Greywater Reuse System for Toilet Flushing

download Greywater Reuse System for Toilet Flushing

of 10

Transcript of Greywater Reuse System for Toilet Flushing

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    1/10

    Greywater reuse systems for toilet ushing in multi-storeybuildings over ten years experience in Berlin

    Abstract

    Water reuse in Germany has gained in signicance in the last 10 years. Several greywater systems, built according to guidelinesintroduced in 1995, operate today with no public health risk. Two greywater treatment systems are described in this paper: a rotary

    biological contactor (RBC) built in 1989 for 70 persons, and a uidized-bed reactor for a one-family household built in 1995 as the

    biological stage for the treatment of household greywater for use in toilet ushing. Both systems were optimized in the following

    years with consideration of a minimal energy and maintenance demand. As numerous investigations have shown, biological

    treatment of the greywater is indispensable in order to guarantee a risk-free service water for reuse applications other than potable

    water. 2000 Elsevier Science Ltd. All rights reserved.

    Keywords: Greywater; Water reuse; Toilet ushing; Service water; Water quality; Biological treatment; Bacterial contamination

    1. Introduction

    1.1. Background

    The exploitation of surface water followed by ad-

    vanced treatment for drinking water supply oers no

    guarantee for continuous microbiologically and chemi-

    cally indisputable drinking water quality (Weller, 1993).

    A long list of household chemicals and drugs which are

    usually only partly biodegradable nd their way back to

    the consumer in drinking water after passing the mu-

    nicipal wastewater treatment plant (Stan & Ling-

    kerhagner, 1995; Seiler, Zuagg, Thomas, & Howcroft,

    1999).

    The substitution of drinking water with service water(dened as water with characteristics dierent than

    drinking water) used for purposes other than potable

    water, e.g., toilet ushing and garden irrigation, helps

    support the sustainability of valuable water resources.

    Furthermore, considerable amounts of added chemicals,

    in addition to sludge which arises during drinking water

    treatment, can be minimized. Service water made

    available from stormwater or greywater systems can be

    cost eective and with proper operation presents no

    hygienic risk or comfort loss for the consumer (Lucke,

    1998). On the other hand, the treatment and distribution

    of service water should not demand more energy and

    chemicals than that needed for conventional systems.

    Water from recycling systems should fulll four cri-

    teria: hygienic safety, aesthetics, environmental toler-

    ance and technical and economical feasibility (Nolde &

    Dott, 1991). In Germany, the classication of household

    wastewater into blackwater and greywater is almost

    unknown and both terms are not yet dened. Here

    ``Greywater'' means if not otherwise dened the low

    polluted wastewater from bathtubs, showers, hand-

    washing basins and washing machines excluding waste-water from the kitchen and the toilet ushing system.

    Some manufacturers of greywater systems assume a

    mechanical treatment of the greywater to be satisfactory

    (Hildebrand, 1999), whereas others claim a more ad-

    vanced treatment technology to be necessary (Zwerenz,

    1999; Zeisel, 1999). Some experts from the German

    Ministry of Environment (formerly German Federal

    Health Department) even prophesied plague and chol-

    era when water with non-drinking quality was provided

    for toilet ushing or other non-potable uses (Moll,

    1991). However, this attitude has changed (fbr, 1998)

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    2/10

    and the rst greywater recycling plants have proved

    their eciency and applicability in practice for almost 10

    years.

    In the meantime, about 76% of the questioned in-

    ternational experts within a Delphi study ``Water

    Technology in Year 2010'' consider it technically feasi-

    ble to use greywater in households by the year 2010 with

    no public health risks (Delphi, 1999).

    In the last 10 years several greywater plants with

    dierent technologies have been developed in Germany

    although only a few have been widely investigated and

    assessed. During an assessment of dierent plants, the

    use pattern as well as the reuse objective should be

    considered. A greywater plant at dierent sites may

    deliver dierent results.

