2012 Edition Redbook
41
11.0 GENERAL DRAWINGS AND STANDARDS
Minimum Vertical Clearances Above Ground and Roofs D1 Minimum Pool Clearances D2
Minimum Clearances of Wires Adjacent to Buildings and Other Structures D3 O.H. 100 400 Amp Mast Services D4
O.H. 100 400 Amp Mast Service General Notes .. D5 Drop Swing Service for Inaccessible Service Entrance Attachment . D6 Pole Mounted Service 100 320 Amps . D7 Pole Mounted Service 400 Amps D8 LIPA Connects Program Connector Installation D9 400 600 Amp Open Wire Services .. D10 Customer Installed Cable Riser .. D11 Customer Installed Cable Riser General Notes D12 Customer Installed Pull Box and Manhole Specifications .. D13 U.G. Service 100 800 Amp Single or Three Phase by Builder/Applicant . D14 U.G. Service 100 800 Amp Single or Three Phase by Builder/Applicant . D15 LIPA Installed Single Phase RUD Service D16 Customer Installed Single Phase Residential RUD Service .. D17 O.H. Single Phase Self Contained Meter Outdoor Socket Meter Installation . D18 U.G. Single Phase Self Contained Meter Outdoor Socket Meter Installation . D19 O.H. & U.G. Single Phase Self Contained Multi-meter Installation .. D20 O.H. & U.G. Single Phase Self Contained Multi-meter Installation .. D21 O.H. Service Poly-Phase Self Contained Meter Installation .. D22 U.G. Service Poly-Phase Self Contained Meter Installation .. D23 Clearances Between Electric & Gas Meters D24 Trough Supply Single and Poly-Phase Self Contained Meter Installations . D25 Meter H-Frame Construction .. D26 Electric Meter Room Equipment Clearances D27 400 800 Amp Trans-S Cabinet Installation D28 400 800 Amp Trans-S Cabinet Installation Notes & Bonding Diagram D29 Transformer Rated Meter Socket and Current Transformer Cabinet Installation .. D30 400 1200 Amp Service Current Transformer Compartment Installation .. D31 1600 Amp Service and Above Current Transformer Compartment Installation . D32 Typical Grounding Requirements Single Meter and Main Installation .. D33 Typical Grounding Details Multi-Meter & Multi-Main Installation D34 Standby Generators .. D35
-
MINIMUM VERTICAL CLEARANCES ABOVE GROUND AND ROOFS
NOT ACCEPTABLE - SEE NOTE 2
NOTES
1. POINT OF SERVICE ATTACHMENT ON BUILDING WALL SHALL NOT BE LESS THAN 15'-0"ABOVE GRADE OR GREATER THAN 21'-0" WITHOUT ELECTRIC DESIGN AND CONSTRUCTIONEXPLICIT APPROVAL IN WRITING (SEE SECTION 4.2.2).2. SERVICE CONNECTIONS LOCATED ABOVE GARAGE OR OTHER BUILDING EXTENSION AS REPRESENTED
IN FIGURE 1 ARE NOT ACCEPTABLE BECAUSE THE SERVICE CONNECTION CAN NOT BE DIRECTLYREACHED FROM A LADDER PLACED ON THE GROUND.
3. CLEARANCES BETWEEN LIPA SERVICES AND VERIZON SERVICE LATERALS SHALL BE 2' MINIMUM.
4. FOR COMMERCIAL DRIVEWAYS AND ANY OTHER LOCATIONS SUBJECT TO TRUCK TRAFFIC MINIMUM CLEARANCE SHALL BE 18'-0".
6. ADD 6" TO ALL MINIMUM CLEARANCES FOR ANY OPEN WIRE CONSTRUCTION.
OVER ROOF SURFACE IF ROOF CANNOTBE READILY WALKED UPON.
SERVICE DROP, DRIP LOOP AND CONNECTION MUSTBE 3' MINIMUM FROM WINDOWS.
3' MIN. FROM WEATHERHEAD, SERVICE DROP
15' CLEARANCEOVER
DRIVEWAYSROOF CAN BE READILYWALKED UPON.18'
CLEARANCEOVERSTREETS
12'OVERSIDE-WALKS
12' OVER
SPACESACCESSIBLEPEDESTRIAN12'
FIGURE 1
SERVICE DROP MUST BE 3' OR MORE
10' IF
FIGURE 2
5. A 3' CLEARANCE IS REQUIRED FROM THE WEATHERHEAD AND/OR SERVICE DROP CONNECTIONS TOALL WINDOWS, DOORS, AND MOUNTINGS ON THE BUILDING WALL. POINT OF ATTACHMENT IS NOT
RESIDENTIAL
AND CONNECTIONS
POINT OF ATTACHMENT NOTPERMITTED BELOW WINDOW
PERMITTED BELOW A WINDOW.
DWG. BASED ONLIPA CS 2701
D1
Section 11 - Drawings
-
LIPA BASES ITS REQUIRED CLEARANCES FROM SWIMMING POOLS AND ASSOCIATED STRUCTURESUPON THE REQUIREMENTS OF THE NATIONAL ELECTRICAL SAFETY CODE (NESC). WHERE WIRESCONDUCTORS OR CABLES CROSS OVER A SWIMMING POOL OR THE SURROUNDING AREA THE
MINIMUM POOL CLEARANCES
THESE CLEARANCE REQUIREMENTS DO NOT APPLY TO TYPE 1 AND TYPE 2 CABLES DESCRIBED ABOVETHAT ARE 10 FEET OR MORE HORIZONTALLY FROM THE EDGE OF THE POOL OR DIVING PLATFORM.
DWG. BASED ONLIPA CS 2035
A A
B B
A VV
SUPPLY CABLES 0 TO 750v(OVERHEAD TRIPLEX ORQUADRAPLEX SECONDARYOR SERVICE WIRE)
OPEN SUPPLY CABLES0 TO 750v (OVERHEADOPEN WIRE SECONDARYOR SERVICE)
OPEN SUPPLY CABLES750v TO 22 kv(PRIMARY WIRE, BAREAND COVERED)
MESSENGERS; SURGEPROTECTION WIRES;GROUNDED GUYS;GROUNDED NEUTRALCONDUCTORS
CLEARANCE IN ANY DIRECTIONFROM THE WATER LEVEL, EDGEOF POOL, BASE OF DIVINGPLATFORM OR ANCHORED RAFT
CLEARANCE IN ANY DIRECTIONTO THE DIVING PLATFORM ORTOWER
VERTICAL CLEARANCE OVERADJACENT LAND
2012 Edition Redbook
D2
(FEET) (FEET) (FEET) (FEET)A:
B:
V: CLEARANCE SHALL BE AS SHOWN ON DRAWING D1
22.0 22.5 23.0 25.0
14.0 14.5 15.0 17.0
FIG. 1(NESC FIG. 234-3)SWIMMING POOL CLEARANCES
TABLE 1
CLEARANCES IN ALL DIRECTIONS SHALL NOT BE LESS THAN THOSE SHOWN IN TABLE 1 AND ILLUSTRATED IN FIG. 1, AND AS DESCRIBED IN THE NESC. LOCAL MUNICIPALITY MAY HAVE STRICTER POOL CLEARANCE REQUIREMENTS. FOR ADDITIONAL PUBLIC POOL REQUIREMENTS SEE SECT. 3.4
HORIZONTALLY FROM THE INSIDE WALL OF A POOL, HOT TUB OR SPA. UNDERGROUND WIRING SHALL NOT BE LOCATED UNDER OR WITHIN AN AREA EXTENDING 5'
TYPE 1: TYPE 2: TYPE 3: TYPE 4:
WARNING: UNDER ON CIRCUMSTANCES SHOULD ANYONE, OTHER THAN LIPA PERSONAL ATTEMPT TO MEASURE CLEARANCES TO LIPA'S DISTRIBUTION SYSTEM.
-
BUT NOT ATTACHED TO BUILDINGS AND OTHER STRUCTURESMINIMUM CLEARANCES OF WIRES ADJACENT TO
1. B
UILD
INGS
:
A. H
ORIZ
ONTA
L
(1)
TO WA
LLS, P
ROJECT
IONS
AND
GUAR
DED
WIND
OWS
(2) TO
UNGUA
RDED W
INDOWS(3)
TO BA
LCONIE
S AND
AREAS
REA
DILY
ACC
ESSI
BLE
TO
(1)
OVER
OR
UNDE
R RO
OFS
OR
PRO
JECT
IONS
NOT
REA
DILY
ACC
ESSI
BLE
TO P
EDES
TRIA
NS
(3) OV
ER ROO
FS ACC
ESSIBL
E TO
VEH
ICLE
S BU
T NO
T SU
BJEC
T
TO
TRUC
K TR
AFFI
C
(4) OV
ER ROO
FS ACC
ESSIBL
E TO
TRU
CK T
RAFF
IC
A
CCES
SIBL
E TO
PED
ESTR
IANS
DEC
KS A
ND R
OOFS
REA
DILY
(2)
OVER
OR UND
ER BAL
CONIES
B.
VER
TICA
L
2. S
IGNS
, CH
IMNE
YS,
BILL
BOAR
DS, RA
DIO
AND
TELE
VISI
ON A
NTEN
NAS,
TA
NKS
AND
OTHE
R IN
STAL
LATI
ONSNO
T CL
ASSI
FIED
AS
BUIL
DING
S
(1) RE
ADILY
ACCESS
IBLE T
O
(2) OV
ER OR
UNDER
PORTIO
NS OF
P
EDES
TRIA
NS
MESS
ENGE
RS,
SURG
E PR
OTEC
TIONWI
RES,
GRO
UNDE
D GU
YS,GR
OUND
ED N
EUTR
AL C
ONDU
CTOR
S
SUPP
LY C
ABLE
S OF
0 T
O 75
0V(OV
ERHEAD
TRIPL
EX ORQUA
DRUPLE
X)OP
EN S
UPPL
Y CO
NDUC
TORS0
TO 7
50V(OV
ERHEAD
OPEN
WIRE)
OPEN
SUP
LY C
ONDU
CTOR
S OV
ER75
0V T
O 22
kV(PR
IMARY
BARE O
R TREE
WIRE)
CL
EARA
NCE
OF
4.5
4.5
4.5
3.0
10.5
10.5
15.5
4.5
3.0
3.5
5.0
16.0
11.0
11.0
3.5
5.0
5.0
5.0
6.0
5.5
16.5
11.5
11.5
10.5
5.5
5.5
5.5
7.5
7.5
7.5
12.5
13.5
13.5
18.5
7.5
8.0
VOLT
AGES
ARE
PHA
SE T
O GR
OUND
FOR
EFF
ECTI
VELY
GRO
UNDE
D CI
RCUI
TS A
ND T
HOSE
OTH
ER C
IRCU
ITS
WHER
E AL
L GR
OUND
FAU
LTS
ARECL
EARE
D BY
PRO
MPTL
Y DE
-ENE
RGIZ
ING
THE
FAUL
TED
SECT
ION,
BOT
H IN
ITIA
LLY
AND
FOLL
OWIN
G SU
BSEQ
UENT
BRE
AKER
OPE
RATI
ONS.TA
BLE
IS T
AKEN
FRO
M NE
SC 2
34-1
, SE
E NE
SC F
OR D
EFIN
ITIO
NS A
ND C
LARI
FYIN
G IN
FORM
ATIO
N.
