GENERAL CABLE_ HEPRZ 12-20 1x400.xls

download GENERAL CABLE_ HEPRZ 12-20 1x400.xls

of 2

Transcript of GENERAL CABLE_ HEPRZ 12-20 1x400.xls

  • 7/27/2019 GENERAL CABLE_ HEPRZ 12-20 1x400.xls

    1/2

    Offer N

    Order N

    Page N 1

    Medium & High Voltage Cables Units Item1

    Product identification and Features

    Cable code 1310122

    Cable type HEPRZ1Standard UNE-HD 620-9E

    Standard IBERDROLA 56.43.01

    Nominal voltage kV 12/20

    N of cores x C.S.A. 1 x400 H16

    Construction and Dimensions

    Conductor material Al

    Shape Circular

    Class / Standard 2 / CEI-60228

    Nominal diameter mm 23,00

    Conductor screen material Extruded semi-conducting layer

    Nominal radial thickness mm 0,5

    Insulation material HEPR

    Nominal radial thickness / Minimum at any point mm 4,3 / --

    Diameter over insulation mm 32,6

    Insulation screen material (non metallic) Extruded semi-conducting layer

    Nominal radial thickness mm 0,5

    Insulation screen (metallic) CWS

    N of wires x Diameter N x mm 60x0,583

    C.S.A. (Cu wires) mm 16

    Outer sheath material LLDPE

    Nominal radial thickness / Minimum at any point mm 3,0 / --

    Nominal overall diameter mm 42,0

    Nominal total weight kg/km 2130

    Minimum bending radius (after installation) mm 650

    Electrical Data

    Maximum conductor DC resistance, at 20 C Ohm/km 0,0778

    Star reactance per phase, at 50 Hz Ohm/km 0,098

    Capacitance per phase F/km 0,472

    Charging current per phase, at Uo, 50 Hz A/km 1,778Maximum permanent current rating (*) A 670 (1) / 471 (2)

    Maximum conductor temperature in service / in short-circuit C 105 / 250

    Maximum adiabatic short-circuit current rating (0.1/0.5/1.0 s) kA 113 / 50,4 / 35,6

    (*) In air, at 40 C / Buried, at 25 C - 1,5 Km/W - 1 m (see more details in ANNEX) Signed by : J.A. Lemus

    N/A = Not Applicable Date : 13/09/2013

    Nominal values subject to the usual manufacturer tolerances

  • 7/27/2019 GENERAL CABLE_ HEPRZ 12-20 1x400.xls

    2/2

    (1)

    3 single-core cables in

    trefoil touching

    formation, with effective

    air renovation.

    In free air at 40C, solar radiation protected, in accordance with UNE 211435

    (2)

    3 single-core cables in

    trefoil touching

    formation, buried directin the ground.

    Buried at 25C - 1,5Km/W - 1m, in accordance with UNE 211435

    (3) 1 three-core cable, with

    effective air renovation.In free air at 40C, solar radiation protected, calculation criteria in accordance with UNE 211435

    (4) 1 three-core cable. Buried at 25C - 1,5Km/W - 1m, calculation criteria in accordance with UNE 211435

    (5)

    3 single-core cables in

    trefoil touching

    formation, with effective

    air renovation.

    In free air at 40C, solar radiation protected , calculation criteria in accordance with IEC 60287

    (6)

    3 single-core cables intrefoil touching

    formation, buried direct

    in the ground.

    Buried at 25C - 1,5Km/W - 1m, calculation criteria in accordance with IEC 60287

    Derating Factors for different installation conditions : Please contact our Technical Department

    Derating Factors for different installation conditions : Please contact our Technical Department

    MEDIUM VOLTAGE CABLES (FROM 1,8/3 kV UP TO 18/30 kV RADIAL FIELD)

    INSTALLATION CONDITIONS DESCRIPTION

    HIGH VOLTAGE CABLES (FROM 26/45 kV UP TO 127/220 kV)