2012 Edition Redbook 41 11.0 GENERAL DRAWINGS AND STANDARDS Minimum Vertical Clearances Above Ground and Roofs ………………………………… D1 Minimum Pool Clearances …………………………………………………………………… D2 Minimum Clearances of Wires Adjacent to Buildings and Other Structures …………… D3 O.H. 100 – 400 Amp Mast Services ………………………………………………………… D4 O.H. 100 – 400 Amp Mast Service General Notes ……………………………………….. D5 Drop Swing Service for Inaccessible Service Entrance Attachment ……………………. D6 Pole Mounted Service 100 – 320 Amps ……………………………………………………. D7 Pole Mounted Service 400 Amps …………………………………………………………… D8 LIPA Connects Program Connector Installation …………………………………………… D9 400 – 600 Amp Open Wire Services ……………………………………………………….. D10 Customer Installed Cable Riser …………………………………………………………….. D11 Customer Installed Cable Riser General Notes …………………………………………… D12 Customer Installed Pull Box and Manhole Specifications ……………………………….. D13 U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D14 U.G. Service 100 – 800 Amp Single or Three Phase by Builder/Applicant ……………. D15 LIPA Installed Single Phase RUD Service ………………………………………………… D16 Customer Installed Single Phase Residential RUD Service …………………………….. D17 O.H. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D18 U.G. Single Phase Self Contained Meter Outdoor Socket Meter Installation …………. D19 O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D20 O.H. & U.G. Single Phase Self Contained Multi-meter Installation …………………….. D21 O.H. Service Poly-Phase Self Contained Meter Installation …………………………….. D22 U.G. Service Poly-Phase Self Contained Meter Installation …………………………….. D23 Clearances Between Electric & Gas Meters ……………………………………………… D24 Trough Supply Single and Poly-Phase Self Contained Meter Installations ……………. D25 Meter H-Frame Construction ……………………………………………………………….. D26 Electric Meter Room Equipment Clearances ……………………………………………… D27 400 – 800 Amp Trans-S Cabinet Installation ……………………………………………… D28 400 – 800 Amp Trans-S Cabinet Installation Notes & Bonding Diagram ……………… D29 Transformer Rated Meter Socket and Current Transformer Cabinet Installation …….. D30 400 – 1200 Amp Service Current Transformer Compartment Installation …………….. D31 1600 Amp Service and Above Current Transformer Compartment Installation ………. D32 Typical Grounding Requirements Single Meter and Main Installation ………………….. D33 Typical Grounding Details Multi-Meter & Multi-Main Installation ………………………… D34 Standby Generators ………………………………………………………………………….. D35

description

electrical construction drawing standard

Transcript of General Drawing and Standards

  • 2012 Edition Redbook

    41

    11.0 GENERAL DRAWINGS AND STANDARDS

    Minimum Vertical Clearances Above Ground and Roofs D1 Minimum Pool Clearances D2

    Minimum Clearances of Wires Adjacent to Buildings and Other Structures D3 O.H. 100 400 Amp Mast Services D4

    O.H. 100 400 Amp Mast Service General Notes .. D5 Drop Swing Service for Inaccessible Service Entrance Attachment . D6 Pole Mounted Service 100 320 Amps . D7 Pole Mounted Service 400 Amps D8 LIPA Connects Program Connector Installation D9 400 600 Amp Open Wire Services .. D10 Customer Installed Cable Riser .. D11 Customer Installed Cable Riser General Notes D12 Customer Installed Pull Box and Manhole Specifications .. D13 U.G. Service 100 800 Amp Single or Three Phase by Builder/Applicant . D14 U.G. Service 100 800 Amp Single or Three Phase by Builder/Applicant . D15 LIPA Installed Single Phase RUD Service D16 Customer Installed Single Phase Residential RUD Service .. D17 O.H. Single Phase Self Contained Meter Outdoor Socket Meter Installation . D18 U.G. Single Phase Self Contained Meter Outdoor Socket Meter Installation . D19 O.H. & U.G. Single Phase Self Contained Multi-meter Installation .. D20 O.H. & U.G. Single Phase Self Contained Multi-meter Installation .. D21 O.H. Service Poly-Phase Self Contained Meter Installation .. D22 U.G. Service Poly-Phase Self Contained Meter Installation .. D23 Clearances Between Electric & Gas Meters D24 Trough Supply Single and Poly-Phase Self Contained Meter Installations . D25 Meter H-Frame Construction .. D26 Electric Meter Room Equipment Clearances D27 400 800 Amp Trans-S Cabinet Installation D28 400 800 Amp Trans-S Cabinet Installation Notes & Bonding Diagram D29 Transformer Rated Meter Socket and Current Transformer Cabinet Installation .. D30 400 1200 Amp Service Current Transformer Compartment Installation .. D31 1600 Amp Service and Above Current Transformer Compartment Installation . D32 Typical Grounding Requirements Single Meter and Main Installation .. D33 Typical Grounding Details Multi-Meter & Multi-Main Installation D34 Standby Generators .. D35

  • MINIMUM VERTICAL CLEARANCES ABOVE GROUND AND ROOFS

    NOT ACCEPTABLE - SEE NOTE 2

    NOTES

    1. POINT OF SERVICE ATTACHMENT ON BUILDING WALL SHALL NOT BE LESS THAN 15'-0"ABOVE GRADE OR GREATER THAN 21'-0" WITHOUT ELECTRIC DESIGN AND CONSTRUCTIONEXPLICIT APPROVAL IN WRITING (SEE SECTION 4.2.2).2. SERVICE CONNECTIONS LOCATED ABOVE GARAGE OR OTHER BUILDING EXTENSION AS REPRESENTED

    IN FIGURE 1 ARE NOT ACCEPTABLE BECAUSE THE SERVICE CONNECTION CAN NOT BE DIRECTLYREACHED FROM A LADDER PLACED ON THE GROUND.

    3. CLEARANCES BETWEEN LIPA SERVICES AND VERIZON SERVICE LATERALS SHALL BE 2' MINIMUM.

    4. FOR COMMERCIAL DRIVEWAYS AND ANY OTHER LOCATIONS SUBJECT TO TRUCK TRAFFIC MINIMUM CLEARANCE SHALL BE 18'-0".

    6. ADD 6" TO ALL MINIMUM CLEARANCES FOR ANY OPEN WIRE CONSTRUCTION.

    OVER ROOF SURFACE IF ROOF CANNOTBE READILY WALKED UPON.

    SERVICE DROP, DRIP LOOP AND CONNECTION MUSTBE 3' MINIMUM FROM WINDOWS.

    3' MIN. FROM WEATHERHEAD, SERVICE DROP

    15' CLEARANCEOVER

    DRIVEWAYSROOF CAN BE READILYWALKED UPON.18'

    CLEARANCEOVERSTREETS

    12'OVERSIDE-WALKS

    12' OVER

    SPACESACCESSIBLEPEDESTRIAN12'

    FIGURE 1

    SERVICE DROP MUST BE 3' OR MORE

    10' IF

    FIGURE 2

    5. A 3' CLEARANCE IS REQUIRED FROM THE WEATHERHEAD AND/OR SERVICE DROP CONNECTIONS TOALL WINDOWS, DOORS, AND MOUNTINGS ON THE BUILDING WALL. POINT OF ATTACHMENT IS NOT

    RESIDENTIAL

    AND CONNECTIONS

    POINT OF ATTACHMENT NOTPERMITTED BELOW WINDOW

    PERMITTED BELOW A WINDOW.

    DWG. BASED ONLIPA CS 2701

    D1

    Section 11 - Drawings

  • LIPA BASES ITS REQUIRED CLEARANCES FROM SWIMMING POOLS AND ASSOCIATED STRUCTURESUPON THE REQUIREMENTS OF THE NATIONAL ELECTRICAL SAFETY CODE (NESC). WHERE WIRESCONDUCTORS OR CABLES CROSS OVER A SWIMMING POOL OR THE SURROUNDING AREA THE

    MINIMUM POOL CLEARANCES

    THESE CLEARANCE REQUIREMENTS DO NOT APPLY TO TYPE 1 AND TYPE 2 CABLES DESCRIBED ABOVETHAT ARE 10 FEET OR MORE HORIZONTALLY FROM THE EDGE OF THE POOL OR DIVING PLATFORM.

    DWG. BASED ONLIPA CS 2035

    A A

    B B

    A VV

    SUPPLY CABLES 0 TO 750v(OVERHEAD TRIPLEX ORQUADRAPLEX SECONDARYOR SERVICE WIRE)

    OPEN SUPPLY CABLES0 TO 750v (OVERHEADOPEN WIRE SECONDARYOR SERVICE)

    OPEN SUPPLY CABLES750v TO 22 kv(PRIMARY WIRE, BAREAND COVERED)

    MESSENGERS; SURGEPROTECTION WIRES;GROUNDED GUYS;GROUNDED NEUTRALCONDUCTORS

    CLEARANCE IN ANY DIRECTIONFROM THE WATER LEVEL, EDGEOF POOL, BASE OF DIVINGPLATFORM OR ANCHORED RAFT

    CLEARANCE IN ANY DIRECTIONTO THE DIVING PLATFORM ORTOWER

    VERTICAL CLEARANCE OVERADJACENT LAND

    2012 Edition Redbook

    D2

    (FEET) (FEET) (FEET) (FEET)A:

    B:

    V: CLEARANCE SHALL BE AS SHOWN ON DRAWING D1

    22.0 22.5 23.0 25.0

    14.0 14.5 15.0 17.0

    FIG. 1(NESC FIG. 234-3)SWIMMING POOL CLEARANCES

    TABLE 1

    CLEARANCES IN ALL DIRECTIONS SHALL NOT BE LESS THAN THOSE SHOWN IN TABLE 1 AND ILLUSTRATED IN FIG. 1, AND AS DESCRIBED IN THE NESC. LOCAL MUNICIPALITY MAY HAVE STRICTER POOL CLEARANCE REQUIREMENTS. FOR ADDITIONAL PUBLIC POOL REQUIREMENTS SEE SECT. 3.4

    HORIZONTALLY FROM THE INSIDE WALL OF A POOL, HOT TUB OR SPA. UNDERGROUND WIRING SHALL NOT BE LOCATED UNDER OR WITHIN AN AREA EXTENDING 5'

    TYPE 1: TYPE 2: TYPE 3: TYPE 4:

    WARNING: UNDER ON CIRCUMSTANCES SHOULD ANYONE, OTHER THAN LIPA PERSONAL ATTEMPT TO MEASURE CLEARANCES TO LIPA'S DISTRIBUTION SYSTEM.

  • BUT NOT ATTACHED TO BUILDINGS AND OTHER STRUCTURESMINIMUM CLEARANCES OF WIRES ADJACENT TO

    1. B

    UILD

    INGS

    :

    A. H

    ORIZ

    ONTA

    L

    (1)

    TO WA

    LLS, P

    ROJECT

    IONS

    AND

    GUAR

    DED

    WIND

    OWS

    (2) TO

    UNGUA

    RDED W

    INDOWS(3)

    TO BA

    LCONIE

    S AND

    AREAS

    REA

    DILY

    ACC

    ESSI

    BLE

    TO

    (1)

    OVER

    OR

    UNDE

    R RO

    OFS

    OR

    PRO

    JECT

    IONS

    NOT

    REA

    DILY

    ACC

    ESSI

    BLE

    TO P

    EDES

    TRIA

    NS

    (3) OV

    ER ROO

    FS ACC

    ESSIBL

    E TO

    VEH

    ICLE

    S BU

    T NO

    T SU

    BJEC

    T

    TO

    TRUC

    K TR

    AFFI

    C

    (4) OV

    ER ROO

    FS ACC

    ESSIBL

    E TO

    TRU

    CK T

    RAFF

    IC

    A

    CCES

    SIBL

    E TO

    PED

    ESTR

    IANS

    DEC

    KS A

    ND R

    OOFS

    REA

    DILY

    (2)

    OVER

    OR UND

    ER BAL

    CONIES

    B.

