16ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for
Repair/Replace Decisionsand Performance Optimization
Electrical ApparatusService Association, Inc.1331 Baur Blvd.St. Louis, Missouri 63132 USA
314-993-2220 • FAX 314-993-1269
www.easa.com
This paper was presented by Austin H. Bonnett, EASA Education and Technology Consultant
at EASA's Convention in Chicago, Illinois, June 25, 2001
![Page 2: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/2.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 2/16
1ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
By Austin M. BonnettEducation and Technology Consultant
Electrical Apparatus Service Association, Inc.
St. Louis, Missouri
Chuck Yung
Technical Support Specialist
Electrical Apparatus Service Association, Inc.
St. Louis, Missouri
ABSTRACT
For general-purpose motors, there are many cases where
replacing a failed motor with a new one of EPACT effi-
ciency levels or better is the best choice. However, insome cases, the motor will fail again unless the root cause
of failure is addressed through some modification to the
motor or the system.
There are also many cases where repairing the existing
motor is the best choice. This is especially true if an up-
grade is required to address the cause of failure, or in
some cases, where cost, availability or unique perfor-
mance is an issue. The motor service center is in an
excellent position to make these assessments. The pur-
pose of this paper is to explore both choices and present
some of the many options available.
Quite often when a motor fails, the procedure is to re-
move the damaged motor from service and replace it
without a thorough evaluation of the “root cause” of the
failure. Depending on the motor size and the amount of
damage, the old motor may be repaired and placed into
spares inventory or even scrapped.
The problem with this approach is that the replacement
motor, whether new or rebuilt, may fail again for the same
reason. If a root cause failure analysis is conducted, it is
often possible to identify and correct the underlying
cause. All that may be required is to modify the motor,
driven equipment or system to extend the mean time
between failures (MTBF) significantly.
In most cases, where a standard motor is no longer suit-
able for the application, the service center is able to make
the required modification faster than the motor manu-
facturer can produce a unique model.
The application checklist in Appendix A can be used to
assist in this analysis.
INTRODUCTION
The Electrical Apparatus Service Association (EASA) has
established Recommended Practices for its 2500 mem-
bers around the world to assure that the repair process
does not degrade the motor performance characteris-
Reliable Solutions Today!
GUIDELINES FOR REPAIR/REPLACE DECISIONS
AND PERFORMANCE OPTIMIZATION
This paper was presented at EASA's Convention inChicago, Illinois, June 25, 2001.
MOTOR REPAIR BEST PRACTICE GUIDES
The Electrical Apparatus Service Association (EASA)
has available the following repair guidelines to assistin providing quality motor repairs.
• ANSI/EASA — AR100-1998, Recommended
Practice for the Repair of Rotating Electrical Ap-
paratus , Copyright 1998.
• Association of Electrical and Mechanical Trades
(AEMT) — Good Practice Guide: The Repair of
Induction Motors, Best Practices to Maintain En-
ergy Efficiency , Crown Copyright 1998.
• EASA — A Guide to AC Motor Repair and Re-
placement , Copyright 1999.
These documents can be obtained from EASA head-
quarters in St. Louis to be used as reference
documents when selecting or working with a motor
repair facility.
Appendix D includes several sample pages from these
documents.
![Page 3: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/3.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 3/16
2ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
tics. This paper provides the reader with a repair guide-
line to implement these procedures with their local repair
organizations.
Criteria are presented to determine when the repair of
the motor is not practical and may lead to reduced effi-
ciency levels. In some cases, it is possible to improve
the level of operating efficiency during the repair pro-cess.
EASA members rebuild electrical equipment, primarily
motors and generators. Many EASA service centers also
rebuild peripheral equipment such as pumps and
switchgear.
EASA is in the process of conducting a major test pro-
gram to verify the results of these Recommended
Practices. This paper will include an update on this work
in progress.
EASA/AEMT MOTOR REWIND STUDY
INTRODUCTION
Previous studies were conducted on motors in the 10 hp
range at four-pole speeds, which do not reflect the true
degree of difficulty associated with rewinding the typical
failed motor. The EASA/AEMT Motor Rewind Study is
focusing on motors that are more typically rewound for
both the NEMA and IEC designs.
OBJECTIVE OF STUDY
The major objectives of the study include:• Issue a best practice guide for motor rewinds.
• Determine whether low- and medium-voltage ma-
chines respond similarly.
• Investigate the impact of repeated rewinds of the
same motor.
• Establish the correlation between the static core
loss test and the running core loss test .
• Evaluate the impact of physical damage to the sta-
tor core.
SCOPE OF PRODUCT EVALUATED
There will be at least 27 motors used in the study, most
of which will be in the 50 to 200 hp range. Both 50 and60 Hertz will be included, as well as low- and medium-
voltage, IEC and NEMA frames, ODP and TEFC
enclosures and two- and four-pole speeds.
PARTICIPATING MANUFACTURERSAND INSTITUTIONS
At least seven different motor manufacturers have com-
mitted to provide motors, technical data and assistance
for the study. The Dowding and Mills facility in Birming-
ham, UK will facilitate all motor modifications and repairs
that are part of the study. The University of Nottingham
will perform the basic load testing on their dynamom-
eters in Nottingham. There may be additional tests
performed at Dowding and Mills.
ROUND ROBIN TESTING AND TEST PROTOCOLOne motor will be selected for round robin testing to en-
sure the accuracy of the Nottingham University facility.
These tests will be conducted at the U.S. Electrical Mo-
tors Motor Technology Center in St. Louis, Mo. and the
Invensys Brook Crompton UK plant. Both IEEE and IEC
methods of efficiency testing will be conducted. All test-
ing will include (at no load and full load) a loss segregation
method that allows for detailed analysis.
OTHER DELIVERABLES
It is expected that due to the large size of the sample
and the data collected additional deliverable might bedeveloped as part of a supplementary document. It may
be possible to update an EASA tutorial on other aspects
of motor repair that affect overall motor performance and
efficiency. Winding configuration, span, slot fill, flux den-
sity and mechanical factors will be considered.
SCHEDULE
The motors are all now at the University of Nottingham
FIGURE 1: REPAIR OR REPLACE OPTIONS
Failed motor
Options
Repair Replace
EPACTLevel Efficient
PremiumEfficient
Customized motor
Redesign/Upgrade• Optimize horsepower
to load
• Optimize voltage• Change speed• Inverter-duty winding• Increase insulation
class
Modify• Improve enclosure• Add seals• Make bearing
modifications
Restore• Repair to original
condition
![Page 4: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/4.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 4/16
3ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
FIGURE 2: REPAIR OR REPLACE DECISION PROCESS
Failed motor
• Additional considerations include increased reliability, life expectancy and benefits of additional features, upgrades
or modifications.
