GST108 GST116 Conventional Fire Panel
Installation & Operation Manual
(Issue 1.2, July 2004)
Global System Technology PLC
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page I
CONTENTS
1 General................................................................................................................... 1
2 Technical specifications........................................................................................ 1
3 Structure and Configuration ................................................................................. 2
3.1 Appearance ..................................................................................................... 2
3.2 Internal Structure ............................................................................................ 2
3.3 Terminals ......................................................................................................... 3
3.4 Operation Panel............................................................................................... 4
3.4.1 Common State Indicators............................................................................ 4 3.4.2 Zone State LEDs ........................................................................................ 4 3.4.3 Operation State LEDs and Keys ................................................................. 5 3.4.4 Output State LEDs...................................................................................... 5
3.5 Working State .................................................................................................. 6
3.5.1 Zone State.................................................................................................. 6 3.5.2 Output State ............................................................................................... 6 3.5.3 Buzzer ........................................................................................................ 6 3.5.4 Notes.......................................................................................................... 7
3.6 System Setting................................................................................................ 7
3.6.1 Setting Operation Level............................................................................... 7 3.6.2 Setting Relay output.................................................................................... 8
4 Mounting................................................................................................................ 9
5 Operation ............................................................................................................... 9
5.1 Basic Operation............................................................................................... 9
5.1.1 Silence of Fault and Fire Alarm................................................................... 9 5.1.2 Self-test and Clearance of Fire Alarm.......................................................... 9 5.1.3 Day/Night Mode.......................................................................................... 9 5.1.4 Control of Sounders.................................................................................. 10
5.2 Setting Isolation State................................................................................... 10
5.3 Setting Test State .......................................................................................... 15
5.4 Output Setting............................................................................................... 16
5.4.1 Setting Default Value ................................................................................ 16 5.4.2 Setting Manual Call Points........................................................................ 17 5.4.3 Setting Sound Mode of Sounders.............................................................. 18 5.4.4 Setting Delay Output Mode of Sounders................................................... 22
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page II
5.4.5 Setting Delay Time of Sounder Output, Alarm Output and Fault Output .... 23
5.5 GND Fault and Aux. Power Setting .............................................................. 29
5.6 Wiring of Detectors, Manual Call Points and Output Loop ......................... 29
5.7 Wiring Diagram.............................................................................................. 30
5.7.1 Typical Wiring ........................................................................................... 30 5.7.2 Wiring Diagram with Signal Output Interface Board................................... 31
5.8 Calculation of Stand-by Battery Capacity.................................................... 31
6 Troubleshooting................................................................................................... 32
7 Appendix I P-9907 Active End Of Line Unit (AEOL) User Guide ....................... 33
8 Appendix 2 Wiring of GST116 Conventional Fire Panel.................................. 35
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 1
1 General
GST108 GST116 Conventional Fire Panel is a kind of multi-wire fire panel developed from single-chip microprocessor. GST108 Conventional Fire Panel (hereinafter called GST108 Panel) can detect 8 zones and GST116 Conventional Fire Panel (hereinafter called GST116 Panel) can detect 16 zones. Those with signal output interface board has a passive normally open alarm output contact and fault output contact for each zone. Each zone can at most be connected with 15 conventional detectors. The two kinds of panel have six output control points through which it can control some indicators, such as sounder strobes and sounders, etc. The rated maximum load is four sounder outputs and one control output. The panels are designed with stand-by batteries and reserved space for installation (two sealed acid storage batteries); They have functions of test and isolation, Day/Night mode, operation indicator, fault indicator, alarm indicator and cable checking for short circuit or broken circuit. It can also identify the location of detecting zone. The reserved LCD repeater panel interface can be used for multi-zone fire alarm indication. Installation and operation of the panel are very simple and convenient. All control functions are realized through a key switch and programming function realized through a key switch and an internal switch. Except for 8 monitoring zones (8 zone inputs) more, 8 passive normally open alarm output contacts and 8 passive normally open fault output contacts more for those with signal output interface board, and some minor differences in appearance and structure, GST116 is the same as GST108 in technical specifications and operation. We will take GST108 as the example.
2 Technical specifications
1 Operating Voltage DC24V 15 or AC220V +10%
-15% 50Hz 2 Stand-by Battery
Stand-by batteries are configured on order. The battery capacity can be calculated according to the formula in Clause 5.8 of this manual. The maximum capacity is 7Ah (lasting for 24 hours in monitoring state).
3 Loop Parameters Output voltage: DC20V DC28V Static current: 2.4mA (connected with 15 conventional detectors) Resistance when alarming fire: 150 1.5k (normally 470 ) Terminal resistor: 4.7k or using active end of line unit (AEOL)
4 Output Parameters Sounder: Output voltage DC20V DC28V, output current 1A, terminal
resistor 4.7k . Fire alarm: Output voltage DC20V DC28V, output current 0.5A. Fault: Passive contact output, capacity 1A DC24V Repeater panel: 10mA
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 2
Aux power: 0.5A DC20V DC28V 5 Dimension
380mm 320mm 95mm
3 Structure and Configuration
3.1 Appearance
Fig. 3.1
3.2 Internal Structure
Fig. 3.2.1
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 3
Power Storage battery Control board Control Enable lock Evacuate lock Code switch (see Fig.3.2.2 and Fig.3.2.3 Display board
Code switch (SW1)
Fig. 3.2.2 Fig. 3.2.3
3.3 Terminals
ISOCOM
+23
SOUNDER OUTPUT4
+- - -+
DAY0V FIREONEARTHCOMPW COM COM
ZONE INPUT5
FAULT1
+21 1
--+ -+43
+- - + - -6 7
- ++ +-DAY8 SOUNDER
START++ -+- MODE
+AUX SUPPLY
Z5FLT Z8 Z7 Z6
REPEATER OUTPUT
Z2 Z1 -Z4 Z3TRANSFER
-COMNO NC +FAULT OUTPUT
N + -LBAT
FAULT2 FAULT4FAULT3 FAULT5 FAULT6 FAULT7 FAULT8
ALARM3ALARM2ALARM1 ALARM6ALARM5ALARM4 ALARM8ALARM7
Fig. 3.3
EARTH: To chassis earth REPEATER OUTPUT: Output terminals of repeater panel PW ON: Power indicator of repeater panel COM 0V: Power earth of repeater panel COM DAY: Day mode terminal of repeater panel COM FIRE: Fire alarm terminal of repeater panel COM ISO: Isolation terminal of repeater panel FLT: Fault terminal of repeater panel Z1 Z8: Zone indication terminals of repeater panel AUX SUPPLY (+, -): Aux power terminal FAULT OUTPUT (NO, COM, NC): Fault output terminals ALARM OUTPUT (+, -): Alarm output terminals ZONE INPUT (1 8): Zone input teminals BAT (+, -): Stand-by battery terminals AC 220V (N, , L): Primary power teminals SOUNDER OUTPUT (1 4): Sounder output terminals SOUNDER START (+ -): Sounder start terminals DAY MODE (+, -): Day/Night mode conversion terminals FAULT1 FAULT8: Fault output terminal of signal output interface board, which is a normally open contact output in normal state, and will be closed after it alarms fault. ALARM1 ALARM8: Alarm output terminal of signal output interface board, which is a normally open contact output in normal state, and will be closed after it alarms fault.
DIP 1 2 3 ONDIP 1 2 3 ON
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 4
3.4 Operation Panel 3.4.1 Common State Indicators
Fig. 3.4.1
FIRE Red, common fire LED. Remains constantly lit in fire alarm until fire is cleared.
Silence Yellow, common silence LED. Constantly lit when the buzzer or sounder is
in silence state.
Common Fault Yellow, common fault LED. Flashes when any fault occurs and constantly lit after “Silence” key is pressed.
Common Isolate Yellow, common isolation LED. Constantly lit when any zone or
output is isolated.
C.P.U Fault Yellow, CPU LED. Flashes when CPU is in fault and constantly lit when
there is memory check error. Power Fault Yellow, primary power fault LED. Constantly lit when primary power is
in fault.
Battery Fault Yellow, stand-by power fault LED. Constantly lit when stand-by power
is in fault.
Ground Fault Yellow, GND fault LED.Constantly lit when GND is in fault. Delay Yellow, delay LED. Constantly lit when there is any output in delay state.
In Test Yellow, test LED. Constantly lit when any zone is in test state.
Day Mode Yellow, day mode LED. Constantly lit when the panel works at day mode.
Power Supply Green, power supply LED. Constantly lit when power supply is
normal. 3.4.2 Zone State LEDs
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
Fault Battery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 5
Fig. 3.4.2
Fire Red, zone fire LED. Flashes when corresponding zone is in fire alarm state and
constantly lit after “Silence” key is pressed.
Zone Fault/ISO/Test Yellow, flash when corresponding zone is in fault or test state and constantly lit when it’s in isolate state.
3.4.3 Operation State LEDs and Keys
Fig. 3.4.3 Isolate — Green, constantly lit on isolation setting.
Test — Green, constantly lit on test setting.
Output Program — Green, constantly lit on output programming.
Select — For entering programming state and selecting operation.
Shift—For state changing. Enter— For confirmation.
Reset — For cancelling or resetting operation.
Silence For changing silence state of buzzer and sounders.
3.4.4 Output State LEDs
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
Fault Battery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
Fault Battery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 6
Fig.3.4.4 Sounder 1 Yellow, constantly lit when sounder 1 outputs and flashes when in fault. Sounder 2 Yellow, constantly lit when sounder 2 outputs and flashes when in fault. Sounder 3 Yellow, constantly lit when sounder 3 outputs and flashes when in fault. Sounder 4 Yellow, constantly lit when sounder 4 outputs and flashes when in fault. Alarm Output — Yellow, constantly lit when alarm output is activated and flashes when in fault or isolation. Fault Output — Yellow, constantly lit when fault is activated and flashes when in isolation. 3.5 Working State 3.5.1 Zone State 1 Alarm: Alarm LED of corresponding zone flashes, common alarm LED is lit.
Passive fire alarm output contact for corresponding zone of GST108 panel with signal output interface board is closed.