    VER

    TICA

    L

    2. S

    IGNS

    , CH

    IMNE

    YS,

    BILL

    BOAR

    DS, RA

    DIO

    AND

    TELE

    VISI

    ON A

    NTEN

    NAS,

    TA

    NKS

    AND

    OTHE

    R IN

    STAL

    LATI

    ONSNO

    T CL

    ASSI

    FIED

    AS

    BUIL

    DING

    S

    (1) RE

    ADILY

    ACCESS

    IBLE T

    O

    (2) OV

    ER OR

    UNDER

    PORTIO

    NS OF

    P

    EDES

    TRIA

    NS

    MESS

    ENGE

    RS,

    SURG

    E PR

    OTEC

    TIONWI

    RES,

    GRO

    UNDE

    D GU

    YS,GR

    OUND

    ED N

    EUTR

    AL C

    ONDU

    CTOR

    S

    SUPP

    LY C

    ABLE

    S OF

    0 T

    O 75

    0V(OV

    ERHEAD

    TRIPL

    EX ORQUA

    DRUPLE

    X)OP

    EN S

    UPPL

    Y CO

    NDUC

    TORS0

    TO 7

    50V(OV

    ERHEAD

    OPEN

    WIRE)

    OPEN

    SUP

    LY C

    ONDU

    CTOR

    S OV

    ER75

    0V T

    O 22

    kV(PR

    IMARY

    BARE O

    R TREE

    WIRE)

    CL

    EARA

    NCE

    OF

    4.5

    4.5

    4.5

    3.0

    10.5

    10.5

    15.5

    4.5

    3.0

    3.5

    5.0

    16.0

    11.0

    11.0

    3.5

    5.0

    5.0

    5.0

    6.0

    5.5

    16.5

    11.5

    11.5

    10.5

    5.5

    5.5

    5.5

    7.5

    7.5

    7.5

    12.5

    13.5

    13.5

    18.5

    7.5

    8.0

    VOLT

    AGES

    ARE

    PHA

    SE T

    O GR

    OUND

    FOR

    EFF

    ECTI

    VELY

    GRO

    UNDE

    D CI

    RCUI

    TS A

    ND T

    HOSE

    OTH

    ER C

    IRCU

    ITS

    WHER

    E AL

    L GR

    OUND

    FAU

    LTS

    ARECL

    EARE

    D BY

    PRO

    MPTL

    Y DE

    -ENE

    RGIZ

    ING

    THE

    FAUL

    TED

    SECT

    ION,

    BOT

    H IN

    ITIA

    LLY

    AND

    FOLL

    OWIN

    G SU

    BSEQ

    UENT

    BRE

    AKER

    OPE

    RATI

    ONS.TA

    BLE

    IS T

    AKEN

    FRO

    M NE

    SC 2

    34-1

    , SE

    E NE

    SC F

    OR D

    EFIN

    ITIO

    NS A

    ND C

    LARI

    FYIN

    G IN

    FORM

    ATIO

    N.

    ( FT )

    ( FT )

    ( FT )

    ( FT )

    DWG. BASED ONLIPA CS 2034

    Section 11 - Drawings

    D3

    (2) NO

    T READ

    ILY AC

    CESSIB

    LE TO

    3.0

    3.5

    5.5

    7.5

    A.

    HOR

    IZON

    TAL

    P

    EDES

    TRIA

    NS

    (1)

    OVER

    OR

    UNDE

    R SU

    RFAC

    E UP

    ON10

    .511

    .011

    .513

    .5

    PER

    SONN

    EL W

    ALK

    B. V

    ERTI

    CAL

    S

    UCH

    INST

    ALLA

    TION

    S

    PEDE

    STRI

    ANS

    OR B

    RIDG

    ES

  • OVERHEAD 100 - 400 AMP SERVICEUSING STRUCTURE SUPPORTED MAST(Sheet 1 of 2)

    10" MAX.

    6" MIN.

    SERV

    ICE

    MAST

    HEI

    GHT

    TABL

    E

    0' T

    O 3'

    -0"

    1

    . 4"

    x6"

    TREA

    TED

    STRU

    CTUR

    AL L

    UMBE

    R

    3

    . 3"x3

    "x1/2"

    GALV.

    STEEL

    ANGLE3'

    -0"

    TO 5

    '-0"

    1

    . 6"

    x6"

    TREA

    TED

    STRU

    CTUR

    AL L

    UMBE

    R

    2

    . 2 1/

    2" SCH

    D. 40

    GALV.

    STEEL

    PIPE

    3

    . 4"x4

    "x1/2"

    GALV.

    STEEL

    ANGLE

    2. 5

    "x5"x1

    /2" GA

    LV. ST

    EEL AN

    GLE5'-

    0" TO

    7'-6"

    1. 3

    1/2"

    SCHD.

    40 GAL

    V STEE

    L PIPE

    2. 6

    "x6"x1

    /2" GA

    LV. ST

    EEL AN

    GLE7'

    -6"

    TO 1

    0'-0

    "

    1. 4

    " SC

    HD.

    40 G

    ALV

    STEE

    L PI

    PE

    MAST

    LEN

    GTH

    ABOV

    EHI

    GHES

    T SU

    PPOR

    TST

    RUCT

    URAL

    MEM

    BERRE

    QUIR

    ED

    IF M

    INIM

    UM C

    LEAR

    ANCE

    CAN

    NOT

    BE

    MET

    USIN

    G AN

    Y OF

    THE

    ABO

    VECO

    NTAC

    T TH

    E LI

    PA E

    LECT

    RIC

    DESI

    GN &

    CON

    STRU

    CTIO

    N DE

    PT.

    STUD

    COND

    UIT

    TO M

    ETER

    GALV

    CON

    DUIT

    STR

    APEV

    ERY

    3'

    1/2" B

    OLTSTH

    ROUG

    H ST

    UD

    BLOC

    KING

    BET

    WEENRO

    OF R

    AFTE

    RS,

    2'-8"

    SIDI

    NGSOLI

    DLY

    INST

    ALLE

    D

    SEE MAST HEIGHT TABLE

    FIGU

    RE 1

    FIGU

    RE 2

    STUD

    COND

    UIT

    TO M

    ETER

    SIDI

    NG

    SEE MAST HEIGHT TABLE

    2'-6"

    THRO

    UGH

    STUD1/2

    " BOLT

    S

    EVER

    Y 3'GA

    LV C

    ONDU

    IT S

    TRAP

    10" MAX.

    6" MIN.

    SPAC

    ERSTRU

    CTUR

    ESU

    PPOR

    TED

    MAST

    ROOF

    ING

    SEE

    FIGU

    RE 2 G

    ABLE

    ROO

    F CO

    NSTR

    UCTI

    ONHI

    P RO

    OF C

    ONST

    RUCT

    ION

    SEE

    FIGU

    RE 1

    MAIN

    TAIN

    NOT

    LES

    S TH

    AN(3'

    -0") V

    ERTICA

    LCL

    EARA

    NCE

    ABOV

    E RO

    OFOUT

    SIDE O

    F (6'-

    0")RA

    DIUS

    FRO

    M TH

    ESE

    RVIC

    E MA

    ST.MA

    INTA

    IN N

    OT L

    ESS

    THAN(18

    ") VER

    TICALCL

    EARA

    NCE

    ABOV

    E RO

    OFINS

    IDE OF

    (6'-0

    ") RAD

    IUSFR

    OM T

    HE S

    ERVI

    CE M

    AST.

    4'MA

    X

    CLEA

    RANC

    ES O

    F SE

    RVIC

    E DR

    OP T

    ERMI

    NATI

    NG O

    N SU

    PPOR

    T MA

    ST4'

    (MAX)

    FROM N

    EAREST

    EDGE.

    6'-0

    "

    18"

    MIN

    SEE

    ADD

    ITIO

    NAL

    NO

    TES

    ON

    SH

    EET

    2 O

    F 2(

    D5)

    ROOF

    PLAN

    VIEW

    3'-0

    " MI

    N

    ELEV

    ATIO

    N

    6'-0

    "

    2. 2

    1/2"

    SCHD.

    40 GAL

    V. STE

    EL PIP

    E

    DWG. BASED ONLIPA CS 2721

    2012 Edition Redbook

    D4

  • NOTES:1. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME INTO CONTACT WITH ANY AWNINGS, SHUTTERS, OR ANY OTHER OBJECTS THAT MAY CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF 8' ABOVE FINISHED GRADE. FOR ADDITIONAL REQUIREMENTS SEE DWG. D18

    2. PVC CONDUIT IS NOT PERMITTED TO BE USED AS A MAST.

    3. CUSTOMER SHALL FURNISH MATERIAL AND LABOR FOR ALL WORK SHOWN, EXCEPT AS NOTED. ALL INSTALLATIONS ARE SUBJECT TO INSPECTION BY AN APPROVED INSPECTION AGENCY.

    4. THROUGH BOLTS ARE REQUIRED FOR ANCHORING ALL SERVICE MASTS. IN THE EVENT THAT A THROUGH BOLT CANNOT BE USED AN ADEQUATELY SIZED LAG SCREW MAY BE APPROVED IF IT CAN BE SHOWN THE SCREW IS SUPPORTED BY A SOUND STRUCTURAL MEMBER.

    5. FOR SOLID BLOCK OR BRICK WALL CONSTRUCTION THROUGH BOLTS SHALL BE SET IN BLOCK JOINTS THOROUGHLY EMBEDED IN MORTAR.

    6. FOR SELF SUPPORTING MAST SERVICES ALL PIPE COUPLINGS MUST BE BELOW THE HIGHEST STRUCTURAL ATTACHMENT POINT.

    7. MAST MUST BE OF SUFFICIENT STRENGTH TO SUPPORT A HORIZONTAL TENSION OF 1000LBS. APPLIED TO THE POINT OF

    ATTACHMENT. FOR UNUSUAL CIRCUMSTANCES GUYING OF THE MAST MAY BE PERMITTED. CONTACT LIPA'S ELECTRIC DESIGN & CONSTRUCTION DEPT. FOR GUYED MAST APPROVAL PRIOR TO INSTALLATION.

    USING STRUCTURE SUPPORTED MAST(Sheet 2 of 2)OVERHEAD 100 - 400 AMP SERVICE

    DWG. BASED ONLIPA CS 2721

    Section 11 - Drawings

    D5

    8. NO OTHER UTILITY MAY SUPPORT OR CONNECT AT THE MAST.

  • DROP SWING SERVICE FORINACCESSIBLE SERVICE ENTRANCE ATTACHMENT

    SERVICE MAST

    SERVICE ENTRANCE CABLE

    GUY WIRE

    SPLIT BOLT CONNECTOR, CONNECTLEAD OF GUY WIRE TO #14 LASHINGWIRE

    4" MAX.

    #14 SOLID COPPER WIREFOR LASHING SERVICE CABLETO GUY WIRE SERVICE CABLE TAPED

    @ END W/ SELF-SEALINGMATERIAL PER NEC

    SERVICE CONNECTORS

    TO POLE

    AUTOMATIC DEAD END

    PARALLEL NEUTRALCONNECTOR

    GUY GRIP FORGUY WIRE

    BAIL

    CONNECT GUY WIRE & #14LASHING TO NEUTRAL WIRE,EXTEND NEUTRAL FOR SERVICECONNECTION

    WORK BYCONTRACTOR LIPA

    WORK BY

    1/2" EYEBOLT

    6" M

    IN.10

    " MA

    X.

    22'-

    6"TO POLEH + 2' LIPA CONNECTION

    21'-

    0"MA

    X. H

    EIGH

    T OF

    LAD

    DERAC

    CESS

    IBLE

    SER

    VICE

    H

    H = HEIGHT BEYONDREACH OF SERVICELADDER

    POOL

    NOTE: ONLY TO BE USED WHERE NORMAL ACCESSIBLE SERVICE CONNECTION IS IMPOSSIBLE

    120' SPAN MAX.1/0-3/C AL (TYPICAL)

    3'-2" SAG AT 120' AT 90 F

    APPROVAL BY LIPA REQUIREDPRIOR TO INSTALLATION

    2012 Edition Redbook

    D6

  • UNDERGROUND/OVERHEAD 100 - 320 AMPPOLE MOUNTED SERVICE

    6" M

    IN.10

    " MA

    X.

    1/2" EYEBOLT

    LIPA SERVICE DROP

    CONDUIT SECUREDWITH STRAPS

    METER SOCKET

    MAIN DISCONNECTPANEL ( MAY BE LOCATED

    CUSTOMERS WIRES & POINTOF ATTACHMENT

    SERVICE POLE, MINIMUM25' - 30' CLASS 7PRESERVATIVE TREATED AND SETTO A MINIMUM DEPTH OF 6'-0"(CUSTOMER OWNED AND INSTALLED)

    6'-0" MIN.

    6'-0

    " MI

    N.

    1/2" X 8' CU WELD OR 5/8" X 8' CU PLATED

    GROUND WIRE, TWO SEPARATE GROUNDINGCONDUCTORS. GROUNDING MUST BE PERFORMEDAT THE MAIN DISCONNECT.

    LIPA METER

    3'-0

    " MI

    N.6'

    -0"

    MAX.

    21'-

    0" M

    AX.15

    '-0"

    MIN

    .

    NOTE:SERVICE POLE MUST BE ADEQUATELY GUYEDTO SUPPORT THE LOADS IMPOSED BY THELIPA SERVICE DROP. AT A MINIMUM THESERVICE POLE MUST BE GUYED WHEN SUPPORTING

    SERVICE SIZE(SINGLE PHASE)

    LIPA SERVICE DROP LENGTH

    100A NONE REQUIRED

    (POLE GUY REQUIRED)

    150A - 320A 60' - 100' (MAX)400A 0' - 60' (MAX)

    THE FOLLOWING SERVICE DROP LENGTHS:

    GROUND ROD GROUND ROD5/8" X 8' CU PLATED 1/2" X 8' CU WELD OR

    UNDERGROUNDLOAD SIDE EXIT

    DWG. BASED ONLIPA CS 2760

    Section 11 - Drawings

    D7

    AT SERVICE ENTRANCE)

    ALTERNATE OVERHEAD

    GUYWIRE (SEE NOTE)

    NOTE: USE OF PLYWOOD TO MOUNTMETER PAN IS NOT APPROVED

    USAGE EXAMPLES:. MOBILE HOME. CUSTOMER OWNED PERMANENT SERVICE. TEMPORARY SERVICE

  • OVERHEAD 400 AMPPOLE MOUNTED SERVICE

    6" M

    IN.10

    " MA

    X.

    LIPA SERVICE DROP

    CONDUIT SECUREDWITH STRAPS

    TRANS S CABINET

    SERVICE POLE, MINIMUM25' - 30' CLASS 7PRESERVATIVE TREATED AND SETTO A MINIMUM DEPTH OF 6'-0"(CUSTOMER OWNED AND INSTALLED)

    6'-0

    " MI

    N.

    LIPA METER

    4'-0

    " MI

    N.6'

    -0"

    MAX.

    POIN

    T OF

    ATT

    ACHM

    ENT

    21'-

    0" M

    AX.

    SEE

    DRAW

    ING

    D1 F

    OR M

    INIM

    UM S

    ERVI

    CE D

    ROP

    CLEA

    RANC

    ES

    NOTE:SERVICE POLE MUST BE ADEQUATELY GUYEDTO SUPPORT THE LOADS IMPOSED BY THELIPA SERVICE DROP. AT A MINIMUM THESERVICE POLE MUST BE GUYED WHEN SUPPORTING

    SERVICE SIZE(SINGLE PHASE)

    LIPA SERVICE DROP LENGTH(POLE GUY REQUIRED)

    400A 0' - 60' (MAX)

    THE FOLLOWING SERVICE DROP LENGTHS:

    LOAD SIDE EXIT

    DWG. BASED ONLIPA CS 2760

    4" X 6" TREATED

    POLE GUY

    3'-6

    " MI

    N.LUMBER POST

    MOUNT CABINET ON HORIZONTALTREATED LUMBER BRACES (3 MINIMUM)WITH LAG BOLTS.

    124072

    124072

    2012 Edition Redbook

    D8

    USE OF PLYWOOD IS NOT APPROVED

  • 6" M

    IN.10

    " MA

    X.

    LIPA CONNECTS PROGRAMCONNECTOR INSTALLATION

    1. CLEANING - WIRE BRUSH ALL COPPER AND ALUMINUM CONDUCTORS UNTIL SURFACES ARE BRIGHT AND CLEAN. COPPER CORROSION PRODUCTS ARE POOR CONDUCTORS AND ALUMINUM OXIDE, WHICH FORMS RAPIDLY AND IS INVISIBLE, IS AN INSULATOR. WIRE BRUSHING IS A VERY IMPORTANT AND CRITICAL STEP IN MAKING A TROUBLE FREE CONNECTION AND SHOULD NEVER BE NEGLECTED EVEN IF THE CONDUCTOR APPEARS TO BE CLEAN.

    2. INHIBITOR - ALL NEW CONNECTORS ARE PRE-LOADED WITH INHIBITOR. IF ANY CONNECTORS DO NOT HAVE INHIBITOR, IT MUST BE FIELD APPLIED.

    3. RE-USE OF CONNECTORS - WHEN CONNECTORS ARE REMOVED AND RE-INSTALLED IN THE FIELD (EVEN FOR A SHORT TIME), THE FOLLOWING STEPS SHALL BE TAKEN: 3.1 WIRE BRUSH BOTH THE CONDUCTOR AND THE JAWS OF THE CONNECTOR.

    3.2 FOR ALUMINUM TO ALUMINUM AND ALUMINUM TO COPPER CONNECTIONS, APPLY INHIBITOR TO CONDUCTORS AND WIRE BRUSH IN.

    3.3 FOR ALUMINUM TO COPPER CONNECTIONS, INSTALL THE ALUMINUM ABOVE THE COPPER CONDUCTOR.

    WEATHERHEAD

    1/2" EYEBOLT POINT OF ATTACHMENT

    LIPA SERVICE WIRE

    CONNECTORS, FURNISHED BY LIPA AND

    MUST BE NO GREATER THAN 24" HORIZONTALLY

    CONNECTOR INSTALLATION:

    INSTALLED BY THE CONTRACTOR

    USE CONNECTOR TO ATTACH CUSTOMERSNEUTRAL TO LIPA SERVICE NEUTRAL

    4. DO NOT TRANSFER SERVICE TO NEW POINT OF ATTACHMENT.

    Section 11 - Drawings

    D9

    FROM WEATHERHEAD

    DWG. BASED ON LIPA CS 2753

  • NOTES:

    1. OVERHEAD SERVICES WHICH ARE 400 AMPERES BUT NOT MORE THAN 600 AMPERES SERVED BY OVERHEAD CONDUCTORS SHALL USE OPEN WIRE CONSTRUCTION. IF THIS IS NOT ACCEPTABLE DUE TO HEIGHT OR APPEARANCE UNDERGROUND SERVICE SHOULD BE SELECTED.

    2. THE CUSTOMER IS TO INSTALL AND SUPPLY WEATHERHEAD, CONDUIT, CONDUIT STRAPS, SECONDARY RACK AND CABLES IN THE CONDUIT. CABLES SHALL BE SUFFICIENT LENGTH TO PROVIDE 48" OF SLACK CABLE AT WEATHERHEAD TO MAKE CONNECTIONS TO OVERHEAD SYSTEM.

    3. SERVICE ENTRANCE HEIGHT SHALL BE BASED ON 60'(FEET) MAXIMUM SPAN AND MAINTENANCE OF 16.5 FEET MINIMUM CLEARANCE ABOVE GROUND UNDER THE GREATEST SAG CONDITIONS AS WELL AS AN 18' MINIMUM CLEARANCE FOR AREAS SUBJECT TO VEHICULAR TRAFFIC. MAXIMUM HEIGHT FOR POINT OF

    LOCATION MUST BE APPROVED BY LIPA.

    4. SECONDARY RACK ON SUPPORTING STRUCTURE MUST BE THRU-BOLTED; ANY OTHER TYPE FASTENERS MUST BE APPROVED BEFORE INSTALLATION.

    OPEN WIRE SERVICES400 TO 600 AMP

    6" M

    IN.10

    " MA

    X.

    60' FEET MAXIMUMSEE NOTE 3

    124072

    124072

    124072

    UTILITYPOLECUSTOMER'SPOINT OF ATTACHMENT

    ATTACHMENT IS 21' ABOVE GRADE. INCREASED HEIGHT FOR ANY INDIVIDUAL

    8" TYPICAL

    DWG. BASED ONLIPA CS 2765

    2012Edition Redbook

    D10

    IMPORTANT NOTE: 600 AMP OVERHEAD SERVICE MUST FIRST BE APPROVED BY LIPA, AND MAY BE PERMITTED ON A CASE BY CASE BASIS ONLY. ALL SERVICES OF THIS TYPE MUST BE APPROVED BY LIPA PRIOR TO INSTALLATION.

  • CABLE RISERCUSTOMER INSTALLED

    COMMUNICATIONS LINE

    CURB

    TRAFFIC

    RISER

    RISER LOCATION ON POLE

    SEENOTE 4

    5'5'

    12"15

    '

    24" MINIMUM COVER FOR SECONDARY30" MINIMUM COVER FOR PRIMARY

    (DIRECT BURIED)

    FINAL GRADE

    FOR DIRECT BURIED CABLES

    IMPORTANT:

    UTILITY SPLICING CREWTO COMPLETE RISER POLE

    (SEE NOTE 6)

    SEE NOTE 3

    MIN.

    SEE SHEET D12 FOR NOTES

    FINAL GRADE

    PIPE

    CONDUIT"OR"

    1-1/

    2"10

    "MA

    X.

    IF CONDUIT IS USED A MANHOLE / SPLICEBOX

    (INCLUDING GROUNDING ANDBONDING MATERIAL)

    IS REQUIRED, SEE NOTE 7

    WARNING RIBBON

    RISER SHALL BE POSITIONED SO THERE IS ACLEAR VERTICAL PATH UP THE POLE TO

    LIPA'S SECONDARY WIRES.

    UNDER NO CIRCUMSTANCES SHALL AN EXISTING OVERHEAD SERVICE BE CONNECTED

    TO AN UNDERGROUND SERVICE.