( FT )
( FT )
( FT )
( FT )
DWG. BASED ONLIPA CS 2034
Section 11 - Drawings
D3
(2) NO
T READ
ILY AC
CESSIB
LE TO
3.0
3.5
5.5
7.5
A.
HOR
IZON
TAL
P
EDES
TRIA
NS
(1)
OVER
OR
UNDE
R SU
RFAC
E UP
ON10
.511
.011
.513
.5
PER
SONN
EL W
ALK
B. V
ERTI
CAL
S
UCH
INST
ALLA
TION
S
PEDE
STRI
ANS
OR B
RIDG
ES
-
OVERHEAD 100 - 400 AMP SERVICEUSING STRUCTURE SUPPORTED MAST(Sheet 1 of 2)
10" MAX.
6" MIN.
SERV
ICE
MAST
HEI
GHT
TABL
E
0' T
O 3'
-0"
1
. 4"
x6"
TREA
TED
STRU
CTUR
AL L
UMBE
R
3
. 3"x3
"x1/2"
GALV.
STEEL
ANGLE3'
-0"
TO 5
'-0"
1
. 6"
x6"
TREA
TED
STRU
CTUR
AL L
UMBE
R
2
. 2 1/
2" SCH
D. 40
GALV.
STEEL
PIPE
3
. 4"x4
"x1/2"
GALV.
STEEL
ANGLE
2. 5
"x5"x1
/2" GA
LV. ST
EEL AN
GLE5'-
0" TO
7'-6"
1. 3
1/2"
SCHD.
40 GAL
V STEE
L PIPE
2. 6
"x6"x1
/2" GA
LV. ST
EEL AN
GLE7'
-6"
TO 1
0'-0
"
1. 4
" SC
HD.
40 G
ALV
STEE
L PI
PE
MAST
LEN
GTH
ABOV
EHI
GHES
T SU
PPOR
TST
RUCT
URAL
MEM
BERRE
QUIR
ED
IF M
INIM
UM C
LEAR
ANCE
CAN
NOT
BE
MET
USIN
G AN
Y OF
THE
ABO
VECO
NTAC
T TH
E LI
PA E
LECT
RIC
DESI
GN &
CON
STRU
CTIO
N DE
PT.
STUD
COND
UIT
TO M
ETER
GALV
CON
DUIT
STR
APEV
ERY
3'
1/2" B
OLTSTH
ROUG
H ST
UD
BLOC
KING
BET
WEENRO
OF R
AFTE
RS,
2'-8"
SIDI
NGSOLI
DLY
INST
ALLE
D
SEE MAST HEIGHT TABLE
FIGU
RE 1
FIGU
RE 2
STUD
COND
UIT
TO M
ETER
SIDI
NG
SEE MAST HEIGHT TABLE
2'-6"
THRO
UGH
STUD1/2
" BOLT
S
EVER
Y 3'GA
LV C
ONDU
IT S
TRAP
10" MAX.
6" MIN.
SPAC
ERSTRU
CTUR
ESU
PPOR
TED
MAST
ROOF
ING
SEE
FIGU
RE 2 G
ABLE
ROO
F CO
NSTR
UCTI
ONHI
P RO
OF C
ONST
RUCT
ION
SEE
FIGU
RE 1
MAIN
TAIN
NOT
LES
S TH
AN(3'
-0") V
ERTICA
LCL
EARA
NCE
ABOV
E RO
OFOUT
SIDE O
F (6'-
0")RA
DIUS
FRO
M TH
ESE
RVIC
E MA
ST.MA
INTA
IN N
OT L
ESS
THAN(18
") VER
TICALCL
EARA
NCE
ABOV
E RO
OFINS
IDE OF
(6'-0
") RAD
IUSFR
OM T
HE S
ERVI
CE M
AST.
4'MA
X
CLEA
RANC
ES O
F SE
RVIC
E DR
OP T
ERMI
NATI
NG O
N SU
PPOR
T MA
ST4'
(MAX)
FROM N
EAREST
EDGE.
6'-0
"
18"
MIN
SEE
ADD
ITIO
NAL
NO
TES
ON
SH
EET
2 O
F 2(
D5)
ROOF
PLAN
VIEW
3'-0
" MI
N
ELEV
ATIO
N
6'-0
"
2. 2
1/2"
SCHD.
40 GAL
V. STE
EL PIP
E
DWG. BASED ONLIPA CS 2721
2012 Edition Redbook
D4
-
NOTES:1. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME INTO CONTACT WITH ANY AWNINGS, SHUTTERS, OR ANY OTHER OBJECTS THAT MAY CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF 8' ABOVE FINISHED GRADE. FOR ADDITIONAL REQUIREMENTS SEE DWG. D18
2. PVC CONDUIT IS NOT PERMITTED TO BE USED AS A MAST.
3. CUSTOMER SHALL FURNISH MATERIAL AND LABOR FOR ALL WORK SHOWN, EXCEPT AS NOTED. ALL INSTALLATIONS ARE SUBJECT TO INSPECTION BY AN APPROVED INSPECTION AGENCY.
4. THROUGH BOLTS ARE REQUIRED FOR ANCHORING ALL SERVICE MASTS. IN THE EVENT THAT A THROUGH BOLT CANNOT BE USED AN ADEQUATELY SIZED LAG SCREW MAY BE APPROVED IF IT CAN BE SHOWN THE SCREW IS SUPPORTED BY A SOUND STRUCTURAL MEMBER.
5. FOR SOLID BLOCK OR BRICK WALL CONSTRUCTION THROUGH BOLTS SHALL BE SET IN BLOCK JOINTS THOROUGHLY EMBEDED IN MORTAR.
6. FOR SELF SUPPORTING MAST SERVICES ALL PIPE COUPLINGS MUST BE BELOW THE HIGHEST STRUCTURAL ATTACHMENT POINT.
7. MAST MUST BE OF SUFFICIENT STRENGTH TO SUPPORT A HORIZONTAL TENSION OF 1000LBS. APPLIED TO THE POINT OF
ATTACHMENT. FOR UNUSUAL CIRCUMSTANCES GUYING OF THE MAST MAY BE PERMITTED. CONTACT LIPA'S ELECTRIC DESIGN & CONSTRUCTION DEPT. FOR GUYED MAST APPROVAL PRIOR TO INSTALLATION.
USING STRUCTURE SUPPORTED MAST(Sheet 2 of 2)OVERHEAD 100 - 400 AMP SERVICE
DWG. BASED ONLIPA CS 2721
Section 11 - Drawings
D5
8. NO OTHER UTILITY MAY SUPPORT OR CONNECT AT THE MAST.
-
DROP SWING SERVICE FORINACCESSIBLE SERVICE ENTRANCE ATTACHMENT
SERVICE MAST
SERVICE ENTRANCE CABLE
GUY WIRE
SPLIT BOLT CONNECTOR, CONNECTLEAD OF GUY WIRE TO #14 LASHINGWIRE
4" MAX.
#14 SOLID COPPER WIREFOR LASHING SERVICE CABLETO GUY WIRE SERVICE CABLE TAPED
@ END W/ SELF-SEALINGMATERIAL PER NEC
SERVICE CONNECTORS
TO POLE
AUTOMATIC DEAD END
PARALLEL NEUTRALCONNECTOR
GUY GRIP FORGUY WIRE
BAIL
CONNECT GUY WIRE & #14LASHING TO NEUTRAL WIRE,EXTEND NEUTRAL FOR SERVICECONNECTION
WORK BYCONTRACTOR LIPA
WORK BY
1/2" EYEBOLT
6" M
IN.10
" MA
X.
22'-
6"TO POLEH + 2' LIPA CONNECTION
21'-
0"MA
X. H
EIGH
T OF
LAD
DERAC
CESS
IBLE
SER
VICE
H
H = HEIGHT BEYONDREACH OF SERVICELADDER
POOL
NOTE: ONLY TO BE USED WHERE NORMAL ACCESSIBLE SERVICE CONNECTION IS IMPOSSIBLE
120' SPAN MAX.1/0-3/C AL (TYPICAL)
3'-2" SAG AT 120' AT 90 F
APPROVAL BY LIPA REQUIREDPRIOR TO INSTALLATION
2012 Edition Redbook
D6
-
UNDERGROUND/OVERHEAD 100 - 320 AMPPOLE MOUNTED SERVICE
6" M
IN.10
" MA
X.
1/2" EYEBOLT
LIPA SERVICE DROP
CONDUIT SECUREDWITH STRAPS
METER SOCKET
MAIN DISCONNECTPANEL ( MAY BE LOCATED
CUSTOMERS WIRES & POINTOF ATTACHMENT
SERVICE POLE, MINIMUM25' - 30' CLASS 7PRESERVATIVE TREATED AND SETTO A MINIMUM DEPTH OF 6'-0"(CUSTOMER OWNED AND INSTALLED)
6'-0" MIN.
6'-0
" MI
N.
1/2" X 8' CU WELD OR 5/8" X 8' CU PLATED
GROUND WIRE, TWO SEPARATE GROUNDINGCONDUCTORS. GROUNDING MUST BE PERFORMEDAT THE MAIN DISCONNECT.
LIPA METER
3'-0
" MI
N.6'
-0"
MAX.
21'-
0" M
AX.15
'-0"
MIN
.
NOTE:SERVICE POLE MUST BE ADEQUATELY GUYEDTO SUPPORT THE LOADS IMPOSED BY THELIPA SERVICE DROP. AT A MINIMUM THESERVICE POLE MUST BE GUYED WHEN SUPPORTING
SERVICE SIZE(SINGLE PHASE)
LIPA SERVICE DROP LENGTH
100A NONE REQUIRED
(POLE GUY REQUIRED)
150A - 320A 60' - 100' (MAX)400A 0' - 60' (MAX)
THE FOLLOWING SERVICE DROP LENGTHS:
GROUND ROD GROUND ROD5/8" X 8' CU PLATED 1/2" X 8' CU WELD OR
UNDERGROUNDLOAD SIDE EXIT
DWG. BASED ONLIPA CS 2760
Section 11 - Drawings
D7
AT SERVICE ENTRANCE)
ALTERNATE OVERHEAD
GUYWIRE (SEE NOTE)
NOTE: USE OF PLYWOOD TO MOUNTMETER PAN IS NOT APPROVED
USAGE EXAMPLES:. MOBILE HOME. CUSTOMER OWNED PERMANENT SERVICE. TEMPORARY SERVICE
-
OVERHEAD 400 AMPPOLE MOUNTED SERVICE
6" M
IN.10
" MA
X.
