Multilin EPM 4600 Multi-feed Power and Energy Metering Solution GE Digital Energy GE Digital Energy 650 Markland Street Markham, Ontario Canada L6C 0M1 TELEPHONE: Worldwide +1 905 927 7070 Europe/Middle East Africa +34 94 485 88 54 North America toll-free 1 800 547 8629 FAX: +1 905 927 5098 E-MAIL: Worldwide [email protected] Europe [email protected] HOME PAGE: Internet: http://www.gedigitalenergy.com/multilin Quickstart Guide GE publication number: GEK-119590 (1601-0297-A1) GE Multilin's Quality Management System is registered to ISO9001:2008 QMI # 005094

Transcript of GE Digital Energy - GE Grid Solutions...GE Digital Energy highly recommends using shorting blocks so...

  • Multilin EPM 4600Multi-feed Power and Energy Metering

    Solution

    GEDigital Energy

    GE Digital Energy650 Markland StreetMarkham, OntarioCanada L6C 0M1TELEPHONE: Worldwide +1 905 927 7070

    Europe/Middle East Africa +34 94 485 88 54North America toll-free 1 800 547 8629

    FAX: +1 905 927 5098E-MAIL: Worldwide [email protected]

    Europe [email protected] PAGE: Internet: http://www.gedigitalenergy.com/multilin

    Quickstart GuideGE publication number: GEK-119590 (1601-0297-A1)

    GE Multilin's QualityManagement System is

    registered to ISO9001:2008

    QMI # 005094

    http://www.gedigitalenergy.com/multilin

  • Copyright © 2013 GE Multilin Inc. All rights reserved.

    EPM 4600 Metering System.

    EPM 4600, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin1.0x Inc.

    The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The manual is for informational use only and is subject to change without notice.

    Part number: 1601-0297-A1 (August 2013)

  • EPM 4600

    Table of Contents

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE i

    CHAPTER 1: MECHANICAL INSTALLATIONRecommended Tools ............................................................3Installation .............................................................................4

    CHAPTER 2: ELECTRONIC INSTALLATIONElectronic Installation ..........................................................7

    CHAPTER 3: METERING SYSTEM CONFIGURATIONConnecting the EPM 4600..................................................13Configuring the EPM 4600.................................................15Communications Settings .................................................17Updating the Device: ..........................................................19

  • ii EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

  • EPM 4600 Multi-feed Power and Energy Metering Solution

    Chapter 1: Mechanical Installation

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 3

    Mechanical Installation

    Recommended ToolsRecommended Tools for EPM 4600 Unit Installation: • #2 Phillips screwdriver• 1/4-inch (0.250”) nut driver socket• box, or open-end wrench• wire cutters. The EPM 4600 unit is designed to withstand harsh environmental conditions; however it is recommended you install it in a dry location, free from dirt and corrosive substances

  • 4 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 1: MECHANICAL INSTALLATION

    .

    InstallationTo install the EPM 4600 Unit:

    1. Mount the unit against any firm, flat surface. 2. Use a #10 screw in each of the four slots on the flange to ensure

    that the EPM 4600 unit is installed securely. IMPORTANT! For safety reasons, mount the EPM 4600 unit in an enclosed and protected environment, such as in a switchgear cabinet.

    193.

    1mm

    286.5mm

    0.28

    in

    0.80

    in20

    .4m

    m

    76.9

    mm

    7.60

    in

    11.28in

    278.9mmcentered

    3.03

    in

    7.2m

    m

    4.8m

    m

    10.98in

    0.19

    in

    cent

    ered

    4.50

    in11

    4.3m

    m

    0.12

    in2.

    9mm

  • CHAPTER 1: MECHANICAL INSTALLATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 5

    3. Connect an earth ground to the post on the side of the EPM 4600 unit, using an AWG 12 wire.

    4. Install a switch or circuit breaker nearby; label it clearly as the EPM 4600 unit’s disconnecting mechanism.

    7.

    62in

    193.