    1.2. Greywater reuse guidelines

    Hygienic/microbiological quality standards, such asthose dened in the German ``Trinkwasserverordnung''

    do not exist for service water. Reuse criteria directed at

    health and environmental protection have been set at

    the beginning of these investigations on the rst grey-

    water pilot plants in Berlin, Germany in 1988. These

    criteria followed the EU-Guidelines for recreational

    waters (EU-Guidelines, 1975), complemented with ad-

    ditional microbiological parameters for the detection of

    P. aeruginosa, Salmonella sp., Legionella sp., Staphylo-

    coccus aureus and Candida albicans. Following success-

    ful operation of these systems and achievement of the set

    criteria, guidelines for service water reuse were then rstintroduced in Germany in 1995 on a local level by the

    Berlin Senate Department for Building and Housing

    (SenBauWohn, 1995). Parameters were dened among

    others for BOD7 ` 5 mg l1, total coliforms

    ` 100 ml1, faecal coliforms ` 10 ml1 and Pseudo-

    monas aeruginosa ` 1 ml1.

    In other countries, guidelines and standards for water

    reuse in buildings either do not exist or are being revised

    or expanded. The US Environmental Protection Agency

    (EPA) published in 1992 ``Guidelines for Water Reuse''

    which describe the treatment stages, water quality re-

    quirements and monitoring tools (EPA, 1992). Accord-

    ing to the EPA, reclaimed water used for toilet ushingshould undergo eventual ltration and disinfection. The

    euent should have no detectable faecal coliforms in

    100 ml of the treated water, a BOD5 of T 10 mg l1 and

    a residual Cl2 of P 1 mg l1, whereby Cl2 should be

    continuously monitored.

    In Tokyo, Japan, the reuse of treated wastewater has

    been highly promoted. A typical use of the reclaimed

    water is for toilet ushing with about 970 000 m3 year1.

    Reclaimed water criteria for use in toilet ushing were

    dened in the ``Report on reuse of treated wastewater''

    among others for total coliforms T 1000 ml1 and

    BOD T 20 mg l1 (Maeda, Nakada, Kawamoto, &Ikeda, 1995).

    1.3. Problems with greywater treatment systems

    The most technical problems were encountered in

    systems in which greywater was not suciently treated.

    These systems were merely aerated and mainly built for

    single-family dwellings for which a high maintenance

    was required. Advanced physical methods for water re-

    use, such as ultraltration and reverse osmosis, are very

    high energy demanding. On the other hand, using

    membrane ltration 0X2 lm which is less energy de-manding, eliminates microorganisms but hardly reduces

    the BOD. This will eventually result in slime formation in

    the distribution net and in the development of anaerobic

    conditions with smell emissions (unpublished data).

    Not all biological treatment systems which are al-

    ready well established to treat household sewage are

    suitable for greywater recycling since the regulatory re-quirements for these systems (COD: 150 mg l1; BOD5:

    40 mg l1) which lack hygiene requirements, are less

    strict than those required for greywater recycling sys-

    tems. As an example, a horizontal-ow planted soil lter

    (650 m2 for 200 persons) treating the greywater from

    kitchen and bathtub delivered unsatisfactory results

    with euent BOD5 concentrations of 1040 mg l1

    (Hegemann, 1993). In comparison, an intermittent,

    vertical-ow soil lter (20 m2 for 15 persons) working

    without the wastewater from the kitchen showed excel-

    lent results BOD7 ` 3 mg l1, even following doubling

    the number of connected persons to the system with a

    daily greywater ow in the soil lter of 7501500 l

    (Nolde & Dott, 1992). However, if a polishing pond, an

    integral part of a municipal wastewater treatment plant,

    is connected to the soil lter from which the service

    water is withdrawn, the pond will exhibit extensive algal

    growth during the summer months rendering the water

    unt for use (Dott, Nolde, & Christen, 1993). Similar to

    stormwater systems, light has also a negative eect on

    greywater systems and therefore, service water tanks

    should be protected against daylight.

    2. System concept and methodology

    2.1. Greywater system concept

    The following concept for greywater treatment has

    proved its eectiveness and suitability for over 10 years.

    Treatment follows a sedimentation stage, biological

    treatment, a clearing stage and eventual UV disinfection

    as shown in Fig. 1 (Nolde, 1996a).

