GEIndustrial Solutions
ASTATSoft starters for 3ph standard induction motorsHigh reliability for multiple applications
GE imagination at work
1
ASTAT S
Approvals/Marking
Small soft starters with integral bypass
ASTAT S is compact, easy to operate soft starter, designed for use with standard 3-phase squirrel cage motors. It provides an advanced method of reducing current during motor starting and stopping.ASTAT S will start supplying a reduced voltage to the motor, increasing up to the rated voltage, so avoiding, high currents and generating soft starting and stopping.The motor has to be able to start in a reduced voltage.
• Solid soft starter for standard 3ph AC motors up to 30kW at 400V AC• Voltage ratings up to 600V• Two phase control with integral bypass• Compact, small case• DIN rail mounting. Optional from 31A• Start and soft stop features
Technical data
Voltage ratings 3ph AC systems 220/230V (+10%, -15%) for units QA02P_ _ _ S 380/415V (+10%, -15%) for units QA12P _ _ _ S 480/500V (+10%, -15%) for units QA22P _ _ _ S 575/600V (+10%, -15%) for units QA32P _ _ _ SFrequency range 50/60Hz (±5%)Load 3ph, AC standard motors
Control specifi cationsRamp up 0.5 - 10 s (set by potentiometer)Ramp down 0.5 - 10 s (set by potentiometer)Initial voltage 0 - 80% Un (set by potentiometer)Starting torque 0 - 64% Tn
Inputs one input for Start/StopOutputs one output for «End of Ramp» signal for ratings 31, 44, 58A
Ambient conditionsOperating temperature 0 to 40ºC. Up to 60ºC derating by 1.2% per ºCStorage temperature -20 to 70ºCRelative humidity up to 80%, without condensation Max. altitude up to 1000m. Above this derate by 5% each 100mProtection degree IP20
Ratings
I/O control
cULus
The cUL, is achieved for all range of ASTAT S, except for 58A models, items QA02P058S, QA12P058S, QA22P058S, QA32P058S.
Small soft starters
2
Dig
ital s
oft s
tart
ers
ASTAT S
Small soft starters with integral bypassMaximum motor power (1)
(1) Ratings for standard 4-poles AC motors(2) See Operations/hour in table below Cycles/hour includes both soft start and soft stop
Time between rampings Start/Stop
Input Current Maximum Cat. No. Ref. no. Pack voltage rating (2) current 220/230V 380/415V 480/500V 575/600V VAC A A kW / HP kW / HP kW / HP kW / HP 220 8 28 1.5 / 2 - - - QA02P008S 120881 1 17 60 4 / 5.5 - - - QA02P017S 120882 1 22 77 5.5 / 7.5 - - - QA02P022S 120883 1 31 110 7.5 / 10 - - - QA02P031S 120884 1 44 150 11 / 15 - - - QA02P044S 120885 1 58 200 15 / 20 - - - QA02P058S 120886 1
400 8 28 - 4 / 5.5 - - QA12P008S 120892 1 17 60 - 7.5 / 10 - - QA12P017S 120893 1 22 77 - 11 / 15 - - QA12P022S 120894 1 31 110 - 15 / 20 - - QA12P031S 120895 1 44 150 - 22 / 30 - - QA12P044S 120896 1 58 200 - 30 / 40 - - QA12P058S 120897 1
500 8 28 - - 5.5 / 7.5 - QA22P008S 120898 1 17 60 - - 11 / 15 - QA22P017S 120899 1 22 77 - - 15 / 20 - QA22P022S 120900 1 31 110 - - 22 / 30 - QA22P031S 120901 1 44 150 - - 30 / 40 - QA22P044S 120902 1 58 200 - - 45 / 60 - QA22P058S 120903 1
600 8 28 - - - 7.5 / 10 QA32P008S 120904 1 17 60 - - - 15 / 20 QA32P017S 120905 1 22 77 - - - 22 / 30 QA32P022S 120906 1 31 110 - - - 30 / 40 QA32P031S 120907 1 44 150 - - - 37 / 50 QA32P044S 120908 1 58 200 - - - 55 / 75 QA32P058S 120909 1
Accessory DIN rail mounting kit for types 31A, 44A and 58A QAOPTDIN 120910 1
Starting Ramp 1 sec. Ramp 2 sec. Ramp 5 sec. Ramp 10 sec. current (A) QA_2P008S 8 7 15 35 70 16 16 33 77 155 24 26 51 125 250 28 (*) 32 62 155 - QA_2P017S 17 7 15 35 70 34 16 33 77 155 51 26 51 125 250 60 (*) 32 62 155 - QA_2P022S 22 7 15 35 70 44 16 33 77 155 66 26 51 125 250 77 (*) 32 62 155 - QA_2P031S 31 4 8 20 40 62 8 15 38 76 93 12 24 62 124 110 (*) 15 31 80 - QA_2P044S 44 4 8 20 40 88 8 15 38 76 132 12 24 62 124 155(*) 15 31 80 - QA_2P058S 58 4 8 20 40 116 8 15 38 76 174 12 24 62 124 200 (*) 15 31 80 -
(*) Maximum starting current at all
3
Small soft starters
ASTAT S
start/stop
Diagrams
Control by permanent command(soft start and stop)
Control by push-buttons, line contactor and thermal overload relay (soft start)
Control by push-buttons and line contactor (soft start)
Forward/reverse control by push-buttons(3)
4 5.5 QA12P008 GPS1B*AK 10 EC25A 268103 - P9 7.5 10 QA12P017 GPS1B*AN 25 EC25A 268105 - P9 11 15 QA12P022 GPS1B*AP 32 EC25A 268106 - P9 15 20 QA12P031 GPS1B*AR 40 EC32A 268108 - P9 22 30 QA12P044 GPS2B*AT 63 CL06A 113722 - P9 30 40 QA12P058 GPS2B*AU 80 CL07A 113723 - P9
Coordination type 2, with thermal overload relays, class 10.For other thermal class, please consult our Controls & Power Electronics catalogue.
Motor power ASTAT S Q1 Q2 KM1 Q3 F1-F2 S1-S2-S3 380/415V Thermal kW Hp Am fuses Contactor overload relay
(1) Use dry contact only.(2) End of Ramp output relay (only types 31A, 44A and 58A).(3) Forward/Reverse operation must be done when motor is not rotating.(4) Ground terminal only for types 31A, 44A and 58A.
4
Dig
ital s
oft s
tart
ers
ASTAT S
Direct-on-line start ASTAT S soft start
Direct-on-line stop ASTAT S soft stop
DOL
Time
Spe
edC
urre
ntVo
ltage
Uo=0.5Un, To=25Tn, RAMP UP 0.9s
Time
Spe
edC
urre
ntVo
ltage
Time
Spe
edC
urre
ntVo
ltage
DOL
Time
Spe
edC
urre
ntVo
ltage
RAMP DOWN 0.5s
Performances
5
ASTAT SSm
all soft starters
Dimensional drawings
Dimensions in mm Dimensions in mm
Dimensions in mm
QA12P008S 0.470 QA22P008S 0.470
TYPE Weight (kg)
QA_2P031S 1.370 QA_2P044S 1.400 QA_2P058S 1.400
TYPE Weight (kg)
Small soft starter with integral bypass
QA_2P017S 0.610 QA_2P022S 0.650 QA32P008S 0.650
TYPE Weight (kg)
2
2
Notes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
ASTATSo
ft s
tart
ers
ASTAT XT
7
Digital soft starters
Digital soft starters for 3ph standard induction motorsGE´s new ASTAT XT solid state soft starter features microprocessor control digital technology. Setup and adjustment is performed through a six-button keypad and parameters or messages are displayed out trough a friendly LCD multilanguage interface with two rows, sixteen alphanumeric characters each. The design includes isolated I/O and high level of protection in their circuits to minimize the disturbance effects while working in the hardest industrial environment.
