y 415 V) or gG fuse, 10 A max.

Cabling Solid cable mm2 1 x 1.5 conductor 1 x 1.5 conductor

Flexible cable without cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor

Flexible cable with cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor

References :page 3/57

Dimensions, schemes :pages 3/62 to 3/73

Page 20: GV2 & GV3

3/19

3

Characteristics 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Characteristics of Start-Stop and fault signalling contactsRated insulation voltage (Ui)

Conforming to IEC 60947-1 V 500

Rated operational voltage (Ue)

Conforming to IEC 60947-1 V 500

Conventional thermal current (Ith)

Conforming to IEC 60947-5-1 A 6

Operational power and currentconforming to IEC 60947-5-1 a.c. operation(C.O.: Closing - Opening)

AC-15. 20 000 C.O.Rated operational voltage (Ue) V 48 110/127 220/240 380/415 440 500

Operational power VA 360 500 800 850 700 700

Occasional breaking and making capacities

VA 4000 12 000 20 000 20 000 15 000 15 000

Rated operational current (Ie) A 6 4.5 3.5 2.2 1.5 1.5

Operational power and currentconforming to IEC 60947-5-1 d.c. operation(C.O.: Closing - Opening)

DC-13. 1000 C.O.

Rated operational voltage (Ue) V 24 48 60 110 220

Operational power W 180 240 180 140 120

Occasional breaking and making capacities

W 240 280 240 210 180

Rated operational current (Ie) A 6 5 3 1.3 0.5

Short-circuit protection Conforming to IEC 60947-5-1 By GB2 CB08 circuit-breaker or gG fuse, 6A max

Cabling Solid cable mm2 1 x 1…4 conductor

Flexible cable without cable end mm2 1 x 2.5 conductor

Flexible cable with cable end mm2 1 x 1…2.5 conductor or 2 x 1…2.5 conductors

Tightening torque N.m 0.8

References :page 3/55

Dimensions, schemes :pages 3/62 to 3/73

Page 21: GV2 & GV3

3/20

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakersElectric trips

Characteristics of electric tripsType of circuit-breaker GV2 ME, GV2 P GV3 ME GV7 RType of trip GV AU GV AX (1) GV AS GV3 B GV3 D GV7 AU GV7 AS

Rated insulation voltage (Ui) Conforming to IEC 60947-1 V 690 500 690 690 690 690 690

Conforming to CSA C22-2 n° 14, UL 508

V 600 – 600 600 (B600) 600 (B600) 600 600

Operational voltage Conforming to IEC 60947-1 V 0.85…1.1 Un 0.7…1.1 Un

0.8…1.1 Un 0.85…1.1 Un

0.7…1.1 Un

Drop-out voltage V 0.7…0.35 Un 0.75…0.2 Un

0.7…0.35 Un 0.35…0.7 Ue

0.2…0.75 Ue

Inrush consumption a VA 12 14 12 < 10

c W 8 10.5 7 < 5

Sealed consumption a VA 3.5 5 7 < 5

c W 1.1 1.6 2.5 < 5

Operating time Conforming to IEC 60947-1 From the moment the voltage reaches its operational value until opening of the circuit-breaker.

ms 10…15 10 15 < 50

On-load factor 100 % 100 % 100 %

Cabling Number of conductors 1 or 2 1 or 2 1

Solid cable mm2 1…2.5 1…2.5 1.5

Flexible cable without cable end mm2 0.75…2.5 0.75…2.5 1.5

Flexible cable with cable end mm2 0.75…1.5 0.75…2.5 1

Tightening torque N.m 1.4 max 1.2 1.2

Mechanical durability(C.O.: Closing - Opening)

C.O. 100 000 50 % of the mechanical durability of the circuit-breaker

(1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only, see page 3/68.

References :pages 3/53 to 3/57

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 22: GV2 & GV3

3/21

3

Characteristics 3 TeSys protection components 3

Thermal-magnetic and magnetic motor circuit-breakers GV2Accessories

Characteristics of 3-pole busbars GV2 GpppRated insulation voltage (Ui)

Conforming to IEC 60947-1 V 690

Conventional thermal current (Ith)

Conforming to IEC 60439-1 A 63

Permissible peak current( I peak)

kA 11

Permissible thermal limit(I2t)

kA2s 104

Degree of protection Conforming to IEC 60529 IP 20

Characteristics of terminal blocks GV2 G05 and GV1 G09Rated insulationvoltage (Ui)

Conforming to IEC 60947-1 V 690

Conventional thermal current (Ith)

Conforming to IEC 60439-1 A 63

Degree of protection Conforming to IEC 60529 IP 20

Cabling Solid cable mm2 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 conductors

Flexible cable without cable end mm2 1 x 1.5 to 25 conductor or 2 x 2.5 to 10 conductors

Flexible cable with cable end mm2 1 x 1.5 to 16 conductor or 2 x 1.5 to 4 conductors

Tightening torque Connector N.m 2.2

Screw clamp N.m 1.7

Characteristics of current limiters (GV2 ME and GV2 P)Type GV1 L3 LA9 LB920

Rated insulation voltage (Ui)

Conforming to IEC 60947-1 V 690 690

Conventional thermal current (Ith)

Conforming to IEC 60947-1 A 63 63

Operating threshold rms current A 1500 (non adjustable threshold) 1000 (non adjustable threshold)

Cabling 1 conductor 2 conductors 1 conductor 2 conductors

Solid cable mm2 1.5…25 1.5…10 1.5…25 1.5…10

Flexible cable without cable end mm2 1.5…25 2.5…10 1.5…25 1.5…10

Flexible cable with cable end mm2 1.5…16 1.5… 4 1.5…16 1.5… 4

Tightening torque N.m 2.2

References :pages 3/53 and 3/59

Dimensions, schemes :pages 3/62 to 3/73

Page 23: GV2 & GV3

3/22

3

Curves 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Thermal-magnetic tripping curves for GV2 ME and GV2 PAverage operating time at 20 °C related to multiples of the setting current:

1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state

0,001

0,1

1

10

100

0,01

1 1,5 10 100

1000

10 000

32

1

Time (s)

x the setting current (Ir)

References :pages 3/45 and 3/46

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 24: GV2 & GV3

3/23

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Current limitation on short-circuit for GV2 ME and GV2 P (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V

1 Maximum peak current2 24-32 A3 20-25 A4 17-23 A5 13-18 A6 9-14 A7 6-10 A8 4-6.3 A9 2.5-4 A10 1.6-2.5 A11 1-1.6 A12 Limit of rated ultimate breaking capacity on short-circuit of GV2 ME (14, 18, 23 and 25 A ratings)

1

6

5

4

3

7

8

9

10

11

2

100

10

1

0,10,1 1 10 100

cos

= 0

.95

= 0.

9

= 0.

8

= 0.

7=

0.5

= 0.

3

= 0.

25

15 (12)

Limited peak current (kA)

Prospective Isc (kA)

References :pages 3/45 and 3/46

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 25: GV2 & GV3

3/24

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME

Thermal limit on short-circuit for GV2 METhermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 24-32 A2 20-25 A3 17-23 A4 13-18 A5 9-14 A6 6-10 A7 4-6.3 A8 2.5-4 A9 1.6-2.5 A10 1-1.6 A

100

10

1

0,1

0,010,1 1 10 100

345

6

7

8

9

10

21

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :pages 3/45 and 3/46

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 26: GV2 & GV3

3/25

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakersGV2 P

Thermal limit on short-circuit for GV2 PThermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 24 -32 A1 20-25 A2 17-23 A3 13-18 A4 9-14 A5 6-10 A6 4-6.3 A7 2.5-4 A8 1.6-2.5 A9 1-1.6 A

100

10

1

0,1

0,010,1 1 10 100

123

4

5

6

7

8

9

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :pages 3/45 and 3/46

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 27: GV2 & GV3

3/26

3

Curves 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME

Thermal-magnetic tripping curvesAverage operating time at 20 °C related to multiples of the setting current:

1 3 poles from cold state, 1.6…16 A rating2 3 poles from hot state, 1.6…16 A rating3 3 poles from cold state, 25…80 A rating4 3 poles from hot state, 25…80 A rating

0,001

0,1

1

10

100

0,01

1 10 100

1000

10 000

4

2

3

1

Time (s)

x the setting current (Ir)

References :page 3/47

Dimensions :page 3/65

Schemes :page 3/69

Page 28: GV2 & GV3

3/27

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME

Current limitation on short-circuit (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V

1 Maximum peak current2 56-80 A3 40-63 A4 25-40 A5 16-25 A6 10-16 A7 6-10 A8 4-6 A9 2.5-4 A10 1.6-2.5 A11 1-1.6 A

1

4

3

2

100

10

1

0,10,1 1 10 100

= 0.

9

= 0.

8

= 0.

7=

0.5

= 0.

3

= 0.

25

15

56

7

9

8

10

11

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/47

Dimensions :page 3/65

Schemes :page 3/69

Page 29: GV2 & GV3

3/28

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME

Thermal limit on short-circuitThermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 56 -80 A2 40-63 A3 25-40 A4 16-25 A5 10-16 A6 6-10 A7 4-6 A8 2.5-4 A9 1.6-2.5 A

100

10

1

0,10,1 1 10 10015

321

45

6

7

8

9

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :page 3/47

Dimensions :page 3/65

Schemes :page 3/69

Page 30: GV2 & GV3

3/29

3

Curves 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Thermal-magnetic tripping curves for GV7 RAverage operating time at 20 °C related to multiples of the setting current:

1 Cold state curve2 Cold state curve3 12…14 Ir

In the event of total phase failure, tripping occurs after 4 s ± 20 %

0,001

0,002

0,1

0,01

0,005

0,05

1

0,5

0,02

0,2

2

5

10

20

50

100

200

500

1000

2000

5000

10 000

102 3 4 7 10020 30 405 50 701

3

1

1,12

2

Time (s)

x the setting current (Ir)

References :page 3/48

Dimensions :pages 3/65 and 3/67

Schemes :page 3/69

Page 31: GV2 & GV3

3/30

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Current limitation on short-circuit (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc)

For GV7 RE only

1 GV7 RE2202 GV7 RE1503 GV7 RE100

For GV7 RS only

1 GV7 RS2202 GV7 RS1503 GV7 RS100

4102

5

7

60

20

10

50

100

30

3 4 6 10020 30 40 60

40

70

5 50

6

8

80

1

2

3

70

Limited peak current (kA)

Prospective Isc (kA)

4102

5

7

60

20

10

50

100

30

3 4 6 10020 30 40 60

40

70

5 50

1

2

3

6

8

80

70

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/48

Dimensions :pages 3/65 and 3/67

Schemes :page 3/69

Page 32: GV2 & GV3

3/31

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Thermal limit (3-phase 400/415 V)

Thermal limit

Sum of I2dt = f (prospective Isc)

For GV7 RE only

1 GV7 RE2202 GV7 RE1503 GV7 RE100

For GV7 RS only

1 GV7 RS2202 GV7 RS1503 GV7 RS100

2x104

102

3x104

5x104

2x106

2x105

105

106

107

5x106

3x105

3 4 6 10020 30 40 60

5x105

3x106

5 50 70

1

2

3

Sum of I2dt (A2s)

