ELECTRIC UTILITY ELECTRIC UTILITY ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION SEPTEMBER 2012

description

Transmission cable catalogue of General cable

Transcript of General Cable Catalogue

ELECTRIC UTILITY

ENERGY WIRE AND CABLE FOR POWER GENERATION, TRANSMISSION AND DISTRIBUTION

S E P T E M B E R 2 012

WELCOME

Join the Wire Wizard for a quick, informative tour showing the interactive features of our catalogs

On-Line Catalog FeaturesViewthecataloginfullscreenmodebyusingthefarleftexpansion logoonthemenubar.(Keyboardinputmaynotworkinfullscreen mode,whichmeansyoumustleavethefullscreenmodeinorderto utilizetheemailfunction.) ClicktheGeneralCablelogoontheleftsideofthemenubartogoto GeneralCablesWebsite. TheTableofContentsbuttoninthecenterofthemenubartakesyou toafullyinteractivepage.Clickonanyproductcategoryorlistingto takeyoutotheappropriatepage.(Allotherpagereferences throughoutthecatalogarealsofullyinteractive.) TheentirecatalogscontentscanbesearchedusingtheSearchbutton locatedintheupperrightofthemenubar. Turncatalogpagesbyclickingyourmouseonthetoporbottomcorner ofthepageorbyusingtheforwardorbackarrowsonthesideofthe pageoronthebottombar. Zoomtodetailsoneachpagebyclickingwhenthemagnifyingglass pointerisactive.Clickagaintoreturntofullview. SharethecompleteinteractivecatalogbyselectingtheSharethis Publicationiconlocatedinthelowerrightonthebottombar. PrintallorselectedpagesusingthePrinticonlocatedinthelower rightonthebottombar. Theentireinteractivecatalogorindividualpagescanbedownloaded asaPDFusingthePDFiconlocatedinthelowerrightonthebottombar. UseCroppartofpageiconlocatedinthelowerrightonthebottom bartotakeasnapshotofanypartofapageandsaveasajpg.

General Cable Website

Contact Us

Electric UtilityThis catalog contains in-depth information on the most comprehensive line of utility products available today for the electric utility marketplace. The product and technical sections have been developed with an easy-to-use spec-ona-page format. They feature the latest information on electric utility products, from applications and construction to detailed technical and specification data. Theres also a user-friendly index. From low-, medium-, highand extra-high-voltage wire and cable for power generation, distribution and transmission, both overhead and underground, General Cable offers a broad spectrum of BICC Brand cables and Silec Brand cables for electric utilities, rural electric co-ops and independent power producers.

Whats New?

SILEC BRAND HIGH- & E X T R A - H I G H -V O LTA G E C A B L E S Y S T E M SThe Silec Brand name has been synonymous with solid-dielectric extruded cable solutions for nearly fifty years. General Cable offers a fully integrated approach to providing a comprehensive range of quality Silec high- and extra-high-voltage cable systems. They are designed, engineered and manufactured to ensure maximum service life and best-in-class performance while maintaining cost effectiveness.

D E L I V E R I N G T H E R E N E WA B L E P O W E R O F W I N D E N E R GYGeneral Cable has the offering to comprise a complete cable solution for wind power applications. From optical fiber and grounding wires for SCADA systems, low-voltage DC and AC connections and mediumvoltage distribution to high-voltage overhead, underground and submarine transmission lines, General Cable has the range of products engineered to withstand the demands of entire wind power generation, transmission and distribution systems from the wind to the outlet. EmPowr Link CL, the next generation in renewable energy collection systems, is the only mediumvoltage cable that costs less now and pays more later. When it comes to ensuring system reliability to satisfy the demand for uninterrupted power, you can rely on the validated performance of EmPowr Link CL. For more information, ask your sales representative.

H A R N E S S I N G T H E R E N E WA B L E P O W E R OF THE SUNGeneral Cable has the offering to comprise a complete cable solution for solar power applications. From low-voltage DC and AC connections and medium-voltage distribution to high-voltage overhead and underground transmission lines, General Cables range of products is engineered to withstand the demands of entire solar power generation, transmission and distribution systems from the sun to the outlet.

F U L L L I N E C ATA L O G SAll information in this catalog is presented solely as a guide to product selection and is believed to be reliable. All printing errors are subject to correction in subsequent releases of this catalog. Although General Cable has taken precautions to ensure the accuracy of the product specifications at the time of publication, the specifications of all products contained herein are subject to change without notice. GENERAL CABLE, SILEC CABLE, BICC BRAND, BIFILL, CDC, EMPOWR, POWRNET, POWRPAK, POWRSERV, STRANDFILL, TRANSPOWR, TRIFILL and ULTRAPOWR are trademarks of General Cable Technologies Corporation. Empowr Fill and PowrPak cables with General Cables semi-conducting shields are protected by U.S. patents 6,274,066; 5,556,697 and other patents pending. Empowr Link cables with General Cables semiconducting shields are protected by U.S. patents 6,274,066; 6,291,772; 6,491,849 and other patents pending. 2012. General Cable Technologies Corporation. Highland Heights, KY 41076 All rights reserved. Printed in USA.

Building WireGeneral Cables building copper wire and cable products include XHHW-2 and tri-rated USE-2. Canadian constructions such as RW90, RWU90 and T90 are also readily available. Our THHN copper products come in a variety of colors and offer a low-friction jacket designed to improve installation even under the most difficult conditions. For todays solar energy projects, General Cable offers a complete line of SunGen solar photovoltaic wire in copper constructions.

Industrial CablesWhen you specify General Cable, not only are you assured of product excellence from legacy cables such as UniShield , FREP and VNTC , but you also have access to the most extensive line of high-quality innovative and commodity industrial low- and medium-voltage cables available anywhere in the industry. While most cable manufacturers try to fit your needs to their existing products, if you cannot find what you require within our thousands of cable constructions, General Cable will design and manufacture cables around your environment.

PRODUCT SELECTION LOCATORSECTION PAGES

1 Low-Voltage Power Cable 2 Medium-Voltage Power Cable 3 High- and Extra-High-Voltage Transmission Cable 4 Overhead Conductors 5 BICC Brand Stock Program

1-22 23-64 65-70 71-170 171 172-175 176-182

6 Handling Recommendations and Packaging Information 7 Code Word Classifications and Index

[email protected]

Table of ContentsSECTION PAGES

1

Low-Voltage Power Cable

1-22

PowrNet and PowrServ Description .......................................................... 1-2 PowrNet Underground Network Cable........................................................ 3-5 PowrServ XL Underground Distribution Cable Single.................................................................................... 6 Duplex................................................................................... 7 Triplex.................................................................................... 8 Quadruplex............................................................................... 9 PowrServ AR Abuse-Resistant Underground Distribution Cable Duplex.................................................................................. 10 Triplex................................................................................... 11 Quadruplex.............................................................................. 12 PowrServ CDC Combined Duct and Cable..................................................... 13 PowrServ OH Service Drop Cable Neutral-Supported DuplexServiceDropCable............................................................... 14-15 TriplexServiceDropCable............................................................... 16-18 QuadruplexServiceDropCable........................................................... 19-20 PowrServ OH Secondary Cable Neutral-Supported TriplexReverseTwistSecondaryTypeRTS..................................................... 21 TriplexParallelSecondaryTypePLAC......................................................... 22

2

Medium-Voltage Power Cable

23-64

EmPowr Description..................................................................... 23-25 EmPowr Fill LF Lead Free EAM Insulated Cable.............................................. 27-28 EmPowr Fill EPR Insulated Cable.......................................................... 29-30 ConcentricNeutralUndergroundDistributionCable15-35kV.................................... 31-35 CopperWireShieldedPowerCable5-35kV................................................. 37-38 LongitudinallyAppliedCorrugatedTape(LACT)ShieldedPowerCable15-35kV..................... 39-40 PowrPak Flat Strap Underground PILC Replacement Cable.................................... 41-44 EmPowr Link TRXLPE Insulated Cable...................................................... 45-46 ConcentricNeutralUndergroundDistributionCable15-35kV.................................... 47-51 CopperWireShieldedPowerCable5-35kV................................................. 53-54 CopperTapeShieldedPowerCable5-35kV................................................. 55-56 LongitudinallyAppliedCorrugatedTape(LACT)ShieldedPowerCable15-35kV..................... 57-58 EmPowr Link CLTM TRXLPE Insulated XLPE Jacketed Underground Distribution Cable 35 kV........ 59-62 EmPowr CDC Combined Duct & Cable........................................................ 63

3

High- and Extra-High-Voltage Transmission Cable

6570

Look for the General Cable green symbol and Go Green with our environmentally responsible [email protected]

Table of ContentsSECTION PAGES

4

Overhead Conductors

71170

TransPowr Description................................................................... 71-72 Bare Overhead AACAll-AluminumConductor.......................................................... 74-78 AAC/TWTrapezoidalAll-AluminumConductor............................................. 80-84 AAACAll-AluminumAlloyConductor..................................................... 86-88 ACSRAluminumConductorSteel-Reinforced............................................. 90-100 ACSR/AWAluminumConductorAluminum-CladSteel-Reinforced........................... 102-112 ACSR/TWTrapezoidalAluminumConductorSteel-Reinforced............................... 114-120 ACSSAluminumConductorSteel-Supported............................................ 122-130 ACSS/AWAluminumConductorAluminum-CladSteel-Supported............................ 132-140 ACSS/TWTrapezoidalAluminumConductorSteel-Supported............................... 142-148 AAC/T-2All-AluminumConductor/TwistedPair.......................................... 150-154 ACSR/T-2AluminumConductorSteel-Reinforced/TwistedPair .............................. 156-164 Weatherproof Overhead Line Wire WeatherproofOverheadLineWire ........................................................ 166-168 Copper-Clad Steel Grounding Conductor Copper-CladSteelGroundingConductor...................................................... 169 Aluminum Tie Wire AluminumTieWire........................................................................ 170

5 6

BICC Brand Stock Program Handling Recommendations and Packaging Information

171 172175

RecommendedReelHandlingProcedures................................................. 172-173 StandardPackageandShippingInformation................................................... 174 ReelessPackage......................................................................... 175

7

Code Word Classifications and Index

176182

Look for the General Cable green symbol and Go Green with our environmentally responsible [email protected]

Our Green Initiative symbol recognizes our role and responsibility in promoting sustainability. The symbol also reflects our commitment to achieving industry-leading standards and responding proactively to environmental global issues.