    MULTIPLE SETS OF CABLE FEEDINGMULTIPLE SERVICES MUST BE CLEARLYIDENTIFIED.

    DWG. BASED ONLIPA CS 2403

    Section 11 - Drawings

    D11

  • NOTES:1. CONTRACTORS SHALL MOUNT ONLY THE UTILITY SPECIFIED RISER MATERIAL ON THE POLE, TO A HEIGHT OF 9 TO 10 FEET ABOVE GRADE. ONLY ONE RISER IS PERMITTED FOR EACH SERVICE.

    U-GUARD - 3" PE OR 3" PVC SCHD. 80 OR 3" DBL. GALV. STEEL - 10' LONG W/ BELL ENDS SECONDARY CABLE MAX. PRIMARY CABLE MAX

    4 - 1/C 350 KCM 3 - 2/C #1/0 AWG 5" DOUBLE GALVANIZED STEEL U-GUARD - 5' LONG W/ BELL ENDS or 5" PE or 5" PVC SCHD.80

    SECONDARY CABLE MIN. SECONDARY CABLE MAX. PRIMARY CABLE MAX. 8 - 1/C 4/0 8 - 1/C 500 KCM 3-2/C 750 KCM 2. A) THE LOCATION OF THE U-GUARD ON THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR OR THE LIPA REPRESENTATIVE ASSIGNED TO THE JOB PRIOR TO INSTALLATION OF THE CABLE / RISER. B) THE LENGTH OF THE CABLE REQUIRED FOR LIPA TO MAKE FINAL CONNECTIONS AT THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR BY THE LIPA REPRESENTATIVE.

    3. A) THE CABLE SUPPLIED BY THE CONTRACTOR FOR USE ON THE POLE SHALL BE INSTALLED AND PROPERLY SECURED TO THE POLE BY THE ELECTRICAL CONTRACTOR TO PREVENT DAMAGE AND/OR ANY ACTS OF VANDALISM FROM DAMAGING THE CABLE PRIOR TO HOOK-UP. B) CABLE IS TO BE ATTACHED TO THE POLE WELL ABOVE THE TOP OF THE RISER WITH A KELLUMS GRIP BASKET OR LENGTH OF LINE TIED IN A "ROLLING BEND KNOT" TO PROTECT THE CABLE FROM MECHANICAL BENDING DAMAGE.

    4. ALL CABLE SHALL BE PROPERLY END CAPPED AT BOTH ENDS BY THE CONTRACTOR WITH APPROVED TIGHTFITTING WATERTIGHT SEALING CAPS OR IN STRICT COMPLIANCE WITH NEC 300-5 (e). **

    6. LIPA SHALL COMPLETE THE CONSTRUCTION OF THE RISER PER THE APPROPRIATE CONSTRUCTION STANDARDS.

    7. IF CONDUIT IS USED, MANHOLES ARE REQUIRED, CONTACT LIPA FOR DETAILS.

    ** THE CONCERN FOR RELIABLE ELECTRIC SERVICE REQUIRES THAT LIPA RESERVE THE RIGHT TO REFUSE TO ACCEPT OR ENERGIZE ANY CABLES THAT HAVE BEEN LEFT WITH 'ENDS' UNCAPED. MOISTURE INTRUSION HAS BEEN DETERMINED TO BE A SUBSTANTIAL CAUSE OF PREMATURE CABLE FAILURES; UNCAPPED CABLE ENDS ARE THE LEADING CAUSE OF THIS PROBLEM.

    CUSTOMER INSTALLED CABLE RISERGENERAL NOTES

    5. POLYETHYLENE AND PVC U-GUARD SHALL BE FASTENED WITH 1/4" X 2 1/2" LAG SCREWS WITH CUSHION. STEEL U-GUARD SHALL BE FASTENED WITH 3/8" X 2 1/2" LAG SCREWS.

    DWG. BASED ONLIPA CS 2403

    2012 Edition Redbook

    D12

  • PULL BOX AND MANHOLE SPECIFICATIONSCUSTOMER / CONTRACTOR INSTALLED

    SERVICE TYPE

    SINGLE PHASEANDTHREE PHASE

    MAXIMUM CABLE SIZE

    1 SET OF 4/0

    BOX DESCRIPTION AND LOCATION

    PE SPLICE BOX IN GRASS AND NOVEHICLE TRAFFIC LOCATION

    SPLICE BOX / MANHOLE MINIMUMDIMENSIONS(LENGTH X WIDTH X DEPTH)

    (INCHES)BOX: 25 X 16 X 16COVER: 22 X 12

    BOX: 33 X 20 X 17COVER: 31 X 17

    BOX: 41 X 41 X 18COVER: 33 XX 33

    BOX ID: 42 X 33 X 24CAST IRON FRAME: 41 X 41CAST IRON COVER: 32 DIAMETER

    BOX ID: 54 X 42 X 48CAST IRON FRAME: 41 X 41CAST IRON COVER: 32 DIAMETER

    SINGLE PHASE2 SETS OF 4/0

    OR1 SET OF 500 KCM VEHICLE TRAFFIC LOCATION

    PE SPLICE BOX IN GRASS AND NO

    SINGLE PHASE 2 SETS OF 500 KCM OR VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO

    SINGLE PHASEANDTHREE PHASE

    4 SETS OF 4/0OR2 SETS OF 500 KCM

    PRECAST CONCRETE BOX TYPE B 3-6LOCATED IN GRASS OR VEHICLETRAFFIC AREA

    THREE PHASEANDSINGLE PHASE

    1 SET OF 3-2/C 1/0 AL 15KVOR

    6 SETS OF 4/0TRAFFIC AREALOCATED IN GRASS OR VEHICLEPRECAST CONCRETE BOX TYPE TS

    1. BOX / MANHOLE SHALL BE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.2. BOX / MANHOLE SHALL BE INSTALLED ON THE CUSTOMERS PROPERTY AT THE LOCATION WHERE THE SERVICE EXITS THE CUSTOMERS PROPERTY AND ENTERS THE PUBLIC RIGHT OF WAY OR LIPA EASEMENT AREA.

    3. INSTALL BOX / MANHOLE PARALLEL TO THE ROADWAY OR REAR PROPERTY EASEMENT LINE.4. FOR CONCRETE MANHOLES: ENTRANCE SHALL BE MADE THROUGH END WALL KNOCKOUTS ONLY. DUCT SHALL EXTEND A MAXIMUM OF 1" PAST THE INTERIOR FACE OF THE MANHOLE WALL. ALL PENETRATIONS THOUGH THE CONCRETE WALL SHALL BE SEALED WITH GROUT.

    5. FOR PE SPLICE BOXES: CONDUIT SHALL ENTER THE BOX BENEATH THE SIDE WALLS BY MEANS OF A CONDUIT SWEEP. CONDUIT SHALL EXTEND 2" ABOVE THE BOTTOM OF THE BOX.

    6. ALL CONDUITS SHALL BE SEALED AT THE BOX/MANHOLE AND BUILDING ENTRANCE USING PRODUCT SPECIFICALLY MADE FOR DUCT SEALING APPLICATION.

    7. BONDING BUSHING MUST BE SUPPLIED FOR METALLIC CONDUITS.

    INSTALLATION REQUIREMENTS:

    DWG. BASED ONLIPA CS 6159

    Section 11 - Drawings

    D13

    THREE PHASE 1 SET OF 500 KCMBOX: 41 X 41 X 18COVER: 33 X 33VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO

    BOX: 33 X 20 X 17COVER: 31 XX 17THREE PHASE 1 SET OF 4/0 VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO

    OR3 SETS OF 500 KCM

    8. 15KV PRIMARY CABLE INSTALLED IN TS BOX OR 41 X 41 X 18 PE BOX ONLY.

    2 SET OF 3-2/C 1/0 AL 15KVOR

    1 SET OF 1-2/C 1/0 AL 15KV

  • SECONDARY CONDUCTORS

    GRADE

    SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY

    SERVICE CONNECTION FROM PRIVATE PROPERTY - REAR PROPERTY POLE LINE

    DIRECT BURIED CABLE (U.S.E.-2)*INSTALLED -OWNED ANDMAINTAINED BY CUSTOMER

    RISER, SEE DWG. D11 & D12

    4"

    METER PAN *

    SLEEVE *2" MIN(SEE NOTE 4)2'-0" MINCOVER

    GRADEEASE

    MENTLI

    NE

    3'-0" MIN6'-0" MAX(SEE NOTE 5)

    1'-0" MIN1'-6" MAX

    UNDERGROUND SERVICE

    FOR REQUIREMENTS* SPLICE BOX REQD. IF

    SERVICE IS IN CONDUIT

    SERVICE CONNECTION FROM OVERHEAD DISTRIBUTION - NEAR SIDE HIGHWAY POLE LINE

    100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT

    5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO TOP

    3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS

    (SEE NOTE 4)2" MINSLEEVE *

    METER PAN *

    DIRECT BURIED CABLE (U.S.E.-2)*MAINTAINED BY CUSTOMERINSTALLED -OWNED AND

    ROAD SURFACE

    SECONDARY CONDUCTORS

    GRADE

    FOR REQUIREMENTSRISER, SEE DWG. D11 & D12

    TO LIPA SECONDARYSUFFICIENT CABLE TO CONNECT

    4"

    SERVICE IS IN CONDUIT* SPLICE BOX REQD. IF

    CURB

    LINEPR

    OPER

    TY

    3'-0" MIN

    1'-6" MAX1'-0" MIN

    (SEE NOTE 5)6'-0" MAX

    GRADE

    2'-0" MINCOVER

    NOTES

    TO CUSTOMERS PROPERTY LINE.

    1. * INDICATES ITEMS PROVIDED BY CUSTOMER.2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR

    AND THE REMAINDER TO BE COMPLETED BY LIPA.

    5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO

    3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS

    2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR AND THE REMAINDER TO BE COMPLETED BY LIPA.

    TO EASMENT LINE.

    NOTES1. * INDICATES ITEMS PROVIDED BY CUSTOMER.

    4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.

    4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.

    WARNING RIBBON

    WARNING RIBBON

    DWG. BASED ONLIPA CS 5523

    2012 Edition Redbook

    D14

    TOP OF METER GLASS.

    3'-0" MAX

    3'-0" MAX

    OF METER GLASS.

  • SECONDARY CONDUCTORS

    NOTES

    GRADE ROAD SURFACECURB

    SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY

    SERVICE CONNECTION FROM FAR SIDE - HIGHWAY POLE LINE

    CURB

    * MIN 2" GI OR SCHEDULE 40 NON-METALIC CUSTOMER INSTALLED

    DIRECT BURIED CABLE (USE-2)INSTALLED -OWNED ANDMAINTAINED BY CUSTOMER

    RISER, SEE DWG. D11 & D12

    4"

    METER PAN *

    SLEEVE *2" MIN(SEE NOTE 3)2'-0" MINCOVER

    GRADEPROP

    ERTYLI

    NE

    3'-0" MIN6'-0" MAX

    (SEE NOTE 4)

    1'-0" MIN1'-6" MAX

    * MIN 2" G.I. SWEEP OR SCHEDULE 80 NON METALIC SWEEP CUSTOMER INSTALLED

    DIRECT BURIED CABLE (USE-2)

    SLEEVE *

    METER PAN *

    (SEE NOTE 3)2" MIN

    MAINTAINED BY CUSTOMER

    1'-6" MAX1'-0" MIN

    INSTALLED -OWNED AND

    2'-0" MINCOVER

    LINEPROPERTY

    CURB

    NOTES

    6'-0" MAX3'-0" MIN

    (SEE NOTE 4)

    GRADE LINEROAD SURFACE

    SPLICE *BOX

    * SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY(LIPA TO PREPARE CONNECTION)

    SEE NOTES 1 & 2

    UNDERGROUND SERVICE

    FOR REQUIREMENTS

    1. * INDICATES ITEMS PROVIDED BY CUSTOMER.

