Multilin EPM 4600Multi-feed Power and Energy Metering
Solution
GEDigital Energy
GE Digital Energy650 Markland StreetMarkham, OntarioCanada L6C 0M1TELEPHONE: Worldwide +1 905 927 7070
Europe/Middle East Africa +34 94 485 88 54North America toll-free 1 800 547 8629
FAX: +1 905 927 5098E-MAIL: Worldwide [email protected]
Europe [email protected] PAGE: Internet: http://www.gedigitalenergy.com/multilin
Quickstart GuideGE publication number: GEK-119590 (1601-0297-A1)
GE Multilin's QualityManagement System is
registered to ISO9001:2008
QMI # 005094
http://www.gedigitalenergy.com/multilin
-
Copyright © 2013 GE Multilin Inc. All rights reserved.
EPM 4600 Metering System.
EPM 4600, Digital Energy, Multilin, and GE Multilin are trademarks or registered trademarks of GE Multilin1.0x Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The manual is for informational use only and is subject to change without notice.
Part number: 1601-0297-A1 (August 2013)
-
EPM 4600
Table of Contents
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE i
CHAPTER 1: MECHANICAL INSTALLATIONRecommended Tools ............................................................3Installation .............................................................................4
CHAPTER 2: ELECTRONIC INSTALLATIONElectronic Installation ..........................................................7
CHAPTER 3: METERING SYSTEM CONFIGURATIONConnecting the EPM 4600..................................................13Configuring the EPM 4600.................................................15Communications Settings .................................................17Updating the Device: ..........................................................19
-
ii EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
-
EPM 4600 Multi-feed Power and Energy Metering Solution
Chapter 1: Mechanical Installation
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 3
Mechanical Installation
Recommended ToolsRecommended Tools for EPM 4600 Unit Installation: • #2 Phillips screwdriver• 1/4-inch (0.250”) nut driver socket• box, or open-end wrench• wire cutters. The EPM 4600 unit is designed to withstand harsh environmental conditions; however it is recommended you install it in a dry location, free from dirt and corrosive substances
-
4 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 1: MECHANICAL INSTALLATION
.
InstallationTo install the EPM 4600 Unit:
1. Mount the unit against any firm, flat surface. 2. Use a #10 screw in each of the four slots on the flange to ensure
that the EPM 4600 unit is installed securely. IMPORTANT! For safety reasons, mount the EPM 4600 unit in an enclosed and protected environment, such as in a switchgear cabinet.
193.
1mm
286.5mm
0.28
in
0.80
in20
.4m
m
76.9
mm
7.60
in
11.28in
278.9mmcentered
3.03
in
7.2m
m
4.8m
m
10.98in
0.19
in
cent
ered
4.50
in11
4.3m
m
0.12
in2.
9mm
-
CHAPTER 1: MECHANICAL INSTALLATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 5
3. Connect an earth ground to the post on the side of the EPM 4600 unit, using an AWG 12 wire.
4. Install a switch or circuit breaker nearby; label it clearly as the EPM 4600 unit’s disconnecting mechanism.
7.
62in
193.
5mm
4.36
in
80.6
mm
3.18
in
110.
6mm
0.
81in
20.5
mm
-
6 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 1: MECHANICAL INSTALLATION
-
EPM 4600 Multi-feed Power and Energy Metering Solution
Chapter 2: Electronic Installation
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 7
Electronic Installation
Electronic Installation
All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces. The current inputs are only to be connected to external current transfomers (CTs).
-
8 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 2: ELECTRONIC INSTALLATION
Service:• Three Phase, 4-Wire WYE Service Direct Voltage and 3 CT
Connection for Metering 8 Three Phase Loads: EPM 4600-T
All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.
3
2
I1-LO
LOAD
B A
LINE
N
1
L(+) N(-)
I1-HI
A
I3-HI
C
C
I2-HI
I2-LO
N
B
N
I3-LO
SERVICES: WYE, 4 WIRE.
Power SupplyConnection
CT Shorting Block
Only one 3 phase circuit is shown.
Duplicate for additional circuits.
Earth Ground
Earth Ground
FUSES
3 x 0.1A
FU
SE
3A
CONNECTION TYPE: Direct Voltage, CTs
-
CHAPTER 2: ELECTRONIC INSTALLATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 9
Service:• Three Phase, 4-Wire WYE Service with 3 PT Voltage and 3 CT
Connection for Metering 8 Three Phase Loads - EPM 4600-T
All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.
3
2
I1-LO
LOAD
B A
LINE
N
1
L(+) N(-)
I1-HI
A
I3-HI
C
C
I2-HI
I2-LO
N
B
N
I3-LO
SERVICES: WYE, 4 WIRE.
Power SupplyConnection
CT Shorting Block
Only one 3 phase circuit is shown.
Duplicate for additional circuits.
Earth Ground
Earth Ground
FUSES
3 x 0.1A
FU
SE
3A
Earth Ground
CONNECTION TYPE: 3PTs, CTs
-
10 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 2: ELECTRONIC INSTALLATION
Service:• Single Phase, 2-Wire Service with Direct Voltage and 1 CT
Connection for Metering 24 Single Phase Loads: EPM 4600-S
All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.
I1-LO
LOADS
VL
LINE
N
1
L(+) N(-)
I1-HI
VL
I3-HI
I2-HII2-LO
N
N
I3-LO
SERVICES: SINGLE PHASE, 2-WIRE CONNECTION TYPE: Direct Voltage, CTs
Power Supply Connection
Only three circuits are shown. Duplicate for additional circuits.
