General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53)...

6
General Specifications GX60 I/O Base Unit (Expandable I/O) GX90EX Expansion Module Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan GS 04L53B00-01EN GS 04L53B00-01EN ©Copyright April 2014 2nd Edition May. 7, 2014 OVERVIEW GX60 I/O Base Unit (Expandable I/O) The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20 using a LAN cable via a private communication network. One GX60 can connect up to six I/O modules. Up to six units can be additionally connected to the GX/GP. The communication distance between the GX/GP and GX60 or between GX60s can be extended by up to 100 m using a LAN cable. GX90EX Expansion Module The expansion module is connected to the GX10/ GX20/GP10/GP20 and GX60. The expansion module, which is supported by the GX/GP and GX60, enables a connection between GX/GP and GX60 or a communication between GX60s. A distributed arrangement with the data time synchronization secured is provided by connecting Expansion modules connected to the GX/GP main unit and GX60 using a LAN cable. Data is transferred to the high-order GX/GP via the expansion module. GX90EX GX60 Power inlet type Power Screw type

Transcript of General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53)...

Page 1: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

GeneralSpecifications

GX60I/O Base Unit (Expandable I/O)GX90EXExpansion Module

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

GS 04L53B00-01EN

GS 04L53B00-01EN©Copyright April 2014

2nd Edition May. 7, 2014

OVERVIEWGX60 I/O Base Unit (Expandable I/O)The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20 using a LAN cable via a private communication network.

● OneGX60canconnectuptosixI/Omodules.● Uptosixunitscanbeadditionallyconnectedto

the GX/GP.● Thecommunicationdistancebetweenthe

GX/GP and GX60 or between GX60s can be extendedbyupto100musingaLANcable.

GX90EX Expansion ModuleThe expansion module is connected to the GX10/GX20/GP10/GP20 and GX60.

● Theexpansionmodule,whichissupportedbythe GX/GP and GX60, enables a connection betweenGX/GPandGX60oracommunicationbetween GX60s.

● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesconnectedtotheGX/GPmainunitandGX60usingaLANcable.

● Dataistransferredtothehigh-orderGX/GPviatheexpansionmodule.

GX90EX

GX60 Power inlet type

Power Screw type

Page 2: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

2

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00

GX60 SPECIFICATIONSModule Connection

• I/Omodule:Max.6modules(Slots0to5)Restrictions:• Upto10GX90YDdigitaloutputmodules

andGX90WDdigitalinput/outputmodulescan be installed together in the GX/GP and GX60.

• OneGX90WDdigitalinput/outputmodulecan be installed in the GX/GP and in each GX60.

• Expansionmodule:1module(Slot("EXT")forconnectionwithExpansionmodule)

Names of Channels• ThemoduleinstalledintheGX60hasachannel

namethatconsistsoftheunitnumber,slotnumber,andchannelnumber.

012345

Channel name

Unit number

Slot number

Channel numberI/O modules

Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06Digital input/output: DI 01 to 08

DO 09 to 14Slot number; 0 to 5Unit number; 1 to 6

Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory

II *1, pollution degree 2 *2

• UL:UL61010-1(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1 Installation category II *1

Pollution degree 2 *2

• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1

• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient

overvoltagecondition. Impliestheregulationforimpulsewithstand

voltage. “II”appliestoelectricalequipmentwhich

issuppliedfromthefixedinstallationlikeadistribution board.

*2 Pollutiondegree2: Describesthedegreetowhichasolid,liquid,

or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate,aluminumalloy• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:412.5mm(W)x164.7mm(H)x127.8mm(D)

• Weight:Approx.3.2kg(installing6modules)

Power Supply• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,

180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:

Supply voltage Normal operation *

Maximum

100VAC 20VA 40VA

240VAC 30VA 55VA

* Whenusing6analoginputmodules.• Allowableinterruptiontime:Lessthan1cycleof

thepowersupplyfrequency

Page 3: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

3

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00

Isolation• Insulationresistance:BetweentheEthernet,

eachinsulationterminals,andearth:20MΩorgreaterat500VDC

• Withstandvoltage: Betweenthepowerterminalandearth:3000VACat50/60Hzforoneminute

Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.

• Grounding:Besuretosetalowgroundingresistance.

• Isolation:

Power terminal

The circuits divided by lines are insulated mutually.

Internal circuit

Ethernet portInput and output module terminal

Input and output module internal circuitEarth (PE) terminal

External DimensionsPowerscrewterminaltype

127.8 (5.03)

148

(5.8

3)

412.5 (16.2)162 (6.38)48 156 (6.14)

164.

7 (6

.48)

6-Φ5 hole(1.89)

8.7

(0.3

4)

(6-Φ0.2) hole

Power inlet type

127.8 (5.03)14

8±0.

4

162±0.2156±0.2 6-Φ4.5 hole or M4

Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).

(6.14±0.0078) (6.38±0.0078)

(5.8

3±0.

0157

)

(0.24-Φ0.18) hole or M4

148

(5.8

3)

412.5 (16.2)162 (6.38)48 156 (6.14)

8.7

(0.3

4)

164.