    2. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS TO BASE OF POLE.

    4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT. TO TOP OF METER GLASS.

    * SPLICE BOX REQD. IFSERVICE IS IN CONDUIT

    1.CONDUIT AND SPLICE BOX WILL BE REQUIRED IN ZONED NETWORK AREAS, IN ZONED U.G. AREAS A SPLICE BOX MAY BE REQUIRED. IF SERVICE IS IN CONDUIT A SPLICE BOX IS REQUIRED.CONTRACTOR TO LEAVE 4' OF SERVICE CABLE IN SPLICE BOX

    2. WHERE NO SPLICE BOX IS REQUIRED, CONTRACTOR TO LEAVE THREE (3) FEET OF SERVICE CABLE (OR AS DIRECTED BY LIPA) FOR LIPA

    CONNECTIONS.

    4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT.

    5. * INDICATES ITEMS PROVIDED BY CUSTOMER.

    FOR LIPA CONNECTIONS.

    SERVICE CONNECTION FROM UNDERGROUND DISTRIBUTION - NEAR OR FAR SIDE FACILITIES

    100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT

    3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE

    SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD 80.3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE

    SCHD. 40 GALV., NON-METALLIC SHALL BESCHD 80.

    WARNINGRIBBON

    WARNING RIBBON

    DWG. BASED ONLIPA CS 5523

    Section 11 - Drawings

    D15

    3'-0" MAX

    TO TOP OF METER GLASS.

    3'-0" MAX

  • METER PAN *

    3" WATERTIGHT ADAPTOR *(CONDUIT TO METER)

    OR RIGID GALVANIZED

    (TO LIPA SPEC)

    3" SCHEDULE 80 PVC *

    FINAL GRADE

    CABLE-IN-CONDUIT

    24"

    MIN.

    6" TO 12"

    45*CUT CONDUIT @CONDUIT ENDDUCT SEAL

    LIPA INSTALLED SINGLE PHASE RESIDENTIAL RUD SERVICE

    36"

    MAX.

    NOTES:

    1. * INDICATES ITEMS PROVIDED BY CONTRACTOR.2. 300 AMP AND LARGER SERVICES MAY REQUIRE TWO CONDUITS INTO METER PAN.

    CABLE-IN-CONDUIT

    24"

    MIN.

    FINAL GRADE

    36"

    MAX.

    (CONDUIT TO METER)

    2" SCHEDULE 80 PVC *OR RIGID GALV. STEEL

    2" WATERTIGHT ADAPTOR *

    (TO LIPA SPEC)METER PAN *

    6"

    2" PVC OR RGS COUPLING*

    45 SWEEP*

    2" MECHANICALCOUPLING *

    AIM IN DIRECTIONOF SPLICE BOX

    3 INCH SERVICE RISER 2 INCH SERVICE RISER

    3. 2" MECHANICAL COUPLING SHALL BE EITHER ANACO P/N HUSKY SD-4006 OR FERNCO P/N 1056-22/SR-11.

    DWG. BASED ONLIPA CS 6491

    2012 Edition Redbook

    D16

  • SPLICE BOX

    IN CONDUIT

    COMM

    ON T

    RENC

    H

    CURB

    UTILITY CABLEIN CONDUIT

    CURBROAD

    ROAD

    SERVICE CONDUIT SYSTEM *

    COILED & COVEREDWITH 4'x4'x1/2" PLYWOOD* SEAL CABLE ENDS

    SCHD. 40 CONDUIT *DUCTSEAL CONDUIT *

    SEAL CABLE *ENDS

    PLYWOOD *

    24" MIN.

    SPLICE BOX

    PLAN VIEW

    UTILITY CABLE

    (TEMPORARY)

    24"

    * TERMINATE CONDUIT24" AWAY FROM SPLICEBOX ON CENTERLINE.

    TEMPORARY 48" x 48" x 1/2"

    (MIN. SCHD 40)

    10 FOOT MINIMUM CABLE *

    ANGLE OF APPROACH TO SPLICE BOXTO BE DETERMINED BY LOCAL FIELDCONDITIONS AND APPROVAL BY UTILITY.

    SINGLE PHASE RESIDENTIAL RUD SERVICECUSTOMER / CONTRACTOR INSTALLED

    NOTES:

    1. * DENOTES ITEMS PERFORMED BY CONTRACTOR / CUSTOMER.2. UTILITY CONNECTS CONDUIT TO SPLICE BOX AND MAKES SERVICE CONNECTIONS IN SPLICE BOX.

    ELEVATION VIEW

    3. 200 AMP SERVICES SHALL BE RUN IN ONE 2" CONDUIT MIN. 320 AMP SERVICES SHALL BE RUN IN A 3 1/2" CONDUITS MIN. . 400 AMP SERVICES SHALL BE RUN IN A SINGLE 4" CONDUIT. ALL SERVICES SHALL BE RUN FROM THE METER PAN TO A SPLICE BOX AT THE PROPERTY LINE.

    4. 600 AND 800 AMP SERVICES SHALL BE RUN IN TWO PARALLEL 4" CONDUITS FROM THE TRANS S CABINET TO A SPLICE BOX AT THE PROPERTY LINE. 600 AND 800 AMP SERVICES ARE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.

    DWG. BASED ONLIPA CS 6491

    Section 11 - Drawings

    D17

    5. UNDER NO CIRCUMSTANCES SHALL A CUSTOMER / CONTRACTOR ENTER A LIPA SPLICE BOX.

    ELECTRIC SERVICECABLE IN CONDUITCOMMUNICATIONSFACILITIES

    GAS SERVICE

    12" MIN. 24"

    SERVICE TRENCH

  • INSIDE WALL

    METER SOCKET ENCLOSURE

    SECURELY AND LEVEL IN HORIZONTALAND VERTICAL PLANES

    MAIN DISCONNECT

    OVERHEAD SERVICE CONDUIT

    CONDUIT STRAP (TYP.)

    "LB" CONDULET

    GROUND CONDUCTOR

    GROUND CLAMP

    5/8" X 8' CU PLATED GROUND ROD

    FINISHED GRADE

    3'-0"

    MIN /

    6'-0"

    MAXSEE NOTES 5 & 6

    7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

    WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

    8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

    6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

    THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

    1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

    OF THE AUTHORIZED ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    CONNECTION TO THE METER ENCLOSURE.

    EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

    INSTALLATION FOR SAFE ACCESS.

    NOTES:

    STATED.

    1/2" x 8' CU WELD OR

    FLOOR TO CEILING4' CLEARANCE

    TO NEUTRAL OF CUSTOMER'S MAINDISTRIBUTION PANEL

    9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURE SHALL BE USED.

    TO CUSTOMER'S

    TOP OF METER GLASSTO BE MOUNTED

    OVERHEAD SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET METER INSTALLATION

    5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).

    ADEQUATELY SECURED

    DWG. BASED ONLIPA CS 8001

    2012 Edition Redbook

    D18

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

  • 1/2" x 8' CU WELD OR5/8" X 8' CU PLATED

    INSIDE WALL

    METER SOCKET

    TO CUSTOMER'S

    CONDUIT STRAP

    "LB" CONDULET

    GROUND CONDUCTOR

    GROUND CLAMP

    MAIN DISCONNECT

    ENCLOSURE SECURELY ANDRIGIDLY MOUNTED

    SERVICE ENTRANCECONDUIT & CABLE

    3'-0" MIN.6'-0" MAX.

    (TYP.)

    GROUND ROD

    LOCKNUT ANDBONDINGBUSHING (TYP.)

    7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    THE NATIONAL ELECTRIC CODE.4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

    1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

    OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

    NOTES:

    STATED.

    TO NEUTRAL OF CUSTOMER'S MAIN

    TOP OFMETER GLASS

    A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS.6.

    4' CLEARANCEFLOOR TO CEILING

    12" MIN.CLEARANCE

    FINISHEDGRADE

    12" MIN.CLEARANCE

    WALL

    WALL

    8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    DISTRIBUTIONPANEL

    UNDERGROUND SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET METER INSTALLATION

    LUGNEUTRAL

    MAIN DISCONNECT

    METER SOCKET

    & LOCKNUT (TYP)BONDING BUSHING

    & CABLECONDUITLINE SIDE TO CUSTOMER

    BYPASS

    (TYP)LEVER

    UNDERGROUND

    (SEE NOTE 5)

    5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

    DWG. BASED ONLIPA CS 8007

    Section 11 - Drawings

    D19

    9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE, RIGHT SIDE OFMETER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE ASSHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED TO PERMIT PROPER OPERATION OF THE LEVEL,AND SHALL BE COVERED WIRE.

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

  • SECURELY AND LEVEL IN HORIZ.AND VERTICAL PLANES

    CONDUIT STRAP

    GROUND CLAMPFINISHED GRADE

    GROUND

    (TYP) OVERHEADSERVICECONDUIT

    CONDUCTOR

    SEE NOTES5 & 6

    6'-0" MAX

    2'-3" MIN

    TOP OF METER GLASS

    TOP OF METER GLASS

    WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

    8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

    6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

    THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE. WIRES INTENDED TO

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE

    1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

    OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    CONNECTION TO THE METER ENCLOSURE.

    BE USED FOR BONDING SHALL NOT BE PLACED IN CONTACT WITH ANY GAS PIPE.

    EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.

    NOTES:

    STATED.

    6' MAX

    A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS.7.

    10. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALYAND EXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES

    9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    1/2" x 8' COPPER WELD OR 5/8" X 8' COPPER PLATED

    GROUND ROD

    4' CLEARANCEFLOOR TO CEILING

    12"MIN.12" MIN

    WALL WALL

    GROUNDCND. TONEUTRALBLOCK.

    FINISHED GRADE

    METER SOCKET ENCLOSURETO BE MOUNTED

    2'-3"MIN.

    GROUND CONDUCTORTO WATER PIPE

    BEING SERVED.

    OVERHEAD AND UNDERGROUND SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET TROUGH MULTIMETER INSTALLATION

    5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).

    UNDERGROUND SERVICE CONDUIT(SEE NOTE 11)

    11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

    SUITE I.D.SEE NOTE 10

    DWG BASED ONLIPA CS 8005

    2012 Edition Redbook

    D20

    OVERHEAD SERVICE CONDUIT

  • 1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE EQUIPPED WITH A FIFTH JAW

    3. GAS PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

    4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICAL 250 OF THE NATIONAL ELECTRICAL CODE.

    6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED APPROXIMATELY ONE INCH FROM THE TOP OF THE METER PAN. WEATHER TIGHT TYPE "SE" CONNECTORS SHALL BE USED

    7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR

    8. IN ADDITION TO LIPA REQUIREMENTS, INSTALLATIONS, MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES HAVING JURISDICTION.

    10. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND EXTERNALLYWITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.

    LOCATED IN THE NINE O' CLOCK POSITION.

    FOR CONNECTION TO THE METER ENCLOSURE.

    NOTES:

    SAFE ACCESS.