    Funnel-shaped sedimentation tanks with automated

    sludge-removing devices proved most eective. Biologi-

    cal treatment can follow in a plant-covered, vertical-ow

    276

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    3/10

    soil lter or a multiple-stage rotary biological contactor

    (RBC) (alternatively a trickling lter), coupled to a

    clearing tank to remove the biomass. The treated water

    is eventually disinfected by UV before it is stored in theservice water tank. Distribution of service water is

    achieved with a booster pump.

    2.2. Case study

    The results from two dierent plants are presented in

    this paper. The rst greywater treatment plant (GW 1) is

    found in a 15 m2 basement (BerlinKreuzberg, Man-

    teuelstrae 41) treating the greywater from showers,

    bathtubs and hand-washing basins from 70 persons. At

    the beginning of these investigations in 1989, the pilot

    plant was not yet optimized and the biological stageconsisted of a two-stage RBC which was replaced in

    1997 with a four-stage RBC (Fig. 2) (Zeisel, 1999).

    The second greywater treatment plant (GW 2) is a

    two-stage uidized-bed reactor (BerlinWedding,

    Bornemannstrae 4) treating the greywater from shower

    and bathtub of a two-person household. The system has

    a total volume of 165 l (stage 1: 105 l; stage 2: 60 l) and

    placed above the toilet in the bathroom (Fig. 3). Cube-

    shaped polyurethane material was used as biolm car-

    rier in both stages.

    2.3. Sampling

    For all physicochemical parameters, samples were

    taken as 24-h quantity proportional mixed samples (GW

    1) or as random samples (GW 2), immediately stored

    without preservation at 4C and processed within 24 h.

    Inuent samples were taken from the sedimentation

    tank (or bathtub in GW 2), and the euent samples

    from the service water reservoir. For all microbiological

    parameters, random samples were taken, stored at 4C

    and processed immediately. Decimal dilution series were

    prepared in physiological saline (0.9%). Testing for

    faecal and total coliforms followed in triplicate serial

    dilutions and were quantied using the Most Probable

    Number (MPN) method (APHA, 1980). Settled sampleswere taken for all parameters.

    2.4. Physicochemical parameters

    UV transmission. UV transmission was determined in

    the settled samples according to DIN 38404-C3. The

    sample was measured in a Shimadzu UV-1201 pho-

    tometer (Kyoto, Japan) at a wavelength of 254 nm in 1

    cm cuvettes against Millipore water.

    Spectral absorption coecient (SAC 254 nm). The

    spectral absorption coecient was detected continuously

    with a UV-probe Type LXG 139 operating at 254 nm anddevice unit Type LXG 144 (Fa. Dr. Lange, Dusseldorf).

    Instead of ltration, the turbidity was compensated

    through a reference measurement at 550 nm. As several

    investigations have shown, the SAC 254 nm correlates

    very well rb 0X9 with the TOC measurements.Total organic carbon (TOC). The determination of

    TOC followed DIN 38409-H3. Measurements were

    made in TOCOR 100 (Fa. Maihak, Hamburg) run in the

    range between 2 and 30 ppm (thermal decomposition).

    Injection quantities varied between 40 and 140 ll de-

    pendent on sample concentration. The inorganic carbon

    portion of the sedimented samples was stripped o with

    synthetic air following acidication to a pH below 2. Allmeasurements were given as the arithmetic mean from a

    minimum of ve consecutive measurements of a sample.

    Chemical oxygen demand (COD). COD measure-

    ments of settled samples were carried out photometri-

    cally using a LASA Plus photometer and quick test

    cuvettes (LCK 414, 560 mg l1; LCK 314, 15150 mg

    l1; LCK 114, 1501000 mg l1; Fa. Dr. Lange,

    Dusseldorf). The coecients of variation were 1.99%

    (LCK 414), 1% (LCK 314) and 0.56% (LCK 114).

    Biological oxygen demand (BOD). BOD7 was deter-

    mined in the fresh settled sample following DIN 38409-Fig. 2. The four-stage greywater treatment system GW 1 in Berlin

    Kreuzberg (Foto: K. Zeisel).

    Fig. 1. Recommended concept for greywater treatment.

    277

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    4/10

    H51 based on dilution with allylthiourea (nal concen-

    tration in the sample was 1 mg l1). The oxygen con-

    centration was measured with a WTW Oximeter OXI 96

    and an oxygen probe EOT 196 (Fa. WTW, Weilheim).

    Due to technical reasons, BOD measurements were de-

    termined following seven days incubation instead of the

    usual ve days. It is expected that the BOD 7 value is

    either larger than or equal to the BOD5 for the samesample. For inoculated domestic polluted water in a

    moderate motion, a conversion factor of 1.17 is used

    1 mg l1 BOD5 1X17 mg l1 BOD7 (Imho & Im-

    ho, 1990). At rst approximation, this factor can also

    be used for greywater.

    2.5. Microbiological parameters

    Colony forming units (CFU). The determination of the

    number of the CFU followed in duplicate serial dilu-

    tions using Kochs pour plate method. The DEV-nutri-

    ent agar plates were incubated for 44 4 h at 20C and37C. Plates which showed between 30 and 300 colonies

    under an 8 magnication were evaluated and thearithmetic means determined.

    Faecal and total coliforms. Detection and enumeration

    of total coliforms followed in Fluorocult-Lauryl-sulfate

    broth using the MPN method. Tubes were incubated at

    37C for 48 h and those showing turbidity and gasformation were recorded as positive. For the detection

    of faecal coliforms, the medium was made alkaline fol-

    lowed by irradiation with a long-wave UV light to ex-

    amine uorescence. In the presence of a light-blue

    uorescence, an additional test was made to check for

    the formation of indole from tryptophan using Kovac's

    reagent. All tubes with turbidity, gas formation, uo-

    rescence and indole formation were considered positive

    for faecal coliforms.

    Contamination studies. Several investigations were

    made to study the survival of health relevant bacteria in

    Fig. 3. The two-stage greywater treatment system GW 2 in a bathroom in BerlinWedding.

    278

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    5/10

    greywater systems. Greywater was articially contami-

    nated with faeces from baby diapers and concentrations

    of faecal bacteria were measured in the greywater

    system.

    3. Results

    3.1. Greywater qualities

    The exact composition of greywater is primarily in-

    uenced by the user's behaviour, the implementation of

    water-saving measures and is dependent on which

    greywater sources have been used. Untreated greywater

    usually contains low nutrient concentrations (Table 1)

    which are below the regulatory requirements for

    euents of modern large sewage treatment plants inGermany Ntotal 18 mg l

    1Y Ptotal 1 mg l

    1.Although no toilet wastes were introduced into the

    above greywater systems, surprisingly high loads of total

    and faecal coliforms were measured over some periods

    (unpublished data). This has been related to the intro-

    duction of faecal bacteria into the system during baby

    washing and diaper changing as tenant questionnaires

    have shown.

    Service water used for toilet ushing can be won from

    the usually low-polluted greywater from showers,

    bathtubs and hand-washing basins. In GW 1, daily av-

    erage values of 3035 l/person were recorded for grey-

    water while in GW 2 only 1520 l/person were

    available daily (water-saving ttings and habits; ow:

    9 l min1).

    3.2. Biodegradability of household chemicals in the

    greywater system

    Fig. 4 shows the degradation of Fa soap, Birkin

    shampoo and oliveoil and spice soaps in GW 2. The

    organic load in the form of TOC and spectral absorp-

    tion coecient (SAC) was biodegradable within a few

    Table 1

    Dierent untreated greywater qualities measured in Berlin plants

    Parameter Unit GW 1 GW 2

    Mainly bath and shower Bath, shower and washing

    machine with baby diapers

    Mainly shower (9 l min1)

    TOD mg l1

    2695COD mg l1 100200 250430 113633

    BOD7 mg l1 50100 150250 70300

    Ntotal mg l1 510

    Ptotal mg l1 0.20.6

    Faecal coliforms ml1 101101 104106 101101

    Total coliforms ml1 102103 104106 101103

    Total counts (CFU) ml1 105106 106107 105106

    Fig. 4. Biodegradation of personal hygiene preparations in the rst stage of the uidized-bed reactor GW 2.

    279

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    6/10

    hours. The TOC as well as SAC (254 nm) of the service

    water were slightly higher than those of drinking water

    (TOC of Berlin drinking water lies between 3 and 4 mg

    l1; SAC between 8 and 10 m1).

    Fig. 5 shows that the greywater from washing ma-

    chines using Awalan washing liquid, which was intro-

    duced in GW 2 for experimental reasons, was almost

    ve times more polluted than the bath and shower

    water, and more time was needed for biodegradation

    (Fig. 4). The almost horizontal curve course at the end

    of the biodegradation experiments indicates the rest of

    the TOC to be only slowly or non-biodegradable.

    3.3. Investigations in a RBC (GW 1)

    As a result of the primary investigations on GW 1

    which ended in 1993 and in order to establish a modular

    greywater system with minimal maintenance, GW 1 was

    extensively automated in 1997 and replaced with a four-

    stage RBC keeping the same system volume while

    achieving a higher system stability especially during load

    uctuations. At least two hours per week were necessary

    for maintenance of the old two-stage GW 1, but this has

    been reduced to below 0.2 h.

    BOD7 concentrations of 50250 mg l1 have been

    measured in GW 1 inuent (Table 1) while euent

    concentrations were always below the 5 mg l1 control

    limit. Fig. 6 shows that the treated greywater had a

    higher UV transmission in all samples measured com-

    pared to the euent of the municipal wastewater treat-

    ment plant of BerlinRuhleben. A UV transmission

    close to that of the drinking water in Berlin was also

    measured.

    On the other hand, many service water samples did

    not fulll the drinking water microbiological standards

    of 100 CFU ml1 (37C) and 1000 CFU ml1 (20C) for

    bacterial total counts as can be seen in Fig. 7.

    Fig. 6. UV transmission of service water from GW 1 compared to Berlin s drinking water and treated municipal wastewater of BerlinRuhleben.

    Fig. 5. Biodegradation of washing-machine liquid in the rst stage of the uidized-bed reactor GW 2.

    280

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    7/10

    Fig. 8 shows that the measured bacterial concentra-

    tions in treated water were usually below the control

    values. Most values, mainly those of faecal coliforms

    and faecal streptococci, were even below the detection

    limit of 0.03 bacteria ml1. Only two out of 46 samples

    exceeded the limits for P. aeruginosa with 4.3 bacteria

    ml1 (Nolde, 1996a).

    3.4. Investigations in a uidized-bed reactor (GW 2)

    The investigations have shown that, a good service

    water quality can be achieved with a smaller greywater

    system (TOC: 48 mg l1; BOD7 ` 5 mg l1), even when

    the organic load is high as shown in Table 1. A number

    of the random samples from stage 1 has fullled the

    microbiological requirements for faecal coliforms in

    service water without further treatment (Fig. 9), whereas

    other samples lay above the limit value, especially when

    faecal material is introduced into the system from baby

    washing. In addition, the hygienic/microbiological pa-rameters of the Berlin service water quality requirements

    were realized following UV disinfection of the treated

    water. Signicantly lower coliform bacterial concentra-

    tions in GW 2 were rst attained following reduction of

    the ow rate in the UV unit (after October 98) as shown

    in Fig. 10. A calculated UV dose of 250400 J m2 was

    held constant. The requirements were even achieved

    following contamination of the system with faeces from

    baby diapers in December 1998.

    3.5. Behaviour of pathogenic microorganisms in greywater

    In addition to the behaviour of household chemicals

    in greywater systems, the presence as well as the survival

    of potentially pathogenic microorganisms is of much

    signicance for the assessment of greywater treatment

    plants and the exclusion of any health hazard connected

    with greywater reuse.Fig. 8. Concentrations of total and faecal coliforms in service water

    tank GW 1 compared to the control values of the quality guidelines.

    Fig. 7. CFU of samples taken from the service water tank in GW 1 at

    20C and 37C, compared to the German ``Trinkwasserverordnung''.

    Fig. 9. Concentrations of total and faecal coliforms in GW 2 (samples from the rst biological stage).