7 (6

.48)

6-Φ5 hole

Dimensions of fixing hole

(1.89)(6-Φ0.2) hole

Page 4: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

4

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00

Normal Operating Conditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)

(no condensation)• Magneticfield:400A/morless(DCand50/60

Hz)• Vibration:

5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2 or less• Shock(IEC-60068-2-27):

Non-energization,500m/s2orless,approximate10ms,6directions(±X,±Y,±Z)

• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.

• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower

on

Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no

condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

condition)

Effects of Operating Conditions• Powersupplyvariation:Shallsatisfythe

accuracyspecificationintherangeof90to132VACor180to250VAC(frequency:50/60Hz).Powersupplyfrequencyfluctuation:Shallsatisfytheaccuracyspecificationintherangeofratedsupplyfrequency+/-2Hz(power-supplyvoltage:100VAC).

GX90EX SPECIFICATIONSCommunication Functions CommunicationbetweenGX/GPandGX60or

betweenGX60sviadedicatedcommunicationnetwork.• Baudrate:10Base-T/100Base-TX(Auto)*1• Numberofports:2• Connectioncable:STPcable,CAT5orgreater• Inter-moduleconnection:Cascadeconnection

(Ring connection is disabled.)• Maximumcommunicationdistance:100m• Connector:RJ-45*1Canbefixedto10Base-TbyDIPswitchsettings.

Display Functions• SystemstatusLEDindicators: RDY(green):LightsupwhentheCPUisrunning

normally. MASTER(green):Turnsoninmastermodeand

offinslavemode. FAIL(red):Lightsupwhenasystemerror

occurs.• 7-segmentLEDindicator:Indicatesaunit

numberoroperationerror.• EthernetstatusindicatorLED:LINKACT(green),

SPEED(orange)

Address Setting Functions Switchsettings:

Switch No. Descriptions1 Forunitnumbersetting

2

3

4

5 -

6 -

7 10 Mpbs/100 Mbps

8 MASTER/SLAVE

Master / Slave FunctionsCanbesettomastermode(wheninstalledintheGX/GP),orslavemode(wheninstalledintheGX60)usingtheDIPswitches.

10 Mbps Fixed ModeCanbesettothe10MbpsfixedmodeusingtheDIPswitches.

MountingCanbemountedintheGX/GPandGX60.• Mountingposition: GX10/GP10:Slot2 GX20/GP20:Slot9 GX60:EXTslot

Page 5: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

5

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00

Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory

II *1, pollution degree 2 *2

• UL:UL61010-1(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1 Installation category II *1

Pollution degree 2 *2

• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1

• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient

overvoltagecondition. Impliestheregulationforimpulsewithstand

voltage. “II”appliestoelectricalequipmentwhich

issuppliedfromthefixedinstallationlikeadistribution board.

*2 Pollutiondegree2: Describesthedegreetowhichasolid,liquid,

or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

• WEEEDirective:Compliant

Construction• Frontpanel(terminal):Wateranddust-proof,

ComplieswithIEC529-IP20• Material:Polycarbonate• Color;

Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)

• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)

• Weight:Approx.0.18kg

Power Supply SuppyfromGX/GPmainunitorGX60expandable

I/O.• Powerconsumption:1.8Worless

External DimensionsUnit: mm (approx. inch)

45.1(1.78)

107.

1

3(0.

12)

8(0.

31)10

0(3.

94)

31.9

82.1

(3.2

3)Normal Operating Conditions

• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)

(no condensation)• Magneticfield:400A/morless(DCand50/60

Hz)• Vibration(IEC-60068-2-6):

Power supply ON, 3 directions, 10 cycles, 1 oct/min(±10%)

5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2 (peak)• Shock(IEC-60068-2-27):

Non-energization,500m/s2,approximate10ms,6directions(±X,±Y,±Z),3timesineachdirection

• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontal.

• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpoweron

Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no

condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

condition)

Effects of Operating Conditions None

Page 6: General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53) • Dimensions: 412.5 mm(W) x 164.7 mm(H) x 127.8 mm(D) • Weight: Approx. 3.2 kg

6

All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00

MODEL AND SUFFIX CODESMODEL and SUFFIX Code (GX60)

Model Suffix Code DescriptionGX60 I/O Base Unit

Type -EX I/O Expansion

Area N General

Power supply 1 100VAC,240VAC

Power cord D Power cord UL/CSA standard

F PowercordVDEstandard

R Power cord AS standard

Q Power cord BS standard

H Power cord GB standard

N Power cord NBR standard

W Screwterminal(M3)*OneGX90EX(I/Oexpansionmodule)isprovided.MODEL and SUFFIX Code (GX90EX)

Model Suffix Code DescriptionGX90EX I/O Expansion Module

Port -02 2 ports

Type -TP1 Twisted Pair Cable

- N Always N

Area -N General

Test certificate (QIC, sold separately)When ordering the GX60, GX90EX gets its own QIC (one QIC per unit).Whenorderingtheexpansionmodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).

User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/

Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.

•SMARTDAC+isaregisteredtrademarkofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•EthernetisaregisteredtrademarkofXEROXCorporation.ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.