    FINISHED FLOOR OR GRADE

    WALL

    12" MIN

    INTERNAL BUSING

    OF METER GLASSTOP

    3'-0" MIN.6'-0" MAX.

    1/2" x 8' CU WELD OR

    OVERHEAD ENTRANCE

    WALL

    12" MIN

    UNDERGROUND AND OVERHEAD SERVICESINGLE PHASE SELF CONTAINED METERSOUTDOOR MULTI-METER SOCKET ENCLOSURE

    (SEE NOTES 5 & 6)

    5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).

    5/8" X 8' CU PLATED GROUND ROD

    ALTERNATE UNDERGROUNDCONDUIT ENTRANCE(SEE NOTE 11)

    11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

    UNIT IDENTIFICATIONSEE NOTE 9

    DWG. BASED ONLIPA CS 8009

    Section 11 - Drawings

    D21

    GROUND CONDUCTOR TONEUTRAL OF CUSTOMERSMAIN DISCONNECT PANEL

    12. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURESHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRE.

  • FINISHED GRADE

    "LB" CONDULET

    INSIDE WALL

    MOUNT PLUMB & LEVEL

    TO CUSTOMER'S

    WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,

    THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY

    6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED

    THE NATIONAL ELECTRIC CODE.4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

    CONNECTION TO THE METER ENCLOSURE.

    SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.

    NOTES:

    CONDUIT STRAPS

    MAIN DISCONNECT

    POINT OFATTACHMENT

    LEAVE 3'-0" OF CONDUCTORFOR CONNECTION. FINAL CONNECTION BY LIPA.

    SERVICE ENTRANCEWEATHER HEAD

    SERVICE DROP CABLE

    TOP OF METER GLASS

    OUTDOOR POLYPHASEMETER SOCKET

    240/120 208Y/120

    PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY

    PHASE A BLUE BLUE

    LINE SIDEHUB

    NEUTRAL LUG

    ALTERNATE POSITIONOF LOAD CONDUIT

    BONDING BUSHING& LOCKNUT

    METER SOCKET

    LOAD SIDE

    15'-

    0"MI

    N

    6'-0

    "MAX

    6"MI

    N10

    "MAX

    3'-0

    "MIN

    CONDUIT

    OVERHEAD SERVICE CONDUIT

    A

    N A

    B C

    B C

    TO NEUTRAL OF CUSTOMER'S MAINDISTRIBUTION PANEL

    4' CLEARANCEFLOOR TO CEILING

    1/2" x 8' CU WELD OR5/8" X 8' CU PLATEDGROUND ROD

    GROUND CONDUCTOR

    PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE

    CONDUCTORS TO BE IDENTIFIED WITH COLOREDTAPE

    DELTA WYE

    OVERHEAD SERVICEPOLY-PHASE SELF CONTAINED METERS200 AMPERE SOCKET METER INSTALLATION

    (SEE NOTES 5 & 6)

    5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.(NEC)

    ADEQUATELY SECURED

    DWG. BASED ONLIPA CS 8207

    2012 Edition Redbook

    D22

    7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

    8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    INSTALLATION FOR SAFE ACCESS.

    9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    10. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURESHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRED.11. CONDUIT SHALL BE RIGID METAL OR SCHEDULE 80 PVC.

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE

  • MOUNT SOCKET SECURELY,

    TO CUSTOMER'S

    6. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER

    7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY SHALL BE EQUIPPED

    1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE

    OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM. ONLY NEUTRAL CONDUCTOR IS PERMITTED BEHIND

    INSTALLATION FOR SAFE ACCESS.

    NOTES:

    CONDUIT STRAP

    PLUMB & LEVEL

    MAIN DISCONNECT

    OUTDOOR POLYPHASEMETER SOCKET

    DELTA WYE

    PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY

    PHASE A BLUE BLUE

    GROUND

    FINISHED GRADE

    "LB" CONDULET

    INSIDE WALL

    3'-0

    "MIN6'

    -0"M

    AX

    CONDUCTOR

    TOP OF METER GLASS

    4' CLEARANCEFLOOR TO CEILING

    TO NEUTRAL OFCUSTOMER'S MAINDISTRIBUTION PANEL

    1/2 x 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD

    PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE

    8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    STATED.

    240/120 208Y/120

    UNDERGROUND SERVICEPOLY-PHASE SELF CONTAINED METERS200 AMPERE SOCKET METER INSTALLATION

    LUGNEUTRAL

    DISCONNECT

    METER SOCKET

    & LOCKNUT (TYP)BONDING BUSHING

    & CABLECONDUITLINE SIDE

    TO CUSTOMERMAIN

    PERMANENT

    BYPASSN BA

    A B

    C

    C (TYP)LEVER

    NEUTRAL JUMPER

    (TYP)

    UNDERGROUND SERVICE CONDUIT(SEE NOTE 5)

    5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHEDULE 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (E.M.T.)

    AND INTERMEDIATE METALLIC CONDUIT (I.M.C.) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

    ADEQUATELY SECURED

    BYPASS LEVER.

    DWG. BASED ONLIPA CS 8209

    Section 11 - Drawings

    D23

    9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER,

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

    AND SHALL BE COVERED WIRE.

  • GAS SERVICE

    GAS METER

    RIGHTALTERNATEPOSITION

    LEFTALTERNATEPOSITION

    2. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE ELECTRIC

    3. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    1. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

    OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    METER INSTALLATION FOR SAFE ACCESS.

    NOTES:

    4. A MINIMUM SEPARATION OF 1'-0" MUST BE MAINTAINED BETWEEN GAS METER, REGULATOR, UNIONS

    5. SEPARATION OF GAS SERVICE PIPE OR TUBING AND ALL OTHER UNDERGROUND FACILITIES OR STRUCTURES SHALL BE MAINTAINED IN ACCORDANCE WITH APPROPRIATE CONSTRUCTION

    6. NO ELECTRIC METER ENCLOSURE SHALL BE INSTALLED ABOVE THE GAS METER.

    MINIMUM1'-0"

    7. NO PROTECTION BOLLARDS SHALL BE PLACED IN FRONT OF THE ELECTRIC METER.

    ELECTRIC METER ENCLOSURE

    STANDARDS.

    8. VENTING OF GAS REGULATOR SHALL BE PLACED A MINIMUM OF 1'-0" FROM THE NEAREST PART OF THE ELECTRIC METER INSTALLATION.

    CLEARANCES BETWEENELECTRIC & GAS METERS

    9. A 1' SEPARATION FROM GAS LOAD PIPE TO THE DISTRIBUTION PANEL IS REQUIRED.

    10. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OF 3' CLEARANCE IS REQUIRED BETWEEENTHE GAS SERVICE PIPING AND METERS AND ANY ELECTRICAL SERVICE EQUIPMENT.

    DWG. BASED ONLIPA CS 8015

    2012 Edition Redbook

    D24

    COUPLINGS, JOINTS, AND VENTS AND ELECTRIC METERING EQUIPMENT.

    MINIMUM1'-0"

    GAS METER

    GAS SERVICE

    GAS METER, REGULATOR, UNIONSAND VENTS NOT PERMITTED INSHADED AREA

  • 7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION

    OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE

    8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL

    AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF LEVER.

    6. LINE AND LOAD CONDUIT CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE

    THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF

    2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY

    1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.

    OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.

    SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.

    FOR SAFE ACCESS.

    NOTES:

    9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY ANDEXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.

    A

    A

    B

    B

    C

    C

    DELTA WYE

    PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY

    PHASE A BLUE BLUE

    NEUTRAL LUGA

    A

    B

    B

    C

    C

    10. LINE CONDUCTORS SHALL ENTER METER ENCLOSURE ON THE TOP OR BOTTOM LEFT.

    11. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.

    OVERHEAD LINE SIDE TROUGH

    POLYPHASEMETERENCLOSURE

    JUMPERNEUTRAL PERMANENT

    (TYP)

    (TYP)

    (TYP)BYPASSLEVER

    LINE SIDECONDUIT & CABLE

    CONDUITLINE SIDE TO CUSTOMER

    MAIN DISCONNECT DISCONNECTMAINTO CUSTOMER

    TO CUSTOMERMAIN DISCONNECT

    ENCLOSURE

    SINGLE PHASEMETER

    2" MIN

    2" MIN

    N N

    & CABLE

    NEMA TYPE 3R MIN.

    2" MIN.

    METERSOCKETASSEMBLY(TPY.)

    (TYP.)

    12"MIN.

    12"MIN.

    WALLWALL

    ALTERNATE LOCATION OF LINE SIDE TROUGHNEMA TYPE 3R MIN.

    4" MIN

    12. IDENTIFICATION OF PHASE CONDUCTORS SHALL BE WITH COLORED TAPE FOR A MINIMUM OF TWO INCHES.

    PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE

    TROUGH SUPPLYSINGLE AND POLY-PHASE SELF CONTAINED METERS

    200 AMPERE MULTI-METER SOCKET INSTALLATION

    240/120 208Y/120

    5. CONDUIT SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC.

    DWG. BASED ONLIPA CS 8211

    Section 11 - Drawings

    D25

    3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.

    AND SHALL BE COVERED WIRE.

  • 2. FOR SELF-CONTAINED METER ENCLOSURES, 2" RIGID GALVANIZED STEEL PIPE WITH APPROPRIATELY SIZED CHANNEL AND CONCRETE BASE MAY BE USED IN PLACE OF 4" PIPE DESIGN ; 4" X 4" TREATED LUMBER MAY

    NOTES:

    METER H FRAME CONSTRUCTIONOUTDOOR MOUNTING FOR TRANSFORMER AND/OR METER CABINET

    1. CONCRETE FILLED PROTECTION BOLLARDS SHALL BE INSTALLED WHEN INSTALLATION IS IN THE VICINITY OF VEHICULAR TRAFFIC. BOLLARDS SHALL BE PLACED A MINIMUM OF 4' FROM THE CABINET AND SHALL BE PAINTED FLUORESCENT YELLOW. BOLLARDS SHALL BE CONSTRUCTED FROM A MINIMUM OF 3.5" OUTSIDE DIAMETER SCHEDULE 40 GALVANIZED PIPE, SHALL BE SPACED 24" ON CENTERS AND SHALL BE A MINIMUM OF 3' HIGH.

    4'- 0" MIN*6'- 0" MAX

    CONDUITSUPPORT

    TOP OF METER

    AS NEEDED

    LOCKNUT

    ENTRANCE CONDUCTORSUNDERGROUND SERVICE

    RGS CONDUITSHC. 80 PVC OR

    12" DIA. CONC.FILLED SONOTUBE

    TRANSFORMER

    METER CABINET

    GALV. U-BOLT

    FINISHED GRADE

    6" MIN.

    W/ CHAMFER6" MIN.

    (TYP.)

    3/8" DIA. (TYP.)

    1-1/2" x 1-7/8"GALV. CHANNEL

    4" SCH. 40 GALV.

    (SEE NOTE #2)

    GALV. CAP

    STEEL PIPE

    (TYP.)

    (TYP.)

    H - FRAME INSTALLATIONS ARE RESTRICTED/NOT PERMITTED BY SOME MUNICIPALITIES. CHECK LOCAL CODES PRIOR TO INSTALLATION.

    (SEE NOTE 3)

    3. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.

    BE USED IN PLACE OF 4" X 6" POST DESIGN. USE OF PLYWOOD FOR EQUIPMENT INSTALLATION IS NOT PERMITTED.

    4. FOR ADDITIONAL TRANS S CABINET REQUIREMENTS SEE DRAWINGS D28 & D29. FOR ADDITIONAL

    (TYP.)

