GOD-A-101 - GROUND & FIRST FLOOR PLANS€¦ · GROUND & FIRST FLOOR PLANS 1/4" = 1'-0" GOD-A-101 -...

1
NURSING STATION 6'-10" X 9'-6" HYGIENIST 8'-10" x 11'-11" MALE WC 5'-11" X 3'-8" LUNCH ROOM 10'-6" X 7'-0" DOCTOR'S OFFICE 01 10'-6" X 13'-2" DENTIST OFFICE 14'-5" X 13'-5" WAITING AREA 9'-8" X 14'-9" JAN CLOSET 3'-9" X 4'-11" 43'-0" [13104] 3'-11 1 4 " [1200] 39'-0 3 4 " [11904] 53'-5 3 4" [16302] 44'-3 3 4" [13503] 9'-2 1 4" [2798] 37'-1" [11303] RECEPTION 10'-6 X 11'-6" PLANTER PLANTER SHELVES MICROWAVE JAN CLOSET 5'-7.5" X 4'-6.5" FOYER 5'-9" X 12'-2" FEMALE WC 5'-11" X 3'-8" EXAMINATION TABLE EXAMINATION TABLE LOBBY 9'-8" X 6'-7" DOCTOR'S OFFICE 02 9'-8" X 12'-4" RECEPTION 8'-10" X 9'-10" LUNCH ROOM 8'-10" X 6'-5" MICROWAVE WAITING AREA 10'-6" X 26'-11" TABLE TABLE TABLE CRADENZA STORAGE UNIT STORAGE UNIT MALE WC 5'-11" X 3'-8" FEMALE WC 5'-11" X 3'-8" CORRIDOR 3'-9" X 10'-10" CORRIDOR 4'-11" X 13'-2" Extract fan in ceiling with minimum turn over rate of 750 cubic ft. per hour. Extract fan in ceiling with minimum turn over rate of 750 cubic ft. per hour. 5'-11" [1802] 24'-4 3 4" [7438] 30'-10" [9400] UP Proposed stairs of non-combustible Conc. construction. UP 1:12 RAMP UP Proposed disabled access ramp in compliance with Approved Document "K" 0'-0" A.F.L 0'-0" A.F.L LUNCH ROOM 8'-10" x 6'-7" 24'-5" [7442] 30'-10" [9400] STORAGE 6'-9"x4'-7" WAITING AREA 20'-10" X 7'-10" RECEPTION 9'-11" x 8'-2" DOCTOR'S OFFICE 9'-10" x 11'-6" DOCTOR'S OFFICE 01 8'-10" x 15'-5" OFFICE 9'-6" x 6'-2" MALE WC 5'-11" X 3'-8" FEMALE WC 5'-11" X 3'-8" LUNCH ROOM 10'-6" X 7'-0" MICROWAVE MICROWAVE NURSING STATION 6'-5" X 11'-6" RECEPTION 10'-6 X 11'-6" STORAGE 6'-8"x4'-7" CRADENZA CRADENZA MALE WC 5'-11" X 3'-8" FEMALE WC 5'-11" X 3'-8" CORRIDOR 3'-3" X 8'-8" CORRIDOR 16'-0" X 4'-0" WAITING AREA 27'-11" X 9'-6" CORRIDOR 4'-2" X 9'-10" CORRIDOR 4'-3" X 8'-0" VESTIBULE 10'-6" X 4'-7" 43'-0" [13104] 3'-11 1 4 " [1200] 39'-0 3 4 " [11904] 56'-2" [17117] 44'-3 3 4" [13503] 9'-2 1 4" [2798] 37'-1" [11303] 5'-11" [1802] HYGIENIST 9'-8" x 12'-2" DENTIST OFFICE 14'-5" X 11'-1" 2'-8" [815] 10 3 4" [275] DN Proposed stairs of non-combustible Conc. construction. 9'-1" A.F.L 9'-1" A.F.L 9'-1" A.F.L 5'-3" A.F.L LANDING Extract fan in ceiling with minimum turn over rate of 750 cubic ft. per hour. Extract fan in ceiling with minimum turn over rate of 750 cubic ft. per hour. POROPOSED GROUND FLOOR PLAN SCALE - 1/4" = 1'-0" 01 PROPOSED FIRST FLOOR PLAN SCALE - 1/4" = 1'-0" 02 CLIENT: DATE: STATUS: GENERAL NOTES: DO NOT SCALE, USE FIGURED DIMENSIONS ONLY. ALL DIMENSIONS & LEVELS IN IMPERIAL & METRIC. ALL DIMENSIONS TO BE CHECKED ON SITE. THIS DRAWING TO BE READ IN CONJUNCTION WITH ALL RELEVANT DRAWINGS & SPECIFICATIONS. IN THE EVENT OF ANY DISCREPANCIES BETWEEN DRAWINGS INFORM THE ARCHITECT IMMEDIATELY COPYRIGHT THIS DRAWING IS NOT TO BE REPRODUCED OR DISTRIBUTED WITHOUT PERMISSION. DRAWING NO: DRAWING: REV. CHECKED BY: SCALES: DRAWING DRAWN BY: DATE: PROJECT CODE: DESCRIPTION. REVISION DATE LEGEND: PROJECT Change of use Ventnor Gardens No.1, Dayrells Road, Christ Church 2016/06/05 SA 2016/06/05 BT DRAFT GODSON GROUND & FIRST FLOOR PLANS 1/4" = 1'-0" GOD-A-101 - N/A N BUILDING GROUND FLOOR AREA: 2222 SQ.FT TOTAL BUILDING FLOOR AREA: 4348 SQ.FT TOTAL ROOF AREA: 2509 SQ.FT Denotes full height fire rated type-x fire code gypsum & metal stud party wall Denotes new none combustible concrete masonry wall construction. Denotes existing none combustible concrete masonry wall construction. Denotes new composite none combustible concrete masonry wall with metal furring construction. BUILDING FIRST FLOOR AREA: 2126 SQ.FT NOTES: x The purpose of this application is for a change of use from a Day Care & apartment building to a medical office rental complex consisting of 4 rental units. x All existing construction is comprised of none-combustible concrete masonry unit envelopes & partitions & concrete floor slabs. x All new construction shall be a combination of none-combustible concrete masonry unit block work and fire rated full height metal stud partition & gypsum board finish. x All new windows shall be 100% ventilating casement or awning style. x Offices to be air conditioned via mini-split A/C units.

Transcript of GOD-A-101 - GROUND & FIRST FLOOR PLANS€¦ · GROUND & FIRST FLOOR PLANS 1/4" = 1'-0" GOD-A-101 -...

Page 1: GOD-A-101 - GROUND & FIRST FLOOR PLANS€¦ · GROUND & FIRST FLOOR PLANS 1/4" = 1'-0" GOD-A-101 - N/A N BUILDING GROUND FLOOR AREA: 2222 SQ.FT TOTAL BUILDING FLOOR AREA: 4348 SQ.FT

NURSING

STATION

6'-10" X 9'-6"

HYGIENIST

8'-10" x 11'-11"

MALE WC

5'-11" X 3'-8"

LUNCH ROOM

10'-6" X 7'-0"

DOCTOR'S

OFFICE 01

10'-6" X 13'-2"

DENTIST

OFFICE

14'-5" X 13'-5"

WAITING AREA

9'-8" X 14'-9"

JAN CLOSET

3'-9" X 4'-11"

43'-0"

[13104]

3'-11

1

4

"

[1200]

39'-0

3

4

"

[11904]

53

'-5

3

4

"

[16302]

44

'-3

3

4

"

[13503]

9'-2

1

4

"

[2798]

37'-1"

[11303]

RECEPTION

10'-6 X 11'-6"

PLANTERPLANTER

SH

EL

VE

S

MICROWAVE

JAN CLOSET

5'-7.5" X 4'-6.5"

FOYER

5'-9" X 12'-2"

FEMALE WC

5'-11" X 3'-8"

EXAMINATION

TABLE

EXAMINATION

TABLE

LOBBY

9'-8" X 6'-7"

DOCTOR'S

OFFICE 02

9'-8" X 12'-4"

RECEPTION

8'-10" X 9'-10"

LUNCH ROOM

8'-10" X 6'-5"

MICROWAVE

WAITING AREA

10'-6" X 26'-11"

TA

BL

E

TA

BL

E

TA

BL

E

CR

AD

EN

ZA

ST

OR

AG

E U

NIT

ST

OR

AG

E U

NIT

MALE WC

5'-11" X 3'-8"

FEMALE WC

5'-11" X 3'-8"

CORRIDOR

3'-9" X

10'-10"

CORRIDOR

4'-11" X

13'-2"

Extract fan in ceiling with

minimum turn over rate of

750 cubic ft. per hour.

Extract fan in ceiling with

minimum turn over rate of

750 cubic ft. per hour.

5'-11"

[1802]

24

'-4

3

4

"

[7438]

30

'-1

0"

[9400]

UP

Proposed stairs of

non-combustible

Conc. construction.

UP

1:12 RAMP UP

Proposed disabled access

ramp in compliance with

Approved Document "K"

0'-0" A.F.L 0'-0" A.F.L

LUNCH ROOM

8'-10" x 6'-7"

24'-5

"

[7442]

30

'-1

0"

[9400]

STORAGE

6'-9"x4'-7"

WAITING AREA

20'-10" X 7'-10"

RECEPTION

9'-11" x 8'-2"

DOCTOR'S

OFFICE

9'-10" x 11'-6"

DOCTOR'S

OFFICE 01

8'-10" x 15'-5"

OFFICE

9'-6" x 6'-2"

MALE WC

5'-11" X 3'-8"

FEMALE WC

5'-11" X 3'-8"

LUNCH ROOM

10'-6" X 7'-0"

MICROWAVE

MICROWAVE

NURSING

STATION

6'-5" X 11'-6"

RECEPTION

10'-6 X 11'-6"

STORAGE

6'-8"x4'-7"

CRADENZA

CRADENZA

MALE WC

5'-11" X 3'-8"

FEMALE WC

5'-11" X 3'-8"

CORRIDOR

3'-3" X 8'-8"

CORRIDOR

16'-0" X 4'-0"

WAITING AREA

27'-11" X 9'-6"

CORRIDOR

4'-2" X 9'-10"

CORRIDOR

4'-3" X 8'-0"

VESTIBULE

10'-6" X 4'-7"

43'-0"

[13104]

3'-11

1

4

"

[1200]

39'-0

3

4

"

[11904]

56

'-2

"

[17117]

44

'-3

3

4

"

[13503]

9'-2

1

4"

[2798]

37'-1"

[11303]

5'-11"

[1802]

HYGIENIST

9'-8" x 12'-2"

DENTIST

OFFICE

14'-5" X 11'-1"

2'-8

"

[815]

10

3

4"

[275]

DN

Proposed stairs of

non-combustible

Conc. construction.

9'-1" A.F.L

9'-1" A.F.L

9'-1" A.F.L

5'-3" A.F.L

LANDING

Extract fan in ceiling with

minimum turn over rate of

750 cubic ft. per hour.

Extract fan in ceiling with

minimum turn over rate of

750 cubic ft. per hour.

POROPOSED GROUND FLOOR PLAN

SCALE - 1/4" = 1'-0"

01

PROPOSED FIRST FLOOR PLAN

SCALE - 1/4" = 1'-0"

02

CLIENT:

DATE:

STATUS:

GENERAL NOTES:

DO NOT SCALE, USE FIGURED DIMENSIONS ONLY.

ALL DIMENSIONS & LEVELS IN IMPERIAL & METRIC.

ALL DIMENSIONS TO BE CHECKED ON SITE.

THIS DRAWING TO BE READ IN CONJUNCTION WITH ALL RELEVANT

DRAWINGS & SPECIFICATIONS.

IN THE EVENT OF ANY DISCREPANCIES BETWEEN DRAWINGS

INFORM THE ARCHITECT IMMEDIATELY

© COPYRIGHT THIS DRAWING IS NOT TO BE REPRODUCED OR

DISTRIBUTED WITHOUT PERMISSION.

DRAWING NO:

DRAWING:

REV.

CHECKED BY:

SCALES:

DRAWING

DRAWN BY: DATE:

PROJECT CODE:

DESCRIPTION.REVISION DATE

LEGEND:

PROJECT

Change of use

Ventnor Gardens No.1,

Dayrells Road,

Christ Church

2016/06/05SA2016/06/05BT

DRAFT

GODSON

GROUND & FIRST FLOOR PLANS

1/4" = 1'-0"

GOD-A-101

-

N/A

N

BUILDING GROUND FLOOR AREA: 2222 SQ.FT

TOTAL BUILDING FLOOR AREA: 4348 SQ.FT

TOTAL ROOF AREA: 2509 SQ.FT

Denotes full height fire

rated type-x fire code

gypsum & metal stud

party wall

Denotes new none

combustible concrete

masonry wall construction.

Denotes existing none

combustible concrete

masonry wall construction.

Denotes new composite

none combustible concrete

masonry wall with metal

furring construction.

BUILDING FIRST FLOOR AREA: 2126 SQ.FT

NOTES:

The purpose of this application is for a change of use from a Day Care & apartment

building to a medical office rental complex consisting of 4 rental units.

All existing construction is comprised of none-combustible concrete masonry unit

envelopes & partitions & concrete floor slabs.

All new construction shall be a combination of none-combustible concrete masonry

unit block work and fire rated full height metal stud partition & gypsum board finish.

All new windows shall be 100% ventilating casement or awning style.

Offices to be air conditioned via mini-split A/C units.