    5mm

    4.36

    in

    80.6

    mm

    3.18

    in

    110.

    6mm

    0.

    81in

    20.5

    mm

  • 6 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 1: MECHANICAL INSTALLATION

  • EPM 4600 Multi-feed Power and Energy Metering Solution

    Chapter 2: Electronic Installation

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 7

    Electronic Installation

    Electronic Installation

    All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces. The current inputs are only to be connected to external current transfomers (CTs).

  • 8 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 2: ELECTRONIC INSTALLATION

    Service:• Three Phase, 4-Wire WYE Service Direct Voltage and 3 CT

    Connection for Metering 8 Three Phase Loads: EPM 4600-T

    All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.

    3

    2

    I1-LO

    LOAD

    B A

    LINE

    N

    1

    L(+) N(-)

    I1-HI

    A

    I3-HI

    C

    C

    I2-HI

    I2-LO

    N

    B

    N

    I3-LO

    SERVICES: WYE, 4 WIRE.

    Power SupplyConnection

    CT Shorting Block

    Only one 3 phase circuit is shown.

    Duplicate for additional circuits.

    Earth Ground

    Earth Ground

    FUSES

    3 x 0.1A

    FU

    SE

    3A

    CONNECTION TYPE: Direct Voltage, CTs

  • CHAPTER 2: ELECTRONIC INSTALLATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 9

    Service:• Three Phase, 4-Wire WYE Service with 3 PT Voltage and 3 CT

    Connection for Metering 8 Three Phase Loads - EPM 4600-T

    All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.

    3

    2

    I1-LO

    LOAD

    B A

    LINE

    N

    1

    L(+) N(-)

    I1-HI

    A

    I3-HI

    C

    C

    I2-HI

    I2-LO

    N

    B

    N

    I3-LO

    SERVICES: WYE, 4 WIRE.

    Power SupplyConnection

    CT Shorting Block

    Only one 3 phase circuit is shown.

    Duplicate for additional circuits.

    Earth Ground

    Earth Ground

    FUSES

    3 x 0.1A

    FU

    SE

    3A

    Earth Ground

    CONNECTION TYPE: 3PTs, CTs

  • 10 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 2: ELECTRONIC INSTALLATION

    Service:• Single Phase, 2-Wire Service with Direct Voltage and 1 CT

    Connection for Metering 24 Single Phase Loads: EPM 4600-S

    All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.

    I1-LO

    LOADS

    VL

    LINE

    N

    1

    L(+) N(-)

    I1-HI

    VL

    I3-HI

    I2-HII2-LO

    N

    N

    I3-LO

    SERVICES: SINGLE PHASE, 2-WIRE CONNECTION TYPE: Direct Voltage, CTs

    Power Supply Connection

    Only three circuits are shown. Duplicate for additional circuits.

    Short Voltage inputs together

    Earth Ground

    CT Shorting Block

    Earth Ground

    FU

    SE 3

    A

  • CHAPTER 2: ELECTRONIC INSTALLATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 11

    Service:• Single Phase, 3-Wire Service with Direct Voltage and 1 CT

    Connection for Metering 24 Single Phase Loads - EPM 4600-S

    All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.

    I1-LO

    LOADS

    VL1

    LINE

    N

    L(+) N(-)

    I1-HI

    VL1

    I3-HI

    I2-HII2-LO

    VL2

    I3-LO

    SERVICE: SINGLE PHASE, 3-WIRE CONNECTION TYPE: Direct Voltage, CTsTo monitor 24 individual loads.See accuracy table for limiting factors.

    Power Supply Connection

    Only one circuit is shown. Duplicate for additional circuits.

    Short Voltage inputs together

    Earth Ground

    CT Shorting Block

    Earth Ground

    FU

    SE 3

    A

    VL2

    VL1VL2

    2 1N

    FUSES2 x 0.1A

    Run lines VL1 and VL2 throughthe CT in opposite directionsSet PT ratio to halfin the meter.