2 Fault: Fault LED of corresponding zone and common fault LED flash (common fault LED turns to be constantly lit after “Silence” key is pressed.) Passive fault output contact for corresponding zone of GST108 panel with signal output interface board is closed.
3 Isolate: Zone fault LEDs in isolation state and common isolate LED are lit. 4 Normal: Zone alarm LED and fault LED turn off. 3.5.2 Output State 1 Action: Corresponding output channel LED turns on. 2 Fault: Corresponding output channel LED and common fault LED flash
(common fault LED turns to be constantly lit after “Silence” key is pressed). 3 Isolate: Corresponding output channel LED flashes and common isolation LED is
lit (Alarm and fault output). 4 Normal: All output channel LEDs turn off. 3.5.3 Buzzer 1 The buzzer vocalizes according to sound priority. The 4 priority levels are: Level 0:
alarm; Level1: fault; Level 2: isolation and test; Level 3: normal. 2 Alarm or manual start of sounder: 0.25s on, 0.25s off. 3 Fault: 0.5s on, 4.5s off. 4 Silence, isolation or test state: 0.5s on 9.5s off.
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
Fault Battery
FaultGround Delay
Test In
ModeDay Power
Supply
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 7
3.5.4 Notes 1 The operation enabled at lower operation level would be also enabled at higher
level.
2 In keyboard operation state, when operation level is changed or no key has been
pressed for more than 4 minutes, the system will cancel all keyboard operations
and resume monitoring state. 3 Conditions for delay output of a certain zone
a The panel is programmed to delay output mode (delay mode is 3, delay time
is not 0).
b In day mode.
c No manual call point in this zone. d No fire alarm in other zones.
e If the zone is in delay mode and fire alarm comes from other zones, it will
cancel delay mode and start output immediately.
4 Memory fault: when there is any fault with the memory, all the programmed
contents have to be set aganin. First, set all parameters as default value (see clause 5.4.1); then set again. The memory fault will be cleared automatically after
reset.
5 In this manual, ” “means constantly lit; “ “means flashing; ” “means not lit.
3.6 System Setting
3.6.1 Setting Operation Level 1 As in Fig.3.6.1a, when “Control Enable” lock points to “O”, the panel is at level 1 (1
of switch SW1 is at “OFF”, see Fig.3.2.2).
Fig. 3.6.1a
2 As in Fig.3.6.1b, when “Control Enable” lock points to “I”, the panel is at level 2 (1
of switch SW1 is at “OFF”, see Fig.3.2.2).
Fig. 3.6.1b
3 1 of switch SW1 is at “ON” as in Fig.3.2.3, the panel is at level 3.
I I
O
Evacuate Control Enable
O
I
O
I
O
Evacuate Control Enable
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 8
3.6.2 Setting Relay output 1 There are three output modes to be set for the four-channel sounder output and
alarm output relay: active output, normally open contact output and normally
closed contact output.
Fig. 3.6.2
a Example 1: to set Sounder 1 as active output, plug fuse F2 and connect foot
5 with 6, and 2 with 3 of pin X1 by jumpers (location of the parts as in
Fig.3.6.2). b Example 2: to set Sounder 1 as normally open output, remove fuse F2 and
connect foot 1 with 2, and 4 with 5 of pin X1 by jumpers (location of the parts
as in Fig.3.6.2).
c Example 3: to set Sounder 1 as normally closed output, remove fuse F2, and
connect foot 1 with 2, and 3 with 4 of pin X1 by jumpers (location of the parts as in Fig.3.6.2).
2 Detailed description as in table 1 (location of the parts as in Fig.3.6.2).
Table 1 Normally closed
contact Normally open contact Active output contact
Output Fuse to be removed
Jumpers Fuse to be removed
Jumpers Fuse to be removed
Jumpers
Sounder 1 F2 X1/ 3&4,1&2
F2 X1/ 5&4,1&2
X1/ 5&6,2&3
Sounder 2 F3 X2/ 3&4,1&2 F3 X2/
5&4,1&2 X2/ 5&6,2&3
Sounder 3 F4 X3/ 3&4,1&2 F4 X3/
5&4,1&2 X3/ 5&6,2&3
Sounder 4 F5 X4/ 3&4,1&2 F5 X4/
5&4,1&2 X4/ 5&6,2&3
Alarm output F6 X5/
3&4,1&2 F6 X5/ 5&4,1&2 X5/
5&6,2&3
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 9
4 Mounting
The panel is walled-mounted, as shown in Fig. 4.1.
Fig. 4.1
5 Operation
5.1 Basic Operation 5.1.1 Silence of Fault and Fire Alarm
1 Silence of fault and fire alarm are done at operation level 2.
2 Press “Silence” in fault state, the buzzer is mute and “Silence” LED is lit; press
“Silence” again, the buzzer will resume non-silence state and “Silence” LED goes
out. 3 In fire alarm state, pressing “Silence” will confirm fire alarm first. If fire alarm in one
zone has been confirmed, corresponding fire LED turns to be constantly lit from
flashing. After all the fire alarms have been confirmed, press “Silence” to change
the silence states of buzzer and sounders.