Look for the General Cable green symbol and Go Green with our environmentally responsible products.Select COMPANY, then select Corporate Social Responsibility

Visit www.generalcable.com

Making Contact with the World Directing Traffic without Gridlock Building Bridges in the Sky

General Cable is a leader in the development, design, manufacture, marketing and distribution of copper, aluminum and fiber optic wire and cable for the energy, industrial, specialty and communications markets. Our products inspire progress worldwide customers use our value-added products to create global infrastructure that improves the standard of living for people everywhere. Each day were building business momentum developing ideas into innovative solutions and industry-leading products, expanding geographic access and furthering our investment in highly capable associates, Lean Manufacturing, material science and technology resources.

General Cable is influencing the world with more than two-thirds of our sales generated outside North America, 13,000 associates worldwide, and 55 manufacturing facilities throughout 26 countries. As one of the largest wire and cable manufacturers, we are the One Company Connecting the World.

Energy CablesOur cables carry energy across the world through the air, underground and under the sea. Increasing demand for energy is accelerating investment in exploration, extraction, power generation, transmission and distribution whether based on coal, natural gas, oil, nuclear, wind, solar or water.

Industrial & Specialty CablesOur cables channel the power and signals that make equipment hum and engines run. From oil rigs and broadcast studios to cars and trains, and in commercial buildings, public venues, factory floors and special applications such as military, nuclear, marine and mining we serve an extensive range of markets.

Communications CablesOur cables keep information flowing facilitating a non-stop stream of words and images around the world. We meet the high-speed bandwidth needs of global communications networks, from fiber optic submarine communications cables, copper and fiber aerial and underground cables to copper and fiber optic enterprise cables and system solutions.

World HeadquartersGeneral Cable 4 Tesseneer Drive Highland Heights, KY 41076-9753 U.S.A.

Electric Utility

Low-Voltage Power Cable

PowrNet Underground Network CableGeneral Cables PowrNet cable was developed for use in congested urban networks (particularly in duct systems) where high-reliability, easy-to-install, low-smoke and -fume cables are needed. PowrNet cables are suitable for use in wet or dry locations and for direct burial or installations in ducts. PowrNets Low-Smoke, Zero-Halogen (LSZH) jacket system reduces the amount of gas and smoke emission in the event of a fire. Its track-resistant design reduces the combustible gases created when operating in harsh environments where salts, oils and chemicals promote electrical leakage along the jacket surface. In addition, the flameresistant properties of the PowrNet cables minimize flame propagation. PowrNet cables are manufactured in accordance with ANSI/NEMA WC70/ICEA S-95-658.

PowrNet Cable Options:Multiplexed Constructions of 2 to 6 Conductors Provide phase and neutral or bare ground conductors on one reel for easy installation. Compact Copper Conductors Reduce overall diameter and use less insulation material. Tinned Copper Conductors Provide additional protective coverage over the conductor. Type RHH/RHW-2 Rating to UL 44 Used in accordance with Article 310 and other applicable parts of the National Electrical Code (NEC). Type USE-2 per UL 854 Used in accordance with Article 338 and other applicable parts of the National Electrical Code (NEC). UL OIL RES I Improves performance when exposed to oil. UL ST-1 Limited Smoke Designation (Sizes 1/0 AWG and Larger) Presents limited smoke when burning. UL For CT Use (Sizes 1/0 AWG and Larger) Used in cable trays. Passed UL vertical flame test. EPR Insulation 2000 V Rating

PowrServ Underground Secondary Distribution CableGeneral Cable manufactures a complete line of insulated underground secondary cable. General Cables PowrServ underground service cables are intended to provide power from secondary power transformers that are pad-mounted. General Cables PowrServ XL underground secondary cables are insulated with leadfree XLPE and manufactured in accordance with ANSI/ICEA S-105-692 and UL 854, listed as Type USE-2 cable. PowrServ AR is also available with lead-free abuse-resistant composite XLPE/HDXLPE and manufactured in accordance with ANSI/ICEA S-81-570 and UL 854, providing protection against cuts and abrasion that may occur during installation. PowrServ service cables are available with numerous conductor design and cable assembly options to meet a customers particular requirements. The most common styles are generally available from [email protected]

1

Electric Utility

Low-Voltage Power Cable

1PowrServ Underground Cable Options:Aluminum 1350 H16 ( Hard) Conductor Copper Conductors Primarily used when more ampacity is needed and/or there are limitations to the overall cable diameter. Series 8000 Aluminum Alloy Conductor Developed to overcome mechanical connection problems associated with circuit sizes 10 to 14 AWG Sizes 250 Through 500 kcmil Available with Reduced Insulation Wall Thickness (0.080") Type RHH/RHW-2 Rating to UL 44 Used in accordance with Article 310 and other applicable parts of the National Electrical Code (NEC). Composite PE/HDPE Insulation, Rated 75C, Type UD-S Used for 75C normal service operation. Suited for applications requiring superior resistance to abrasion, scoring and crushing. Other Phase Identification Methods Identified by colored extruded stripes. CDC Combined Duct & Cable Designed for direct burial. The pre-installed system reduces the installation and repair cost. Various designs of wall thickness HDPE conduits are available. Reeless Package Supplied in coils without the wooden reel. Provides an environmentally friendly packaging option to avoid the disposal cost and save landfill space. Index Low-Voltage Power Cable PowrNet and PowrServ PowrNet Underground Network Cable PowrServ XL Underground Distribution Cable Single Duplex Triplex Quadruplex PowrServ AR Abuse-Resistant Underground Distribution Cable Duplex Triplex Quadruplex PowrServ CDC Combined Duct & Cable PowrServ OH Service Drop Cable Neutral-Supported Duplex Service Drop Cable Triplex Service Drop Cable Quadruplex Service Drop Cable PowrServ OH Secondary Cable Neutral-Supported Triplex Reverse Twist Secondary Type RTS 21 14-15 16-18 19-20 10 11 12 13 6 7 8 9 1-2 3-5 Page

PowrServ Overhead Secondary Distribution CableGeneral Cable manufactures a complete line of insulated products for overhead secondary distribution. General Cables PowrServ OH overhead service cables are intended to provide power from secondary power transformers that are pole-mounted. The overhead service cables can also be used as pole line secondary with service splices at the pole or mid-span. General Cables PowrServ OH overhead products are insulated with lead-free XLPE and manufactured in accordance with ANSI/ICEA S-76-474. General Cables PowrServ overhead service cables are available in numerous conductor design and cable assembly options to meet a customers particular requirements. The most common styles are generally available from stock.

PowrServ Overhead Cable Options:Aluminum 1350 H16 ( Hard) Conductor Copper Conductors Primarily used when more ampacity is needed and/or there are environmental corrosion concerns. High-Molecular-Weight Polyethylene (PE) Insulation Used for 75C normal service operation. High-Density Polyethylene (HDPE) Insulation Used for 75C normal service operation. Provides tough insulation. Corrosion Inhibitor Conductor corrosion-resistant inhibitor treatment. Other Phase Identification Methods Printed numbers on black colored insulation or extruded colored stripes. Reeless Package Supplied in coils without the wooden reel. Provides an environmentally friendly packaging option to avoid the disposal cost and save landfill space.

Triplex Parallel Secondary Type PLAC 22

Look for the General Cable green symbol and Go Green with our environmentally responsible products.

[email protected]

2

600 Volt Secondary Network CableInstalled Where Maximum Reliability and Performance Are CriticalGeneral Cables PowrNet cable was engineered for use in congested urban secondary network duct and buried systems in wet or dry locations where maximum reliability, ease of installation, and low-smoke cables are required.

Net

Electrical & Physical PerformanceIncreasing demand for energy consumption puts added stress on secondary networks already at capacity that can degrade the networks at a much faster rate than normal loads. Continuous improvements made to PowrNet have extended the cables maximum breakdown voltage, providing enhanced performance at maximum load.

Dielectric Breakdown Performance1200Breakdown Strength (V/mil)

1000 800 600 400 200 0 AC Step Rise* AC Rapid Rise* Impulse** 5 specimen averages

This unique cable offers the advantages of a trackresistant, low-smoke and reduced gas evolution design. These inherent performance characteristics are complemented by excellent abrasion and tear-resistant properties coupled with a low coefficient of friction, which allows for ease of pulling into existing duct systems. PowrNet network cables are manufactured to meet ANSI/NEMA WC70 ICEA S-95-658, Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy.

PowrNet Performance Features> Installation Performance Added Flexibility, Less Spring-Back, Low Coefficient of Friction, High Abuse- & Tear-Resistant > Environmental Performance Fire- and FlameResistant, Oil- and Chemical-Resistant, and Low Generation of Combustible and Caustic Gases > Electrical & Physical Performance High Dielectric Strength, High- and Low-Temperature Range, Superior Track Resistance

PowrNet s proven performance as a superior secondary network cable is further demonstrated by the following qualification tests over and above the industry-standard requirements.

PowrNet - Additional Qualification TestsInstallation Performance Coefficient of Friction - Composite Cable Tear Resistance Test - Jacket Puncture Resistance - Composite Cable Abrasion Resistance - Composite Cable Electrical and Physical Performance Rapid ac Voltage Rise - Insulation Step ac Voltage Withstand - Insulation Impulse Test - Composite Cable Roasting Test (260C Limiter) - Composite Cable Bond Fire Test - Composite Cable Cold Bend Withstand Test - Composite Cable 6 Month AWA Test - Composite Cable Surface Resistivity - Insulation and Jacket Arrhenius Elongation - Insulation and Jacket Environmental Performance Flame Testing - Composite Cable Smoke and Toxicity - Composite Cable Tracking and Erosion Resistance - Jacket 10 Cycle Oil Resistance - Jacket Lead TCLP Test - Composite Cable Test Reference GCC In-house ANSI/ICEA T-37-581 ANSI/ICEA S-81-570 ANSI/ICEA S-81-570 Test Reference EO-18 EO-18 EO-18 EO-6068 EO-6068 EO-18 EO-18 ANSI/ICEA T-37-581 GCC In-house Test Reference IEEE 1202 IEEE 1202 ASTM D2132 EO-18 ICP SW846

PowrNet , with its Low-Smoke, Zero-Halogen (LSZH) Jacket, is your Greener Choice for Modernizing the Secondary Network.As energy consumption in densely populated urban areas continues to grow, existing power and secondary networks are required to operate under ever more severe conditions. General Cable has stayed ahead of this trend by offering its highly engineered PowrNet cable to meet the challenges of the most demanding urban environments. Designed to be installed either in ducts or directly buried, PowrNet gives system engineers a proven choice to specify a highly reliable cable that is easy to install, with excellent electrical performance and track resistance, and provides the assurance of low-smoke and reduced gas emission in the event of a fire.

