Guide to Equipment Certification Requirements for ... · PDF fileGuide to Equipment...

1
Guide to Equipment Certification Requirements for Hazardous Locations Quality Assurance Quality Assurance is concerned with the continued monitoring of systems and processes in relation to manufacturers of Ex products, and is concerned mainly with post-compliance activities. CSA Group offers the full range of QA services including ATEX & IECEx Product & Production Quality Assurance, Certification of Service Facilities involved in repair and overhaul of Ex Equipment and technical auditing services. The routes to market for ATEX and IECEx: • ATEX QAN (Quality Assurance Notification): Quality system certification for the manufacture of category 1 and category 2 electrical equipment (refer IEC/ISO 80079-34 and ATEX Directive Annexes IV / VII). • IECEx QAR (Quality Assessment Report): Required together with the ExTR (test report) to enable issue of an IECEx Certificate of Conformity (refer IEC/ISO 80079-34 and IECEx Scheme Rules). • ATEX Conformity-to-Type Notification: Certification for the manufacture of category 2 electrical equipment (refer ATEX Directive Annexes VI). • ATEX Product Verification: Certification for the manufacture of category 1 equipment - 100% verification by the Notified Body (refer ATEX Directive Annexes V). • ATEX or IECEx Unit Verification: Certification covering design and manufacture of equipment - 100% verification by the Notified Body (refer ATEX Directive Annexes IX and IECEx Scheme Rules). ATEX & IEC Training & Competence CSA Group has been at the forefront of hazardous area training for over 25 years, utilising the skills and experience of our highly specialised engineers and lecturers to ‘transfer knowledge’. This detailed knowledge and vast experience allows us to offer a comprehensive range of training courses and competence schemes that can be delivered as part of our ‘open’ training programme or tailored to your needs and delivered on-site at your premises. • Hazardous Area Training (ATEX, DSEAR & IEC) • Functional Safety Training • Environmental & MCERTS Training • Competence Certification (CoPC) - IECEx Certification of Personnel Competence Scheme - MCERTS Personnel Competence Scheme For further details please contact CSA Group on: + 44 1244 670 900 or Email: [email protected] Functional Safety CSA Group is a leading provider of functional safety certification. IEC 61508 is the international standard for electrical, electronic and programmable electronic safety (E/E/PE) related systems. It sets out the requirements for ensuring that systems are designed, implemented, operated and maintained to provide the required safety integrity level (SIL). Four SILs are defined according to the risks involved in the system application, with SIL4 being used to protect against the highest risks. The standard specifies a process that can be followed by all links in the supply chain so that information about the system can be communicated using common terminology and system parameters. The standard consists of the following parts: IEC 61508-1 General requirements. IEC 61508-2 Requirements for E/E/PE safety-related systems. IEC 61508-3 Software requirements. IEC 61508-4 Definitions and abbreviations. IEC 61508-5 Examples and methods for the determination of safety integrity levels. IEC 61508-6 Guidelines on the application of IEC 61508-2 and IEC 61508-3. IEC 61508-7 Overview of techniques and measures. Sector specific standards related to IEC 61508 include: IEC 61511 Process industries. IEC 61513 Nuclear power plants. IEC 62061 Machinery sector and ISO 13849. IEC 61800-5-2 Power drive systems. EN 50272 and EN 50402 Functional safety requirements for portable and fixed gas detection systems. EN 50495 safety devices requirements for safe operation of equipments with respect to explosion risks. www.csagroup.org www.siracertification.com CSA Group Hazardous Location Certification Offices Chester, UK: + 44 1244 670 900 Cleveland, OH, USA: + 1 877 235 9791 Dallas, TX, USA: + 1 817 652 9600 Edmonton, AB, CDN: + 1 780 450 2111 Toronto, ON, CDN: + 1 