ASTAT XT soft starter offers reliable performance and smooth acceleration for a variety of standard AC motors up to 1400A and up to 690V, reducing mechanical shock to the driving system, resulting in extended component and motor life.
ASTAT XT offers many traditional features such a motor overload function, adjustable ramps, current limit , kick start , but also other high end features like Inside-Delta operation, Torque control, Pump control and a reliable motor and unit set of protections.
Key features• Ratings up to 1400Amps and up to 690VAC• Friendly multilanguage interface with two rows, sixteen characters each• Built-in with three extra power terminals for external bypass• In-Line or Inside-Delta operation modes• Torque control and pump control advanced features• Motor protection according IEC 10, 20 and NEMA 10, 20, 30, even if
ASTAT XT is in bypass• Built-in communications RS485 port, and ModBus protocol as standard• Profi busDP and DeviceNet optional interfaces for communications
ASTAT XT
Approvals / Marking
For units up to 820A. “U” type
Control panel
DinGdkeLCeaciin
Afoma
A
ASTAT XT
8
Dig
ital s
oft s
tart
ers
QT10008U21MSASTAT XT 8A-72A
QT10105U21MSASTAT XT 105A-170A
QT10460N21MSASTAT XT 460A-650A
Recommended motor and type unit ratings
Light DutyLight Duty Normal Duty (IEC Class 10)Normal Duty (IEC Class 10) Heavy DutyHeavy DutyBuilt-in communication network International version
Modbus Profi bus DP DeviceNet Modbus Profi bus DP DeviceNet
Max rating Rated 230V 400V-415V 480V-500V 690V Rated 230V 400V-415V 480V-500V 690Vcurrent (A) current (A) kW kW kW kW current (A) kW kW kW kW
Mains voltage 8 8 1.5 3 4 - 8 1.5 3 4 -230-500Vac 17 17 4 7.5 7.5 - 12 3 5.5 5.5 -
Control voltage 34 31 7.5 15 18.5 - 31 7.5 15 18.5 -230Vac 54 44 11 22 30 - 44 11 22 30 -
65 58 15 30 37 - 55 15 30 37 -72 72 22 37 45 - 66 18.5 37 45 -
104 85 22 45 55 - 80 22 45 55 -Digital inputs 130 105 30 55 55 - 99 30 55 55 -
voltage 156 145 45 75 90 - 130 37 55 90 -90-230Vac 170 170 55 90 110 - 134 37 75 90 -
248 210 55 110 132 - 203 55 110 132 -361 310 90 160 200 - 310 75 160 200 -390 390 110 200 250 - 344 110 160 250 -480 460 132 250 315 - 432 132 250 315 -480 460 132 250 315 - 432 132 250 315 -610 580 160 315 400 - 488 160 250 355 -610 580 160 315 400 - 552 160 315 400 -820 650 200 355 400 - 552 160 315 400 -820 820 250 400 560 - 690 200 400 500 -
1180 950 315 560 630 - 950 315 560 630 -1375 1100 355 630 800 - 1076 355 630 800 -1750 1400 400 800 1000 - 1400 400 800 1000 -
Mains voltage 8 8 - - - 5.5 8 - - - 5.5690Vac 17 17 - - - 15 12 - - - 7.5
Control voltage 34 31 - - - 22 31 - - - 22230Vac 54 44 - - - 37 44 - - - 37
65 58 - - - 55 55 - - - 4572 72 - - - 55 66 - - - 55
104 85 - - - 75 80 - - - 75Digital inputs 130 105 - - - 90 99 - - - 90
voltage 156 145 - - - 132 130 - - - 9090-230Vac 170 170 - - - 160 134 - - - 132
248 210 - - - 200 203 - - - 200361 310 - - - 250 310 - - - 250390 390 - - - 355 344 - - - 315480 460 - - - 400 432 - - - 400610 580 - - - 560 488 - - - 400820 650 - - - 630 552 - - - 560
1180 950 - - - 900 950 - - - 9001375 1100 - - - 1000 1076 - - - 10001750 1400 - - - - 1400 - - - -
Remarks page 8- Motor kW ratings given in above table are for IEC, standard AC four poles motors. - Always check that motor rated current is less than the specifi ed rated current of the starter, for the specifi c application (Normal Duty or Heavy Duty)- Other control and digital inputs voltages are available. Please contact GE- Profi bus or DeviceNet options cannot be ordered separately. For those communication networks, please order the ASTAT XT with the required option built-in
remarks page 9- Motor HP ratings given in NEMA table are for standard AC four poles motors. - Always check that motor rated current is less than the specifi ed rated current of the starter, for the specifi c application (Light Duty, Normal Duty or Heavy Duty)- Remote mounting kit for keypad that includes cable (3m), remote keypad box, dummy cover, frame and brackets: - Frame A QTAKPADKIT1 169072- Frame B and others QTAKPADKIT2 169073
For the international version:- Frame A QTAKPADKIT1SG 129052- Frame B and others QTAKPADKIT2SG 129053
ASTAT XT
9
Order codes
NEMA ratings. Recommended unit type and motor ratingsLight Duty - NEMA 10 Normal Duty - NEMA 20 Heavy Duty - NEMA 30
Currentrating 230V 460V 575V Current
rating 230V 460V 575V Currentrating 230V 460V 575V Cat. No. Ref. No.
A HP HP HP A HP HP HP A HP HP HPMains voltage 8 2 5 - 8 2 5 - 8 2 5 - QT10008U21MS 169075
230-500VAC 17 5 10 - 17 5 10 - 12 3 7.5 - QT10017U21MS 16907634 10 25 - 31 10 20 - 31 10 20 - QT10031U21MS 16907754 20 40 - 44 15 30 - 44 15 30 - QT10044U21MS 16907865 20 50 - 58 20 40 - 55 20 40 - QT10058U21MS 16907972 25 50 - 72 25 50 - 66 20 50 - QT10072U21MS 169080
104 40 75 - 85 30 60 - 80 30 60 - QT10085U21MS 169081130 50 100 - 105 40 75 - 99 40 75 - QT10105U21MS 169082156 60 125 - 145 50 100 - 130 50 100 - QT10145U21MS 169083170 60 125 - 170 60 125 - 134 50 100 - QT10170U21MS 169084262 100 200 - 210 75 150 - 203 75 150 - QT10210U21MS 169085387 150 300 - 310 100 250 - 310 100 250 - QT10310U21MS 169086414 150 350 - 390 150 300 - 361 150 300 - QT10390U21MS 169087480 200 400 - 460 150 350 - 432 150 350 - QT10460U21MS 169088610 250 500 - 580 200 400 - 552 200 400 - QT10580U21MS 169089820 - - - 820 250 500 - 690 250 500 - QT10820U21MS 169090
Mains voltage 8 - 5 5 8 - 5 5 8 - 5 5 QT20008U21MS 169100460-600VAC 17 - 10 15 17 - 10 15 12 - 7.5 10 QT20017U21MS 169101
34 - 25 30 31 - 20 25 31 - 20 25 QT20031U21MS 16910254 - 40 50 44 - 30 40 44 - 30 40 QT20044U21MS 16910365 - 50 60 58 - 40 50 55 - 40 50 QT20058U21MS 16910472 - 50 60 72 - 50 60 66 - 50 60 QT20072U21MS 169105
104 - 75 100 85 - 60 75 80 - 60 75 QT20085U21MS 169106130 - 100 125 105 - 75 100 99 - 75 100 QT20105U21MS 169107156 - 125 150 145 - 100 150 130 - 100 125 QT20145U21MS 169108170 - 125 150 170 - 125 150 134 - 100 125 QT20170U21MS 169109262 - 200 250 210 - 150 200 203 - 150 200 QT20210U21MS 169110387 - 300 400 310 - 250 300 310 - 250 300 QT20310U21MS 169111414 - 350 400 390 - 300 400 361 - 300 300 QT20390U21MS 169112480 - 400 500 460 - 350 400 432 - 350 400 QT20460U21MS 169113610 - 500 - 580 - 400 400 552 - 400 500 QT20580U21MS 169114820 - - - 820 - 500 500 690 - 500 - QT20820U21MS 169115
Light Duty Normal Duty (IEC Class 10) Heavy DutyBuilt-in communication networkBuilt-in communication network International versionInternational version
ModbusModbus Profi bus DPProfi bus DP DeviceNetDeviceNet ModbusModbus Profi bus DPProfi bus DP DeviceNetDeviceNetQT___N21PS QT___N21DS QT___N21PSG QT___N21DSGQT___U21PS QT___U21DS QT___U21PSG QT___U21DSG
Cat. No. Ref. No. Ref. No. Ref. No. Cat. No. Ref. No. Ref. No. Ref. No.