Installation PerformanceBecause network cables may at times be installed in challenging conditions, General Cable has designed PowrNet to withstand the unique rigors of installation with a low coefficient of friction jacket, enhanced tear strength and exceptional cable flexibility.

Environmental PerformanceAn aging urban network system required to meet modern needs with ever-increasing electrical loads challenges utility system engineers to find affordable, reliable and safe solutions. In response, PowrNet s low-smoke, zero-halogen jacket system reduces the amount of gas and smoke emission in the event of a fire. Its track-resistant design reduces the combustible gases created when operating in harsh environments where salts, oils and chemicals promote electrical leakage along the jacket surface. In addition, the flame-resistant properties of the PowrNet cables minimize flame propagation. General Cable has engineered PowrNet cables for extreme environments where unparalleled performance and safety are critical and cable failures are not an option.

Low-Voltage Power Cable

Electric Utility

PowrNet 600 V Underground Network Cable

600 V Single Cu Conductor EAM Insulation LSZH JacketProduct Construction: Complete Cable:General Cables PowerNet 600 V network cables consist of a Class B compressed copper conductor, covered with EAM insulation and a black Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset jacket. All cables are manufactured and tested in accordance with ANSI/NEMA WC70/ICEA S-95-658. Conductors: Class B compressed copper meeting the requirements of ASTM B8. Insulation/Jacket: The extruded thermoset, flame-retardant EAM insulation meets the requirements of an EPR Type II (Class E-2) insulation of ANSI/NEMA WC70/ICEA S-95-658. The extruded thermoset black jacket is a Type II Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset polyolefin and meets the requirements of ANSI/NEMA WC70/ ICEA S-95-658.

600 V SINGLE COPPER CONDUCTOR EAM INSULATION LSZH JACKETSIZE AWG OR kcmil 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 NO. OF WIRES 7 7 7 19 19 19 19 19 37 37 37 61 61 NOM. COND. O.D. 0 .178 0 .225 0 .283 0 .313 0 .352 0 .395 0 .443 0 .498 0 .558 0 .641 0 .789 0 .968 0 .117 INS./JACKET NOM. THKN. INCHES 0.045/0.030 0.045/0.030 0.045/0.030 0.055/0.045 0.055/0.045 0.055/0.045 0.055/0.045 0.055/0.045 0.065/0.065 0.065/0.065 0.065/0.065 0.080/0.065 0.080/0.065 NOM. O.D. INCHES 0 .34 0 .39 0 .44 0 .52 0 .56 0 .61 0 .65 0 .71 0 .83 0 .91 1 .06 1 .27 1 .42 APPROX. WEIGHT LB/1000 FT COPPER TOTAL 81 129 205 258 326 411 518 653 772 1081 1544 2316 3088 120 176 262 341 416 510 627 774 949 1280 1783 2632 3448 AMPACITY (1) DIRECT BURIED IN DUCT (2) 120 155 200 225 255 290 330 375 410 490 590 720 820 80 105 140 165 190 215 250 280 315 390 475 585 670

Features and Benefits:General Cables PowrNet 600 V network cable was developed for use in congested urban networks (particularly in duct systems) where high-reliability, easy-to-install low-smoke and -fume cables are needed. This unique cable design provides advantages of a track-resistant, low-smoke and reduced-gas evolution in the event of a fire. These installed performance features are complemented by excellent abrasion and tear resistance properties coupled with a low coefficient of friction which allows easy pulling into existing duct systems. PowrNet is rated 600 V and has a wet and dry conductor operating temperature rating of 90C.

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedononethree-phase circuitburiedtogetherwithnocurrentintheneutralconductor.Forspecificampacities,contactyourGeneralCable salesrepresentative. (2)Resultsmayalsobeappliedtoasingle12x12ductbankinstallationwheretheductisencasedinconcrete. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Applications :General Cables PowerNet cable was engineered for use in congested urban secondary network duct and buried systems in wet or dry locations where maximum reliability, ease of installation, and low-smoke cables are required.

Options:Multiplexedconstructionsof2to6conductors Multiplexedwithbaregroundconductors Compactcopperconductors Tinnedcopperconductors TypeRHH/RHW-2perUL44 TypeUSE-2perUL854 ULOILRESI ULST-1limitedsmokedesignation (sizes 1/0 AWG and larger) ULForCTUse(sizes1/0AWGandlarger) EPRinsulation 2000Vrating For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

5

Electric Utility

Low-Voltage Power Cable

PowrServ XL Underground Distribution Cable600 V Single Al Conductor XLPE Insulation, UL Type USE-2Product Construction: Complete Cable:600 V PowrServ XL cables consist of an aluminum conductor insulated with extruded lead-free Cross-linked Polyethylene (XLPE). These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-105-692 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Insulation: The insulation is black extruded lead-free Cross-linked Polyethylene (XLPE). Phase Identification: Phase identification is provided by means of white print legend markings and sequential footage markings on the phase conductor.

POWRSERV XL CABLEXLPE INSULATION600 VOLTSCODE WORD Princeton/XLP Mercer/XLP Clemson/XLP Kenyon/XLP Harvard/XLP Yale/XLP Tufts/XLP Beloit/XLP Hofstra/XLP Gonzaga/XLP Rutgers/XLP Dartmouth/XLP Emory/XLP Duke/XLP Furman/XLP Sewanee/XLP Fordham/XLP SIZE NO. AWG OR OF kcmil WIRES 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 1000 7 7 7 19 19 19 19 19 37 37 37 37 37 61 61 61 61 INS. THKN. INCHES 0 .060 0 .060 0 .060 0 .080 0 .080 0 .080 0 .080 0 .080 0 .095 0 .095 0 .095 0 .095 0 .095 0 .110 0 .110 0 .110 0 .110 NOM. O.D. INCHES 0 .30 0 .35 0 .40 0 .47 0 .51 0 .56 0 .60 0 .66 0 .75 0 .78 0 .85 0 .90 0 .98 1 .09 1 .16 1 .19 1 .34 APPROX. WEIGHT LB/1000 FT AL TOTAL 25 39 62 78 99 125 157 198 234 281 328 375 469 562 656 703 937 44 63 92 120 145 176 214 262 317 369 426 479 584 707 811 864 1122 AMPACITY (1) DIRECT BURIED IN DUCT 95 125 160 180 205 230 265 300 330 360 395 420 475 525 570 590 680 60 80 105 125 140 170 195 220 245 275 300 325 375 420 455 480 560 PACKAGING 1000 FT REEL (2) NR24.12 NR24.12 NR24.12 NR24.12 NR24.18 NR24.18 NR27.18 NR27.18 NR30.18 NR30.18 NR30.18 NR32.24 NR32.24 NR36.24 NR40.24 NR40.24 NR42.26

Features and Benefits:600 V PowrServ XL underground distribution cables are suitable for direct burial or installations in ducts and are resistant to abrasion, impact and sunlight. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying temperature of 90C in wet or dry locations.

Applications:PowrServ XL underground distribution cable is intended for use in underground systems operated at 600 volts or less.

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedononethree-phase circuitburiedtogetherwithnocurrentintheneutralconductor.Forspecificampacities,contactyourGeneralCable salesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forreelesspackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Options:Aluminum1350-H16conductor Copperconductors Series8000aluminumalloyconductor Sizes250through500kcmilavailablewith thin wall (0.080") insulation TypeRHH/RHW-2perUL44 CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

6

Low-Voltage Power Cable

Electric Utility

PowrServ XL Underground Distribution Cable

600 V Duplex Al Conductor XLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Duplex 600 V PowrServ XL cables consist of one phase conductor and one neutral conductor that are insulated with extruded lead-free Cross-linked Polyethylene (XLPE). The cables are twisted together to form a duplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-105-692 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Insulation: The insulation is extruded lead-free Crosslinked Polyethylene (XLPE). The phase conductor is black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of white print legend markings and sequential footage markings on the phase conductor and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV XL DUPLEX CABLEXLPE INSULATION600 VOLTSPHASE CONDUCTOR NEUTRAL CONDUCTOR AMPACITY (1) APPROX. WEIGHT EFF. PACKAGING SIZE NO. INS. SIZE NO. INS. LB/1000 FT DIRECT IN 1000 FEET AWG OR OF THKN. AWG OR OF THKN. O.D. kcmil WIRES INCHES kcmil WIRES INCHES INCHES AL TOTAL BURIED DUCT REEL (2) 6 4 2 1/0 2/0 3/0 4/0 7 7 7 19 19 19 19 0 .060 0 .060 0 .060 0 .080 0 .080 0 .080 0 .080 6 4 2 1/0 2/0 3/0 4/0 7 7 7 19 19 19 19 0 .060 0 .60 0 .060 0 .69 0 .060 0 .81 0 .080 1 .02 0 .080 1 .11 0 .080 1 .21 0 .080 1 .32 49 89 110 145 185 235 270 305 350 70 NR24.18 90 NR24.18 120 NR27.18 160 NR32.24 185 NR32.24 210 NR36.24 245 NR40.24

CODE WORDClaflin/XLP/EYS Delgado/XLP/EYS Everett/XLP/EYS -noneFindlay/XLP/EYS -noneHanover/XLP/EYS

78 127 125 185 199 291 250 353 315 430 398 526

Features and Benefits:600 V PowrServ XL underground distribution cables are suitable for direct burial or installations in ducts and are resistant to abrasion, impact and sunlight. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedoncurrentinboththe phaseandneutralconductors.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Applications:PowrServ XL underground distribution cable is intended for use in underground systems operated at 600 volts or less.