What is the condition of the
stator core?
Is the motor suitable for theapplication? Investigate replacement with suitable motor (size/enclosure).
Is return on investment of EPACT
motor acceptable?
Is it an EPACT motor?
Has catastrophic failure occurred,
or is there evidence of prior
catastrophic failure?
Is the rotor damaged, or is there
severe damage to other
mechanical parts?
Is the cost of repair greater than
the cost to replace the motor?
Is replacement motor available?
Are replacement funds available?
Is lead time of replacement motor
acceptable?
Significant damage or high losses
Yes
Yes
No
Yes
No
No
No
OK
Yes
Yes
Yes
Yes
Yes No
No
No
No
Repair motor Replace motor
Yes
No
Special cases(e.g., very expensive
motors)
and testing is under way. lt is expected that this evalua-
tion will be complete by the end of 2001. The co-chairmen
are David Walters and Austin Bonnett. The technical
group will review progress monthly and have already held
one meeting in Birmingham.
REPAIR-REPLACE DECISION MODEL
In the past, the decision whether to repair or replace an
electric motor has been one of economics. Replacement
of an older electric motor with a more efficient model
often makes sense for a motor operating continuously.
However, in most cases the decision is more complex
(Figures 1 and 2). A motor operating infrequently, a mo-
tor with special mounting or design features, an EPACT
motor or a motor larger than those covered by EPACT
are all examples where the repair option may be the bet-
ter choice.
When comparing the cost to replace or repair an electric
motor, the equation should include not only operating
cost and payback period, but also downtime and associ-
ated factors such as capital depreciation, lost
opportunities and customer good will. A replacement
EPACT motor that fails within a year or two may have a
significantly higher cost than a repair that optimizes the
motor for its unique application.
![Page 5: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/5.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 5/16
4ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
Annual energy savings of several hundred dollars are
quickly wiped out by unscheduled downtime when a
motor fails unexpectedly.
Much of today’s literature emphasizes efficiency and the
cost of energy as stand-alone factors in the repair-re-
place decision matrix. Frequently, the cost of the motor –
or its repair – is a small fraction of the total cost of down-time when lost production is factored in.
Considerations (other than efficiency and simple pay-
back) include reliability, performance and anticipated
motor life as well as availability of a replacement. Of these,
the most critical may be reliability. A motor customized
to its application will offer the greatest chance of long
life. (See Appendix C for a list of repair options.) “Zero
downtime” is a noble goal, one that requires commitment
and planning.
NEMA MG 1-1998 defines Unusual Service Conditions(Appendix B). Most readers will recognize many of these
as the norm for real-life motor applications. By itself, this
fact may be justification for repair and customization of
a failed electric motor.
It makes economic sense to identify the weak link in any
process, and to detect imminent failure before it occurs.
When the weak link is strengthened, the entire process
becomes stronger. A motor subject to accidental wash-
down should be of a suitable enclosure, and can be
modified to further protect the motor from this hazard.
Likewise, since more than 50% of electric motor failures
start as bearing failures, bearing temperature detectors
or vibration probes are logical options in many cases, as
shown in Figure 3.
With today’s rapidly changing technology, the motormanufacturer is hard-pressed to incorporate emerging
technology within a 2- to 3-year period. One advantage
the service center has is its ability to deal with each
unique motor and apply new technology as it develops
to address specific concerns about that particular motor’s
application and environment.
This means the end user can take advantage of unique
technology that meets their unique needs.
B e a r i n g s E n v i r o n m e n t
L u b r
i c a t i o
n
D r i v e
n l o
a d
W i n d
i n g s
L i n e v o l
t a g e
Bearing 51%*
Stator winding 16%*(May have been voltage,
water, overload, etc.)
External 16%*(Environment, voltageand load — will likelyoccur again)
Shaft/coupling 2%Rotor bar 5%
Unknown 10%*(No root causefailure analysis
performed)
* For each component shown, appropriate measures
to either prevent or predict the failure could greatly
reduce three-quarters of motor failures.
FIGURE 3: FAILURES BY COMPONENTS
Reference: IEEE Petro-Chemical paper PCIC-94-01
TABLE 1: LEVELS OF REPAIR
Level 1 Basic reconditioning. Includes replacing
bearings, cleaning all parts and replacing
lubricant. Also adds seals and other acces-
sories as agreed with customer.
Level 2 Includes Level 1 with the addition of varnish
treatment of stator windings, repair of worn
bearing fits and straightening of bent shafts.
Level 3 Includes Level 1 as well as rewinding the sta-
tor (replacing windings and insulation).
Level 4 Includes rewinding of the stator plus major
lamination repair or rotor rebar. May include
replacement of the stator laminations or
restacking of laminations. Shaft replacement
would normally fall into this category. In short,
Level 4 involves major repairs that are costly
enough to justify examining the option of re-
placement.
Level 5 Motors that would normally be replaced ex-cept for special circumstances faced by the
customer (i.e., no spare or unacceptable lead
time for a replacement). Level 5 includes
misapplied motors, inadequate enclosures
and pre U-frame motors. A motor that should
be replaced, if not for the owners’ inability to
operate without it.
As these five levels imply, the damage resulting from
a motor failure varies widely as do the associated re-
pair costs. An evaluation process that fails to consider
the various levels of “repair” is too simplistic to yield
an accurate assessment.
![Page 6: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/6.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 6/16
5ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
Bearings
• Replace bearings*
• Add seals*
• Install automatic
lubrication device
• Special grease
• Change bearing type*
Windings
• Core damaged?
• Rewind?
Other options
• Upgrade enclosure
• Improve sealing of
the enclosure
• Upgrade paint for corrosion
resistance
Moisture
• Special coatings
• Shaft seals
• Seal leads
• Gaskets
• Seal brackets
• Space heaters
Corrosion
• Special paints
• Varnish treatment
• Stainless steel shaft
Inverters
• Spike-resistant wire
• Higher corona-inception voltage
• Upgrade winding bracing
Heat
• Add RTDs
• Improve fan design
• Heat exchanger
• Upgrade insulation class
Abrasion
• Special energy-absorbing coatings
• Improve wedging
• Upgrade enclosure and add filters
Severe starts
• Better shaft material
• Stronger shaft design
• Additional winding bracing
• Change starting method
Mechanical damage
to shaft and housing
• Is is repairable?