LIPA SERVICE DROP
CONDUIT SECUREDWITH STRAPS
TRANS S CABINET
SERVICE POLE, MINIMUM25' - 30' CLASS 7PRESERVATIVE TREATED AND SETTO A MINIMUM DEPTH OF 6'-0"(CUSTOMER OWNED AND INSTALLED)
6'-0
" MI
N.
LIPA METER
4'-0
" MI
N.6'
-0"
MAX.
POIN
T OF
ATT
ACHM
ENT
21'-
0" M
AX.
SEE
DRAW
ING
D1 F
OR M
INIM
UM S
ERVI
CE D
ROP
CLEA
RANC
ES
NOTE:SERVICE POLE MUST BE ADEQUATELY GUYEDTO SUPPORT THE LOADS IMPOSED BY THELIPA SERVICE DROP. AT A MINIMUM THESERVICE POLE MUST BE GUYED WHEN SUPPORTING
SERVICE SIZE(SINGLE PHASE)
LIPA SERVICE DROP LENGTH(POLE GUY REQUIRED)
400A 0' - 60' (MAX)
THE FOLLOWING SERVICE DROP LENGTHS:
LOAD SIDE EXIT
DWG. BASED ONLIPA CS 2760
4" X 6" TREATED
POLE GUY
3'-6
" MI
N.LUMBER POST
MOUNT CABINET ON HORIZONTALTREATED LUMBER BRACES (3 MINIMUM)WITH LAG BOLTS.
124072
124072
2012 Edition Redbook
D8
USE OF PLYWOOD IS NOT APPROVED
-
6" M
IN.10
" MA
X.
LIPA CONNECTS PROGRAMCONNECTOR INSTALLATION
1. CLEANING - WIRE BRUSH ALL COPPER AND ALUMINUM CONDUCTORS UNTIL SURFACES ARE BRIGHT AND CLEAN. COPPER CORROSION PRODUCTS ARE POOR CONDUCTORS AND ALUMINUM OXIDE, WHICH FORMS RAPIDLY AND IS INVISIBLE, IS AN INSULATOR. WIRE BRUSHING IS A VERY IMPORTANT AND CRITICAL STEP IN MAKING A TROUBLE FREE CONNECTION AND SHOULD NEVER BE NEGLECTED EVEN IF THE CONDUCTOR APPEARS TO BE CLEAN.
2. INHIBITOR - ALL NEW CONNECTORS ARE PRE-LOADED WITH INHIBITOR. IF ANY CONNECTORS DO NOT HAVE INHIBITOR, IT MUST BE FIELD APPLIED.
3. RE-USE OF CONNECTORS - WHEN CONNECTORS ARE REMOVED AND RE-INSTALLED IN THE FIELD (EVEN FOR A SHORT TIME), THE FOLLOWING STEPS SHALL BE TAKEN: 3.1 WIRE BRUSH BOTH THE CONDUCTOR AND THE JAWS OF THE CONNECTOR.
3.2 FOR ALUMINUM TO ALUMINUM AND ALUMINUM TO COPPER CONNECTIONS, APPLY INHIBITOR TO CONDUCTORS AND WIRE BRUSH IN.
3.3 FOR ALUMINUM TO COPPER CONNECTIONS, INSTALL THE ALUMINUM ABOVE THE COPPER CONDUCTOR.
WEATHERHEAD
1/2" EYEBOLT POINT OF ATTACHMENT
LIPA SERVICE WIRE
CONNECTORS, FURNISHED BY LIPA AND
MUST BE NO GREATER THAN 24" HORIZONTALLY
CONNECTOR INSTALLATION:
INSTALLED BY THE CONTRACTOR
USE CONNECTOR TO ATTACH CUSTOMERSNEUTRAL TO LIPA SERVICE NEUTRAL
4. DO NOT TRANSFER SERVICE TO NEW POINT OF ATTACHMENT.
Section 11 - Drawings
D9
FROM WEATHERHEAD
DWG. BASED ON LIPA CS 2753
-
NOTES:
1. OVERHEAD SERVICES WHICH ARE 400 AMPERES BUT NOT MORE THAN 600 AMPERES SERVED BY OVERHEAD CONDUCTORS SHALL USE OPEN WIRE CONSTRUCTION. IF THIS IS NOT ACCEPTABLE DUE TO HEIGHT OR APPEARANCE UNDERGROUND SERVICE SHOULD BE SELECTED.
2. THE CUSTOMER IS TO INSTALL AND SUPPLY WEATHERHEAD, CONDUIT, CONDUIT STRAPS, SECONDARY RACK AND CABLES IN THE CONDUIT. CABLES SHALL BE SUFFICIENT LENGTH TO PROVIDE 48" OF SLACK CABLE AT WEATHERHEAD TO MAKE CONNECTIONS TO OVERHEAD SYSTEM.
3. SERVICE ENTRANCE HEIGHT SHALL BE BASED ON 60'(FEET) MAXIMUM SPAN AND MAINTENANCE OF 16.5 FEET MINIMUM CLEARANCE ABOVE GROUND UNDER THE GREATEST SAG CONDITIONS AS WELL AS AN 18' MINIMUM CLEARANCE FOR AREAS SUBJECT TO VEHICULAR TRAFFIC. MAXIMUM HEIGHT FOR POINT OF
LOCATION MUST BE APPROVED BY LIPA.
4. SECONDARY RACK ON SUPPORTING STRUCTURE MUST BE THRU-BOLTED; ANY OTHER TYPE FASTENERS MUST BE APPROVED BEFORE INSTALLATION.
OPEN WIRE SERVICES400 TO 600 AMP
6" M
IN.10
" MA
X.
60' FEET MAXIMUMSEE NOTE 3
124072
124072
124072
UTILITYPOLECUSTOMER'SPOINT OF ATTACHMENT
ATTACHMENT IS 21' ABOVE GRADE. INCREASED HEIGHT FOR ANY INDIVIDUAL
8" TYPICAL
DWG. BASED ONLIPA CS 2765
2012Edition Redbook
D10
IMPORTANT NOTE: 600 AMP OVERHEAD SERVICE MUST FIRST BE APPROVED BY LIPA, AND MAY BE PERMITTED ON A CASE BY CASE BASIS ONLY. ALL SERVICES OF THIS TYPE MUST BE APPROVED BY LIPA PRIOR TO INSTALLATION.
-
CABLE RISERCUSTOMER INSTALLED
COMMUNICATIONS LINE
CURB
TRAFFIC
RISER
RISER LOCATION ON POLE
SEENOTE 4
5'5'
12"15
'
24" MINIMUM COVER FOR SECONDARY30" MINIMUM COVER FOR PRIMARY
(DIRECT BURIED)
FINAL GRADE
FOR DIRECT BURIED CABLES
IMPORTANT:
UTILITY SPLICING CREWTO COMPLETE RISER POLE
(SEE NOTE 6)
SEE NOTE 3
MIN.
SEE SHEET D12 FOR NOTES
FINAL GRADE
PIPE
CONDUIT"OR"
1-1/
2"10
"MA
X.
IF CONDUIT IS USED A MANHOLE / SPLICEBOX
(INCLUDING GROUNDING ANDBONDING MATERIAL)
IS REQUIRED, SEE NOTE 7
WARNING RIBBON
RISER SHALL BE POSITIONED SO THERE IS ACLEAR VERTICAL PATH UP THE POLE TO
LIPA'S SECONDARY WIRES.
UNDER NO CIRCUMSTANCES SHALL AN EXISTING OVERHEAD SERVICE BE CONNECTED
TO AN UNDERGROUND SERVICE.
MULTIPLE SETS OF CABLE FEEDINGMULTIPLE SERVICES MUST BE CLEARLYIDENTIFIED.
DWG. BASED ONLIPA CS 2403
Section 11 - Drawings
D11
-
NOTES:1. CONTRACTORS SHALL MOUNT ONLY THE UTILITY SPECIFIED RISER MATERIAL ON THE POLE, TO A HEIGHT OF 9 TO 10 FEET ABOVE GRADE. ONLY ONE RISER IS PERMITTED FOR EACH SERVICE.
U-GUARD - 3" PE OR 3" PVC SCHD. 80 OR 3" DBL. GALV. STEEL - 10' LONG W/ BELL ENDS SECONDARY CABLE MAX. PRIMARY CABLE MAX
4 - 1/C 350 KCM 3 - 2/C #1/0 AWG 5" DOUBLE GALVANIZED STEEL U-GUARD - 5' LONG W/ BELL ENDS or 5" PE or 5" PVC SCHD.80
SECONDARY CABLE MIN. SECONDARY CABLE MAX. PRIMARY CABLE MAX. 8 - 1/C 4/0 8 - 1/C 500 KCM 3-2/C 750 KCM 2. A) THE LOCATION OF THE U-GUARD ON THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR OR THE LIPA REPRESENTATIVE ASSIGNED TO THE JOB PRIOR TO INSTALLATION OF THE CABLE / RISER. B) THE LENGTH OF THE CABLE REQUIRED FOR LIPA TO MAKE FINAL CONNECTIONS AT THE POLE SHALL BE IDENTIFIED FOR THE CONTRACTOR BY THE LIPA REPRESENTATIVE.
3. A) THE CABLE SUPPLIED BY THE CONTRACTOR FOR USE ON THE POLE SHALL BE INSTALLED AND PROPERLY SECURED TO THE POLE BY THE ELECTRICAL CONTRACTOR TO PREVENT DAMAGE AND/OR ANY ACTS OF VANDALISM FROM DAMAGING THE CABLE PRIOR TO HOOK-UP. B) CABLE IS TO BE ATTACHED TO THE POLE WELL ABOVE THE TOP OF THE RISER WITH A KELLUMS GRIP BASKET OR LENGTH OF LINE TIED IN A "ROLLING BEND KNOT" TO PROTECT THE CABLE FROM MECHANICAL BENDING DAMAGE.