Options:Aluminum1350-H16conductor Copperconductors Series8000aluminumalloyconductor Sizes250through500kcmilavailablewith thinwall(0.080)insulation TypeRHH/RHW-2perUL44 Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

7

Electric Utility

Low-Voltage Power Cable

PowrServ XL Underground Distribution Cable600 V Triplex Al Conductor XLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Triplex 600 V PowrServ XL cables consist of two phase conductors and one neutral conductor, all of which are insulated with extruded lead-free Cross-linked Polyethylene (XLPE). The cables are twisted together to form a triplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-105-692 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Insulation: The insulation is extruded lead-free Crosslinked Polyethylene (XLPE). The two phase conductors are black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of white print legend markings and sequential footage markings on one phase conductor, white print legend markings on the other phase conductor, and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV XL TRIPLEX CABLEXLPE INSULATION600 VOLTSPHASE CONDUCTORS NEUTRAL CONDUCTOR EFF. SIZE NO. INS. SIZE NO. INS. AWG OR OF THKN. AWG OR OF THKN. O.D. kcmil WIRES INCHES kcmil WIRES INCHES INCHES 6 4 2 2 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 350 500 7 7 7 7 19 19 19 19 19 19 19 19 37 37 37 0 .060 0 .060 0 .060 0 .060 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .095 0 .095 0 .095 6 4 4 2 2 1/0 1 2/0 1/0 3/0 2/0 4/0 3/0 4/0 350 7 7 7 7 7 19 19 19 19 19 19 19 19 19 37 0 .060 0 .64 0 .060 0 .74 0 .060 0 .84 0 .060 0 .87 0 .060 1 .04 0 .080 1 .10 0 .080 1 .15 0 .080 1 .20 0 .080 1 .25 0 .080 1 .30 0 .080 1 .36 0 .080 1 .42 0 .080 1 .53 0 .080 1 .69 APPROX. WEIGHT LB/1000 FT AL 74 118 164 187 261 298 329 375 415 473 523 597 628 AMPACITY (1) PACKAGING DIRECT IN 1000 FEET TOTAL BURIED DUCT REEL (2) 133 110 190 145 248 185 277 185 384 235 437 235 474 270 530 270 576 305 645 305 702 350 789 350 852 380 70 NR27.18 90 NR30.18 120 NR32.24 120 NR32.24 160 NR36.24 160 NR40.24 185 NR40.24 185 NR40.24 210 NR40.24 210 NR42.26 245 NR42.26 245 NR45.28 270 NR45.28 325 NR50.32 410 NR58.32

CODE WORDErskine/XLP/EYS Vassar/XLP/EYS Stephens/XLP/EYS Ramapo/XLP/EYS Brenau/XLP/EYS Bergen/XLP/EYS Converse/XLP/EYS Hunter/XLP/EYS Hollins/XLP/EYS Rockland/XLP/EYS Sweetbriar/XLP/EYS Monmouth/XLP/EYS Pratt/XLP/EYS Wesleyan/XLP/EYS Rider/XLP/EYS

Features and Benefits:600 V PowrServ XL underground distribution cables are suitable for direct burial or installations in ducts and are resistant to abrasion, impact and sunlight. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

858 1111 455

0 .095 2 .03 1269 1596 555

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedonnocurrentinthe neutralconductor.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Applications:PowrServ XL underground distribution cable is intended for use in underground systems operated at 600 volts or less.

Options:Aluminum1350-H16conductor Copperconductors Series8000aluminumalloyconductor Sizes250through500kcmilavailablewith thin wall (0.080") insulation TypeRHH/RHW-2perUL44 Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

8

Low-Voltage Power Cable

Electric Utility

PowrServ XL Underground Distribution Cable

600 V Quadruplex Al Conductor XLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Quadruplex 600 V PowrServ XL cables consist of three phase conductors and one neutral conductor, all of which are insulated with extruded lead-free Cross-linked Polyethylene (XLPE). The cables are twisted together to form a quadruplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-105-692 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Insulation: The insulation is extruded lead-free Cross-linked Polyethylene (XLPE). The three phase conductors are black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of whiteprintlegendmarkings,PhaseAmarking, and sequential footage markings on one phase conductor, white print legend markings and PhaseBmarkingonanotherphaseconductor, whiteprintlegendmarkingsandPhaseC marking on another phase conductor, and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV XL QUADRUPLEX CABLEXLPE INSULATION600 VOLTSPHASE CONDUCTORS NEUTRAL CONDUCTOR AMPACITY (1) APPROX. WEIGHT EFF. LB/1000 FT PACKAGING SIZE NO. INS. SIZE NO. INS. DIRECT IN 1000 FEET AWG OR OF THKN. AWG OR OF THKN. O.D. kcmil WIRES INCHES kcmil WIRES INCHES INCHES AL TOTAL BURIED DUCT REEL (2) 4 2 2 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 350 500 7 7 7 19 19 19 19 19 19 19 19 37 37 37 0 .060 0 .060 0 .060 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .080 0 .095 0 .095 0 .095 4 4 2 2 1/0 1 2/0 1/0 3/0 2/0 4/0 3/0 4/0 350 7 7 7 7 19 19 19 19 19 19 19 19 19 37 0 .060 0 .83 0 .060 0 .94 0 .060 0 .97 0 .060 1 .17 0 .080 1 .24 0 .080 1 .29 0 .080 1 .34 0 .080 1 .40 0 .080 1 .46 0 .080 1 .53 0 .080 1 .59 0 .080 1 .72 157 253 125 226 340 160 250 369 160 360 529 205 397 583 205 454 651 230 501 707 230 573 791 265 631 860 265 722 965 300 796 1052 300 863 1170 330 80 NR32.24 105 NR32.34 105 NR36.24 140 NR42.26 140 NR42.26 170 NR42.26 170 NR45.28 195 NR45.28 195 NR45.28 220 NR50.32 220 NR50.32 245 NR50.32 300 NR58.32 375 NR66.36

CODE WORDTulsa/XLP/EYS Dyke/XLP/EYS Wittenberg/XLP/EYS NotreDame/XLP/EYS Purdue/XLP/EYS Syracuse/XLP/EYS Lafayette/XLP/EYS Swarthmore/XLP/EYS Davidson/XLP/EYS WakeForest/XLP/EYS Earlham/XLP/EYS Rust/XLP/EYS SlipperyRock/XLP/EYS Wofferd/XLP/EYS

Features and Benefits:600 V PowrServ XL underground distribution cables are suitable for direct burial or installations in ducts and are resistant to abrasion, impact and sunlight. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

0 .080 1 .91 1187 1535 395 0 .095 2 .28 1739 2182 475

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedonnocurrentinthe neutralconductor.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Applications:PowrServ XL underground distribution cable is intended for use in underground systems operated at 600 volts or less.

Options:Aluminum1350-H16conductor Copperconductors Series8000aluminumalloyconductor Sizes250through500kcmilavailablewith thin wall (0.080") insulation TypeRHH/RHW-2perUL44 Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

9

Electric Utility

Low-Voltage Power Cable

PowrServ AR Underground Distribution Cable

600 V Duplex Al Conductor Composite XLPE/HDXLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Duplex PowrServ abuse-resistant (AR) underground distribution cables consist of one phase and one neutral conductor, both of which are insulated with extruded lead-free composite Cross-linked Polyethylene (XLPE) and High-Density Cross-linked Polyethylene (HDXLPE). The cables are twisted together to form a duplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-81-570 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Composite Insulation: The extruded lead-free cross-linked polyethylene insulation meets the requirements of ANSI/ICEA S-81-570. The extruded lead-free high-density cross-linked polyethylene meets the requirements of ASTM D1248, Type III. The phase conductor is black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of white print legend markings and sequential footage markings on the phase conductor and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV AR DUPLEX CABLEXLPE/HDXLPE600 VOLTSPHASE CONDUCTOR NEUTRAL CONDUCTOR SIZE NO. XL XLHD SIZE NO. XL XLHD EFF. AWG OR OF THKN. THKN. AWG OR OF THKN. THKN. O.D. IN kcmil WIRES IN IN kcmil WIRES IN IN 4 2 1/0 2/0 3/0 4/0 7 0 .030 0 .030 7 0 .030 0 .030 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 4 2 1/0 2/0 3/0 4/0 7 7 19 19 19 19 0 .030 0 .030 0 .69 0 .030 0 .030 0 .81 0 .040 0 .040 1 .02 0 .040 0 .040 1 .11 0 .040 0 .040 1 .21 0 .040 0 .040 1 .32 APPROX. WEIGHT LB/1000 FT AL AMPACITY (1) PKG. DIRECT IN 1000 FEET TOTAL BURIED DUCT REEL (2) 145 185 265 270 305 350 90 NR24.18 120 NR27.18 160 NR32.24 185 NR32.24 210 NR36.24 245 NR40.24

CODE WORDDelgado/AR/EYS Everett/AR/EYS -noneFindlay/AR/EYS -noneHanover/AR/EYS

78 127 125 185 199 293 250 355 315 432 398 528

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedoncurrentinboththe phaseandneutralconductors.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Features and Benefits:The dual extruded composite insulation system provides a very high degree of protection against insulation damage from unclean backfill material and from cuts and abrasions that can occur during installation. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

Applications:PowrServ AR XLPE/HDXLPE underground distribution cable is intended for use in underground systems operated at 600 volts or less.

Options:Aluminum1350-H16conductor Copperconductors CompositePE/HDPEinsulation,rated75C, Type UD-S Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

10

Low-Voltage Power Cable

Electric Utility

PowrServ AR Underground Distribution Cable

600 V Triplex Al Conductor Composite XLPE/HDXLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Triplex PowrServ abuse-resistant (AR) cables consist of two phase conductors and one neutral conductor, all of which are insulated with extruded lead-free composite Cross-linked Polyethylene (XLPE) and High-Density Crosslinked Polyethylene (HDXLPE). The cables are twisted together to form a triplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-81570 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Composite Insulation: The extruded lead-free cross-linked polyethylene insulation meets the requirements of ANSI/ICEA S-81-570. The extruded lead-free highdensity cross-linked polyethylene meets the requirements of ASTM D1248, Type III. The two phase conductors are black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of white print legend markings and sequential footage markings on one phase conductor, white print legend markings on the other phase conductor, and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV AR TRIPLEX CABLEXLPE/HDXLPE600 VOLTSPHASE CONDUCTORS NEUTRAL CONDUCTOR SIZE NO. XL XLHD SIZE NO. XL XLHD EFF. AWG OR OF THKN. THKN. AWG OR OF THKN. THKN. O.D. IN kcmil WIRES IN IN kcmil WIRES IN IN 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 300 300 350 350 500 7 0 .030 0 .030 7 0 .030 0 .030 7 0 .030 0 .030 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 37 0 .045 0 .050 37 0 .045 0 .050 37 0 .045 0 .050 4 4 2 2 1 2 1/0 1 2/0 1/0 3/0 2/0 4/0 3/0 4/0 4/0 7 0 .030 0 .030 0 .74 7 0 .030 0 .030 0 .84 7 0 .030 0 .030 0 .87 7 0 .030 0 .030 1 .00 19 0 .040 0 .040 1 .04 7 0 .030 0 .030 1 .04 19 0 .040 0 .040 1 .10 19 0 .040 0 .040 1 .15 19 0 .040 0 .040 1 .20 19 0 .040 0 .040 1 .25 19 0 .040 0 .040 1 .30 19 0 .040 0 .040 1 .36 19 0 .040 0 .040 1 .42 19 0 .040 0 .040 1 .53 37 0 .045 0 .050 1 .61 19 0 .040 0 .040 1 .65 37 0 .045 0 .050 1 .73 19 0 .040 0 .040 1 .69 37 0 .045 0 .050 1 .79 APPROX. WEIGHT LB/1000 FT AL 118 164 187 220 236 261 298 329 375 415 473 523 597 628 705 PKG. 1000 FEET DIRECT IN REEL TOTAL BURIED DUCT (2) 191 249 278 337 367 386 439 476 532 578 648 705 792 855 959 145 185 185 210 210 265 265 270 270 305 305 350 350 380 380 420 420 455 455 555 90 NR30.18 120 NR32.24 120 NR32.24 140 NR32.24 140 NR36.24 160 NR36.24 160 NR40.24 185 NR40.24 185 NR40.24 210 NR40.24 210 NR42.26 245 NR42.26 245 NR45.28 270 NR45.28 270 NR50.32 300 NR50.32 300 NR50.32 325 NR50.32 325 NR58.32 410 NR58.32 AMPACITY (1)