• If replacing shaft, is
there a better material?
• Is stainless steel
warranted?
• Are shaft modifications
warranted?
• Optimize voltage?
• Special coatings?
• Inverter duty?
• Optimize slot fill
• Winding RTDs?
• Repair/restack core
• Replace core
• Change starting method to
reduce in-rush current
• Add space heaters
• Precision balance rotor
• Increase air flow
Special considerations
* Adding seals or changing bearing types may affect efficiency.
Illustration courtesy of Siemens AG
FIGURE 4 : POSSIBLE MOTOR UPGRADES AND MODIFICATIONS
Whether the concern is winding temperature, vibration
or bearing temperature, specific accessories can be in-
corporated into the repair process to enhance motor
life and permit the end-user to monitor the critical fea-
ture.
Consider winding temperature alone: There are 4 dif-
ferent RTD resistances, 14 different thermocouples andnumerous thermistors and bimetallic switches in com-
mon use. Clearly, a stock motor cannot cover all these
options. These features are a special order from motor
manufacturers and usually require long lead times. The
service center is able to tailor the motor repair to match
the monitoring equipment used by the user, incorporat-
ing special features without impacting the repair
turnaround.
Vibration monitoring is available as a continuous, on-
line system. Accelerometers are but one item that can
be retrofitted to improve the user’s ability to predictequipment failure. Non-contact shaft probes, acceler-
ometers intended for continuous monitoring and periodic
data collection, accelerometers integral to a sophisti-
cated continuous monitoring system; all are available
![Page 7: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/7.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 7/16
6ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
Table 2 illustrates the effect on efficiency and winding
temperature.
Low voltages are especially common in rural areas,
where the motor may be operating at a considerable dis-
tance from the nearest substation. Irrigation pumps and
municipal pump stations are two examples.
While many manufacturers can deliver a motor to opti-
mize non-standard line voltage, typical manufacturer lead
times of five to eight weeks may be prohibitive. The ser-
vice center can accomplish the same voltage optimization
during a motor repair.
An added benefit: It is common practice for manufactur-
ers to produce motors with up to 12 leads, so that the
motor may be used on multiple voltages, often as a part-
winding start or wye-start, delta-run. This means the
electrician may deal with 9 to 12 leads in the junction
box, increasing the chances of a ground failure from
abraded leads. When an electric motor is repaired, the
service center has the option of installing only the num-
ber of leads required. With only 3 or 6 leads, there is
more room in the junction box and less chance of lead
damage or misconnection during installation.
Note: Tri-voltage motors represent a compromise be-
tween the possible applied voltages. This improves
potential availability, to the detriment of efficiency at cer-
tain applied voltages.
VIBRATION MONITORING AND IMPROVEMENT
A Blanchard grinder begins to vibrate, and pieces of valu- able precision plate are scrapped before the cause is
identified.
technology today. Once a user makes the financial com-
mitment to a particular system, it is rarely practical to
abandon it in favor of another emerging technology. That
makes the service center a partner in maintaining the
system(s) selected by each end user.
With most companies returning to their “core business,”
and outsourcing maintenance, the competent servicecenter is best qualified to assess the cause of each mo-
tor failure and develop a plan to reduce the possibility of
a repeat failure. The service center warranty ensures
the repairer has a vested interest in identifying the root
cause of the motor failure, and performing a quality re-
pair.
EXAMPLES OF UPGRADESAND MODIFICATIONS
Once a cause of failure is determined, the service cen-
ter can work with the equipment owner to identify specific
remedies to extend MTBF. The following are but a few
examples of frequent problems — and solutions — ser-
vice centers encounter.
VOLTAGE OPTIMIZATION
A municipal pump station is located at the end of the
power transmission line. Motor failures are common, and
winding temperatures are higher than identical motors
operating at the water treatment plant in town. Repeated
measurements have confirmed chronic low voltage.
When a winding failure is the result of low applied volt-
age, the replacement motor — regardless of efficiency — will be subject to the same low line voltage. The solu-
tion, then, is to redesign the motor to optimize
performance at the actual applied voltage. It is common
to apply a 230 volt motor to a 200 or 208 volt application.
Compounding the problem, the utility supplying 208 volts
is allowed to deviate and may supply even lower voltage.
FIGURE 5: ROTOR BALANCING
Rotor being dynamically balanced in a service center.
stloV 802 032
)%(ycneiciffE 6.08 4.48
)%(rotcafrewoP 0.58 7.28
)spma(tnerrucdaollluF 5.03 9.62
)spma(tnerruchsurnI 921 841
)C°(esirerutarepmeT 19 27
)%(pilS 9.5 1.4
Design B, 4-pole, tri-voltage motor (208-230/460)
TABLE 2: EFFICIENCY AND WINDINGTEMPERATURE
![Page 8: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/8.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 8/16
7ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
Vibration sensors are vital when the application is a pre-
cision grinder or similar vibration-sensitive equipment.
Installation of vibration probes can be accomplished by
the service center with minimal intrusion into the motor.
Accelerometers can be installed on the frame or in the
junction box, while non-contact shaft probes may be pre-
ferred for sleeve bearing machines. A finishing grinder in
a machine shop must hold close tolerances to minimizescrap. Vibration from a defective bearing can be expen-
sive.
Another good candidate for vibration sensors is a pump
motor operating in a remote location. Continuous moni-
toring by instrument is infinitely better than a weekly visit
by a plant operator.
The service center can install the appropriate vibration
sensing accessories on eligible motors in the course of
each repair.
Manufacturers’ standard motors are balanced to NEMA
MG 1-1998, Part 7 specifications while the service cen-
ter can routinely balance to one-quarter of NEMA or
better. While precision manufacturing has a legitimate
need for this, many end-users request special balance
tolerances because they recognize that there is a reli-
ability factor associated with vibration.
BEARING TEMPERATURE PROTECTION
The cause of a plant fire is tracked back to a bearing
failure. The bearing, unmonitored, failed catastrophically.
Vibration damaged the pump seal and the pump leaked,
by which time the bearing temperature was high enough
to ignite the spewing liquid.