4. ALL CABLE SHALL BE PROPERLY END CAPPED AT BOTH ENDS BY THE CONTRACTOR WITH APPROVED TIGHTFITTING WATERTIGHT SEALING CAPS OR IN STRICT COMPLIANCE WITH NEC 300-5 (e). **
6. LIPA SHALL COMPLETE THE CONSTRUCTION OF THE RISER PER THE APPROPRIATE CONSTRUCTION STANDARDS.
7. IF CONDUIT IS USED, MANHOLES ARE REQUIRED, CONTACT LIPA FOR DETAILS.
** THE CONCERN FOR RELIABLE ELECTRIC SERVICE REQUIRES THAT LIPA RESERVE THE RIGHT TO REFUSE TO ACCEPT OR ENERGIZE ANY CABLES THAT HAVE BEEN LEFT WITH 'ENDS' UNCAPED. MOISTURE INTRUSION HAS BEEN DETERMINED TO BE A SUBSTANTIAL CAUSE OF PREMATURE CABLE FAILURES; UNCAPPED CABLE ENDS ARE THE LEADING CAUSE OF THIS PROBLEM.
CUSTOMER INSTALLED CABLE RISERGENERAL NOTES
5. POLYETHYLENE AND PVC U-GUARD SHALL BE FASTENED WITH 1/4" X 2 1/2" LAG SCREWS WITH CUSHION. STEEL U-GUARD SHALL BE FASTENED WITH 3/8" X 2 1/2" LAG SCREWS.
DWG. BASED ONLIPA CS 2403
2012 Edition Redbook
D12
-
PULL BOX AND MANHOLE SPECIFICATIONSCUSTOMER / CONTRACTOR INSTALLED
SERVICE TYPE
SINGLE PHASEANDTHREE PHASE
MAXIMUM CABLE SIZE
1 SET OF 4/0
BOX DESCRIPTION AND LOCATION
PE SPLICE BOX IN GRASS AND NOVEHICLE TRAFFIC LOCATION
SPLICE BOX / MANHOLE MINIMUMDIMENSIONS(LENGTH X WIDTH X DEPTH)
(INCHES)BOX: 25 X 16 X 16COVER: 22 X 12
BOX: 33 X 20 X 17COVER: 31 X 17
BOX: 41 X 41 X 18COVER: 33 XX 33
BOX ID: 42 X 33 X 24CAST IRON FRAME: 41 X 41CAST IRON COVER: 32 DIAMETER
BOX ID: 54 X 42 X 48CAST IRON FRAME: 41 X 41CAST IRON COVER: 32 DIAMETER
SINGLE PHASE2 SETS OF 4/0
OR1 SET OF 500 KCM VEHICLE TRAFFIC LOCATION
PE SPLICE BOX IN GRASS AND NO
SINGLE PHASE 2 SETS OF 500 KCM OR VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO
SINGLE PHASEANDTHREE PHASE
4 SETS OF 4/0OR2 SETS OF 500 KCM
PRECAST CONCRETE BOX TYPE B 3-6LOCATED IN GRASS OR VEHICLETRAFFIC AREA
THREE PHASEANDSINGLE PHASE
1 SET OF 3-2/C 1/0 AL 15KVOR
6 SETS OF 4/0TRAFFIC AREALOCATED IN GRASS OR VEHICLEPRECAST CONCRETE BOX TYPE TS
1. BOX / MANHOLE SHALL BE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.2. BOX / MANHOLE SHALL BE INSTALLED ON THE CUSTOMERS PROPERTY AT THE LOCATION WHERE THE SERVICE EXITS THE CUSTOMERS PROPERTY AND ENTERS THE PUBLIC RIGHT OF WAY OR LIPA EASEMENT AREA.
3. INSTALL BOX / MANHOLE PARALLEL TO THE ROADWAY OR REAR PROPERTY EASEMENT LINE.4. FOR CONCRETE MANHOLES: ENTRANCE SHALL BE MADE THROUGH END WALL KNOCKOUTS ONLY. DUCT SHALL EXTEND A MAXIMUM OF 1" PAST THE INTERIOR FACE OF THE MANHOLE WALL. ALL PENETRATIONS THOUGH THE CONCRETE WALL SHALL BE SEALED WITH GROUT.
5. FOR PE SPLICE BOXES: CONDUIT SHALL ENTER THE BOX BENEATH THE SIDE WALLS BY MEANS OF A CONDUIT SWEEP. CONDUIT SHALL EXTEND 2" ABOVE THE BOTTOM OF THE BOX.
6. ALL CONDUITS SHALL BE SEALED AT THE BOX/MANHOLE AND BUILDING ENTRANCE USING PRODUCT SPECIFICALLY MADE FOR DUCT SEALING APPLICATION.
7. BONDING BUSHING MUST BE SUPPLIED FOR METALLIC CONDUITS.
INSTALLATION REQUIREMENTS:
DWG. BASED ONLIPA CS 6159
Section 11 - Drawings
D13
THREE PHASE 1 SET OF 500 KCMBOX: 41 X 41 X 18COVER: 33 X 33VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO
BOX: 33 X 20 X 17COVER: 31 XX 17THREE PHASE 1 SET OF 4/0 VEHICLE TRAFFIC LOCATIONPE SPLICE BOX IN GRASS AND NO
OR3 SETS OF 500 KCM
8. 15KV PRIMARY CABLE INSTALLED IN TS BOX OR 41 X 41 X 18 PE BOX ONLY.
2 SET OF 3-2/C 1/0 AL 15KVOR
1 SET OF 1-2/C 1/0 AL 15KV
-
SECONDARY CONDUCTORS
GRADE
SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY
SERVICE CONNECTION FROM PRIVATE PROPERTY - REAR PROPERTY POLE LINE
DIRECT BURIED CABLE (U.S.E.-2)*INSTALLED -OWNED ANDMAINTAINED BY CUSTOMER
RISER, SEE DWG. D11 & D12
4"
METER PAN *
SLEEVE *2" MIN(SEE NOTE 4)2'-0" MINCOVER
GRADEEASE
MENTLI
NE
3'-0" MIN6'-0" MAX(SEE NOTE 5)
1'-0" MIN1'-6" MAX
UNDERGROUND SERVICE
FOR REQUIREMENTS* SPLICE BOX REQD. IF
SERVICE IS IN CONDUIT
SERVICE CONNECTION FROM OVERHEAD DISTRIBUTION - NEAR SIDE HIGHWAY POLE LINE
100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT
5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO TOP
3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS
(SEE NOTE 4)2" MINSLEEVE *
METER PAN *
DIRECT BURIED CABLE (U.S.E.-2)*MAINTAINED BY CUSTOMERINSTALLED -OWNED AND
ROAD SURFACE
SECONDARY CONDUCTORS
GRADE
FOR REQUIREMENTSRISER, SEE DWG. D11 & D12
TO LIPA SECONDARYSUFFICIENT CABLE TO CONNECT
4"
SERVICE IS IN CONDUIT* SPLICE BOX REQD. IF
CURB
LINEPR
OPER
TY
3'-0" MIN
1'-6" MAX1'-0" MIN
(SEE NOTE 5)6'-0" MAX
GRADE
2'-0" MINCOVER
NOTES
TO CUSTOMERS PROPERTY LINE.
1. * INDICATES ITEMS PROVIDED BY CUSTOMER.2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR
AND THE REMAINDER TO BE COMPLETED BY LIPA.
5. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT TO
3. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS
2. FIRST 10' OF U-GUARD RISER TO BE INSTALLED BY CONTRACTOR AND THE REMAINDER TO BE COMPLETED BY LIPA.
TO EASMENT LINE.
NOTES1. * INDICATES ITEMS PROVIDED BY CUSTOMER.
4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.
4. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD. 80.
WARNING RIBBON
WARNING RIBBON
DWG. BASED ONLIPA CS 5523
2012 Edition Redbook
D14
TOP OF METER GLASS.
3'-0" MAX
3'-0" MAX
OF METER GLASS.
-
SECONDARY CONDUCTORS
NOTES
GRADE ROAD SURFACECURB
SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY
SERVICE CONNECTION FROM FAR SIDE - HIGHWAY POLE LINE
CURB
* MIN 2" GI OR SCHEDULE 40 NON-METALIC CUSTOMER INSTALLED
DIRECT BURIED CABLE (USE-2)INSTALLED -OWNED ANDMAINTAINED BY CUSTOMER
RISER, SEE DWG. D11 & D12
4"
METER PAN *
SLEEVE *2" MIN(SEE NOTE 3)2'-0" MINCOVER
GRADEPROP
ERTYLI
NE
3'-0" MIN6'-0" MAX
(SEE NOTE 4)
1'-0" MIN1'-6" MAX
* MIN 2" G.I. SWEEP OR SCHEDULE 80 NON METALIC SWEEP CUSTOMER INSTALLED
DIRECT BURIED CABLE (USE-2)
SLEEVE *
METER PAN *
(SEE NOTE 3)2" MIN
MAINTAINED BY CUSTOMER
1'-6" MAX1'-0" MIN
INSTALLED -OWNED AND
2'-0" MINCOVER
LINEPROPERTY
CURB
NOTES
6'-0" MAX3'-0" MIN
(SEE NOTE 4)
GRADE LINEROAD SURFACE
SPLICE *BOX
* SUFFICIENT CABLE TO CONNECTTO LIPA SECONDARY(LIPA TO PREPARE CONNECTION)
SEE NOTES 1 & 2
UNDERGROUND SERVICE
FOR REQUIREMENTS
1. * INDICATES ITEMS PROVIDED BY CUSTOMER.
2. OWNED AND MAINTAINED BY LIPA FROM SECONDARY CONDUCTORS TO BASE OF POLE.
4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT. TO TOP OF METER GLASS.
* SPLICE BOX REQD. IFSERVICE IS IN CONDUIT
1.CONDUIT AND SPLICE BOX WILL BE REQUIRED IN ZONED NETWORK AREAS, IN ZONED U.G. AREAS A SPLICE BOX MAY BE REQUIRED. IF SERVICE IS IN CONDUIT A SPLICE BOX IS REQUIRED.CONTRACTOR TO LEAVE 4' OF SERVICE CABLE IN SPLICE BOX
2. WHERE NO SPLICE BOX IS REQUIRED, CONTRACTOR TO LEAVE THREE (3) FEET OF SERVICE CABLE (OR AS DIRECTED BY LIPA) FOR LIPA
CONNECTIONS.
4. 400 AMP - 800 AMP WILL REQUIRE 4'-0" MIN. HEIGHT.
5. * INDICATES ITEMS PROVIDED BY CUSTOMER.
FOR LIPA CONNECTIONS.
SERVICE CONNECTION FROM UNDERGROUND DISTRIBUTION - NEAR OR FAR SIDE FACILITIES
100 - 800 AMP SINGLE OR THREE PHASE BY BUILDER/APPLICANT
3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE
SCHD. 40 GALV., NON-METALLIC SHALL BE SCHD 80.3. 2" MINIMUM SLEEVE, RIGID METAL SHALL BE
SCHD. 40 GALV., NON-METALLIC SHALL BESCHD 80.
WARNINGRIBBON
WARNING RIBBON
DWG. BASED ONLIPA CS 5523
Section 11 - Drawings
D15
3'-0" MAX
TO TOP OF METER GLASS.
