Gritcomm Inteligent Technolog (Shenzhen) Co.Ltd Product Spec... · Web viewConnection of a energy...
Transcript of Gritcomm Inteligent Technolog (Shenzhen) Co.Ltd Product Spec... · Web viewConnection of a energy...
Gritcomm Intelligent Technology (Shenzhen) Co.Ltd
Product Specification
Name Street lighting Centralized Server
Model MTC-001-UP1200
Date June 16, 2016
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd2
Product Specification
Catalog
一、Product overview.........................................................................................................................................................3
1. Introduction..............................................................................................................................................................3
a. System Profile.........................................................................................................................................................3
b. System Platform.............................................................................................................................................4
2. Technical Characteristics.....................................................................................................................................5
二、 Major Function.............................................................................................................................................................5
三、 Main technical index.................................................................................................................................................7
四、 Terminal unit and installation instructions........................................................................................................8
1. Terminal structure..................................................................................................................................................8
2. Terminal installation diagram............................................................................................................................8
3. Terminal description..............................................................................................................................................9
a. Outline dimension..........................................................................................................................................9
b. Key definition.................................................................................................................................................10
c. Status indication...........................................................................................................................................10
d. Terminal connection....................................................................................................................................11
4. SIM card installation............................................................................................................................................13
5. Antenna installation............................................................................................................................................13
6. Connection of a energy meter.........................................................................................................................14
2
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd3
五、 Installation and debugging...................................................................................................................................15
1. Matters needing attention................................................................................................................................15
2. Installation preparation......................................................................................................................................16
3. Installation method.............................................................................................................................................16
4. Trial operation method.......................................................................................................................................17
六、 Transportation and storage...................................................................................................................................17
七、 Common failures and troubleshooting methods...........................................................................................18
3
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd4
一、Product overview
1. Introduction
Street lighting Centralized Server (SLCS) is intermediate mechanism
that is connected with the Smart street lamp node (SSLN) and the
Cloud server(CS); It is responsible for the downward transmission of
control commands issued by the cloud server, and the collected data
of each street lamp node status information to the cloud server.
SLCS & CS through the GPRS communication, and SLCS & SSLN
utilize the Power line Communication (PLC).
a. System Profile
This product is mainly composed of five parts: Power Supply Unit
(PSU), Processing Unit (PU), PLC Unit (PLC), GPRS Unit(GPRS), Human-
machine Interface Unit (HMI) and the Coupling Unit (CU), the product
system block diagram as shown below:
4
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd5
Power Supply Unit (PSU)for other units to provide a stable voltage.
GPRS Unit (GPRS/CDMA) engaging the GPRS network and the
cloud server, data will transfer from the data concentrator, data will be
executed with the cloud server command.
Processing Unit (PU) it coordinate each unit of data collection
and analysis, and then stored in the SD card in the concentrator. At the
same time, the processing unit also carries commands issued by the
server. It is also equipped with standard RS485 interface and Ethernet
interface.
PLC Unit (PLC) through the power line medium will monitor Street
5
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd6
commands to each pole, realization of the intelligent monitoring
system of street lamp.
Man-machine Interface Unit (HMI) provides a liquid crystal
screen and a press key operation, which is convenient for the user to
configure and view all kinds of information of the smart street lamp
system.
b. System Platform
Embedded real-time operating system embedded operating system,
the software uses the embedded operating system development,
hardware uses 32 bit Cotex-M3 core CPU, 512KB program memory,
96KB static memory, external Flash 32GB memory. With the cloud
server communication using industrial grade GPRS/CDMA
communication module in the concentrator, TCP/IP protocol and WEB
server, supports a variety of wired and wireless network
communication, network support through remote upgrade firmware
concentrator.
6
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd7
2. Technical Characteristics
This product can not only collect street lamp node operation and
power distribution box related electrical parameters and environmental
parameters, and all the lights through the original lamp wire laying
monitoring distribution box connected. It can collect the data for scientific
analysis of abnormal operation of the statistical data reflect the formation
of street management needs and equipment.
二、 Major Function
Energy collection: This product through the external 485
communication port digital meter, collect all kinds of electrical
parameters of the power distribution cabinet, including three-phase
voltage, three-phase current, three-phase active power, three-
phase reactive power, three-phase power factor, energy
consumption, frequency and so on.
Anti theft switch of the cabinet: This product through the
7
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd8
sensor switch cabinet, power distribution cabinet door detection on
and off state, automatically determine whether the equipment is
abnormally opened, once detected the abnormal situation, timely
reporting of anti-theft alarm.
Abnormal alarm: This product can generate various alarm
information such as power distribution cabinets, power outages,
overload alarm alarms, phase loss, abnormal alarm lights off alarm
and so on, so the alarm event can be stored in the concentrator,
easy to trace.
Signal acquisition: This product can be detected by the analog
port and the switch port, realize the measurement of temperature,
humidity, switches and other sensor data.