    281

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    8/10

    Since Salmonella (in 100 ml samples), Legionella (in

    10 ml samples), Staphylococcus aureus (in 1 ml samples)

    and Candida albicans (in 0.1 ml samples) were not de-tected in the treated greywater (GW 1), the water was

    articially contaminated with relevant pathogenic mi-

    croorganisms in order to investigate their behaviour.

    The concentrations of faecal coliforms in the greywater

    inuent (GW 1) that has been contaminated on a daily

    basis is shown in Fig. 11. After day 7, contamination

    was stopped and a reduction of the faecal coliforms was

    observed afterwards. However, samples taken from the

    toilet ushing system always showed values below the

    control limit for faecal coliforms and no regrowth of

    the bacteria was detectable in the system.

    Further contamination experiments in batch culturesshowed no increase in the number of pathogenic mi-

    croorganisms in greywater. Instead, a continuous death

    rate was observed with all tested microorganisms. Fig. 12 shows the survival of Salmonella sp. in articially con-

    taminated greywater in batch experiments. Very high

    start concentrations of 107 were reduced below the limit

    of detection within three weeks of incubation at room

    temperature in the dark.

    4. Discussion

    On the basis of the collected experience on dierent

    greywater systems over the past 10 years, it is clear thatan extensive biological treatment of the greywater is

    indispensable in order to avoid technical problems and

    public health risk as well as promotion of public ac-

    ceptance.

    Dierent quality requirements for non-potable water

    uses should be scientically justied and a risk assess-

    ment analysis is desirable in every case. With regard to

    sustainable water concepts, a lower energy and chemical

    demand than that needed for conventional systems

    should be achieved in service water systems. For large

    greywater systems working with a multistage RBC, the

    Fig. 11. Survival of faecal coliforms following continuous contami-

    nation of the greywater with faecal material over a period of 7 days.

    The vertical line shows the end of the contamination in GW 1.

    Fig. 12. Survival of Salmonella sp. in articially contaminated grey-water in batch cultures.

    Fig. 10. Concentrations of total and faecal coliforms in GW 2 following UV disinfection compared to the control values of the quality guidelines.

    282

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    9/10

    energy demand for greywater treatment, UV disinfec-

    tion and service water distribution was determined to be

    less than 1.5 kWh m3 (Nolde, 1996b). Low energy and

    maintenance costs can thus be a challenge especially for

    smaller greywater plants.

    The use of chemical disinfectants (e.g., chlorine

    compounds) in greywater systems should be avoided

    since treated greywater can be satisfactorily disinfected

    with a UV dose ranging between 250 and 400 J m2.

    Several investigations have also shown that common

    personal hygiene preparations and household-cleaning

    chemicals as well as the occasional use of medicinal baths,

    or even a contamination of the greywater with faeces and

    pathogenic bacteria, cause no problems in properly

    functioning greywater systems working with dierent

    carrier material (e.g., sand, polyethylene, and polyure-

    thane) for biolm xation, followed by an eventual UV

    disinfection (Nolde & Dott, 1992; Mehlhart, 1999).

    From the author's point of view it is today indispens-

    able, that every greywater system be tested once underseveral dierent conditions (e.g., faecal contamination,

    application of household chemicals) before operation.

    Following installation, a qualied inspection should be

    made in which a full compliance to DIN or other stan-

    dard-installation regulations takes place. In order to

    avoid cross connections with the drinking water network,

    it is recommended that the service water is dyed once prior

    to operation. The operation of non-registered and un-

    tested greywater systems is connected to a potential hy-

    gienic risk to the user and the drinking water network.

    At this point in time, it is dicult to give general

    recommendations regarding planning and design of a

    greywater plant, since the user behaviour, volume and

    concentration of greywater can vary widely as for ex-

    ample in a one-family household and in a hotel. The

    greywater systems that have been realized until now

    with extensive treatment of the greywater were mainly

    prototypes or special productions, whereby the total

    costs were decisively dependent on site conditions. As

    such it is still dicult to give precise details on the in-

    vestment costs of such systems, to which a second pipe

    system and additional space are also needed. Dependent

    on system size, the specic investment costs beginning

    with water treatment and ending with the service water

    pump would at a rst approximation be between 300 for large systems and up to 1000 for small ones per

    connected person. With drinking water and wastewater

    prices in Germany of 5 m3, it can be ensured that

    such an investment will pay for itself taking into con-

    sideration the operation and maintenance costs.

    5. Conclusions

    Greywater processing has proved to be technically

    feasible. There are enough positive examples which

    verify that the total water for toilet ushing (about 15 to

    55 l/person/day) can be substituted with service water

    without a hygienic risk or comfort loss.

    The Berlin quality requirements for service water

    have proved to be eective for the reuse of treated

    greywater for toilet ushing. Regulatory requirements

    for other reuse purposes, such as in washing machines,

    are still desirable. These requirements should be in every

    case use-oriented and based on a risk assessment.

    It should be possible in the future to have a dual

    water system in households with two water qualities.

    The rst a high quality drinking water originating pri-

    marily from natural water resources, and a second wa-

    ter quality for all other uses. This should bring with it

    an environmental relief on both the water and energy

    sectors.

    Acknowledgements

    This research was mainly supported by the Berlin

    Senate Department for Building and Housing. Dipl.

    Ing. Jochen Zeisel from Sanitarsystemtechnik, Berlin,

    and Dipl.Ing. Rudi Buttner from Fa. Lokus, Berlin, for

    greywater system planning and design. Hans Grohe for

    supporting investigations on the uidized-bed reactor.

    References

    American Public Health Association. (1980). Standard methods for the

    examination of water and wastewater (15th ed.). New York:

    American Public Health Association.

    Delphi (1999). Delphi-Study Watertechnology in the year 2010.

    Ministry of the Environment, Hessen, Referat Oentlichkeitsarbeit,

    Postfach 3109, 65021 Wiesbaden.

    Dott, W., Nolde, E., & Christen, S. (1993). Teilprojekt D Hygiene. In

    W. Hegemann et al. (Eds.), Integriertes Wasserkonzept in Berlin-

    Kreuzberg, Block 6. Projektdokumentation und Ergebnisse der

    Forschungsphase II (19901993). Erstellt im Auftrag der Senats-

    verwaltung fur Bau- und Wohnungswesen, Berlin (Unpublished

    data).

    EU-Guidelines (1975). Richtlinie des Rates der Europaischen Gemein-

    schaft vom 8.12.1975 uber die Qualitat der Badegewasser (76/160/

    EWG-Amtsblatt der EG vom 5.02.1976-L31/1).

    fbr (1998). Hygienische Aspekte der Regenwassernutzung Dokumen-

    tation des fbr-Fachsymposiums in Fulda. Fachvereinigung Be-

    triebs- und Regenwassernutzung e.V. (fbr), Darmstadt.

    Hegemann, W. (1993). Teilprojekt C2-Abwasserreinigung. In W.

    Hegemann et al. (Eds.), Integriertes Wasserkonzept in Berlin-

    Kreuzberg, Block 6. Projektdokumentation und Ergebnisse der

    Forschungsphase II (19901993). Erstellt im Auftrag der Senats-

    verwaltung fur Bau- und Wohnungswesen, Berlin (Unpublished

    data).

    Hildebrand, R. (1999). Sedimentationsanlage Hildebrand. In Grau-

    wasser Recycling, Schriftenreihe fbr 5 (1999), (pp. 5160). Fach-

    tagung der fbr 1999, Fachvereinigung Betriebs- und

    Regenwassernutzung e.V. (Hrsg.), Darmstadt.

    Imho, K. R., & Imho, K. (1990). Taschenbuch der Stadtentwasse-

    rung. Wien: R Oldenbourg Verlag Munchen.

    283

  • 7/29/2019 Greywater Reuse System for Toilet Flushing

    10/10

    Lucke, F. -K. (1998). Betriebswasser in Trinkwasserqualitat. In

    Innovation Betriebs- und Regenwassernutzung, Schriftenreihe fbr 3

    (1998), (pp. 3164). Fachtagung der fbr 1998, Fachvereinigung

    Betriebs- und Regenwassernutzung e.V. (Hrsg.), Darmstadt.

    Maeda, M., Nakada, K., Kawamoto, K., & Ikeda, M. (1995). Area-

    wide Use of Reclaimed Water in Tokyo, Japan. In A. Angelakis,

    T. Asano, E. Diamadopoulos, & G. Tschobanoglous (Eds.),

    Proceedings of the Second International Symposium on Wastewater

    Reclamation and Reuse (pp. 5562). October 1720, 1995, Iraklio,Crete, Greece (Symposium Reprint Book 1).

    Mehlhart, G. (1999). Internationale Entwicklungen zum Grauwasser-

    Recycling. In Grauwasser Recycling, Schriftenreihe fbr 5 (1999),

    (pp. 155172). Fachtagung der fbr 1999, Fachvereinigung Betriebs-

    und Regenwassernutzung e.V. (Hrsg.), Darmstadt.

    Moll, H. -G. (1991). Zu treen: Vorkehrungen gegen Typhus und

    Cholera Dach- und (Regen-) wassernutzung im Haushalt? Sanitar

    und Heizungstechnik, 6, 461466.

    Nolde, E., & Dott, W. (1991). Verhalten von hygienisch relevanten

    Bakterien und Pilzen im Grauwasser-Einuss der UV-Desinfektion

    und Wiederverkeimung. gwf Wasser Abwasser, 132(3), 108114.

    Nolde, E., & Dott, W. (1992). Experimenteller Wohnungs- und

    Stadtebau Forschungskonzept Block 103 Grauwasserprojekte in

    Berlin-Kreuzberg. Erstellt im Auftrag der Senatsverwaltung fur

    Bau- und Wohnungswesen, Berlin (Unpublished data).Nolde, E. (1996a). Greywater Reuse in Households-Experience from

    Germany. In J. Staudenmann, A. Schonborn, & C. Etnier (Eds.),

    Proceedings of the Second International Conference on Ecological

    Engineering for Wastewater Treatment. Environmental Research

    Forum Volumes 56 (1996). In Recycling the ResourceEcological

    Engineering for Wastewater Treatment (pp. 5564), September 18

    22, 1995, Wadenswil, Zurich, Switzerland.

    Nolde, E. (1996b). Wasserrecycling in einem 4-Sterne-Hotel. wwt, 6,

    3941.

    Seiler, R. L., Zaugg, S. D., Thomas, J. M., & Howcroft, D. L. (1999).

    Caeine and Pharmaceuticals as Indicators of Wastewater Con-

    tamination in Wells. Ground Water, 37(3), 405410.

    Stan, H. -J, & Linkerhagner, M. (1995). Identizierung von 2-(4-

    chlorphenoxy)-2-methylpropinsaure im Grundwasser mittelsKapillar-Gaschromatographie mit Atomemissionsdetektion und

    Massenspektrometrie. Vom Wasser, 79, 8588.

    SenBauWohn. (1995). Merkblatt Betriebswassernutzung in Gebauden,

    Senatsverwaltung fur Bau- und Wohungswesen, Wurttembergische

    Strae 610, 10707 Berlin.

    U.S. Environmental Protection Agency. (1992). Guidelines for Water

    Reuse. EPA/625/R-92/004, U.S. Environmental Protection

    Agency, Center for Environmental Research Information, Cincin-

    nati, Ohio.

    Weller, U. (1993). Aachener mussen auch weiterhin Trinkwasser

    abkochen, TAZ Nr. 4133, 32, 9 October 1993.

    Zeisel, J. (1999). Tauchtropfkorperanlagen im Grauwasser-Recycling,

    Fa. Lokus GmbH. In Grauwasser Recycling, Schriftenreihe fbr 5

    (pp. 97130). Fachtagung der fbr 1999, Fachvereinigung Betriebs-

    und Regenwassernutzung e.V. (Hrsg.), Darmstadt.Zwerenz, A. (1999). Investition in die Zukunft-die Duschwasser-

    Recycling-Anlage von Hansgrohe. In Grauwasser Recycling,

    Schriftenreihe fbr 5 (pp. 6783). Fachtagung der fbr 1999,

    Fachvereinigung Betriebs- und Regenwassernutzung e.V. (Hrsg.),

    Darmstadt.

    284