5.1.2 Self-test and Clearance of Fire Alarm 1 Self-test and Clearance of fire alarm are done in operation level 2.
2 Press “Reset” for 1 second to clear fire alarm in alarm state and to self-test sound
and LEDs in other states.
5.1.3 Day/Night Mode
1 The Day/Night mode is relevant to delay output. Two methods can change the Day/Night mode.
2 Short Day Mode input terminal to enforce the panel into night mode.
3 In level 2, press “Shift” for 1 second to change Day/Night mode. If Day mode is
selected, the Day mode LED will be lit.
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 10
4 Note: If the panel works over 18 hours in Day mode, it will change to Night mode automatically, the Day mode LED flashes and the panel goes into fault. In level 2,
press “Silence” to clear the fault.
5.1.4 Control of Sounders
1 See Fig.5.1.4.1, when “Evacuate” lock points to “I”, the four sounders will be
activated.
Fig. 5.1.4.1
2 See Fig.5.1.4.2, when “Evacuate” lock points to “O”, the sounders will be stopped.
Fig. 5.1.4.2
5.2 Setting Isolation State
1 Isolation setting is valid for the 8 zones, alarm output and fault output.
2 Turn “Control Enable” lock to “I”, press “Select” for 1 second, “Isolate” LED will
flash. Press “Enter”, “Isolate” LED will become constantly lit and the panel enters
isolation setting state (See Fig.5.2a, 5.2b, 5.2c, and 5.2d).
I
O
I
O
Evacuate Control Enable
I
O
I
O
Evacuate Control Enable
Press for 1 second
Fig.5.2b
Enter Day/Night <Shift>
Select
Isolate Test Output Program
Control Enable
Fig 5.2a
Evacuate
O O
I
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 11
3 Press “Select” to select one zone or one output (alarm output or fault output).
Press “Shift” to change isolation state of the selected zone. Isolation state is indicated by the fault LED of corresponding zone, which is not lit in proper
operation and lit in isolation state. The selected state is indicated by the flashing of
alarm LED of corresponding zone. The following example shows how to select
zone No. 6 and set its isolation state (See Fig.5.2e and 5.2f).
FIRE Silence Fault
Common
Fault Isolate Common
Fault C.P.U Power
Fault Battery
Fault Ground Delay
Test In
Mode Day Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig.5.2d
Fig.5.2c
Enter Day/Night <Shift>
Select
Isolate Test Output Program
Press “Enter”
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 12
图 6.2e
2
Enter Day/Night<Shift> Select
Isolate Test Output Program
Press it 5 times
1
Zone No.
Fire
Zone Fault/ISO/Test
1 2 3 4 5 6 7 8
Zone No.
Fire
Zone Fault/ISO/Test
1 2 3 4 5 6 7 8
3
4 5 Zone No.
Fire
Zone Fault/ISO/Test
1 2 3 4 5 6 7 8
Fig. 5.2e
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 13
4 Press “Enter” to exit and save the settings (See Fig.5.2g).
Press it 3 times
Enter Day/Night<Shift> Select
Isolate Test Output Program
Zone No.
Fire
Zone Fault/ISO/Test
1 2 3 4 5 6 7 8
Zone No.
Fire
Zone Fault/ISO/Test
1 2 3 4 5 6 7 8
3
1
2
Fig. 5.2f
ENTER
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press Enter
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 14
5 Press “Reset” to exit and the settings will not be saved. See Fig. 5.2h.
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig. 5.2g
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press Reset
RESET
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig. 5.2h
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 15
5.3 Setting Test State 1 Press “Select” for 1 second; “Isolate” LED will flash. See Fig.5.2a 5.2c.
2 Press “Shift” once, “Test” LED will flash. When the LED is flashing, pressing
“Enter” the “Test” LED will become constantly lit and the panel enters test setting
mode. (See Fig. 5.3a)
Enter Day/Night<Shift> Select
Isolate Test Output Program
Enter Day/Night<Shift> Select
Isolate Test Output Program
Press Shift Press Enter
Fig.5.3a
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Press 4 times
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press Shift
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 16
3 Press “Select” to select the zone to be tested (See Fig. 5.3a and Fig. 5.3b,taking
zone No. 5 as an example). Press “Shift” to change test state of selected zone.
The test state is indicated by corresponding alarm LED, which is not lit in proper
operation and constantly lit in testing. Fault LED of corresponding zone will flash
when the zone is selected. Confirmation and clearance operation are the same as
isolation setting.
5.4 Output Setting
5.4.1 Setting Default Value
All following operations are in operating level 3.
1 Setting default mode To set all programmable items as default:
a There should be manual call points in all zones.
b The sound mode of all sounders and all delay modes are mode 3.
c All delay time is 0.
d Clearing isolation state (Only GST 116 panel has this default mode). 2 Press “Select” for 1 second and “Isolate” LED flashes. Press “Shift” twice, “Output
Program” LED flashes. When “Output Program” LED is flashing, press “Enter”,
“Output Program” LED is lit and the panel enters programming state as shown in
Fig.5.4.1 (If “Enter” is pressed for more than 2s, all programmable settings will be
default).