Prospective Isc (kA)

2x104

102

3x104

5x104

2x106

2x105

105

106

107

5x106

3x105

3 4 6 10020 30 40 60

5x105

3x106

5 50 70

1

2

3

Sum of I2dt (A2s)

Prospective Isc (kA)

References :page 3/48

Dimensions :pages 3/65 and 3/67

Schemes :page 3/69

Page 33: GV2 & GV3

3/32

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Current limitation on short-circuit (3-phase 690 V)

Dynamic stress

I peak = f (prospective Isc)

For GV7 RE only

1 GV7 RE2202 GV7 RE150 and GV7 RE100

For GV7 RS only

1 GV7 RS2202 GV7 RS150 and GV7 RS100

4102

5

6

30

10

8

20

50

40

3 4 6 205

12

7

9

Limited peak current (kA)

Prospective Isc (kA)

4102

5

6

30

10

8

20

50

40

3 4 6 205

12

7

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/48

Dimensions :pages 3/65 and 3/67

Schemes :page 3/69

Page 34: GV2 & GV3

3/33

3

Curves (continued) 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Thermal limit on short-circuit (3-phase 690 V)

Thermal stress limit

Sum of I2dt = f (prospective Isc)

For GV7 RE only

1 GV7 RE2202 GV7 RE150 and GV7 RE100

For GV7 RS only

1 GV7 RS2202 GV7 RS150 and GV7 RS100

102 3 4 6 205

2x106

2x105

105

106

3x105

5x105

3x106

1

2

8

Sum of I2dt (A2s)

Prospective Isc (kA)

102 3 4 6 205

2x106

2x105

105

106

3x105

5x105

3x106

1

2

Sum of I2dt (A2s)

Prospective Isc (kA)

References :page 3/48

Dimensions :pages 3/65 and 3/67

Schemes :page 3/69

Page 35: GV2 & GV3

3/34

3

Curves 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 RT

Thermal-magnetic tripping curves for GV2 RT

1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state

10

10 000

1

0,1

0,0011 10 100

1000

100

0,01

21

3

Time (s)

k x Ir

References :page 3/49

Dimensions :page 3/64

Schemes :page 3/68

Page 36: GV2 & GV3

3/35

3

Curves 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Tripping curves for GV2 L or GV2 LE combined with thermal overload relay LRD or LR2 KAverage operating time at 20 °C related to multiples of the setting current

1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state

10

10 000

1

0,1

0,0011 10 100

1000

100

0,01

32

1

Time (s)

x the setting current (Ir)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 37: GV2 & GV3

3/36

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Current limitation on short-circuit for GV2 L and GV2 LE only (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V

1 Maximum peak current2 32 A3 25 A4 18 A5 14 A6 10 A7 6.3 A8 4 A9 2.5 A10 1.6 A11 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

100

10

1

0,10,1 1 100

1

5

4

3

8

9

10

7

6

cos

= 0

.95

= 0.

9

= 0.

8=

0.7

= 0.

5

= 0.

3

= 0.

25

151011

2

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 38: GV2 & GV3

3/37

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Current limitation on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 K (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V

1 Maximum peak current2 32 A3 25 A4 18 A5 14 A6 10 A7 6.3 A8 4 A9 2.5 A10 1.6 A11 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

100

10

1

0,10,1 1 10 100

cos

= 0

.95

= 0.

9

= 0.

8

= 0.

7=

0.5

= 0.

3

= 0.

25

15 11

1

2

3

4

5

6

7

8

9

10

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 39: GV2 & GV3

3/38

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 LE onlyThermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 32 A2 25 A3 18 A4 14 A5 10 A6 6.3 A7 4 A8 2.5 A9 1.6 A

100

10

1

0,1

0,010,1 1 10 100

1 2

3

4

5

6

7

8

9

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 40: GV2 & GV3

3/39

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 L onlyThermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 25 A and 32 A2 18 A3 14 A4 10 A5 6.3 A6 4 A7 2.5 A8 1.6 A

100

10

1

0,1

0,010,1 1 10 100

1234

5

6

8

7

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 41: GV2 & GV3

3/40

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 KThermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 32 A (GV2 LE32)2 25 A and 32 A (GV2 L32)3 18 A4 14 A5 10 A6 6.3 A7 4 A8 2.5 A9 1.6 A10 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

100

10

1

0,1

0,010,1 1 10 100

2

3

4

5

6

7

8

9

15

1

10

Sum of I2dt (kA2s)

Prospective Isc (kA)

References :page 3/50

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 42: GV2 & GV3

3/41

3

Curves 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Tripping curves for GK3 combined with thermal overload relay LRD 33Average operating time at 20 °C without prior current flow

1 3 poles from cold state2 2 poles from cold state3 3 poles from hot state

A Thermal overload relay protection zoneB GK3 protection zone

10

10 000

1

0,1

0,0011 10 100

1000

100

0,01

32

1

B

A

Time (s)

x the setting current (Ir)

References :page 3/51

Dimensions :page 3/72

Schemes :page 2457/5

Page 43: GV2 & GV3

3/42

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Current limitation on short-circuit for GK3 only (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V

1 Maximum peak current2 80 A3 65 A4 40 A

1

0,11 10 100

10

100

0,1

432

1

Limited peak current (kA)

Prospective Isc (kA)

References :page 3/51

Dimensions :page 3/72

Schemes :page 3/73

Page 44: GV2 & GV3

3/43

3

Curves (continued) 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Thermal limit on short-circuit for GK3 onlyThermal limit in A2s

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V

1 80 A2 65 A3 40 A

10

11 10 100

100

1000

0,1

3

2

1

Sum of I2dt (A2s)

Prospective Isc (kA)

References :page 3/51

Dimensions :page 3/72

Schemes :page 3/73

Page 45: GV2 & GV3

3/44

3

Presentation 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2, GV3 and GV7

GV2 ME, GV2 P, GV3 ME and GV7 R motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers specifically designed for the control and protection of motors, conforming to standards IEC 60947-2 and IEC 60947-4-1

These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2 ME can be supplied with spring terminal connections.These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact and is even more effective when conductors without cable ends are used. Each connection can take two independent conductors.

Control is manual and local when the motor circuit-breaker is used on its own.Control is automatic and remote when it is associated with a contactor.

Pushbutton control.Energisation is controlled manually by operating the Start button “I” 1.De-energisation is controlled manually by operating the Stop button “O” 2, or automatically by the thermal-magnetic protection elements or by a voltage trip attachment.

Control by rotary knob.

Control by rocker lever.Energisation is controlled manually by moving the knob or rocker lever to position “I” 1.De-energisation is controlled manually by moving the knob or rocker lever to position “O” 2.De-energisation due to a fault automatically places the knob or rocker lever in the “Trip” position 3. Re-energisation is possible only after having returned the knob or rocker switch to position “O”.

Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker.The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about 13 times the maximum setting current of the thermal trips.The thermal elements (overload protection) include automatic compensation for ambient temperature variations.The rated operational current of the motor is displayed by means of a graduated knob 4.

Personnel protection is also provided. All live parts are protected against direct finger contact.

The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltage condition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, since the Start button “I” has to be pressed to restart the motor.

With the addition of a shunt trip, de-energisation of the unit can be remotely controlled.

The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position “O” by up to 3 padlocks.

Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distance and indicate the actual position of the moving contacts by the position of the operators.

These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screw fixing or clip-on mounting on symmetrical, asymmetrical or combination rails.

Connection

Operation

IO 1

2

4

GV2 ME

O I12

4

GV3 ME

1

2

4

3

GV2 P

O 23

1

GV7 R

GV2 ME with screw clamp connections

5338

86

GV2 ME with spring terminal connections

5338

87

GV2 P

5338

88

GV3 ME

5338

89

GV7 R

5338

90

GV2 ME and GV3 ME

GV2 P

GV7 R

Protection of motors and personnel

Special features

Characteristics :pages 3/6 to 3/21

Dimensions :pages 3/62 to 3/67

Schemes :pages 3/68 and 3/69

Page 46: GV2 & GV3

3/45

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Thermal magnetic circuit-breakers GV2 ME and GV2 P with screw clamp terminalsGV2 ME: pushbutton control, GV2 P: control by rotary knobStandard power ratings of 3-phase motors50/60 Hz in category AC-3

Setting rangeof thermaltrips (2)

Magnetic tripping currentId ± 20 %

Reference Weight

400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)

kW kA % kW kA % kW kA % A A kg– – – – – – – – – 0.1…0.16 1.5 GV2 ME01 0.260

or GV2 P01 0.350

0.06 g g – – – – – – 0.16…0.25 2.4 GV2 ME02 0.260or GV2 P02 0.350

0.09 g g – – – – – – 0.25…0.40 5 GV2 ME03 0.260

or GV2 P03 0.350

0.12 g g – – – 0.37 g g 0.40…0.63 8 GV2 ME04 0.260

or GV2 P04 0.350

0.18 g g – – – – – – 0.40…0.63 8 GV2 ME04 0.260or GV2 P04 0.350

0.25 g g – – – 0.55 g g 0.63…1 13 GV2 ME05 0.260

or GV2 P05 0.350

0.37 g g 0.37 g g – – – 1…1.6 22.5 GV2 ME06 0.260

or GV2 P06 0.350

0.55 g g 0.55 g g 0.75 g g 1…1.6 22.5 GV2 ME06 0.260or GV2 P06 0.350

– – – 0.75 g g 1.1 g g 1…1.6 22.5 GV2 ME06 0.260

or GV2 P06 0.350

0.75 g g 1.1 g g 1.5 3 75 1.6…2.5 33.5 GV2 ME07 0.260

0.75 g g 1.1 g g 1.5 8 100 1.6…2.5 33.5 GV2 P07 0.350

1.1 g g 1.5 g g 2.2 3 75 2.5…4 51 GV2 ME08 0.2601.1 g g 1.5 g g 2.2 8 100 2.5…4 51 GV2 P08 0.350

1.5 g g 2.2 g g 3 3 75 2.5…4 51 GV2 ME08 0.260

1.5 g g 2.2 g g 3 8 100 2.5…4 51 GV2 P08 0.350

2.2 g g 3 50 100 4 3 75 4…6.3 78 GV2 ME10 0.260

2.2 g g 3 g g 4 6 100 4…6.3 78 GV2 P10 0.350

3 g g 4 10 100 5.5 3 75 6…10 138 GV2 ME14 0.2603 g g 4 50 100 5.5 6 100 6…10 138 GV2 P14 0.350

4 g g 5.5 10 100 7.5 3 75 6…10 138 GV2 ME14 0.260

4 g g 5.5 50 100 7.5 6 100 6…10 138 GV2 P14 0.350

5.5 15 50 7.5 6 75 9 3 75 9…14 170 GV2 ME16 0.260

5.5 g g 7.5 42 75 9 6 100 9…14 170 GV2 P16 0.350

– – – – – – 11 3 75 9…14 170 GV2 ME16 0.260– – – – – – 11 6 100 9…14 170 GV2 P16 0.350

7.5 15 50 9 6 75 15 3 75 13…18 223 GV2 ME20 0.260

7.5 50 50 9 10 75 15 4 100 13…18 223 GV2 P20 0.350

9 15 40 11 4 75 18.5 3 75 17…23 327 GV2 ME21 0.260

9 50 50 11 10 75 18.5 4 100 17…23 327 GV2 P21 0.350

11 15 40 15 4 75 – – – 20…25 327 GV2 ME22 (3) 0.26011 50 50 15 10 75 – – – 20…25 327 GV2 P22 0.350

15 10 50 18.5 4 75 22 3 75 24…32 416 GV2 ME32 0.260

15 35 50 18.5 10 75 22 4 100 24…32 416 GV2 P32 0.350

Thermal magnetic circuit-breakers GV2 ME with lugsTo order termal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected above. Example: GV2 ME08 becomes GV2 ME086.

Thermal magnetic circuit-breakers GV2 ME with built-in auxiliary contact blockWith instantaneous auxiliary contact block (composition, see page 3/53):b GV AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE1TQ.b GV AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE11TQ.b GV AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AN11TQ.These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.(1) As % of Icu.(2) For use of GV2 ME in an enclosure, see page 2/10.(3) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office.g > 100 kA.

GV2 ME

5338

95

GV2 P

533

896

Characteristics :pages 3/6 to 3/9

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 47: GV2 & GV3

3/46

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME

(1) For connection of conductors from 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.(2) As % of Icu.g > 100 kA.

Thermal magnetic circuit-breakers GV2 ME with spring terminal connections (1)

Pushbutton controlStandard power ratings of 3-phase motors 50-60 Hz in category AC-3

Setting rangeof thermaltrips

Magnetictripping currentId ± 20 %

Reference Weight

400/415 V 500 VP Icu Ics (2) P Icu Ics (2)

kW kA % kW kA % A A kg– – – – – – 0.1…0.16 1.5 GV2 ME013 0.280

0.06 g g – – – 0.16…0.25 2.4 GV2 ME023 0.280

0.09 g g – – – 0.25…0.40 5 GV2 ME033 0.280

0.120.18

gg

gg

– – – 0.40…0.63 8 GV2 ME043 0.280

0.250.37

gg

gg

0.37 g g 0.63…1 13 GV2 ME053 0.280

0.370.55

gg

gg

0.370.550.75

ggg

ggg

1…1.6 22.5 GV2 ME063 0.280

0.75 g g 1.1 g g 1.6…2.5 33.5 GV2 ME073 0.280

1.11.5

gg

gg

1.52.2

gg

gg

2.5…4 51 GV2 ME083 0.280

2.2 g g 3 50 100 4…6.3 78 GV2 ME103 0.280

34

gg

gg

45.5

1010

100100

6…10 138 GV2 ME143 0.280

5.5 15 50 7.5 6 75 9…14 170 GV2 ME163 0.280

7.5 15 50 9 6 75 13…18 223 GV2 ME203 0.280

911

1515

4040

11 4 75 17…23 327 GV2 ME213 0.260

11 15 40 15 4 75 20…25 327 GV2 ME223 0.260

Contact blocksDescription Mounting Maximum

numberType of contacts

Sold in lots of

Unit reference

Weightkg

Instantaneous auxiliary contacts

Front 1 N/O + N/C 10 GV AE113 0.030

N/O + N/O 10 GV AE203 0.030

LH side 2 N/O + N/C 1 GV AN113 0.060

N/O + N/O 1 GV AN203 0,060

AccessoryDescription Application Sold in

lots ofUnit reference

Weightkg

Cable end reducer For connection of conductors from 1 to 1.5 mm2

20 LA9 D99 –

GV2 MEpp3

5338

97

LA9 D99

Characteristics :pages 3/6 to 3/19

Dimensions :pages 3/62 to 3/64

Schemes :page 3/68

Page 48: GV2 & GV3

3/47

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME

(1) As % of Icu.(2) Recommended for use in association with a contactor.

Thermal magnetic circuit-breakers GV3 ME with screw clamp terminalsPushbutton controlStandard power ratings of 3-phase motors 50/60 Hz in category AC-3

Settingrange of thermal trips

Reference Weight

400/415 V 500 V 660/690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)

kW kA % kW kA % kW kA % A kg0.370.55

100100

100100

0.370.550.75

100100100

100100100

0.751.1

100100

100100

1…1.6 GV3 ME06 0.600

0.75 100 100 1.1 100 100 1.5 100 100 1.6…2.5 GV3 ME07 0.600

1.11.5

100100

100100

1.52.2

100100

100100

2.23

44

100100

2.5…4 GV3 ME08 0.600

2.2 100 100 3 100 100 4 4 100 4…6 GV3 ME10 0.600

34

100100

100100

45.5

88

100100

5.57.5

44

100100

6…10 GV3 ME14 0.600

7.5 100 50 9 8 100 911

44

100100

10…16 GV3 ME20 0.600

911

100100

5050

1115

88

100100

1518.5

44

100100

16…25 GV3 ME25 0.600

1518.5

3535

5050

18.522

88

7575

2230

44

7575

25…40 GV3 ME40 (2) 0.700

2230

3535

5050

3037

88

7575

3745

44

7575

40…63 GV3 ME63 (2) 0.700

37 15 50 45 4 100 55 2 100 56…80 GV3 ME80 (2) 0.700

GV3 ME20

5338

99

Characteristics :pages 3/6 to 3/10

Dimensions :page 3/65

Schemes :page 3/69

Page 49: GV2 & GV3

3/48

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

(1) As % of Icu.

Thermal magnetic circuit-breakers GV7 R with screw clamp terminalsControl by rocker leverStandard power ratings of 3-phase motors 50/60 Hz in category AC-3

Settingrange of thermal trips

Reference Weight

400/415 V 500 V 660/690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)

kW kA % kW kA % kW kA % A kg7.59

3636

100100

911

1818

100100

1115

88

100100

12…20 GV7 RE20 2.010

7.59

7070

100100

911

5050

100100

1115

1010

100100

12…20 GV7 RS20 2.010

911

3636

100100

1115

1818

100100

1518.5

88

100100

15…25 GV7 RE25 2.010

911

7070

100100

1115

5050

100100

1518.5

1010

100100

15…25 GV7 RS25 2.010

18.5 36 100 18.522

1818

100100

22 8 100 25…40 GV7 RE40 2.010

18.5 70 100 18.5 50 100 22 10 100 25…40 GV7 RS40 2.010

22 36 100 30 18 100 30 8 100 30…50 GV7 RE50 2.015

22 70 100 30 50 100 30 10 100 30…50 GV7 RS50 2.015

37 36 100 4555

1818

100100

55 8 100 48…80 GV7 RE80 2.040

37 70 100 4555

5050

100100

55 10 100 48…80 GV7 RS80 2.040

45 36 100 – 18 100 75 8 100 60…100 GV7 RE100 2.040

45 70 100 – 50 100 75 10 100 60…100 GV7 RS100 2.040

5575

3535

100100

7590

3030

100100

90110

88

100100

90…150 GV7 RE150 2.020

5575

7070

100100

7590

5050

100100

90110

1010

100100

90…150 GV7 RS150 2.020

90110

3535

100100

110132160

303030

100100100

160200

88

100100

132…220 GV7 RE220 2.350

90110

7070

100100

110132160

505050

100100100

160200

1010

100100

132…220 GV7 RS220 2.350

GV7 RE

5339

00

GV7 RS

5339

01

Characteristics :pages 3/6 to 3/11

Dimensions :page 3/65

Schemes :page 3/69

Page 50: GV2 & GV3

3/49

3

References 3 TeSys protection components 3

Thermal-magnetic circuit-breakersGV2 RT

(1) Other accessories such as mounting, cabling and marking accessories are identical to those used for GV2 ME motor circuit-breakers, see page 3/59.

For motors with high current peak on startingControl by rocker leverStandard power ratings of 3-phase motors 50-60 Hz in category AC-3

Setting rangeof thermal trips

Magnetic tripping currentId ± 20 %

Reference Weight

220/230 V

400/415 V

440 V 500 V 690 V

kW kW kW kW kW A A kg0.06 0.09 0.09

0.12– – 0.25…0.40 8 GV2 RT03 0.350

– 0.120.18

0.18 – 0.37 0.40…0.63 13 GV2 RT04 0.350

0.090.12

0.250.37

0.250.37

0.37 0.55 0.63…1 22 GV2 RT05 0.350

0.180.25

0.370.55

0.370.55

0.370.550.75

0.751.1

1…1.6 33 GV2 RT06 0.350

0.37 0.75 0.751.1

1.1 1.5 1.6…2.5 51 GV2 RT07 0.350

0.550.75

1.11.5

1.5 1.52.2

2.23

2.5…4 78 GV2 RT08 0.350

1.1 2.2 2.23

3 4 4…6.3 138 GV2 RT10 0.350

1.52.2

34

4 45.5

5.57.5

6…10 200 GV2 RT14 0.350

2.23

5.5 5.57.5

7.5 911

9…14 280 GV2 RT16 0.350

4 7.5 7.59

9 15 13…18 400 GV2 RT20 0.350

5.5 911

11 11 18.5 17…23 400 GV2 RT21 0.350

For primaries of 3-phase transformersControl by rocker leverStandard power ratings Setting range

of thermal trips

Magnetic tripping currentId ± 20 %

Reference Weight

230/240 V 400/415 V 440 V 500 V 690 VkW kW kW kW kW A A kg

– – – – – 0.25…0.40 8 GV2 RT03 0.350

– – – – – 0.40…0.63 13 GV2 RT04 0.350

– – 0.63 0.63 1 0.63…1 22 GV2 RT05 0.350

0.4 0.63 1 1 – 1…1.6 33 GV2 RT06 0.350

0.63 1 – 1.6 1.62

1.6…2.5 51 GV2 RT07 0.350

1 1.62

1.62

22.5

2.5 2.5…4 78 GV2 RT08 0.350

1.62

2.5 2.54

4 456.3

4…6.3 138 GV2 RT10 0.350

2.5 45

5 56.3

– 6…10 200 GV2 RT14 0.350

4 6.3 6.3 – 1012.5

9…14 280 GV2 RT16 0.350

56.3

10 10 1012.5

10 13…18 400 GV2 RT20 0.350

Accessory (1)Description Reference Weight

kgPadlockable external operator (IP 54)black handle, blue legend plate

GV2 AP03 0.280

GV2 RT

5339

02

Characteristics :pages 3/6 to 3/21

Dimensions :page 3/64

Schemes :page 3/68

Page 51: GV2 & GV3

3/50

3

References 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 LE and GV2 L

Magnetic circuit-breakers GV2 LE and GV2 L with screw clamp terminalsGV2 LE: control by rocker lever, GV2 L: control by rotary knobStandard power ratings of 3-phase motors50/60 Hz in category AC-3

Magnetic protection rating

Tripping currentId ± 20 %

Use in association with thermal overload relay

Reference Weight

400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1)

kW kA kW kA kW kA A A kg0.06 g g – – – – – – 0.4 5 LR2 K0302 GV2 LE03 0.330

0.09 g g – – – – – – 0.4 5 LR2 K0304 GV2 LE03 0.330

or LRD 03 GV2 L03 0.3300.12 g g – – – 0.37 g g 0.63 8 LR2 K0304 GV2 LE04 0.330

or LRD 04 GV2 L04 0.330

0.18 g g – – – – – – 0.63 8 LR2 K0305 GV2 LE04 0.330

or LRD 04 GV2 L04 0.330

– – – – – – 0.55 g g 1 13 LR2 K0305 GV2 LE05 0.330

or LRD 05 GV2 L05 0.3300.25 g g – – – – – – 1 13 LR2 K0306 GV2 LE05 0.330

or LRD 05 GV2 L05 0.330

– – – – – – 0.75 g g 1 13 LR2 K0306 GV2 LE05 0.330

or LRD 06 GV2 L05 0.330

0.37 g g 0.37 g g – – – 1 13 LR2 K0306 GV2 LE05 0.330

or LRD 05 GV2 L05 0.3300.55 g g 0.55 g g 1.1 g g 1.6 22.5 LR2 K0307 GV2 LE06 0.330

or LRD 06 GV2 L06 0.330

– – – 0.75 g g – – – 1.6 22.5 LR2 K0307 GV2 LE06 0.330

or LRD 06 GV2 L06 0.330

0.75 g g 1.1 g g 1.5 3 75 2.5 33.5 LR2 K0308 GV2 LE07 0.330

0.75 g g 1.1 g g 1.5 4 100 2.5 33.5 LRD 07 GV2 L07 0.3301.1 g g – – – – – – 2.5 33.5 LR2 K0308 GV2 LE07 0.330

or LRD 08 GV2 L07 0.330

1.5 g g 1.5 g g 3 3 75 4 51 LR2 K0310 GV2 LE08 0.330

1.5 g g 1.5 g g 3 4 100 4 51 LRD 08 GV2 L08 0.330

– – – 2.2 g g – – – 4 51 LR2 K0312 GV2 LE08 0.330

or LRD 08 GV2 L08 0.3302.2 g g 3 50 100 4 3 75 6.3 78 LR2 K0312 GV2 LE10 0.330

2.2 g g 3 g g 4 4 100 6.3 78 LRD 10 GV2 L10 0.330

3 g g 4 10 100 5.5 3 75 10 138 LR2 K0314 GV2 LE14 0.330

3 g g 4 10 100 5.5 4 100 10 138 LRD 12 GV2 L14 0.330

4 g g 5.5 10 100 – – – 10 138 LR2 K0316 GV2 LE14 0.330

or LRD 14 GV2 L14 0.330– – – – – – 7.5 3 75 10 138 LRD 14 GV2 LE14 0.330

– – – – – – 7.5 4 100 10 138 LRD 14 GV2 L14 0.330

– – – – – – 9 3 75 14 170 LRD 16 GV2 LE16 0.330

– – – – – – 9 4 100 14 170 LRD 16 GV2 L16 0.330

5.5 15 50 7.5 6 75 11 3 75 14 170 LR2 K0321 GV2 LE16 0.330

5.5 50 50 7.5 10 75 11 4 100 14 170 LRD 16 GV2 L16 0.3307.5 15 50 9 6 75 15 3 75 18 223 LRD 21 GV2 LE20 0.330

7.5 50 50 9 10 75 15 4 100 18 223 LRD 21 GV2 L20 0.330

9 15 40 11 4 75 18.5 3 75 25 327 LRD 22 GV2 LE22 0.330

9 50 50 11 10 75 18.5 4 100 25 327 LRD 22 GV2 L22 0.330

11 15 40 15 4 75 – – – 25 327 LRD 22 GV2 LE22 0.330

11 50 50 15 10 75 – – – 25 327 LRD 22 GV2 L22 0.33015 10 50 18.5 4 75 22 3 75 32 416 LRD 32 GV2 LE32 0.330

15 35 50 18.5 10 75 22 4 100 32 416 LRD 32 GV2 L32 0.330

(1) As % of Icu.g > 100 kA.

GV2 LE

534

101

GV2 L

5341

02

Characteristics :pages 3/12 and 3/13

Dimensions :pages 3/70 to 3/72

Schemes :page 3/73

Page 52: GV2 & GV3

3/51

3

References 3 TeSys protection components 3

Magnetic motor circuit-breakers GK3

Magnetic circuit-breakers GK3 with screw clamp connectionsControl by rotary knobStandard power ratings of 3-phase motors 50-60 Hz in category AC-3

Associated equipment Circuit-breakerContactor minimum size

Thermal overload relay

Short-circuit protection

400/415 V 500 V 690 VP Icu Ics (1) P Icu Ics (1) P Icu Ics (1) Reference Reference Rating (1) Reference WeightkW kA kW kA kW kA A kg

15 50 30 18.5 20 30 – – – LC1 D32 LRD 32 40 GK3 EF40 0.710

– – – – – – 22 6 60 LC1 D40 LRD 3353 40 GK3 EF40 0.710

18.5 50 30 22 20 30 30 6 60 LC1 D40 LRD 3355 40 GK3 EF40 0.710

22 35 25 30 15 30 – – – LC1 D50 LRD 3357 65 GK3 EF65 0.790

– – – – – – 37 6 50 LC1 D65 LRD 3357 65 GK3 EF65 0.790

30 35 25 37 15 30 – – – LC1 D65 LRD 3359 65 GK3 EF65 0.790

30 35 25 37 15 30 – – – LC1 D65 LRD 3361 65 GK3 EF65 0.790

– – – – – – 45 6 50 LC1 D80 LRD 3359 65 GK3 EF65 0.790

37 35 25 45 15 30 – – – LC1 D80 LRD 3361 80 GK3 EF80 0.795

37 35 25 55 15 30 – – – LC1 D80 LRD 3363 80 GK3 EF80 0.795

(1) Associated current limiter or fuses, where required. See characteristics page 3/15.

GK3 EF

534

103

Characteristics :pages 3/14 and 3/15

Dimensions :page 3/72

Schemes :page 3/73

Page 53: GV2 & GV3

3/52

3

33

GV2 AK00GV1 L3

GV AD

GV AM11

GV AM11

GV AN

GV AN

GV2 P

GV2 ME

GV AX

GV AU

GV AS

GV AE1

GV AE1

GV AE11, AE20

GV2 L

GV2 LE

Page 54: GV2 & GV3

3/53

3

References 3 TeSys protection components 3

Thermal-magnetic and magnetic motor circuit-breakers GV2 with screw clamp connectionsAccessories

Contact blocksDescription Mounting Maximum

numberType of contacts

Sold in lots of

Unit reference

Weightkg

Instantaneous auxiliary contacts

Front (1) 1 N/O or N/C (2) 10 GV AE1 0.015N/O + N/C 10 GV AE11 0.020

N/O + N/O 10 GV AE20 0.020

Side (LH) 2 N/O + N/C 1 GV AN11 0.050

N/O + N/O 1 GV AN20 0.050

Fault signalling contact + instantaneous auxiliary contact

Side (3)(LH)

1 N/O (fault) + N/O 1 GV AD1010 0.055

+ N/C 1 GV AD1001 0.055N/C (fault) + N/O 1 GV AD0110 0.055

+ N/C 1 GV AD0101 0.055

Short-circuit signalling contact

Side(LH)

1 C/O common point 1 GV AM11 0.045

Electric tripsMounting Voltage Reference Weight

kg

Undervoltage or shunt trips (4)

Side(1 block on RH side of circuit-breaker)

24 V 50 Hz GV Ap025 0.105

60 Hz GV Ap026 0.10548 V 50 Hz GV Ap055 0.105

60 Hz GV Ap056 0.105

100 V 50 Hz GV Ap107 0.105

100…110 V 60 Hz GV Ap107 0.105

110…115 V 50 Hz GV Ap115 0.105

60 Hz GV Ap116 0.105120…127 V 50 Hz GV Ap125 0.105

127 V 60 Hz GV Ap115 0.105

200 V 50 Hz GV Ap207 0.105

200…220 V 60 Hz GV Ap207 0.105

220…240 V 50 Hz GV Ap225 0.105

60 Hz GV Ap226 0.105380…400 V 50 Hz GV Ap385 0.105

60 Hz GV Ap386 0.105

415…440 V 50 Hz GV Ap415 0.105

415 V 60 Hz GV Ap416 0.105

440 V 60 Hz GV Ap385 0.105

480 V 60 Hz GV Ap415 0.105500 V 50 Hz GV Ap505 0.105

600 V 60 Hz GV Ap505 0.105

Undervoltage trip, INRS (can only be mounted on GV2 ME)Safety device for dangerous machines conforming to INRS and VDE 0113

Side(1 block on RH side of circuit-breaker GV2 ME)

110…115 V 50 Hz GV AX115 0.110

60 Hz GV AX116 0.110

127 V 60 Hz GV AX115 0.110220…240 V 50 Hz GV AX225 0.110

60 Hz GV AX226 0.110

380…400 V 50 Hz GV AX385 0.110

60 Hz GV AX386 0.110

415…440 V 50 Hz GV AX415 0.110

440 V 60 Hz GV AX385 0.110

Add-on contact blocksDescription Mounting Maximum

numberReference Weight

kgVisible isolation block (5) Front (1) 1 GV2 AK00 0.150Limiters At top

(GV2 ME and GV2 P)1 GV1 L3 0.130

Independent 1 LA9 LB920 0.320

(1) Mounting of a GV AE contact block or a GV2 AK00 visible isolation block on GV2 P and GV2 L(2) Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted.(3) The GV AD is always mounted next to the circuit-breaker.(4) To order an undervoltage trip: replace the dot (p) in the reference with a U, example: GV AU025.

To order a shunt trip: replace the dot (p) in the reference with an S, example: GV AS025.(5) Visible isolation of the 3 poles upstream of circuit-breaker GV2 P and GV2 L.

LA9 LB920

Characteristics :pages 3/16, 3/20 and 3/21

Dimensions, schemes :pages 3/62 to 3/73

Page 55: GV2 & GV3

3/54

3

33

GV3 A08GV3 A09

GV3 A01...A07

Page 56: GV2 & GV3

3/55

3

References 3 TeSys protection components 3

Motor circuit-breakers, thermal-magnetic GV3 ME and magnetic GK3 with screw clamp connectionsAccessories

For thermal-magnetic motor circuit-breakers GV3 MEContact blocksDescription Type of standard

early break contactsReference Weight

kg

Instantaneous auxiliary contact blocks (1 per circuit-breaker)

N/C + N/O GV3 A01 0.060N/O + N/O GV3 A02 0.060

N/C + N/O + N/O GV3 A03 0.070

N/O + N/O + N/O GV3 A05 0.070

N/O + N/O + 2 volt-free terminals GV3 A06 0.070

N/C + N/O + 2 volt-free terminals GV3 A07 0.070

Fault signalling contacts (1) N/C GV3 A08 0.030

N/O GV3 A09 0.030

Electric tripsDescription Voltages Reference Weight

50 Hz 60 Hz kgUdervoltage trips (1) 110, 120, 127 V 120, 127 V GV3 B11 0.070

220, 240 V 277 V GV3 B22 0.070

380, 415 V 440 V, 480 V GV3 B38 0.070

Shunt trips (1) 110, 120, 127 V 120, 127 V GV3 D11 0.070

220, 240 V 277 V GV3 D22 0.070

380, 415 V 440 V, 480 V GV3 D38 0.070

AccessoryDescription Sold in

lots ofUnit reference

Weightkg

Padlocking device, for locking the start button (on open-mounted product)

5 GV1 V02 0.010

For magnetic circuit-breakers GK3Contact blocksDescription Composition Reference Weight

kgAuxiliary contact blocks for On-Off signalling and “control circuit test” function (1 or 2 blocks per device) mounted on RH side of GK3 EF

N/O GK2 AX10 0.025N/O + N/O GK2 AX20 0.031

N/C + N/O GK2 AX50 0.031

Instantaneous fault signalling contact blocks (1 or 2 blocks per device)mounted on LH side of GK3 EF

N/O GK2 AX12 0.025

N/O + N/O GK2 AX22 0.031N/C + N/O GK2 AX52 0.031

AccessoriesDescription Reference Weight

kgPadlocking device for padlocking the operator, using up to 3 padlocks(padlocks not supplied)

GK3 AV01 0.020

External operator for mounting on the enclosure door.Red Ø 40 pushbutton on yellow plate. Can be locked in position "O" by means of up to 3 padlocks, with door locked in position "I" and door locked in position "O" when padlocked.

GK3 AP03 0.300

(1) 1 voltage trip OR 1 fault signalling contact to be fitted inside the motor circuit-breaker.

Other versions 24 to 690 V, 50 or 60 Hz voltage trips for circuit-breakers GV3 ME.Please consult your Regional Sales Office.

Characteristics :pages 3/16 and 3/20

Dimensions, schemes :pages 3/62 to 3/73

Page 57: GV2 & GV3

3/56

3

33

GV7 RE, RS

GV7 AE11, AB11

GV7 AU, AS

12

34

Page 58: GV2 & GV3

3/57

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connectionsAccessories

Add-on auxiliary contactsThey allow remote indication of the circuit-breaker contact states. They can be used for signalling, electrical locking, relaying, etc. Two versions are available: standard and low level. They include a terminal block and the auxiliary circuits leave the circuit-breaker through a hole provided for this purpose.They perform the following functions, depending on where they are located in the circuit-breaker:

Location Function Application1 and/or 4 C/O contact Indicates the position of the circuit-breaker poles2 Trip indication Indicates that the circuit-breaker has tripped due to an

overload, a short-circuit, a differential fault or the operation of a voltage trip (undervoltage or shunt trip) or of the “push to trip” test button. It resets when the circuit-breaker is reset.

3 Electrical fault indication Indicates that the circuit-breaker has tripped due to an overload, a short-circuit or a differential fault. It resets when the circuit-breaker is reset.

Type Reference Weightkg

Standard GV7 AE11 0.015

Low level GV7 AB11 0.015

Fault discrimination devicesThey make it possible to:b either differentiate a thermal fault from a magnetic fault,b or open the contactor only in the event of a thermal fault.

Voltage Reference Weightkg

a 24...48 and c 24…72 V GV7 AD111 (1) 0.100

z 110…240 V GV7 AD112 (1) 0.100

Electric tripsThese allow the circuit-breaker to be tripped via an electrical control signal.

b Undervoltage trip GV7 AUv Trips the circuit-breaker when the control voltage drops below the tripping threshold, which is between 0.35 and 0.7 times the rated voltage.v Circuit-breaker closing is only possible if the voltage exceeds 0.85 times the rated voltage.Circuit-breaker tripping by a GV7 AU trip meets the requirements of IEC 60947-2.

b Shunt trip GV7 ASTrips the circuit-breaker when the control voltage rises above 0.7 times the rated voltage.

b Operation (GV7 AU or GV7 AS)v When the circuit-breaker has been tripped by a GV7 AU or AS, it must be reset either locally or by remote control. (For remote control, please consult your Regional Sales Office).v Tripping has priority over manual closing: if a tripping instruction is present, manual action does not result in closing, even temporarily, of the contacts.v Durability: 50 % of the mechanical durability of the circuit-breaker.

Type Voltage Reference Weightkg

Undervoltage trip 48 V, 50/60 Hz GV7 AU055 (1) 0.105110…130 V, 50/60 Hz GV7 AU107 (1) 0.110

200…240 V, 50/60 Hz GV7 AU207 (1) 0.110

380…440 V, 50/60 Hz GV7 AU387 (1) 0.105

525 V, 50 Hz GV7 AU525 (1) 0.100

Shunt trip 48 V, 50/60 Hz GV7 AS055 (1) 0.105

110…130 V, 50/60 Hz GV7 AS107 (1) 0.110

200…240 V, 50/60 Hz GV7 AS207 (1) 0.110

380…440 V, 50/60 Hz GV7 AS387 (1) 0.105

525 V, 50 Hz GV7 AS525 (1) 0.100

(1) For mounting of a GV7 AD or a GV7 AU or AS.

Characteristics :pages 3/16, 3/20 and 3/21

Dimensions :pages 3/65 to 3/67

Schemes :page 3/69

Page 59: GV2 & GV3

3/58

3

33

O

TRIP.

RESET RESET

Page 60: GV2 & GV3

3/59

3

References 3 TeSys protection components 3

Thermal-magnetic and magnetic motor circuit-breakers GV2 with screw clamp connectionsAccessories

AccessoriesDescription Application Sold in

lots of Unit reference

Weightkg

Adapter plates For mounting a GV2 ME or GV2 LE by screw fixing

10 GV2 AF02 0.021

For mounting a GV2 ME or GV2 P and contactor LC1 D09…D38 with front faces aligned

1 LAD 311 0.040

Height compensation plate 7.5 mm 10 GV1 F03 0.003

Combination blocks Between GV2 and contactor LC1 K or LP1 K

10 GV2 AF01 0.020

Between GV2 and contactor LC1 D09…D38

10 GV2 AF3 0.016

Between GV2 mounted on LAD 311 and contactor LC1 D09…D38

10 GV2 AF4 0.016

Motor starter adapter plate With 3-pole connection for mounting a GV2 and a contactor LC1 D09…D25

1 GK2 AF01 0.120

Description Application Pitch Reference Weightmm kg

Sets of 3-pole busbars63 A

2 tap-offs 45 GV2 G245 0.036

54 GV2 G254 0.038

72 GV2 G272 0.042

3 tap-offs 45 GV2 G345 0.058

54 GV2 G354 0.060

4 tap-offs 45 GV2 G445 0.07754 GV2 G454 0.085

72 GV2 G472 0.094

5 tap-offs 54 GV2 G554 0.100

Description Application Sold in lots of

Unit reference

Weightkg

Protective end cover For unused busbar outlets 5 GV1 G10 0.005

Terminal block for supply to one or more GV2 G busbar sets

Connection from the top 1 GV1 G09 0.040Can be fitted with current limiter GV1 L3 (GV2 ME and GV2 P)

1 GV2 G05 0.115

Cover for terminal block For mounting in modular panels 10 LA9 E07 0.005

Flexible 3-pole connection for connecting a GV2 to acontactor LC1-D09…D25

Centre distance between mounting rails: 100…120 mm

10 GV1 G02 0.013

Set of connections upstream/downstream

For connecting GV2 ME to a printed circuit board 10 GV2 GA01 0.045

Clip-in marker holders (supplied with each circuit-breaker)

For GV2 P, GV2 L, GV2 LE and GV2 RT (8 x 22 mm)

100 LA9 D92 0.001

Padlockable external operatorsDescription Reference Weight

kgFor GV2 P and GV2 L (150 to 290 mm)

Padlocking in “On” and “Off” positionBlack handle, blue legend plate, IP 54

GV2 AP01 0.200

Padlocking in “Off” positionRed handle, yellow legend plate, IP 54

GV2 AP02 0.200

For GV2 LE Padlocking in “On” and “Off” positionBlack handle, blue legend plate, IP 54

GV2 AP03 0.280

Padlocking deviceDescription Reference Weight

kgFor all GV2 devices For use with up to 4 padlocks (not supplied),

Ø 6 mm shank max.GV2 V03 0.092

Dimensions :pages 3/62 to 3/72

Page 61: GV2 & GV3

3/60

3

33

ON

OFFO

ON

OFFO

ON

OFFO

OFFO

ON

ON

OFFO

GV7 RE, RS

GV7 AP03

OFFO

ON

GV7 AP04

GV7 AP01, AP02

GV7 V01

GV7 AP05

GV7 RE, RS

GV7 AC01

GV7 AC03 GV7 AC01

GV7 AC04

GV7 AC04

Page 62: GV2 & GV3

3/61

3

References 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connectionsAccessories

Cabling accessoriesDescription Application For

contactorSold in lots of

Unit reference

Weight

kgClip-on connectors for GV7 R

Up to 150 A, 1.5…95 mm2 – 3 GV7 AC021 0.300

Up to 220 A, 1.5…185 mm2 – 3 GV7 AC022 0.350

Spreader 3-pole (1)

To increase the pitch to 45 mm – 1 GV7 AC03 0.180

Terminal shields IP 405 (1)

Supplied with sealing accessory

– 1 GV7 AC01 0.125

Phase barriers Safety accessories used when fitting of shields is impossible

– 2 GV7 AC04 0.075

Insulating screens Ensure insulation between the connections and the backplate

– 2 GV7 AC05 0.075

Kit for combination with contactor (2)

Allowing link between the circuit-breaker and the contactor. The cover provides protection against direct finger contact.

LC1 F115…F185 1 GV7 AC06 0.550

LC1 F225 and F265 1 GV7 AC07 0.550

LC1 D115 and D150

1 GV7 AC08 0.550

Direct rotary handleReplaces the circuit-breaker front cover; secured by screws. It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). A conversion accessory allows the direct rotary handle to be mounted on the enclosure door. In this case, the door cannot be opened if the circuit-breaker is in the “ON” position. Circuit-breaker closing is inhibited if the enclosure door is open.

Description Type Degree of protection Reference Weightkg

Direct rotary handle Black handle, black legend plate IP 40 GV7 AP03 0.205

Red handle, yellow legend plate IP 40 GV7 AP04 0.205

Adapter plate (3) Four mounting direct rotary handle on enclosure door

IP 43 GV7 AP05 0.100

Extended rotary handleAllows a circuit-breaker installed in the back of an enclosure to be operated from the front of the enclosure. It comprises:b a unit which replaces the circuit-breaker front cover; secured by screws,b an assembly (handle and front plate) to be fitted on the enclosure door,b an extension shaft which must be adjusted (distance between the mounting surface and the door: 185 mm minimum, 600 mm maximum). It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). This prevents the enclosure door from being opened.

Description Type Degree of protection Reference Weightkg

Extended rotary handle Black handle, black legend plate IP 55 GV7 AP01 0.775

Red handle, yellow legend plate IP 55 GV7 AP02 0.775

Locking deviceAllows circuit-breakers not fitted with a rotary handle to be locked in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied).

Description Application Reference Weightkg

Locking device For circuit-breaker not fitted with a rotary handle GV7 V01 0.100

(1) Terminal shields cannot be used together with spreaders.(2) The kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker.(3) This conversion accessory makes it impossible to open the door if the device is closed and prevents the device from being

closed if the door is open.

Dimensions :pages 3/65 to 3/67

Schemes :page 3/69

Page 63: GV2 & GV3

3/62

3

Dimensions,mounting 3

TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

GV2 ME GV AX GV AD, AM, AN, AU, AS, AX

GV AE

bGV2 MEpp 89

GV2 MEpp3 101(1) MaximumX1 Electrical clearance = 40 mm for Ue y 690 V

GV2 P GV AD, AM, AN, AU, AS GV2 AK00

(1) MaximumX1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V,or 120 mm for Ue = 500 and 690 VX2 = 40 mm

Mounting of GV2 MEOn 35 mm 5 rail On panel with adapter

plate GV2 AF02AM1 PA On pre-slotted mounting

plate On mounting rails DZ5 MB201

c = 78.5 on AM1 DP200 (35 x 7.5)c = 86 on AM1 DE200, ED200 (35 x 15)

Mounting of GV2 POn rail AM1 DE200, ED200 (35 x 15)

On panel On pre-slotted mounting plate AM1 PA

Adapter plate GK2 AF01

b

67,2

X1

46

15,7 X1

11

45=

=

44,5 16 9,3 9,3

81(1)

18

Block GV AD, AM, ANBlock GV AU, AS, AX 15

10

44,5 9,3 9,3

81(1)

1818

89

82

X1

5026

X2

15

6145

==

Block GV AD, AM, AN

Block GV AU, AS

9814

44,5

32

80

50/6

0

4,2

35c

==

AF1 EA4

35

50/6

0

356050

15

DZ5 MB201GV2 AF02

DZ5 ME8

13,5

84

44,5

44,5

106

45

35

54

105

±5

35 5

AF1 EA4

84

13,5 24

5545

135

9,5

Characteristics :pages 3/6 to 3/21

References :pages 3/44 to 3/46

Schemes :page 3/68

Page 64: GV2 & GV3

3/63

3

Dimensions,mounting (continued) 3

TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

GV2 AF01 GV2 AF3Combination GV2 ME + k contactor Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

GV2 ME + LC1 D09…D18 LC1 D25 & D32 GV2 P + LC1 D09…D18 LC1 D25 & D32b 176.4 186.8 b 177.4 187.8

c1 88.65 94.95 c1 88.6 94.95

c 94.15 100.45 c 94.1 100.45

d1 91 91

d 96.8 96.8

GV2 AF4 + LAD 31 GV2 ME + GV1 L3 (current limiter)

Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue y 690 V

7.5 mm height compensation plate GV1 F03

GV2-ME + LC2 D09…D18 LC2 D25 and D32 GV2 P + LC2 D09…D18 LC2 D25 & D32b 188.6 199 b 169.1 199.5c1 92.7 99 c1 116.8 116.8

c 98.2 104.5 c 122.3 122.3

d1 98.3 98.3

d 103.8 103.8

Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 PDoor cut-out

79 45

152

c1

c

45

b

45

b

c1c

dd1

c1

c

d1

d

45

b

45

b

c1

c45

129

44,5

89

77

X1

X1

40

39

3513

1,5...5

7

53 135…284

65

5,2

= =

54

= =

==

54

Characteristics :pages 3/6 to 3/21

References :pages 3/44 to 3/46

Schemes :page 3/68

Page 65: GV2 & GV3

3/64

3

Dimensions,mounting (continued) 3

TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P, GV2 RT

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05

l pGV2 G445 (4 x 45 mm) 179 45GV2 G454 (4 x 54 mm) 206 54

GV2 G472 (4 x 72 mm) 260 72

aNumber of tap-offs 5 6 7 8

GV2 G445 224 269 314 359GV2 G454 260 314 368 422

GV2 G472 332 404 476 548

Sets of busbars GV2 Gppp with terminal block GV1 G09 Sets of busbars GV2 G245, GV2 G254, GV2 G272

lGV2 G245 (2 x 45 mm) 89

GV2 G254 (2 x 54 mm) 98GV2 G272 (2 x 72 mm) 116

Sets of busbars GV2 G554 Sets of busbars GV2 G345 and GV2 G354

lGV2 G345 (3 x 45 mm) 134

GV2 G354 (3 x 54 mm) 152

Dimensions of GV2 RT Mounting of external operator GV2 AP03

X1 Electrical clearance = 40 mm for Ue < 690 V

Mounting of GV2 RTOn 35 mm 7 rail On panel with adapter

plate GV2 AF02On pre-slotted mounting plate AM1 PA

On mounting rails DZ5 MB

c = 80 on AM1 DP200 (35 x 7.5)c = 88 on AM1 DE200, ED200 (35 x 15)

63

l3

a

18

p

45

GV1 G09

30

l

260 l

89

66

X1

44167,5 X1

12,5

45=

=

44,5 1,5...5

13

53 133…282

65

6 = =

12,3

c

44,5

44,5

84,5

50/6

0

4,2

35

AF1 EA4

35

50/6

0

35

6050

15

DZ5 MB201GV2 AF02

DZ5 ME8

Characteristics :pages 3/6 to 3/21

References :pages 3/49 and 3/59

Schemes :page 3/68

Page 66: GV2 & GV3

3/65

3

Dimensions,mounting 3

TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R

Motor circuit-breakers GV3 ME Mounting on rail AM1 DE200 or AM1 ED201

X1 Electrical clearance (ISC max) 40 mm for Ue < 500 V, 50 mm for Ue < 690 V

(1) Block GV3 A01…A07

MountingOn panel On pre-slotted mounting plate AM1 PA

Motor circuit-breakers GV7 R Motor circuit-breakers with terminal shields or phase barriersGV7 R + GV7 AC01 or AC04

(1) 126 for GV7 Rp220(2) Phase barriers: GV7 AC04

(3) Terminal shields: GV7 AC01

Combination of GV7 R and LC1 F with kit GV7 AC0p Minimum electrical clearance

a b cGV7 R + LC1 F115 or F150 + GV7 AC06

119 334 181

GV7 R + LC1 F185 + GV7 AC06

119 338 188

GV7 R + LC1 F225 + GV7 AC07

131 358 188

GV7 R + LC1 F265 + GV7 AC07

131 364 215

Minimum distance between 2 circuit-breakers mounted side-by-side = 0

x1 x2Painted or insulated metal plate,insulation or insulated bar

0 30

Bare metal plate

U y 440 V 5 35

440 V < U < 600 V 10 35U u 600 V 20 35

17,3

22 77,5

113

100…

110

120

5,5

X1

X1

4,5

70,4

(1)

122,5

113

100…

110

61,2

21,2

==

202020

100…

110

113 AF1 EA4

81

86

111 (1)

=

161

=

=

=

125

=

105

= =

35

=

=

321

=

81

=

=

==

==

161

==

357

(2)

(3)

ac

b

x1x1

x2x2

Characteristics :pages 3/6 to 3/21

References :pages 3/47 to 3/48

Schemes :page 3/69

Page 67: GV2 & GV3

3/66

3

Mounting 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7 R

Panel mounting Mounting on 2 mounting rails DZ5 MB201

Flush-mounting1 circuit-breaker GV7 R n circuit-breakers GV7 R

side-by-side

Combination of GV7 R and LC1 F with kit GV7 AC0p

E G HGV7 R + LC1 F115 + GV7 AC06 44 85 120GV7 R + LC1 F150 + GV7 AC06 46 85 120

GV7 R + LC1 F165 + GV7 AC06 48 85 120

GV7 R + LC1 F225 + GV7 AC07 57 85 120

GV7 R + LC1 F265 + GV7 AC07 60 85 120

35

=12

5

35 35

=

135

35

125

DZ5 ME5

15

=

29

=

29

47

76

88 83

==

108

= =

108

==

108

G

EH

Characteristics :pages 3/6 to 3/21

References :page 3/48

Schemes :page 3/69

Page 68: GV2 & GV3

3/67

3

Dimensions,mounting (continued) 3

TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV7

Spreaders GV7 AC03 Cabling Smooth terminals Connectors

aGV7 Rp40…Rp150 19.5

GV7 Rp220 21.5

Direct rotary handle GV7 AP03, GV7 AP04Flush-mounting

Direct rotary handle GV7 AP03 or GV7 AP04 with conversion accessory GV7 AP05Front face cut-out Enclosure viewed from top

Door cut-outs require a minimum distance between the centre of the circuit-breaker and the door hinge point ∆ u 100 + (h x 5).

e = 1 to 3 max

Extended rotary handle GV7 AP01, GV7 AP02

l: 185 min, 600 maxThe shaft of the extended rotary handle GV7 AP01 or GV7 AP022 must be cut to length: l – 126 mm.

45 45

114

30 41

Z

X

X

7010

,5 Z

70

Z

X

19

a

73

4528

155

121

0

I

55

91

36 =

29

=

97

47

76

89

=

41

=

100

59

100

69

=

51

120

=

120

125 ±2

e

9

9,25

h

75

=

60

60

0

I

=

75

==

l

9

9,25

Characteristics :pages 3/6 to 3/21

References :page 3/48

Schemes :page 3/69

Page 69: GV2 & GV3

3/68

3

Schemes 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P and GV2 RT

GV2 MEpp and GV2 RT GV2 Ppp

Current limiter Front mounting add-on contact blocksInstantaneous auxiliary contacts

GV1 L3 GV AE1 GV AE11 GV AE20

Side mounting add-on contact blocksInstantaneous auxiliary contacts and fault signalling contactsGV AD0110 GV AD0101 GV AD1010 GV AD1001

Instantaneous auxiliary contacts Short-circuit signalling contactsGV AN11 GV AN20 GV AM11

Voltage tripsGV AUppp GV ASppp GV AXppp

Use of fault signalling contact and short-circuit signalling contact

Connection of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

1/L1

3/L2

5/L3

1314 12

11or

1314 22

21 1314

2324

535496

95

5251

9695 97

98

5354

9798

5152

(62) 32

(61) 31 43 (73)

44 (74)

(64) 34

(63) 33 43 (73)

44 (74) 05

0608

D1

D2

C1

C2

D1

D2

E1

E2

GV AD10ppGV AM11

Short-circuit signalling

Trip signalling

N/C or N/O Start-Stop contact

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

D1

D2

E2

E1

10Agl max

Characteristics :pages 3/6 to 3/21

References :pages 3/45 to 3/47

Dimensions :pages 3/62 to 3/64

Page 70: GV2 & GV3

3/69

3

Schemes 3 TeSys protection components 3

Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R

Motor circuit-breakers Auxiliary contact blocksGV3 ME GV3 A01 GV3 A02 GV3 A03 GV3 A05 GV3 A06 GV3 A07

Fault signalling contacts Voltage tripsGV3 A08 GV3 A09 GV3 B GV3 D

Motor circuit-breakers Add-on auxiliary contacts according to their location (1)GV7 R GV7 AE11, GV7 AB11 Location 1

C/O contactLocation 2Trip indication

Location 3Electrical fault indication

Location 4C/O contact

A self-adhesive label, supplied with the contact, can be affixed to the front face of the circuit-breaker to allow personalised marking according to the function of the contact or contacts.

(1) See pages 3/18 and 3/57.

Electric tripsGV7 AUppp GV7 ASppp GV7 AD111, AD112

Recommended application schemes GV7 AD111, AD112Fault indication Contactor opening on overload

Associated componentsKA1: CA2 KN or CAD N

Associated componentsKA1: CAD N + LA6 DK10 or RHKKM1: LC1 D or LC1 F

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3 13

14 2221 13

14

2324

1314

2324 32

31 1314

2324

3334

1314

2324

3334

2324 32

311314

9695 97

98

D1

D2

U

C1

C2

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

1114 12

9194 92

8184 82

2124 22

D1

D4

C1

C2

9897 50 ms

9897 50 ms

– KA1

2324

1314

– KA1

Reset

Overload fault

9897 50 ms

– KM1– KA1

A1

A2

A1

A2

B1

– KA1

2122

Reset

Characteristics :pages 3/6 to 3/21

References :pages 3/47 and 3/48

Dimensions :pages 3/65 to 3/67

Page 71: GV2 & GV3

3/70

3

Dimensions,mounting 3

TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

GV2 L GV AD, AM, AN, AU, AS GV2 AK00

X1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V, or 120 mm for Ue = 500 and 690 V.X2 = 40 mm.

(1) Maximum

Mounting of GV2 L Adapter plate GK2 AF01On rail AM1 DE200, AM1 ED200 (35 x 15)

On panel On pre-slotted mounting plate AM1 PA

7.5 mm height compensation plate GV1 F03

GV2 LE GV AD, AM, AN, AU, AS GV AE

X1 Electrical clearance = 40 mm for Ue y 690 V. (1) Maximum

Mounting of GV2 LEOn 35 mm 7 rail On panel with adapter plate GV2 AF02 On pre-slotted plate AM1 PA On rails DZ5 MB201

c = 80 on AM1 DP200 (35 x 7.5) and 88 on AM1 DE200, ED200 (35 x 15)

44,5 9,3 9,3

81 (1)

1818

89

82

X1

5026

X2

15

6145

==

Block GV AD, AM, AN

Block GV AU, AS9814

44,5

32

13,5

84

44,5

44,5

106

45

35

54

105±

5

35

Ø5,5

5

AF1 EA4

84

13,5 24

5545

135

9,5

39

3513

44

89

167,5

6612,5

X1

X1 44,5

45=

=

9,3 9,3 18

81 (1)

Block GV AD, AM, AN

Block GV AU, AS 15

10

c

44,5

44,5

84,54,2

35

50/6

0

AF1 EA4

35

50/6

0

15 35

50 60

DZ5 MB201GV2 AF02

DZ5 ME8

Characteristics :pages 3/6 to 3/21

References :page 3/50

Schemes :page 3/73

Page 72: GV2 & GV3

3/71

3

Dimensions,mounting (continued) 3

TeSys protection components 3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 L

Mounting of external operator GV2 AP03 for GV2 LE

Door cut-out

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05

l pGV2 G445 (4 x 45 mm) 179 45GV2 G454 (4 x 54 mm) 206 54

GV2 G472 (4 x 72 mm) 260 72

aNumber of tap-offs 5 6 7 8

GV2 G445 224 269 314 359GV2 G454 260 314 368 422

GV2 G472 332 404 476 548

5,2

= =

1,5...5

7

53 6135…284

65

1,5...5

13

53 133…282

65

6 = =

12,3

54

= =

==

54

4xØ3,5 Ø43

63

l3

a

18

p

45

Characteristics :pages 3/12 and 3/13

References :page 3/50

Schemes :page 3/73

Page 73: GV2 & GV3

3/72

3

Dimensions,mounting 3

TeSys protection components 3

Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3

Sets of busbars GV2 Gppp with terminal block GV1 G09 Sets of busbars GV2 G245, GV2 G254, GV2 GR272

lGV2 G245 (2 x 45 mm) 89

GV2 G254 (2 x 54 mm) 98

GV2 G272 (2 x 72 mm) 116

Set of busbars GV2 G554 Sets of busbars GV2 G345 and GV2 G354

lGV2 G345 (3 x 45 mm) 134GV2 G354 (3 x 54 mm) 152

GK3 EF GK3 EF + 4 GK2 AX

Number of GK2 AX0 1 2 3 4

a 66 74.8 83.5 92.5 101

X1 Electrical clearance, 40 mm for Ue y 690 V.

MountingOn mounting rail AM1 EDpp or AM1 Dpppp On panel

Mounting of external operator GK3 AP03 Door cut-out

(1) 150 min, 305 max. with operating shaft, 97 without operating shaft

GV1 G09

30

l

260 l

70 4,515

120

X1

X1

105 38 28

45=

=

a

80

115,5115,5

=10

5=

=20=

4xØ4,5

(1)53

1,5…5

12065 =

=

54

4xØ3,5 Ø43

==

54

Characteristics :pages 3/12 to 3/15

References :pages 3/50 and 3/51

Schemes :page 3/73

Page 74: GV2 & GV3

3/73

3

Schemes 3 TeSys protection components 3

Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3

GV2 Lpp GV2 LEpp

Front mounting add-on contact blocksInstantaneous auxiliary contactsGV AE1 GV AE11 GV AE20

Side mounting add-on contact blocksInstantaneous auxiliary contacts and fault signalling contactsGV AD0110 GV AD0101 GV AD1010 GV AD1001

Instantaneous auxiliary contacts Short-circuit signalling contactsGV AN11 GV AN20 GV AM11

Voltage tripsGV AUppp GV ASppp

Motor circuit-breakers GK3 EF

Start-Stop signalling contact blocksGK2 AX10 GK2 AX20 GK2 AX50

Fault signalling contact blocksGK2 AX12 GK2 AX22 GK2 AX52

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

2/T

1

4/T

2

6/T

3

1/L1

3/L2

5/L3

1314 12

11

OR

1314 22

21 1314

2324

535496

95

5251

9695 97

98

5354

9798

5152

(62) 32

(61) 31 43 (73)

44 (74)

(64) 34

(63) 33 43 (73)

44 (74) 05

0608

D1

D2

C1

C2

2 4 6

– Q

1 3 5

1314

1314

2324 22

211314

9798

9798

0708

9798 06

05

Characteristics :pages 3/12 to 3/15

References :pages 3/50 and 3/51

Dimensions :pages 3/70 to 3/72

Page 75: GV2 & GV3

3/74

3

Selection guide 3 Protection components 3

Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformers

Applications Protection of industrial equipment control circuits and of single-phase loads

Tripping threshold on short-circuit 5…7 In 12…16 In

Operational current 0.5 and 1 A 0.5…20 A

Maximum operational voltage 415 V 250 V

Number of poles 1 1 + neutral

Breaking capacity (Icu) conforming to IEC 60947-2 50 kA at 415 V 1.5…50 kA at 415 V 1.5…50 kA at 250 V

Device type GB2 CS GB2 CB GB2 CD

Pages 3/81 3/80 3/80

Page 76: GV2 & GV3

3/75

3

33

Protection of transformers

Single-phase y 5000 VA/415 V 3-phase y 10 kVA/415 VPrimary Secondary

About 20 In

0.25…23 A

415 V 690 V

2 1 + neutral 3

1.5…50 kA at 415 V 1.5…50 kA at 250 V 15…100 kA at 415 V

GB2 DB GB2 DB GB2 CD GV2 RT

3/80 3/80 3/80 3/49

Page 77: GV2 & GV3

3/76

3

Presentation, selection 3 Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

GB2 thermal-magnetic circuit-breakers protect and isolate the control circuits of industrial equipment with contactor coils, transformers.…They protect and isolate single-phase auxiliary circuits such as solenoid valves, electro-brakes, battery chargers, supplied from the control circuit voltage.

12 ratings are available, from 0.5 to 20 A, in single-pole (GB2 CB), single-pole + neutral (GB2 CD) and 2-pole (GB2 DB) versions.They have a magnetic tripping threshold set at between 12 and 16 In to withstand the current peaks generated by many industrial components.

2 ratings are available, 0.5 and 1 A, in single-pole version.The magnetic tripping threshold is set between 5 and 7 In.

Clip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick mounting plates.Upstream and downstream marking by means of AB1 clip-in markers.Clear indication of “I” and “O” positions on the operator.Tamper-proof device which requires no special maintenance (fixed magnetic and thermal tripping thresholds).

Single-phase transformers.Magnetising peak: 20 In.Operation of magnetic trips: 13 In.

(1) If the breaking capacity of the GB2 is insufficient, use a GV2 RT with 2 poles connected in series, see page 3/49.

Presentation

GB2 CB, GB2 CD, GB2 DB

GB2 CS

Functions, installation

Selection for the protection of circuits supplied by transformers

Power Primary (1) SecondaryVA 220/240 V 380/415 V 24 V 48 V 110 V 220 V

40 GB2 DB05 GB2 DB05 GB2 CD07 GB2 CD06 GB2 CD05 GB2 CD05

63 GB2 DB05 GB2 DB05 GB2 CD08 GB2 CD07 GB2 CD06 GB2 CD05

100 GB2 DB06 GB2 DB05 GB2 CD10 GB2 CD07 GB2 CD06 GB2 CD05

160 GB2 DB07 GB2 DB06 GB2 CD14 GB2 CD09 GB2 CD07 GB2 CD06

250 GB2 DB07 GB2 DB06 GB2 CD16 GB2 CD12 GB2 CD08 GB2 CD07

400 GB2 DB08 GB2 DB07 GB2 CD22 GB2 CD14 GB2 CD09 GB2 CD07

630 GB2 DB10 GB2 DB08 – GB2 CD21 GB2 CD12 GB2 CD08

1000 GB2 DB14 GB2 DB09 – – GB2 CD16 GB2 CD10

1600 GB2 DB20 GB2 DB14 – – – GB2 CD14

2000 GB2 DB21 GB2 DB14 – – GB2 CD22 GB2 CD16

2500 GB2 DB22 GB2 DB20 – – – GB2 CD20

3000 GB2 DB22 GB2 DB20 – – – GB2 CD21

4000 – GB2 DB21 – – – GB2 CD22

5000 – GB2 DB22 – – – –

Characteristics :pages 3/77 to 3/79

References :pages 3/80 and 3/81

Dimensions :page 3/81

Schemes :page 3/81

Page 78: GV2 & GV3

3/77

3

Characteristics 3 Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type GB2 CB GB2 CD GB2 DB GB2 CS

EnvironmentConforming to standards IEC 60947-1, 947-2, EN 60947-1, 60947-2

Product certifications CSA, NEMKO, UL NEMKO, UL – –

Protective treatment “TC”Degree of protection Conforming to IEC 60529 IP 20

Shock resistance Conforming to IEC 60068-2-27 22 gn for 20 ms

Vibration resistance Conforming to IEC 60068-2-6 5 gn (5…110 Hz)

Ambient air temperature around the device

Storage °C - 40…+ 80

Operation °C - 20…+ 60

Flame resistance Conforming to IEC 60695-2-1 °C 960Maximum operating altitude m 3000

Operating position In relation to normal vertical mounting plane

GB2 CB,CD, CS GB2 DB

Cabling Minimum c.s.a. Maximum c.s.a.Solid cable mm2 1 x 0.75 1 x 6 or 2 x 4

Flexible cable with cable end mm2 1 x 0.75 1 x 4 or 2 x 2.5

Tightening torque N.m 1.2

Technical characteristicsUtilisation category Conforming to IEC 60947-2 A A A A

Rated operational voltage (Ue)

Conforming to IEC 60947-2 V 415 (1) 250 415 415 (1)

Conforming to CSA C22-2 Nr 14 and UL 1077

V 277 – 277 –

Rated operational frequency Conforming to IEC 60947-2 Hz 50/60 50/60 50/60 50/60Rated impulse withstand voltage (U imp)

Conforming to IEC 60947-2 kV 4 4 4 4

Total power dissipated per pole W 2 2 2 1.9

Mechanical andelectrical durability

C.O.: Closing - Opening C.O. 8000 8000 8000 8000

Operational current correction coefficient (a or c)

According to the permissible ambient temperature

°C - 20 - 10 0 + 10 + 20 + 30 + 40 + 50 + 60

Correction coefficient 1.2 1.15 1.1 1.05 1 0.95 0.90 0.85 0.80

Tripping threshold Of the magnetic trips 12…16 In 12…16 In 12…16 In 5…7 In

(1) One GB2 circuit-breaker on each live conductor.