Bearing temperature protective devices (Figure 6) can
be installed during routine repairs to provide early warn-
ing of increased temperature. Excessive lubrication
intervals, high ambient temperature, imminent bearing
failure and other general machinery faults may cause
an increase in bearing temperature before damage oc-
curs. A bearing RTD is not intended to just protect the
bearing, but rather to protect the machinery by alerting
personnel when an equipment fault results in an increase
in bearing temperature. Depending on the critical nature
of the machine, feedback can take the form of a light in
the control room, or automatic shutdown of the equip-
ment.
The service center can install the appropriate tempera-
ture detectors to interface with instrumentation already
in use at the plant.
The cost to fit an electric motor with bearing thermals
may be only a few hundred dollars. That cost should be
weighed against the possible consequences of failure,
not against the cost of the motor.
CORROSION RESISTANCE
A chemical plant removed a 600 hp motor for routine
repairs. The corrosive environment had rusted through
the motor frame in numerous places, even the mounting
Weatherproof terminal head
BearingSpring-loaded, fluid-seal holder
Probe element
Bracket outer wall
Customer's
conduit
entrance
FIGURE 6: BEARING TEMPERATUREDETECTORS
Courtesy of Minco
FIGURE 7: TYPICAL MOTOR ENCLOSUREUPGRADES
Courtesy of Siemens AG
![Page 9: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/9.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 9/16
8ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
A B C
FIGURE 8: STRESS RAISERS
The lines indicate the path of stresses in the shaft. Where stresses converge, the chance of failure is much higher. The sharp
inside corner of shaft C is 40% weaker than it would be with an appropriate radius.
feet. Although running when removed from service, the
motor was beyond repair and had to be replaced.
When a motor (new or rebuilt) is placed into a known
corrosive atmosphere, the service center can take pre-
cautions to greatly improve motor life. At the simplest,corrosion-resistant paint can be used to protect the frame.
In extreme cases, the shaft can be chrome plated, or
replaced with a stainless steel shaft to better resist cor-
rosive materials. When caustic solutions are evident,
aluminum parts may be quickly eroded. Preventive mea-
sures may be as simple as dipping the rotor with varnish
to protect it. The rotor might even be rebarred using
bronze alloy of similar resistivity to avoid changing the
torque characteristics (rotor cage resistance should be
maintained to avoid changing motor performance). The
rotor should also be balanced after work is done to the
rotor. A precision balance requires only slightly more time
than a “standard” balance.
The exploded view of an open motor (Figure 7) illus-
trates the ease with which various degrees of weather
protection can be accomplished by the addition of cov-
ers, filters or guards. While an open motor is ill-suited to
outdoor operation, the upgraded WPII enclosure was de-
signed for outdoor service.
HIGH-TORQUE APPLICATIONS
An electric motor driving a hammer mill application fre-
quently experiences a broken shaft.
There are several ways to approach this problem de-
pending on the application. One would be to replace the
shaft using material with higher tensile strength than the
original shafting. The corners should all be radiused to
minimize potential stress raisers (Figures 8 and 9). The
keyway can be machined in a manner to reduce the stress
raisers at the end of the keyway (a sled-type keyway as
opposed to a milled keyway.) In extreme cases, the key-
way can be milled with a radius bottom and fitted with a
custom key. It is not necessary to modify the keyway in
the coupling.
Most service centers can machine custom shafts and
keyways to address concerns about fatigue-related fail-ures.
WASH DOWN AND FLOODING
When a power outage occurs, the sump pumps stop and
the pit floods. Electric motors must be removed, cleaned
and dried before production can be restored.
Accidental wash down and flooding cause many electric
motor failures. To increase reliability, special seals are
installed on the shaft openings to exclude water from
the bearings (Figure 10). Special water-resistant grease
can be used to pack the bearings, to further resist wash-ing of lubricants. Sealed bearings may be preferred when
the installation precludes regular maintenance.
The service center can seal T-leads using special pot-
ting compounds to prevent water from entering through
the lead opening. End brackets can be sealed with sili-
cone during the assembly process. These are
inexpensive steps, but are very effective for a motor sub-
ject to flooding or inadvertent wash down. Examples of
VENT FAN
BEARING
ROTOR CORE
BEARING
COUPLING/PULLEY
A B C D E F G H I J
FIGURE 9: STRESS RAISERS
All of the highlighted areas create stress raisers. Points F,H, I and J are usually the most vulnerable because of shaft
load at these points. It is hard for a shaft to fracture atpoints A, B, C, D or E.
![Page 10: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/10.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 10/16
9ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
candidates for this sort of modification include motors
operating below grade in pump rooms, as well as cool-
ing tower motors.
PROTECTION FROM ABRASIVE DUST
An electric motor operates downwind of a rock quarry
and abrasive dust sandblasts the windings.
Unprotected windings do not last very long in this typeof environment. The service center can topcoat the wind-
ings with a special material that absorbs impact energy,
thus protecting the windings. Filters can be added to
exclude the dust from the motor enclosure, or additional
covers can be installed to upgrade the enclosure.
Motors operating in rock quarries, cement mills or power
plants benefit from this treatment. Motors operating near
agricultural fields may also benefit. These treatments can
also be applied to new motors before they are placed
into service.
RECONNECTION
To reduce starting torque, a wye-start/delta-run connec-
tion can be used. In some cases a motor can be
reconnected, while in other cases a rewind is required.
Other starting options include a VFD or a solid-state soft-
starter.
There will always be applications where reduced start-
ing current will be required. In most cases a Design A
motor will still be justified, when coupled with an appro-priate starter sized for the current. Typical paybacks when
comparing energy savings against capital investment
range between 1 and 3 years, based on the cost of en-
ergy and hours of running time. Wye-delta starting
reduces inrush current to 37% and provides one-third
the torque. Part-winding start methods reduce inrush cur-
rent to one-half to two-thirds while supplying one-half
the starting torque.
The service center can often reconnect an existing wind-
ing to reduce starting current and torque. (See Figure 11.)
ENERGY EFFICIENCY IMPROVEMENT
There are occasions when rewinding a motor where the
opportunity may exist to enhance the motor performance
and reliability by modifying the winding configuration and
copper content. For many designs, the copper loss (I2R)
is the largest loss component (Figure 12). In some cases,
this loss can be reduced by converting from a concen-
tric, machine-wound configuration to a traditional,
hand-inserted lap winding. In many cases, the copper
FIGURE 10: NON-CONTACT BEARING ISOLATOR
The standard-design non-contact bearing isolator consists
of two parts: The stator, which is press-fitted into a bearinghousing and is designed to retain lubricant in the housing,
and the rotor, which in combination with the stator, isdesigned to keep contamination out of the bearing housing.
Courtesy of Inpro/Seals Company
FIGURE 11: ALTERNATIVE METHODSOF CONNECTION
wye start - delta run
double delta
part winding
![Page 11: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/11.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 11/16
10ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
content (slot fill) can also be increased. Figure 13 shows
the contrast between a relatively low slot fill (40 to 50%
where the wire is PD2 / 4) and one of a much higher per-
cent slot fill (60 to 64%).
This modification will improve heat transfer, reduce the
copper loss and winding temperature and improve mo-
tor efficiency. There will be less coil movement, andincreased resistance to moisture, due to better varnish
retention. Even though these improvements are difficult
for the service shop to quantify, they are none the less
real and will usually improve motor performance and re-
liability. With this modification, the motor’s service factor
will be improved and it will be able to withstand wider
variations in voltage, ambient and starting conditions.
Table 4 shows the possible efficiency improvements that
can be made for a generation of T frame motors pro-
duced during the 1970s and ’80s. Not all motors offer
this opportunity, but for those that do this option should
be considered as a possible product improvement.
CONCLUSION
By incorporating effective technology as it becomes avail-
able, it is possible to reduce downtime, improve
productivity and operate more efficiently. Reduced costs
make an organization more profitable. Savings can be
redirected to improve other “weak links.” The savvy main-
tenance professional is always looking for ways to
improve processes, and the competent service center is
able to assist in this task.
When evaluating the operating cost of an electric motor,
the cost of energy is only one variable (and often not thebiggest one) in the equation. The key to maximizing pro-
ductivity is to eliminate downtime. While zero downtime
is not always possible, any significant reduction in down-
time improves profitability. When downtime is measured
in thousands of dollars per hour, the payback reaped
from extending motor life can be enormous.
The economics of the repair or replace decision process
are complex. All variables must be considered in order
to select the best option.
TCAPE-erplanigirO 52 enihcaM 0.34 5.88 7.88
TCAPE-erpdnuoweR 52 paL 0.26 2.09 8.09
ecnereferTCAPE 52 7.19
TCAPE-erplanigirO 05 enihcaM 0.64 7.19 6.19
TCAPE-erpdnuoweR 05 paL 0.06 4.29 6.29
ecnereferTCAPE 05 0.39
TABLE 4: ENERGY EFFICIENCY IMPROVEMENT
Typical 4-pole, open dripproof, general purpose, T-frame motors of pre-
energy efficient design.
Horsepower
Windingtype
Spacefactor(%)*
Namep
lateNNE(%)
Full-loa
defficiency(%)
*Percent space factor =
Total number of wires per slotD 2
4 of wire
Total slot area - area of insulation
wire diameter
×
×
=
3 14
100
.
D
Stator core losses15-20%
Rotor losses15-20%
Stator winding losses35-40%
Stray load losses10-15%
Friction and windage losses5-10%
FIGURE 12: TYPICAL DISTRIBUTION OF LOSSES
The laminated core, stator windings and rotor account for
as much as 80% of the total losses for the typical electric
motor. While losses are generally associated with lost
efficiency, they represent energy converted to heat.
NEMA Standards MG 10-1994, Table 2-2 (National Elec-
trical Manufacturers Association, Rosslyn, VA, 1994).
FIGURE 13: EXAMPLES OF SLOT FILL
Low slot fill Improved slot fill
![Page 12: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/12.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 12/16
11ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
• Principles of Large AC Motors . Electrical Apparatus
Service Association, Inc., St. Louis, MO, 2000.
• Intelligent Motors Take the Lead in Predictive Main-
tenance . Matt O’Kane, U.S. Electrical Motors, St.Louis, MO. Presented at EASA Convention 2000,
Anaheim, CA, April 5, 2000.
• Ongoing Issues With AC Electric Motors . Austin
Bonnett, Education and Technology Consultant, Elec-
trical Apparatus Service Association, Inc., St. Louis,
MO, and Cynthia Nyberg, Technical Support Special-
ist, Electrical Apparatus Service Association, Inc., St.
Louis, MO. Presented to the EPRI-sponsored National
Motors & Drives Steering Committee, Montreal, Que-
bec, Canada, June 29, 2000.
• A Survey of Faults on Induction Motors in Offshore Oil Industry, Petrochemical Industry, Gas Terminals
and Oil Refineries . Olav Vaag Thorsen, Senior Mem-
ber IEEE and Magnus Dalva, Member IEEE. IEEE
Transactions on Industry Applications, Vol. 31, No. 5,
Sept./Oct. 1995.
• Root Cause Failure Analysis for Large AC Induction
Motors. Austin Bonnett, Education and Technology
Consultant, Electrical Apparatus Service Association,
Inc., St. Louis, MO. Presented at EASA Convention
1999, Toronto, Ontario, Canada.
REFERENCES
![Page 13: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/13.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 13/16
12ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
APPENDIX A • Application Checklist
Voltage
• What is the nominal voltage?
• How much voltage variation is present?
• Is there voltage drop when starting under load?
• Is there nuisance tripping?
• Are there transient peaks?Environmental factors
• What is the frequency of moisture ingression?
• What is the frequency of condensation?
• What is the ambient temperature range?
• What other contaminants are present?
Load conditions
• Are there load swings? If so, how wide?
• What is the hp required versus rated hp?
• What is the load – pump, fan, compressor, conveyor?
How is the motor mounted / coupled?
• Direct coupled • What are the thrust conditions?
• Overhung load • Describe the motor’s mounting.
Starting method
• Across-the-line • Part-winding start
• Wye start, Delta run • Soft-start
Frequency of starting
• What is the running time between starts?
• How many starts per hour / 8-hours / 24-hours?
• Is it a demand system?
• Is it a constant or variable load?
• Describe the cycling.• Are there load-shedding opportunities?
Describe unusual service conditions
• See Appendix B, NEMA MG 1-1998, 14.3
Describe the application
• How critical is the operation?
• Is it a dedicated or redundant system?
• What is the availability of spares or backups?
• What are the consequences of shutdown?
History of failures or repairs
• Has the motor been rewound? If so, how many
times?
• What is the mean time between failures?
Root cause failure analysis
• What is the cause of failure?
• What can be done to eliminate the cause?
• What is the best method to detect the condition?