416 747 4000 ATEX & IECEx Certificate Number 700º 600º 500º 400º 300º 200º 100º T6 85º T5 100º T4 135º T3 200º T2 300º T1 450º Protection Concepts Type of Protection Code Country Class Division / Zone Standard Basic Concept of Protection Electrical Equipment for Flammable Gas, Vapors and Mists - Class I General Requirements AEx Ex US CA US CA Class I Class I Class I Class I Division 1 & 2 Division 1 & 2 Zone 1 & 2 Zone 1 & 2 FM 3600 - ISA 60079-0 CSA 60079-0 Increased Safety AEx e Ex e US CA Class I Class I Zone 1 Zone 1 ISA 60079-7 CSA C22.2 No. 60079-7 No arcs, sparks or hot surfaces Non-Incendive (NI) (NI) US CA Class I Class I Division 2 Division 2 ISA 12.12.01 / FM 3611 C22.2 No. 213 Non-Sparking AEx nA Ex nA US CA Class I Class I Zone 2 Zone 2 ISA 60079-15 CSA C22.2 No. 60079-15 Explosion Proof (XP) (XP) US CA Class I Class I Division 1 Division 1 UL 1203 / FM 3615 C22.2 No. 30 Contain the explosion and extinguish the flame Flameproof AEx d AEx d Ex d US US CA Class I Class I Class I Zone 1 Zone 1 Zone 1 ISA 60079-1 UL 1203 / FM 3615 CSA 60079-1 Powder Filled AEx q Ex q US CA Class I Class I Zone 1 Zone 1 ISA 60079-5 CSA C22.2 No. 60079-5 Enclosed Break AEx nC Ex nC US CA Class I Class I Zone 2 Zone 2 ISA 60079-15 CSA C22.2 No. 60079-15 Intrinsic Safety (IS) (IS) AEx ia AEx ib EX ia Ex ib US CA US US CA CA Class I Class I Class I Class I Class I Class I Division 1 Division 1 Zone 0 Zone 1 Zone 0 Zone 1 UL 913 / FM 3610 C22.2 No. 157 ISA 60079-11 / FM 3610 ISA 60079-11 / FM 3610 CSA C22.2 No. 60079-11 CSA C22.2 No. 60079-11 Limit energy of sparks and surface temperature Limited Energy AEx nC Ex nL US CA Class I Class I Zone 2 Zone 2 ISA 60079-15 CSA C22.2 No. 60079-15 Pressurised Type X Type X Type Y Type Y Type Z Type Z AEx px Ex px AEx py Ex py AEx pz Ex pz US CA US CA US CA US CA US CA US CA Class I Class I Class I Class I Class I Class I Class I Class I Class I Class I Class I Class I Division 1 Division 1 Division 1 Division 1 Division 2 Division 2 Zone 1 Zone 1 Zone 1 Zone 1 Zone 2 Zone 2 NFPA 496 (FM 3620) NFPA 496 NFPA 496 (FM 3620) NFPA 496 NFPA 496 (FM 3620) NFPA 496 ISA 60079-2 CSA C22.2 No. 60079-2 ISA 60079-2 CSA C22.2 No. 60079-2 ISA 60079-2 CSA C22.2 No. 60079-2 Keep flammable gas out Restricted Breathing AEx nR Ex nR US CA Class I Class I Zone 2 Zone 2 ISA 60079-15 CSA C22.2 No. 60079-15 Encapsulated AEx ma AEx m Ex m AEx mb US US CA US Class I Class I Class I Class I Zone 0 Zone 1 Zone 1 Zone 1 ISA 60079-18 ISA 60079-18 CSA C22.2 No. 60079-18 ISA 60079-18 Oil Immersion AEx o Ex o US CA Class I Class I Zone 1 Zone 1 ISA 60079-6 CSA C22.2 No. 60079-6 Electrical Equipment for Combustible Dust and Fibres - Class II / Class III General Requirements Ex US CA US CA US Class II Class II Class III Class III - Division 1 & 2 Division 1 & 2 Division 1 & 2 Division 1 & 2 Zone 20, 21, 22 FM 3600 CSA C22.2 No.0 FM 3600 CSA C22.2 No.0 ISA 60079-0 Dust Ignition Proof - US CA Class II Class II Division 1 Division 1 UL 1203 / FM 3616 CSA C22.2 No. 25 Keep combustible dust out Dust Protected - US CA Class II Class II Division 2 Division 2 ISA 12.12.01 / FM 3611 CSA C22.2 No. 25 Protection by Enclosure AEx ta AEx tb AEx tc Ex ta Ex tb Ex tc US US US CA CA CA Class II Class II Class II Class II Class II Class II Zone 20 Zone 21 Zone 22 Zone 20 Zone 21 Zone 22 ISA 60079-31 ISA 60079-31 ISA 60079-31 CSA C22.2 No. 60079-31 CSA C22.2 No. 60079-31 CSA C22.2 No. 60079-31 Fiber & Flying Protection - - US CA Class III Class III Division 1 & 2 Division 1 & 2 UL 1203 / ISA 12.12.01 CSA C22.2 No. 25 Encapsulation AEx maD AEx mbD US US - - Zone 20 Zone 21 ISA 60079-18 ISA 60079-18 Pressurisation (PX) (PX) (PY) (PY) (PZ) (PZ) AEx pD US CA US CA US CA US Class II Class II Class II Class II Class II Class II - Division 1 Division 1 Division 1 Division 1 Division 2 Division 2 Zone 21 NFPA 496 (FM 3620) NFPA 496 NFPA 496 (FM 3620) NFPA 496 NFPA 496 (FM 3620) NFPA 496 ISA 61241-2 Intrinsic Safety (IS) (IS) AEx iaD AEx ibD (IS) (IS) US CA US US US CA Class II Class II - - Class III Class III Division 1 Division 1 Zone 20 Zone 21 Division 1 Division 1 UL 913 / FM 3610 