QT10008U21MS 169075 169214 169314 QT10008U21MSG 129213 120954 817850QT10017U21MS 169076 169215 169315 QT10017U21MSG 129214 120957 817851QT10031U21MS 169077 169216 169316 QT10031U21MSG 129215 120958 817852QT10044U21MS 169078 169217 169317 QT10044U21MSG 129216 120959 817853QT10058U21MS 169079 169218 169318 QT10058U21MSG 129217 120960 817854QT10072U21MS 169080 169219 169319 QT10072U21MSG 129218 120961 817855QT10085U21MS 169081 169220 169320 QT10085U21MSG 129219 120962 817856QT10105U21MS 169082 169221 169321 QT10105U21MSG 129220 120963 817857QT10145U21MS 169083 169222 169322 QT10145U21MSG 129221 120964 817858QT10170U21MS 169084 169223 169323 QT10170U21MSG 129222 120965 817859QT10210U21MS 169085 169224 169324 QT10210U21MSG 129223 120966 817860QT10310U21MS 169086 169225 169325 QT10310U21MSG 129224 120967 817861QT10390U21MS 169087 169226 169326 QT10390U21MSG 129225 120968 817862QT10460N21MS 169094 169233 169333 QT10460N21MSG 129229 120972 817863QT10460U21MS 169088 169227 169327 QT10460U21MSG 129226 120969 817864QT10580N21MS 169095 169234 169334 QT10580N21MSG 129230 120973 817865QT10580U21MS 169089 169228 169328 QT10580U21MSG 129227 120970 817866QT10650N21MS 169096 169235 169335 QT10650N21MSG 129231 120974 817867QT10820U21MS 169090 169229 169329 QT10820U21MSG 129228 120971 817868QT10950N21MS 169097 169236 169336 QT10950N21MSG 129232 120975 817869QT11100N21MS 169098 169237 169337 QT11100N21MSG 129233 120976 817870QT11400N21MS 169099 169238 169338 QT11400N21MSG 129234 120977 817871
QT30008N21MS 169119 169490 169573 QT30008N21MSG 129257 129511 817872QT30017N21MS 169120 169491 169574 QT30017N21MSG 129258 129512 817873QT30031N21MS 169121 169492 169575 QT30031N21MSG 129259 129513 817874QT30044N21MS 169122 169493 169576 QT30044N21MSG 129260 129539 817875QT30058N21MS 169123 169494 169577 QT30058N21MSG 129261 129540 817876QT30072N21MS 169124 169495 169578 QT30072N21MSG 129262 129541 817877QT30085N21MS 169125 169496 169579 QT30085N21MSG 129263 129542 817878QT30105N21MS 169126 169497 169580 QT30105N21MSG 129264 129543 817879QT30145N21MS 169127 169498 169581 QT30145N21MSG 129265 129544 817880QT30170N21MS 169128 169499 169582 QT30170N21MSG 129266 129545 817881QT30210N21MS 169129 169500 169583 QT30210N21MSG 129267 129546 817882QT30310N21MS 169130 169501 169584 QT30310N21MSG 129268 129547 817883QT30390N21MS 169131 169502 169585 QT30390N21MSG 129269 129548 817884QT30460N21MS 169132 169503 169586 QT30460N21MSG 129270 129549 817885QT30580N21MS 169133 169504 169587 QT30580N21MSG 129271 129550 817886QT30650N21MS 169134 169505 169588 QT30650N21MSG 129272 129551 817887QT30950N21MS 169135 169506 169589 QT30950N21MSG 129273 129552 817888QT31100N21MS 169136 169507 169590 QT31100N21MSG 129274 129553 817889QT31400N21MS 169137 169508 169591 QT31400N21MSG 129275 129554 817890
ASTAT XT
10
Dig
ital s
oft s
tart
ers
Unit confi guration
(1) - ASTAT XT up to 600V, and up to 170A (Cat Numbers up to QT10170_ or up to QT20170) are always cUL certifi ed. Option “N” not available- Units QT2, from QT20008_, up to QT20820_ are always cUL certifi ed. Option “N” not available.- Units QT1, or QT2 from QTx0950_ up to QTx1400 are not UL certifi ed. Option “U” not available.- Units QT3__, rated to 690V, are not UL certifi ed. Option “U” not available
(2) ASTAT XT standard control voltage confi guration is option 2, voltage 230VAC, +10%, -15%(3) ASTAT XT standard confi guration for inputs is option 1, voltage 90-230VAC, +10%, -15%
OPTIONS:- Remote mounting kit for keypad that includes cable (3m), remote keypad box, dummy cover, frame and brackets: - Frame A QTAKPADKIT1 169072- Frame B and others QTAKPADKIT2 169073
For the international version:- Frame A QTAKPADKIT1SG 129052- Frame B and others QTAKPADKIT2SG 129053
QT 1 0008 U 2 1 M SASTAT XT range
Digital inputs, voltage(3)
Communications
Main voltage
Current ratings
UL certification(1)
Control voltage(2)
230-500V460-600V690V
123
StandardProfibusDeviceNet
MPD
ULnon-UL
UN
110VAC230VAC
12
90-230VAC24VDC
12
Versions StandardInternational
SSG
ASTAT XT
11
Technical data
Technical data
RatingsMain voltage 3ph AC supply 230 to 500VAC +10%, -15% for QT1xxx units
460 to 600VAC +10%, -15% for QT2xxx units690VAC +10%, -15% for QT3xxx units
Starter current rating for 3ph AC motors From 8A up to 1400A. Motor current rating 3ph Induction motors Motor rated current from 50% to 100% of starter currentControl voltage 1ph AC supply 230VAC, +10, -15%, 50/60Hz or
110VAC, +10, -15%, 50/60Hz (optional)Frequency range 50/60Hz systems Wide from 45Hz to 65Hz. Auto-tracking frequency rangeDigital inputs voltage 90-230Vac, +10 -15%, 50/60Hz
24Vdc, +10%, -15% (optional)
Control specifi cationsControl system Digital control with microcontroller.
