SmartLockPRO™ GFCI Features
F2
SmartLockPRO™GFCI Features
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Leviton SmartLockPRO™ iconensures improved GFCI
product design.
Lockout action blocks the “RESET”button if GFCI protection has been
compromised.
UL Standard 943 Class A (GFCI) & 498 (Receptacles)
CSA Certified (File #057)Meets July 28, 2006 UL Requirements
Triple combinationterminal screws.
“Surge hardened” electronicsoffer superior resistance tosurges and overvoltages.
LED power indicator light helpsdiagnose improper wiring and,when illuminated, offers visualconfirmation that power is available.
Heavy duty double wipe for15 Amp contacts and triplewipe for 20 Amp contacts
Patented lockout feature prevents“RESET” if GFCI is not functioningproperly or miswired due to reversal ofline and load leads.
Thick-walled, impact-resistantthermoplastic nylon cover andbody withstands abuse
Silver alloy contacts for reliablemake/break switching.
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL 943 CSA NOMWD1&WD6 C-73 Listed Class A & 498
U U #E48380 U #LR-57811 #057
Eight back-wire holes
(two per terminal) and
back-wire ground.
Provisions for back- or side-wiring.
COMPONENT DESCRIPTION
Face Nylon
Back Polycarbonate
Line Contacts Brass
Terminal Screws Brass #8-32
Grounding Screw Brass #8-32
Yoke Zinc Steel
Clamp Nuts Steel
Internal Contacts Silver Alloy
Leviton SmartLockPRO™ and The New 2006UL943 GFCI Safety Standards
Line-Load Reversal IndicationNew UL 2006 Standard:• If a miswiring (line-load reversal) occurs during installation,
the GFCI must not be capable of supplying power to eitherthe GFCI’s face or to feed-through terminals.
“End-of-Life” IndicationNew UL 2006 Standard:• GFCIs are required to provide a visual and/or audible
indication OR be able to render themselves incapable ofdelivering power when they no longer offer ground fault protection based on a failure to pass their internal test.
For additional details on these new requirements, see page F10.
Dual function LED offers indication
of line/load reversal & power availability.
7599-W
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
15A 125V & 20A 125V
F3
Hospita
l & Com
mercial
Grade
GFCI De
vices
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Hospital & Commercial Grade, GFCI’s
MECHANICAL
TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.
Brass, hot
Grounding
Silver, neutral
15A 125V, NEMA 5-15R; 20A 125V Feed-Through
ELECTRICAL
DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE
Withstands 2kA 1500V
perUL 498
80ºC max at fullrated current
after 50 cyclesoverload at150% rated
current for bothAC and DC appl.
per UL 498
ENVIRONMENTAL
FLAMMABILITY OPERATING TEMP.
Rated V-2 per UL 94 -35ºC to 65ºC
Ratingspermanently
marked on device
#14 - #12 AWG solid or stranded
copper wire
7899-HG SERIES 7599 SERIES 7590 SERIES 7299 SERIES
4.2
1 (1
06
.93
mm
)
3.7
0 (9
3.9
8 m
m)
1.31
0.94
3.8
1 (
96
.77
mm
)
3.2
8 (
83
.81
mm
)
2.7
4 (6
9.6
0 m
m)2
.62
(6
6.5
5 m
m)
1.19
0.2
9 (
7.3
7 m
m)
(23.88 mm)
(33.27 mm)(30.23 mm)
7590-W7599-I
Back & Side Wired
TRIP LEVEL
5±1 mA
7599-LI
20A 125V, NEMA 5-20R at Receptacle & Feed-Through
7899-HGR
3.8
1 (
96.7
7 m
m)
3.2
8 (
83.8
1 m
m)2
.74 (6
9.6
0 m
m)2
.62 (
66.5
5 m
m)
1.19
0.2
9 (
7.3
7 m
m)
4.2
1 (1
06.9
3 m
m)
3.7
0 (9
3.9
8 m
m)
0.94
1.31
(30.23 mm)
(23.88 mm)
(33.27 mm)1.7 (43.2 mm)
1.12 (28 mm)
2.7
(6
8.6
mm
)
4.2
1 (
10
6.9
3 m
m)
CLASS A
LEVITON
GF
CI
CL
AS
S
20 A
MP
125V
1.53 (38.9 mm) 1.7 (43.2 mm)
1.12 (28 mm)
2.7
(6
8.6
mm
)
4.2
1 (
10
6.9
3 m
m)
GF
CI
1.53 (38.9 mm)
SHALLOW WALLBOX
COLOR EXTENDERFOR GFCI's
Brown 6197
Ivory 6197-IWhite 6179-W
7299-A
15A 125V, NEMA 5-15R;20A 125V Feed-Through
#LR-57811 #057–
MISC. MOTOR CONTROL RATING
15A-1875W
20A-2500W
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL CSA NOM
WD-6 C-73 943 Fed Spec C22.2
Class A Listed& 498 WC-596
U U U
FACE GFCI COMBO DEVICE RECEPTACLE
COLOR & SINGLE-POLE SWITCH
Meets 2006 UL Requirements
Ivory 7299-I
White 7299-WAlmond 7299-A
GFCI GFCI GFCI GFCIHOSPITAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE
FACE SMARTLOCKPRO™ SMARTLOCKPRO™ SMARTLOCKPRO™ BLANK FACECOLOR DUPLEX w/ LED DUPLEX w/ LED DUPLEX w/ LED S-P SWITCH
w/ 6" Leads. 1.5HP@120V ACMeets 2006 Meets 2006 Meets 2006 Meets 2006
UL Requirements UL Requirements UL Requirements UL Requirements
Brown 7599-HG 7599 – –Ivory 7599-HGI 7599-I 7599-LI 7590-IWhite 7599-HGW 7599-W 7599-LW 7590-WGray 7599-HGG 7599-G – –Red 7599-HGR 7599-R – –Black – 7599-E – 7590-EAlmond 7599-HGA 7599-A – 7590-ALt. Almond 7599-HGT 7599-T – 7590-T
Brown 7899-HG 7899 – –Ivory 7899-HGI 7899-I 7899-LI –White 7899-HGW 7899-W 7899-LW –Gray 7899-HGG 7899-G – –Red 7899-HGR – – –Black 7899-HGE 7899-E – –Almond 7899-HGA 7899-A – –Lt. Almond 7899-HGT 7899-T – –
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
15A 125V & 20A 125V
F4
Commercial Grade GFCI Devices
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Commercial Grade, GFCI’s
GFCI-Protected Fluorescent Work Light w/Receptacle15A 125V, 2-P 3-W Grounding
LENGTH GFCI CORD SET, YELLOW CORD, 16/3 SJTW NEMA NEMA
BLACK BODY, ON/OFF POWER SWITCH, PLUG CONNECTOR
13 WATT LAMP
20’ 66591-WL 5-15P 5-15RG
W
G
W
PANEL MOUNT FOR TEMPORARYPOWER DISTRIBUTION BOXES
36597
PANEL MOUNT GFCI FOR PHASE-CONTROL THEATER
DIMMING SYSTEMS
36895
TOGGLE BLANK FACE
COLOR RESET BUTTONS
Ivory 8895-80I
White 8895-80W
Black 8895-80E
16893 16594
COLOR WATERPROOF COVER WITH GROUND PIN UP
ORIENTATION
Clear 86593
Right Angle Plugs Accessory
20A 125V, NEMA 5-20P15A 125V, NEMA 5-15P
Right Angle GFCI Plugs
30ºC max at fullrated current
after 50 cyclesoverload at150% rated
current for bothAC and DC per
UL 498
Ratingspermanently
marked on device
#18- #12 AWG
#LR-57811 #057–
MISC. MOTOR CONTROL RATING
15A-1875W
20A-2500W
TRIP LEVEL
5±1 mA
ENVIRONMENTAL
FLAMMABILITY OPERATING TEMP.
Rated V-2 per UL 94 -35ºC to 66ºC
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL CSA NOM
WD-6 C-73 943 Fed Spec C22.2
Class A Listed& 498 WC-596
U U U
Recognized Component*
Recognized Component
High Current GFCIContact Rating: 20A 125V ACLoad Capability with 125V Control Relay80@240V AC Max.
36596, 36597, 36895 RIGHT ANGLE GFCI PLUGS 8895
~~~~~~~
~~~~~~
~~~~~~~TESTRESE
1.74 (44.2 mm)
3.8
(9
6.5
mm
)
2.7
(68
.6 m
m)
2.40 (64 mm)
4.7
5 (
121 m
m)
5.1
2 (
130 m
m)
1.29 DIA.
(33 mm)
1.60 DIA.(41 mm)
1.83 DIA. (49 mm)
.023 R
EF
.
1.7 (43.2 mm)
1.12 (28 mm)
2.7
(6
8.6
mm
)
4.2
1 (
10
6.9
3 m
m)
15A 125V
RECEPTACLE
CLASS A
LEVITON
GF
CI
CL
AS
S
20 A
MP
125V
1.26 (32 mm)
OFF
ON
SWITCH
RESETRESET
FO
LL
OW
DIR
EC
TIO
NS
SU
IVE
Z I
NS
TR
UC
TIO
N
TE
ST
MO
NT
HL
YT
ES
T M
EN
SU
EL
TEST
TEST
GROUND FAULT CIRCUIT
INTERRUPTER-MISC. MOTOR
CONTROLLER AND SWITCH
1.77 (45 mm)
2.58 (65.5 mm)
.81
0
(20
.6 m
m)
Recognized Component
MECHANICAL
TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.
Brass, hot
Grounding
Silver, neutral
ELECTRICAL
DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE
Withstands 2kA1500V
perUL 498
Front View Side View
16593
PLUG ANGLE PLUG ANGLE PLUGCOLOR AUTOMATIC MANUAL AUTOMATIC MANUAL
RESET RESET RESET RESET
Black 16593 – 16893 –Yellow – 16594 – 16894
Wiring Termination Area
Rated 20A-125 VAC
*Catalog numbers 6593, 6893, 6594 and 6894 series are available – consult factory. For additional information,see catalog L-100, page H5.
Refer to footnoteunder Right AngleGFCI Plugs Table
86593
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Available in 2-ft., 6-ft. and 25-ft.lengths, except where indicated
RTV injected at cord entrance andexit of the housing
Choice of Automatic or Manualreset models
GFCI Cord Set Features
F5
GFCI Co
rd Set F
eature
s
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Power indicator light goes OFF ifGFCI trips, power is interruptedor line cord is unplugged
GFCI Cord Set Features
Water-resistant enclosure sealedby ultrasonic welding to ensurelong service life
Equipped with Industrial Grade plugs andconnectors to provide long service life inheavy-duty applications
Water-resistant SJTW-A cable(14/3 for 15A, 12/3 for 20A)
Agency Standards• Complies with UL Standard 943 as a
Recognized Component Class A GFCIpower supply with open neutral protection
• UL Listed (File #E-48380), 15A devices alsoCSA Certified (File #LR-5781)
• Fully complies with NEC code article #527.6,6(A) and 6(B) and OSHA regulation CFR1926-404b(i)(ii) for construction sites
• In-line GFCI units are NEMA 3R
GFCI Protection: An OSHA Requirement on the Job Site OSHA definitely means business, with fines for willful violations reaching as high as $70,000! The secondmost common OSHA electrical violation at construction sites involves non-compliance with either theAssured Equipment Grounding Program or Ground Fault Protection. Whichever program you choose,portable GFCI Cord Sets or an approved grounding conductor program, make sure it is used 100% of thetime. Ignoring OSHA requirements can cost money as well as business. Compliance with OSHA and NECstandards is absolutely mandatory, and use of Leviton GFCI Cord Sets is a reliable, economical way toaccomplish that.
GFCI Cord Sets Must Have Open-Neutral ProtectionOpen-Neutral Protection immediately trips the GFCI if the neutral conductor on the line side is opened.This eliminates the possibility of the GFCI Cord Set having a live hot leg, even though it may appear asthough power is off due to the open neutral. A normal GFCI receptacle would not be able to trip underthese conditions.
Automatic vs. Manual Reset Cord SetsAutomatic Reset GFCI Cord Sets (black body) automatically reset ON when power is restored. Manual Resetunits (yellow body) will not automatically reset after power interruption; the reset button must be pushed in.
Automatic Reset GFCI Cord Sets and Extension Cords – Black Body
• Automatically resets to ON when plugged in or after power interruption
• Available in 2-ft, 6-ft and 25-ft lengths except where indicated
Cat. No. 66591-WLProvides lighting and GFCI protection in
out-of-the-way locations
Manual Reset GFCI Cord Sets withWetguard® plugs and connectors provideoutstanding corrosion-resistance where
water is present
Custom lengths and configurationsavailable as special order
69593-3
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
15A 125V&250V;20A 125V&250V
F6
Automatic Reset GFCI Cord Sets & Power Supply Cords
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
ELECTRICAL
DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE
Withstands 2kA 1500V
perUL 498
GFCI CORD SET AUTOMATIC RESETLENGTH (15 AMP) 14/3 SJTW NEMA NEMA
(20 AMP) 12/3 SJTW PLUG CONNECTORYELLOW CORD, BLACK BODYBLACK PLUG & CONNECTOR
66891-3 66593-3
5-15P 5-15R
5-15P 5-15R
L5-15P L5-15R
5-15P
6-15P
5-20P 5-20R
L5-20P L5-20R
15A 125V, Cord Sets
15A 240V, Power Supply Cord
20A 125V, Cord Sets
20A 125V, Locking Cord Set
15A 125V, Power Supply Cord
15A 125V, Locking Cord Set
15A 125V, Cord Set Triple Outlet
20A 125V, Power Supply Cord
5-20P
20A 240V, Power Supply Cord
6-20P
Automatic reset GFCI cord sets (black body) automatically reset ON when power is restored.
66591-25C
30ºC max at fullrated current
after 50 cyclesoverload at150% rated
current for bothAC and DC per
UL 498
Ratingspermanently
marked on device
Not Applicable
TRIP LEVEL
5±1 mA
ENVIRONMENTAL
FLAMMABILITY OPERATING TEMP.
Rated V-2 per UL 94 -35ºC to 66ºC
MECHANICAL
TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.
Brass, hot
Grounding
Silver, neutral
FACTORY-ASSEMBLED CORD SETS — Consult Techline for changes in length and/or configurations.
2' 66591-2C
6' 66591-6C
25' 66591-25C
3' 66593-3
3' 66597-3
37' 26591-37C –
35' 26592-E –
3' 66891-3
3' 66897-3
37' 36591-37C –
35' 36592-E –
#LR-57811 #057–
MISC. MOTOR CONTROL RATING
15A-1875W
20A-2500W
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL CSA NOM
WD-6 C-73 943 Fed Spec C22.2
Class A Listed& 498 WC-596
U U U
Automatic Reset GFCI Cord Sets & Power Supply Cords
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
15A 125V;20A 125V
F7
Manua
l Reset
GFCI Co
rd Sets
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Manual Reset GFCI Cord Sets 1 YEAR LIMITED
GFCI CORD SET MANUAL RESETLENGTH (15 AMP) 14/3 SJTW NEMA NEMA
(20 AMP) 12/3 SJTW PLUG CONNECTORYELLOW CORD,YELLOW BODYYELLOW PLUG & CONNECTOR
5-15P 5-15R
5-15P 5-15R
5-20P 5-20R
15A 125V, Cord Sets
20A 125V, W/ Wetguard Plug & Connector Cord Set
15A 125V, W/ Wetguard Plug & Connector Cord Set
15A 125V, Cord Set Triple Outlet
5-15P 5-15R
36.0 (914.4 mm)
1.6
3 (
41.1
mm
)
6.70 (170.2 mm)
1.7
8 (
45.2
mm
)
2.5
0 (
63.5
mm
)0.63 (15.6 mm)
MANUAL RESET GFCI CORD69591-W3
TEST RESET
TEST RESET
FOLLOW DIRECTIONS
TEST BEFORE EACH USE
6.70 (170.2 mm)
(9.32 ± 2 mm) 2.50 (63.5 mm)
0.367± 0.07
15A AUTO GFCI CORD66591-2C — on page F6
Manual reset units (yellow body) will not automatically reset after power interruption; the reset button must be pushed in.
69591-W3 69891-3
30ºC max at fullrated current
after 50 cyclesoverload at150% rated
current for bothAC and DC per
UL 498
Ratingspermanently
marked on device
Not Applicable
TRIP LEVEL
5±1 mA
ENVIRONMENTAL
FLAMMABILITY OPERATING TEMP.
Rated V-2 per UL 94 -35ºC to 66ºC
MECHANICAL
TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.
Brass, hot
Grounding
Silver, neutral
ELECTRICAL
DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE
Withstands 2kA 1500V
perUL 498
#LR-57811 #057–
MISC. MOTOR CONTROL RATING
15A-1875W
20A-2500W
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL CSA NOM
WD-6 C-73 943 Fed Spec C22.2
Class A Listed& 498 WC-596
U U U
FACTORY-ASSEMBLED CORD SETS - Consult Techline for changes in length and/or configurations.
3' 69591-325' 69591-25
3' 69593-3
3' 69591-W325' 69591-W25
3' 69891-W3
69593-3 69591-W3
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
50A 125/250V
F8
Temporary Portable Power Distribution Center/GFCI & Power Cords
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
1 YEAR LIMITED Power Center “THE BOX” & Power Cords
LENGTH BLACK FLEXIBLE CORD w/ YELLOW & WHITE YELLOW & WHITE(3) #6 AWG and (1) #8 WEATHER-RESISTANT PLUG WEATHER-RESISTANT CONNECTORAWG CONDUCTORS NON-NEMA NON-NEMA
50' KRS-A9519
100' KUS-A9519
ELECTRICAL
DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE
Withstands 2kA1500V
perUL 498
FACTORY-ASSEMBLED CORD SETS
ENVIRONMENTAL
FLAMMABILITY OPERATING TEMP.
Rated V-2 per UL 94 -35ºC to 66ºC
Ratings &NEMA I.D.permanently
marked on device
Not Applicable
Power CordsFeatures Flexible, Abrasion-Resistant Construction Offering Reliable Performance to -31ºF
EQ GRX
Y
W
X
Y
W
EQ GR
NON-NEMA† NON-NEMA†
50A 125/250V, NON-NEMA
22 in.
22 in.
12 in. 19.50 in.
12 in
.
16.00 in.
OUTLET
125/250V
TO MEET OSHA REQUIREMENTS
50A USE UL LISTED OUTDOOR
POWER SUPPLY CORD
R
T
POWER SUPPLY CORD
USE UL LISTED OUTDOOR
50ATO MEET OSHA REQUIREMENTS
125/250V
INLETEMPORARY
POWE
DISTRIBUTION
CENTER
250V/30A
125V/20A
125V/20A
GFCIfor
30A-250VRECEPTACLE
60 Hz, 4-Wire
125/250 Volts
50 AmpsDISTRIBUTION UNIT
PORTABLE POWER
LISTED
11BK
Cat. No. PB103-SGF
OSHAMade to Meet
Requirements
Receptacles rated 50A are Not ground-fault protected.
Persons Who Contact More Than One Leg of
the National Electrical Code, ANSI/NFPA 70.
Program as defined by Section 305-6(b) of
conjunction with an Assured Equipment Grounding
protection for personnel m
ust be used in
All receptacles not provided with ground fault
Suitable for use in damp locations.SAFETY INFORMATION
FOR USE BY QUALIFIED PERSONNEL ONLY.
CAUTION - To Reduce the Risk of Electic Shock,
Ground This Unit at the Supply Source and Use
Only in the Upright Position.
All receptacles rated 20A & 30A are provided
withground fault protection for personnel.
the Circuit Are Not Protected.
Protection is Not Provided if there are Defects
in an Extension Cord or Other Wirin
g Supplying
the Unit.
Type 3R Enclosure - Rainproof
Service by authorized service center only.
Fuse Rating: 250V/0.5A
125V/20A 125V/20A 125V/20A
250V/30A250V/30A 125V/20A125V/20A
Weather Resistant CoverFor 30A Locking Recept.
Circuit Breaker Cover
END VIEW 1 SIDE VIEW 1
TOP VIEW END VIEW 2 SIDE VIEW 2
30ºC max at fullrated current
after 50 cyclesoverload at150% rated
current for bothAC and DC per
UL 498
TRIP LEVEL
5±1 mA
MECHANICAL
TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.
Brass, hot
Grounding
White,neutral #LR-57811 #057–
OSHA
“The Box” Meets Regulation 20, Part 1926, Subpart K Standards
STANDARDS & CERTIFICATIONS
NEMA ANSI UL UL CSA NOM
WD-6 C-73 943 Fed Spec C22.2
Class A Listed& 498 WC-596
U U U
†Consult Factory for Other Configurations.
Power Distribution Box Available with or without GFCI Protection on 30A Receptacles Consult Factory for Other Configurations
Power Inlet Power Outlet 6 NEMA Locking 6 NEMA Straight 1 NEMA Locking Catalogue No. Non-NEMA Non-NEMA Receptacles Blade Receptacles Receptacle
50A, 125/250V 50A, 125/250V 20A, 125V, L5-20R 20A, 125V, 5-20R 30A, 250V, L6-30R
PB101-SGF 4 4 4 4
PB101-000 4 4 4 4
PB103-SGF 4 4 4 4
PB103-000 4 4 4 4
No GFCI ProtectionNo GFCI Protection
No GFCI Protection
No GFCI Protection
No GFCI Protection
No GFCI Protection
No GFCI Protection
No GFCI Protection
GFCI Protection
GFCI Protection
GFCI Protection
GFCI Protection
GFCI Protection
No GFCI Protection
No GFCI ProtectionGFCI Protection
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
GFCI Accessories
F9
GFCIAc
cessor
ies
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
1 YEAR LIMITED
Single-Gang Flush Cover Wallplates
Raintight While-In-Use Covers
Surface-Mounted
Outdoor-Type Boxes
or Flush-Mounted
Wall Boxes
5977-CL 5977-GY 4992 4998-GY 5997-GY 5997-CL
3.75 (95.6 mm)
6.5
9 (
16
7.4
mm
)
3.30 (83.8 mm)
Ø 0.25 (16.0 mm)cord opening
5977
5.05 (128.3 mm)Ø 0.25 (6.4 mm)padlock opening
5.4
6 (
138
.7 m
m)
2.88 (73.2 mm)
Ø 0.63 (16.0 mm)cord opening
5997
TYPE MOUNTING POSITION SINGLE-GANG FITS
FLUSH COVER TYPE OF BOX
Gray Die-Cast Zinc Vertical 6196-V Standard
Gray Die-Cast Zinc Horizontal 6196 Standard
Gray Die-Cast Zinc Vertical 6196-VFS FS (4 Screws)
Gray Die-Cast Zinc Horizontal 6196-FS FS (4 Screws)
Gray Die-Cast Zinc Horizontal 4990 Standard
Gray Die-Cast Zinc Vertical 4992 Standard
Gray Plastic Horizontal 4996-GY Standard
White Plastic Horizontal 4996-W Standard
Gray Plastic Vertical 4998-GY Standard
White Plastic Vertical 4998-W Standard
TYPE MOUNTING POSITION SINGLE-GANG FITSFLUSH COVER TYPE OF BOX
Gray Plastic Vertical 5977-GY
Gray Plastic Vertical Mount w/ 5977-DGYExtra Deep Cover
Clear Plastic Vertical 5977-CL
Clear Plastic Vertical Mount w/ 5977-DCLExtra Deep Cover
Gray Plastic Horizontal 5997-GY
Gray Plastic Horizontal Mount w/ 5997-DGYExtra Deep Cover
Clear Plastic Horizontal 5997-CL
Clear Plastic Horizontal Mount w/ 5997-DCLExtra Deep Cover
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
SmartLockPRO™ Information
F10
SmartLockPRO™Information
To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: e www.leviton.com
Other GFCI manufacturers have taken the alternate route inthe 2006 UL Standard by providing an indicator light for end-of-life indication. They allow the compromised GFCI to bereset, thereby permitting it to continue delivering unprotect-ed power to the GFCI face and downstream receptacles. Wedisagree with this approach.
