GCB.hec 3-6.Emergancy Spare Parts and Comp.V1
-
Upload
fabyano-britto -
Category
Documents
-
view
372 -
download
24
Transcript of GCB.hec 3-6.Emergancy Spare Parts and Comp.V1
© ABB Group June 6, 2011 | Slide 1
ABB Switzerland Ltd, High Voltage Products, V01
Breaker Type HEC 3-6
Emergency Spare Parts and Components
© ABB Group June 6, 2011 | Slide 2
Agenda
Breaker Type HEC 3-6
Modular Design Concept
Breaker Ratings
Equipment Options
Component View
Main Component
Suggested Shelf Spare Parts
Suggested Strategic Spare Components
© ABB Group June 6, 2011 | Slide 3
Emergency Spare Parts and ComponentsModular Design Concept
HEC 3-6 Standard design includes:
SF6 circuit-breaker
Disconnector
Earthing switches
Capacitors
Current Transformers
Voltage Transformers
Optional items:
Surge Arrestor on Transformer side
Short-circuiting connection
Starting switch (SFC)
© ABB Group June 6, 2011 | Slide 4
Emergency Spare Parts and ComponentsBreaker Ratings HEC 3-6
Type Rated short
circuit breakingRated current Rated current
current in kA, rms
I rms @ 50 Hzin kA
I rms @ 60 Hzin kA
HEC 3/4 100 12.0/13.0 11.5/12.5
HEC 5/6 120 12.0/13.0 11.5/12.5
Rated voltage for all types 25.3 kV
© ABB Group June 6, 2011 | Slide 5
Emergency Spare Parts and ComponentsEquipment Options
Equipment options
Single line diagramQ0 Circuit breaker
Q9 Disconnector
Q6 Braking switch
Q81 Earthing switch (generator side)
Q82 Earthing switch (transformer side)
Q91 Starting switch
Q92 BTB
G
Q91 Q82Q81
GCB System
Q0 Q9
Q92
T
Q6
© ABB Group June 6, 2011 | Slide 6
Emergency Spare Parts and ComponentsComponent View
Component overview:
1. Flexible Connection
2. Disconnector
3. Arcing chamber
4. Isolation in air
5. Enclosure
6. Earthing Switch
7. IPB Connection
8. Current Transformer
9. Potential Transformer (not shown)
10. Surge Arrester (not shown)
1 12 4 3 5
66 8
7
© ABB Group June 6, 2011 | Slide 7
Emergency Spare Parts and ComponentsMain Components (1)
Main Components1 Arcing Chamber
2 Disconnector
3 Earthing Switch
4 Capacitors
5 Surge Arrestor
6 Flexible Connection
7 Bus Bar
8 Enclosure to IPB
2
3
4
5
1
3
6
74
8
© ABB Group June 6, 2011 | Slide 8
Emergency Spare Parts and ComponentsMain Components (2)
Drives1 Main Drive Q0
2 Disconnector Drive Q9
3 Earthing Switch Drive Q81
4 Earthing Switch Drive Q82
12 34
© ABB Group June 6, 2011 | Slide 9
Emergency Spare Parts and ComponentsMain Components (3)
Control Cubicle1 Control Cubicle
2 Local Control Panel (w/ Mimic)
1 2
© ABB Group June 6, 2011 | Slide 10
Emergency Spare Parts and ComponentsSuggested Shelf Spare Parts HEC 3-6 (1)
7 PCHAGG401909P0001Sealing cord (Enclosure-cores)
1 PCHAGG301141P0001Density Monitor
1 PCHASV403979R0001Lubrication Grease
1 PCCustomer specific scaleDensity Indication
1 PCHASV405272R0010Hydraulic Oil 0.9 kg (1 liter)
2 PCGPFX730094P0001Pilot Valve AHMA/HMB 220-250 V(DC)
2 PCGPFX730094P0002Pilot Valve AHMA/HMB 110-125 V(DC)