    OR STRAP

    AND/OR

    (TYP.)

    3'-6"

    CONDUIT STRAP

    STEEL OR GALVANIZED LAGFASTENED WITH STAINLESSMETER ENCLOSURE TO BE

    ANGLE CUTS (TYP).

    4" X 6" TREATED LUMBERPOSTS, AND 5/4" CROSS

    METAL CAP OR

    TRANSFORMER

    METER CABINETAND/OR

    (TYP.)LOCKNUT

    (TYP.)

    MIN.

    OR THROUGH BOLTS

    ALTERNATE DESIGN

    FINISHED GRADE

    STANDARD DESIGN

    DWG. BASED ONLIPA CS 8602

    2012 Edition Redbook

    D26

    CT CABINET WITH REMOTE METER SOCKET REQUIREMENTS SEE DRAWINGS D30 & D31.

    SHC. 80 PVC OR RGS CONDUIT(SEE NOTE 3)UNDERGROUND SERVICE ENTRANCE CONDUCTORS

    BRACES SEE NOTE #2

    5/4 X 6" TREATED LUMBERCROSS BRACE (TYP)

    may be 3'-0"meters, min. height * Note: For self-contained

    5. CHECK WITH LOCAL MUNICIPALITY FOR ANY SPECIAL REQUIREMENTS BEFORE INSTALLING METERINGEQUIPMENT ON H-FRAME.

  • 12"TRANS "S" TRANS "S"

    MULTI - METER STACK

    2. WHEN METERS ARE ON WALLS FACING EACH OTHER, THERE MUST BE 4' OF CLEAR SPACE FROM FLOOR TO CEILING BETWEEN METERS.

    SWIT

    CHGE

    AROR

    TRA

    NS "

    S"

    3. SWITCHGEAR DOORS MUST BE ABLE TO OPEN FULLY WITHOUT BEING OBSTRUCTED BY ANY METER ENCLOSURES OR WALLS.

    4' MIN

    4' MIN

    TRANS "S"

    OR T

    RANS

    "S"SW

    ITCH

    GEAR

    SELF-CONTAINEDMETER ENCLOSURES

    SELF-CONTAINED METER ENCLOSURES

    4. ROOMS CLASSIFIED AS CONFINED SPACE AND THOSE THAT REQUIRE LADDER ACCESS SHALL SHALL NOT BE USED AS METER ROOMS.5. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS.

    6. MINIMUM METER ROOM CEILING HEIGHT SHALL BE 6'-6". ADEQUATE LIGHTING SHALL BE

    7. GAS METERS ARE NOT PERMITTED IN ELECTRIC METER ROOMS.

    ELECTRIC METER ROOMEQUIPMENT CLEARANCES

    2" 2"

    12"TRANS "S"2"

    PROVIDED IN METER ROOM.

    DWG. BASED ONLIPA CS 8604

    Section 11 - Drawings

    D27

    NOTES:

    1. METER ROOM CONSTRUCTION SHALL COMPLY WILL ALL CODE REQUIREMENTS ( eg. NEC110.26) PERTAINING TO ACCESS, EGRESS, AND SAFETY.

    8. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OR 3' CLEARANCE IS REQUIRED BETWEEN THE GAS SERVICE PIPING AND METER AND ANY ELECTRICAL SERVICE EQUIPMENT.

    12"

    12"

    12"

    12"

    4' MIN

    4' MIN

    5'MIN

    12"

    5'MIN

    12"

    NOT TO SCALE

    NOT TO SCALE

  • TIN PLATED COPPER BUS

    STANDOFFINSULATOR

    NEUTRALBUS

    LIPA APPROVED

    WITH METER SOCKETAND

    4", 3.5" CONCENTRICKNOCKOUTS (4 TYP.)

    TOP VIEW

    TEST SWITCH

    SILVER OR

    HEX SCREW ( 3 typ.)

    K.O TO ACCOMODATELIPA's LOCKING DEVICE

    METER ENCLOSURERECESSED IN DOOR

    CURRENT TRANSFORMERSFURNISHED AND INSTALLED

    BOTTOM VIEW

    METER FURNISHEDAND INSTALLED BY LIPA

    GROUND STRAP

    CONTINUOUS STAINLESSSTEEL PIANO HINGED DOOR.LEFT HAND SWING ONLY

    SIDE VIEW

    (2 TYP.)

    7"6"6"5"

    6" 6"6" 6" 3"3"

    HUB OPENING FOR 3", 3.5" OR 4" HUB

    CL CL CL

    GROUND LUG

    NEMA TWO HOLE LUGPATTERN

    RACEWAYFORBOTTOMENTRY OR EXIT

    400 TO 800 AMPERE SERVICETRANS "S" CABINET INSTALLATION

    FOR NOTES SEE DRAWING D29 DWG. BASED ONLIPA CS 8804

    2012Edition Redbook

    D28

    TRANS-S CABINET

  • NOTES:

    1. BUS BARS SHALL BE SILVER OR TIN PLATED COPPER AND SHALL BE SIZED PER THE NEC.

    2. ONLY THE RIGHT HAND SIDE OF THE CABINET SHALL ALLOW FOR LINE AND LOAD CABLES TO ENTER AND EXIT THROUGH THE BOTTOM OF THE CABINET. THIS SPACE SHALL ALLOW FOR THE CABLES TO MEET THE MINIMUM BENDING RADIUS TO THE NEAREST PHASE OR NEUTRAL BUS. AS PER THE NEC.

    3. CABINET DESIGN SHALL HAVE PROVISIONS FOR A SOLID DOOR TO ALLOW FOR THE METER ENCLOSURE TO BE MOUNTED REMOTELY FROM THE CABINET.

    4. MANUFACTURER SHALL FURNISH AND INSTALL 1/2-13 STUDS WITH SPLIT LOCK WASHERS AND HEX NUTS FOR C.T MOUNTING.5. USE ONLY MANUFACTURED APPROVED LUG KITS.

    7. THIS STANDARD SHALL NOT BE USED AS A DESIGN CRITERIA. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS ONLY. LARGER DIMENSIONS SHALL BE USED WHERE REQUIRED BY CODE.

    400 TO 800 AMPERE SERVICETRANS "S" CABINET INSTALLATION - NOTES & BONDING DIAGRAM

    8. MAINTAIN CLEARANCES BETWEEN TRANS S CABINET AND TROUGHS OF 2" ON TOP AND 4" ON BOTTOM OF CABINET.

    Section 11 - Drawings

    D29

    NN

    NON-METALLICCONDUIT/

    LINE

    BOND STRAPNEUTRAL-TO-ENCLOSURE

    BONDINGBUSHING

    BOND TOENCLOSURE

    RACEWAYRACEWAYCONDUIT/METALLIC

    TRANS SCABINET

    TRANS SCABINET

    BOND STRAPNEUTRAL-TO-ENCLOSURE

    LINE

    TRANS S CABINET BONDING DIAGRAMNON - GFI MAIN DISCONNECT INSTALLATION

    GFI MAIN DISCONNECT INSTALLATIONTRANS S CABINET BONDING DIAGRAM

    LINE

    RACEWAYCONDUIT/

    NON-METALLIC

    N

    BOND* ENCLOSURE

    TRANS SCABINET

    METALLICCONDUIT/RACEWAY

    BONDINGBUSHING

    N

    CABINETTRANS S

    NO BOND

    GFI

    BETWEENNEUTRAL &CABINET CABINET

    NEUTRAL &BETWEENNO BOND

    BOND*ENCLOSURETO GFIBONDPOINT

    GFI

    LINE

    TO BONDINGBUSHING

    9. PERMANENTLY IDENTIFY LINE AND LOAD CONDUCTORS INSIDE CABINET.

    (APPLIES TO 120/208V & 277/480V SERVICES)

    6. METERING ENCLOSURES SHALL NOT BE ADDED. ONLY FACTORY SUPPLIED KNOCKOUTS AND PERMITTED. FIELD MADE KNOCKOUTS OR ANY OTHER FIELD ALTERATIONS WILL NOT BE ACCEPTED.

    * USE MANUFACTURER'S BOND ATTACHMENT POINT

  • CURRENT

    AND TEST SWITCHMETER SOCKET TRANSFORMER RATED

    NEUT

    RAL

    BUS

    NOTES:

    SIDELOAD (LINE)

    1-1/4" CONDUIT MIN.(SEE NOTE #6 AND #7)

    WITH CONTROL CABLE

    CT

    ENCLOSURE

    400-1200 C.T CABINETMOUNTED TO WALL

    COPPER BUS

    WALL

    OR APPROVED STRUCTURE.(Note4)

    METER SOCKET ENCLOSURE AND TO THE CT. CABINET.

    1. LIPA APPROVED CURRENT TRANSFORMER CABINET AND METER SOCKET SHALL NOT BE LOCATED IN ANY AREA CLASSIFIED AS A HALLWAY, CONFINED SPACE, OR WHERE A LADDER ACCESS IS REQUIRED. (Ref Sect-8.2.3)2. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS. METER ENCLOSURES OR CURRENT TRANSFORMER CABINETS SHALL NOT BE LOCATED IN THESE

    3. REFER TO NEC ARTICLE 250 FOR GROUNDING AND BONDING REQUIREMENT.

    4. CENTERLINE OF C.T CABINET SHALL BE A MAXIMUM OF 5'-0" OR A MINIMUM OF 3'-6"

    5. CONTROL CABLE SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR, SEE SECT. 8.9. FINAL TERMINATION IN THE METER AND TRANSFORMER CABINET SHALL BE DONE BY LIPA

    6. MAXIMUM DISTANCE OF METER SOCKET FROM C.T CABINET SHALL BE DETERMINED BY LIPA

    7. WHEN PVC CONDUIT IS USED A # 8 AWG 600 VOLT FACTORY INSULATED COPPER BOND WIRE SHALL BE INSTALLED BETWEEN THE METER SOCKET ENCLOSURE AND THE C.T CABINET THE BOND WIRE SHALL BE GREEN OR MARKED AS SUCH AND SHALL BE BONDED TO THE

    TYPES OF AREAS.

    FROM FINISHED FLOOR.

    TRANSFORMER RATED METER SOCKETANDCURRENT TRANSFORMER CABINET INSTALLATION

    CT CT

    LINE (LOAD)SIDE

    TRANSFORMER (TYP)

    DWG. BASED ONLIPA CS 8606

    2012 Edition Redbook

    D30

    6'-0

    " MA

    XIMU

    M4'

    -0"

    MINI

    MUM

    FINISHED GRADE

    EXIT THROUGH MFG.KNOCKOUT ONLY

    LIPA APPROVED

    LIPA APPROVED CT/TRANS CABINET

    LIPA APPROVED

    8. REFER TO DRAWINGS D26, D27, D28, AND D29 FOR OTHER REQUIREMENTS. 9. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY

    MARKED.