CSA C22.2 No. 157 ISA 60079-11 ISA 60079-11 UL 913 / FM 3610 CSA C22.2 No. 157 Limit energy of sparks and surface temperature Note: For associated intrinsically safe apparatus suitable for installation in a hazardous location, the symbol for the type of protection “ia” or “ib” are enclosed within square brackets on the marking, e.g. AEx d [ia] IIC T4. Note: For intrinsically safe apparatus not suitable for installation in a hazardous location, both the symbol “Ex” or “AEx” and the symbol for the type of protection “ia” or “ib” are enclosed within the same square brackets on the marking, e.g. [AEx ia] IIC; in this case, a temperature class is not included. Protection Concepts [ATEX and IECEx] Type of Protection Symbol Typical IEC EPL Typical Zone(s) IEC Standard Basic Concept of Protection Electrical equipment for Gases, Vapours and Mists (G) General Requirements - - - IEC 60079-0 - Optical Radiation Op pr Op sh Op is Gb Ga Ga 1,2 0,1,2 0,1,2 IEC 60079-28 Protection against ignitions from optical radiation Increased Safety Type ‘n’ (non-sparking) e nA Gb Gc 1,2 2 IEC 60079-7 IEC 60079-15 No arcs, sparks or hot surfaces. Enclosure IP54 or better Flameproof d Gb 1,2 IEC 60079-1 Contain the explosion, quench the flame Type ‘n’ (enclosed break) nC Gc 2 IEC 60079-15 Quartz / Sand Filled q Gb 1,2 IEC 60079-5 Quench the flame Intrinsic Safety ia ib ic Ga Gb Gc 0,1,2 1,2 2 IEC 60079-11 Limit the energy of sparks and surface temperatures Pressurised px py pz Gb Gb Gc 1,2 1,2 2 IEC 60079-2 Keep the flammable gas out Type ‘n’ (sealing & hermetic sealing) Type ‘n’ (restricted breathing) nC nR Gc Gc 2 2 IEC 60079-15 Encapsulation ma mb mc Ga Gb Gc 0,1,2 1,2 2 IEC 60079-18 Oil Immersion o Gb 1,2 IEC 60079-6 Electrical equipment for Combustible Dusts (D) General Requirements - - - IEC 60079-0 - Enclosure ta tb tc Da Db Dc 20 21 22 IEC 60079-31 Standard protection for dusts, rugged tight enclosure Intrinsic Safety ia ib ic Da Db Dc 20 21 22 IEC 60079-11 Limit the energy of sparks and surface temperatures Encapsulation ma mb mc Da Db Dc 20 21 22 IEC 60079-18 Protection by encapsulation of incendive parts Pressurised pD Db 21,22 IEC 61241-4 Protection by pressurisation of enclosure Dc 22 Non-Electrical equipment General Requirements - - - EN 13463-1 Low potential energy Flow Restricted Enclosure Flameproof Enclosure fr d - - 2,22 1,2,21,22 EN 13463-2 EN 13463-3 Relies on tight seals, closely matched joints and tough enclosures to restrict the breathing of the enclosure Constructional Safety c - All, See EPL EN 13463-5 Ignition hazards eliminated by good engineering methods Control of Ignition Sources b - All, See EPL EN 13463-6 Control equipment fitted to detect malfunctions Pressurisation p - 1,2, 21,22 EN 60079-2 EN 61241-4 Enclosure is purged and pressurised to prevent ignition sources from arising Liquid Immersion k - All, See EPL EN 13463-8 Enclosure uses liquid to prevent contact with explosive atmosphere Apparatus Groups [ATEX and IECEx] Group Environment Location Typical Substance I Gases, Vapours Coal Mining Methane (Fire damp) IIA Surface and other locations Acetic acid, Acetone, Ammonia, Butane, Cyclohexane, Gasoline (petrol), Kerosene, Methane (natural gas) (non-mining), Metha- nol (methyl alcohol), Propane, Propan-2-ol (iso-propyl alcohol), Toluene, Xylene IIB Di-ethyl ether, Ethylene, Methyl ethyl ketone (MEK), Propan-1-ol (n-propyl alcohol), Ethanol (ethyl alcohol) IIC Acetylene, Hydrogen, Carbon disulphide IIIA Combustible Dusts Surface and other locations Combustible flyings IIIB Non-conductive IIIC Conductive Classification of Divisions and Zones Type of Area NEC and CEC* ATEX and IEC Definitions Continous hazard Division 1 Zone 0 / Zone 20 Cat 1 A place in which an explosive atmosphere is continuously present Intermittent hazard Division 1 Zone 1 / Zone 21 Cat 2 A place in which an explosive atmosphere is likely to occur in normal operation Hazard under abnormal conditions Division 2 Zone 2 / Zone 22 Cat 3 A place in which an explosive atmosphere is not likely to occur in normal operation, but may occur for short periods * On occasion the ATEX