GFCI Personnel Safety Devices Catalog - Barr-Thorp Electric

11

Transcript of GFCI Personnel Safety Devices Catalog - Barr-Thorp Electric

SmartLockPRO™ GFCI Features

F2

SmartLockPRO™GFCI Features

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Leviton SmartLockPRO™ iconensures improved GFCI

product design.

Lockout action blocks the “RESET”button if GFCI protection has been

compromised.

UL Standard 943 Class A (GFCI) & 498 (Receptacles)

CSA Certified (File #057)Meets July 28, 2006 UL Requirements

Triple combinationterminal screws.

“Surge hardened” electronicsoffer superior resistance tosurges and overvoltages.

LED power indicator light helpsdiagnose improper wiring and,when illuminated, offers visualconfirmation that power is available.

Heavy duty double wipe for15 Amp contacts and triplewipe for 20 Amp contacts

Patented lockout feature prevents“RESET” if GFCI is not functioningproperly or miswired due to reversal ofline and load leads.

Thick-walled, impact-resistantthermoplastic nylon cover andbody withstands abuse

Silver alloy contacts for reliablemake/break switching.

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL 943 CSA NOMWD1&WD6 C-73 Listed Class A & 498

U U #E48380 U #LR-57811 #057

Eight back-wire holes

(two per terminal) and

back-wire ground.

Provisions for back- or side-wiring.

COMPONENT DESCRIPTION

Face Nylon

Back Polycarbonate

Line Contacts Brass

Terminal Screws Brass #8-32

Grounding Screw Brass #8-32

Yoke Zinc Steel

Clamp Nuts Steel

Internal Contacts Silver Alloy

Leviton SmartLockPRO™ and The New 2006UL943 GFCI Safety Standards

Line-Load Reversal IndicationNew UL 2006 Standard:• If a miswiring (line-load reversal) occurs during installation,

the GFCI must not be capable of supplying power to eitherthe GFCI’s face or to feed-through terminals.

“End-of-Life” IndicationNew UL 2006 Standard:• GFCIs are required to provide a visual and/or audible

indication OR be able to render themselves incapable ofdelivering power when they no longer offer ground fault protection based on a failure to pass their internal test.

For additional details on these new requirements, see page F10.

Dual function LED offers indication

of line/load reversal & power availability.

7599-W

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

15A 125V & 20A 125V

F3

Hospita

l & Com

mercial

Grade

GFCI De

vices

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Hospital & Commercial Grade, GFCI’s

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

Silver, neutral

15A 125V, NEMA 5-15R; 20A 125V Feed-Through

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 2kA 1500V

perUL 498

80ºC max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC appl.

per UL 498

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35ºC to 65ºC

Ratingspermanently

marked on device

#14 - #12 AWG solid or stranded

copper wire

7899-HG SERIES 7599 SERIES 7590 SERIES 7299 SERIES

4.2

1 (1

06

.93

mm

)

3.7

0 (9

3.9

8 m

m)

1.31

0.94

3.8

1 (

96

.77

mm

)

3.2

8 (

83

.81

mm

)

2.7

4 (6

9.6

0 m

m)2

.62

(6

6.5

5 m

m)

1.19

0.2

9 (

7.3

7 m

m)

(23.88 mm)

(33.27 mm)(30.23 mm)

7590-W7599-I

Back & Side Wired

TRIP LEVEL

5±1 mA

7599-LI

20A 125V, NEMA 5-20R at Receptacle & Feed-Through

7899-HGR

3.8

1 (

96.7

7 m

m)

3.2

8 (

83.8

1 m

m)2

.74 (6

9.6

0 m

m)2

.62 (

66.5

5 m

m)

1.19

0.2

9 (

7.3

7 m

m)

4.2

1 (1

06.9

3 m

m)

3.7

0 (9

3.9

8 m

m)

0.94

1.31

(30.23 mm)

(23.88 mm)

(33.27 mm)1.7 (43.2 mm)

1.12 (28 mm)

2.7

(6

8.6

mm

)

4.2

1 (

10

6.9

3 m

m)

CLASS A

LEVITON

GF

CI

CL

AS

S

20 A

MP

125V

1.53 (38.9 mm) 1.7 (43.2 mm)

1.12 (28 mm)

2.7

(6

8.6

mm

)

4.2

1 (

10

6.9

3 m

m)

GF

CI

1.53 (38.9 mm)

SHALLOW WALLBOX

COLOR EXTENDERFOR GFCI's

Brown 6197

Ivory 6197-IWhite 6179-W

7299-A

15A 125V, NEMA 5-15R;20A 125V Feed-Through

#LR-57811 #057–

MISC. MOTOR CONTROL RATING

15A-1875W

20A-2500W

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOM

WD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

U U U

FACE GFCI COMBO DEVICE RECEPTACLE

COLOR & SINGLE-POLE SWITCH

Meets 2006 UL Requirements

Ivory 7299-I

White 7299-WAlmond 7299-A

GFCI GFCI GFCI GFCIHOSPITAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE

FACE SMARTLOCKPRO™ SMARTLOCKPRO™ SMARTLOCKPRO™ BLANK FACECOLOR DUPLEX w/ LED DUPLEX w/ LED DUPLEX w/ LED S-P SWITCH

w/ 6" Leads. 1.5HP@120V ACMeets 2006 Meets 2006 Meets 2006 Meets 2006

UL Requirements UL Requirements UL Requirements UL Requirements

Brown 7599-HG 7599 – –Ivory 7599-HGI 7599-I 7599-LI 7590-IWhite 7599-HGW 7599-W 7599-LW 7590-WGray 7599-HGG 7599-G – –Red 7599-HGR 7599-R – –Black – 7599-E – 7590-EAlmond 7599-HGA 7599-A – 7590-ALt. Almond 7599-HGT 7599-T – 7590-T

Brown 7899-HG 7899 – –Ivory 7899-HGI 7899-I 7899-LI –White 7899-HGW 7899-W 7899-LW –Gray 7899-HGG 7899-G – –Red 7899-HGR – – –Black 7899-HGE 7899-E – –Almond 7899-HGA 7899-A – –Lt. Almond 7899-HGT 7899-T – –

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

15A 125V & 20A 125V

F4

Commercial Grade GFCI Devices

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Commercial Grade, GFCI’s

GFCI-Protected Fluorescent Work Light w/Receptacle15A 125V, 2-P 3-W Grounding

LENGTH GFCI CORD SET, YELLOW CORD, 16/3 SJTW NEMA NEMA

BLACK BODY, ON/OFF POWER SWITCH, PLUG CONNECTOR

13 WATT LAMP

20’ 66591-WL 5-15P 5-15RG

W

G

W

PANEL MOUNT FOR TEMPORARYPOWER DISTRIBUTION BOXES

36597

PANEL MOUNT GFCI FOR PHASE-CONTROL THEATER

DIMMING SYSTEMS

36895

TOGGLE BLANK FACE

COLOR RESET BUTTONS

Ivory 8895-80I

White 8895-80W

Black 8895-80E

16893 16594

COLOR WATERPROOF COVER WITH GROUND PIN UP

ORIENTATION

Clear 86593

Right Angle Plugs Accessory

20A 125V, NEMA 5-20P15A 125V, NEMA 5-15P

Right Angle GFCI Plugs

30ºC max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC per

UL 498

Ratingspermanently

marked on device

#18- #12 AWG

#LR-57811 #057–

MISC. MOTOR CONTROL RATING

15A-1875W

20A-2500W

TRIP LEVEL

5±1 mA

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35ºC to 66ºC

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOM

WD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

U U U

Recognized Component*

Recognized Component

High Current GFCIContact Rating: 20A 125V ACLoad Capability with 125V Control Relay80@240V AC Max.

36596, 36597, 36895 RIGHT ANGLE GFCI PLUGS 8895

~~~~~~~

~~~~~~

~~~~~~~TESTRESE

1.74 (44.2 mm)

3.8

(9

6.5

mm

)

2.7

(68

.6 m

m)

2.40 (64 mm)

4.7

5 (

121 m

m)

5.1

2 (

130 m

m)

1.29 DIA.

(33 mm)

1.60 DIA.(41 mm)

1.83 DIA. (49 mm)

.023 R

EF

.

1.7 (43.2 mm)

1.12 (28 mm)

2.7

(6

8.6

mm

)

4.2

1 (

10

6.9

3 m

m)

15A 125V

RECEPTACLE

CLASS A

LEVITON

GF

CI

CL

AS

S

20 A

MP

125V

1.26 (32 mm)

OFF

ON

SWITCH

RESETRESET

FO

LL

OW

DIR

EC

TIO

NS

SU

IVE

Z I

NS

TR

UC

TIO

N

TE

ST

MO

NT

HL

YT

ES

T M

EN

SU

EL

TEST

TEST

GROUND FAULT CIRCUIT

INTERRUPTER-MISC. MOTOR

CONTROLLER AND SWITCH

1.77 (45 mm)

2.58 (65.5 mm)

.81

0

(20

.6 m

m)

Recognized Component

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

Silver, neutral

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 2kA1500V

perUL 498

Front View Side View

16593

PLUG ANGLE PLUG ANGLE PLUGCOLOR AUTOMATIC MANUAL AUTOMATIC MANUAL

RESET RESET RESET RESET

Black 16593 – 16893 –Yellow – 16594 – 16894

Wiring Termination Area

Rated 20A-125 VAC

*Catalog numbers 6593, 6893, 6594 and 6894 series are available – consult factory. For additional information,see catalog L-100, page H5.

Refer to footnoteunder Right AngleGFCI Plugs Table

86593

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

Available in 2-ft., 6-ft. and 25-ft.lengths, except where indicated

RTV injected at cord entrance andexit of the housing

Choice of Automatic or Manualreset models

GFCI Cord Set Features

F5

GFCI Co

rd Set F

eature

s

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Power indicator light goes OFF ifGFCI trips, power is interruptedor line cord is unplugged

GFCI Cord Set Features

Water-resistant enclosure sealedby ultrasonic welding to ensurelong service life

Equipped with Industrial Grade plugs andconnectors to provide long service life inheavy-duty applications

Water-resistant SJTW-A cable(14/3 for 15A, 12/3 for 20A)

Agency Standards• Complies with UL Standard 943 as a

Recognized Component Class A GFCIpower supply with open neutral protection

• UL Listed (File #E-48380), 15A devices alsoCSA Certified (File #LR-5781)

• Fully complies with NEC code article #527.6,6(A) and 6(B) and OSHA regulation CFR1926-404b(i)(ii) for construction sites

• In-line GFCI units are NEMA 3R

GFCI Protection: An OSHA Requirement on the Job Site OSHA definitely means business, with fines for willful violations reaching as high as $70,000! The secondmost common OSHA electrical violation at construction sites involves non-compliance with either theAssured Equipment Grounding Program or Ground Fault Protection. Whichever program you choose,portable GFCI Cord Sets or an approved grounding conductor program, make sure it is used 100% of thetime. Ignoring OSHA requirements can cost money as well as business. Compliance with OSHA and NECstandards is absolutely mandatory, and use of Leviton GFCI Cord Sets is a reliable, economical way toaccomplish that.

GFCI Cord Sets Must Have Open-Neutral ProtectionOpen-Neutral Protection immediately trips the GFCI if the neutral conductor on the line side is opened.This eliminates the possibility of the GFCI Cord Set having a live hot leg, even though it may appear asthough power is off due to the open neutral. A normal GFCI receptacle would not be able to trip underthese conditions.

Automatic vs. Manual Reset Cord SetsAutomatic Reset GFCI Cord Sets (black body) automatically reset ON when power is restored. Manual Resetunits (yellow body) will not automatically reset after power interruption; the reset button must be pushed in.

Automatic Reset GFCI Cord Sets and Extension Cords – Black Body

• Automatically resets to ON when plugged in or after power interruption

• Available in 2-ft, 6-ft and 25-ft lengths except where indicated

Cat. No. 66591-WLProvides lighting and GFCI protection in

out-of-the-way locations

Manual Reset GFCI Cord Sets withWetguard® plugs and connectors provideoutstanding corrosion-resistance where

water is present

Custom lengths and configurationsavailable as special order

69593-3

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

15A 125V&250V;20A 125V&250V

F6

Automatic Reset GFCI Cord Sets & Power Supply Cords

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 2kA 1500V

perUL 498

GFCI CORD SET AUTOMATIC RESETLENGTH (15 AMP) 14/3 SJTW NEMA NEMA

(20 AMP) 12/3 SJTW PLUG CONNECTORYELLOW CORD, BLACK BODYBLACK PLUG & CONNECTOR

66891-3 66593-3

5-15P 5-15R

5-15P 5-15R

L5-15P L5-15R

5-15P

6-15P

5-20P 5-20R

L5-20P L5-20R

15A 125V, Cord Sets

15A 240V, Power Supply Cord

20A 125V, Cord Sets

20A 125V, Locking Cord Set

15A 125V, Power Supply Cord

15A 125V, Locking Cord Set

15A 125V, Cord Set Triple Outlet

20A 125V, Power Supply Cord

5-20P

20A 240V, Power Supply Cord

6-20P

Automatic reset GFCI cord sets (black body) automatically reset ON when power is restored.

66591-25C

30ºC max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC per

UL 498

Ratingspermanently

marked on device

Not Applicable

TRIP LEVEL

5±1 mA

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35ºC to 66ºC

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

Silver, neutral

FACTORY-ASSEMBLED CORD SETS — Consult Techline for changes in length and/or configurations.

2' 66591-2C

6' 66591-6C

25' 66591-25C

3' 66593-3

3' 66597-3

37' 26591-37C –

35' 26592-E –

3' 66891-3

3' 66897-3

37' 36591-37C –

35' 36592-E –

#LR-57811 #057–

MISC. MOTOR CONTROL RATING

15A-1875W

20A-2500W

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOM

WD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

U U U

Automatic Reset GFCI Cord Sets & Power Supply Cords

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

15A 125V;20A 125V

F7

Manua

l Reset

GFCI Co

rd Sets

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Manual Reset GFCI Cord Sets 1 YEAR LIMITED

GFCI CORD SET MANUAL RESETLENGTH (15 AMP) 14/3 SJTW NEMA NEMA

(20 AMP) 12/3 SJTW PLUG CONNECTORYELLOW CORD,YELLOW BODYYELLOW PLUG & CONNECTOR

5-15P 5-15R

5-15P 5-15R

5-20P 5-20R

15A 125V, Cord Sets

20A 125V, W/ Wetguard Plug & Connector Cord Set

15A 125V, W/ Wetguard Plug & Connector Cord Set

15A 125V, Cord Set Triple Outlet

5-15P 5-15R

36.0 (914.4 mm)

1.6

3 (

41.1

mm

)

6.70 (170.2 mm)

1.7

8 (

45.2

mm

)

2.5

0 (

63.5

mm

)0.63 (15.6 mm)

MANUAL RESET GFCI CORD69591-W3

TEST RESET

TEST RESET

FOLLOW DIRECTIONS

TEST BEFORE EACH USE

6.70 (170.2 mm)

(9.32 ± 2 mm) 2.50 (63.5 mm)

0.367± 0.07

15A AUTO GFCI CORD66591-2C — on page F6

Manual reset units (yellow body) will not automatically reset after power interruption; the reset button must be pushed in.

69591-W3 69891-3

30ºC max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC per

UL 498

Ratingspermanently

marked on device

Not Applicable

TRIP LEVEL

5±1 mA

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35ºC to 66ºC

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

Silver, neutral

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 2kA 1500V

perUL 498

#LR-57811 #057–

MISC. MOTOR CONTROL RATING

15A-1875W

20A-2500W

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOM

WD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

U U U

FACTORY-ASSEMBLED CORD SETS - Consult Techline for changes in length and/or configurations.

3' 69591-325' 69591-25

3' 69593-3

3' 69591-W325' 69591-W25

3' 69891-W3

69593-3 69591-W3

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

50A 125/250V

F8

Temporary Portable Power Distribution Center/GFCI & Power Cords

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

1 YEAR LIMITED Power Center “THE BOX” & Power Cords

LENGTH BLACK FLEXIBLE CORD w/ YELLOW & WHITE YELLOW & WHITE(3) #6 AWG and (1) #8 WEATHER-RESISTANT PLUG WEATHER-RESISTANT CONNECTORAWG CONDUCTORS NON-NEMA NON-NEMA

50' KRS-A9519

100' KUS-A9519

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 2kA1500V

perUL 498

FACTORY-ASSEMBLED CORD SETS

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35ºC to 66ºC

Ratings &NEMA I.D.permanently

marked on device

Not Applicable

Power CordsFeatures Flexible, Abrasion-Resistant Construction Offering Reliable Performance to -31ºF

EQ GRX

Y

W

X

Y

W

EQ GR

NON-NEMA† NON-NEMA†

50A 125/250V, NON-NEMA

22 in.

22 in.

12 in. 19.50 in.

12 in

.

16.00 in.

OUTLET

125/250V

TO MEET OSHA REQUIREMENTS

50A USE UL LISTED OUTDOOR

POWER SUPPLY CORD

R

T

POWER SUPPLY CORD

USE UL LISTED OUTDOOR

50ATO MEET OSHA REQUIREMENTS

125/250V

INLETEMPORARY

POWE

DISTRIBUTION

CENTER

250V/30A

125V/20A

125V/20A

GFCIfor

30A-250VRECEPTACLE

60 Hz, 4-Wire

125/250 Volts

50 AmpsDISTRIBUTION UNIT

PORTABLE POWER

LISTED

11BK

Cat. No. PB103-SGF

OSHAMade to Meet

Requirements

Receptacles rated 50A are Not ground-fault protected.

Persons Who Contact More Than One Leg of

the National Electrical Code, ANSI/NFPA 70.

Program as defined by Section 305-6(b) of

conjunction with an Assured Equipment Grounding

protection for personnel m

ust be used in

All receptacles not provided with ground fault

Suitable for use in damp locations.SAFETY INFORMATION

FOR USE BY QUALIFIED PERSONNEL ONLY.

CAUTION - To Reduce the Risk of Electic Shock,

Ground This Unit at the Supply Source and Use

Only in the Upright Position.

All receptacles rated 20A & 30A are provided

withground fault protection for personnel.

the Circuit Are Not Protected.

Protection is Not Provided if there are Defects

in an Extension Cord or Other Wirin

g Supplying

the Unit.

Type 3R Enclosure - Rainproof

Service by authorized service center only.

Fuse Rating: 250V/0.5A

125V/20A 125V/20A 125V/20A

250V/30A250V/30A 125V/20A125V/20A

Weather Resistant CoverFor 30A Locking Recept.

Circuit Breaker Cover

END VIEW 1 SIDE VIEW 1

TOP VIEW END VIEW 2 SIDE VIEW 2

30ºC max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC per

UL 498

TRIP LEVEL

5±1 mA

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

White,neutral #LR-57811 #057–

OSHA

“The Box” Meets Regulation 20, Part 1926, Subpart K Standards

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOM

WD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

U U U

†Consult Factory for Other Configurations.

Power Distribution Box Available with or without GFCI Protection on 30A Receptacles Consult Factory for Other Configurations

Power Inlet Power Outlet 6 NEMA Locking 6 NEMA Straight 1 NEMA Locking Catalogue No. Non-NEMA Non-NEMA Receptacles Blade Receptacles Receptacle

50A, 125/250V 50A, 125/250V 20A, 125V, L5-20R 20A, 125V, 5-20R 30A, 250V, L6-30R

PB101-SGF 4 4 4 4

PB101-000 4 4 4 4

PB103-SGF 4 4 4 4

PB103-000 4 4 4 4

No GFCI ProtectionNo GFCI Protection

No GFCI Protection

No GFCI Protection

No GFCI Protection

No GFCI Protection

No GFCI Protection

No GFCI Protection

GFCI Protection

GFCI Protection

GFCI Protection

GFCI Protection

GFCI Protection

No GFCI Protection

No GFCI ProtectionGFCI Protection

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

GFCI Accessories

F9

GFCIAc

cessor

ies

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

1 YEAR LIMITED

Single-Gang Flush Cover Wallplates

Raintight While-In-Use Covers

Surface-Mounted

Outdoor-Type Boxes

or Flush-Mounted

Wall Boxes

5977-CL 5977-GY 4992 4998-GY 5997-GY 5997-CL

3.75 (95.6 mm)

6.5

9 (

16

7.4

mm

)

3.30 (83.8 mm)

Ø 0.25 (16.0 mm)cord opening

5977

5.05 (128.3 mm)Ø 0.25 (6.4 mm)padlock opening

5.4

6 (

138

.7 m

m)

2.88 (73.2 mm)

Ø 0.63 (16.0 mm)cord opening

5997

TYPE MOUNTING POSITION SINGLE-GANG FITS

FLUSH COVER TYPE OF BOX

Gray Die-Cast Zinc Vertical 6196-V Standard

Gray Die-Cast Zinc Horizontal 6196 Standard

Gray Die-Cast Zinc Vertical 6196-VFS FS (4 Screws)

Gray Die-Cast Zinc Horizontal 6196-FS FS (4 Screws)

Gray Die-Cast Zinc Horizontal 4990 Standard

Gray Die-Cast Zinc Vertical 4992 Standard

Gray Plastic Horizontal 4996-GY Standard

White Plastic Horizontal 4996-W Standard

Gray Plastic Vertical 4998-GY Standard

White Plastic Vertical 4998-W Standard

TYPE MOUNTING POSITION SINGLE-GANG FITSFLUSH COVER TYPE OF BOX

Gray Plastic Vertical 5977-GY

Gray Plastic Vertical Mount w/ 5977-DGYExtra Deep Cover

Clear Plastic Vertical 5977-CL

Clear Plastic Vertical Mount w/ 5977-DCLExtra Deep Cover

Gray Plastic Horizontal 5997-GY

Gray Plastic Horizontal Mount w/ 5997-DGYExtra Deep Cover

Clear Plastic Horizontal 5997-CL

Clear Plastic Horizontal Mount w/ 5997-DCLExtra Deep Cover

This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com

SmartLockPRO™ Information

F10

SmartLockPRO™Information

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com