  • 11. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY

    MOUNTING OF CURRENT TRANSFORMERS. BOLTS SHALL BE PERMANENTLY AFFIXED10. GALVANIZED BOLTS, BELLEVILLE WASHERS AND NUTS SHALL BE PROVIDED FOR

    9. BUS BAR SUPPORT SHALL BE CONSTRUCTED FROM INSULATING MATERIALS CONFORMING

    SHALL BE LOCATED WITHIN AN ENCLOSURE EQUIPPED WITH TAMPER PROOF SCREWS.8. ALL BUS BARS LOCATED ON THE LINE SIDE OF THE CURRENT TRANSFORMER COMPARTMENT

    PROVISIONS FOR HOLDING THE DOORS IN THE OPEN POSITION.7. DOOR SWING SHALL BE GREATER THAN 90 DEGREES AND SHALL BE EQUIPPED WITH

    WHICH SHALL BE EQUIPPED WITH A THREE POINT LATCHING MECHANISM AND HAVE 6. THE FRONT OF THE CUBICLE SHALL BE FURNISHED WITH A DOUBLE SWING DOOR

    5. THE NEUTRAL BUS SHALL BE DRILLED WITH A 1/4 - 20 TAP FOR CURRENT

    3. BUS BARS WITHIN THE CURRENT TRANSFORMER CUBICLE SHALL BE COPPER AND SHALL

    FROM THE REMAINDER OF THE SWITCHGEAR CUBICLE BY MEANS OF INSULATING BARRIERS2. THE CURRENT TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED

    SWITCHGEAR CUBICLE WHICH SHALL BE CONSTRUCTED IN CONFORMANCE WITH UL 891.1. THE LIPA APPROVED CURRENT TRANSFORMER COMPARTMENT SHALL BE LOCATED WITHIN THE INCOMING NOTES:

    TO THE COPPER LANDING PADS.

    PROVISIONS FOR LIPA PADLOCKING.

    TRANSFORMER CONNECTION.

    AS A MINIMUM BE TIN PLATED AT TERMINATION POINTS.

    AS PER UL 891.

    TO UL 746.

    MARKED.

    LC LC

    7"MIN7"MINLC

    7.5" MIN

    SEE DETAIL A

    25.0" MIN.

    DETAIL A

    6.875"

    1.375"

    .625"

    HOLES(TYP.)9/16" DIA.

    36.0" MIN.

    15.0" MIN.

    INSULATINGBARRIER

    400 TO 1200 AMPERE SERVICECURRENT TRANSFORMER COMPARTMENT INSTALLATION

    4. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED AS PER NEC FOR 1000 AMPERES PER SQUARE INCH.

    DWG. BASED ONLIPA CS 8801

    WHITE OR GRAY

    BLACK

    120/208 277/480

    PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE ON EACH END.

    PHASE CNEUTRAL

    PHASE BPHASE A

    ORANGEBLACKBLUEDELTA

    RED

    BLUEWYE

    YELLOW

    BROWNORANGE

    WYE120/240

    Section 11 - Drawings

    D31

    7"MIN7"MIN 7"MINLC

  • REPLACEMENT OF THE INSTRUMENT TRANSFORMERS.2. THE BUS BAR INSTALLATION SHALL BE SO DESIGNED AS TO PERMIT A PRACTICAL AND EASY

    8. THERE SHALL BE A MINIMUM OF FOUR FEET FROM FLOOR TO CEILING OF CLEAR WORKING SPACE MINIMUM, THE OVERALL WIDTH AND HEIGHT OF THE TRANSFORMER COMPARTMENT. SHALL BE ACCESSIBLE THROUGH A LOCKABLE DOUBLE HINGED DOOR WHICH SHALL SPAN, AS A ENCLOSURE WITH AN INSULATING MATERIAL CONFORMING TO UL 746 AND UL 94. THE TRANSFORMERS 7. THE TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED FROM THE REST OF THE

    6. THE TRANSFORMER SHELF AND SUPPORTING BRACKETS SHALL BE CONSTRUCTED FROM NON-FERROUS

    5. ALL PHASE BUS AND THE NEUTRAL BUS SHALL BE DRILLED AND TAPPED FOR 1/4" - 20 SCREWS LOCATED ON THE LINE SIDE WHEREBY THE SECONDARY CONNECTIONS WILL BE READILY ACCESSIBLE.4. THE TRANSFORMERS SHALL BE INSTALLED SO THAT THE PRIMARY POLARITY MARKS (H1) IS REQUIRED. THE MINIMUM DISTANCES BETWEEN CENTERLINES OF TRANSFORMERS SHALL BE 10 INCHES.3. MOUNTING OF THE TRANSFORMERS MAY BE STAGGERED VERTICALLY WHERE CLOSER CENTERS ARE

    CONDUCTOR SHALL BE COPPER BUS AND SHALL BE TIN PLATED AT TERMINATION POINTS AS A MINIMUM. BUS 1. CURRENT TRANSFORMER COMPARTMENT SHALL BE LIPA APPROVED, AND SHALL BE INSTALLED AS SHOWN.

    IN FRONT OF THE TRANSFORMER CABINET.

    ON THE LINE SIDE OF THE TRANSFORMERS.

    NOTES:

    MIN.7"

    ELEVATION

    MIN.13"

    MIN13"

    MIN.7"

    5.375"

    SECTION A-A

    11" MIN 7" MIN

    8.5"

    8.5"

    9. WHEN NEUTRAL BUS IS RECESSED, PROVISIONS SHALL BE MADE TO EXTEND THE NEUTRAL CONNECTION TO THE FRONT OF THE CUBICLE TO ACCOMODATE THE CONNECTION OF THE INSTRUMENT TRANSFORMERS.

    NON-CONDUCTING, TYPE MATERIAL. MATERIAL SHALL CONFORM TO UL 746 AND UL 94.

    A

    A

    MUST BE CENTERED IN THE WINDOW OF THE TRANSFORMER.

    10. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED PER THE NEC FOR 1000 AMPERES PER SQUARE INCH. MAXIMUM BUS WIDTH SHALL BE 5 INCHES.11. THE INSTRUMENT TRANSFORMER COMPARTMENT SHALL BE FURNISHED WITH A DOUBLE SWING DOOR EQUIPPED WITH A THREE POINT LATCHING MECHANISM WITH PROVISIONS FOR LIPA PADLOCKING.

    CURRENT TRANSFORMER PLAN VIEW

    B

    B

    CT SECONDARYTERMINAL

    1600 AMPERE SERVICE AND ABOVECURRENT TRANSFORMER COMPARTMENT INSTALLATION

    WHITE OR GRAY

    BLACK

    120/208 277/480

    PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE ON EACH END.

    PHASE CNEUTRAL

    PHASE BPHASE A

    ORANGEBLACKBLUEDELTA

    RED

    BLUEWYE

    YELLOW

    BROWNORANGE

    WYE

    12. LINE AND LOAD SIDES OF THE COMPARTMENT MUST BE CLEARLY AND

    CT SHELF MIN.1" THK. NON-CONDUCTIVEMATERIAL

    DWG. BASED ONLIPA CS 8802PERMANENTLY MARKED.

    2012 Edition Redbook

    D32

    NEUTRALBUS

    11" MIN. BUS EDGE TO ACCESS DOOR

    42" MIN

    7" MIN. BUSEDGETO REAR INSULATINGBARRIER

    METAL ENCL.SIDEWALL

    LC LC LC

  • BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER. BUSHING. BUSHINGS SHALL BE BONDED TO THEIR RESPECTIVE ENCLOSURES. 3. WHERE GALVANIZED OR ELECTRICAL METAL TUBING IS USED WITH BONDING

    ELECTRICAL CODE.2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL

    IS APPLICABLE WHERE TEN FEET OF CONTINUOUS METAL WATER PIPE IN SIX FEET FROM THE FIRST. THE REQUIREMENT FOR A SECOND GROUND ROD GROUND ROD IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF 1. WHERE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND

    INSULATED NEUTRAL CONDUCTOR

    GROUND CONDUCTOR

    CUSTOMER'S MAIN DISCONNECTNEUTRAL BLOCK

    ELECTRIC METER ENCLOSURE

    EARTH IS NOT AVAILABLE.

    NOTES:

    (SEE NOTE #1)WATER PIPING SYSTEMUNDERGROUND METAL

    PER NEC.

    WATERMETER

    FINISHEDGRADE

    TYPICAL GROUNDING REQUIREMENTSSINGLE METER / MAIN INSTALLATION

    1/2" X 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD

    DWG. BASED ONLIPA CS 8603

    Section 11 - Drawings

    D33

  • WATERMETER

    GROU

    ND B

    US

    1/2" X 8' COPPER WELD OR

    WIRE SIZED IN ACCORDANCE W/ THE NEC REQUIREMENTS

    WIRE SIZED FOR SERVICE ENTRANCE CONDUCTOR SIZE IN ACCORDANCE W/

    WITHIN 5' OF BUILDINGENTRANCE AND 10' OFCONTACT WITH EARTH

    TROUGH

    MAINORPANEL

    TYPICAL GROUNDING DETAILSMULTI METER / MULTI MAIN INSTALLATION

    PANEL

    MAINOR

    GROU

    ND B

    US

    PANEL

    MAINOR

    GROU

    ND B

    US

    METERSOCKET SOCKET

    METERSOCKET

    METER

    THE NEC REQUIREMENTS

    1. WHERE THE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND GROUND ROD IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF SIX FEET FROM THE FIRST. THE REQUIREMENT FOR A SECOND GROUND ROD IS APPLICABLE WHERE TEN FEET OF CONTINUOUS METAL WATER PIPE IN EARTH IS NOT AVAILABLE.

    2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE.

    3. WHERE GALV. OR ELECTRICAL METAL TUBING IS USED WITH BONDING BUSHING. BUSHINGS SHALL BE BONDED TO THEIR RESPECTIVE ENCLOSURES. BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER.

    NOTES:

    UNDERGROUND METAL WATERPIPING SYSTEM PER NEC(SEE NOTE 1) 5/8" X 8' COPPER PLATED

    2012 Edition Redbook

    D34

    Apt.1

    Apt.1

    Apt.2

    Apt.2

    Apt.3

    Apt.3

    GROUND ROD

  • OPTIONAL STANDBY SYSTEMS

    THE FOLLOWING 2 ONE-LINE SCHEMATICS OUTLINE THE CONNECTIONSLIPA WILL ALLOW FOR THE INTERCONNECTION OF OPTIONAL STANDBYSYSTEM EQUIPMENT. THE INTENT OF THE INTERCONNECTION SCHEMES IS TO PREVENT BOTH BACKFEED INTO THE LIPAELECTRIC DISTRIBUTION SYSTEM, AND UNINTENTIONAL PARALLELOPERATION WITH AN ENERGIZED LIPA SYSTEM. IMPROPERPARALLEL OPERATION CAN RESULT IN SERIOUS DAMAGE TO THEGENERATOR, THE LIPA DISTRIBUTION SYSTEM, OR BOTH, AND BEA SAFETY HAZARD TO PERSONNEL.

    TO ENTIRELOAD

    GGENERATOR

    GENERATORPROTECTIVECIRCUIT BREAKERMAINDISCONNECT

    LIPAMETERED

    FIG. 1: STANDBY GENERATOR FOR ENTIRE LOAD.

    DOUBLE THROW SWITCH

    DOUBLE THROW SWITCH

    CIRCUIT BREAKERPROTECTIVE

    GENERATOR

    GENERATORG

    STANDBY LOAD

    LOADS NOT BACKED UPBY GENERATOR

    FIG. 2: STANDBY GENERATOR FOR PARTIAL LOADS

    SERVICE

    METEREDSERVICE

    LIPA

    MAINDISCONNECT

    Section 11 - Drawings

    D35

    NOTE: CUSTOMER'S METERINGEQUIPMENT MUST BEPLACARDED THAT A GENERATOR IS PRESENT

    NOTE: CUSTOMER'S METERINGEQUIPMENT MUST BEPLACARDED THAT A GENERATOR IS PRESENT