and IEC Zones may be used in the corresponding NEC and CEC system Enclosure Type Ratings (NEMA / CSA / UL) Type Area Brief Definition 1 Indoor General purpose 2 Indoor Protection against angled dripping water 3, 3R, 3S Indoor / Outdoor Protection against rain, snow 4, 4X Indoor / Outdoor Protection against rain, snow, hose directed water 5 Indoor Protection against angled dripping water, dust, fibers, flyings 6 Indoor / Outdoor Protection against temporary submersion 6P Indoor / Outdoor Protection against prolonged submersion 12, 12K Indoor Protection against circulating dust, fibers, flyings 13 Indoor Protection against circulating dust, fibers, flyings, seepage Dusts Typical Ignition Temperatures (°C) Dusts Cloud Layer Aluminium Coal dust (lignite) Flour Grain dust Methyl cellulose Phenolic resin Polythene PVC Soot Starch Sugar 590 °C 380 °C 490 °C 510 °C 420 °C 530 °C 420 °C 700 °C 810 °C 460 °C 490 °C >450 °C 225 °C 340 °C 300 °C 320 °C >450 °C (melts) °C >450 °C 570 °C 435 °C 460 °C Apparatus Groups (US / CAN) Substance Hazard Class NEC 500 NEC 505 Acetylene Class I Flammable Gases Group A IIC Hydrogen Group B IIC Ethylene Group C IIB Propane Group D IIA Methane (mining) Group D - Combustible Metal Dusts Class II Combustible Dusts Group E - Combustible Carbonaceous Dusts Group F - Combustible Dusts not in Group E or F (Flour, Grain, Wood, Plastics, Chemicals) Group G - Combustible Fibers and Flyings Class III Fibers and Flyings - - Equipment Groups [ATEX and IECEx] Equipment Group Equipment Category Equipment Protection Level Atmosphere Protection Level Required Protection Performance & Operation I (Mines with firedamp) M1 Ma Methane & Dust Very High Two Faults, Remain energised and functioning I (Mines with firedamp) M2 Mb Methane & Dust High Severe normal operation, De-energise in explosive atmosphere II (all other areas) 1 Ga / Da Gas, Vapour, Mist, Dust Very High Two Faults II (all other areas) 2 Gb / Db Gas, Vapour, Mist, Dust High One Fault II (all other areas) 3 Gc / Dc Gas, Vapour, Mist, Dust Low Normal operation Typical ATEX & IECEx Marking [*ATEX only] Typical North American Marking (CSA) Reference to ATEX 95 Directive Serial Number Year of Certification Name of Notified Body performing EC-type examination SIRA 13 ATEX 1234 Gas Group Dust Group Temperature Class Area Classification Area Classification Hazard Class Hazard Class Class I, Division 1, Groups A,B,C,D T4 Class II, Division 1, Groups E,F,G II 2 G *Specific Marking for Explosion Protection *Equipment Group *Equipment Category *Environment *Complies with European Directives *Notified Body Number Gas Group Protection Concept Code Approved to US Standards Temperature Class Area Classification Hazard Class Class I, Zone 0, AEx ia IIC T4 Equipment Protection Level (EPL) Temperature Class (T1-T6) Gas Group Type of Protection Explosion Protection Ex d IIC T4 Gb Equipment Protection Level Temperature Class (°C) Dust Type Type of Protection Explosion Protection Ex tb IIIC T135°C Db Serial Number Year of Certification Name of Body Performing IECEx Certification Reference to IECEx Scheme IECEx CSA 13.1234 Temperature Classification Classification of maximum surface temperatures for Group II Electronic Equipment (T Class). IIA T1 Ammonia 630° IIC T1 Hydrogen 560° IIA T1 Methane 537° IIA T1 Propane 470° IIB T2 Ethylene 425° IIA T2 Butane 372° IIC T2 Acetylene 305° IIA T3 Cyclohexane 259° IIA T3 Kerosene 210° IIB T4 Di-ethyl Ether 160° IIC T6 Carbon Disulphide 95° CCSAUS ATEX & IECEx Suffixes: U – component certification X – special conditions for safe use apply Ingress Protection Codes First Number (protect from solid bodies) Second Number (protect from water) 0 No protection 0 No protection 1 Objects > 50mm 1 Vertical drip 2 Objects > 12.5mm 2 Angled drip 3 Objects > 2.5mm 3 Spraying 4 Objects > 1.0mm 4 Splashing 5 Dust-protected 5 Jetting 6 Dust-tight 6 Powerful jetting 7 Temporary immersion 8 Continuous immersion °C CSA Group has provided the technical information for this publication. CSA Group retains all intellectual property including copyright in its work. Issued October 2013

Transcript of Guide to Equipment Certification Requirements for ... · PDF fileGuide to Equipment...

Page 1: Guide to Equipment Certification Requirements for ... · PDF fileGuide to Equipment Certification Requirements for Hazardous Locations ... issue of an IECEx Certificate of Conformity

Guide to Equipment Certification Requirements for Hazardous Locations

Quality AssuranceQuality Assurance is concerned with the continued monitoring of systems and processes in relation to manufacturers of Ex products, and is concerned mainly with post-compliance activities.

CSA Group offers the full range of QA services including ATEX & IECEx Product & Production Quality Assurance, Certification of Service Facilities involved in repair and overhaul of Ex Equipment and technical auditing services.

The routes to market for ATEX and IECEx:

• ATEXQAN(QualityAssuranceNotification):Qualitysystemcertificationforthemanufactureof category1andcategory2electricalequipment(referIEC/ISO80079-34andATEXDirective AnnexesIV/VII).

• IECExQAR(QualityAssessmentReport):RequiredtogetherwiththeExTR(testreport)toenable issueofanIECExCertificateofConformity(referIEC/ISO80079-34andIECExSchemeRules).

• ATEXConformity-to-TypeNotification:Certificationforthemanufactureofcategory2 electricalequipment(referATEXDirectiveAnnexesVI).

• ATEXProductVerification:Certificationforthemanufactureofcategory1equipment -100%verificationbytheNotifiedBody(referATEXDirectiveAnnexesV).

• ATEXorIECExUnitVerification:Certificationcoveringdesignandmanufactureofequipment -100%verificationbytheNotifiedBody(referATEXDirectiveAnnexesIXandIECExSchemeRules).

ATEX & IEC Training & CompetenceCSAGrouphasbeenattheforefrontofhazardousareatrainingforover25years,utilisingtheskills and experience of our highly specialised engineers and lecturers to ‘transfer knowledge’.

This detailed knowledge and vast experience allows us to offer a comprehensive range of trainingcoursesandcompetenceschemesthatcanbedeliveredaspartofour‘open’trainingprogramme or tailored to your needs and delivered on-site at your premises.

• HazardousAreaTraining(ATEX,DSEAR&IEC)

• FunctionalSafetyTraining

• Environmental&MCERTSTraining

• CompetenceCertification(CoPC)

- IECEx Certification of Personnel Competence Scheme

- MCERTSPersonnelCompetenceScheme

ForfurtherdetailspleasecontactCSAGroupon:+441244670900orEmail:[email protected]

Functional SafetyCSAGroupisaleadingprovideroffunctionalsafetycertification.IEC61508istheinternationalstandardforelectrical,electronicandprogrammableelectronicsafety(E/E/PE)relatedsystems.It sets out the requirements for ensuring that systems are designed, implemented, operated and maintainedtoprovidetherequiredsafetyintegritylevel(SIL).FourSILsaredefinedaccordingtotherisksinvolvedinthesystemapplication,withSIL4beingusedtoprotectagainstthehighestrisks.Thestandardspecifiesaprocessthatcanbefollowedbyalllinksinthesupplychainsothatinformationaboutthesystemcanbecommunicatedusingcommonterminologyandsystemparameters.

The standard consists of the following parts:

IEC 61508-1 General requirements. IEC 61508-2RequirementsforE/E/PEsafety-relatedsystems.IEC 61508-3 Software requirements. IEC 61508-4 Definitionsandabbreviations.IEC 61508-5 Examples and methods for the determination of safety integrity levels.IEC 61508-6 GuidelinesontheapplicationofIEC61508-2andIEC61508-3.IEC 61508-7 Overviewoftechniques and measures.

Sector specific standards related to IEC 61508 include:

IEC 61511 Process industries. IEC 61513Nuclearpowerplants.IEC 62061MachinerysectorandISO13849.IEC 61800-5-2 Power drive systems. EN 50272 and EN 50402 Functional safety requirementsforportableandfixedgasdetectionsystems.EN 50495 safety devices requirements for safe operation of equipments with respect to explosion risks.

www.csagroup.orgwww.siracertification.com

CSA Group Hazardous Location Certification Offices

Chester, UK: + 44 1244 670 900 Cleveland, OH, USA: + 1 877 235 9791 Dallas, TX, USA: + 1 817 652 9600 Edmonton, AB, CDN: + 1 780 450 2111 Toronto, ON, CDN: + 1 416 747 4000

ATEX & IECEx Certificate Number

700º

600º

500º

400º

300º

200º

100ºT6 85º

T5 100º

T4 135º

T3 200º

T2 300º

T1 450º

Protection ConceptsType ofProtection

Code Country Class Division / Zone StandardBasic Conceptof Protection

Electrical Equipment for Flammable Gas, Vapors and Mists - Class I

General

Requirements

AEx

Ex

US

CA

US

CA

Class I

Class I

Class I

Class I

Division1&2

Division1&2

Zone 1 & 2

Zone 1 & 2

FM3600

-

ISA60079-0

CSA60079-0

Increased

Safety

AEx e

Ex e

US

CA

Class I

Class I

Zone 1

Zone 1

ISA60079-7

CSAC22.2No.60079-7

Noarcs,sparks

or hot surfacesNon-Incendive

(NI)

(NI)

US

CA

Class I

Class I

Division2

Division2

ISA12.12.01/FM3611

C22.2No.213

Non-SparkingAEx nA

Ex nA

US

CA

Class I

Class I

Zone 2

Zone 2

ISA60079-15

CSAC22.2No.60079-15

Explosion Proof(XP)

(XP)