CODE WORD Vassar/AR/EYS Stephens/AR/EYS Ramapo/AR/EYS -noneGrossmont/AR/EYS Brenau/AR/EYS Bergen/AR/EYS Converse/AR/EYS Hunter/AR/EYS Hollins/AR/EYS Rockland/AR/EYS Sweetbriar/AR/EYS Monmouth/AR/EYS Pratt/AR/EYS Yeshiva/AR/EYS -none-noneWesleyan/AR/EYS Newark/AR/EYS Rider/AR/EYS

Features and Benefits:The dual extruded composite insulation system provides a very high degree of protection against insulation damage from unclean backfill material and from cuts and abrasions that can occur during installation. For NECcomplying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for noncode-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

37 0 .045 0 .050 250 37 0 .045 0 .050 300 37 0 .045 0 .050 350 37 0 .045 0 .050 350

763 1012 846 1123 858 1115 988 1277

37 0 .045 0 .050 2 .03 1269 1601

Applications:PowrServ AR XLPE/HDXLPE underground distribution cable is intended for use in underground systems operated at 600 volts or less.

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedonnocurrentinthe neutralconductor.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Options:Aluminum1350-H16conductor Copperconductors Sizes250through500kcmilavailablewith thin wall (0.080") insulation CompositePE/HDPEinsulation,rated75C, Type UD-S Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

11

Electric Utility

Low-Voltage Power Cable

PowrServ AR Underground Distribution Cable

600 V Quadruplex Al Conductor Composite XLPE/HDXLPE Insulation, UL Type USE-2Product Construction: Complete Cable:Quadruplex PowrServ abuse-resistant (AR) cables consist of three phase conductors and one neutral conductor, all of which are insulated with extruded lead-free composite Cross-linked Polyethylene (XLPE) and High-Density Cross-linked Polyethylene (HDXLPE). The cables are twisted together to form a quadruplex assembly. These XLPE insulated cables are manufactured and tested in accordance with ANSI/ICEA S-81-570 and UL 854, listed as a Type USE-2 cable. Conductors: Class B compressed aluminum 1350-H19 meeting the requirements of ASTM B231. Composite Insulation: The extruded lead-free cross-linked polyethylene insulation meets the requirements of ANSI/ICEA S-81-570. The extruded lead-free high-density cross-linked polyethylene meets the requirements of ASTM D1248, Type III. The three phase conductors are black, and the neutral conductor is black, identified by three extruded yellow stripes. Phase Identification: Phase identification is provided by means of white printlegendmarkings,PhaseAmarking,and sequential footage markings on one phase conductor, whiteprintlegendmarkingsandPhaseBmarking on another phase conductor, white print legend markingsandPhaseCmarkingonanotherphase conductor, and white print legend markings and three extruded yellow stripes on the neutral conductor.

POWRSERV AR QUADRUPLEX CABLEXLPE/HDXLPE600 VOLTSPHASE CONDUCTORS NEUTRAL CONDUCTOR SIZE NO. XL XLHD SIZE NO. XL XLHD EFF. AWG OR OF THKN. THKN. AWG OR OF THKN. THKN. O.D. IN kcmil WIRES IN IN kcmil WIRES IN IN 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 300 300 350 500 7 0 .030 0 .030 7 0 .030 0 .030 7 0 .030 0 .030 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 19 0 .040 0 .040 4 4 2 2 1 2 1 7 7 7 7 19 7 19 19 19 19 19 19 19 19 37 19 37 19 37 37 0 .030 0 .030 0 .83 0 .030 0 .030 0 .94 0 .030 0 .030 0 .97 0 .030 0 .030 1 .12 0 .040 0 .040 1 .16 0 .030 0 .030 1 .17 0 .040 0 .040 1 .24 0 .040 0 .040 1 .29 0 .040 0 .040 1 .34 0 .040 0 .040 1 .40 0 .040 0 .040 1 .46 0 .040 0 .040 1 .53 0 .040 0 .040 1 .59 0 .040 0 .040 1 .72 0 .045 0 .050 1 .81 APPROX. WEIGHT LB/1000 FT AL 157 226 250 298 315 360 397 454 501 573 631 722 PKG. 1000 FEET DIRECT IN REEL TOTAL BURIED DUCT (2) 255 125 342 160 371 160 460 180 489 180 532 205 586 205 654 230 710 230 794 265 864 265 969 300 80 NR32.24 105 NR32.24 105 NR36.24 125 NR40.24 125 NR40.24 140 NR42.26 140 NR42.26 170 NR42.26 170 NR45.28 195 NR45.28 195 NR45.28 220 NR50.32 220 NR50.32 245 NR50.32 245 NR58.32 275 NR58.32 275 NR58.32 295 NR58.32 255 NR58.32 375 NR66.36 AMPACITY (1)

CODE WORD Tulsa/AR/EYS Dyke/AR/EYS Wittenberg/AR/EYS -none-noneNotreDame/AR/EYS Purdue/AR/EYS Syracuse/AR/EYS Lafayette/AR/EYS Swarthmore/AR/EYS Davidson/AR/EYS WakeForest/AR/EYS Earlham/AR/EYS Rust/AR/EYS Palomar/AR/EYS -none-noneNiagara/AR/EYS Wofferd/AR/EYS

19 0 .040 0 .040 1/0 19 0 .040 0 .040 2/0 19 0 .040 0 .040 1/0 19 0 .040 0 .040 3/0 19 0 .040 0 .040 2/0 19 0 .040 0 .040 4/0 37 0 .045 0 .050 3/0 37 0 .045 0 .050 250 37 0 .045 0 .050 4/0 37 0 .045 0 .050 300 37 0 .045 0 .050 4/0 37 0 .045 0 .050 350 37 0 .045 0 .050 350

796 1056 300 863 1175 330 940 1277 330

Features and Benefits:The dual extruded composite insulation system provides a very high degree of protection against insulation damage from unclean backfill material and from cuts and abrasions that can occur during installation. For NEC-complying applications, the maximum conductor operating temperature is 90C in wet or dry locations. This cable is also suitable for non-code-complying installations with a maximum conductor temperature of 90C in wet or dry locations.

0 .040 0 .040 1 .85 1045 1386 360 0 .045 0 .050 1 .93 1128 1494 360 0 .040 0 .040 1 .91 1187 1541 395 0 .045 0 .050 2 .09 1320 1768 390 0 .045 0 .050 2 .28 1739 2189 475

SlipperyRock/AR/EYS 350

(1) Ampacitiesarefornon-code-complyinginstallations.ForinstallationscoveredbyNationalElectricalCode(NEC),see theappropriatesectionoftheNEC.Ampacitybasedonearththermalresistivityof90C-cm/watt,90Cconductor temp.,20Cearthambienttemperature,100%loadfactorand36depthofburial.Valuesbasedonnocurrentinthe neutralconductor.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionand typicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Applications:PowrServ AR XLPE/HDXLPE underground distribution cable is intended for use in underground systems operated at 600 volts or less.

Options:Aluminum1350-H16conductor Copperconductors Sizes250through500kcmilavailablewith thin wall (0.080") insulation CompositePE/HDPEinsulation,rated75C, Type UD-S Otherphaseidentificationmethods CDC Combined Duct & Cable Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

12

Low-Voltage Power Cable

Electric Utility

PowrServ CDC Underground DistributionSecondary Combined Duct & CableSecondary Cable Installed in Extruded High-Density Polyethylene DuctProduct Construction: Complete Assembly:PowrServ CDC Combined Duct & Cable consists of insulated conductor(s) factory installed in a black high-density polyethylene conduit. The polyethylene conduit is extruded directly over any prior-made single or plexed 600 volt cable assembly. Complete Cable: All underground distribution cables in PowrServ CDC are manufactured and tested in accordance with applicable industry standards and/or individual customer specifications. See the appropriate catalog section for a complete cable description. Conduit: The high-density polyethylene EPEC-A conduit is manufactured and tested in accordance with NEMAStandardTC7,Smooth-wallCoilable ElectricalPolyethyleneConduit. NOMINAL CONDUIT SIZE (INCHES) 11/4 11/2 2

POWERSERV CDCO.D. ( 0.012") (INCHES) 1 .660 1 .900 2 .375 MINIMUM INSIDE AREA (SQ. INCHES) 1 .557 2 .056 3 .246 APPROX. WEIGHT (LB/1000 FT) 240 310 475 MINIMUM* WALL MINIMUM THICKNESS BEND RADIUS (INCHES) (INCHES) 0 .100 0 .115 0 .145 18 21 26

MINIMUM I.D. (INCHES) 1 .408 1 .618 2 .033

*Themaximumwallthicknessistheminimumgivenabove+0.020inches.

Applications:PowrServ CDC Combined Duct & Cable offers an economical alternative to pulling cable in previously installed short lengths of duct joined with sleeve couplings. The inherent construction advantages and versatility of the PowrServ CDC design are ideally suited for underground secondary distribution systems.