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig. 5.3b
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 17
5.4.2 Setting Manual Call Points
1 Execute step 2 of 5.4.1 to enter output programming (see Fig.5.4.1). “Isolate” and
“Test” LED flash alternately. Press “Enter” to confirm and enter setting state for
manual call point (see Fig. 5.4.2).
2
Enter Day/Night<Shift>
Select
Isolate Test Output Program
Press
twice
Enter Day/Night<Shift>
Select
Isolate Test Output Program
1
Enter Day/Night<Shift>
Select
Isolate Test Output Program
Press “Enter” for more than 2s to set
all programmable values as default
Enter Day/Night<Shift>
Select
Isolate Test Output Program
Isolate and Test
LEDs flash
alternately
Fig. 5.4.1
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 18
2 Press “Select” to select zone. Flashing of corresponding fault LED will indicate the
selected state. Press “Shift” to change the state of selected zone (whether there is
manual call point), which is indicated by corresponding alarm LED. The alarm
LED is not lit in proper operation and lit when manual call point is selected. Please refer to setting of test state for detailed operation.
3 Press “Reset” to exit without saving the settings. Press “Enter” to exit and save
the settings.
5.4.3 Setting Sound Mode of Sounders
1 Execute step 2 in 5.4.1 to enter output programming (see Fig.5.4.1). “Isolate” and “Test” LED flash (Fig. 5.4.3a), and press “Shift” to select the state shown in
Fig.5.4.3b. Press “Enter” to confirm, and enter setting state of sound mode of
sounders (see Fig. 5.4.3c).
Press Enter
Enter Day/Night<Shift>
Select
Isolate Test Output Program
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig. 5.4.2
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 19
2 See Fig.5.4.3c, the alarm LED of zone No. 1 is lit; “Sounder 1” output LED is lit; “Silence” LED and buzzer indicate the primarily programmed sound mode (see 3
of 5.4.3). If you don’t want to change the sound mode, press “Select” to select the
next sounder (as in Fig.5.4.3d, we selected sounder 4 as an example) or press
“Enter” to set the next zone (see Fig.5.4.3e). If you want to change the sound
mode, press “Shift” to select one of the three sound modes. If the settings for zone No. 1 have been finished, press “ Enter” to save the results and go on settings for
the next zone, and alarm LED of the next zone will be lit. Press “Reset” at any time
to exit setting.
Fig.5.4.3a
Press “Shift”
Enter Day/Night<Shift>
Select
Isolate Test Output Program
Enter Day/Night<Shift> Select
Isolate Test Output Program
Press “Enter”
Fig.5.4.3b
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig. 5.4.3c
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 20
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
2
1
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
Enter Day/Night<Shift> Select
Isolate Test Output Program
Press 3
times
3
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
Fig.5.4.3d
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 21
3 “Silence” LED and buzzer
a Mode 1: Buzzer is mute and “Silence” LED is blank-off.
b Mode 2: Buzzer rings with 1:1 interval and “Silence” LED flashes by 1:1
(0.25s on, 0.25s off).
c Mode 3: Buzzer rings with 1:3 interval and “Silence” LED flashes by 1:3. The above indication modes are used for setting sound mode and delay output mode
Fig.5.4.3e
2
3
Zone Fault/ISO/Test
Zone No
Fire 1 2 3 4 5 6 7 8
1
Enter Day/Night<Shift> Select
Isolate Test Output Program
Zone Fault/ISO/Test
Zone No
Fire 1 2 3 4 5 6 7 8
Press 8
times
Zone Fault/ISO/Test
Zone No
Fire
1 2 3 4 5 6 7 8
4
5
6
7
8
Zone Fault/ISO/Test
Zone No
Fire 1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No
Fire
1 2 3 4 5 6 7 8
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 22
of sounders. 4 Three sound modes
a Mode 1, non-output
b Mode 2, intermittent output
c Mode 3, continuous output
5.4.4 Setting Delay Output Mode of Sounders 1 Execute step 2 of 5.4.1 to enter output programming (See Fig.5.4.1). Press “Shift”
twice (See Fig.5.4.4a Fig.5.4.4c), then press “Enter” to confirm and the system
enters programming of delay output of sounders (See Fig.5.4.4d).
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fau lt/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig.5.4.4d
Enter Day/Night<Shift>
Select
2
Fig.5.4.4a Fig.5.4.4b
1
Enter Day/Night<Shift> Select
Press twice
Enter Day/Night<Shift> Select
Isolate Test Output Program Isolate Test Output Program
Fig.5.4.4c
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 23
2 Setting method in this step is the same as 2 of 5.4.3, except that the four indication modes of the “Silence” LED and buzzer here represent four delay modes while in
5.4.3 it represents the former three sound modes.
3 Fourl delay modes of sounders
1 Mode 1, non-output.
2 Mode 2, connecting with the alarm output. 3 Mode 3, delay output.
4 Mode 4, non-delay output. 5.4.5 Setting Delay Time of Sounder Output, Alarm Output and Fault Output
1 Note: when the panel is in setting mode of delay time, the delay time can be
calculated by the indication of fault LED in alarming zones. The method is as follows:
Suppose Td is the delay time, Cn(n=1 2 3 4 5 6 7 8) is weighting coefficient.