US

CA

Class I

Class I

Division1

Division1

UL1203/FM3615

C22.2No.30

Contain the

explosion and

extinguish the

flame

Flameproof

AEx d

AEx d

Ex d

US

US

CA

Class I

Class I

Class I

Zone 1

Zone 1

Zone 1

ISA60079-1

UL1203/FM3615

CSA60079-1

Powder FilledAEx q

Ex q

US

CA

Class I

Class I

Zone 1

Zone 1

ISA60079-5

CSAC22.2No.60079-5

EnclosedBreakAEx nC

Ex nC

US

CA

Class I

Class I

Zone 2

Zone 2

ISA60079-15

CSAC22.2No.60079-15

Intrinsic Safety

(IS)

(IS)

AEx ia

AExib

EX ia

Exib

US

CA

US

US

CA

CA

Class I

Class I

Class I

Class I

Class I

Class I

Division1

Division1

Zone0

Zone 1

Zone0

Zone 1

UL913/FM3610

C22.2No.157

ISA60079-11/FM3610

ISA60079-11/FM3610

CSAC22.2No.60079-11

CSAC22.2No.60079-11

Limitenergy

of sparks

and surface

temperature

LimitedEnergyAEx nC

ExnL

US

CA

Class I

Class I

Zone 2

Zone 2

ISA60079-15

CSAC22.2No.60079-15

Pressurised

Type X

Type X

Type Y

Type Y

Type Z

Type Z

AEx px

Ex px

AEx py

Ex py

AExpz

Expz

US

CA

US

CA

US

CA

US

CA

US

CA

US

CA

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Class I

Division1

Division1

Division1

Division1

Division2

Division2

Zone 1

Zone 1

Zone 1

Zone 1

Zone 2

Zone 2

NFPA496(FM3620)

NFPA496

NFPA496(FM3620)

NFPA496

NFPA496(FM3620)

NFPA496

ISA60079-2

CSAC22.2No.60079-2

ISA60079-2

CSAC22.2No.60079-2

ISA60079-2

CSAC22.2No.60079-2

Keep

flammable

gas out

Restricted

Breathing

AExnR

ExnR

US

CA

Class I

Class I

Zone 2

Zone 2

ISA60079-15

CSAC22.2No.60079-15

Encapsulated

AEx ma

AEx m

Ex m

AExmb

US

US

CA

US

Class I

Class I

Class I

Class I

Zone0

Zone 1

Zone 1

Zone 1

ISA60079-18

ISA60079-18

CSAC22.2No.60079-18

ISA60079-18

OilImmersionAEx o

Ex o

US

CA

Class I

Class I

Zone 1

Zone 1

ISA60079-6

CSAC22.2No.60079-6

Electrical Equipment for Combustible Dust and Fibres - Class II / Class III

General

RequirementsEx

US

CA

US

CA

US

Class II

Class II

Class III

Class III

-

Division1&2

Division1&2

Division1&2

Division1&2

Zone20,21,22

FM3600

CSAC22.2No.0

FM3600

CSAC22.2No.0

ISA60079-0

DustIgnition

Proof-

US

CA

Class II

Class II

Division1

Division1

UL1203/FM3616

CSAC22.2No.25

Keep

combustible

dust out

DustProtected -US

CA

Class II

Class II

Division2

Division2

ISA12.12.01/FM3611

CSAC22.2No.25

Protectionby

Enclosure

AEx ta

AExtb

AEx tc

Ex ta

Extb

Ex tc

US

US

US

CA

CA

CA

Class II

Class II

Class II

Class II

Class II

Class II

Zone20

Zone 21

Zone 22

Zone20

Zone 21

Zone 22

ISA60079-31

ISA60079-31

ISA60079-31

CSAC22.2No.60079-31

CSAC22.2No.60079-31

CSAC22.2No.60079-31

Fiber&Flying

Protection

-

-

US

CA

Class III

Class III

Division1&2

Division1&2

UL1203/ISA12.12.01

CSAC22.2No.25

EncapsulationAExmaD

AExmbD

US

US

-

-

Zone20

Zone 21

ISA60079-18

ISA60079-18

Pressurisation

(PX)

(PX)

(PY)

(PY)

(PZ)

(PZ)

AExpD

US

CA

US

CA

US

CA

US

Class II

Class II

Class II

Class II

Class II

Class II

-

Division1

Division1

Division1

Division1

Division2

Division2

Zone 21

NFPA496(FM3620)

NFPA496

NFPA496(FM3620)

NFPA496

NFPA496(FM3620)

NFPA496

ISA61241-2

Intrinsic Safety

(IS)

(IS)

AExiaD

AExibD

(IS)

(IS)

US

CA

US

US

US

CA

Class II

Class II

-

-

Class III

Class III

Division1

Division1

Zone20

Zone 21

Division1

Division1

UL913/FM3610

CSAC22.2No.157

ISA60079-11

ISA60079-11

UL913/FM3610

CSAC22.2No.157

Limitenergy

of sparks

and surface

temperature

Note:Forassociatedintrinsicallysafeapparatussuitableforinstallationinahazardouslocation,thesymbolforthetype

ofprotection“ia”or“ib”areenclosedwithinsquarebracketsonthemarking,e.g.AExd[ia]IICT4.