GFCIs are first and foremost proven safety devices. TheNational Electrical Code requires GFCIs to be installed inbathrooms, kitchens, workshops and other locations wherewater is present and there’s a risk of ground fault shock
hazard. Leviton believes that a GFCI should be replacedimmediately if it no longer provides ground fault protection.There is absolutely no people protection when a compro-mised GFCI functions as a “live” standard receptacle.
That’s why Leviton’s SmartLockPRO GFCI performs a self-test every time it is reset. If it is not capable of responding toa ground fault, the reset is blocked. Leviton’s SmartLockPRO approach locks out a compromised GFCI, thereby pro-viding the safest and smartest solution to people protection.
Underwriter’s Laboratories (UL) has issued newrequirements on GFCI functionality effective July 28, 2006:
Line-Load Reversal Indication
If an old style GFCI is miswired with a line-load reversal, itis a potentially hazardous situation because the GFCIreceptacle face will be live and unprotected even after theGFCI is tripped.
2003 UL Standard:• There must be a diagnostic indicator if a miswiring (line-
load reversal) occurs during installation. However, the GFCIreceptacle’s face may still be live and unprotected.
New UL 2006 Standard:• If a miswiring (line-load reversal) occurs during installation,
the GFCI must not be capable of supplying power to eitherthe GFCI’s face or to feed-through terminals.
The SmartLockPRO Solution:• SmartLockPRO provides a true dead-face design with an
LED indicator for line-load reversals.
“End-of-Life” Indication
GFCIs reach the end of their service life when they nolonger provide ground fault protection. As with any electronic device, a GFCI can be damaged by surges,other electrical disturbances, or environmental andphysical abuse.
2003 UL Standard:
• There are no requirements related to “end of life”
New UL 2006 Standard:
• GFCIs are required to provide a visual and/or audible indication OR be able to render themselves incapable ofdelivering power when they no longer offer ground faultprotection based on a failure to pass their internal test.
The SmartLockPRO Solution:
• Though a standard GFCI CAN be reset even if it is not pro-viding protection…the SmartLockPRO’s reset button will not engage if protection has been compromised. WithSmartLockPRO’s unique patented professional grade end-of-life lock-out action you can avoid having a live, unprotectedreceptacle in the event that the GFCI can no longer provideprotection. The robust design of SmartLockPRO GFCIs alsogreatly reduces the frequency of GFCI failures, contributing toa longer GFCI service life.
SmartLockPRO and The New 2006 UL943 GFCI Safety Standards
Non-Lockout Style GFCI SmartLockPRO GFCI
Plug a lamp or radio into the GFCI receptacle. Plug a lamp or radio into the GFCI receptacle.
Turn ON lamp or radio. Turn ON lamp or radio.
Push the TEST button on the GFCI. If the GFCI is working Push the TEST button on the SmartLockPRO GFCI. The properly, it will trip and power to the lamp or radio will GFCI will trip and power to the lamp or radio will be cut off.be cut off. Push reset button to restore power.
Your GFCI is working properly and should be retested every month.
If power did not go off: Your GFCI is working properly if you can push the RESET If power did not go off when you pushed the TEST button, button on the SmartLockPRO GFCI to restore powerthen the GFCI is not providing protection and should be to the lamp or radio.replaced immediately. Standard GFCIs can still be reset and provide power even though they are not providing IMPORTANT: The RESET button will not restore power if protection. the GFCI is damaged and cannot respond to a ground fault.
That’s why we developed SmartLockPRO…
The Choice for 2006 UL End-of-Life Indication: Protection or No Protection?
General Testing Procedures