Are there similar motors and applications?
APPENDIX B • Unusual Service Factors, NEMA MG 1-1998, 14.3
14.3 UNUSUAL SERVICE CONDITIONS
The manufacturer should be consulted if any unusual ser-
vice conditions exist which may affect the construction or
operation of the motor. Among such conditions are:
a. Exposure to:
1. Combustible, explosive, abrasive, or conducting dusts
2. Lint or very dirty operating conditions where the accu-
mulation of dirt may interfere with normal ventilation
3. Chemical fumes, flammable or explosive gases
4. Nuclear radiation
5. Steam, salt-laden air, or oil vapor
6. Damp or very dry locations, radiant heat, vermin in-
festation, or atmospheres conducive to the growth of
fungus
7. Abnormal shock, vibration, or mechanical loading from
external sources
8. Abnormal axial or side thrust imposed on the motorshaft
b. Operation where:
1. There is excessive departure from rated voltage or
frequency, or both (see 12.45 for alternating-current
motors and 12.68 for direct-current motors)
2. The deviation factor of the alternating-current supply
voltage exceeds 10 percent
3. The alternating-current supply voltage is unbalanced
by more than 1 percent (see 12.46 and 14.36)
4. The rectifier output supplying a direct-current motor is
unbalanced so that the difference between the highest
and lowest peak amplitudes of the current pulses over
one cycle exceed
10 percent of the highest pulse amplitude at rated arma-
ture current
5. Low noise levels are required
6. The power system is not grounded (see 14.31)
c. Operation at speeds above the highest rated speed
d. Operation in a poorly ventilated room, in a pit, or in an
inclined position
e. Operation where subjected to:
1. Torsional impact loads
2. Repetitive abnormal overloads
3. Reversing or electric braking
4. Frequent starting (see 12.55)
5. Out-of-phase bus transfer (see 14.45)6. Frequent short circuits
f. Operation of machine at standstill with any winding con-
tinuously energized or of short-time-rated machine with any
winding continuously energized
g. Operation of direct-current machine where the average
armature current is less than 50 percent of the rated full-
load amperes over a 24-hour period, or continuous
operation at armature current less than 50 percent of rated
current for more than 4 hours
![Page 14: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/14.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 14/16
13ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
At the time of the motor repair, in addition to the task of
restoring the motor to its original condition, it is possible to
make modifications and upgrades. During the repair it may
become evident that the motor will fail again if returned to its
existing environment without modification. It may also be ex-
pedient to implement certian “upgrades” to enhance motor
performance, reliability and life.
The following is a list of possible options that may be con-
sidered by the repair facility.
Bearings
• Enclosure — sealed, shielded or open
• Roller or ball (for direct couple or radial load)
External seals
• Non-contact bearing isolator
• Lip seal
Lubrication
• Synthetic grease• Automatic grease applicators
• Oil-mist systems
• Forced-lube oil systems
• Mineral oil for food service or potable water applica-
tions
Severe starting conditions
• Increase rigidity of winding blocking
• Redesign to wye start, delta run to reduce torque and
inrush current
• Increase slot fill
Environmental protection
• Abrasion resistance
Special coatings
Full-length slot wedges for form coil machines
• Corrosion resistance
Special epoxy paints
Stainless steel shafting
Lead potting compound
Filters
Screens, baffles or covers
Power considerations
• Power factor correction capacitors
• Surge protection or lightning arrestors
Increase motor cooling
• Directional fans
• Special fans to increase air flow
• Heat exchanger
• Auxiliary blower (especially for VFD-fed motors)
• Maximize slot fill
Special accessories
• Winding temperature detectors
• Bearing temperature detectors
• Vibration monitoring: accelerometers or non-contact
shaft probes
• Oil chamber heater and thermostat for cold climates
Leads
• Bring out minimum number of leads
• Seal the lead opening against moisture and chemicals
• Increase the lead size
• Other special considerations such as bus bar, special
lugs, etc.Noise reduction
• Add soundproofing material
• Add exterior shrouding
• Utilize special fan configurations
• Special balance requirements
Outlet box
• Size
• Better enclosure for weather protection
Efficiency considerations
• Voltage optimization
• Upgrade insulation class
• Concentric to lap conversion
• Optimize span
• Maximize slot fill (copper and insulation)
• Connection options (wye start, delta run; part-winding
start)
Field support
• Startup
• Predictive maintenance
Vibration monitoring
Current analysis
Thermography
Tribology
APPENDIX C • Repair Options
![Page 15: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/15.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 15/16
14ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
APPENDIX D • Motor Repair Guidelines and Resources
EASA AR100-1998 Recommended Practice - Rev. January 1998
TABLE OF CONTENTS