Starting ramp, with progressive increase in voltage and current limitationOperation mode In-Line (three wires) or Inside-Delta (six wires) of the motorRun operation Soft Start and Soft stop by multiple choices, including torque control both at start or Stop phasesOperator interface By LCD display, keypad and Indication LEDs
Display: LCD with two rows, 16 characters each Type: Multilanguage, dip-switch selectable for English, Italian, Spanish and German Keys: Six keys, Mode, reset, Set, Select and Up / Down LEDs: ON, Start, Run, Soft Stop, Stop, Save / Slow Speed, Dual Set / Reverse and Fault
Initial voltage 10-50% Un. Up to 80% with expanded settings functionStarting current 100-400% In. Can be extended up to 500%, by using extended settingsAcceleration ramp time 1-30 sec. Can be extended up to 90 sec, by using extended settingsDeceleration ramp time 1-30 sec. Can be extended up to 90 sec, by using extended settingsCurrent limitation 100-400% of motor rated current. Can be extended up to 500% by using extended settingsBypass By external contactor while motor is full protected by ASTAT XTMonitoring Motor current, line voltage, motor thermistor resistance, test and maintenance and statistics
Environmental conditionsOperating temperature -10°C up to 60ºC, with current derating by 2.5% per °C, from 50ºCStorage temperature -20ºC up to 70ºCMaximum altitude Up to 1000 mts. Ask your dealed for installation at higher altitudeHumidity 95% at 50ºC or 98% at 45ºCProtection degree IP20 for units up to 72A, IP00 for units from 85A up to 1400APollution degree Class 3
StandardsGlobal standards CE for the full trange. UL, cUL for specifi ed units up to 820AEMC emissions EN 61000-6-4 CISPR 11 Class AImmunity EN 61000-6-2 ESD 8KV air, IEC 801-2;
Electric RF fi eld 10 V/m, 20-1000Mhz, IEC 801-3Fast transients 2KV, IEC 801-4
Safety EN 600947-1 Related to safety requirements. UL508C
ASTAT XT
12
Dig
ital s
oft s
tart
ers
Functions
Available standard functionsSoft start and soft stop ASTAT XT is provided with a soft start and soft stop features, including fi ve independent acceleration and
decelertaion curve models.The factory default curve is used for general purpose, other three are used for pump control and the last one for torque control.
Pump control Specifi c function for pump control, that avoids overpressure in the system at the end of acceleration phase and suppresses the hammering at stopping phase.
Torque control Provides a smoth time controlled torque ramp acelleration and deceleration, with linear deceleration of the torqueresulting in a close to linear speed deceleration, thus eliminating stall conditions.
In line / Inside delta ASTAT XT allows either traditional Line operation or Inside Delta operation.When the ASTAT XT is installed to operate Inside Delta, the individual phases of the starter are connected in series with the individual motor windings (six wiring connections like the Start-Delta starters), thus reducing the current x1.73, and allowing the use of a much smaller starter (x1.5 less than motor rated current).
Bypass ASTAT XT allows bypass operation using an external contactor, controlled ON/OFF by starter function EOR(End Of Ramp).The starter is provided with three dedicated power terminals to facilitate wirings to the bypass contactor. ASTAT XT protections to motor are enabled, even in bypass.
Kick start This function allows to start high friction loadsthat require high starting torque for a short period of time. When this function is enabled, a pulse of 80% Un during an adjustable time from 0 to 1sec is given to the motor. After this pulse the output voltage is ramping down to starting voltage setting, before ramping up again to full voltage.
End of ramp Detects end of acceleration and outputs a signal by an dry relay contact. This signal can be delayed by an adjustable timer from 0-120 sec.
Lock-out Allows to control the number of startings into a period of time, then protecting both motor and ASTAT.Dual settings By this function, ASTAT XT is able to control a secondary motor Dual setting of Starting voltage, Starting current,
Current limit, Ramp up, Ramp down and Motor current parameters can be selected by using one of the programmable ASTAT XT inputs.
Energy saving Activated when the motor has a light load for extended periods of time, then reducing the output voltage level and decreasing the reactive current and motor copper/Iron losses.This function can be enabled or disabled by dedicated parameters in ASTAT XT.
Slow speed Function that allows the motor to run at 1/6 constant rated speed, for a short period of time of maximum 30sec.This function supports forward and reverse operation.
Auto reset This function allows the ASTAT XT automatic recover after a fault caused by Undervoltage, Undercurrent orPhase lost. Auto-reset can be programed up to maximum 10 attempts.
Cooling fan control Allows thre method of control for the ASTAT´s built-in cooling fans. - Continuous operation- Controlled by an external Input- Automatically OFF controlled, after fi ve minutes ASTAT XT is stopped
Generator supply This is a specifi c function useful when the starter is powered from a diesel generator rather than fromcommercial power supply. The function is enabled by an internal Dip switch, and helps to minimize the negative effects caused by the generator´s voltage fl uctuations during starting.
Keypad lock This function is enabled by means of starter´s internal dipswitch, then locking the keypad.This is usefull to prevent undesired parameter modifi cations.
Built-in communications ASTAT XT includes a ModBus RTU communications protocol. Communications are carried out through a half duplex RS485 port, with maximum baudrate of 9600, supporting up to 247 stations.
Statistic data ASTAT XT records useful data for maintenance and start up- Last 10 trip events- Statistical data like number of starts, number of trip events and elapsed RUN time.- Last trip data information of motor current, starting current and acceleration time.
Motor and starter protectionOverload Trips the ASTAT XT when current exceeds the overload trip level according IEC Class 10, 20 or NEMA 10, 20, 30.Motor thermistor Trips when motor thermistor resinstance decreases below trip level set ASTAT XT allows both PTC or NTC sensors,
with adjustable trip level.Too many starts Trips if the number of starts, during duty cycle time exceeds the preset number.Long start time Trips if output voltage does not reach rated voltage at the preset Max. Start time.O/C JAM fault Trips under the following conditions:
- Instantaneously when current exceeds 8.5 x ASTAT XT current- During starting when current exceeds 8.5 x motor current- During running when current exceeds 200-850% of motor currentO/C JAM has a programmable triping delay of 0-5 seconds
Undercurrent Trips when line current drops below the preset level for the preset time.Undervoltage Trips when line voltage drops below the preset level for the preset time.Overvoltage Trips when line voltage increases above a preset level for a preset time.Phase loss Trips if 1 or 2 phases are lost.Frequency loss Trips if frequency is not in the range of 40-66.6Hz.Phase sequence Trips if line phase sequence is wrong.Slow speed time Trips when operating at slow speed for extended periodsWrong connection Trips the ASTAT XT when one or more motor phases is not properly connected to ASTAT XT’s load terminals
or if there is an internal disconnection in the motor winding.Shorted SCR Trips and prevents starting if any SCR is short-circuited or when motor windings are shorted.Over temperature Heat-sink over-temperature. Trips the ASTAT XT when the heat-sink temperature rises above 85°C.External fault Trips the ASTAT XT when a NO contact between terminals 19-21 closes for over two seconds.Wrong parameters Parameters not transferred from RAM to EEPROM or vice versa.OC or wrong CON Trips when the ASTAT XT is connected inside Delta and wrong connection or overcurrent is detected.
ASTAT XT
13
Overload protections
Overload protections - Thermal characteristicsThe ASTAT XT allows motor protection according IEC Class 10 or Class 20 and NEMA 10, 20 or 30.User free selectable by ASTAT internal dedicated parameter.
IEC Class 10
Sec.
Multiples of motor FLA Rating In1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10000
1000
100
10
1
COLD
HOT
IEC Class 20
Sec.
Multiples of motor FLA Rating In1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10000
1000
100
10
1
COLD
HOT
NEMA 10
Sec.
Multiples of motor FLA Rating In1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10000
1000
100
10
1
COLD
HOT
NEMA 20
Sec.
Multiples of motor FLA Rating In1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10000
1000
100
10
1
COLD
HOT
NEMA 30
Sec.