Value modes are as follows: when fault LED of zone No. n is constantly lit, Cn=1
On the contrary Cn=0. Xn is weighting coefficient and value mode is Xn=n. Delay
time can be calculated by the following formula:
∑=
××=n
i
XnCnTd1
)(5.0 (Td unit: minute , n=1 2 3 4 5 6 7 8)
For example, in Fig.5.4.5a, Td=(1 1+0 2+1 3+1 4+0 5+0 6+0 7+0 8)
0.5= 4 minutes 2 Execute step 2 of 5.4.1 to enter output-programming mode (see Fig.5.4.1). Press
“Shift” 3 times, then press “Enter” to confirm and enter setting mode of output
delay time (see Fig.5.4.5b 5.4.5c).
Zone Fault/ISO/Test
Zone No
Fire
1 2 3 4 5 6 7 8
Fig.5.4.5
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 24
3 See Fig.5.4.5c, Flashing of Sounder1 Sounder4 LEDs shows that sounder delay
output can be set now. In this mode, we can select the object by pressing “Shift”. Press “Shift” to choose linkage alarm delay output (Alarm O/P LED flashes) or
fault delay output (Fault O/P LED flashes). See Fig.5.4.5d.
1
3
Fig.5.4.5b
Enter Day/Night<Shift> Select
Isolate Test Output Program
Enter Day/Night<Shift> Select
Isolate Test Output Program
Enter Day/Night<Shift> Select
Isolate Test Output Program
Enter Day/Night<Shift> Select
Isolate Test Output Program
2
Press Enter
Press 3
times
Fig.5.4.5c
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 25
4 Setting Delay Time of Sounders
a In setting delay output, the delay time of four channels of sounder are the
same, while the output mode can be different.
b Execute step 2 of 5.4.1, and enter the delay time setting. The indication on front panel is shown in Fig. 5.4.5c. Press “Enter” to set delay time of
sounders, as in Fig.5.4.5e, The LEDs of Sounder1 Sounder4 turn into
constantly lit from flashing, and the alarm LED of zone No. 1 flashes. The
state of fault LED of the alarming zone can indicate the sounder’s output
delay time. (Delay time in Fig.5.4.5e is 0).
Fig.5.4.5d
3
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
1
2
Enter Day/Night<Shift> Select
Isolate Test Output Program
Press it 3
times Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
Sounder1 Sounder3
Sounder2 Sounder4
Alarm Output
Fault Output
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 26
c Press “Select” to select zone number, indicated by the flashing of zone alarm when selected. Press “Shift” to change fault LED state of selected zone, which will be constantly lit after selected. According to the selected zone, we can calculate the delay output time. For details please refer to step 1 of 5.4.5. After finishing setting, press “Enter” to exit and save the results or press “Reset” to exit without saving the result. The setting method is the same as isolation setting.
5 Setting Delay Time of Alarm Output a Execute step 2 of 5.4.5 to enter delay time setting. The indication on front
panel is shown in Fig.5.4.5c. Press “Shift” once and the front panel shows as in Fig.5.4.5f. Press “Enter” to set the alarm output delay time as in Fig.5.4.5g, alarm O/P LED becomes constantly lit from flashing, while the alarm LED of zone No.1 flashes. The state of fault LED of the alarming zone can indicate alarm output delay time.
b Setting method and calculation is the same as setting output delay time of sounders; see c of 4 of 5.4.5.
FIRE Silence Fault
Common
FaultIsolateCommon
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press Enter
Fig.5.4.5e
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 27
Complies To EN 54-2
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Evacuate Control Enable
I I
OO
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Press Shift
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Fig.5.4.5f
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Evacuate Control Enable
I I
OO
FIRE Silence Fault
Common
FaultIsolateCommon
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Press Enter
Fig.5.4.5g
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Complies To EN 54-2
Complies To EN 54-2
Evacuate Control Enable
I I
OO
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 28
6 Set fault delay time a Execute step 2 of 5.4.5 to enter delay time setting. The indication on front
panel is shown in Fig.5.4.5c. Press “Shift” twice, the front panel is as in
Fig.5.4.5h. Press “Enter” to set the delay time of fault output. See Fig.5.4.5i.
Fault O/P LED becomes constantly lit from flashing, and the alarm LED of
zone No. 1 flashes. The state of fault LED of the alarming zone can indicate
fault output delay time. b Setting method and calculation is the same as setting output delay time of
sounders; see c of 4 of 5.4.5.
Fig.5.4.5h
FIRE Silence Fault
Common
FaultIsolate Common
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press Enter
FIRE Silence Fault
Common
FaultIsolateCommon
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2Press
twice
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 29
5.5 GND Fault and Aux. Power Setting 1 Short pin X8 (Location as in Fig.3.6.2) with a jumper to check GND fault.
Otherwise it won’t check GND fault.
2 Selecting output mode of aux. power: Connect 1 and 2 of X9 (Location as in
Fig.3.6.2) as constant output. Connect 2 and 3 and the reset of the system will
interrupt output for 3 seconds. 5.6 Wiring of Detectors, Manual Call Points and Output Loop
1 Wires acceptable by terminals of this panel: cross section: 0.5mm2 2.5mm2 .
Considering electromagnetic compatibility, shielded cable should be used. Keep
the shield reliable 360-degree contact with the chassis in installation.
2 There can be 15 detectors and infinite manual call points in each loop, and there are two wiring methods.
a In the loop, all manual call points are connected in front of the detectors and a
4.7k resistor should be connected at end of the loop. See Fig.5.6.2a.
ZoneInputTerms
Panel
MCP
470R
(normal)
MCP
470R
(normal)
-
+
4K7Resistor
NO DIODE
Fig.5.6.2a
b In the loop, the detectors and manual call points can be connected at any
location and an AEOL is connected at end of the loop. A diode is connected
on the detector base. See Fig.5.6.2b.
FIRE Silence Fault
Common
FaultIsolateCommon
FaultC.P.U Power
FaultBattery
FaultGround Delay
Test In
ModeDay Power
Supply
1 2 3 4 5 6 7 8
Zone Fault/ISO/Test
Zone No.
Fire
Isolate Test Output Program
Program
Select <Shift> Day/Night
Enter Reset Silence
Resound
Sounder 1
Sounder 2 Sounder 4
Sounder 3 Alarm Output
Fault Output
Evacuate Control Enable
I I
OO
Complies To EN 54-2
Fig.5.4.5i
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 30
ZoneInputTerms
Panel
470R(normal)
+
-
A.E.O.L
MCP
Fig.5.6.2b
3 Wiring of Output Loop: The sounders and remote devices should be polarized and connected into the loop according to the marked polarity. A 4.7k resistor is paralleled at end of the loop.
5.7 Wiring Diagram
5.7.1 Typical Wiring
Fig.5.7
REPEATER Repeater panel output
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 31
ALARM OUTPUT Alarm output SOUNDER OUTPUT Sounder output WIRED SIMILARLY Similar wiring FIELD DEVICES Detector AEOL Active end of line unit VOLT-FREE CONTACT Active contact EMI FILTER Filter PSU Power TO DISPLAY BOARD To display board BATT Stand-by battery terminal
5.7.2 Wiring Diagram with Signal Output Interface Board
PSU
FAULT7
ALARM7
FAULT2
ALARM2
FAULT1
ALARM1
FAULT4 FAULT5FAULT3 FAULT6
ALARM4ALARM3 ALARM5 ALARM6
FAULT8
ALARM8
Fault Output Contact
Fire Alarm Output Contact
Fig. 5.8 5.8 Calculation of Stand-by Battery Capacity 1 Battery voltage: DC24V
2 Power supply specifications
Table 2 PSU Capacity Maximum current of output
circuit Capacity of interior
battery 2.0A 1A 7Ah
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 32
Stand-by battery works in normal monitoring state, current (I1)=0.13A Stand-by battery works in alarming state (I2)
Table 3 Stand-by battery
current (A) Quantity
(Zone number) Current Total current
Remarks
Input Loop n 0.044 0.044xn 15 detectors in each zone
Output Loop 1A Output of Aux. power
Suppose C is the required minimum capacity and T is the time that the battery works
normally (unit: hour). Suppose I1 as the total current at normal monitoring state and I2 as the total current at alarming state. Then the battery capacity can be calculated by
the following formula:
C=1.25[(I1 T)+I1+I2] Ah
6 Troubleshooting
Table 5 Fault Disposal and cause
All the LEDs are dark after the panel is started.
+24V output, +5V non-output: check N7 3M03 and its peripheral circuit
+24V non-output, +5V non-output Check the fuse F7 of main board cut-off or not Check the relay K7 of main board and its peripheral circuit
No report on primary and standby power fault
Check N6 of main board and the peripheral circuit
Wrong judgment of detecting zone
or cable checking
Nuisance alarm from several zones: Measure voltage on VREF_H of main board normal or not. It can befigured out according to the power voltage+24V(measured), R67 and R60. Normally, when the power voltage is +27V, the measured voltage is 3.65V.
False fault report from several zones: Measure voltage on VREF_L of main board normal or not. It can be figured out according to the power voltage +24V(measured), R68 and R61. Normally, when the power voltage is +27V, the measured voltage is 1.0V. Measure the voltage on VREF_S of main board normal or not. It can be figured out according to the power voltage +24V(measured), R58 and R6. Normally, when the power voltage is +27V, the measured voltage is 24.7V.
Nuisance alarm from several output loops: Measure the voltage on VREF_H of main board normal or not. Check pin X1 X5 correct or not and fuse F2 F6 correct or not.