3'-0" MAX
-
METER PAN *
3" WATERTIGHT ADAPTOR *(CONDUIT TO METER)
OR RIGID GALVANIZED
(TO LIPA SPEC)
3" SCHEDULE 80 PVC *
FINAL GRADE
CABLE-IN-CONDUIT
24"
MIN.
6" TO 12"
45*CUT CONDUIT @CONDUIT ENDDUCT SEAL
LIPA INSTALLED SINGLE PHASE RESIDENTIAL RUD SERVICE
36"
MAX.
NOTES:
1. * INDICATES ITEMS PROVIDED BY CONTRACTOR.2. 300 AMP AND LARGER SERVICES MAY REQUIRE TWO CONDUITS INTO METER PAN.
CABLE-IN-CONDUIT
24"
MIN.
FINAL GRADE
36"
MAX.
(CONDUIT TO METER)
2" SCHEDULE 80 PVC *OR RIGID GALV. STEEL
2" WATERTIGHT ADAPTOR *
(TO LIPA SPEC)METER PAN *
6"
2" PVC OR RGS COUPLING*
45 SWEEP*
2" MECHANICALCOUPLING *
AIM IN DIRECTIONOF SPLICE BOX
3 INCH SERVICE RISER 2 INCH SERVICE RISER
3. 2" MECHANICAL COUPLING SHALL BE EITHER ANACO P/N HUSKY SD-4006 OR FERNCO P/N 1056-22/SR-11.
DWG. BASED ONLIPA CS 6491
2012 Edition Redbook
D16
-
SPLICE BOX
IN CONDUIT
COMM
ON T
RENC
H
CURB
UTILITY CABLEIN CONDUIT
CURBROAD
ROAD
SERVICE CONDUIT SYSTEM *
COILED & COVEREDWITH 4'x4'x1/2" PLYWOOD* SEAL CABLE ENDS
SCHD. 40 CONDUIT *DUCTSEAL CONDUIT *
SEAL CABLE *ENDS
PLYWOOD *
24" MIN.
SPLICE BOX
PLAN VIEW
UTILITY CABLE
(TEMPORARY)
24"
* TERMINATE CONDUIT24" AWAY FROM SPLICEBOX ON CENTERLINE.
TEMPORARY 48" x 48" x 1/2"
(MIN. SCHD 40)
10 FOOT MINIMUM CABLE *
ANGLE OF APPROACH TO SPLICE BOXTO BE DETERMINED BY LOCAL FIELDCONDITIONS AND APPROVAL BY UTILITY.
SINGLE PHASE RESIDENTIAL RUD SERVICECUSTOMER / CONTRACTOR INSTALLED
NOTES:
1. * DENOTES ITEMS PERFORMED BY CONTRACTOR / CUSTOMER.2. UTILITY CONNECTS CONDUIT TO SPLICE BOX AND MAKES SERVICE CONNECTIONS IN SPLICE BOX.
ELEVATION VIEW
3. 200 AMP SERVICES SHALL BE RUN IN ONE 2" CONDUIT MIN. 320 AMP SERVICES SHALL BE RUN IN A 3 1/2" CONDUITS MIN. . 400 AMP SERVICES SHALL BE RUN IN A SINGLE 4" CONDUIT. ALL SERVICES SHALL BE RUN FROM THE METER PAN TO A SPLICE BOX AT THE PROPERTY LINE.
4. 600 AND 800 AMP SERVICES SHALL BE RUN IN TWO PARALLEL 4" CONDUITS FROM THE TRANS S CABINET TO A SPLICE BOX AT THE PROPERTY LINE. 600 AND 800 AMP SERVICES ARE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.
DWG. BASED ONLIPA CS 6491
Section 11 - Drawings
D17
5. UNDER NO CIRCUMSTANCES SHALL A CUSTOMER / CONTRACTOR ENTER A LIPA SPLICE BOX.
ELECTRIC SERVICECABLE IN CONDUITCOMMUNICATIONSFACILITIES
GAS SERVICE
12" MIN. 24"
SERVICE TRENCH
-
INSIDE WALL
METER SOCKET ENCLOSURE
SECURELY AND LEVEL IN HORIZONTALAND VERTICAL PLANES
MAIN DISCONNECT
OVERHEAD SERVICE CONDUIT
CONDUIT STRAP (TYP.)
"LB" CONDULET
GROUND CONDUCTOR
GROUND CLAMP
5/8" X 8' CU PLATED GROUND ROD
FINISHED GRADE
3'-0"
MIN /
6'-0"
MAXSEE NOTES 5 & 6
7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER
WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,
8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY
6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED
THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE
OF THE AUTHORIZED ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
CONNECTION TO THE METER ENCLOSURE.
EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.
INSTALLATION FOR SAFE ACCESS.
NOTES:
STATED.
1/2" x 8' CU WELD OR
FLOOR TO CEILING4' CLEARANCE
TO NEUTRAL OF CUSTOMER'S MAINDISTRIBUTION PANEL
9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURE SHALL BE USED.
TO CUSTOMER'S
TOP OF METER GLASSTO BE MOUNTED
OVERHEAD SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET METER INSTALLATION
5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).
ADEQUATELY SECURED
DWG. BASED ONLIPA CS 8001
2012 Edition Redbook
D18
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
-
1/2" x 8' CU WELD OR5/8" X 8' CU PLATED
INSIDE WALL
METER SOCKET
TO CUSTOMER'S
CONDUIT STRAP
"LB" CONDULET
GROUND CONDUCTOR
GROUND CLAMP
MAIN DISCONNECT
ENCLOSURE SECURELY ANDRIGIDLY MOUNTED
SERVICE ENTRANCECONDUIT & CABLE
3'-0" MIN.6'-0" MAX.
(TYP.)
GROUND ROD
LOCKNUT ANDBONDINGBUSHING (TYP.)
7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
THE NATIONAL ELECTRIC CODE.4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE
OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.
NOTES:
STATED.
TO NEUTRAL OF CUSTOMER'S MAIN
TOP OFMETER GLASS
A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS.6.
4' CLEARANCEFLOOR TO CEILING
12" MIN.CLEARANCE
FINISHEDGRADE
12" MIN.CLEARANCE
WALL
WALL
8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
DISTRIBUTIONPANEL
UNDERGROUND SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET METER INSTALLATION
LUGNEUTRAL
MAIN DISCONNECT
METER SOCKET
& LOCKNUT (TYP)BONDING BUSHING
& CABLECONDUITLINE SIDE TO CUSTOMER
BYPASS
(TYP)LEVER
UNDERGROUND
(SEE NOTE 5)
5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.
DWG. BASED ONLIPA CS 8007
Section 11 - Drawings
D19
9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE, RIGHT SIDE OFMETER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE ASSHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED TO PERMIT PROPER OPERATION OF THE LEVEL,AND SHALL BE COVERED WIRE.
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
-
SECURELY AND LEVEL IN HORIZ.AND VERTICAL PLANES
CONDUIT STRAP
GROUND CLAMPFINISHED GRADE
GROUND
(TYP) OVERHEADSERVICECONDUIT
CONDUCTOR
SEE NOTES5 & 6
6'-0" MAX
2'-3" MIN
TOP OF METER GLASS
TOP OF METER GLASS
WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,
8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY
6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED
THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE. WIRES INTENDED TO
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE
OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
CONNECTION TO THE METER ENCLOSURE.
BE USED FOR BONDING SHALL NOT BE PLACED IN CONTACT WITH ANY GAS PIPE.
EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O'CLOCK POSITION.
NOTES:
STATED.
6' MAX
A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS.7.
10. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALYAND EXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES
9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
1/2" x 8' COPPER WELD OR 5/8" X 8' COPPER PLATED
GROUND ROD
4' CLEARANCEFLOOR TO CEILING
12"MIN.12" MIN
WALL WALL
GROUNDCND. TONEUTRALBLOCK.
FINISHED GRADE
METER SOCKET ENCLOSURETO BE MOUNTED
2'-3"MIN.
GROUND CONDUCTORTO WATER PIPE
BEING SERVED.
OVERHEAD AND UNDERGROUND SERVICESINGLE PHASE SELF CONTAINED METEROUTDOOR SOCKET TROUGH MULTIMETER INSTALLATION
5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).
UNDERGROUND SERVICE CONDUIT(SEE NOTE 11)
11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.
SUITE I.D.SEE NOTE 10
DWG BASED ONLIPA CS 8005
2012 Edition Redbook
D20
OVERHEAD SERVICE CONDUIT
-
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE EQUIPPED WITH A FIFTH JAW
3. GAS PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICAL 250 OF THE NATIONAL ELECTRICAL CODE.
6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED APPROXIMATELY ONE INCH FROM THE TOP OF THE METER PAN. WEATHER TIGHT TYPE "SE" CONNECTORS SHALL BE USED
7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR
8. IN ADDITION TO LIPA REQUIREMENTS, INSTALLATIONS, MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES HAVING JURISDICTION.
10. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND EXTERNALLYWITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.
LOCATED IN THE NINE O' CLOCK POSITION.
FOR CONNECTION TO THE METER ENCLOSURE.
NOTES:
SAFE ACCESS.
FINISHED FLOOR OR GRADE
WALL
12" MIN
INTERNAL BUSING
OF METER GLASSTOP
3'-0" MIN.6'-0" MAX.
1/2" x 8' CU WELD OR
OVERHEAD ENTRANCE
WALL
12" MIN
UNDERGROUND AND OVERHEAD SERVICESINGLE PHASE SELF CONTAINED METERSOUTDOOR MULTI-METER SOCKET ENCLOSURE
(SEE NOTES 5 & 6)
5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).
5/8" X 8' CU PLATED GROUND ROD
ALTERNATE UNDERGROUNDCONDUIT ENTRANCE(SEE NOTE 11)
11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.
UNIT IDENTIFICATIONSEE NOTE 9
DWG. BASED ONLIPA CS 8009
Section 11 - Drawings
D21
GROUND CONDUCTOR TONEUTRAL OF CUSTOMERSMAIN DISCONNECT PANEL
12. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURESHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRE.
-
FINISHED GRADE
"LB" CONDULET
INSIDE WALL
MOUNT PLUMB & LEVEL
TO CUSTOMER'S
WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE,
THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FORFEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROMCONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHTTHE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED INOTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ONPROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY
6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED
THE NATIONAL ELECTRIC CODE.4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.
CONNECTION TO THE METER ENCLOSURE.
SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.
NOTES:
CONDUIT STRAPS
MAIN DISCONNECT
POINT OFATTACHMENT
LEAVE 3'-0" OF CONDUCTORFOR CONNECTION. FINAL CONNECTION BY LIPA.