Note:Forintrinsicallysafeapparatusnotsuitableforinstallationinahazardouslocation,boththesymbol“Ex”or“AEx”

andthesymbolforthetypeofprotection“ia”or“ib”areenclosedwithinthesamesquarebracketsonthemarking,

e.g.[AExia]IIC;inthiscase,atemperatureclassisnotincluded.

Protection Concepts [ATEX and IECEx]Type ofProtection

SymbolTypicalIEC EPL

TypicalZone(s)

IEC StandardBasic Conceptof Protection

Electrical equipment for Gases, Vapours and Mists (G)

GeneralRequirements - - - IEC60079-0 -

OpticalRadiationOpprOpshOpis

GbGaGa

1,20,1,20,1,2

IEC60079-28Protection against ignitions from optical radiation

Increased SafetyType‘n’(non-sparking)

enA

GbGc

1,22

IEC60079-7IEC60079-15

Noarcs,sparksorhotsurfaces.EnclosureIP54orbetter

Flameproof d Gb 1,2 IEC60079-1 Contain the explosion, quench the flameType‘n’(enclosedbreak) nC Gc 2 IEC60079-15

Quartz/SandFilled q Gb 1,2 IEC60079-5 Quench the flame

Intrinsic Safetyiaibic

GaGbGc

0,1,21,22

IEC60079-11Limittheenergyofsparksand surface temperatures

Pressurisedpxpypz

GbGbGc

1,21,22

IEC60079-2

Keeptheflammablegas out

Type‘n’(sealing&hermeticsealing)Type‘n’(restrictedbreathing)

nCnR

GcGc

22

IEC60079-15

Encapsulationmambmc

GaGbGc

0,1,21,22

IEC60079-18

OilImmersion o Gb 1,2 IEC60079-6

Electrical equipment for Combustible Dusts (D)

GeneralRequirements - - - IEC60079-0 -

Enclosuretatbtc

DaDbDc

202122

IEC60079-31Standard protection for dusts, rugged tight enclosure

Intrinsic Safetyiaibic

DaDbDc

202122

IEC60079-11Limittheenergyofsparksand surface temperatures

Encapsulationmambmc

DaDbDc

202122

IEC60079-18Protectionbyencapsulationof incendive parts

Pressurised pDDb 21,22

IEC61241-4Protectionbypressurisationof enclosureDc 22

Non-Electrical equipment

GeneralRequirements - - - EN13463-1 Lowpotentialenergy

FlowRestrictedEnclosureFlameproof Enclosure

frd

--

2,221,2,21,22

EN13463-2EN13463-3

Reliesontightseals,closelymatched joints and tough enclosures to restrict the breathingoftheenclosure

Constructional Safety c -All,SeeEPL

EN13463-5Ignitionhazardseliminatedbygoodengineeringmethods

Control of Ignition Sources b -All,SeeEPL

EN13463-6Control equipment fitted to detect malfunctions

Pressurisation p -1,2,21,22

EN60079-2EN61241-4

Enclosure is purged andpressurised to prevent ignition sources from arising

LiquidImmersion k -All,SeeEPL

EN13463-8Enclosure uses liquid to prevent contact with explosive atmosphere

Apparatus Groups [ATEX and IECEx]Group Environment Location Typical Substance

I

Gases, Vapours

CoalMining Methane(Firedamp)

IIA

Surface

and other

locations

Aceticacid,Acetone,Ammonia,Butane,

Cyclohexane,Gasoline(petrol),Kerosene,

Methane(naturalgas)(non-mining),Metha-

nol(methylalcohol),Propane,Propan-2-ol

(iso-propylalcohol),Toluene,Xylene

IIB

Di-ethylether,Ethylene,Methylethylketone

(MEK),Propan-1-ol(n-propylalcohol),Ethanol

(ethylalcohol)

IIC Acetylene,Hydrogen,Carbondisulphide

IIIA

CombustibleDusts

Surface

and other

locations

Combustibleflyings

IIIB Non-conductive

IIIC Conductive

Classification of Divisions and ZonesType of Area NEC and CEC* ATEX and IEC Definitions

Continous

hazardDivision1

Zone0/Zone20

Cat 1

A place in which an explosive atmosphere is

continuously present

Intermittent

hazardDivision1

Zone1/Zone21

Cat 2

A place in which an explosive atmosphere is

likely to occur in normal operation

Hazardunder

abnormalconditionsDivision2

Zone2/Zone22

Cat3

A place in which an explosive atmosphere is

notlikelytooccurinnormaloperation,but

may occur for short periods

*OnoccasiontheATEXandIECZonesmaybeusedinthecorrespondingNECandCECsystem

Enclosure Type Ratings (NEMA / CSA / UL)Type Area Brief Definition

1 Indoor General purpose

2 Indoor Protection against angled dripping water

3,3R,3S Indoor/Outdoor Protection against rain, snow

4,4X Indoor/Outdoor Protection against rain, snow, hose directed water

5 Indoor Protectionagainstangleddrippingwater,dust,fibers,flyings

6 Indoor/Outdoor Protectionagainsttemporarysubmersion

6P Indoor/Outdoor Protectionagainstprolongedsubmersion

12, 12K Indoor Protectionagainstcirculatingdust,fibers,flyings

13 Indoor Protectionagainstcirculatingdust,fibers,flyings,seepage

Dusts Typical Ignition Temperatures (°C)Dusts Cloud Layer

Aluminium

Coaldust(lignite)

Flour

Grain dust

Methylcellulose

Phenolic resin

Polythene

PVC

Soot

Starch

Sugar

590°C

380°C

490°C

510°C

420°C

530°C

420°C

700°C

810°C

460°C

490°C

>450°C

225°C

340°C

300°C

320°C

>450°C

(melts)°C

>450°C

570°C

435°C

460°C

Apparatus Groups (US / CAN)Substance Hazard Class NEC 500 NEC 505

Acetylene

Class I

FlammableGases

Group A IIC

Hydrogen GroupB IIC

Ethylene Group C IIB

Propane GroupD IIA

Methane(mining) GroupD -

CombustibleMetalDusts

Class II

CombustibleDusts

Group E -

CombustibleCarbonaceousDusts Group F -

CombustibleDustsnotinGroupEorF

(Flour,Grain,Wood,Plastics,Chemicals)Group G -

CombustibleFibersandFlyingsClass III

FibersandFlyings- -

Equipment Groups [ATEX and IECEx]

Equipment GroupEquipmentCategory

EquipmentProtectionLevel

AtmosphereProtectionLevel

Required ProtectionPerformance & Operation

I(Mineswithfiredamp) M1 Ma Methane&Dust VeryHighTwoFaults,Remain

energised and functioning

I(Mineswithfiredamp) M2 Mb Methane&Dust High

Severe normal operation,

De-energiseinexplosive

atmosphere

II(allotherareas) 1 Ga/Da Gas,Vapour,Mist,Dust VeryHigh Two Faults

II(allotherareas) 2 Gb/Db Gas,Vapour,Mist,Dust High OneFault

II(allotherareas) 3 Gc/Dc Gas,Vapour,Mist,Dust Low Normaloperation

Typical ATEX & IECEx Marking [*ATEX only]

Typical North American Marking (CSA)

Reference toATEX 95 Directive

Serial NumberYear ofCertification

Name of Notified Body performing EC-type examination

SIRA 13 ATEX 1234Gas

Group

DustGroup

TemperatureClass

AreaClassification

AreaClassification

Hazard Class

Hazard Class

Class I, Division 1, Groups A,B,C,D T4

Class II, Division 1, Groups E,F,G

II 2 G*Specific

Marking forExplosionProtection

*EquipmentGroup

*EquipmentCategory

*Environment*Complieswith European

Directives

*NotifiedBody

Number

GasGroup

ProtectionConcept

Code

Approved toUS Standards

TemperatureClass

AreaClassification

Hazard Class

Class I, Zone 0, AEx ia IIC T4

EquipmentProtection Level (EPL)

TemperatureClass (T1-T6)

Gas GroupType ofProtection

ExplosionProtection

Ex d IIC T4 Gb

EquipmentProtection Level

TemperatureClass (°C)

Dust TypeType ofProtection

ExplosionProtection

Ex tb IIIC T135°C Db

Serial NumberYear ofCertification

Name of Body PerformingIECEx Certification

Reference toIECEx Scheme

IECEx CSA 13.1234

Temperature Classification

Classification of maximum surface temperatures

forGroupIIElectronicEquipment(TClass).

IIA T1 Ammonia 630°

IIC T1 Hydrogen 560°

IIA T1 Methane 537°

IIA T1 Propane 470°

IIB T2 Ethylene 425°

IIA T2 Butane 372°

IIC T2 Acetylene 305°

IIA T3 Cyclohexane 259°

IIA T3 Kerosene 210°

IIB T4 Di-ethylEther 160°

IIC T6 CarbonDisulphide 95°

CCSAUS ATEX & IECEx

Suffixes: U – component certification X – special conditions for safe use apply

Ingress Protection CodesFirst Number (protect from solid bodies) Second Number (protect from water)

0 Noprotection 0 Noprotection

1 Objects>50mm 1 Vertical drip

2 Objects>12.5mm 2 Angled drip

3 Objects>2.5mm 3 Spraying

4 Objects>1.0mm 4 Splashing

5 Dust-protected 5 Jetting

6 Dust-tight 6 Powerful jetting

7 Temporary immersion

8 Continuous immersion

°CCSAGrouphasprovidedthetechnicalinformationforthispublication.CSAGroupretainsallintellectualpropertyincludingcopyrightinitswork.

Issu

ed

Oc

tob

er 2

013