MAXIMUM CROSS-SECTIONAL AREA OF CONDUCTORS PER CONDUIT NOMINAL CONDUIT SIZE (INCHES) 11/4 11/2 2 MINIMUM INSIDE AREA (SQ. INCHES) 1 .557 2 .056 3 .246MAXIMUM TOTAL CROSS-SECTIONAL AREA OF CONDUCTORS (SQUARE INCHES)

53% FILL ONE CONDUCTOR 0 .825 1 .090 1 .720

31% FILL TWO CONDUCTORS 0 .483 0 .637 1 .006

40% FILL THREE CONDUCTORS 0 .623 0 .822 1 .298

40% FILL FOUR CONDUCTORS 0 .623 0 .822 1 .298

Features and Benefits:In addition to the initial labor savings achieved from installation of cable and conduit in a single operation, cable replacement costs and ground disruption are significantly less for the PowrServ CDC cable system. Tough, yet light and flexible, high-density polyethylene conduit provides ease of installation and high impact resistance for cable protection.

Note:Themaximumpercentfillusedaboveisbasedon1999NationalElectricaCoderecommendations.Largerfillareascanbefurnishedwhen requiredbytheuser.

MAXIMUM DIAMETER OF CONDUCTORS PER CONDUIT NOMINAL CONDUIT SIZE (INCHES) 11/4 11/2 2MAXIMUM DIAMETER OF EACH CONDUCTOR (INCHES)

MINIMUM I.D. (INCHES) 1 .408 1 .618 2 .033

ONE CONDUCTOR 1 .025 1 .178 1 .480

TWO CONDUCTORS 0 .555 0 .637 0 .800

THREE CONDUCTORS 0 .514 0 .591 0 .742

FOUR CONDUCTORS 0 .445 0 .512 0 .643

Options:EPEC-B,EPEC-40orEPEC-80Smooth-Wall Coilable Electrical Polyethylene Conduit to NEMA TC7 Grayorredcolor Extrudedredstripes For more information, contact your General Cable sales representative or e-mail [email protected]

ThemaximumdiameterofeachconductoraboveisbasedonNationalElectricalCoderecommendations.Largerconductordiameterscanbefurnished whenrequiredbytheuser.Allconductorsintheconduitarethesamesize. Otherconduitsizesmaybefurnishedonrequest.

[email protected]

13

Electric Utility

Low-Voltage Power Cable

PowrServ OH Service Drop Cable Neutral-Supported600 V Duplex Al Conductor XLPE InsulationProduct Construction: Complete Cable:Overhead (OH) duplex service drop cable consists of one aluminum conductor insulated with extruded lead-free Cross-linked Polyethylene (XLPE), twisted around a bare conductor which serves as a supporting neutral. Service drop cable meets the requirements of ANSI/ICEA S-76-474. Conductors meet ASTM B231, B232 and B399 as applicable. Insulated Conductors: The all-aluminum stranded conductors are Class A or Class B compressed 1350-H19 aluminum. Solid conductors are H16 temper. Insulation: The insulation is black extruded lead-free Cross-linked Polyethylene (XLPE). Bare Neutral: The all-aluminum stranded conductors are Class AA or Class A 1350-H19 (AAC) or 6201T81 alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The direction of lay of the outer layer is right-hand. Phase Identification: Phase identification is provided by means of white print legend markings on the phase conductor.

POWRSERV OH DUPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTOR SIZE AWG 6 6 6 4 4 4 2 1 1/0 1/0 NEUTRAL CONDUCTOR NO. INS. NO. RATED EFF. OF THKN. SIZE OF STRG. O.D. WIRES INCHES AWG WIRES POUNDS INCHES 1 7 7 1 7 7 7 19 7 19 0 .045 0 .045 0 .060 0 .045 0 .045 0 .060 0 .045 0 .060 0 .060 0 .060 6 6 6 4 4 4 2 1 1/0 1/0 7 7 7 7 7 7 7 7 7 7 563 563 563 881 881 881 1350 1640 1990 1990 0 .44 0 .45 0 .48 0 .53 0 .55 0 .58 0 .67 0 .76 0 .84 0 .84 APPROX. WEIGHT LB/1000 FT AL 49 49 49 78 78 78 125 157 199 199 TOTAL 61 64 69 92 96 103 147 188 236 233 PACKAGING (2) AMPS (1) 110 110 110 145 145 145 195 225 260 260 TYPE & SIZE COIL NR27.18 COIL NR27.18 COIL NR30.18 COIL NR30.18 COIL NR27.18 COIL NR30.18 COIL NR32.24 COIL NR36.24 COIL NR32.24 COIL NR32.24 LENGTH FEET 1000 3600 1000 3300 1000 3600 1000 2600 1000 2200 1000 2200 500 2500 500 2500 500 1500 500 1500

CODE WORD Pekingese/XLP Collie/XLP Cocker/XLP Dachshund/XLP Spaniel/XLP Cairn/XLP Doberman/XLP Airedale/XLP Basset/XLP Malemute/XLP

ALUMINUM 1350 FULL-SIZE NEUTRAL MESSENGER

Features and Benefits:The insulated conductors of service drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. This cable is rated at 600 volts with a maximum conductor operating temperature of 90C for cross-linked polyethylene insulation.

Applications:Duplex service drop cable is intended to deliver single phase power from the secondary power line or pole mounted transformer to the serviceentrance conductors at the users building or other structure. It may also be used as pole line secondary with service splices at the pole or in mid-span.

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientof emissivity,nosun.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2) ormallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailablesee N Section6forReelessPackagedescriptionandtypicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

Options:Aluminum1350-H16conductor Copperconductors High-molecular-weightPolyethylene(PE) insulation High-DensityPolyethylene(HDPE)insulation Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

[email protected]

14

Low-Voltage Power Cable

Electric Utility

PowrServ OH Service Drop Cable Neutral-Supported

600 V Duplex Al Conductor XLPE Insulation

POWRSERV OH DUPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTOR SIZE AWG 6 6 6 4 4 4 2 1 1/0 1/0 BARE NEUTRAL RATED STRG. POUNDS 1190 1190 1190 1860 1860 1860 2850 3550 4380 4380 EFF. O.D. INCHES 0 .45 0 .47 0 .50 0 .54 0 .57 0 .60 0 .69 0 .79 0 .87 0 .87 APPROX. WEIGHT LB/1000 FT AL 49 49 49 78 78 78 125 157 198 198 TOTAL 72 75 80 110 115 121 177 225 283 279 AMPS (1) 110 110 110 145 145 145 195 225 260 260 PACKAGING (2) TYPE & SIZE COIL NR27.18 COIL NR30.18 COIL NR30.18 COIL NR27.18 COIL NR30.18 COIL NR30.18 COIL NR32.24 COIL NR36.24 COIL NR32.24 COIL NR32.24 COIL NR27.18 COIL NR27.18 COIL NR30.18 COIL NR27.18 COIL NR32.24 COIL NR32.24 COIL NR32.24 LENGTH FEET 1000 3300 1000 3300 1000 3300 1000 2400 1000 2400 1000 2400 500 2400 500 2400 500 1500 500 1500 1000 3600 1000 3300 1000 2600 1000 2200 500 2500 500 1500 500 500

CODE WORDSetter/XLP Shepherd/XLP Retriever/XLP Eskimo/XLP Terrier/XLP Yorkshire/XLP Chow/XLP Labrador/XLP Bloodhound/XLP Bull/XLP

NO. INS. THKN. SIZE AWG NO. OF WIRES INCHES OR kcmil OF WIRES 1 7 7 1 7 7 7 19 7 19 0 .045 0 .045 0 .060 0 .045 0 .045 0 .060 0 .045 0 .060 0 .060 0 .060 6 6 6 4 4 4 2 1 1/0 1/0 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1

ACSR FULL-SIZE NEUTRAL MESSENGER

ALUMINUM 6201-T81 FULL-SIZE NEUTRAL MESSENGERChihuahua/XLP Vizsla/XLP Harrier/XLP Whippet/XLP Schnauzer/XLP Afghan/XLP Heeler/XLP

6 6 4 4 2 1/0 1/0

1 7 1 7 7 7 19

0 .045 0 .045 0 .045 0 .045 0 .045 0 .060 0 .060

30 .58 30 .58 48 .69 48 .69 77 .47 123 .3 123 .3

7 7 7 7 7 7 7

1110 1110 1760 1760 2800 4270 4270

0 .45 0 .47 0 .54 0 .57 0 .69 0 .88 0 .87

53 53 84 85 135 215 215

65 67 98 103 157 252 249

110 110 145 145 195 260 260

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientofemissivity,nosun.Forspecificampacities,contactyourGeneral Cablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionandtypicaldimensions forselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

[email protected]

15

Electric Utility

Low-Voltage Power Cable

PowrServ OH Service Drop Cable Neutral-Supported600 V Triplex Al Conductor XLPE InsulationProduct Construction: Complete Cable:Overhead (OH) triplex service drop cable consists of two aluminum conductors insulated with extruded lead-free Cross-linked Polyethylene (XLPE), twisted around a bare conductor which serves as a supporting neutral. Service drop cable meets the requirements of ANSI/ICEA S-76-474. Conductors meet ASTM B231, B232 and B399 as applicable. Insulated Conductors: The all-aluminum stranded conductors are Class A or Class B compressed 1350-H19 aluminum. Solid conductors are H16 temper. Insulation: The insulation is black extruded lead-free Cross-linked Polyethylene (XLPE). Bare Neutral: The all-aluminum stranded conductors are Class AA or Class A 1350-H19 (AAC) or 6201T81 alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The direction of lay of the outer layer is right-hand. Phase Identification: Phase identification is provided by means of white print legend markings on one phase conductor.

POWRSERV OH TRIPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTORS SIZE AWG 6 6 4 2 1 1 1/0 1/0 2/0 2/0 3/0 4/0 4/0 NEUTRAL CONDUCTOR NO. INS. NO. RATED EFF. OF THKN. SIZE OF STRG. O.D. WIRES INCHES AWG WIRES POUNDS INCHES 1 7 7 7 7 19 7 19 7 19 19 7 19 0 .045 0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 6 6 4 2 1 1 1/0 1/0 2/0 2/0 3/0 4/0 4/0 7 7 7 7 7 7 7 7 7 7 19 7 19 563 563 881 1350 1640 1640 1990 1990 2510 2510 3310 3830 4020 0 .50 0 .53 0 .63 0 .76 0 .90 0 .87 0 .97 0 .96 1 .06 1 .05 1 .16 1 .29 1 .29 APPROX. WEIGHT LB/1000 FT AL 73 74 118 187 236 236 298 298 375 375 473 597 597 TOTAL 97 102 153 232 305 297 373 366 461 451 558 708 693 PACKAGING (2) AMPS (1) 110 110 145 195 225 225 260 260 300 300 350 405 405 TYPE & SIZE COIL NR30.18 COIL NR30.18 COIL NR30.18 COIL NR32.24 COIL NR36.24 COIL NR36.24 COIL NR36.24 COIL NR36.24 NR42.26 LENGTH FEET 1000 2500 1000 2200 500 1500 500 1800 500 1500 500 1500 500 1200 500 1200 1500

CODE WORD Haiotis/XLP Patella/XLP Oyster/XLP Clam/XLP Pyrula/XLP Hyas/XLP Murex/XLP Purpura/XLP Nassa/XLP Trophon/XLP Melita/XLP Coquina/XLP Portunus/XLP

ALUMINUM 1350 FULL-SIZE NEUTRAL MESSENGER

Features and Benefits:The insulated conductors of service drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. This cable is rated at 600 volts with a maximum conductor operating temperature of 90C for cross-linked polyethylene insulation.