Other GFCI manufacturers have taken the alternate route inthe 2006 UL Standard by providing an indicator light for end-of-life indication. They allow the compromised GFCI to bereset, thereby permitting it to continue delivering unprotect-ed power to the GFCI face and downstream receptacles. Wedisagree with this approach.

GFCIs are first and foremost proven safety devices. TheNational Electrical Code requires GFCIs to be installed inbathrooms, kitchens, workshops and other locations wherewater is present and there’s a risk of ground fault shock

hazard. Leviton believes that a GFCI should be replacedimmediately if it no longer provides ground fault protection.There is absolutely no people protection when a compro-mised GFCI functions as a “live” standard receptacle.

That’s why Leviton’s SmartLockPRO GFCI performs a self-test every time it is reset. If it is not capable of responding toa ground fault, the reset is blocked. Leviton’s SmartLockPRO approach locks out a compromised GFCI, thereby pro-viding the safest and smartest solution to people protection.

Underwriter’s Laboratories (UL) has issued newrequirements on GFCI functionality effective July 28, 2006:

Line-Load Reversal Indication

If an old style GFCI is miswired with a line-load reversal, itis a potentially hazardous situation because the GFCIreceptacle face will be live and unprotected even after theGFCI is tripped.

2003 UL Standard:• There must be a diagnostic indicator if a miswiring (line-

load reversal) occurs during installation. However, the GFCIreceptacle’s face may still be live and unprotected.

New UL 2006 Standard:• If a miswiring (line-load reversal) occurs during installation,

the GFCI must not be capable of supplying power to eitherthe GFCI’s face or to feed-through terminals.

The SmartLockPRO Solution:• SmartLockPRO provides a true dead-face design with an

LED indicator for line-load reversals.

“End-of-Life” Indication

GFCIs reach the end of their service life when they nolonger provide ground fault protection. As with any electronic device, a GFCI can be damaged by surges,other electrical disturbances, or environmental andphysical abuse.

2003 UL Standard:

• There are no requirements related to “end of life”

New UL 2006 Standard:

• GFCIs are required to provide a visual and/or audible indication OR be able to render themselves incapable ofdelivering power when they no longer offer ground faultprotection based on a failure to pass their internal test.

The SmartLockPRO Solution:

• Though a standard GFCI CAN be reset even if it is not pro-viding protection…the SmartLockPRO’s reset button will not engage if protection has been compromised. WithSmartLockPRO’s unique patented professional grade end-of-life lock-out action you can avoid having a live, unprotectedreceptacle in the event that the GFCI can no longer provideprotection. The robust design of SmartLockPRO GFCIs alsogreatly reduces the frequency of GFCI failures, contributing toa longer GFCI service life.

SmartLockPRO and The New 2006 UL943 GFCI Safety Standards

Non-Lockout Style GFCI SmartLockPRO GFCI

Plug a lamp or radio into the GFCI receptacle. Plug a lamp or radio into the GFCI receptacle.

Turn ON lamp or radio. Turn ON lamp or radio.

Push the TEST button on the GFCI. If the GFCI is working Push the TEST button on the SmartLockPRO GFCI. The properly, it will trip and power to the lamp or radio will GFCI will trip and power to the lamp or radio will be cut off.be cut off. Push reset button to restore power.

Your GFCI is working properly and should be retested every month.

If power did not go off: Your GFCI is working properly if you can push the RESET If power did not go off when you pushed the TEST button, button on the SmartLockPRO GFCI to restore powerthen the GFCI is not providing protection and should be to the lamp or radio.replaced immediately. Standard GFCIs can still be reset and provide power even though they are not providing IMPORTANT: The RESET button will not restore power if protection. the GFCI is damaged and cannot respond to a ground fault.

That’s why we developed SmartLockPRO…

The Choice for 2006 UL End-of-Life Indication: Protection or No Protection?

General Testing Procedures