General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53)...
Transcript of General GX60 6SHFL¿FDWLRQV GX90EX Expansion Module · 2020. 4. 11. · Bezel: Smoke blue (CC53)...
GeneralSpecifications
GX60I/O Base Unit (Expandable I/O)GX90EXExpansion Module
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
GS 04L53B00-01EN
GS 04L53B00-01EN©Copyright April 2014
2nd Edition May. 7, 2014
OVERVIEWGX60 I/O Base Unit (Expandable I/O)The GX60 provides a function to expand an I/O module for recording and controlling, when it is connected to the expansion module that is connected to the GX10/GX20/GP10/GP20 using a LAN cable via a private communication network.
● OneGX60canconnectuptosixI/Omodules.● Uptosixunitscanbeadditionallyconnectedto
the GX/GP.● Thecommunicationdistancebetweenthe
GX/GP and GX60 or between GX60s can be extendedbyupto100musingaLANcable.
GX90EX Expansion ModuleThe expansion module is connected to the GX10/GX20/GP10/GP20 and GX60.
● Theexpansionmodule,whichissupportedbythe GX/GP and GX60, enables a connection betweenGX/GPandGX60oracommunicationbetween GX60s.
● AdistributedarrangementwiththedatatimesynchronizationsecuredisprovidedbyconnectingExpansionmodulesconnectedtotheGX/GPmainunitandGX60usingaLANcable.
● Dataistransferredtothehigh-orderGX/GPviatheexpansionmodule.
GX90EX
GX60 Power inlet type
Power Screw type
2
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00
GX60 SPECIFICATIONSModule Connection
• I/Omodule:Max.6modules(Slots0to5)Restrictions:• Upto10GX90YDdigitaloutputmodules
andGX90WDdigitalinput/outputmodulescan be installed together in the GX/GP and GX60.
• OneGX90WDdigitalinput/outputmodulecan be installed in the GX/GP and in each GX60.
• Expansionmodule:1module(Slot("EXT")forconnectionwithExpansionmodule)
Names of Channels• ThemoduleinstalledintheGX60hasachannel
namethatconsistsoftheunitnumber,slotnumber,andchannelnumber.
012345
Channel name
Unit number
Slot number
Channel numberI/O modules
Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06Digital input/output: DI 01 to 08
DO 09 to 14Slot number; 0 to 5Unit number; 1 to 6
Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory
II *1, pollution degree 2 *2
• UL:UL61010-1(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1 Installation category II *1
Pollution degree 2 *2
• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1
• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient
overvoltagecondition. Impliestheregulationforimpulsewithstand
voltage. “II”appliestoelectricalequipmentwhich
issuppliedfromthefixedinstallationlikeadistribution board.
*2 Pollutiondegree2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
• WEEEDirective:Compliant
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material:Polycarbonate,aluminumalloy• Color;
Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)
• Dimensions:412.5mm(W)x164.7mm(H)x127.8mm(D)
• Weight:Approx.3.2kg(installing6modules)
Power Supply• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,
180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:
Supply voltage Normal operation *
Maximum
100VAC 20VA 40VA
240VAC 30VA 55VA
* Whenusing6analoginputmodules.• Allowableinterruptiontime:Lessthan1cycleof
thepowersupplyfrequency
3
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00
Isolation• Insulationresistance:BetweentheEthernet,
eachinsulationterminals,andearth:20MΩorgreaterat500VDC
• Withstandvoltage: Betweenthepowerterminalandearth:3000VACat50/60Hzforoneminute
Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.
• Grounding:Besuretosetalowgroundingresistance.
• Isolation:
Power terminal
The circuits divided by lines are insulated mutually.
Internal circuit
Ethernet portInput and output module terminal
Input and output module internal circuitEarth (PE) terminal
External DimensionsPowerscrewterminaltype
127.8 (5.03)
148
(5.8
3)
412.5 (16.2)162 (6.38)48 156 (6.14)
164.
7 (6
.48)
6-Φ5 hole(1.89)
8.7
(0.3
4)
(6-Φ0.2) hole
Power inlet type
127.8 (5.03)14
8±0.
4
162±0.2156±0.2 6-Φ4.5 hole or M4
Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).
(6.14±0.0078) (6.38±0.0078)
(5.8
3±0.
0157
)
(0.24-Φ0.18) hole or M4
148
(5.8
3)
412.5 (16.2)162 (6.38)48 156 (6.14)
8.7
(0.3
4)
164.
7 (6
.48)
6-Φ5 hole
Dimensions of fixing hole
(1.89)(6-Φ0.2) hole
4
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00
Normal Operating Conditions• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)
(no condensation)• Magneticfield:400A/morless(DCand50/60
Hz)• Vibration:
5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2 or less• Shock(IEC-60068-2-27):
Non-energization,500m/s2orless,approximate10ms,6directions(±X,±Y,±Z)
• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.
• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower
on
Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
Effects of Operating Conditions• Powersupplyvariation:Shallsatisfythe
accuracyspecificationintherangeof90to132VACor180to250VAC(frequency:50/60Hz).Powersupplyfrequencyfluctuation:Shallsatisfytheaccuracyspecificationintherangeofratedsupplyfrequency+/-2Hz(power-supplyvoltage:100VAC).
GX90EX SPECIFICATIONSCommunication Functions CommunicationbetweenGX/GPandGX60or
betweenGX60sviadedicatedcommunicationnetwork.• Baudrate:10Base-T/100Base-TX(Auto)*1• Numberofports:2• Connectioncable:STPcable,CAT5orgreater• Inter-moduleconnection:Cascadeconnection
(Ring connection is disabled.)• Maximumcommunicationdistance:100m• Connector:RJ-45*1Canbefixedto10Base-TbyDIPswitchsettings.
Display Functions• SystemstatusLEDindicators: RDY(green):LightsupwhentheCPUisrunning
normally. MASTER(green):Turnsoninmastermodeand
offinslavemode. FAIL(red):Lightsupwhenasystemerror
occurs.• 7-segmentLEDindicator:Indicatesaunit
numberoroperationerror.• EthernetstatusindicatorLED:LINKACT(green),
SPEED(orange)
Address Setting Functions Switchsettings:
Switch No. Descriptions1 Forunitnumbersetting
2
3
4
5 -
6 -
7 10 Mpbs/100 Mbps
8 MASTER/SLAVE
Master / Slave FunctionsCanbesettomastermode(wheninstalledintheGX/GP),orslavemode(wheninstalledintheGX60)usingtheDIPswitches.
10 Mbps Fixed ModeCanbesettothe10MbpsfixedmodeusingtheDIPswitches.
MountingCanbemountedintheGX/GPandGX60.• Mountingposition: GX10/GP10:Slot2 GX20/GP20:Slot9 GX60:EXTslot
5
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00
Safety and EMC Standards• CSA:CSA22.2No.61010-1,installationcategory
II *1, pollution degree 2 *2
• UL:UL61010-1(CSANRTL/C)• CE: EMCdirective EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1 Lowvoltagedirective EN61010-1 Installation category II *1
Pollution degree 2 *2
• EMCRegulatoryArrangementinAustraliaandNewZealand(RCM):EN55011compliance,Class A Group 1
• KCmarking:Electromagneticwaveinterferencepreventionstandard,electromagneticwaveprotectionstandardcompliance*1 Installationcategory(overvoltagecategory)II: Describesanumberwhichdefinesatransient
overvoltagecondition. Impliestheregulationforimpulsewithstand
voltage. “II”appliestoelectricalequipmentwhich
issuppliedfromthefixedinstallationlikeadistribution board.
*2 Pollutiondegree2: Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.
• WEEEDirective:Compliant
Construction• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20• Material:Polycarbonate• Color;
Front:Charcoalgreylight(CC28) Bezel:Smokeblue(CC53)
• Dimensions:45mm(W)x100mm(H)x133mm(D)(D:includingterminalcover)
• Weight:Approx.0.18kg
Power Supply SuppyfromGX/GPmainunitorGX60expandable
I/O.• Powerconsumption:1.8Worless
External DimensionsUnit: mm (approx. inch)
45.1(1.78)
107.
1
3(0.
12)
8(0.
31)10
0(3.
94)
31.9
82.1
(3.2
3)Normal Operating Conditions
• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)
(no condensation)• Magneticfield:400A/morless(DCand50/60
Hz)• Vibration(IEC-60068-2-6):
Power supply ON, 3 directions, 10 cycles, 1 oct/min(±10%)
5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2 (peak)• Shock(IEC-60068-2-27):
Non-energization,500m/s2,approximate10ms,6directions(±X,±Y,±Z),3timesineachdirection
• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontal.
• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpoweron
Transport and Storage Conditions• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no
condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged
condition)
Effects of Operating Conditions None
6
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation GS 04L53B00-01EN May. 7, 2014-00
MODEL AND SUFFIX CODESMODEL and SUFFIX Code (GX60)
Model Suffix Code DescriptionGX60 I/O Base Unit
Type -EX I/O Expansion
Area N General
Power supply 1 100VAC,240VAC
Power cord D Power cord UL/CSA standard
F PowercordVDEstandard
R Power cord AS standard
Q Power cord BS standard
H Power cord GB standard
N Power cord NBR standard
W Screwterminal(M3)*OneGX90EX(I/Oexpansionmodule)isprovided.MODEL and SUFFIX Code (GX90EX)
Model Suffix Code DescriptionGX90EX I/O Expansion Module
Port -02 2 ports
Type -TP1 Twisted Pair Cable
- N Always N
Area -N General
Test certificate (QIC, sold separately)When ordering the GX60, GX90EX gets its own QIC (one QIC per unit).Whenorderingtheexpansionmodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).
User's ManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL: www.smartdacplus.com/manual/en/
Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.
•SMARTDAC+isaregisteredtrademarkofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•EthernetisaregisteredtrademarkofXEROXCorporation.ModbusisaregisteredtrademarkofAEGSchneider.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.