SERVICE ENTRANCEWEATHER HEAD
SERVICE DROP CABLE
TOP OF METER GLASS
OUTDOOR POLYPHASEMETER SOCKET
240/120 208Y/120
PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY
PHASE A BLUE BLUE
LINE SIDEHUB
NEUTRAL LUG
ALTERNATE POSITIONOF LOAD CONDUIT
BONDING BUSHING& LOCKNUT
METER SOCKET
LOAD SIDE
15'-
0"MI
N
6'-0
"MAX
6"MI
N10
"MAX
3'-0
"MIN
CONDUIT
OVERHEAD SERVICE CONDUIT
A
N A
B C
B C
TO NEUTRAL OF CUSTOMER'S MAINDISTRIBUTION PANEL
4' CLEARANCEFLOOR TO CEILING
1/2" x 8' CU WELD OR5/8" X 8' CU PLATEDGROUND ROD
GROUND CONDUCTOR
PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE
CONDUCTORS TO BE IDENTIFIED WITH COLOREDTAPE
DELTA WYE
OVERHEAD SERVICEPOLY-PHASE SELF CONTAINED METERS200 AMPERE SOCKET METER INSTALLATION
(SEE NOTES 5 & 6)
5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.(NEC)
ADEQUATELY SECURED
DWG. BASED ONLIPA CS 8207
2012 Edition Redbook
D22
7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER
8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
INSTALLATION FOR SAFE ACCESS.
9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
10. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURESHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRED.11. CONDUIT SHALL BE RIGID METAL OR SCHEDULE 80 PVC.
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE
-
MOUNT SOCKET SECURELY,
TO CUSTOMER'S
6. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER
7. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY SHALL BE EQUIPPED
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE
OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM. ONLY NEUTRAL CONDUCTOR IS PERMITTED BEHIND
INSTALLATION FOR SAFE ACCESS.
NOTES:
CONDUIT STRAP
PLUMB & LEVEL
MAIN DISCONNECT
OUTDOOR POLYPHASEMETER SOCKET
DELTA WYE
PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY
PHASE A BLUE BLUE
GROUND
FINISHED GRADE
"LB" CONDULET
INSIDE WALL
3'-0
"MIN6'
-0"M
AX
CONDUCTOR
TOP OF METER GLASS
4' CLEARANCEFLOOR TO CEILING
TO NEUTRAL OFCUSTOMER'S MAINDISTRIBUTION PANEL
1/2 x 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD
PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE
8. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
STATED.
240/120 208Y/120
UNDERGROUND SERVICEPOLY-PHASE SELF CONTAINED METERS200 AMPERE SOCKET METER INSTALLATION
LUGNEUTRAL
DISCONNECT
METER SOCKET
& LOCKNUT (TYP)BONDING BUSHING
& CABLECONDUITLINE SIDE
TO CUSTOMERMAIN
PERMANENT
BYPASSN BA
A B
C
C (TYP)LEVER
NEUTRAL JUMPER
(TYP)
UNDERGROUND SERVICE CONDUIT(SEE NOTE 5)
5. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHEDULE 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (E.M.T.)
AND INTERMEDIATE METALLIC CONDUIT (I.M.C.) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.
ADEQUATELY SECURED
BYPASS LEVER.
DWG. BASED ONLIPA CS 8209
Section 11 - Drawings
D23
9. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER,
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
AND SHALL BE COVERED WIRE.
-
GAS SERVICE
GAS METER
RIGHTALTERNATEPOSITION
LEFTALTERNATEPOSITION
2. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE ELECTRIC
3. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
1. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
METER INSTALLATION FOR SAFE ACCESS.
NOTES:
4. A MINIMUM SEPARATION OF 1'-0" MUST BE MAINTAINED BETWEEN GAS METER, REGULATOR, UNIONS
5. SEPARATION OF GAS SERVICE PIPE OR TUBING AND ALL OTHER UNDERGROUND FACILITIES OR STRUCTURES SHALL BE MAINTAINED IN ACCORDANCE WITH APPROPRIATE CONSTRUCTION
6. NO ELECTRIC METER ENCLOSURE SHALL BE INSTALLED ABOVE THE GAS METER.
MINIMUM1'-0"
7. NO PROTECTION BOLLARDS SHALL BE PLACED IN FRONT OF THE ELECTRIC METER.
ELECTRIC METER ENCLOSURE
STANDARDS.
8. VENTING OF GAS REGULATOR SHALL BE PLACED A MINIMUM OF 1'-0" FROM THE NEAREST PART OF THE ELECTRIC METER INSTALLATION.
CLEARANCES BETWEENELECTRIC & GAS METERS
9. A 1' SEPARATION FROM GAS LOAD PIPE TO THE DISTRIBUTION PANEL IS REQUIRED.
10. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OF 3' CLEARANCE IS REQUIRED BETWEEENTHE GAS SERVICE PIPING AND METERS AND ANY ELECTRICAL SERVICE EQUIPMENT.
DWG. BASED ONLIPA CS 8015
2012 Edition Redbook
D24
COUPLINGS, JOINTS, AND VENTS AND ELECTRIC METERING EQUIPMENT.
MINIMUM1'-0"
GAS METER
GAS SERVICE
GAS METER, REGULATOR, UNIONSAND VENTS NOT PERMITTED INSHADED AREA
-
7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION
OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE
8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL
AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF LEVER.
6. LINE AND LOAD CONDUIT CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE
THE NATIONAL ELECTRIC CODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.
OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES.
SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM.
FOR SAFE ACCESS.
NOTES:
9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY ANDEXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.
A
A
B
B
C
C
DELTA WYE
PHASE B BLACK BLACKPHASE C ORANGE REDNEUTRAL WHITE OR GRAY
PHASE A BLUE BLUE
NEUTRAL LUGA
A
B
B
C
C
10. LINE CONDUCTORS SHALL ENTER METER ENCLOSURE ON THE TOP OR BOTTOM LEFT.
11. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.
OVERHEAD LINE SIDE TROUGH
POLYPHASEMETERENCLOSURE
JUMPERNEUTRAL PERMANENT
(TYP)
(TYP)
(TYP)BYPASSLEVER
LINE SIDECONDUIT & CABLE
CONDUITLINE SIDE TO CUSTOMER
MAIN DISCONNECT DISCONNECTMAINTO CUSTOMER
TO CUSTOMERMAIN DISCONNECT
ENCLOSURE
SINGLE PHASEMETER
2" MIN
2" MIN
N N
& CABLE
NEMA TYPE 3R MIN.
2" MIN.
METERSOCKETASSEMBLY(TPY.)
(TYP.)
12"MIN.
12"MIN.
WALLWALL
ALTERNATE LOCATION OF LINE SIDE TROUGHNEMA TYPE 3R MIN.
4" MIN
12. IDENTIFICATION OF PHASE CONDUCTORS SHALL BE WITH COLORED TAPE FOR A MINIMUM OF TWO INCHES.
PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE
TROUGH SUPPLYSINGLE AND POLY-PHASE SELF CONTAINED METERS
200 AMPERE MULTI-METER SOCKET INSTALLATION
240/120 208Y/120
5. CONDUIT SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC.
DWG. BASED ONLIPA CS 8211
Section 11 - Drawings
D25
3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.
AND SHALL BE COVERED WIRE.
-
2. FOR SELF-CONTAINED METER ENCLOSURES, 2" RIGID GALVANIZED STEEL PIPE WITH APPROPRIATELY SIZED CHANNEL AND CONCRETE BASE MAY BE USED IN PLACE OF 4" PIPE DESIGN ; 4" X 4" TREATED LUMBER MAY
NOTES:
METER H FRAME CONSTRUCTIONOUTDOOR MOUNTING FOR TRANSFORMER AND/OR METER CABINET
1. CONCRETE FILLED PROTECTION BOLLARDS SHALL BE INSTALLED WHEN INSTALLATION IS IN THE VICINITY OF VEHICULAR TRAFFIC. BOLLARDS SHALL BE PLACED A MINIMUM OF 4' FROM THE CABINET AND SHALL BE PAINTED FLUORESCENT YELLOW. BOLLARDS SHALL BE CONSTRUCTED FROM A MINIMUM OF 3.5" OUTSIDE DIAMETER SCHEDULE 40 GALVANIZED PIPE, SHALL BE SPACED 24" ON CENTERS AND SHALL BE A MINIMUM OF 3' HIGH.
4'- 0" MIN*6'- 0" MAX
CONDUITSUPPORT
TOP OF METER
AS NEEDED
LOCKNUT
ENTRANCE CONDUCTORSUNDERGROUND SERVICE
RGS CONDUITSHC. 80 PVC OR
12" DIA. CONC.FILLED SONOTUBE
TRANSFORMER
METER CABINET
GALV. U-BOLT
FINISHED GRADE
6" MIN.
W/ CHAMFER6" MIN.
(TYP.)
3/8" DIA. (TYP.)
1-1/2" x 1-7/8"GALV. CHANNEL
4" SCH. 40 GALV.
(SEE NOTE #2)
GALV. CAP
STEEL PIPE
(TYP.)
(TYP.)
H - FRAME INSTALLATIONS ARE RESTRICTED/NOT PERMITTED BY SOME MUNICIPALITIES. CHECK LOCAL CODES PRIOR TO INSTALLATION.
(SEE NOTE 3)
3. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.
BE USED IN PLACE OF 4" X 6" POST DESIGN. USE OF PLYWOOD FOR EQUIPMENT INSTALLATION IS NOT PERMITTED.
4. FOR ADDITIONAL TRANS S CABINET REQUIREMENTS SEE DRAWINGS D28 & D29. FOR ADDITIONAL
(TYP.)
OR STRAP
AND/OR
(TYP.)
3'-6"
CONDUIT STRAP
STEEL OR GALVANIZED LAGFASTENED WITH STAINLESSMETER ENCLOSURE TO BE
ANGLE CUTS (TYP).
4" X 6" TREATED LUMBERPOSTS, AND 5/4" CROSS
METAL CAP OR
TRANSFORMER
METER CABINETAND/OR
(TYP.)LOCKNUT
(TYP.)
MIN.
OR THROUGH BOLTS
ALTERNATE DESIGN
FINISHED GRADE
STANDARD DESIGN
DWG. BASED ONLIPA CS 8602
2012 Edition Redbook
D26
CT CABINET WITH REMOTE METER SOCKET REQUIREMENTS SEE DRAWINGS D30 & D31.