Multiples of motor FLA Rating In1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10000
1000
100
10
1
COLD
HOT
Maximum number starting /hourRamp time
10s 20s 30s
StartingcurrentI/In (1)
2 24 12 8
3 16 8 5
4 12 6 4
(1) In= rated current of ASTAT XT in the specifi ed class IEC/NEMA
Light Duty
ASTAT XT
14
Dig
ital s
oft s
tart
ers
I/O Wiring, basic scheme
1L1
A
3L2
B
5L3
C
L
FControl supply
Mai
n su
pply
N
4
5
6
7
8
9
19
21
Stop
Soft Stop
Start
Energy save/Slow speed/reset
D.Adj./Reversing/Reset
Common
External fault input
Neutral
Ground Grd
CT1
CT2
2T1
4T2
6T3
M3ph
10
11
12
13
14
15
16
17
18
SG
D-
D+
InmediateRUN
Power supply
Signal CAN-H
Drain
Signal CAN-L
Power supply
Dev
iceN
et (o
ptio
n)V-
CL
Dr
CH
V+
Fault relay
EOR (End Of Ramp) relay
RS485 port
Profibus(option)
28
29
30Ground
T2
T1 31
32
(-)
(+)Analogue output
Thermistor input
Note: Profi bus or DeviceNet options cannot be ordered separately.For those communication networks, please order the ASTAT XT with the required option built-in (see pages 8 and 9).
ASTAT XT
15
I/O term
inal board
I/O terminal board specifi cations
Power I/O terminals
Terminals Function Description
1L1, 3L2, 5L3 Mains input 3ph Input voltage according ASTAT XT main voltage option rating(Option 1, QT1_) 230-500VAC, +10%/-15% 50/60Hz(Option 2, QT2_) 460-600VAC, +10%/-15% 50/60Hz(Option 3, QT3_) 690VAC, +10%/-15% 50/60Hz
2T1, 4T2, 6T3 Output to motor Power output terminals to 3ph AC motorA, B, C Bypass Bypass terminals for external bypass contactorG Ground ASTAT XT, ground connection
Control power supplyL, N Control supply 110VAC or 220VAC, according ASTAT XT control voltage ratingF Fan control Cooling fan external control, together with jumper J1
Control voltage and fan consumption VA:QTx0008 to QTx0031: No fan. Total consumption: 150VAQTx0044 to QTx0072: Fan 35 VA. Total consumption 185VAQTx0085 to QTx0170: Fan 60 VA. Total consumption 210VAQTx0210 to QTx0390: Fans 105VA. Total consumption 255VAQTx0390 to QTx 1400A : Fans 150VA. Total consumption 300VA
Digital inputs4 Stop Dedicated input to Stop5 Soft Stop Dedicated input to Soft Stop6 Start Dedicated input to Start7 Progammable inputs Programmable to functions Energy saving, slow speed and reset8 Progammable inputs Programmable to functions Dual set, Reverse and Reset9 Common Common terminal for digital inputs from 4, 5, 6, 7 and 8
Operating voltage of digital inputs from 4 to 9Digital Input hardware is operated according either of below ordered voltage ratings (Option 1, standard) from 90 to 230VAC +10%, 50/60Hz(Option 2, optional) 24VDC +10%/ -15%
Other inputs19, 21 External fault Requires a free voltage relay contact, to detect external fault21 Neutral This terminal may be connected to mains neutral when available28, 29 Motor thermistor PTC or NTC programable input for motor thermistor protection
The input can be enabled or disabled, and programmed at desired trip level resistance
Digital outputs10, 11, 12 RUN Run relay with NO and NC dry contact. Programmable ON delay13, 14, 15 FAULT Fault to ON or Fault to OFF programmable function 16, 17, 18 EOR End of ramp relay. Programmable ON delay
Relay outputs ratingsMax rating: 8A, 250VAC, 2000VA max
Analogue output31, 32 Current output Range 0 to 2xIn. Programmable 0-10VDC, 0-20mA or 4-20mA. 30 Ground Ground terminal for analogue output
CommunicationsD+, D-, SG RS485 terminals RS485 communication port, half duplex for ModBus protocol
Baudrate 1200, 2400, 4800, 9600 BPSD-9 connector Profi bus port Optional Profi bus communications portV+, CL, Dr, CH, V- DeviceNet terminals Optional Devicenet communications port
ASTAT XT
16
Dig
ital s
oft s
tart
ers
Application wiring diagrams
Basic diagram without line contactor(1)
Basic diagram without line contactor(1)
Remarks1. Check coordination tables for proper selection of breaker and line contactor.2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.4. In spite of ASTAT XT can operate without line contactor, the use of a line contactor will increase the operation safety. Anyway provide a way to
switch off the breaker in case of an emergency.5. Line and bypass contactors should be dimensioned according AC1 category.
A1
L1
Q11
2
3
4
5
6
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3L2
4T2
L3
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
0 STOPI START
SOFT
STO
P 5
STAR
T 6
18
EORR
17 16 15
FAULTR
14 13 12
RUNR
11 10
A1
L1
Q11
2
3
4
5
6
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3L2
4T2
L3
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
SOFT
STO
P 5
0 STOPI START
STAR
T 6
18
EORR
17 16 15
FAULTR
14 13 12
RUNR
11 10
With Soft Start and Soft Stop by permanent command control
With Soft Start and coast to Stop by permanent command control
(1) Schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
ASTAT XT
17
Wiring diagram
s
Remarks1. Check coordination tables for proper selection of breaker and line contactor.2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.4. In spite of ASTAT XT can operate without line contactor, the use of a line contactor will increase the operation safety. Anyway provide a way to
switch off the breaker in case of an emergency.5. Line and bypass contactors should be dimensioned according AC1 category.
Application wiring diagrams
Basic diagram without line contactor(1)
Basic diagram with line contactor(1)
A1
L1
Q11
2
3
4
5
6
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3L2
4T2
L3
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
STOP
SOFT
STO
P 5
START
STAR
T 6
18
EORR
17 16 15
FAULTR
14 13 12
RUNR
11 10
A1
L1
Q11
2
3
4
5
6
KM1 1
2.8
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3
4
3L2
4T2
L3
5
6
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
K121
24
STO
P 4
SOFT
STO
P 5
STAR
T 6
A1FAULTRELAY
18
Q1 13
14.2
STOP
START
14
15
K1A1
A2
EORR
17 16
K111
14
A1
15
RUNRELAY
FAULTR
14
KM113
14
10
12
KM1A1
A2
13 12
K131
34
RUNR
11 10
(1) Schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
With Soft Start and coast to Stop by push-buttons control
With Soft Start and Soft Stop by push-buttons control
ASTAT XT
18
Dig
ital s
oft s
tart
ers
Basic diagram with line contactor(1)
Basic diagram with line and bypass contactors(1)
Remarks1. Check coordination tables for proper selection of breaker and line contactor.2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.4. Line and bypass contactors should be dimensioned according AC1 category.
A1
L1
Q11
2
3
4
5
6
KM1 1
2.8
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3
43L
24T
2
L3
5
65L
36T
3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
K121
24
SOFT
STO
P 5
STAR
T 6
A1FAULTRELAY
18
Q1 13
14.2
STOP
START
14
15
K1A1
A2
EORR
17 16
K111
14
A1
15
RUNRELAY
FAULTR
14
KM113
14
10
12
KM1A1
A2
13 12
K131
34
RUNR
11 10
BPC
KM2 1
2=8/1.93
4
5
6
A1 A B C
L1
Q11
2
3
4
5
6
KM1 1
2=8/1.8
F1
1L1
2T1
M3 ~
U1 V1 W1
L2
3
4
3L2
4T2
L3
5
6
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
K121
24
SOFT
STO
P 5
STAR
T 6
A1
FAULTRELAY
18
Q113
14
STOP
START
14
15
K1A1
A2
EORR
17 16
K111
14
A1
15
RUNRELAY
FAULTR
14
KM113
14
10
12
KM1A1
A2
13 12
K131
34
RUNR
11 10
A1
EOARELAY
16
18
KM2A1
A2
(1) Above schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
Application wiring diagrams
With Soft Start and Soft Stop by push-buttons control
With Soft Start and Soft Stop by push-buttons control
ASTAT XT
19
Wiring diagram
s
Application wiring diagrams
Basic diagram in “Inside Delta” confi guration with line and bypass contactors(1)
Remarks1. Check coordination tables for proper selection of breaker and line contactor.2. Control voltage and control input voltage are from same source in above example. Please check manuals if you have different sources for
control voltage and control input voltage.3. Semiconductor fuses “F” are only required for Type 2 coordination. Please check coordination tables.4. Wrong connection of the motor, or the ASTAT XT when it is inside-delta connected may seriously damage the motor or the ASTAT XT.
Please check additional details given in the ASTAT XT instruction manual.5. Line and bypass contactors should be dimensioned according AC1 category.
KM31
2
3
4
5
6BPC
KM21
2
3
4
5
6
A1A B C
L1
Q11
2
3
4
5
6
KM11
2
F1
1L1
2T1
U1
U2
V1
V2
W1
PE
W2
L2
3
43L
24T
2
L3
5
6
5L3
6T3
Q2
1
3
2
4
GND
T1
Q3
1 2
N
COM
MO
N 9 L
STO
P 4
K121
24
SOFT
STO
P 5
STAR
T 6
A1FAULTRELAY
18
Q113
14
STOP
START
14
15
K1A1
A2
EORR
17 16
K111
14
A1
15
RUNRELAY
FAULTR
14
KM113
14
10
12
KM1A1
A2
13 12
K131
34
KM3A1
A2
RUNR
11 10
A1EOA
RELAY
16
18
KM2A1
A2
(1) Above schemes are given for information purposes. Add additional emergency safety stop, if it is required for your application.
With Soft Start and Soft Stop by push-buttons control
ASTAT XT
20
Dig
ital s
oft s
tart
ers
Type 1 coordination with GE circuit breakers Record PlusSoft starter Record Plus circuit breakers
Rated current Overload current Frame type O/L type Breaking capacityA A kA
8 16 FD63 LTMD 16 6517 40 FD63 LTMD 40 6531 50 FD63 LTMD 50 6544 63 FD160 LTMD 63 6558 80 FD160 LTMD 80 6572 80 FE160 LTMD 80 6585 125 FE160 SMR1-125 65
105 160 FE160 SMR1-160 65145 160 FE160 LTMD 160 65170 250 FE250 LTMD 250 65210 250 FE250 LTMD 250 65310 400 FG630 SMR1-400 65390 400 FG400 SMR1-400 65460 630 FG630 SMR1-630 65580 630 FG630 SMR1-630 65650 800 FK800 SMR1s-800 50820 1250 FK1250 SMR1s-1250 50950 1250 FK1250 SMR1s-1250 50
1100 1250 FK1250 SMR1s-1250 501400 1600 FK1600 SMR1s-1600 50
Type 1 coordination with Type aM Siba fusesSoft starter Siba aM fuses
Rated current Rated current Part No. Size Un Type Breaking capacityA A kA
8 16 20 477 08.16 0 690 aM 12017 20 20 477 08.20 0 690 aM 12031 35 20 477 08.35 0 690 aM 12044 50 20 477 08.50 0 690 aM 12058 80 20 209 08.80 0 690 aM 12072 100 20 209 08.100 0 690 aM 12085 125 20 209 08.125 0 690 aM 120
105 160 20 210 08.160 0 690 aM 120145 200 20 211 08.200 1 690 aM 120170 200 20 211 08.200 1 690 aM 120210 250 20 211 08.250 1 690 aM 120310 400 20 212 08.400 2 690 aM 120390 500 20 213 08.500 3 690 aM 120460 630 20 213 08.630 3 690 aM 120580 800 20 225 08.800 4 690 aM 120650 800 20 225 08.800 4 690 aM 120820 1000 20 225 08.1000 4 690 aM 120950 2x630 2x20 213 08.630 2x3 690 aM 120
1100 2x800 2x20 225 08.800 2x4 690 aM 1201400 2x800 2x20 225 08.800 2x4 690 aM 120
Coordination Type 1
ASTAT XT
21
Coordination tables
Type 2 coordination with Bussman fusesSoft starter Bussman fuses DIN 43620
Rated current A2 sec Rated current Part No. Size Un Type Breaking capacityA A kA
8 400 40 170M3808D 1 690 H.S.D.I. 20017 5000 63 170M3810D 1 690 H.S.D.I. 20031 10000 125 170M3813D 1 690 H.S.D.I. 20044 12000 160 170M3814D 1 690 H.S.D.I. 20058 15000 160 170M3814D 1 690 H.S.D.I. 20072 18000 200 170M3815D 1 690 H.S.D.I. 20085 50000 250 170M3816D 1 690 H.S.D.I. 200
105 60000 315 170M3817D 1 690 H.S.D.I. 200145 10000 315 170M3817D 1 690 H.S.D.I. 200170 140000 400 170M3819D 1 690 H.S.D.I. 200210 200000 500 170M4864D 1 690 H.S.D.I. 200310 600000 500 170M4864D 1 690 H.S.D.I. 200390 700000 800 170M5814D 2 690 H.S.D.I. 200460 800000 900 170M6813D 3 690 H.S.D.I. 200580 1200000 1000 170M6814D 3 690 H.S.D.I. 200650 2000000 2x800 2x170M5814D 2x2 690 H.S.D.I. 200820 2000000 2x800 2x170M5814D 2x2 690 H.S.D.I. 200950 4500000 2x1000 2x170M5816D 2x2 690 H.S.D.I. 200
1100 4500000 2x1100 2x170M6892D 2x2 690 H.S.D.I. 2001400 6500000 2x1400 2x170M8555D 2x3 690 H.S.D.I. 200
Coordination Type 2
For Type 2 coordinationUse fuses for semiconductor protection to protect the ASTAT XT soft starter from a short circuit . Fuses for semiconductor protection give excellent results because they have low I²t values and high interruption ratings.
Recommended fuse selection procedureFuse rated voltageChoose minimum fuse rated voltage which is above the rated voltage of the mains.Fuse rated currentSelect a fuse which is able to carry 8 times the rated ASTAT XT soft starter current for 30 seconds (this is double the maximum ASTAT XT soft starter current for the maximum acceleration time).Fuse I²tVerify that the I²t value of the fuse is less than or equal to the I²t value of the thyristor in the ASTAT XT soft starter as shown in the table.
ASTAT XT
22
Dig
ital s
oft s
tart
ers
Dimensions and weights
1L1, 3L2, 5L3
2T1, 4T2, 6T3
BypassA B C
GND M5
298
310
130153
7
D1D2
158
BypassA B C
GND M6
365
385
200274
9
278104.5 65.5 65.5
O 8.5
71.8 32.7 32.8 32.7 32.8
137 4
117 4
243
1535
5
188
201L1, 3L2, 5L3
2T1, 4T2, 6T3
Cat. No.: QTx0008U_ , QTx0017U_ , QTx0031U_ , QTx0044U_ , QTx0058U_ , QTx0072U_
Cat. No.: QTx0085U_ , QTx0105U_
Power terminal size (mm²)
Cat. No Dimensions Input Bypass Output Weight (kg)
D1 D2 1L1, 3L2, 5L3 A, B, C 2T1, 4T2, 6T3QTx0008U__ 160 182.5 16 16 16 4.2QTx0017U__ 160 182.5 16 16 16 4.2QTx0031U__ 160 182.5 16 16 16 5.3QTx0044U__ 207 229.5 16 16 35 6.7QTx0058U__ 207 229.5 16 16 35 6.7QTx0072U__ 207 229.5 35 35 35 6.7
Cat. No. Weight (kg)QTx0085U__ 15.2QTx0105U__ 15.2
IEC and UL certifi ed units
IEC and UL certifi ed units
ASTAT XT
23
Dim
ensions
Dimensions and weights
Cat. No. Dimensions Weight (kg)
H1 H2 H3 H4QTx0210U__ 455 425 414 427 32.7QTx0310U__ 455 425 414 427 32.7QTx0390U__ 455 425 414 427 32.7QTx0460N__ 555 525 528.5 527 58.4
Cat. No.: QTx0210U_ , QTx0310U_ , QTx0390U_ , QTx0460N_
By PassA B C
2T1, 4T2, 6T3
GND M8
H1
380
H3
H4
9.5
125 125 43.5
43.5 125 125160
54.2 5182.2 5
182.2 5299.4
O 10 30
H2
15
1L1, 3L2, 5L3
Cat. No.: QTx0145U_ , QTx0170U_
Cat. No. Weight (kg)QTx0145U__ 15.2QTx0170U__ 15.2
1L1, 3L2
2T1, 4T2, 6T3
BypassA B C
GND M6
365
385
200274
9
278
244
66.8 32.7 32.8 32.7 32.8 32.7
99.5 65.5 65.5188
137 4
117 4
1535
5
O 8.5
20
IEC and UL certifi ed units
IEC and UL certifi ed units
This 460A frame is only IEC certifi ed.Please consult dimensions of 460A frame for UL in page 26
ASTAT XT
24
Dig
ital s
oft s
tart
ers
Cat. No.: QTx0580N_
BypassA B C
GND M8
50.5150150180
9.5
2061
5
50.5 150 150
470
655
O 13.5
171.7 5221.7 5
542
216.7 5
309.4
528
615
600
40
1L1, 3L2, 5L3
2T1, 4T2, 6T3
Cat. No. Weight (kg)QTx0580U__ 63.2Non-UL certifi ed unit
Cat. No.: QTx0650N_
Cat. No. Weight (kg)QTx0650N__ 64.8Non-UL certifi ed units
BypassA B C
GND M8
50.5150150180
9.5
2061
5
50.5 150 150
470
655
O 13.5
171.7 5221.7 5
542
216.7 5
309.4
528
615
600
40
1L1, 3L2, 5L3
2T1, 4T2, 6T3
Dimensions and weights
ASTAT XT
25
Dim
ensions
Dimensions and weights
Cat. No.: QTx0950N_
Cat. No.: QTx1100N_ , QTx1400N
GNDM8
O10.5
195 195
625
626.
5
640
234.5
292.4
9.5
5011410
24511410
44011410
659
17.5 45
74.7 80
2045
2T1, 4T2, 6T3
1L1, 3L2, 5L3
Cat. No. Weight (kg)QTx1100N__ 169.8QTx1400N__ 175.5
Cat. No. Weight (kg)QTx0950N__ 86.7
O10.5
O10.5
O9
GND M10
191.5 230 230
131.5 230 230
20
45
45
786
8
9
165
1100
20
45
45
80
230 230
376.8
266 10
94 10
2971
2
23023023016.5
723
80
1L1, 3L2, 5L3
2T1, 4T2, 6T3
Non-UL certifi ed unit
Non-UL certifi ed unit
Remarks1. This unit must be operated with a bypass contactor2. Add space for current transformers (supplied separately from the main unit)
and bus bars for preparation for bypassApproximate current transformers dimensions: W=240mm, H=130mm, D=90mm
Remarks1. Units must be operated with a bypass contactor2. Add space for current transformers (supplied separately from main unit)
and bus bars for preparation for bypassApproximate current transformers dimensions: W=240mm, H=130mm, D=90mm. (for 1100A unit , Cat. No. QTx1100N__ W=270mm, H=155mm, D=90mm. (for 1400A unit , Cat. No. QTx1400N__
ASTAT XT
26
Dig
ital s
oft s
tart
ers
Cat. No.: QTx0460U_
Cat. No. Weight (kg)QTx0460U__ 61.8
1L1, 3L2, 5L3
O10
BypassA B C
GNDM8
195 195625
8065130651306513
25
25
50
626.
5
640
659
818
234.5292.4
74.2 6
155.2 6
9.5
13
25
25
2T1, 4T2, 6T3
UL certifi ed unit
Dimensions and weights
Cat. No.: QTx0580U_ , QTx0820U_
Cat. No. Weight (kg)QTx0580U__ 69.5QTx0820U__ 69.5
GNDM8
BypassA B C
195 195625
73.5
50
626.
5
640
659
234.5292.4
155.2 6
9.5
13
25
25
818
771951951325
25
74.2 6
1L1, 3L2, 5L32T1, 4T2, 6T3
UL certifi ed unit
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes
ASTAT
28
Num
eric
al in
dex
ASTAT
Numerical index
By reference number By catalogue numberRef. No. Typbez. Pag.
120000120881 QA02P008S 2120882 QA02P017S 2120883 QA02P022S 2120884 QA02P031S 2120885 QA02P044S 2120886 QA02P058S 2120892 QA12P008S 2120893 QA12P017S 2120894 QA12P022S 2120895 QA12P031S 2120896 QA12P044S 2120897 QA12P058S 2120898 QA22P008S 2120899 QA22P017S 2120900 QA22P022S 2120901 QA22P031S 2120902 QA22P044S 2120903 QA22P058S 2120904 QA32P008S 2120905 QA32P017S 2120906 QA32P022S 2120907 QA32P031S 2120908 QA32P044S 2120909 QA32P058S 2120910 QAOPTDIN 2129000129213 QT10008U21MSG 9129214 QT10017U21MSG 9129215 QT10031U21MSG 9129216 QT10044U21MSG 9129217 QT10058U21MSG 9129218 QT10072U21MSG 9129219 QT10085U21MSG 9129220 QT10105U21MSG 9129221 QT10145U21MSG 9129222 QT10170U21MSG 9129223 QT10210U21MSG 9129224 QT10310U21MSG 9129225 QT10390U21MSG 9129226 QT10460U21MSG 9129227 QT10580U21MSG 9129228 QT10820U21MSG 9129229 QT10460N21MSG 9129230 QT10580N21MSG 9129231 QT10650N21MSG 9129232 QT10950N21MSG 9129233 QT11100N21MSG 9129234 QT11400N21MSG 9129257 QT30008N21MSG 9129258 QT30017N21MSG 9129259 QT30031N21MSG 9129260 QT30044N21MSG 9129261 QT30058N21MSG 9129262 QT30072N21MSG 9129263 QT30085N21MSG 9129264 QT30105N21MSG 9129265 QT30145N21MSG 9129266 QT30170N21MSG 9129267 QT30210N21MSG 9129268 QT30310N21MSG 9129269 QT30390N21MSG 9129270 QT30460N21MSG 9129271 QT30580N21MSG 9129272 QT30650N21MSG 9129273 QT30950N21MSG 9129274 QT31100N21MSG 9129275 QT31400N21MSG 9169000169075 QT10008U21MS 9169076 QT10017U21MS 9169077 QT10031U21MS 9169078 QT10044U21MS 9169079 QT10058U21MS 9169080 QT10072U21MS 9169081 QT10085U21MS 9169082 QT10105U21MS 9169083 QT10145U21MS 9169084 QT10170U21MS 9169085 QT10210U21MS 9169086 QT10310U21MS 9169087 QT10390U21MS 9
Ref. No. Typbez. Pag.
169088 QT10460U21MS 9169089 QT10580U21MS 9169090 QT10820U21MS 9169094 QT10460N21MS 9169095 QT10580N21MS 9169096 QT10650N21MS 9169097 QT10950N21MS 9169098 QT11100N21MS 9169099 QT11400N21MS 9169100 QT20008U21MS 9169101 QT20017U21MS 9169102 QT20031U21MS 9169103 QT20044U21MS 9169104 QT20058U21MS 9169105 QT20072U21MS 9169106 QT20085U21MS 9169107 QT20105U21MS 9169108 QT20145U21MS 9169109 QT20170U21MS 9169110 QT20210U21MS 9169111 QT20310U21MS 9169112 QT20390U21MS 9169113 QT20460U21MS 9169114 QT20580U21MS 9169115 QT20820U21MS 9169119 QT30008N21MS 9169120 QT30017N21MS 9169121 QT30031N21MS 9169122 QT30044N21MS 9169123 QT30058N21MS 9169124 QT30072N21MS 9169125 QT30085N21MS 9169126 QT30105N21MS 9169127 QT30145N21MS 9169128 QT30170N21MS 9169129 QT30210N21MS 9169130 QT30310N21MS 9169131 QT30390N21MS 9169132 QT30460N21MS 9169133 QT30580N21MS 9169134 QT30650N21MS 9169135 QT30950N21MS 9169136 QT31100N21MS 9169137 QT31400N21MS 9
Cat. No. Ref. No. Pag.
QA...QA02P008S 120881 2QA02P017S 120882 2QA02P022S 120883 2QA02P031S 120884 2QA02P044S 120885 2QA02P058S 120886 2QA12P008S 120892 2QA12P017S 120893 2QA12P022S 120894 2QA12P031S 120895 2QA12P044S 120896 2QA12P058S 120897 2QA22P008S 120898 2QA22P017S 120899 2QA22P022S 120900 2QA22P031S 120901 2QA22P044S 120902 2QA22P058S 120903 2QA32P008S 120904 2QA32P017S 120905 2QA32P022S 120906 2QA32P031S 120907 2QA32P044S 120908 2QA32P058S 120909 2QAOPTDIN 120910 2QTQT10008U21MS 169075 9QT10008U21MSG 129213 9QT10017U21MS 169076 9QT10017U21MSG 129214 9QT10031U21MS 169077 9QT10031U21MSG 129215 9QT10044U21MS 169078 9QT10044U21MSG 129216 9QT10058U21MS 169079 9QT10058U21MSG 129217 9QT10072U21MS 169080 9QT10072U21MSG 129218 9QT10085U21MS 169081 9QT10085U21MSG 129219 9QT10105U21MS 169082 9QT10105U21MSG 129220 9QT10145U21MS 169083 9QT10145U21MSG 129221 9QT10170U21MS 169084 9QT10170U21MSG 129222 9QT10210U21MS 169085 9QT10210U21MSG 129223 9QT10310U21MS 169086 9QT10310U21MSG 129224 9QT10390U21MS 169087 9QT10390U21MSG 129225 9QT10460N21MS 169094 9QT10460N21MSG 129229 9QT10460U21MS 169088 9QT10460U21MSG 129226 9QT10580N21MS 169095 9QT10580N21MSG 129230 9QT10580U21MS 169089 9QT10580U21MSG 129227 9QT10650N21MS 169096 9QT10650N21MSG 129231 9QT10820U21MS 169090 9QT10820U21MSG 129228 9QT10950N21MS 169097 9QT10950N21MSG 129232 9QT11100N21MS 169098 9QT11100N21MSG 129233 9QT11400N21MS 169099 9QT11400N21MSG 129234 9QT20008U21MS 169100 9QT20017U21MS 169101 9QT20031U21MS 169102 9QT20044U21MS 169103 9QT20058U21MS 169104 9QT20072U21MS 169105 9QT20085U21MS 169106 9QT20105U21MS 169107 9QT20145U21MS 169108 9QT20170U21MS 169109 9QT20210U21MS 169110 9
Cat. No. Ref. No. Pag.
QT20310U21MS 169111 9QT20390U21MS 169112 9QT20460U21MS 169113 9QT20580U21MS 169114 9QT20820U21MS 169115 9QT30008N21MS 169119 9QT30008N21MSG 129257 9QT30017N21MS 169120 9QT30017N21MSG 129258 9QT30031N21MS 169121 9QT30031N21MSG 129259 9QT30044N21MS 169122 9QT30044N21MSG 129260 9QT30058N21MS 169123 9QT30058N21MSG 129261 9QT30072N21MS 169124 9QT30072N21MSG 129262 9QT30085N21MS 169125 9QT30085N21MSG 129263 9QT30105N21MS 169126 9QT30105N21MSG 129264 9QT30145N21MS 169127 9QT30145N21MSG 129265 9QT30170N21MS 169128 9QT30170N21MSG 129266 9QT30210N21MS 169129 9QT30210N21MSG 129267 9QT30310N21MS 169130 9QT30310N21MSG 129268 9QT30390N21MS 169131 9QT30390N21MSG 129269 9QT30460N21MS 169132 9QT30460N21MSG 129270 9QT30580N21MS 169133 9QT30580N21MSG 129271 9QT30650N21MS 169134 9QT30650N21MSG 129272 9QT30950N21MS 169135 9QT30950N21MSG 129273 9QT31100N21MS 169136 9QT31100N21MSG 129274 9QT31400N21MS 169137 9QT31400N21MSG 129275 9
The policy of GE is one of continuous improvement.The right is reserved to alter the design or any structural details of the products at any time without giving notice.
May 2013GE Industrial Solutions
1087
81
GE imagination at work
GEIndustrial Solutions
680855Ref. C/4694/E/EX 4.0 Ed. 05/13
© Copyright GE Industrial Solutions 2013
BelgiumGE Industrial BelgiumNieuwevaart 51B-9000 GentTel. +32 (0)9 265 21 11
FinlandGE Industrial SolutionsKuortaneenkatu 2FI-00510 HelsinkiTel. +358 (0)10 394 3760
FranceGE Industrial SolutionsParis Nord 213, rue de la PerdrixF-95958 Roissy CDG CédexTel. +33 (0)800 912 816
GermanyGE Industrial SolutionsRobert-Bosch Str. 2aD-50354 Hürth-EfferenTel. +49 (0) 2233/ 9719-0
HungaryGE Hungary Kft .Vaci ut 81-83.H-1139 BudapestTel. +36 1 447 6050
RussiaGE Industrial Solutions27/8, Electrozavodskaya streetMoscow, 107023Tel. +7 495 937 11 11
South AfricaGE Industrial SolutionsUnit 4, 130 Gazelle AvenueCorporate Park Midrand 1685P.O. Box 76672 Wendywood 2144 Tel. +27 11 238 3000
SpainGE Industrial SolutionsP.I. Clot del Tufau, s/nE-08295 Sant Vicenç de CastelletTel. +34 900 993 625
United Arab EmiratesGE Industrial SolutionsInjaz Building, 3rd FloorDubai Internet CityPO Box 11549, DubaiTel. +971 4 4546912
United KingdomGE Industrial Solutions2 The Arena, Downshire WayBracknell, Berkshire.RG12 1PUTel. +44 (0)800 587 1239
ItalyGE Industrial SolutionsCentro Direzionale ColleoniVia Paracelso 16Palazzo Andromeda B1I-20864 Agrate Brianza (MB)Tel. +39 039 637 3701
NetherlandsGE Industrial SolutionsParallelweg 10Nl-7482 CA HaaksbergenTel. +31 (0)53 573 03 03
PolandGE Power ControlsUl. Odrowaza 1503-310 WarszawaTel. +48 22 519 76 00
Ul. Leszczyńska 643-300 Bielsko-Biała Tel. +48 33 828 62 33
PortugalGE Industrial SolutionsRua Camilo Castelo Branco, 805Apartado 2770P-4401-601 Vila Nova de GaiaTel. +351 22 374 60 00
GE Industrial Solutions is a fi rst class global supplier of low and medium voltage products including wiring devices, residential and industrial electrical distribution components, automation products, enclosures and switchboards. Demand for the company’s products comes from wholesalers, installers, panelboard builders, contractors,OEMs and utilities worldwide.
www.ge.com/ex/industrialsolutionswww.ge.com/uk/industrialsolutions