Tripping curvesAverage operating time at 20 °C without prior current flow (cold state)

GB2 CB, GB2 CD, GB2 DB GB2 CS

1,051,5

2 3 4 5 6 810

1

52

2010

10050

1

52

2010

1

52

2010

60120

500200

100 x In1,051,5

2 3 4 5 6 810

1

52

2010

10050

1

52

2010

1

52

2010

60120

500200

100 x In

Mill

ise

cond

sS

econ

dsM

inu

tes

1,051,5

2 3 4 5 6 810

1

52

2010

10050

1

52

2010

1

52

2010

60120

500200

100 x In

Mill

ise

cond

sS

econ

dsM

inu

tes

Presentation, selection :page 3/76

References :pages 3/80 and 3/81

Dimensions :page 3/81

Schemes :page 3/81

Page 79: GV2 & GV3

3/78

3

Characteristics (continued) 3 Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type GB2CB05 CB06 CB07 CB08 CB09 CB10 CB12 CB14 CB16 CB20 CB21 CB22

Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

Breaking capacityconforming to IEC 60947-2 a 50/60 Hz

110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2

Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

230/240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

400/415 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

Associated fuses, if requiredif Isc > breaking capacity Icu conforming to IEC 60947-2

110 V aM A g g 20 25 25 40 40 50 50 63 63 63

gG A g g 25 32 32 50 50 63 63 80 80 80

230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50

gG A g g 25 32 32 40 40 50 50 63 63 63

400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50

gG A g g 25 32 32 40 40 50 50 63 63 63

Circuit-breaker type GB2CD05 CD06 CD07 CD08 CD09 CD10 CD12 CD14 CD16 CD20 CD21 CD22

Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

Breaking capacityconforming to IEC 60947-2 a 50/60 Hz

110 V Icu kA 50 50 15 10 6 3 3 3 2 2 2 2

Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

230/ 240 V Icu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

Associated fuses, if requiredif lsc > breaking capacity Icu conforming to IEC 60947-2

110 V aM A g g 20 25 25 40 40 50 50 63 63 63

gG A g g 25 32 32 50 50 63 63 80 80 80

230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50

gG A g g 25 32 32 40 40 50 50 63 63 63

Circuit-breaker type GB2DB05 DB06 DB07 DB08 DB09 DB10 DB12 DB14 DB16 DB20 DB21 DB22

Rating A 0.5 1 2 3 4 5 6 8 10 12 16 20

Breaking capacityconforming to IEC 60947-2 a 50/60 Hz

110 V lcu kA 50 50 15 10 6 3 3 3 2 2 2 2

Ics % (1) 100 50 50 50 50 75 75 75 75 75 75 75

230/240 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 1.5

Ics % (1) 25 25 25 50 50 75 75 75 75 75 75 75

400/415 V lcu kA 50 50 15 3 3 2 1.5 1.5 1.5 1.5 1.5 75

Ics % (1) 25 25 25 50 50 75 75 75 75 75 1.5 75

Associated fuses, if requiredif lsc > breaking capacity Icu conforming to IEC 60947-2

110 V aM A g g 20 25 25 40 40 50 50 63 63 63

gG A g g 25 32 32 50 50 63 63 80 80 80

230/240 V aM A g g 16 20 20 32 32 40 40 50 50 50

gG A g g 25 32 32 40 40 50 50 63 63 63

400/415 V aM A g g 16 20 20 32 32 40 40 50 50 50

gG A g g 25 32 32 40 40 50 50 63 63 63

(1) As % of Icu.g Fuse not required. Breaking capacity Icu > lsc.

Presentation, selection :page 3/76

References :pages 3/80 and 3/81

Dimensions :page 3/81

Schemes :page 3/81

Page 80: GV2 & GV3

3/79

3

Characteristics (continued) 3 Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type GB2pp05 pp06 pp07 pp08 pp09 pp10 pp12 pp14 pp16 pp20 pp21 pp22

Breaking capacity (lcu) conforming to IEC 60947-2c

24 V kA 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.548 V kA 1 1 1 1 1 1 1 1 – – – –

Operational currentconforming to IEC 60947-5-1 c

DC-12 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20

48 V A 0.5 1 2 3 4 5 6 8 10 12 16 20

DC-13 24 V A 0.5 1 2 3 4 5 6 8 10 12 16 20

48 V A 0.5 1 2 3 4 5 6 8 – – – –

Circuit-breaker type GB2CS05 CS06

Rating A 0.5 1

Breaking capacityconforming to IEC 60947-2 a 50/60 Hz

110 V lcu kA 50 50

lcs % (1) 100 100

230/240 V lcu kA 50 50

lcs % (1) 25 25

400/415 V (2)

lcu kA 50 50

lcs % (1) 25 25

Breaking capacity (lcu) conforming to IEC 60947-2c

24 V kA 1.5 1.5

48 V kA 1 1

Operational currentconforming to IEC 60947-5-1 c

DC-12 24 V A 0.5 1

48 V A 0.5 1

DC-13 24 V A 0.5 1

48 V A 0.5 1

Maximum permissible line length for star-delta starting (length of cable containing 2 or more conductors)

With contactors LCp D09 …D18

Operational voltage V 48 110 230 48 110 230

C.s.a. 060 mm2 m (3) 31 365 6 85 230

0.75 mm2 m (3) 39 460 8 110 290

1 mm2 m (3) 52 610 10 145 380

1.5 mm2 m (3) 78 910 15 220 570

2.5 mm2 m (3) 130 1520 26 360 9504 mm2 m (3) 200 2400 41 580 1500

With contactors LCp D25…D32

Operational voltage V 48 110 230 48 110 230

C.s.a. 0.60 mm2 m (3) (3) 230 (3) 56 230

0.75 mm2 m (3) (3) 290 (3) 70 290

1 mm2 m (3) (3) 390 (3) 95 380

1.5 mm2 m (3) (3) 580 (3) 140 570

2.5 mm2 m (3) (3) 970 (3) 230 950

4 mm2 m (3) (3) 1500 (3) 375 1500

With contactors LCp D40…D80

Operational voltage V 48 110 230 48 110 230

C.s.a. 0.60 mm2 m (3) (3) 46 (3) 13 1000.75 mm2 m (3) (3) 60 (3) 17 130

1 mm2 m (3) (3) 80 (3) 22 170

1.5 mm2 m (3) (3) 120 (3) 34 250

2.5 mm2 m (3) (3) 190 (3) 56 420

4 mm2 m (3) (3) 310 (3) 90 680

(1) As % of Icu.(2) One GB2 CS circuit-breaker on each live conductor.(3) Use relays.

Presentation, selection :page 3/76

References :pages 3/80 and 3/81

Dimensions :page 3/81

Schemes :page 3/81

Page 81: GV2 & GV3

3/80

3

References 3 Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breakers with magnetic tripping threshold: 12 to 16 InSingle-poleConventionalrated thermal current Ith (1)

Magnetictripping currentId ± 20 %

Sold in lots of

Unitreference

Weight

A A kg0.5 6.6 6 GB2 CB05 0.060

1 14 6 GB2 CB06 0.060

2 26 6 GB2 CB07 0.0603 40 6 GB2 CB08 0.060

4 52 6 GB2 CB09 0.060

5 66 6 GB2 CB10 0.060

6 83 6 GB2 CB12 0.060

8 108 6 GB2 CB14 0.060

10 138 6 GB2 CB16 0.06012 165 6 GB2 CB20 0.060

16 220 6 GB2 CB21 0.060

20 270 6 GB2 CB22 0.060

Single-pole + neutralConventional rated thermal current Ith (1)

Magnetic tripping current Id ± 20 %

Sold in lots of

Unit reference

Weight

A A kg0.5 6.6 6 GB2 CD05 0.0701 14 6 GB2 CD06 0.070

2 26 6 GB2 CD07 0.070

3 40 6 GB2 CD08 0.070

4 52 6 GB2 CD09 0.070

5 66 6 GB2 CD10 0.070

6 83 6 GB2 CD12 0.0708 108 6 GB2 CD14 0.070

10 138 6 GB2 CD16 0.070

12 165 6 GB2 CD20 0.070

16 220 6 GB2 CD21 0.070

20 270 6 GB2 CD22 0.070

2-poleConventional rated thermal current Ith (1)

Magnetictripping currentId ± 20 %

Sold in lots of

Unit reference

Weight

A A kg0.5 6.6 3 GB2 DB05 0.115

1 14 3 GB2 DB06 0.115

2 26 3 GB2 DB07 0.115

3 40 3 GB2 DB08 0.1154 50 3 GB2 DB09 0.115

5 66 3 GB2 DB10 0.115

6 83 3 GB2 DB12 0.115

8 108 3 GB2 DB14 0.115

10 138 3 GB2 DB16 0.115

12 165 3 GB2 DB20 0.11516 220 3 GB2 DB21 0.115

20 270 3 GB2 DB22 0.115

(1) Conforming to IEC 60947-1.

534

268

GB2 CBpp

5342

69

GB2 CDpp

5342

70

GB2 DBpp

Presentation, selection :page 3/76

Characteristics :pages 3/77 to 3/79

Dimensions :page 3/81

Schemes :page 3/81

Page 82: GV2 & GV3

3/81

3

References (continued),dimensions,schemes 3

Protection components 3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breakers with magnetic tripping threshold: 5 to 7 InSingle-poleConventional rated thermal current Ith (1)

Magnetic tripping currentId ± 20 %

Sold in lots of

Unit reference

Weight

A A kg0.5 3.3 6 GB2 CS05 0.055

1 6 6 GB2 CS06 0.055

(1) Conforming to IEC 60947-1.

Accessories for circuit-breakers GB2 CB, DB and CSDescription Sold in

lots ofUnit reference

Weight

kgBusbar set for supply to 10 GB2 DB or 20 GB2 CB or GB2 CS with 2 connectors

1 GB2 G210 0.100

Supply connector 10 GB2 G01 –

DimensionsGB2 CBpp, GB2 CDpp, GB2 CSpp GB2 DBpp

Marking: up to twelve AB1 R clip-in markers.

SchemesGB2 CBpp GB2 CDpp GB2 DBpp GB2 CSpp

5342

71

GB2 CSpp

74

1582

82

75

79

67

30

74

85

85

78

82

70

2/T

11/

L1

2/T

11/

L1

3/L2

(13

) 4

/T2

( 14)

1/L1

3/L2

2/T

1

4/T

2

2/T

11/

L1

Presentation, selection :page 3/76

Characteristics :pages 3/77 and 3/79