Communication function: concentrator and cloud server through
the GPRS/CDMA communication, and the design of local
maintenance interface, local maintenance through RS-485 or
Ethernet interface. Concentrator and lampposts in node through the
power line carrier communication, the communication signal to
OFDM modulation to the power line, realize communication with the
8
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd9
Smart street lamp node.
Clock management: built-in industrial grade clock chip and
industrial battery, clock error < 0.12S/h, clock hold time > 10 years.
Remote upgrade: This product supports remote online upgrade
firmware function.
三、 Main technical index
Item ParameterInput voltage 100Vac - 240Vac (-20%/+20%), 50/60Hz
Power Operation <3Watts, Active power
9
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd10
Operating temperature
-40 to +60℃
Storage temperature
-40 to +85℃
Operating humidity
10 to 90% RH @ 60℃
Storage humidity 5 to 90% RH max @ 60℃
Processor speed Cotex-M3,72MHz
Storage 32GB SD;96KB RAM
Carrier channel OFDM 9KHz to 495KHz
Control button Up turn key,Down key,Left shift key,Right shift key,Determine key
Indicator light Power indicator light - always on / off;
Connection indicator light - always on / off;
Task run indicator light - flash / slow flash.
Ethernet interface
RJ-45
serial interface 1*RS485 接口;1*RS232(DB9)Digital input
interface 2 * Opt coupler input,30V AC/DC
Relay output 3* SPST Relay output,240VAC@10A or 24VDC@10A
Pulse electric meter interface 2 way digital pulse meter input,DIN 43 864,Port maximum
voltage <12VDC,Port maximum current <27mA
10
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd11
Analog input interface Analog signal interface, Input voltage 0~10V,
Power Resolution =1024
Dimension H x W x D = 155 x 111 x 59 (mm)
Mounting method
8TE DIN Guide
EMC FCC Part 15 Class B, EN55022 Class B, EN55024, CISPR 22 Class B, VCCI Class B
Certificate CCC, CE, UL60905
四、 Terminal and installation instructions
1. Terminal structure
The product structure components include three parts: human-
machine interaction part, antenna interface part, terminal part.
11
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd12
2. Terminal installation diagram
Description: the industrial guide behind the use of the
concentrator, the equipment installed in the wall or in the
distribution box, and the four corner screw holes are to
stabilize the installation.
12
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd13
3. Terminal description
a. Outline dimension
13
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd14
b. Key definition
Left shift Up turn Determine Down Right shift
c. Status indication
Power —— Power indicator light, red, power on when the lights are
often light, power off when the lights go out.
Link —— Link indicator light, red, light is often bright, the normal
connection with the server, when the lights go off, and the cloud server is
disconnected.
Run ——Running lights, red, when the collector has a power line task,
flash 4 times per second (fast flickering), when the power line
concentrator did not perform the task, flash 1 times per second (slow
14
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd15
flashing).
d. Terminal connection
Mun Mean
Definition Mun Mean
Definition
1 N N line input 14 K1 Switch capacity 1 isolated input,
(-) negative
2 L1 AC line A phase
(equipment power supply)
15 A1 Switch capacity 1 isolated input,
(+) positive
15
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd16
3 L2 AC line B phase 16 K2 Switch 2 isolated input,
(-) negative
4 L3 AC line C phase 17 A2 Switch 2 isolated input,
(+) positive
5 NC Reserve 18 SOA1
Pulse electric meter 1 input,
(+)positive
6 GND
Equipment low current Grounding
19 SOK1
Pulse electric meter 1 input,
(-) negative
7 +12V
Equipment 12V DC output, current < 200mA
20 SOA2
Pulse electric meter 2 input,
(+)positive
8 S1A Relay output S1A,240VAC @ 10A
21 SOK2
Pulse electric meter 2 input,
(-) negative
9 S1B Relay output S1B,240VAC @ 10A
22 GND Equipment low current Grounding
10 S2A Relay output S2A,240VAC @ 10A
23 AD1 Analog input 1
11 S2B Relay output S2B,240VAC @ 10A
24 AD2 Analog input 2
12 S3A Relay output S3A,240VAC @ 10A
25 B RS-485 interface, B
13 S3B Relay output S3B, 26 A RS-485 interface, A
16
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd17
240VAC @ 10A
Three-phase four wire power supply:1) Power supply mode
This product uses three-phase four wire system power supply, power
supply, we must ensure that the normal power supply N and L1, in
order to make the equipment work normally, when L2, L3 any phase
power, do not affect the normal operation of the equipment.
2) Power supply voltage
Rated voltage of working voltage of this product:220VAC/380VAC;Operating error :-20% ~ +20%;Allowable deviation:-6% ~ +2%;
3) Spare battery
The interrupt of power supply, can be maintained by the built-in
battery data concentrator and the clock, holding time of a month.