NR42.26 1500 NR42.26 1300 NR42.26 1000 NR42.26 1000

Applications:Triplex service drop cable is intended to deliver 3-wire single phase power from the secondary power line or pole mounted transformer to the service-entrance conductors at the users building or other structure. It may also be used as pole line secondary with service splices at the pole or in mid-span.

Options:Aluminum1350-H16conductor Copperconductors High-molecular-weightPolyethylene(PE) insulation High-DensityPolyethylene(HDPE)insulation Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

ALUMINUM 1350 REDUCED-SIZE NEUTRAL MESSENGERLimpet/XLP Mussel/XLP Snail/XLP 4 2 1/0 7 7 7 0 .045 0 .045 0 .060 6 4 2 7 7 7 563 881 1350 0 .60 0 .72 0 .92 102 164 261 137 209 337 145 COIL 500 NR30.18 1500 195 COIL 500 NR32.24 1800 260 COIL 500 NR32.24 1200

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientof emissivity,nosun.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailablesee Section6forReelessPackagedescriptionandtypicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

[email protected]

16

Low-Voltage Power Cable

Electric Utility

PowrServ OH Service Drop Cable Neutral-Supported

600 V Triplex Al Conductor XLPE Insulation

POWRSERV OH TRIPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTORS SIZE AWG 6 6 4 4 4 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 BARE NEUTRAL RATED STRG. POUNDS 1190 1190 1860 2360 1860 2850 3550 3550 4380 4380 5300 5300 6620 6620 8350 8350 EFF. O.D. INCHES 0 .51 0 .54 0 .61 0 .62 0 .64 0 .77 0 .91 0 .89 0 .99 0 .98 1 .09 1 .08 1 .20 1 .19 1 .32 1 .31 APPROX. WEIGHT LB/1000 FT AL 73 74 116 116 118 187 236 236 297 297 375 375 472 472 596 596 TOTAL 108 114 163 173 172 262 342 334 420 413 520 510 644 632 801 786 AMPS (1) 110 110 145 145 145 195 225 225 260 260 300 300 350 350 405 405 PACKAGING (2) TYPE & SIZE COIL NR30.18 COIL NR30.18 COIL NR30.18 COIL NR30.18 COIL NR30.18 COIL NR36.24 COIL NR36.24 COIL NR36.24 COIL NR36.24 COIL NR36.24 NR42.26 NR42.26 NR42.26 NR42.26 NR42.26 NR42.26 LENGTH FEET 1000 2500 1000 2200 500 1700 500 1500 500 1500 500 1800 500 1500 500 1500 500 1200 500 1200 1500 1500 1300 1300 1000 1000

CODE WORDPaludina/XLP Voluta/XLP Whelk/XLP Weakfish/XLP Periwinkle/XLP Conch/XLP Vermeths/XLP Atya/XLP Neritina/XLP Cenia/XLP Runcina/XLP Triton/XLP Cherrystone/XLP Mursia/XLP Razor/XLP Zuzara/XLP

NO. INS. THKN. NO. OF WIRES INCHES SIZE AWG OF WIRES 1 7 1 1 7 7 7 19 7 19 7 19 7 19 7 19 0 .045 0 .045 0 .045 0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 6 6 4 4 4 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 6/1 6/1 6/1 7/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1

ACSR FULL-SIZE NEUTRAL MESSENGER

ACSR REDUCED-SIZE NEUTRAL MESSENGERScallop/XLP Strombus/XLP Cockle/XLP Janthina/XLP Ranella/XLP Cavolina/XLP Clio/XLP Sanddollar/XLP Aega/XLP Cuttlefish/XLP Cerapus/XLP

4 4 2 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0

1 7 7 7 19 7 19 7 19 7 19

0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060

6 6 4 2 2 1 1 1/0 1/0 2/0 2/0

6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1

1190 1190 1860 2850 2850 3550 3550 4380 4380 5300 5300

0 .58 0 .61 0 .73 0 .93 0 .92 1 .02 1 .01 1 .13 1 .12 1 .24 1 .23

101 103 164 261 261 329 329 414 414 522 522

142 150 228 366 358 452 442 558 547 692 677

145 145 195 260 260 300 300 350 350 405 405

COIL NR30.18 COIL NR30.18 COIL NR32.24 COIL NR32.24 COIL NR36.24 NR40.24 NR40.24 NR40.24 NR40.24 NR40.24 NR40.24

500 1700 500 1500 500 1800 500 1200 500 1200 1500 1500 1300 1300 1000 1000

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientofemissivity,nosun.Forspecificampacities,contactyourGeneral Cablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionandtypicaldimensions forselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext, weightmeansmass.

[email protected]

17

Electric Utility

Low-Voltage Power Cable

PowrServ OH Service Drop Cable Neutral-Supported600 V Triplex Al Conductor XLPE InsulationPOWRSERV OH TRIPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTORS SIZE AWG 6 4 2 1/0 1/0 2/0 2/0 3/0 4/0 BARE NEUTRAL RATED STRG. POUNDS 1110 1760 2800 4280 4280 5390 5390 6790 8560 EFF. O.D. INCHES 0 .54 0 .64 0 .77 0 .99 0 .98 1 .09 1 .08 1 .19 1 .31 APPROX. WEIGHT LB/1000 FT AL 78 124 197 313 313 395 395 497 627 TOTAL 106 160 242 389 382 481 472 584 724 AMPS (1) 110 145 195 260 260 300 300 350 405 PACKAGING (2) TYPE & SIZE COIL NR30.18 COIL NR30.18 COIL NR32.24 COIL NR36.24 COIL NR36.24 NR42.26 NR42.26 NR42.26 NR42.26 LENGTH FEET 1000 2200 500 1500 500 1800 500 1200 500 1200 1500 1500 1300 1000

CODE WORDHippa/XLP Barnacles/XLP Shrimp/XLP Gammarus/XLP Leda/XLP Dungeness/XLP Cyclops/XLP Flustra/XLP Lepas/XLP

NO. INS. THKN. NO. OF WIRES INCHES SIZE kcmil OF WIRES 7 7 7 7 19 7 19 19 19 0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 30 .58 48 .69 77 .47 123 .3 123 .3 155 .4 155 .4 195 .7 246 .9 7 7 7 7 7 7 7 7 7

6201-T81 FULL-SIZE NEUTRAL MESSENGER

6201-T81 REDUCED-SIZE NEUTRAL MESSENGERArtemia/XLP Crab/XLP Solaster/XLP Sandcrab/XLP Fulgar/XLP Squid/XLP Arca/XLP

4 4 2 1/0 3/0 4/0 4/0

1 7 7 7 19 7 19

0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060

30 .58 30 .58 48 .69 77 .47 123 .3 155 .4 155 .4

7 7 7 7 7 7 7

1110 1110 1760 2800 4280 5390 5390

0 .58 0 .61 0 .73 0 .93 1 .12 1 .24 1 .23

106 107 170 271 431 543 543

134 143 215 347 516 654 639

145 145 195 260 350 405 405

COIL NR30.18 COIL NR30.18 COIL NR32.24 COIL NR36.24 NR40.24 NR40.24 NR40.24

500 1700 500 1500 500 1800 500 1200 1300 1000 1000

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientofemissivity,nosun.Forspecificampacities,contactyourGeneral Cablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionandtypicaldimensions forselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

[email protected]

18

Low-Voltage Power Cable

Electric Utility

PowrServ OH Service Drop Cable Neutral-Supported

600 V Quadruplex Al Conductor XLPE InsulationProduct Construction: Complete Cable:Overhead (OH) quadruplex service drop cable consists of three aluminum conductors insulated with extruded lead-free Cross-linked Polyethylene (XLPE), twisted around a bare conductor which serves as a supporting neutral. Service drop cable meets the requirements of ANSI/ICEA S-76-474. Conductors meet ASTM B231, B232 and B399 as applicable. Insulated Conductors: The all-aluminum stranded conductors are Class A or Class B compressed 1350-H19 aluminum. Solid conductors are H16 temper. Insulation: The insulation is black extruded lead-free Cross-linked Polyethylene (XLPE). Bare Neutral: The all-aluminum stranded conductors are Class AA or Class A 1350-H19 (AAC) or 6201-T81 alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The direction of lay of the outer layer is righthand. Phase Identification: Phase identification is provided by means of white print legend markings on one phase conductor, one rib on another phase conductor, and two ribs on another phase conductor.

POWRSERV OH QUADRUPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTORS SIZE AWG 6 4 4 2 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 NEUTRAL CONDUCTOR NO. INS. NO. RATED EFF. O.D. OF THKN. SIZE OF STRG. WIRES INCHES AWG WIRES POUNDS INCHES 1 1 7 7 19 7 19 7 19 7 19 7 19 0 .045 0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 6 4 4 2 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 7 7 7 7 7 7 7 7 7 7 19 7 19 563 881 881 1350 1640 1990 1990 2510 2510 3040 3310 3830 4020 0 .57 0 .67 0 .71 0 .85 1 .00 1 .09 1 .08 1 .20 1 .19 1 .32 1 .31 1 .45 1 .44 APPROX. WEIGHT LB/1000 FT AL 97 155 157 250 315 397 397 501 501 631 631 796 796 TOTAL 133 197 210 317 408 510 499 629 614 776 758 962 939 PACKAGING (2) AMPS (1) 105 TYPE & SIZE LENGTH FEET 500 2500 500 1700 500 1700 1800

CODE WORD Quarter/XLP Clydesdale/XLP Pinto/XLP Mustang/XLP Shire/XLP Libyan/XLP Criollo/XLP Orloff/XLP Percheron/XLP Mongolian/XLP Hanoverian/XLP Singlefoot/XLP Oldenberg/XLP

ALUMINUM 1350 FULL-SIZE NEUTRAL MESSENGERCOIL NR32.24 135 COIL NR32.24 135 COIL NR32.24 175 NR40.24

205 NR40.24 1500 240 NR40.24 1200 240 NR40.24 1200 280 NR45.28 1500 280 NR45.28 1500 325 NR45.28 1300 325 NR45.28 1300 375 NR50.32 1100 375 NR50.32 1100

Features and Benefits:The insulated conductors of service drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. This cable is rated at 600 volts with a maximum conductor operation temperature of 90C for cross-linked polyethylene insulation.