Cannot store the result D9 24LC02 on display board is defective Failure of manual lock or a certain key
Loose contact between D1 on display board and socket
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 33
7 Appendix I P-9907 Active End Of Line Unit (AEOL) User
Guide
1 Technical Specifications
a Technical specification
Working voltage range: DC24+4 -9 V
Nominal voltage: DC24V
Equivalent resistor: 4.7k
Operating circumstance:
Temperature: -10 +50
Relative humidity: 95%, no condensation
2 Structure
Fig. A-1 Bottom view
Fig. A-2 Top view (cover uninstalled)
1: Enclosure
2: Fixing screw
3: Circuit board
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 34
3 Mounting and Wiring The mounting method of P-9907 End of Line Unit is the same as that of detector bases,
but there are two methods to mount it.
a Used as detector base, on which conventional detectors can be installed. By
this method, the anode of loop should be connected to terminal “1”, and
cathode to “3”. System wiring is shown in Fig. A-3.
Fig. A-3 P-9907 AEOL used as detector base
b If P-9907 AEOL is not installed with a detector, the loop anode should be
connected to terminal “2” and cathode to “3”, as shown in Fig. A-4.
Fig. A-4 P-9907 AEOL not used as detector base
Diode
O-
O+
Diode Diode
Conventional Detector
Conventional Detector
Output end of multi-wire fire alarm controller or intelligent zone monitor unit
AEOL
O-
O+
Diode Diode
Conventional Detector
Conventional Detector
AEOL
Output end of multi-wire fire alarm controller or intelligent zone monitor unit
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 35
8 Appendix 2 Wiring of GST116 Conventional Fire Panel
1 Typical Wiring Diagram
Fig. A-5 GST116 Typical Wiring Diagram
REPEATER Repeater panel output
ALARM OUTPUT Alarm output
SOUNDER OUTPUT Sounder output
WIRED SIMILARLY Similar wiring
FIELD DEVICES Detectors AEOL Active end of line unit
VOLT-FREE CONTACT Active contact
EMI FILTER Filter
PSU Power supply
TO DISPLAY BOARD To display board BATT Stand-by battery
2 Wiring Diagram with Signal Output Interface Board
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 36
PSUALARM6
FAULT6
ALARM2
FAULT2
ALARM1
FAULT1
ALARM5
FAULT5
ALARM4ALARM3
FAULT4FAULT3
ALARM15
FAULT16
FAULT11
ALARM11
FAULT10FAULT9
ALARM9 ALARM10ALARM8ALARM7
FAULT8FAULT7 FAULT15
ALARM14ALARM13
FAULT14FAULT13FAULT12
ALARM12 ALARM16
Fault Output Contact
Fire Alarm Output Contact
Fig. A-6 GST116 Wiring Diagram with Signal Output Interface Board
3 Terminals
ISOCOM
+23
SOUNDER OUTPUT4
+- - -+
DAY0V FIREONEARTHCOMPW COM COM
b+6
ZONE INPUT5
+-- +b+1
-+b+2 b+3
- +b+4
+ --b+5
+21 1
--+ -+43
+- - + -
+-+b+7
+-b+8
-6 7
- ++ +-DAY8 SOUNDER
START++ -+- MODE
+AUX SUPPLY
Z5FLT Z8 Z7 Z6
REPEATER OUTPUT
Z2 Z1 -Z4 Z3TRANSFER
-COMNO NC +FAULT OUTPUT
N + -LBAT
FAULT6FAULT3FAULT2FAULT1 FAULT4 FAULT5 FAULT7 FAULT8 FAULT14FAULT11FAULT10FAULT9 FAULT12 FAULT13 FAULT15 FAULT16
ALARM6ALARM3ALARM1 ALARM2 ALARM5ALARM4 ALARM8ALARM7 ALARM12ALARM9 ALARM11ALARM10 ALARM15ALARM13 ALARM14 ALARM16
-+ + 16 --+ + - + --+ + --+9 10 1211 151413
ZONE INPUT
Fig. A-7 Terminals of GST116
GST108 GST116 Conventional Fire Panel Global System Technology PLC Installation and Operation Manual The Intelligent Solution
Global System Technology PLC London EC1R 3AU England
www.gstplc.com Email [email protected] Page 37
EARTH To chassis earth REPEATER OUTPUT Output terminal of repeater panel
PW ON Power indication terminal of repeater panel
COM 0V Power earth terminal of repeater panel
COM DAY Day mode terminal of repeater panel
COM FIRE Fire alarm terminal of repeater panel COM ISO Isolation terminal of repeater panel
FLT Fault terminal of repeater panel
Z1 Z8 Zone indication terminals of repeater panel
AUX SUPPLY + - Aux power terminals
FAULT OUTPUT NO COM NC Fault output terminals ALARM OUTPUT + - Alarm output terminals
ZONE INPUT 1 8 , Zone input terminals
b+1 b+8: Zone input terminals on expansion board
ZONE INPUT 9 16 Zone input terminals on signal output interface board
BAT + - Stand-by battery terminals AC 220V N L Primary power terminals
SOUNDER OUTPUT 1~4 Sounder output terminals
SOUNDER START + - Sounder startup terminals
DAY MODE + - Day/Night mode conversion terminals
FAULT1 FAULT16: Fault output terminal of signal output interface board, which is a normally open contact output in normal state, and will be closed after it alarms fault. ALARM1 ALARM16: Alarm output terminal of signal output interface board, which is a normally open contact output in normal state, and will be closed after it alarms fault.