Power recovery, the preservation of the data is not lost, the normal
operation of the internal clock.
17
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd18
4) Power consumption
When the product in the non communication state, three-phase
power supply, the operating power is less than 3W, as the power is
less than 5va. When the communication state of concentrator
three-phase power supply, power is less than 6W, the apparent
power is less than 10va.
4. SIM card installation
SIM card slot in the concentrator side will have launched GPRS
services in the SIM card slot into the concentrator as shown, and
note that the SIM card insertion direction cannot be inserted. There
are external concentrator antenna location, concentrator through
GPRS communication, must be connected to the antenna.
18
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd19
5. Antenna installation
The side of the product is provided with an external antenna
interface.
Advice note:
The signal strength of the installation position should be confirmed
before antenna installation. The antenna should be placed in an open
position, and an external antenna is recommended.
In the use of electromagnetic shielding applications, should use
an external antenna, and the antenna should be placed in a
shielded area.
19
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd20
Long connecting line should be set into a ring and fixed to the
safety, the antenna is not too large angle.
Poor environmental signals (such as the basement, tunnel),
should contact the local operators to solve the problem of signal
coverage.
6. Connection of electric meter
This product through the RS-485 interface data acquisition of
three-phase digital ammeter, can measure power three-phase
voltage, current, power, power frequency power parameter, but
also has accumulated power, electric energy pulse, alarm, switch
input and output, analog quantity output and the loose network
communication function. The meter has a friendly man-machine
interface. Electric wiring diagram and wiring diagram as shown in
the concentrator:
20
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd21
Be careful: Voltage input :When direct input, the rated input voltage input
voltage should be not higher than the meter (400V), you should
consider the use of voltage transformer (PT). 1A fuses must be
installed at the voltage input.
Current input: Standard rated current is 5A, when the input
current is more than 5A, you must use the external current
transformer (CT).
To ensure that the input voltage, input current corresponding to
the same order, the line and the direction of the line is
consistent, otherwise there will be a number of measurements
21
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd22
and symbol error.
The electric meter input connection mode according to the
number of the current mutual inductor, in the case of external 2
current transformers, select three-phase three wire connection
mode. In the case of external 3 current transformers, select the
three-phase four wire connection mode.
The specific use of electricity meters, please refer to the
instructions for the use of electricity meters.
五、 Installation and debugging
1. Matters needing attention
Be careful: Please operate strictly in accordance with the relevant provisions
of the electricity sector;
No power leads off the concentrator charged in the case, in order
22
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd23
to avoid danger;
The installation site should take careful safety measures to
prevent personnel from electric shock;
Please make sure that you have read the instructions carefully
before the operation;
2. Construction preparation
1. In the installation of concentrator before at least need to install a
fixed IP address of the cloud server and can run normally. In order
to speed up the progress of the installation and configuration of IP
and the port number of the concentrator best done in the office.
2. Prepare a SIM GPRS card, in order to connect to the use of the cloud
server.
3. To prepare all kinds of wire, such as voltage wiring, current wiring,
RS-485 communication line, switch control line, Ethernet cable,
sensor access lines, etc.
23
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd24
3. Installation method
The product needs to be installed in the two power distribution
transformer side of the street lamp power distribution cabinet, through
the back of the guide rail card slot and power distribution cabinet
fixed, requiring vertical installation. When installing the first guide rail
is fixed in the wall frame in power distribution cabinet, then buckle for
concentrator can be strengthened, the concentrator of the four corners
of the fixed screw. This product cannot be exposed to outdoor alone.
4. Trial operation method
The product installation, wiring diagram right after the operation, in
the confirmation of each connection line is accurate, can be air switch
in power distribution cabinet, into the voltage of liquid crystal display,
concentrator can normal light, and display the correct time (power),
the power indicator light in the steady state, the connection (Link the
indicator is off state), operation (Run) indicator light in the slow flash
(1 seconds flashes 1 times) state.
24
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd25
六、 Transportation and storage
1. Packing is in accordance with GB/T15464-95.
2. To avoid the rain and snow shower directly hit should be transportation
and unpacking process, to prevent violent vibration and impact.
3. Storage conditions: the ambient temperature is not more than ~+70 C
-30 C, relative humidity 5%~100%, the place should be kept clean,
and in the air does not contain enough to cause corrosion of harmful
substances.
七、 Common failures and
troubleshooting methods
Failure phenomena Resolvent
25
Gritcomm Intelligent Technology (Shenzhen) Co., Ltd26
1The LCD screen does not display the concentrator after power on, the power indicator light is not bright
View the device N, L1 terminal pin, there is no 220V power input
2 Device connected to the cloud server failed
View terminal SIM card is inserted, the antenna is connected, the server IP address and port settings are correct.
3 Meter data acquisition failure View the RS-485 interface with the meter connection is properly connected
4Can't control and collect
the street lamp node
View whether the street lamp node
through the power line network