Applications:Quadruplex service drop cable is intended to deliver 4-wire three phase power from the secondary power line or pole-mounted transformer to the service-entrance conductors at the users building or other structure. It may also be used as pole line secondary with service splices at the pole or in mid-span.

Options:Aluminum1350-H16conductor Copperconductors High-molecular-weightPolyethylene(PE) insulation High-DensityPolyethylene(HDPE)insulation Reelesspackage For more information, contact your General Cable sales representative or e-mail [email protected]

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientof emissivity,nosun.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailablesee Section6forReelessPackagedescriptionandtypicaldimensionsforselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

[email protected]

19

Electric Utility

Low-Voltage Power Cable

PowrServ OH Service Drop Cable Neutral-Supported600 V Quadruplex Al Conductor XLPE InsulationPOWRSERV OH QUADRUPLEX SERVICE DROPXLPE INSULATION600 VOLTSPHASE CONDUCTORS SIZE AWG 6 6 4 4 2 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 BARE NEUTRAL RATED STRG. POUNDS 1190 1190 1860 1860 2850 3550 4380 4380 5300 5300 6620 6620 8350 8350 EFF. O.D. INCHES 0 .58 0 .61 0 .69 0 .72 0 .87 1 .02 1 .11 1 .10 1 .22 1 .20 1 .34 1 .32 1 .48 1 .46 APPROX. WEIGHT LB/1000 FT AL 97 99 154 157 249 314 397 397 500 500 630 630 795 795 TOTAL 144 153 216 229 347 446 557 546 688 673 850 833 1055 1033 AMPS (1) 105 105 135 135 175 205 240 240 280 280 325 325 375 375 PACKAGING (2) TYPE & SIZE COIL NR32.24 COIL NR32.24 COIL NR32.24 COIL NR32.24 NR40.24 NR40.24 NR42.26 NR42.26 NR45.28 NR45.28 NR50.32 NR50.32 NR50.32 NR50.32 LENGTH FEET 500 2500 500 2500 500 1700 500 1700 1800 1500 1200 1200 1500 1500 1300 1300 1100 1100

CODE WORDMorchuca/XLP Chola/XLP Morgan/XLP Hackney/XLP Palomino/XLP Albino/XLP Standardbred/ XLP Costena/XLP Chicoteagues/ XLP Grullo/XLP Mare/XLP Suffolk/XLP Stallion/XLP Appaloosa/XLP

NO. INS. THKN. SIZE AWG NO. OF WIRES INCHES OR kcmil OF WIRES 1 7 1 7 7 19 7 19 7 19 7 19 7 19 0 .045 0 .045 0 .045 0 .045 0 .045 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 0 .060 6 6 4 4 2 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1 6/1

ACSR FULL-SIZE NEUTRAL MESSENGER

6201-T81 FULL-SIZE NEUTRAL MESSENGERArabian/XLP Belgian/XLP Shetland/XLP Thoroughbred/ XLP Trotter/XLP Walking/XLP

4 2 1/0 2/0 3/0 4/0

7 7 19 19 19 19

0 .045 0 .045 0 .060 0 .060 0 .060 0 .060

48 .69 77 .47 123 .3 155 .4 195 .7 246 .9

7 7 7 7 7 7

1760 2800 4270 5390 6790 8560

0 .72 0 .87 1 .10 1 .20 1 .32 1 .46

163 260 413 521 656 828

217 327 515 635 784 971

135 175 240 280 325 375

COIL NR32.24 NR40.24 NR40.24 NR45.28 NR50.32 NR50.32

500 1700 1800 1200 1500 1300 1100

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientofemissivity,nosun.Forspecificampacities,contactyourGeneral Cablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary.Reelesspackage(largecoil)isavailableseeSection6forReelessPackagedescriptionandtypicaldimensions forselectedlow-voltageproducts. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturingtolerances.Inthiscontext,weightmeansmass.

[email protected]

20

Low-Voltage Power Cable

Electric Utility

PowrServ OH Secondary Cable Neutral-Supported Type RTS600 V Triplex Al Conductor XLPE Insulation Reverse Twist Secondary (RTS)Product Construction: Complete Cable:Reverse Twist Secondary (RTS) cable consists of two aluminum conductors insulated with extruded lead-free Cross-linked Polyethylene (XLPE), reverse twisted around an aluminum alloy or ACSR conductor which serves as a supporting neutral. RTS cable meets the requirements of ANSI/ICEA S-76-474. Conductors meet ASTM B231, B232 and B399 as applicable. Insulated Conductors: The all-aluminum stranded conductors are Class A or Class B compressed 1350-H19 aluminum. Insulation: The insulation is black extruded lead-free CrossLinked Polyethylene (XLPE). Bare Neutral: The all-aluminum alloy stranded conductors are Class AA or Class A 6201-T81 aluminum alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The outer layer is right-hand. Lashing Wire: Aluminum 1350 wire, either flat wire approximately #10 AWG with beveled edges or #10 AWG wire covered with high-density polyethylene.

POWRSERV OH TRIPLEX REVERSE TWIST SECONDARYXLPE INSULATIONPHASE CONDUCTORS SIZE AWG 2 1/0 2/0 3/0 4/0 NEUTRAL CONDUCTOR APPROX. WEIGHT NO. INS. SIZE NO. RATED EFF. LB/1000 FT OF THKN. AWG OR OF STRG. O.D. WIRES INCHES kcmil WIRES POUNDS INCHES AL TOTAL AMPS (1) 7 7 7 7 7 0 .045 0 .060 0 .060 0 .060 0 .060 77 .47 123 .3 155 .4 195 .7 246 .9 7 7 7 7 7 2800 4270 5390 6790 8560 0 .77 0 .98 1 .08 1 .19 1 .31 197 314 396 499 629 242 382 472 584 724 195 260 300 350 405 PACKAGING (2) TYPE & SIZE NR32.24 NR42.26 NR40.24 NR50.32 NR40.24 NR50.32 NR42.26 NR58.32 NR50.32 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR32.24 NR42.26 NR40.24 NR50.32 NR40.24 NR50.32 NR42.26 NR58.32 NR50.32 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 NR66.36 LENGTH FEET 1100 2100 1100 2500 1000 2000 1000 2500 1300 2700 3400 1600 2400 1500 2000 1200 1600 1100 2100 1100 2500 1000 2000 1000 2500 1300 2700 3400 1600 2400 1500 2000 1200 1600

CODE WORD Pope/XLP Auburn/XLP Rockne/XLP Case/XLP Durant/XLP

ALUMINUM 6201-T81 NEUTRAL MESSENGER

-none-none-none-

266 .8 336 .4 397 .5

19 19 19

0 .080 0 .080 0 .080

312 .8 394 .5 465 .4

19 19 19

10500 13300 15600

1 .54

794

941

470 550 610

1 .70 1002 1167 1 .83 1183 1363

Features and Benefits:The insulated conductors of RTS cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. Conventional equipment can be used to string RTS. This cable is rated at 600 volts with a maximum conductor operations temperature of 90C for extruded cross-linked polyethylene insulation.

ACSR FULL-SIZE NEUTRAL MESSENGEREdsel/XLP Essex/XLP Cord/XLP Stutz/XLP Reo/XLP 2 1/0 2/0 3/0 4/0 7 7 7 7 7 0 .045 0 .060 0 .060 0 .060 0 .060 2 1/0 2/0 3/0 4/0 6/1 6/1 6/1 6/1 6/1 2850 4380 5300 6620 8350 0 .77 0 .98 1 .08 1 .19 1 .31 187 297 375 472 596 262 413 510 632 786 195 260 300 350 405

Applications:Reverse twist secondary cable is used as a secondary overhead distribution cable for 3-wire single phase power. The alternating lay direction (left-right-left) provides additional cable length for mid-span taps.

Options:Aluminum1350-H16conductor Copperconductors High-molecular-weightPolyethylene(PE) insulation High-DensityPolyethylene(HDPE)insulation Separatortapeunderinsulation For more information, contact your General Cable sales representative or e-mail [email protected]

-none-none-none-

266 .8 336 .4 397 .5

19 19 19

0 .080 0 .080 0 .080

266 .8 336 .4 397 .5

26/7 26/7 26/7

11300 14100 16300

1 .54 1 .70

754 950

1018 1263

470 550 610

1 .83 1123 1477

(1) Ampacitiesarebasedonconductortemperatureof65Cover25Cambient,2ft/seccrosswind,.9coefficientof emissivity,nosun.Forspecificampacities,contactyourGeneralCablesalesrepresentative. (2)Normallengthandshippingtolerancesapply.Reelsizesmayvary. Dimensionsandweightsnotdesignatedminimumormaximumarenominalvaluesandsubjecttomanufacturing tolerances.Inthiscontext,weightmeansmass.

[email protected]

21

Electric Utility

Low-Voltage Power Cable

PowrServ OH Secondary Cable Neutral-Supported Type PLAC600 V Triplex Al Conductor XLPE Insulation Parallel Secondary (PLAC)Product Construction: Complete Cable:Triplex Parallel Lashed Aerial Cable (PLAC) consists of two aluminum conductors insulated with extruded lead-free Cross-linked Polyethylene, and one bare aluminum alloy or an ACSR conductor laid parallel to each other. The bare conductor, which serves as a supporting neutral, is in the outside position. The cable is bound together with lashing wire with a lay of from four to six inches. Type PLAC cable meets the requirements of ANSI/ICEA S-76-474. Conductors meet ASTM B231, B232 and B399 as applicable. Insulated Conductors: The all-aluminum stranded conductors are Class A or Class B compressed 1350-H19 aluminum. Insulation: The insulation is black extruded lead-free Crosslinked Polyethylene (XLPE). Bare Neutral: The all-aluminum alloy stranded conductors are Class AA or Class A 6201-T81 aluminum alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The outer layer is right-hand. Lashing Wire: Aluminum 1350 wire, either flat w