1 PAA (2 PC)GPFX052143P0098Carbon Brushes
1 PCGPFX052220R0002Compound Motor 120-250 V(DC)
1 PCGPFX052220R0001Compound Motor 110-125 V(DC)
Rec. quantity:Identification Number:Description:
GCB Type HEC 3-6
© ABB Group June 6, 2011 | Slide 11
Emergency Spare Parts and ComponentsSuggested Shelf Spare Parts HEC 3-6 (2)
1
2
1 Compound Motor (Pump Motor)
2 Pilot Valves
3 Carbon Brushes
3
© ABB Group June 6, 2011 | Slide 12
Emergency Spare Parts and ComponentsSuggested Shelf Spare Parts HEC 3-6 (3)
SF6 Pressure Gauge SF6 Density Monitor
Sealing cord (Enclosure-Cover) Hydraulic Oil 0.9 kg (for AHMA/HMB)
© ABB Group June 6, 2011 | Slide 13
Emergency Spare Parts and ComponentsSuggested Strategic Components HEC 3-6 (1)
3 PCHAGG001042R0001 (HEC 3/5)
HAGG001042R0002 (HEC 4/6)Disconnector complete
1 PC / TypeHAGG200738P0002 (0,260MYF/125KV)
HAGG200738P0004 (0,260MYF/150KV)Capacitor, transformer side
1 PC / TypeHAGG200738P0001 (0,132MYF/125KV)
HAGG200738P0003 (0,132MYF/150KV)Capacitor, generator side
1 PCHAGG100471Pxxxx
Customer specific scaleSurge Arrestor
1 PC / TypeProject specific configurationVoltage transformer
1 PC / TypeProject specific configurationCurrent transformer
3 PC1HC0002837M0001
Project specific configurationSpare Arcing chamber4)
1 PC1HC600661M0001
Project specific configurationBreaker Operating Mechanism3)
1 PCHATM303065K0002 (~ until 2001)
1HC0005396K0001 (~ from 2001)Disconnector Switch Motor2)
1 PCHATM303065K0003 (~ until 2001)
1HC0005396K0001 (~ from 2001)Earthing Switch Drive Motor1)
Rec. quantity:Identification Number:Description:
GCB Type HEC 3-6
1) 2) 3) 4) See next slide
© ABB Group June 6, 2011 | Slide 14
Emergency Spare Parts and ComponentsSuggested Strategic Components HEC 3-6 (2)
Location of Drives
1 Earthing Switch Motor
2 Disconnector Switch Motor
3 Breaker Operating Mechanism
Earthing / Disconnector Switch Motor
Braker Operating Mechanism (AHMA/HMB)
2 1 3
© ABB Group June 6, 2011 | Slide 15
Emergency Spare Parts and ComponentsSuggested Strategic Components HEC 3-6 (3)
Disconnector complete Spare Arcing chamber
© ABB Group June 6, 2011 | Slide 16
Emergency Spare Parts and ComponentsSuggested Strategic Components HEC 3-6 (4)
Current transformer
Voltage transformer
Capacitor
Surge Arrestor
© ABB Group June 6, 2011 | Slide 17
Emergency Spare Parts and ComponentsSuggested Strategic Components HEC 3-6 (5)
Note 1):
Earthing switch motor is identical for HEC 3-6
Note 2):
Disconnector switch motor is identical for HEC 3-6
Note 3):
In principle:Breaker Operating Mechanism “HMB 4.x”, compatible to HEC 3/4
Breaker Operating Mechanism “HMB 4.x”, compatible to HEC 5/6
Breaker Operating Mechanism “AHMA 4”, compatible to “HMB 4.x” w/o additional material
Attention:Project specific configuration (coil voltage, frequency, wiring, etc.)
Note 4):
Arcing chamber configuration is breaker and project specific
HEC 3, HEC 4, HEC 5, HEC 6 are NOT compatible