Short Voltage inputs together
Earth Ground
CT Shorting Block
Earth Ground
FU
SE 3
A
-
CHAPTER 2: ELECTRONIC INSTALLATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 11
Service:• Single Phase, 3-Wire Service with Direct Voltage and 1 CT
Connection for Metering 24 Single Phase Loads - EPM 4600-S
All CTs must have one side grounded to reduce shock hazard. GE Digital Energy highly recommends using shorting blocks so that the meter can be removed from service while the CT is energized.
I1-LO
LOADS
VL1
LINE
N
L(+) N(-)
I1-HI
VL1
I3-HI
I2-HII2-LO
VL2
I3-LO
SERVICE: SINGLE PHASE, 3-WIRE CONNECTION TYPE: Direct Voltage, CTsTo monitor 24 individual loads.See accuracy table for limiting factors.
Power Supply Connection
Only one circuit is shown. Duplicate for additional circuits.
Short Voltage inputs together
Earth Ground
CT Shorting Block
Earth Ground
FU
SE 3
A
VL2
VL1VL2
2 1N
FUSES2 x 0.1A
Run lines VL1 and VL2 throughthe CT in opposite directionsSet PT ratio to halfin the meter.
-
12 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 2: ELECTRONIC INSTALLATION
-
EPM 4600 Multi-feed Power and Energy Metering Solution
Chapter 3: Metering System Configuration
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 13
Metering System Configuration
Connecting the EPM 4600To configure the EPM 4600 Metering System:
1. Connect to the EPM 4600 unit through its USB port:Use a USB Type A to B plug to connect from your PC’s USB port to the EPM 4600 unit’s USB port. If your PC doesn’t automatically find the USB driver, download it from the product CD that came with the EPM 4600 unit (see Chapter 11 in the EPM 4600 Metering System Installation and Operation Manual on the CD).NOTE: The EPM 4600 Quickstart guide shows connection using the USB port. For Ethernet/Wifi or RS485 connection, see the EPM 4600 Instruction Manual.
-
14 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 3: METERING SYSTEM CONFIGURATION
2. Open GE Communicator software (download from product CD). 3. Click Connect on the tool bar. You will see the Connect screen,
shown on the right. Make sure the Address, Baud Rate, and Protocol settings match the ones here.
4. Click Connect - the Device Status screen confirms the connection; then click OK - the GE Communicator application’s main screen opens.
USB Port
-
CHAPTER 3: METERING SYSTEM CONFIGURATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 15
Configuring the EPM 46001. Click the Profile button on the tool bar. The Device Profile screen
opens. The Tree menu on the left side of the screen lets you choose setting screens.
2. Click System Settings to open one of the screens shown below. Use this screen to name the EPM 4600 unit (CPU) and to label the circuits (individual meters). You must give the EPM 4600 CPU an individual, unique name to properly download data to the database.
-
16 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 3: METERING SYSTEM CONFIGURATION
3. Click Communications (see instructions below).4. Click CT, PT Ratios and System Hookup (see instructions below).
-
CHAPTER 3: METERING SYSTEM CONFIGURATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 17
Communications SettingsCOM 1: RS485/ Ethernet/WIFI (optional)
Address: 1-247; Baud Rate: 57600; Protocol: Modbus RTU/Modbus ASCII;
-
18 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 3: METERING SYSTEM CONFIGURATION
Response Delay: 0-750ms; Parity: Odd, Even or None
COM 2: USB portNOTE: The USB port settings are fixed.
COM 3: RS485Address: 1-247; Protocol: Modbus RTU/ASCIIBaud Rate: 9600, 19200, 38400, 57600Response Delay: 0-750msNOTE: Click the (1)Default to Ethernet or (2)Default to Display button to set either the (1)Ethernet settings for COM1 or (2)Display settings for COM3, to their default values.
CT, PT Ratios and System HookupNote that the settings you see on the screen depend on your EPM 4600 unit’s circuit configuration. The top screen is for an EPM 4600 unit with the single phase circuit configuration (EPM 4600-S). The bottom screen is for an EPM 4600 unit with the three phase circuit configuration (EPM 4600-T). For PT settings, see the EPM 4600 Metering System Instruction manual, on the enclosed CD. The CT settings are: CT Ratios
CT Numerator (Primary): 1 - 65535
-
CHAPTER 3: METERING SYSTEM CONFIGURATION
EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE 19
CT Denominator (Secondary): 10 or 2 Amps, depending on the EPM 4600 unit’s ordered option (this field is display only).
Updating the Device:To Update the EPM 4600:
1. When changes are complete, click the Update button to send a new profile to the EPM 4600 unit.
2. Click Cancel to Exit the screen.NOTE: For further details and additional programming screens, refer to the GE Communicator Software User Manual on the enclosed CD (access the software manual by clicking Help>Contents from the GE Communicator application’s Title bar).
-
20 EPM 4600 POWER AND ENERGY METERING SOLUTION QUICKSTART GUIDE
CHAPTER 3: METERING SYSTEM CONFIGURATION
Mechanical InstallationRecommended ToolsInstallation
Electronic InstallationElectronic Installation
Metering System ConfigurationConnecting the EPM 4600Configuring the EPM 4600Communications SettingsUpdating the Device: