GENERAL ELECTRICAL NOTES

1
9 ELECTRICAL LUMINAIRE/SYMBOL SCHEDULE AND DETAILS GENERAL ELECTRICAL NOTES 7. NO ALUMINUM CONDUIT OR CONDUCTORS WILL BE ACCEPTED. 6. ALL DEVICE COVER PLATES TO BE 305 STAINLESS STEEL. 4. CEILING (B) CONTRACTOR TO MAKE FINAL CONNECTIONS OF CONDUCTORS. 3. CONTROLS 1. WALK-IN FREEZERS AND COOLERS PROVIDE AND INSTALL A SUITABLE LENGTH OF S.T.O. CORD FROM EACH PRE-WIRED JUNCTION BOX OF EVAPORATOR COIL, TO POWER RECEPTACLE CORD TO BE EQUIPPED WITH A HUBBLE #7311 CAP AND SUITABLE FOR CONNECTION TO A #7310 RECEPTACLE. (A) CONTRACTOR TO PROVIDE AND INSTALL ALL CONDUIT AND CONDUCTORS FROM THERMOSTATS, FIRESTAT, HUMIDSTAT AS SHOWN ON DRAWINGS. CONTRACTOR TO REFER TO REFLECTED CEILING PLAN FOR EXACT LOCATION OF LIGHTING FIXTURES, AIR CONDITIONING DIFFUSERS, SPRINKLER SYSTEM, ETC. 8. ALL LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED BY PUBLIX AND INSTALLED AND WIRED BY CONTRACTOR. 11. EMERGENCY GENERATOR 10. FIRE ALARM (A) CONTRACTOR TO INSTALL AND CONNECT AUTOMATIC TRANSFER 9. ALL SUPPLY AND EXHAUST FANS TO BE FURNISHED AND INSTALLED BY OTHERS WIRED AND CONNECTED BY ELECTRICAL CONTRACTOR 12. DO NOT USE MACHINE ROOM ROOF STRUCTURE FOR SUPPORTING OF ANY ELECTRICAL EQUIPMENT, SUCH AS CONDUIT OR LIGHTING FIXTURES, USE UNI-STRUT WELDED TO OR CONNECTED TO BEAMS. 14. ALL CONDUIT ROUTING SHOWN SOLID TO BE FED CONCEALED ABOVE CEILING. ALL CONDUIT ROUTING SHOWN WITH DASH LINES TO BE CONCEALED WITHIN WALLS OR BENEATH SLAB. (C) FIRE ALARM SYSTEM SHALL MEET ALL LOCAL REQUIREMENTS, NFPA NO. 72. AND ADA. 13. CONTRACTOR TO PROVIDE PULL CORD IN ALL EMPTY CONDUITS, (ELECTRICAL. TELEPHONE, COMMUNICATIONS, ETC.) FOR FUTURE USE, TERMINATE CORD WITH SUITABLE SIZE WASHER TO PREVENT SLIPPAGE AND PROVIDE BLANK COVERS FOR ALL BOXES NOT USED. ALL CONUITS TO HAVE BUSHINGS TO PREVENT CABLING DAMAGE. 15. ALL CIRCUITS TO INCLUDE EQUIPMENT GROUND CONDUCTOR SIZED PER ARTICLE 250 OF 1999 NFPA 70. ISOLATED GROUND CONDUCTOR (WHERE REQUIRED). ISOLATED GROUNDCONDUCTOR(IG) TO BE GREEN WITH YELLOW STRIP. (B) ALL FIRE ALARM EQUIPMENT WILL BE FURNISHED, INSTALLED AND CONNECTED BY FIRE ALARM CONTRACTOR. 2. NOT USED 5. NOT USED (A) INSTALL ALL CONDUIT AND OUTLET BOXES AS SHOWN ON FIRE ALARM DRAWING. SWITCHES AS FURNISHED BY PUBLIX AND INDICATED ON PLANS. (B) GENERATOR TRANSFER SWITCH ARE TO BE INSTALLED IN LOCATION AS SHOWN ON DRAWINGS AND TO MEET ALL LOCAL AND NATIONAL CODES. N.T.S. TYP. POWER POLE INSTALLATION DETAIL UNSWITCHED POWER TRACK (CASE POWER) TYP. POWER BOX SUPPLIED WITH POWER GRID - INSTALLED BY CONTRACTOR POWER GRID SUPPORT (INSTALL NO MORE THAN 8 FOOT ON CENTER) EXISTING LITELAB CRISS-CROSS BRACKET N.T.S. 4 PARALLEL BUSRUN TRACK POWER POLE COVER WITH RECEPTACLE KNOCKOUTS TO BE MTD. ON FRONT OF POLE - OPPOSITE POWER CONDUCTOR COMPARTMENT COMMUNICATION/DATA COMPARTMENT FOR SCALE CABLE SECURE POWER POLE TO FLOOR AND CAULK WITH SILICON TO FLOOR LAY-IN CEILING (TYP.) CONTRACTOR TO SECURE POWER POLE AS PER MANUFACTURERS RECOMMENDATIONS COMMUNICATION CONDUIT (MIN. SIZE AS INDICATED ON E-6 & CONDUCTORS AS INDICATED ON DWG. E-6 FLEX CONDUIT TO POWER POLE CONTRACTOR TO INSTALL CONDUCTORS AS INDICATED ON E-03 THRU FACTORY SUPPLIED J-BOX TO RESPECTIVE PANEL IN 1"C (MAX.). CONDUIT QTY. MAY VARY. CONTRACTOR TO MOUNT J-BOX AT TOP OF POWER POLE. CONTRACTOR TO PROVIDE & INSTALL DIVIDED POWER POLE (WIREMOLD #PUBNP600-12-8X (12’-8") OR #PUBNP600-15-2X (15’-2") ) & RECEPT.S AS INDICATED ON DWG. E-03 (KNOCK OUTS PROVIDED). COORD. EXACT LOCATION OF POLES WITH PUBLIX REP. PRIOR TO FINAL INSTALL - ALL POLES ARE TO BE INSTALLED SO PLUGS ARE PARALLEL WITH TO REAR OF CASE OR SERVICE LINE-UP. CALL WES TURNIPSEED AT UNITED ELECTRICAL SALES (888 475 1326) FOR ORDER ASSISTANCE IF NEEDED. SWITCHED LIGHTING TRACK (ACCENT LIGHTING) BLANK POWER POLE COVER TO BE INSTALLED ON BACK OF POLE TO CLOSE OFF POWER CONDUCTOR COMPARTMENT POWER CONDUCTORS TO BE RUN IN POWER CONDUCTOR COMPARTMENT AND BROUGHT THROUGH POWER POLE SPINE TO MAKE CONNECTION TO RECEPTACLES AS REQUIRED BOLTED TO JOIST CONNECTOR EXISTING STEEL JOIST AND ROOF DECK VARIES 6" VARI ES C L 2 N.T.S TYP. E.D.F RECEPTACLE MOUNTING DETAIL N.T.S TYP. PENDANT HUNG RECEPTACLE CORD & RECEPT. ASSEMBLY (SEE SYMBOL SCHEDULE) RECEPT. @ +3’-0" STRAIN RELIEF RIGID NIPPLE AND COUPLING CADDY CLIP CLG. TEE CLG. BD. 4" x 4" J-BOX TYP. ELECTRIC WATER COOLER (E.D.F.) SUPPLIED BY OTHERS TYP. RECEPTACLE LOCATION (ELEC. CONTRACTOR TO VERIFY ALL DIMENSIONS AND COORDINATE WITH PLUMBING CONTRACTOR) 3 1 AREAS OF HORIZONTAL RUNS BY TRADES ELECTRICAL: TOP OF STEEL GIRDER AND JOIST TO 32 IN. BELOW TOP OF STEEL; WHERE EXPOSED IN THIS PROTOTYPE, IMMEDIATELY BENEATH TOP OF JOIST MEMBER AND PASSING BETWEEN STEEL JOIST WEBBING. (THE INSTALLATION SHALL BE IN COMPLIANCE WITH NEC 300.4(E)) REFRIGERATION: 32 IN. TO 36 IN. BELOW TOP OF STEEL GIRDER OR JOIST; WHERE EXPOSED IN THIS PROTOTYPE, IMMEDIATELY BELOW BOTTOM CHORD OF STEEL JOIST GIRDERS AND JOISTS. FIRE SPRINKLER: 8 IN. ABOVE CEILING; WHERE EXPOSED IN THIS PROTOTYPE, 8 IN. ABOVE BOTTOM CHORD OF STEEL GIRDER JOISTS AND JOISTS. AIR CONDITIONING: 36 IN. BELOW ROOF DECK TO 10 IN. ABOVE CEILING; WHERE EXPOSED IN THIS PROTOTYPE, HANG AS CLOSE UNDER BOTTOM CHORD OF STEEL JOIST GIRDERS AND JOISTS AS POSSIBLE WHILE LEAVING ROOM FOR REFRIGERATION LINES. IF DEVIATION FROM THESE AREAS IS INDICATED, SUCH DEVIATION MUST BE AGREED UPON BY JOB SUPERINTENDENT AND PUBLIX REPRESENTATIVE. E08.01 E08_01 17 SECTION ’A’ SECTION ’B’ MICROWAVE OPEN SPACE SINK & REFRIG. CABINET SECTION ’A’ SECTION ’B’ DEMO ISLAND ELEVATION 1 ’- 6" APRON’S KIOSK KEY PLAN F APRON’S KIOSK - DEMO ISLAND G APRON’S KIOSK - SINK & REFRIG CABINET 10:12 9 A B G F A B 13 13 13 19 5 SCALE: 1 2 "=1’-0" APRON’S KIOSK (F & G) L14 20 SPLIT 21,23 4" 4" 2" D E M O I S L AND CONTRACTOR SHALL DRILL 1" HOLE IN SIDE OF CABINET AS INDICATED CONTRACTOR SHALL DRILL 1" HOLE IN SIDE OF MILWORK WHERE INDICATED. PROVIDE 1" HOLE IN POWER POLE AT RESPECTIVE LOCATION 20A RATED TOGGLE SWITCH 20A RATED GFI RECEPT. WIREMOLD SERIES AMTC-4 ALUM. POWER POLE CONTRACTOR TO INSTALL 20A DUPLEX RECEPT.S IN MILLWORK (OPENINGS PROVIDED) GFI WIREMOLD SERIES AMTC-4 ALUM. POWER POLE. SECURE FLUSH TO MILLWORK RUN 4#10; 1#10(EG) IN " FMC DOWN INSIDE WIREMOLD SERIES AMTC-4 ALUM. POWER POLE. ROUTE FMC THROUGH 1" HOLE IN MILWORK TO RECEPT.s. - SECURE POWER POLE FLUSH TO MILLWORK, FLOOR, AND STRUCTURE. CONTRACTOR TO INSTALL 20A GFI DUPLEX RECEPT.S AND TOGGLE SWITCHIN MILLWORK (OPENINGS PROVIDED) DE S CRI P T I ON DATE MARK DE S CRI P T I ON DATE MARK RE V I S I ONS : PROFESSIONAL SEAL: 1 2 3 4 5 6 7 8 9 A / E OF RECORD: HECTOR E. VAZQUEZ FLORIDA P.E. NO. 66804 SHEET INFORMATION: JOB NO.: CHECKED BY: QC REVIEW: ORIGINAL DATE: 10/20/17 SHEET TITLE: NOT VALID FOR CONSTRUCTION UNLESS SIGNED IN THIS BOX 100056077 SHEET NUMBER: SHEET: OF S T O RE No . 0032 (I NTE RI O R RE M ODEL ) P ROJ E CT NA M E : CL I E NT : F BPE COA No . : 24 COA No . : AA000723 2001 NW 107 T H AVE. M I AM I , F L ORI DA 33172 - 2507 TEL : 305 . 592 . 7275 C OR P OR A TE OFF I C E S , A RC HI TE C T UR E DE P T . B OX 407 , L AK EL AND, F L 33802 TELE P HONE ( 941 ) 688 - 1188 10 11 13 14 15 16 17 18 12 2 1 3 4 5 5 4 3 2 1 A B C D E A B C D E DESIGNED/DRAWN BY: H.V. H.S. 08-ELEC\ 06-ELEC\ 0032- 44 R M ODEL : F I LE \ P A T H \ NA M E : G :\ B L DG S V C S \ C O MM ON \ P ub li x S up e r ma r k e t s \ 01 - P r o j ec t s \ 01 - R e mod e l s \ 0032 - 2017_100056077 \ I . P r odu c ti on \ 01 - Wo r k s e t\ 05 . B e n tl e y \ 12 S HO PP E S A T HA MM O CK COV E 4370 T HO M A SS ON DR NA P LE S , F L 34112 - 6725 H.V./O.R. Reviewed for Code Compliance PRBD20171042446

Transcript of GENERAL ELECTRICAL NOTES

9

ELECTRICAL

LUMINAIRE/SYMBOL

SCHEDULE AND DETAILS

GENERAL ELECTRICAL NOTES

7. NO ALUMINUM CONDUIT OR CONDUCTORS WILL BE ACCEPTED.

6. ALL DEVICE COVER PLATES TO BE 305 STAINLESS STEEL.

4. CEILING

(B) CONTRACTOR TO MAKE FINAL CONNECTIONS OF CONDUCTORS.

3. CONTROLS

1. WALK-IN FREEZERS AND COOLERS

PROVIDE AND INSTALL A SUITABLE LENGTH OF S.T.O. CORD FROM EACH

PRE-WIRED JUNCTION BOX OF EVAPORATOR COIL, TO POWER RECEPTACLE

CORD TO BE EQUIPPED WITH A HUBBLE #7311 CAP AND SUITABLE FOR

CONNECTION TO A #7310 RECEPTACLE.

(A) CONTRACTOR TO PROVIDE AND INSTALL ALL CONDUIT AND

CONDUCTORS FROM THERMOSTATS, FIRESTAT, HUMIDSTAT AS

SHOWN ON DRAWINGS.

CONTRACTOR TO REFER TO REFLECTED CEILING PLAN FOR EXACT

LOCATION OF LIGHTING FIXTURES, AIR CONDITIONING DIFFUSERS,

SPRINKLER SYSTEM, ETC.

8. ALL LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED BY PUBLIX AND

INSTALLED AND WIRED BY CONTRACTOR.

11. EMERGENCY GENERATOR

10. FIRE ALARM

(A) CONTRACTOR TO INSTALL AND CONNECT AUTOMATIC TRANSFER

9. ALL SUPPLY AND EXHAUST FANS TO BE FURNISHED AND INSTALLED BY OTHERS

WIRED AND CONNECTED BY ELECTRICAL CONTRACTOR

12. DO NOT USE MACHINE ROOM ROOF STRUCTURE FOR SUPPORTING OF ANY

ELECTRICAL EQUIPMENT, SUCH AS CONDUIT OR LIGHTING FIXTURES, USE

UNI-STRUT WELDED TO OR CONNECTED TO BEAMS.

14. ALL CONDUIT ROUTING SHOWN SOLID TO BE FED CONCEALED ABOVE

CEILING. ALL CONDUIT ROUTING SHOWN WITH DASH LINES TO BE

CONCEALED WITHIN WALLS OR BENEATH SLAB.

(C) FIRE ALARM SYSTEM SHALL MEET ALL LOCAL REQUIREMENTS,

NFPA NO. 72. AND ADA.

13. CONTRACTOR TO PROVIDE PULL CORD IN ALL EMPTY CONDUITS, (ELECTRICAL.

TELEPHONE, COMMUNICATIONS, ETC.) FOR FUTURE USE, TERMINATE CORD

WITH SUITABLE SIZE WASHER TO PREVENT SLIPPAGE AND PROVIDE BLANK

COVERS FOR ALL BOXES NOT USED. ALL CONUITS TO HAVE BUSHINGS TO

PREVENT CABLING DAMAGE.

15. ALL CIRCUITS TO INCLUDE EQUIPMENT GROUND CONDUCTOR SIZED PER

ARTICLE 250 OF 1999 NFPA 70. ISOLATED GROUND CONDUCTOR (WHERE

REQUIRED). ISOLATED GROUNDCONDUCTOR(IG) TO BE GREEN WITH YELLOW STRIP.

(B) ALL FIRE ALARM EQUIPMENT WILL BE FURNISHED, INSTALLED AND

CONNECTED BY FIRE ALARM CONTRACTOR.

2. NOT USED

5. NOT USED

(A) INSTALL ALL CONDUIT AND OUTLET BOXES AS SHOWN ON FIRE ALARM

DRAWING.

SWITCHES AS FURNISHED BY PUBLIX AND INDICATED ON PLANS.

(B) GENERATOR TRANSFER SWITCH ARE TO BE INSTALLED IN LOCATION

AS SHOWN ON DRAWINGS AND TO MEET ALL LOCAL AND NATIONAL CODES.

N.T.S.

TYP. POWER POLE

INSTALLATION DETAIL

UNSWITCHED

POWER TRACK

(CASE POWER)

TYP. POWER BOX SUPPLIED

WITH POWER GRID - INSTALLED

BY CONTRACTOR

POWER GRID SUPPORT

(INSTALL NO MORE THAN

8 FOOT ON CENTER)

EXISTING LITELAB

CRISS-CROSS

BRACKET

N.T.S.

