GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360...
Transcript of GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360...
G A S T E C
LB1360
27.05.2004
Multicalor 700.1 MDMulticalor 800.1 MDMulticalor 1000.1 MDMulticalor 1200.1 MD Light oil / Natural Gas 300 mbar
MODELS
techniques for energy saving
GAS / LIGHT-OIL DUAL BURNERS
pag.2
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
mbar
2000 3000 4000 5000 6000 7000 8000 9000 10000
10
12
14
16
1000
18
20
22
-2
11000
0
2
4
6
8
0
24
26
28
30
12000 kW13000
32
34
36
Multicalor 700.1 MD
Multicalor 800.1 M
D
Multicalor 1000.1 M
D
Multicalor 1200.1 M
D
WORKING FIELDS
Burner output
Bac
kpre
ssur
e in
com
bust
ion
cham
ber
E D - D1
G
CBA
F I
L
M
H
N
O
SUNTECSUNTECSUNTEC
OVERALL DIMENSIONS
Models Multicalor 700.1 MD 800.1 MD 1000.1 MD 1200.1 MDThermal power max. kW 7.250 8.500 10.500 13.100
kcal/h 6.250.000 7.327.500 9.052.000 11.293.100Thermal power min. kW 1.500 2.000 2.500 2.700
kcal/h 1.290.000 1.724.000 2.155.000 2.327.600Max. capacity (Natural Gas) Nm3/ h 729 855 1.056 1.318Min. capacity (Natural Gas) Nm3/ h 150 201 251 272Max. light oil flow rate kg/h 613 718 887 1.107Min. light oil flow rate kg/h 126 169 211 228Gas pressure mbar 300 300 300 300Voltage 50 Hz V 230/400 230/400 230/400 230/400Motor kW 15 18,5 22 37Rpm N° 2800 2800 2800 2800Fuels: Nat. Gas LHV = 35,9 Mj/Nm3 = 8.570 kcal/Nm3; Light Oil LHV = 10.200 kcal/kg max. 1,5° at 20 °C
D = Short headD1= Long head
MODELS A B C D D1 E F G H I L M N OMulticalor 700.1 1215 585 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 800.1 1285 655 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 1000.1 1315 685 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 1200.1 1425 795 630 570 - 1420 450 800 480 460 460 M20 195 232
pag.3
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
CONNECTION TO THE GAS PIPELINE Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verifythat the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gaugeconnector, then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats tothe desired temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end ofthe test the burner will be enabled to run the start-up sequence.
ELECTRICAL CONNECTIONSAll burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral forauxiliary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors onburner as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtai-ning in the country in question.
BURNER START-UPBefore starting the burner, make sure it is mounted correctly. Then check connections are correct according to thediagram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make surevoltage corresponds to burner plate data. The connection diagram and start-up cycle are shown separately. Forwiring from control box to burner, see the enclosed connection diagram. Pay particular attention to neutral andphase connections : never exchange them!. Vent air and impurities of gas pipe. Check gas pressure conforms to thelimits stated on the burner plate when connecting a master gauge to the test port provided on the burner. Blowermotor starts and pre-purging begins. Since pre-purging has to be carried out with the max.air delivery, the burner control circuit turns the air damper to the max. delivery position bythe air servocontrol in approximately 30 seconds time. When the servocontrol is fully open,a signal to the electronic control unit starts the 66 seconds pre-purge cycle. At the end ofthe prepurging time, the air servocontrol gets to the Low Flame position so that burnerignition is ensured at min. output. Simultaneously the ignition transformer receives voltageand after 3 seconds (pre-ignition) opens the pilot gas valve. Fuel flows to the combustion head and ignites. Twoseconds after pilot gas valves have opened, the ignition transformer is excluded from the circuit. In case of no igni-tion the burner goes to lock-out within two seconds. After 6 sec. open the working gas valve, governed by the gasfiring butterfly valve.Now the burner is operating at the min. firing rate (about 30% of the max. firing rate). The airservocontrol runs at the Low Flame position and in case the temperature control has to be set at the max. output itgoes to a fully open position of air damper and butterfly valve. During the burner-off periods the air damper closesup fully.