SHC. 80 PVC OR RGS CONDUIT(SEE NOTE 3)UNDERGROUND SERVICE ENTRANCE CONDUCTORS
BRACES SEE NOTE #2
5/4 X 6" TREATED LUMBERCROSS BRACE (TYP)
may be 3'-0"meters, min. height * Note: For self-contained
5. CHECK WITH LOCAL MUNICIPALITY FOR ANY SPECIAL REQUIREMENTS BEFORE INSTALLING METERINGEQUIPMENT ON H-FRAME.
-
12"TRANS "S" TRANS "S"
MULTI - METER STACK
2. WHEN METERS ARE ON WALLS FACING EACH OTHER, THERE MUST BE 4' OF CLEAR SPACE FROM FLOOR TO CEILING BETWEEN METERS.
SWIT
CHGE
AROR
TRA
NS "
S"
3. SWITCHGEAR DOORS MUST BE ABLE TO OPEN FULLY WITHOUT BEING OBSTRUCTED BY ANY METER ENCLOSURES OR WALLS.
4' MIN
4' MIN
TRANS "S"
OR T
RANS
"S"SW
ITCH
GEAR
SELF-CONTAINEDMETER ENCLOSURES
SELF-CONTAINED METER ENCLOSURES
4. ROOMS CLASSIFIED AS CONFINED SPACE AND THOSE THAT REQUIRE LADDER ACCESS SHALL SHALL NOT BE USED AS METER ROOMS.5. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS.
6. MINIMUM METER ROOM CEILING HEIGHT SHALL BE 6'-6". ADEQUATE LIGHTING SHALL BE
7. GAS METERS ARE NOT PERMITTED IN ELECTRIC METER ROOMS.
ELECTRIC METER ROOMEQUIPMENT CLEARANCES
2" 2"
12"TRANS "S"2"
PROVIDED IN METER ROOM.
DWG. BASED ONLIPA CS 8604
Section 11 - Drawings
D27
NOTES:
1. METER ROOM CONSTRUCTION SHALL COMPLY WILL ALL CODE REQUIREMENTS ( eg. NEC110.26) PERTAINING TO ACCESS, EGRESS, AND SAFETY.
8. FOR EXISTING METER ROOMS WITH GAS METERS, A MINIMUM OR 3' CLEARANCE IS REQUIRED BETWEEN THE GAS SERVICE PIPING AND METER AND ANY ELECTRICAL SERVICE EQUIPMENT.
12"
12"
12"
12"
4' MIN
4' MIN
5'MIN
12"
5'MIN
12"
NOT TO SCALE
NOT TO SCALE
-
TIN PLATED COPPER BUS
STANDOFFINSULATOR
NEUTRALBUS
LIPA APPROVED
WITH METER SOCKETAND
4", 3.5" CONCENTRICKNOCKOUTS (4 TYP.)
TOP VIEW
TEST SWITCH
SILVER OR
HEX SCREW ( 3 typ.)
K.O TO ACCOMODATELIPA's LOCKING DEVICE
METER ENCLOSURERECESSED IN DOOR
CURRENT TRANSFORMERSFURNISHED AND INSTALLED
BOTTOM VIEW
METER FURNISHEDAND INSTALLED BY LIPA
GROUND STRAP
CONTINUOUS STAINLESSSTEEL PIANO HINGED DOOR.LEFT HAND SWING ONLY
SIDE VIEW
(2 TYP.)
7"6"6"5"
6" 6"6" 6" 3"3"
HUB OPENING FOR 3", 3.5" OR 4" HUB
CL CL CL
GROUND LUG
NEMA TWO HOLE LUGPATTERN
RACEWAYFORBOTTOMENTRY OR EXIT
400 TO 800 AMPERE SERVICETRANS "S" CABINET INSTALLATION
FOR NOTES SEE DRAWING D29 DWG. BASED ONLIPA CS 8804
2012Edition Redbook
D28
TRANS-S CABINET
-
NOTES:
1. BUS BARS SHALL BE SILVER OR TIN PLATED COPPER AND SHALL BE SIZED PER THE NEC.
2. ONLY THE RIGHT HAND SIDE OF THE CABINET SHALL ALLOW FOR LINE AND LOAD CABLES TO ENTER AND EXIT THROUGH THE BOTTOM OF THE CABINET. THIS SPACE SHALL ALLOW FOR THE CABLES TO MEET THE MINIMUM BENDING RADIUS TO THE NEAREST PHASE OR NEUTRAL BUS. AS PER THE NEC.
3. CABINET DESIGN SHALL HAVE PROVISIONS FOR A SOLID DOOR TO ALLOW FOR THE METER ENCLOSURE TO BE MOUNTED REMOTELY FROM THE CABINET.
4. MANUFACTURER SHALL FURNISH AND INSTALL 1/2-13 STUDS WITH SPLIT LOCK WASHERS AND HEX NUTS FOR C.T MOUNTING.5. USE ONLY MANUFACTURED APPROVED LUG KITS.
7. THIS STANDARD SHALL NOT BE USED AS A DESIGN CRITERIA. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS ONLY. LARGER DIMENSIONS SHALL BE USED WHERE REQUIRED BY CODE.
400 TO 800 AMPERE SERVICETRANS "S" CABINET INSTALLATION - NOTES & BONDING DIAGRAM
8. MAINTAIN CLEARANCES BETWEEN TRANS S CABINET AND TROUGHS OF 2" ON TOP AND 4" ON BOTTOM OF CABINET.
Section 11 - Drawings
D29
NN
NON-METALLICCONDUIT/
LINE
BOND STRAPNEUTRAL-TO-ENCLOSURE
BONDINGBUSHING
BOND TOENCLOSURE
RACEWAYRACEWAYCONDUIT/METALLIC
TRANS SCABINET
TRANS SCABINET
BOND STRAPNEUTRAL-TO-ENCLOSURE
LINE
TRANS S CABINET BONDING DIAGRAMNON - GFI MAIN DISCONNECT INSTALLATION
GFI MAIN DISCONNECT INSTALLATIONTRANS S CABINET BONDING DIAGRAM
LINE
RACEWAYCONDUIT/
NON-METALLIC
N
BOND* ENCLOSURE
TRANS SCABINET
METALLICCONDUIT/RACEWAY
BONDINGBUSHING
N
CABINETTRANS S
NO BOND
GFI
BETWEENNEUTRAL &CABINET CABINET
NEUTRAL &BETWEENNO BOND
BOND*ENCLOSURETO GFIBONDPOINT
GFI
LINE
TO BONDINGBUSHING
9. PERMANENTLY IDENTIFY LINE AND LOAD CONDUCTORS INSIDE CABINET.
(APPLIES TO 120/208V & 277/480V SERVICES)
6. METERING ENCLOSURES SHALL NOT BE ADDED. ONLY FACTORY SUPPLIED KNOCKOUTS AND PERMITTED. FIELD MADE KNOCKOUTS OR ANY OTHER FIELD ALTERATIONS WILL NOT BE ACCEPTED.
* USE MANUFACTURER'S BOND ATTACHMENT POINT
-
CURRENT
AND TEST SWITCHMETER SOCKET TRANSFORMER RATED
NEUT
RAL
BUS
NOTES:
SIDELOAD (LINE)
1-1/4" CONDUIT MIN.(SEE NOTE #6 AND #7)
WITH CONTROL CABLE
CT
ENCLOSURE
400-1200 C.T CABINETMOUNTED TO WALL
COPPER BUS
WALL
OR APPROVED STRUCTURE.(Note4)
METER SOCKET ENCLOSURE AND TO THE CT. CABINET.
1. LIPA APPROVED CURRENT TRANSFORMER CABINET AND METER SOCKET SHALL NOT BE LOCATED IN ANY AREA CLASSIFIED AS A HALLWAY, CONFINED SPACE, OR WHERE A LADDER ACCESS IS REQUIRED. (Ref Sect-8.2.3)2. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS. METER ENCLOSURES OR CURRENT TRANSFORMER CABINETS SHALL NOT BE LOCATED IN THESE
3. REFER TO NEC ARTICLE 250 FOR GROUNDING AND BONDING REQUIREMENT.
4. CENTERLINE OF C.T CABINET SHALL BE A MAXIMUM OF 5'-0" OR A MINIMUM OF 3'-6"
5. CONTROL CABLE SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR, SEE SECT. 8.9. FINAL TERMINATION IN THE METER AND TRANSFORMER CABINET SHALL BE DONE BY LIPA
6. MAXIMUM DISTANCE OF METER SOCKET FROM C.T CABINET SHALL BE DETERMINED BY LIPA
7. WHEN PVC CONDUIT IS USED A # 8 AWG 600 VOLT FACTORY INSULATED COPPER BOND WIRE SHALL BE INSTALLED BETWEEN THE METER SOCKET ENCLOSURE AND THE C.T CABINET THE BOND WIRE SHALL BE GREEN OR MARKED AS SUCH AND SHALL BE BONDED TO THE
TYPES OF AREAS.
FROM FINISHED FLOOR.
TRANSFORMER RATED METER SOCKETANDCURRENT TRANSFORMER CABINET INSTALLATION
CT CT
LINE (LOAD)SIDE
TRANSFORMER (TYP)
DWG. BASED ONLIPA CS 8606
2012 Edition Redbook
D30
6'-0
" MA
XIMU
M4'
-0"
MINI
MUM
FINISHED GRADE
EXIT THROUGH MFG.KNOCKOUT ONLY
LIPA APPROVED
LIPA APPROVED CT/TRANS CABINET
LIPA APPROVED
8. REFER TO DRAWINGS D26, D27, D28, AND D29 FOR OTHER REQUIREMENTS. 9. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY
MARKED.
-
11. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY
MOUNTING OF CURRENT TRANSFORMERS. BOLTS SHALL BE PERMANENTLY AFFIXED10. GALVANIZED BOLTS, BELLEVILLE WASHERS AND NUTS SHALL BE PROVIDED FOR
9. BUS BAR SUPPORT SHALL BE CONSTRUCTED FROM INSULATING MATERIALS CONFORMING
SHALL BE LOCATED WITHIN AN ENCLOSURE EQUIPPED WITH TAMPER PROOF SCREWS.8. ALL BUS BARS LOCATED ON THE LINE SIDE OF THE CURRENT TRANSFORMER COMPARTMENT
PROVISIONS FOR HOLDING THE DOORS IN THE OPEN POSITION.7. DOOR SWING SHALL BE GREATER THAN 90 DEGREES AND SHALL BE EQUIPPED WITH
WHICH SHALL BE EQUIPPED WITH A THREE POINT LATCHING MECHANISM AND HAVE 6. THE FRONT OF THE CUBICLE SHALL BE FURNISHED WITH A DOUBLE SWING DOOR
5. THE NEUTRAL BUS SHALL BE DRILLED WITH A 1/4 - 20 TAP FOR CURRENT
3. BUS BARS WITHIN THE CURRENT TRANSFORMER CUBICLE SHALL BE COPPER AND SHALL
FROM THE REMAINDER OF THE SWITCHGEAR CUBICLE BY MEANS OF INSULATING BARRIERS2. THE CURRENT TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED
SWITCHGEAR CUBICLE WHICH SHALL BE CONSTRUCTED IN CONFORMANCE WITH UL 891.1. THE LIPA APPROVED CURRENT TRANSFORMER COMPARTMENT SHALL BE LOCATED WITHIN THE INCOMING NOTES:
TO THE COPPER LANDING PADS.