4PARALLEL BUSRUN TRACK

POWER POLE COVER WITH

RECEPTACLE KNOCKOUTS

TO BE MTD. ON FRONT OF

POLE - OPPOSITE POWER

CONDUCTOR COMPARTMENT

COMMUNICATION/DATA

COMPARTMENT FOR

SCALE CABLE

SECURE POWER

POLE TO FLOOR

AND CAULK WITH

SILICON TO FLOOR

LAY-IN

CEILING (TYP.)

CONTRACTOR TO SECURE POWER

POLE AS PER MANUFACTURERS

RECOMMENDATIONS

COMMUNICATION CONDUIT

(MIN. SIZE AS INDICATED

ON E-6 & CONDUCTORS

AS INDICATED ON DWG. E-6

FLEX CONDUIT TO

POWER POLE

CONTRACTOR TO INSTALL CONDUCTORS

AS INDICATED ON E-03 THRU FACTORY

SUPPLIED J-BOX TO RESPECTIVE PANEL

IN 1"C (MAX.). CONDUIT QTY. MAY VARY.

CONTRACTOR TO MOUNT J-BOX AT TOP

OF POWER POLE.

CONTRACTOR TO PROVIDE & INSTALL DIVIDED

POWER POLE (WIREMOLD #PUBNP600-12-8X (12’-8")

OR #PUBNP600-15-2X (15’-2") ) & RECEPT.S AS

INDICATED ON DWG. E-03 (KNOCK OUTS PROVIDED).

COORD. EXACT LOCATION OF POLES WITH PUBLIX REP.

PRIOR TO FINAL INSTALL - ALL POLES ARE TO BE

INSTALLED SO PLUGS ARE PARALLEL WITH TO REAR OF

CASE OR SERVICE LINE-UP.

CALL WES TURNIPSEED AT UNITED ELECTRICAL

SALES (888 475 1326) FOR ORDER ASSISTANCE

IF NEEDED.

SWITCHED LIGHTING

TRACK (ACCENT LIGHTING)

BLANK POWER POLE COVER

TO BE INSTALLED ON BACK

OF POLE TO CLOSE OFF

POWER CONDUCTOR

COMPARTMENT

POWER CONDUCTORS TO BE

RUN IN POWER CONDUCTOR

COMPARTMENT AND BROUGHT

THROUGH POWER POLE SPINE

TO MAKE CONNECTION TO

RECEPTACLES AS REQUIRED

BOLTED TO JOIST

CONNECTOR

EXISTING STEEL JOIST

AND ROOF DECK

VARIES

6"

VA

RIE

S

CL

2N.T.S

TYP. E.D.F RECEPTACLE

MOUNTING DETAIL N.T.S

TYP. PENDANT

HUNG RECEPTACLE

CORD & RECEPT. ASSEMBLY

(SEE SYMBOL SCHEDULE)

RECEPT. @ +3’-0"

STRAIN

RELIEF

RIGID NIPPLE

AND COUPLING

CADDY CLIP

CLG. TEE

CLG. BD.

4" x 4" J-BOXTYP. ELECTRIC WATER COOLER

(E.D.F.) SUPPLIED BY OTHERS

TYP. RECEPTACLE LOCATION

(ELEC. CONTRACTOR TO VERIFY

ALL DIMENSIONS AND COORDINATE

WITH PLUMBING CONTRACTOR)

3

1

AREAS OF HORIZONTAL RUNS BY TRADES

ELECTRICAL: TOP OF STEEL GIRDER AND JOIST TO 32 IN. BELOW TOP OF STEEL;

WHERE EXPOSED IN THIS PROTOTYPE, IMMEDIATELY BENEATH TOP

OF JOIST MEMBER AND PASSING BETWEEN STEEL JOIST WEBBING.

(THE INSTALLATION SHALL BE IN COMPLIANCE WITH NEC 300.4(E))

REFRIGERATION: 32 IN. TO 36 IN. BELOW TOP OF STEEL GIRDER OR JOIST; WHERE

EXPOSED IN THIS PROTOTYPE, IMMEDIATELY BELOW BOTTOM CHORD

OF STEEL JOIST GIRDERS AND JOISTS.

FIRE SPRINKLER: 8 IN. ABOVE CEILING; WHERE EXPOSED IN THIS PROTOTYPE,

8 IN. ABOVE BOTTOM CHORD OF STEEL GIRDER JOISTS AND JOISTS.

AIR CONDITIONING: 36 IN. BELOW ROOF DECK TO 10 IN. ABOVE CEILING; WHERE

EXPOSED IN THIS PROTOTYPE, HANG AS CLOSE UNDER BOTTOM

CHORD OF STEEL JOIST GIRDERS AND JOISTS AS POSSIBLE

WHILE LEAVING ROOM FOR REFRIGERATION LINES.