  • 12 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 2: ELECTRONIC INSTALLATION

  • EPM 4600 Multi-feed Power and Energy Metering Solution

    Chapter 3: Metering System Configuration

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 13

    Metering System Configuration

    Connecting the EPM 4600To configure the EPM 4600 Metering System:

    1. Connect to the EPM 4600 unit through its USB port:Use a USB Type A to B plug to connect from your PC’s USB port to the EPM 4600 unit’s USB port. If your PC doesn’t automatically find the USB driver, download it from the product CD that came with the EPM 4600 unit (see Chapter 11 in the EPM 4600 Metering System Installation and Operation Manual on the CD).NOTE: The EPM 4600 Quickstart guide shows connection using the USB port. For Ethernet/Wifi or RS485 connection, see the EPM 4600 Instruction Manual.

  • 14 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 3: METERING SYSTEM CONFIGURATION

    2. Open GE Communicator software (download from product CD). 3. Click Connect on the tool bar. You will see the Connect screen,

    shown on the right. Make sure the Address, Baud Rate, and Protocol settings match the ones here.

    4. Click Connect - the Device Status screen confirms the connection; then click OK - the GE Communicator application’s main screen opens.

    USB Port

  • CHAPTER 3: METERING SYSTEM CONFIGURATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 15

    Configuring the EPM 46001. Click the Profile button on the tool bar. The Device Profile screen

    opens. The Tree menu on the left side of the screen lets you choose setting screens.

    2. Click System Settings to open one of the screens shown below. Use this screen to name the EPM 4600 unit (CPU) and to label the circuits (individual meters). You must give the EPM 4600 CPU an individual, unique name to properly download data to the database.

  • 16 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 3: METERING SYSTEM CONFIGURATION

    3. Click Communications (see instructions below).4. Click CT, PT Ratios and System Hookup (see instructions below).

  • CHAPTER 3: METERING SYSTEM CONFIGURATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 17

    Communications SettingsCOM 1: RS485/ Ethernet/WIFI (optional)

    Address: 1-247; Baud Rate: 57600; Protocol: Modbus RTU/Modbus ASCII;

  • 18 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 3: METERING SYSTEM CONFIGURATION

    Response Delay: 0-750ms; Parity: Odd, Even or None

    COM 2: USB portNOTE: The USB port settings are fixed.

    COM 3: RS485Address: 1-247; Protocol: Modbus RTU/ASCIIBaud Rate: 9600, 19200, 38400, 57600Response Delay: 0-750msNOTE: Click the (1)Default to Ethernet or (2)Default to Display button to set either the (1)Ethernet settings for COM1 or (2)Display settings for COM3, to their default values.

    CT, PT Ratios and System HookupNote that the settings you see on the screen depend on your EPM 4600 unit’s circuit configuration. The top screen is for an EPM 4600 unit with the single phase circuit configuration (EPM 4600-S). The bottom screen is for an EPM 4600 unit with the three phase circuit configuration (EPM 4600-T). For PT settings, see the EPM 4600 Metering System Instruction manual, on the enclosed CD. The CT settings are: CT Ratios

    CT Numerator (Primary): 1 - 65535

  • CHAPTER 3: METERING SYSTEM CONFIGURATION

    EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 19

    CT Denominator (Secondary): 10 or 2 Amps, depending on the EPM 4600 unit’s ordered option (this field is display only).

    Updating the Device:To Update the EPM 4600:

    1. When changes are complete, click the Update button to send a new profile to the EPM 4600 unit.

    2. Click Cancel to Exit the screen.NOTE: For further details and additional programming screens, refer to the GE Communicator Software User Manual on the enclosed CD (access the software manual by clicking Help>Contents from the GE Communicator application’s Title bar).

  • 20 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE

    CHAPTER 3: METERING SYSTEM CONFIGURATION

    Mechanical InstallationRecommended ToolsInstallation

    Electronic InstallationElectronic Installation

    Metering System ConfigurationConnecting the EPM 4600Configuring the EPM 4600Communications SettingsUpdating the Device: