GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: BUILDING PLUMBING NOTES: MECHANICAL AND PLUMBING SYMBOLS AND ABBREVIATIONS BUILDING MECHANICAL NOTES: UNITS - GENERAL MECHANICAL NOTES: UNITS - GENERAL PLUMBING NOTES: FIRE SPRINKLER NOTES: 6x8 LEGEND: DUCT LEAKAGE TEST: Project Number: Drawn By: Issue For 2014 JHP All Rights Reserved. All materials embodied herein constitute an original work by the Architect; the Architect owns all copyrights herein. The viewer may not reproduce, display or distribute this work or prepare derivative works based on this work without the express written consent of the copyright owner. Revision Date 9722-13 A PRICING SET 01-30-2014 B CITY COMMENTS 04-30-2014 Tarlton 360 Townhomes 2500 Walsh Tarlton Lane Austin, Texas 78746 Construction 08.31.2015 PHA MP0.00

Transcript of GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas...

Page 1: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS:

BUILDING PLUMBING NOTES:

MECHANICAL AND PLUMBING SYMBOLS AND ABBREVIATIONS

BUILDING MECHANICAL NOTES:

UNITS - GENERAL MECHANICAL NOTES:

UNITS - GENERAL PLUMBING NOTES:

FIRE SPRINKLER NOTES:

6x8

LEGEND:

DUCT LEAKAGE TEST:

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

PHA

MP0.00

Page 2: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

1" CW UP FROM

1ST FLOOR. REFER 1ST FLOOR

PLAN FOR CONTINUATION.

ROUTE CW PIPE IN 2ND FLOOR

CEILING SPACE.

1" CW AT

2ND FLOOR CEILING

(TYPICAL).

NOTE:

INSULATE ALL WATER PIPING EXPOSED TO FREEZING CONDITIONS.

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

DCO

4" SANITARY SEWER SERVICE U/G.

(DEMAND 80 D.F.U.)

INVERT BASED ON 1/4" SLOPE

PER FOOT @ 5.0' OUT FROM

BLDG. LINE: 4.3' B.F.F.

4"FD

4"

4" FIRE SERVICE

1" DOMESTIC WATER SERVICE

WITH SHUT-OFF VALVE.

DEMAND= 15 WSFU OR 11 GPM)

REFER SITE PLAN FOR CONTINUATION

(TYPICAL)

1" CW AT

CEILING.

1" GAS U/G

@ LESS THAN 2 PSI

GAS DEMAND 108.5 MBH

(TYPICAL)

1" GAS UP IN WALL TO

1ST FLOOR CEILING SPACE

(TYPICAL)

NFHB

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1" CW UP IN WALL TO

2ND FLOOR CEILING SPACE

REFER 2ND FLOOR PLAN

FOR CONTINUATION

(TYPICAL)

P

T3

P

T3

P

T5

P

T2

P

T1

P

T1

P

T1

P

T1

P

T8

P

T8

P

T8

P

T7

P

T7

P

T5

P

T4

P

T6

P

T5

P

T4

P

T5

P

T6

P

T7

P

T9

P

T9

P

T10

P

T10

P

T9

P

T9

P

T4

P

T6

P

T11

P

T3

P

T3

P

T2

P

T1

P

T1

P

T1

P

T1

P

T8

P

T8

P

T8

P

T7

P

T7

P

T5

P

T4

P

T6

P

T5

P

T4

P

T5

P

T6

P

T7

P

T3

P

T5

P

T5

P

T12

P

T2P

T1

P

T1

P

T8

P

T7

P

T5

P

T9

P

T9

P

T10

P

T10

P

T9

P

T9

P

T4

P

T6

P

T11

3"

3"

4"

4"

3"

3"

4"

3"

3"

3"

3"

3"

3"

3"

3"

3"

3"

3"

3"

3"

4"

3"

3"

4"

3"

4"

3"

4"4"

3"

3"

3"

3"

4"4"

3"

4"

4"

P

T12

P

T12

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

BY GAS UTILITY

COMPANY

MGM

GAS METER, PRESSURE REGULATOR,

AND SHUT OFF VALVES. REFER SITE

PLAN FOR LOCATION.

PROVIDE 2" LOW PRESSURE NATURAL

GAS-LESS THAN 2 PSI

0.5 IN. W.C. PRESSURE DROP,

0.60 SPECIFIC GRAVITY

GAS DEMAND-434 MBH

TOTAL DEVELOPED LENGTH

NOT TO EXCEED 250'

EF-3 EF-3 EF-3

1" GAS AT

CEILING SPACE

(TYPICAL)

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

MP2.16(B)

Page 3: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

DCO

1" DOMESTIC WATER SERVICE

WITH SHUT-OFF VALVE.

DEMAND= 15 WSFU OR 11 GPM)

REFER SITE PLAN FOR CONTINUATION

(TYPICAL)

1" CW UP IN WALL TO

1ST FLOOR CEILING SPACE

INSULATE ALL WATER PIPES

AT GARAGE CEILING SPACE.

(TYPICAL)

1" GAS UP IN WALL TO

1ST FLOOR CEILING SPACE

(TYPICAL)

4"FD

4" FIRE SERVICE

NOTE:

INSULATE ALL WATER PIPING EXPOSED TO FREEZING CONDITIONS.

1" CW AT

2ND FLOOR CEILING

(TYPICAL).

1" CW

1" CW

1" CW

1" CW

1" CW UP FROM

1ST FLOOR. REFER 1ST FLOOR

PLAN FOR CONTINUATION.

ROUTE CW PIPE IN 2ND FLOOR

CEILING SPACE.

P

T3

P

T5

P

T2

P

T1

P

T5

P

T3

P

T2

P

T3

P

T5

P

T2

P

T1

P

T5

P

T1

P

T3

P

T2

P

T1

P

T3

P

T8

P

T8

P

T6

P

T4

P

T5

P

T3

P

T1

P

T4

P

T5

P

T6

P

T1

P

T1

P

T6

P

T4

P

T9

P

T10

P

T9

P

T10

P

T9

P

T9

P

T4

P

T6

P

T6

P

T4

P

T9

P

T10

P

T9

P

T10

P

T9

P

T9

P

T4

P

T6

P

T3

P

T5

P

T2

P

T1

P

T5

P

T1

P

T3

P

T2

P

T1

P

T3

P

T8

P

T8

P

T6

P

T4

P

T5

P

T3

P

T1

P

T4

P

T5

P

T6

P

T12

3"

4"

3"

3"

4"4"

3"

4"

3"

4"

3"

4"

3"

4"

4"

3"

4"

3"

4"

4"4"

3"

3"

4"

3"

3"

3"

3"

4"

4"

3"

3

"

3"

3"

3"

3"

3"

3"

4"

3"

3"

3"

P

T12

P

T6

P

T12

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

BY GAS UTILITY

COMPANY

MGM

GAS METER, PRESSURE REGULATOR,

AND SHUT OFF VALVES. REFER SITE

PLAN FOR LOCATION.

PROVIDE 2" LOW PRESSURE NATURAL

GAS-LESS THAN 2 PSI

0.5 IN. W.C. PRESSURE DROP,

0.60 SPECIFIC GRAVITY

GAS DEMAND-434 MBH

TOTAL DEVELOPED LENGTH

NOT TO EXCEED 250'

EF-3 EF-3EF-3

EF-3

1" GAS U/G

@ LESS THAN 2 PSI

GAS DEMAND 108.5 MBH

(TYPICAL)

1" GAS AT

CEILING SPACE

(TYPICAL)

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

MP2.17(B)

Page 4: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

POWDER

GARAGE

STUDY

14'-0" x 10'-1"

ENTRY

FSC

UTILITY

DCO

4" SANITARY SEWER SERVICE U/G.

(DEMAND 60 D.F.U.)

INVERT BASED ON 1/4" SLOPE

PER FOOT @ 5.0' OUT FROM

BLDG. LINE: 3.9' B.F.F.

4"FD

4"

4" FIRE SERVICE

1" DOMESTIC WATER SERVICE

WITH SHUT-OFF VALVE.

DEMAND= 15 WSFU OR 11 GPM)

REFER SITE PLAN FOR CONTINUATION

(TYPICAL)

1" CW UP FROM

1ST FLOOR. REFER 1ST FLOOR

PLAN FOR CONTINUATION.

ROUTE CW PIPE IN 2ND FLOOR

CEILING SPACE.

(TYPICAL)

1" CW AT

2ND FLOOR CEILING

(TYPICAL).

1" GAS U/G

@ LESS THAN 2 PSI

GAS DEMAND 108.5 MBH

(TYPICAL)

1" GAS UP IN WALL TO

1ST FLOOR CEILING SPACE

(TYPICAL)

NFHB

NOTE:

INSULATE ALL WATER PIPING EXPOSED TO FREEZING CONDITIONS.

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1" CW UP IN WALL TO

2ND FLOOR CEILING SPACE

REFER 2ND FLOOR PLAN

FOR CONTINUATION

(TYPICAL)

P

T1

P

T2

P

T1

P

T8

P

T8

P

T7

P

T6

P

T4

P

T5

P

T5

P

T3

P

T1

P

T7

P

T1

P

T2

P

T1

P

T8

P

T5

P

T3

P

T7

P

T5

P

T5

P

T6

P

T4

P

T9

P

T9

P

T9

P

T10

P

T11

P

T12

P

T6

P

T4

P

T9

P

T9 P

T9

P

T10

P

T11

P

T12

P

T3

P

T6

P

T4

P

T9

P

T9

P

T1

P

T2

P

T1

P

T8

P

T8

P

T7

P

T6

P

T4

P

T5

P

T5

P

T3

P

T1

P

T7

P

T5

4"

3"

4" 4"

3"

4" 4"

3"

4"

3"

3"

4"

3"

3"

3"

4"

4"

4"

3"

3"

4"

4"

BY GAS UTILITY

COMPANY

MGM

GAS METER, PRESSURE REGULATOR,

AND SHUT OFF VALVES. REFER SITE

PLAN FOR LOCATION.

PROVIDE 1-1/2" LOW PRESSURE NATURAL

GAS-LESS THAN 2 PSI

0.5 IN. W.C. PRESSURE DROP,

0.60 SPECIFIC GRAVITY

GAS DEMAND-326 MBH

TOTAL DEVELOPED LENGTH

NOT TO EXCEED 175'

EF-3 EF-3

EF-3

1" GAS AT

CEILING SPACE

(TYPICAL)

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

MP2.18(B)

Page 5: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

DCO

4" SANITARY SEWER SERVICE U/G.

(DEMAND 60 D.F.U.)

INVERT BASED ON 1/4" SLOPE

PER FOOT @ 5.0' OUT FROM

BLDG. LINE: 3.9' B.F.F.

4"FD

4" FIRE SERVICE

1" DOMESTIC WATER SERVICE

WITH SHUT-OFF VALVE.

DEMAND= 15 WSFU OR 11 GPM)

REFER SITE PLAN FOR CONTINUATION

(TYPICAL)

1" GAS UP IN WALL TO

1ST FLOOR CEILING SPACE

(TYPICAL)

NOTE:

INSULATE ALL WATER PIPING EXPOSED TO FREEZING CONDITIONS.

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1" CW UP FROM

1ST FLOOR. REFER 1ST FLOOR

PLAN FOR CONTINUATION.

ROUTE CW PIPE IN 2ND FLOOR

CEILING SPACE.

(TYPICAL)

1" CW AT

2ND FLOOR CEILING

(TYPICAL).

1" CW UP IN WALL TO

2ND FLOOR CEILING SPACE

REFER 2ND FLOOR PLAN

FOR CONTINUATION

(TYPICAL)

P

T10

P

T6

P

T10

P

T6

P

T4

P

T1

P

T2

P

T3

P

T5

P

T6

P

T4

P

T9

P

T6

P

T9

P

T5

P

T2

P

T3

P

T4

P

T1

P

T4

P

T5

P

T6

P

T1

P

T7

P

T8

P

T5

P

T2

P

T3

P

T4

P

T4

P

T5

P

T6

P

T1

P

T7

P

T8

P

T5

P

T2

P

T3

P

T12

P

T12

P

T12

3"

4"

3"

4"

3"

4"

3"

3"

4" 4"

3"

4"

3"

4"

4"

3"

3"

4" 4"

3"

4"

3"

3"

4"

4"

4" 4"

3"

3"

3"

3"

3"

3"

3"

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

1ST FLOOR

UNIT

2ND FLOOR

UNIT

3RD FLOOR

UNIT

BY GAS UTILITY

COMPANY

MGM

GAS METER, PRESSURE REGULATOR,

AND SHUT OFF VALVES. REFER SITE

PLAN FOR LOCATION.

PROVIDE 1-1/2" LOW PRESSURE NATURAL

GAS-LESS THAN 2 PSI

0.5 IN. W.C. PRESSURE DROP,

0.60 SPECIFIC GRAVITY

GAS DEMAND-326 MBH

TOTAL DEVELOPED LENGTH

NOT TO EXCEED 175'

EF-3 EF-3EF-3

1" GAS AT

CEILING SPACE

(TYPICAL)

1" GAS U/G

@ LESS THAN 2 PSI

GAS DEMAND 108.5 MBH

(TYPICAL)

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

MP2.19(B)

Page 6: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

6

7

3

4

3

4

8

9

10

UNIT GAS KEYNOTES:

3/4" GAS LINE DN TO WATER HEATER IN LEVEL-1 (70,000 BTU)

1/2" GAS LINE UP TO DRYER IN LEVEL-1 ( 22,000 BTU)

1/2" GAS LINE DN TO RANGE IN LEVEL-2 ( 16,500 BTU)

3/4" GAS UP IN WALL TO LEVEL-2 CEILING SPACE.

G1

G2

G3

G4

1/2" GAS

1/2" GAS

13

1

3" FD

3/4" GAS

WH-3

UNIT WATER KEYNOTES:

1" DOMESTIC WATER SERVICE WITH SHUT-OFF VALVE

1" CW AND HW DN TO WATER HEATER

1/2" CW AND HW DN IN WALL TO WASHER BOX IN 1ST FLOOR

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW EACH TO LAV,

WC AND TUB, EXTEND 1/2" HW EACH TO LAV AND TUB IN 1ST

1/2" CW DN TO ICEMAKER

1

2

3

4

6

1/2" CW AND HW DN IN WALL TO LAV

ALL DOMESTIC WATER PIPING IN EXTERIOR WALLS AND

UNCONDITIONED SPACES TO BE INSULATED WITH

UNICELLULAR FOAM, FLEXIBLE R-4 PIPE INSULATION.

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV AND WC, EXTEND 1/2" HW LINE EACH TO LAV

10

FLOOR

1" CW AND HW UP IN WALL, TO 2ND FLOOR 5

7 1/2" CW AND 3/4" HW DN IN WALL TO SINK

8 1/2" CW DN IN WALL TO WC

9

1/2" CW AND HW DN IN WALL TO LAV IN 1ST FLOOR11

12 1/2" CW DN IN WALL TO WC IN 1ST FLOOR

1/2" CW AND HW DN IN WALL TO TUB13

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC AND TUB, EXTEND 1/2" HW LINE EACH TO LAV AND

14

TUB IN 3RD FLOOR

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC, SH AND TUB, EXTEND 1/2" HW LINE EACH TO LAV,

15

SH AND TUB

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

P3.03

Page 7: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

POWDER

GARAGE

STUDY

14'-0" x 10'-1"

ENTRY

FSC

UTILITY

WH-3

7

13

10

6

14

3

12

1

2

14

12

3" FD

G1

UNIT GAS KEYNOTES:

3/4" GAS LINE DN TO WATER HEATER IN LEVEL-2 (70,000 BTU )

1/2" GAS LINE DN TO DRYER IN LEVEL-1 ( 22,000 BTU)

1/2" GAS LINE DN TO RANGE IN LEVEL-2 ( 16,500 BTU)

G1

G2

G3

3/4" GAS

1/2" GAS

1/2" GAS

3/4" HW TO

AH UNIT

3

UNIT WATER KEYNOTES:

1" DOMESTIC WATER SERVICE WITH SHUT-OFF VALVE

1" CW AND HW DN TO WATER HEATER

1/2" CW AND HW DN IN WALL TO WASHER BOX IN 1ST FLOOR

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW EACH TO LAV,

WC AND TUB, EXTEND 1/2" HW EACH TO LAV AND TUB IN 1ST

1/2" CW DN TO ICEMAKER

1

2

3

4

6

1/2" CW AND HW DN IN WALL TO LAV

ALL DOMESTIC WATER PIPING IN EXTERIOR WALLS AND

UNCONDITIONED SPACES TO BE INSULATED WITH

UNICELLULAR FOAM, FLEXIBLE R-4 PIPE INSULATION.

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV AND WC, EXTEND 1/2" HW LINE EACH TO LAV

10

FLOOR

1" CW AND HW UP IN WALL, TO 2ND FLOOR 5

7 1/2" CW AND 3/4" HW DN IN WALL TO SINK

8 1/2" CW DN IN WALL TO WC

9

1/2" CW AND HW DN IN WALL TO LAV IN 1ST FLOOR11

12 1/2" CW DN IN WALL TO WC IN 1ST FLOOR

1/2" CW AND HW DN IN WALL TO TUB13

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC AND TUB, EXTEND 1/2" HW LINE EACH TO LAV AND

14

TUB IN 3RD FLOOR

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC, SH AND TUB, EXTEND 1/2" HW LINE EACH TO LAV,

15

SH AND TUB

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

P3.04(B)

Page 8: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

12

11

15

6

7

14

12

11

14

1

WH-3

2

3" FD

3/4" HWR FROM

AH UNIT TO WH

UNIT GAS KEYNOTES:

3/4" GAS LINE DN TO WATER HEATER IN LEVEL-1 (70,000 BTU )

1/2" GAS LINE UP TO DRYER IN LEVEL-1 ( 22,000 BTU)

1/2" GAS LINE DN TO RANGE IN LEVEL-2 ( 16,500 BTU)

3/4" GAS UP IN WALL TO LEVEL-2 CEILING SPACE.

G1

G2

G3

G4

1/2" GAS

1/2" GAS

5

5

G1

UNIT WATER KEYNOTES:

1" DOMESTIC WATER SERVICE WITH SHUT-OFF VALVE

1" CW AND HW DN TO WATER HEATER

1/2" CW AND HW DN IN WALL TO WASHER BOX IN 1ST FLOOR

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW EACH TO LAV,

WC AND TUB, EXTEND 1/2" HW EACH TO LAV AND TUB IN 1ST

1/2" CW DN TO ICEMAKER

1

2

3

4

6

1/2" CW AND HW DN IN WALL TO LAV

ALL DOMESTIC WATER PIPING IN EXTERIOR WALLS AND

UNCONDITIONED SPACES TO BE INSULATED WITH

UNICELLULAR FOAM, FLEXIBLE R-4 PIPE INSULATION.

3/4" CW AND HW DN IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV AND WC, EXTEND 1/2" HW LINE EACH TO LAV

10

FLOOR

1" CW AND HW UP IN WALL, TO 2ND FLOOR 5

7 1/2" CW AND 3/4" HW DN IN WALL TO SINK

8 1/2" CW DN IN WALL TO WC

9

1/2" CW AND HW DN IN WALL TO LAV IN 1ST FLOOR11

12 1/2" CW DN IN WALL TO WC IN 1ST FLOOR

1/2" CW AND HW DN IN WALL TO TUB13

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC AND TUB, EXTEND 1/2" HW LINE EACH TO LAV AND

14

TUB IN 3RD FLOOR

3/4" CW AND HW UP IN WALL, EXTEND 1/2" CW LINE EACH TO

LAV, WC, SH AND TUB, EXTEND 1/2" HW LINE EACH TO LAV,

15

SH AND TUB

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

XX

P3.05(B)

Page 9: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

FIRE SERVICE LINE

(REFER TO SITE

PLAN FOR SIZE)

DIR

EC

TIO

N O

F F

LO

W

FINISHED FLOOR

PIPE SLEEVE

BACKFLOW FOR FIRE PROTECTION SHALL

BE DOUBLE CHECK DETECTOR

BACKFLOW PREVENTER

MODEL #WATTS 757DCDA

TO BE PROVIDED WITH A BADGER METER

AND REMOTE READER.

TO FIRE RISER

GALLONSTAG MODELMANUFACTURER

@90°F RISE

RECOVER

VOLTS/PH/HZAMPS(MBH)

1. WATER HEATER SHALL MEET STATE OF TEXAS LOW NOX REQUIREMENTS.

2. PROVIDE CONCENTRIC VENT TERMINATION KIT.

NATURAL GAS WATER HEATER SCHEDULE

FACTOR

A.O. SMITH70.000.5864WH-3 75

GPD - 75L

3 120/1/60

LOCATION

TOWN HOME (TH-2)

T&P LINE PIPING.

PROVIDE 3/4"Ø PIPE AT

TOP FLOOR AND INCREASE

(1) PIPE DIAMETER AT EACH

FLOOR BELOW PRIOR TO T&P

LINE CONNECTION.

TERMINATE PIPE AT FLOOR DRAIN

LOCATED AT THE FIRST FLOOR WITH

AIR GAP (SEE DETAIL THIS SHEET).

GAS PIPE TO WH

GAS

COCK

WATER FAUCETS.

HOT WATER LINE WILL BE PURGED OUT THE DOMESTIC

SHOULD FACE "DOWN". THIS INSURES THAT ANY AIR IN

NOTE: "T" CONNECTION TAKEN FROM HORIZONTAL HOT WATER LINE

HW TO SYSTEM

FLOW CONTROL

MODULE

EXPANSION

TANK

CW SUPPLY

CW TO SYSTEM

3"Ø INTAKE AND

EXHAUST PIPING.

PROVIDE CONCENTRIC

VENT TERMINATION

KIT.

HWR

P&T RELIEF VALVE.

SEE NOTE

AIR HANDLER

HW TO A/C

AQUATHERM

DRAIN PAN UNDER WATER

HEATER AND DRAIN LINE

WC-A

PLUMBING FIXTURE SCHEDULE

FLOOR DRAIN SHALL BE CAST IRON WITH MOUNTING FLANGE, INTEGRAL,

REVERSIBLE CLAMPING COLLAR, SEEPAGE OPENINGS AND A 4-INCH BY 4-INCH

STRAINER. STRAINER IS TO SATIN NICKEL BRONZE. FIXTURE TO BE WADE

#W1103-G4.

NON FREEZE WALL HYDRANT SHALL BE 1/2-INCH BY 4-INCH, AUTOMATIC

DRAINING, FREEZELESS WITH VACUUM BREAKER/BACKFLOW PREVENTER.

FIXTURE SHALL BE PROFLO FROST FREE SILLCOCK #AM72ASDP.

WATER CLOSET SHALL BE VITREOUS CHINA, HIGH EFFICIENCY (1.28 GPF), MEETS

EPA WATERSENSE CRITERIA, ELONGATED SIPHON ACTION JETTED BOWL.

FIXTURE SHALL BE AMERICAN STANDARD CADET 3 FLOWISE ELONGATED

MODEL# 2832.128.

FAUCET: SHOWER/TUB PRESSURE BALANCING MIXING VALVE AND TRIMS MOEN TL183EP

AND SHOWER HEAD MODEL #6306. FLOW IS LIMITED TO 1.75 GPM MAX

MEETS EPA WATERSENSE CRITERIA

REFER ARCHITECTURAL PLANS FOR FAUCET MOUNTING HEIGHT'S

DIMENSIONS: 60"L BY 30"W BY 15"H , STANDARD BATHTUB, LASCOAT GELCOAT FINISH,

FIBERGLASS REINFORCED POLYESTER, FULL SLIP-RESISTANT SURFACE AND END DRAIN

OUTLET. SUPPLIY W/ ALL NECCESSARY TRIMS.

MODEL: LASCO #2600-30

WATER CLOSET SHALL BE ADA COMPLIANT, VITREOUS CHINA, HIGH EFFICIENCY (1.28

GPF), MEETS EPA WATERSENSE CRITERIA, ELONGATED SIPHON ACTION JETTED BOWL.

FIXTURE SHALL BE AMERICAN STANDARD CADET 3 FLOWISE RIGHT HEIGHT ELONGATED

MODEL# 2835.128.

WC-B

SELF-RIMMING, ROUND COUNTER TOP SINK

VITREOUS CHINA, FRONT INTEGRAL OVERFLOW

NOMINAL DIMENSIONS OF 19" DIAMETER

BOWL SIZE: 15" WIDE, 12-1/8" FRONT TO BACK, 5-3/4" DEEP

FAUCET HOLES ON 4" CENTER

MODEL: GERBER #12-884

FAUCET: 4" CENTERSET

POLISHED CHROME

KNOB STYLE HANDLES

MEETS EPA WATERSENSE CRITERIA

MODEL: CFG #4920 SERIES. FLOW IS LIMITED TO 1.0 GPM

LAV-A

ADA COMPLIANT LAVATORY SHOULD BE EQUAL WITH LAV-A WITH THE FOLLOWING

RESTRICTIONS:

SINK INSTALLED 2" FROM FRONT EDGE

FAUCET: ADA COMPLIANT

4" CENTERSET

POLISHED CHROME

LEVER TYPE HANDLES

50

50

POP UP DRAIN

MEETS EPA WATERSENSE CRITERIA

MODEL: CFG #CA41211 SERIES. FLOW IS LIMITED TO 1.0 GPM

AMERICAN STANDARD "LEDGELYN" MODEL# 3211.059; WITH FREEHAND

SENSOR-OPERATED FAUCET- BRASS CONSTRUCTION WITH MAX 0.5 GPM VANDAL

RESISTANT AERATOR. ADA COMPLIANT, MODEL "MOEN" MODEL # 8305(BATTERY), 8306

(AC). PROVIDE STOPS AND P TRAP

LAV-B

KORAL GELCOAT FINISH, FIBERGLASS REINFORCED POLYESTER

FAUCET: SHOWER/TUB PRESSURE BALANCING MIXING VALVE AND TRIMS MOEN 62320.

TUB-A

MODEL: KORAL INDUSTRIES TUB MODEL T0251LH/256RH

MODEL: MOEN T2133BN, SHOWER HEAD 6306. FLOW LIMITED TO 1.75 GPM MAX

OVAL BATHTUB, DIMENSIONS: 60"X42"

FULL SLIP-RESISTANT SURFACE

SUPPLIY W/ ALL NECESSARY TRIMS.

END DRAIN OUTLET.

TUB-B

SH-A

WHITE, ACRYLIC AND FIBERGLASS REINFORCEMENT

MODEL : VIGO VGO6019WHT3648L

TEXTURED BOTTOM, PRE-LEVELED WITH INTEGRAL TILE FLANGE ON 2 SIDES

LEFT-HAND DRAIN

SHOWER PAN 36" x 48" (REFER EXACT DIMENSIONS WITH ATCHITECT)

SLIP RESISTANT DESIGN

SHOWER PAN 60" X 36" (REFER EXACT DIMENSIONS WITH ATCHITECT)

HIGH GLOSS ACRYLIC BACKED WITH SOLID SURFACE

MODEL : AMERICAN STANDARD # CIENCIA 6036S1.STC WITH CENTER DRAIN

SH-B

FAUCET: SHOWER PRESSURE BALANCING MIXING VALVE AND TRIMS

SHOWER HEAD MODEL #6306. FLOW IS LIMITED TO 1.75 GPM MAX

MEETS EPA WATERSENSE CRITERIA

REFER ARCHITECTURAL PLANS FOR FAUCET MOUNTING HEIGHT'S

FAUCET: SHOWER PRESSURE BALANCING MIXING VALVE AND TRIMS

SHOWER HEAD MODEL #6306. FLOW IS LIMITED TO 1.75 GPM MAX

MEETS EPA WATERSENSE CRITERIA

REFER ARCHITECTURAL PLANS FOR FAUCET MOUNTING HEIGHT'S

SELF RIMMING, DOUBLE EQUAL BOWL, STAINLESS STEEL KITCHEN SINK

DIMENSIONS: 33"X22"X7"

MODEL: FHP #DS703BX

FAUCET: 8" CENTERSET

FINISH CHROME

LEVER STYLE HANDLES

MODEL: MOEN #7425

FLOW LIMITED TO 1.5 GPM WITH AERATOR #116711

REFER ARCHITECTURAL SPECIFICATIONS FOR GARBAGE DISPOSER

ADA COMPLIANT KITCHEN SINK

SELF RIMMING, DOUBLE EQUAL BOWL, STAINLESS STEEL KITCHEN SINK

DIMENSIONS: 33"X22"X6"

MODEL: FHP #PDS603

FAUCET: ADA COMPLIANT

8" CENTERSET

FINISH CHROME

LEVER STYLE HANDLES

MODEL: MOEN #7425

FLOW LIMITED TO 1.5 GPM WITH AERATOR #116711

REFER ARCHITECTURAL SPECIFICATIONS FOR GARBAGE DISPOSER

SINK-A

SINK-B

FLOW LIMITED TO 1.5 GPM WITH AERATOR #116711

SINK-C

1/2Ø

CLOSEST PLUMBING

FIXTURE STOP VALVE

1/2" TYPE "K" SOFT

TUBING TO TRAP PRIMER

CONNECTION ON FLOOR

DRAIN OR FLOOR SINK

3/4Ø

CW DROP IN WALL

TO WATER CLOSET

1/2" CW PIPING

CONCEALED IN WALL

"PPP" MODEL PR-500

TRAP PRIMER, EXPOSED

TO VIEW. PROVIDE C.P.