SECTION 1: GENERAL1. 1 P U RP OS E
1.2 S COP E
1 .3 I D E N TI F I C ATI O N
1.3.1 Serv ice Center Labeling
1 .3 .2 R ec or ds
1 .3 .3 N a me pl a t e
1 .4 C L EAN IN G
1 .5 TE R M I NA L L E AD S
1.6 TERMINAL CONNECTORS
1 .7 TE R M I NA L B OX E S
1 .8 C O OL I N G S YS TE M
1 .9 E X TE R I OR F I NI S H
1.10 PACKAGING AND TRANSPORTATION
SECTION 2: MECHANICAL REPAIR
2 .1 S H AF TS
2 .1 .1 S h a f t E xt e n si on s
2 .1.1 .1 Diameter Tolerances
2 .1.1 .2 Permissible Runout
2 .1.1 .3 Keyseat (Keyway) Width
Tolerances
2. 2 B E AR IN GS
2 .2 .1 B a l l o r R ol l er B e ar i n gs
2 .2 .2 S l ee v e B e ar i ng s
2 .2.2 .1 Sleeve Bear ing E nd-Thrust
2 .2.2 .2 Oil R ings
2 .2 .2 .3 S e a l s
2 .3 L UB R I C ATI O N
2. 3. 1 G r ea s e
2. 3. 2 O il
2 .4 F R AM E A ND B E A R I NG H O US I N G S
2 .4 .1 G e ne ra l
2 .4.2 Mounting Sur face Tolerances ,
Eccentricity and Face Runout
2 .5 L AM I NA TI O NS
2 .6 B AL AN CI N G
2. 7 S LI P R IN GS
2.8 COMMUTATORS
2 .8 .1 M a ch in in g
2 .8 .2 Un d e rc u tt i n g
2 .9 B R U SH H OL D ER S
2 .1 0 B R US H E S
2.11 BRUSH SETTING FOR DC MACHINES
2.12 AIR GAP MEASUREMENTOF DC
MACHINES
2.13 ACCESSORIESTABLE S
2 -1 S h a f t E x t e n si o n D i ame t e r To l er an c e s—
NEMA Frame Size Machines
2-2 Shaft Extension Diameter Tolerances—IEC
Frame Size Machines
2-3 Permissible Shaft Extension Runout—NEMA
Frame Size Machines
2-4 Permissible Shaft Extension Runout—IEC
Frame Size Machines
2-5 Shaft E xtension Keyseat Width Tolerances—
NEMA Frame Size Machines
2-6 Shaft Extension Keyseat (Keyway) Width
Tolerances—IEC Fra me Size Machines
2-7 Sleeve Bear ing Diametral Clearance Guide—
Horizontal Mounting
2-8 Labyr inth Seal Diametral Clearance Guide
2-9 Mounting Surface Tolerances, Eccentricity,
and Face Runout—NEMA Type C Face-
Mounting Motors and Type D Flange-Mount-
ing Motors
2-10 Mounting Surface Tolerances, Eccentricity,
and Face Runout—NEMA Type P Flange-
Mounting Motors
2-11 Mounting Rabbet (Spigot) Diameter Toler-
ances—IEC Flange-Mounted Machines
2-12 Mounting Sur face Eccentr ici ty and Face
Runout—IEC Flang e-Mounted Machines
2-13 Brush-to-Brushholder Cleara nce
SECTION 3: REWINDING
3. 1 I N SP E C TI O N
3 .1 .1 Wi n d in g s
3 .1 .2 C o re L ami na t i on s
3 .1.3 Thermal Protectors or Sensors
3 .2 R E WI N D I NG S P E C I F I C ATI O N
3 .3 S TR I P P I N G O F WI N D I NG S
3.4 INSULATION SYSTEM
3 .5 C O ND UC TO R S
3.6 STATOR, ROTOR, AND ARMATURE
COILS
3 .6.1 Random-Wound Coils
3 .6.2 Form-Wound Coils
3. 7 F I E LD CO I LS
3 .7 .1 S t a t i on ar y Co il s
3 .7 .2 R ot a t i n g C o il s
3 .8 AMORTISSEUR AND SQUIRREL CAGE
WINDINGS
Table of Contents, Page 1 EASA AR100-1998 Recommended Practice - Rev. January 1998
3.9 THERMAL PROTECTORS OR SENSORS
3.10 SHAPING AND LACING OF STATOR
WINDINGS
3.11 COIL CONNECTIONS
3.11 .1 Making Connections
3 .11 .2 Insulat ing Connections
3 .1 2 WE D G E S
3.13 BANDING OF ROTORS AND
ARMATURE S
3.14 IMPREGNATION OF WINDINGS
SECTION 4: TESTING
4.1 SAFETY CONSIDERATIONS
4.2 INSULATION CONDITION TESTS
4 .2 .1 I n s pe ct i on
4 .2.2 Insulat ion Resis tance Test
4 .2.3 Polar izat ion Index (P-I) Test
4 .2.4 Insulat ion Power Factor Tests
4 .2.5 Step Voltage Test
4 .2.6 Turn-to-Turn Test
4 .2.7 Inter laminar Insulat ion Test
4 .2.8 Bear ing Insulat ion Test
4 .3 RECOMMENDED WINDING TESTS
4.3.1 Stator and Wound-Rotor Windings
4 .3.2 Squirrel Cage Windings
4 .3 .3 Ar mat ur e W in d in g s
4 .3.4 Shunt, Ser ies , In terpole, Compen-
sating and Synchronous Rotor
Windings
4 .3.5 Interconnection of Windings
4 .4 HIGH-POTENTIAL TESTS
4 .4 .1 Wi n di n gs
4 .4.1 .1 New Windings
4.4.1.2 Reconditioned Windings
4.4.1.3 Windings Not Recondi-
tioned
4 .4.2 Accessor ies
4.4.2.1 New Accessories
4.4.2.2 Accessories of Machines
with Reconditioned
Windings
4.4.2.3 Accessories of Machines
with Windings Not
Reconditioned
4 .5 NO-LOAD TESTS
4. 5. 1 S pe ed
4. 5. 2 C u rr en t
4 .5 .3 C oo li n g S y st e m
4 .5 .4 S o un d Le v el
4 .5 .5 B e ar in g T e mper a t u r e
4 .5.6 Vibration Tests
4 .6 P E R F O RM AN C E T E S TS
4.7 INSTRUMENTCALIBRATION
TABLE S
4-1 High-Potential Test U sing AC—New
Windings
4-2 High-Potential Test Using DC—New
Windings
4-3 High-Potential Test U sing AC—New
Accessories
4-4 High-Potential Test Using DC—New
Accessories
4-5 Unfi l tered Vibration Limits—Resiliently
Mounted Machines
APPENDIX: ELECTRICAL TESTING
SAFETY CONSIDERATIONS
A.1 PERSONAL SAFETY
A. 1. 1 Tr a in in g
A. 1. 2 C lo th in g
A .1 .3 S uper v is i on
A. 1. 4 F i rs t Ai d
A. 2 TE S T A RE A
A .2 .1 E n c lo sur e
A. 2. 2 G a t es
A. 2. 3 S ig ns
A. 2. 4 L ig ht i ng
A .2 .5 S a fe t y E q u ipmen t
A .2 .6 Te s t Un it C l e a ran c e
A. 3 UN I T UN D E R TE S T
A.3 .1 Suitabi l i ty for Test
A.3 .2 Exclusive Attention
A. 3. 3 G r ou n di ng
A.3.4 B a se
A. 4 TE S T P A NE L S
A .4 .1 C o ns t r uct i on
A. 4. 2 V ol t a ge s
A .4 .3 War n i ng L ig h t s
A .4 .4 D i s co n ne ct
A. 4. 5 S a f et y S w i t ch
A. 4. 6 L ea d s
A.4 .7 High-Potential Ground Test
BIBLIOGRAPHY
STANDARDS ORGANIZATIONS &
OTHER RESOURCES
Note: Sections pertaining to the repa ir of l iquid-filled
and dry-type distribution transformers were withdrawn
from this edition of EASA Recommended Practice for the
Repair of Rotating Electr ical Apparatus .