PROVISIONS FOR LIPA PADLOCKING.
TRANSFORMER CONNECTION.
AS A MINIMUM BE TIN PLATED AT TERMINATION POINTS.
AS PER UL 891.
TO UL 746.
MARKED.
LC LC
7"MIN7"MINLC
7.5" MIN
SEE DETAIL A
25.0" MIN.
DETAIL A
6.875"
1.375"
.625"
HOLES(TYP.)9/16" DIA.
36.0" MIN.
15.0" MIN.
INSULATINGBARRIER
400 TO 1200 AMPERE SERVICECURRENT TRANSFORMER COMPARTMENT INSTALLATION
4. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED AS PER NEC FOR 1000 AMPERES PER SQUARE INCH.
DWG. BASED ONLIPA CS 8801
WHITE OR GRAY
BLACK
120/208 277/480
PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE ON EACH END.
PHASE CNEUTRAL
PHASE BPHASE A
ORANGEBLACKBLUEDELTA
RED
BLUEWYE
YELLOW
BROWNORANGE
WYE120/240
Section 11 - Drawings
D31
7"MIN7"MIN 7"MINLC
-
REPLACEMENT OF THE INSTRUMENT TRANSFORMERS.2. THE BUS BAR INSTALLATION SHALL BE SO DESIGNED AS TO PERMIT A PRACTICAL AND EASY
8. THERE SHALL BE A MINIMUM OF FOUR FEET FROM FLOOR TO CEILING OF CLEAR WORKING SPACE MINIMUM, THE OVERALL WIDTH AND HEIGHT OF THE TRANSFORMER COMPARTMENT. SHALL BE ACCESSIBLE THROUGH A LOCKABLE DOUBLE HINGED DOOR WHICH SHALL SPAN, AS A ENCLOSURE WITH AN INSULATING MATERIAL CONFORMING TO UL 746 AND UL 94. THE TRANSFORMERS 7. THE TRANSFORMER COMPARTMENT SHALL BE COMPLETELY ISOLATED FROM THE REST OF THE
6. THE TRANSFORMER SHELF AND SUPPORTING BRACKETS SHALL BE CONSTRUCTED FROM NON-FERROUS
5. ALL PHASE BUS AND THE NEUTRAL BUS SHALL BE DRILLED AND TAPPED FOR 1/4" - 20 SCREWS LOCATED ON THE LINE SIDE WHEREBY THE SECONDARY CONNECTIONS WILL BE READILY ACCESSIBLE.4. THE TRANSFORMERS SHALL BE INSTALLED SO THAT THE PRIMARY POLARITY MARKS (H1) IS REQUIRED. THE MINIMUM DISTANCES BETWEEN CENTERLINES OF TRANSFORMERS SHALL BE 10 INCHES.3. MOUNTING OF THE TRANSFORMERS MAY BE STAGGERED VERTICALLY WHERE CLOSER CENTERS ARE
CONDUCTOR SHALL BE COPPER BUS AND SHALL BE TIN PLATED AT TERMINATION POINTS AS A MINIMUM. BUS 1. CURRENT TRANSFORMER COMPARTMENT SHALL BE LIPA APPROVED, AND SHALL BE INSTALLED AS SHOWN.
IN FRONT OF THE TRANSFORMER CABINET.
ON THE LINE SIDE OF THE TRANSFORMERS.
NOTES:
MIN.7"
ELEVATION
MIN.13"
MIN13"
MIN.7"
5.375"
SECTION A-A
11" MIN 7" MIN
8.5"
8.5"
9. WHEN NEUTRAL BUS IS RECESSED, PROVISIONS SHALL BE MADE TO EXTEND THE NEUTRAL CONNECTION TO THE FRONT OF THE CUBICLE TO ACCOMODATE THE CONNECTION OF THE INSTRUMENT TRANSFORMERS.
NON-CONDUCTING, TYPE MATERIAL. MATERIAL SHALL CONFORM TO UL 746 AND UL 94.
A
A
MUST BE CENTERED IN THE WINDOW OF THE TRANSFORMER.
10. BUS BARS SHALL HAVE A MINIMUM THICKNESS OF 0.25 INCHES AND SHALL BE RATED PER THE NEC FOR 1000 AMPERES PER SQUARE INCH. MAXIMUM BUS WIDTH SHALL BE 5 INCHES.11. THE INSTRUMENT TRANSFORMER COMPARTMENT SHALL BE FURNISHED WITH A DOUBLE SWING DOOR EQUIPPED WITH A THREE POINT LATCHING MECHANISM WITH PROVISIONS FOR LIPA PADLOCKING.
CURRENT TRANSFORMER PLAN VIEW
B
B
CT SECONDARYTERMINAL
1600 AMPERE SERVICE AND ABOVECURRENT TRANSFORMER COMPARTMENT INSTALLATION
WHITE OR GRAY
BLACK
120/208 277/480
PHASE CONDUCTOR IDENTIFICATIONMIN. 2" COLORED TAPE ON EACH END.
PHASE CNEUTRAL
PHASE BPHASE A
ORANGEBLACKBLUEDELTA
RED
BLUEWYE
YELLOW
BROWNORANGE
WYE
12. LINE AND LOAD SIDES OF THE COMPARTMENT MUST BE CLEARLY AND
CT SHELF MIN.1" THK. NON-CONDUCTIVEMATERIAL
DWG. BASED ONLIPA CS 8802PERMANENTLY MARKED.
2012 Edition Redbook
D32
NEUTRALBUS
11" MIN. BUS EDGE TO ACCESS DOOR
42" MIN
7" MIN. BUSEDGETO REAR INSULATINGBARRIER
METAL ENCL.SIDEWALL
LC LC LC
-
BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER. BUSHING. BUSHINGS SHALL BE BONDED TO THEIR RESPECTIVE ENCLOSURES. 3. WHERE GALVANIZED OR ELECTRICAL METAL TUBING IS USED WITH BONDING
ELECTRICAL CODE.2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL
IS APPLICABLE WHERE TEN FEET OF CONTINUOUS METAL WATER PIPE IN SIX FEET FROM THE FIRST. THE REQUIREMENT FOR A SECOND GROUND ROD GROUND ROD IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF 1. WHERE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND
INSULATED NEUTRAL CONDUCTOR
GROUND CONDUCTOR
CUSTOMER'S MAIN DISCONNECTNEUTRAL BLOCK
ELECTRIC METER ENCLOSURE
EARTH IS NOT AVAILABLE.
NOTES:
(SEE NOTE #1)WATER PIPING SYSTEMUNDERGROUND METAL
PER NEC.
WATERMETER
FINISHEDGRADE
TYPICAL GROUNDING REQUIREMENTSSINGLE METER / MAIN INSTALLATION
1/2" X 8' CU WELD OR5/8" X 8' CU PLATED GROUND ROD
DWG. BASED ONLIPA CS 8603
Section 11 - Drawings
D33
-
WATERMETER
GROU
ND B
US
1/2" X 8' COPPER WELD OR
WIRE SIZED IN ACCORDANCE W/ THE NEC REQUIREMENTS
WIRE SIZED FOR SERVICE ENTRANCE CONDUCTOR SIZE IN ACCORDANCE W/
WITHIN 5' OF BUILDINGENTRANCE AND 10' OFCONTACT WITH EARTH
TROUGH
MAINORPANEL
TYPICAL GROUNDING DETAILSMULTI METER / MULTI MAIN INSTALLATION
PANEL
MAINOR
GROU
ND B
US
PANEL
MAINOR
GROU
ND B
US
METERSOCKET SOCKET
METERSOCKET
METER
THE NEC REQUIREMENTS
1. WHERE THE WATER PIPING SYSTEM IS CONSTRUCTED FROM PLASTIC, A SECOND GROUND ROD IS REQUIRED TO BE INSTALLED AT A MINIMUM DISTANCE OF SIX FEET FROM THE FIRST. THE REQUIREMENT FOR A SECOND GROUND ROD IS APPLICABLE WHERE TEN FEET OF CONTINUOUS METAL WATER PIPE IN EARTH IS NOT AVAILABLE.
2. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE.
3. WHERE GALV. OR ELECTRICAL METAL TUBING IS USED WITH BONDING BUSHING. BUSHINGS SHALL BE BONDED TO THEIR RESPECTIVE ENCLOSURES. BOND WIRE SHALL BE A MINIMUM OF #8 AWG GREEN INSULATED COPPER.
NOTES:
UNDERGROUND METAL WATERPIPING SYSTEM PER NEC(SEE NOTE 1) 5/8" X 8' COPPER PLATED
2012 Edition Redbook
D34
Apt.1
Apt.1
Apt.2
Apt.2
Apt.3
Apt.3
GROUND ROD
-
OPTIONAL STANDBY SYSTEMS
THE FOLLOWING 2 ONE-LINE SCHEMATICS OUTLINE THE CONNECTIONSLIPA WILL ALLOW FOR THE INTERCONNECTION OF OPTIONAL STANDBYSYSTEM EQUIPMENT. THE INTENT OF THE INTERCONNECTION SCHEMES IS TO PREVENT BOTH BACKFEED INTO THE LIPAELECTRIC DISTRIBUTION SYSTEM, AND UNINTENTIONAL PARALLELOPERATION WITH AN ENERGIZED LIPA SYSTEM. IMPROPERPARALLEL OPERATION CAN RESULT IN SERIOUS DAMAGE TO THEGENERATOR, THE LIPA DISTRIBUTION SYSTEM, OR BOTH, AND BEA SAFETY HAZARD TO PERSONNEL.
TO ENTIRELOAD
GGENERATOR
GENERATORPROTECTIVECIRCUIT BREAKERMAINDISCONNECT
LIPAMETERED
FIG. 1: STANDBY GENERATOR FOR ENTIRE LOAD.
DOUBLE THROW SWITCH
DOUBLE THROW SWITCH
CIRCUIT BREAKERPROTECTIVE
GENERATOR
GENERATORG
STANDBY LOAD
LOADS NOT BACKED UPBY GENERATOR
FIG. 2: STANDBY GENERATOR FOR PARTIAL LOADS
SERVICE
METEREDSERVICE
LIPA
MAINDISCONNECT
Section 11 - Drawings
D35
NOTE: CUSTOMER'S METERINGEQUIPMENT MUST BEPLACARDED THAT A GENERATOR IS PRESENT
NOTE: CUSTOMER'S METERINGEQUIPMENT MUST BEPLACARDED THAT A GENERATOR IS PRESENT