WALL ESCUTCHEONS AT

WALL PENETRATIONS

"PPP" MODEL AG-500

AIR GAP FITTING

1/2" CW PIPING

CONCEALED IN WALL

LAV-C

LOCHINVAR40.000.6041WH-4 40

PRN0-40 40

3 120/1/60

SINGLE BATH UNITS

A.O. SMITH40.000.5941WH-5 50

PRN050 40

3 120/1/60

DOUBLE BATH UNITS

File: ..\..\..\..\..\BLOCK\Plumbing\Grease Interceptor\2014-10-03 GREASE INTERCEPTOR FLUSH TO FLOOR INSIDE TRASH COMPACTOR.pdf

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015

Page 10: GENERAL MECHANICAL AND PLUMBING SPECIFICATIONS: …€¦ · 2500 walsh tarlton lane austin, texas 78746 construction 08.31.2015 xx mp2.16(b) dco 1" domestic water service with shut-off

5.0 D.F.U.

T10

P

2.0 D.F.U.

T9

P

4.0 D.F.U.

T11

P

2.0 D.F.U.

T1

P

3.0 D.F.U.

T4

P

2.0 D.F.U.

T8

P

2.0 D.F.U.

T12

P

1.0 D.F.U.

T6

P

2.0 D.F.U.

T5

P

9.0 D.F.U.

T2

P

7.0 D.F.U.

T3

P

5.0 D.F.U.

T7

P

* REFER TO PLANS FOR ACTUAL SIZES.

WATER CLOSET

KITCHEN SINK

BATHTUB/SHOWER

URINAL

HUB DRAIN *

LAVATORY

SHOWER

MINIMUM BRANCH

DRAIN SIZE

MINIMUM

TRAP SIZE

FIXTURE TYPE

MINIMUM

VENT SIZE

PLUMBING FIXTURE ROUGHIN SCHEDULE

DOMESTIC CLOTHES

WASHER

2"

DRINKING FOUNTAIN 1-1/4"

FLOOR DRAIN 2"

2"

2"

3"

1-1/2"

1-1/2"

1-1/4"

1-1/2"

2"

1-1/2"

2"

1-1/2"

1-1/2"

1-1/2"

2"

2"

3"

2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

1-1/2"

2"

BY GAS UTILITY

COMPANY

MGM

GAS METER, PRESSURE REGULATOR,

AND SHUT OFF VALVES

3" HEADER

PROVIDE 3" LOW PRESSURE NATURAL

GAS-LESS THAN 2 PSI

0.5 IN. W.C. PRESSURE DROP,

0.60 SPECIFIC GRAVITY

TOTAL DEVELOPED LENGTH

NOT TO EXCEED 300'

3/4"

3/4"

3/4"

3/4"

1"

M

WH-1

40 MBH

3/4"

3/4"

WH-1

WH-1

40 MBH

WH-1

40 MBH

1-1/4"

(160 MBH)

1

G

M

M

M

3/4"

3/4"

1"

M

WH-2

40 MBH

3/4"

3/4"

WH-2

WH-2

40 MBH

1-1/4"

(120 MBH)

2

G

M

M

3/4"

3/4"

3/4"

3/4"

1"

M

WH-2

40 MBH

3/4"

3/4"

WH-2

WH-2

40 MBH

WH-2

40 MBH

1-1/4"

(160 MBH)

3

G

M

M

M

40 MBH 40 MBH40 MBH

4.0 D.F.U.

40

P

8.0 D.F.U.

41

P

6.0 D.F.U.

42

P

3/4"

3/4"

WH-2

40 MBH

3/4"

(40 MBH)

4

G

M

B

E

4.0 D.F.U.

43

P

16.0 D.F.U.

44

P

Project Number:

Drawn By:

Issue For

© 2014 JHP

All Rights Reserved.

All materials embodied herein constitute an

original work by the Architect; the Architect

owns all copyrights herein. The viewer may

not reproduce, display or distribute this work

or prepare derivative works based on this

work without the express written consent of

the copyright owner.

Revision

Date

9722-13

A PRICING SET 01-30-2014

B CITY COMMENTS 04-30-2014

Tarlton 360 Tow

nhom

es

2500 W

alsh Tarlton Lane

Austin, Texas 78746

Construction 08.31.2015