IF DEVIATION FROM THESE AREAS IS INDICATED, SUCH DEVIATION

MUST BE AGREED UPON BY JOB SUPERINTENDENT AND PUBLIX

REPRESENTATIVE.

E08.01

E08_01

17

SECTION ’A’ SECTION ’B’

MICROWAVE

OPENSPACE

SINK & REFRIG. CABINET

SECTION ’A’

SECTION ’B’

DEMO ISLAND ELEVATION

1’-

6"

APRON’S KIOSK KEY PLAN

F APRON’S KIOSK - DEMO ISLAND G APRON’S KIOSK - SINK & REFRIG CABINET

10:12

9

A

B

G

F

AB

1313

13

19

5SCALE: 12"=1’-0"

APRON’S KIOSK (F & G)

L1420

SPLIT

21,23

4"

4"

2�"

DEMO ISLAND

CONTRACTOR SHALL

DRILL 1�" HOLE IN

SIDE OF CABINET AS

INDICATED

CONTRACTOR SHALL DRILL

1�" HOLE IN SIDE OF MILWORK

WHERE INDICATED. PROVIDE 1�"

HOLE IN POWER POLE AT

RESPECTIVE LOCATION

20A RATED

TOGGLE SWITCH

20A RATED

GFI RECEPT.

WIREMOLD SERIES

AMTC-4 ALUM. POWER

POLE

CONTRACTOR TO INSTALL 20A

DUPLEX RECEPT.S IN MILLWORK

(OPENINGS PROVIDED) GFI

WIREMOLD SERIES

AMTC-4 ALUM. POWER

POLE. SECURE FLUSH

TO MILLWORK

RUN 4#10; 1#10(EG) IN �" FMC DOWN INSIDE

WIREMOLD SERIES AMTC-4 ALUM. POWER

POLE. ROUTE FMC THROUGH 1�" HOLE IN

MILWORK TO RECEPT.s. - SECURE POWER POLE

FLUSH TO MILLWORK, FLOOR, AND STRUCTURE.

CONTRACTOR TO INSTALL 20A

GFI DUPLEX RECEPT.S AND

TOGGLE SWITCHIN MILLWORK

(OPENINGS PROVIDED)

DES

CRIP

TIO

ND

ATE

MA

RK

DES

CRIP

TIO

ND

ATE

MA

RK

RE

VISIO

NS:

PROFESSIONAL SEAL:

1 2 3 4 5 6 7 8 9

A / E OF RECORD:

HECTOR E. VAZQUEZ

FLORIDA P.E. NO. 66804

SHEET INFORMATION:

JOB NO.:

CHECKED BY:

QC REVIEW:

ORIGINAL DATE: 10/20/17

SHEET TITLE:

NOT VALID FOR CONSTRUCTION

UNLESS SIGNED IN THIS BOX

100056077

SHEET NUMBER:

SHEET: OF

ST

OR

E N

o. 0032 (IN

TE

RIO

R R

EM

OD

EL)

PR

OJE

CT N

AM

E:

CLIE

NT:

FB

PE C

OA N

o.: 2

4C

OA N

o.: A

A000723

2001 N

W 1

07T

H A

VE.

MIA

MI, F

LO

RID

A 33172-2

507

TE

L: 305.5

92.7

275

CO

RP

OR

ATE

OFFIC

ES,

AR

CHIT

EC

TU

RE

DEPT.

BO

X 407, LA

KELA

ND, FL 33802

TELEP

HO

NE (9

41)688-11

88

10

11

13

14

15

16

17

18

12

21 3 4 5

54321

A

B

C

D

E

A

B

C

D

EDESIGNED/DRAWN BY:

H.V.

H.S.

08-ELEC\ 06-ELEC\ 0032-

44

RM

OD

EL:

FILE\PATH\NAME: G:\BLDGSVCS\COMMON\Publix Supermarkets\ 01-Projects\ 01-Remodels\ 0032-2017_100056077\ I. Production\ 01-Workset\ 05.Bentley\

12

SH

OPP

ES A

T H

AM

MO

CK C

OV

E

4370 T

HO

MASS

ON D

R

NAP

LES, FL 3

4112-6

725

H.V./O.R.

Reviewed for CodeCompliance

PRBD20171042446