Glove Spec
Transcript of Glove Spec
-
8/12/2019 Glove Spec
1/2
0333
ELECTRICAL INSULATING GLOVES
INSTRUCTIONS FOR USE
Range Available: sizes and codes
Size 8 9 10 11
Class 00 RE00360/08 RE00360/09 RE00360/10 RE00360/11
Class 0 RE0360/08 RE0360/09 RE0360/10 RE0360/11
Class 1 RE1360/08 RE1360/09 RE1360/10 RE1360/11
Class 2 RE2360/08 RE2360/09 RE2360/10 RE2360/11
Class 3 RE3360/08 RE3360/09 RE3360/10 RE3360/11
EC type examination carried out by: APAVE - 13-17 rue Salneuve 75854 Paris Cedex 17 (France).
Notified Body number 0077Manufacturer certified ISO-9001 by : AFAQ - 116 avenue A.Briand - 92224 Bagneux Cedex (France).
Notified body number 0033
STORAGE & TRANSPORT:
Keep away from direct heat or light sources and store in temperatures between 10 and 21c, humidity 60+/-10%.Do not crush or fold the gloves. The gloves should be kept in their original packaging or in an electricians bagwhen not in use.
BEFORE USE:
Inflate the gloves with air in order to detect potential faults. Carry out a thorough visual inspection.
PRECAUTIONS:
Avoid contact with petrols, oils, grease, acids or any corrosive products.Do not use the gloves if wet.
CARE:
To get the best service from these gloves ensure that after use all contaminant is removedWash the gloves with soap and water. Do not dry at temperatures above 65c
CAUTION:
The life of these gloves, whether used or in storage is limited.The standard EN60903:2003 recommends a periodic inspection, electric retesting or periodic replacement
THESE GLOVES ARE DESIGNED TO BE USED
EXCLUSIVELY FOR ELECTRICAL PURPOSE
You are advised to retain this packaging for future reference
The life of gloves when they are stored or used is limited. The standards EN60903:2003and IEC60903:2002 indicate in Annex E that : No
gloves of classes 1,2 & 3, not even those held in storage, should be used unless they have been tested within a maximum period of six
months.The tests consist of air inflation to check for air leaks, a visual inspection while pressurised, and then a routine dielectric test.
For Class 00 and Class 0, a check for air leaks and visual inspection may be considered adequate. However a routine dielectric test may beperformed at the users request.
All gloves have a straight cuff.
Also avai lable : leather over gloves grey leather gloves w ith a c hrom e leather safety c uff and nylon
tension strap on the back of the hand to adjust the f i t . Designed to be worn over the electr ic ian gloves to
protect i t from mechanical r isks.
Regeltex-2005
BM Polyco Ltd, Great CambridgeIndustrial Estate,Lincoln Road, Enfield, EN1 1SH. UK.www.superglove.co.uk
-
8/12/2019 Glove Spec
2/2
PROTECTION LEVELS & ELECTRICAL REQUIREMENTS:
Routine test: The proof test voltage is applied for one minute. During the test, no puncture can occur. The leakagecurrent (reduced by 2mA) can not exceed the value indicated in the table below.Sampling test: After conditioning for 16 hours in water for moisture absorption, the proof test voltage is applied forthree minutes, then the withstand voltage is reached and immediately reduced. The test is considered a successif no puncture occurs and if the leakage current does not exceed the values specified in the table below.The sampling test (without moisture absorption) is also done after:ageing, ozone conditioning, Oil conditioning, acid conditioning and very low temperature conditioning
Class
Test Voltage
Working Voltage
Length
Sizes
00
2500v
500v
360mm
8,9,10,11
0
5000v
1000v
360mm
8,9,10,11
1
10000v
7500v
360mm
8,9,10,11
2
20000v
17000v
360mm
8,9,10,11
3
30000v
26500v
360mm
8,9,10,11
Max proof testcurrent (mA rms)
14 14 16 18 20
Withstand testvoltage (kV rms)
5000v 10000v 20000v 30000v 40000v
GLOVE MARKING - INFORMATION
CLASS 00/AZC
XX / YY
LOT XXXX 0333
EN 60903:2003 IEC 60903:2002
SIZE 10
REG
MECHANICAL REQUIREMENTS:
Minimum
value
Ageing
(168hrs @ 70c)
Immersion in 32 B
Sulphuric acid for 8hrs
Immersion in liquid 102 at
70c for 24hrs
Tensile strength 16MPa
Elongation at break 600% > 80% of unaged values
Not less than 75% of theinitial value
Not less than 75% of theinitial value
Tension set 15% max 15% max
Puncture resistance 18N/mm
CATEGORIES:
A : Acid H : Oil Z : Ozone C : very low temperature R = A + H + Z
Marking of periodic Inspection date
Mandatory
Identification of Manufacturer
Standards references
Marking of datehen first used
Size
Class category
Month and year of production