Table of Contents, Page 2
EASA AR100-1998 Recommended Practice - Rev. January 1998
Standards Organizations & Other Resources
The following organizations produce documents
and standards, some of which are referenced in the
EASA Recommended Practi ce for th e Repair of Ro-
tat ing El ectr ical Apparatus .
ABMA—American Bearing
Manufacturers Association
1200 19th St., NW, Suite 300
Washin gton, DC 20036
(202) 429-5155
Fa x: (202) 223-4579
ANSI—American National
Standards Inst itute
11 West 42nd St., 13th Floor
New York, NY 10036
(212) 642-4900
Fa x: (212) 302-1286
IEC —Internat ional
Electrotechnical Commission *
3 rue de Varembe
CH 1211 Geneva 20, Switzerland
IEEE—Institute of Electrical and Electronics
Engineers, Inc.
345 East 47th St.
New York, NY 10017
(212) 705-7900
Fa x: (212) 752-4929
For Publications:
445 Hoes Lane
P. O. Box 1331Piscat awa y, NJ 08855-1331
(800) 678-4333
Fa x: (908) 981-9667
ISO—Internat ional Organizat ion
of Standardizat ion *
1 rue de Varembe
CH 1211 Geneva 20, Switzerland
MIL-STD—United Sta tes Government
Printing Office
710 North Capitol St.
Washin gton, DC 20420
(202) 512-1800
Fa x: (202) 512-2250
NEMA—National Electrical
Manufacturers Association
1300 N. 17th St., S uite 1847
Rossly n, VA 22209(703) 841-3200
For Publications:
(703) 841-3201
Fax: (703) 841-3300
NFPA—National Fire
Protection Association
One Bat terymarch Park
Quincy, MA 02269
(617) 770-3000
Fax: (617) 770-0700
For Publications:
P. O. Box 9146
Quincy, MA 02269
(800) 344-3555
Fax: (617) 984-7057
NIST—National Institute of
Stan dards a nd Technology
Route 270
Gaithersburg, MD 20899
(301) 975-2000
UL—Underwriters’ Laboratories, Inc.
333 Pfingsten Rd.
Northbrook, IL 60062
(847) 272-8800, Ext . 42612
Fax: (708) 272-8129
Standards Organizations
* IEC and ISO standards are available through ANSI, which
is the American representative to all international stan-
dards groups.
![Page 16: Guidelines for Repair_Replacement](https://reader030.fdocuments.us/reader030/viewer/2022021320/577cc0661a28aba7118ff75a/html5/thumbnails/16.jpg)
8/9/2019 Guidelines for Repair_Replacement
http://slidepdf.com/reader/full/guidelines-for-repairreplacement 16/16
15ELECTRICAL APPARATUS SERVICE ASSOCIATION, INC. • www.easa.com
Guidelines for Repair/Replace Decisions and Performance Optimization
A Guid e T o A C M oto r R epa ir And Rep lac eme nt
Table Of Contents
Introduction ............................................................................................................................1
Plan Ahead............................................................................................................................. 2
Why Motors Fail ..................................................................................................................... 2
Making The Decision To Repair Or Replace .............................................................................. 3
Obtaining Quality Motor Repairs .............................................................................................. 8
Specifying A Motor Rewind......................................................................................................11
Evaluating And Selecting A Motor Service Center ..................................................................... 13
Obtaining Motor Repairs Of The Highest Quality...................................................................... 15
EASA’s Quality Initiatives........................................................................................................ 16
About EASA.......................................................................................................................... 17
Appendix: Motor Repair Procedures ........................................................................................18
References............................................................................................................................. 21
Prepared by Electrical Apparatus Service Association, Inc. in cooperation with the U.S. Department of Energy’s Motor Challenge Program.
Copyright©1999 Electrical Apparatus Service Association, Inc.1331 Baur Blvd., St. Louis, MO 63132, 3 14-993-2220.
APPENDIX D • Motor Repair Guidelines and Resources (continued)
CONTENTS
P a g e
Introduction ........................................... ................................................. .... 1
Energy Losses in Induction Motors .............................................. ......... 4
The Motor Repair P rocess .......................................... ............................. 7Prelimina ry Inspection ................................................. .................... 7
Repair or Replacement of P arts . . . . . . .. . . . . . .. . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . 9
Repairs to the Rotor Assembly ............................................... .........11
Recording the Winding Deta ils ............................................. ......... 13
Stripping the Stat or Winding.. . . . . . . . . .. . . . . . .. . . . . . .. . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . 14
Specifying the Replacement Winding ............................................ 17
Cleaning and Inspecting the St r ipped S tator . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . 21
Rewindin g ............................................. ........................................... 22
Testing the Wound St ator ............................................. .................. 23
Impregnating and Cleaning the Rewound Stat or . . . . . . .. . . . . . .. . . . . . .. . . . 24
Re-assembly .................................................. ................................... 25
Testing the Assembled Motor ................................................ ......... 28
Appendix 1 ............................................. .................................................. .. 30
Winding Variations; Their Effect on Performance
Appendix 2 ............................................. .................................................. .. 34
Burn-out Ovens and Their Effect on St ator Core Losses
Appendix 3 ............................................. .................................................. .. 38
Calcula tion of Losses and Efficiency From Test Da ta
Appendix 4 ............................................. .................................................. .. 40
Glossa ry of Terms
Appendix 5 ............................................. .................................................. .. 42Check List of Best P ractices to Mainta in Energy E fficiency
AEMT
Association of Electrical and Mechanical Trades
G OOD P RACTICE G U IDE
THE REPAIR OF
INDU CTION MOTORSBest Practices
to Mainta in Energy E ff iciency
© Crown Copyright 1998
All rights reserved. No part of the publication may be produced or transmit ted in
any form or by any means, including photocopying and recording, without the
written permission of the copyright holder, application for which should be addressed
to the publishers. Such writt en permission must a lso be obtained before any part
of this publication is stored in a retrieval system of any nature.
ISB N: AEMT 0 9509409 3 3
Published by t he Association of Electrical and Mechanical Trades
177 Bagnall Road, Basford, Nottingham, NG6 8SJ
Tel. 0115 978 0086 Fa x. 0115 942 4488
Reprinted with permission (1999) by
Electrical Apparatus Service Association, Inc.
1331 Baur B lvd., St. Louis, MO 63132 U.S.A.
314-993-2220 • Fax: 314-993-1269 • ww w.easa .com