0
12
0 - STOP1 - GASOLIO2 - GAS
LIGHT-OIL
ADJUSTING THE COMBUSTION PROCESSIMPORTANT: to obtain the right adjustment of the combustion and thermal capacity it is important to analyzethe reducts of combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment isdone simultaneously, together with the analysis of the products of combustion, making sure that the measuredvalues are suitable and that they comply with current safety standards. On this matter, please refer to the table andfigure below.THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.
NOTE: ALL SAFETY DEVICES (AIR PRESSURE SWITCH, MINIMUM GAS PRESSURE SWITCH, GAS SOLE-NOID VALVES AND GAS GOVERNOR) SHALL BE DULY SEALED AFTER CALIBRATION AND BUR-NER START UP BY ECOFLAM’S TECHNICIANS.
CALCULATING THE BURNER CAPACITYTo calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters)on the counter and the time of the reading in seconds.Proceed with the calculation using the following formula: x f = kWe
sec
e = Litres gassec = Time in secondG20 = 34,02G30 = 116G31 = 88
f
pag.4
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTORRemove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key providedfor. Description:
I - High flame operating opening position adjusting cam (Light-Oil /Gas)II - Limit switch for the air damper position at burner’s shut downIII - Ignition flame opening position adjusting cam (Gas). IV - Ignition flame opening position adjusting cam(Light-Oil)V - Low flame operating opening position adjusting cam (Gas)VI - Low flame operating opening position adjusting cam (Light-Oil)VII - Not used camVIII - Not used cam
Manual change
The control box starts the burnerfan, to carry out the prepurging ofthe combustion chamber, andcheks the vent air pressure throughthe air pressure switch. At the endof prepurging, the ignition tran-sformer cuts-in and generates aspark between the electrodes. Atthe same time the two gas valvesopen (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out,is granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gaslack or a major pressure drop, the minimum air pressure switch shuts down the burner.
LANDIS & STAEFA, Model LFL1.622 OPERATING CYCLERef. Descriptiont1 Duration Waiting time for confirmationt2 of air pressuret3 Preventilation timet4 Safety timet5 Pressurizing time
Time for enabling operation of the main gas valve on minimum capacity
t6 Time for enabling operation of the main gas valve on maximum capacity
Duration
8”66”2”4”
10”
10”
Rivelazionedi fiamma
Spia di blocco
Valvola gas
Serranda aria
Serranda gas
Trasformatoredi accensione
Pressostato aria
Motore ventilatore
Pressostato gas
0min
100%
t1 t2
t4
t3
t6t5
Ciclo di funzionamento normaleCiclo di funzionamento
in mancanza di fiamma all'accensionet1 t2
t4
t3
Consensomin./max. potenza
Gas manostat
Fan motor
Air Switch
Ignition transformer
Gas valve
Min/max capacity enabling device
Air damper
Gas damper
Flame detector
Cut-out pilot lamp
Normal operating cycleOperating cycle in the event of
ignition failureNormal operating cycle
pag.5
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
+
--
Part. 1
Part. 2
Part. 3
-
+
-COMMUTATORE
0
AUTO
0 = bloccaggio degli apparati per il funzionamento in una posizione intermadia = funzionamento alla massima potenza = funzionamento alla minima potenza AUTO = funzionamento automatico
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GASPosition the selector placed on the control panel on position 2 and proceed as follows: Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gasflow, as established by analyzing the combustion process.
ADJUSTING THE MAXIMUM CAPACITY OF THE GASPosition the selector, situated on the control panel, on position 1 and proceed as follows:Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in thegovernor.
ADJUSTING THE MAXIMUM AIR FLOW RATE Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;The correct air flow as established by analyzing the combustion process.
ADJUSTING THE INTERMEDIATE BURNER CAPACITY Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment ismade as outlined below. Repeat the operation for the other cam points.Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the positionof the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
AIR ADJUSTMENT
operating elements locked in an intermediatepositionoperation on maximum capacity operation on minimum capacity automatic operation
SELECTOR
SETTING THE FIRING HEAD
+-
pag.6
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
The ionization current is checked by inserting a microam-meter with an end of scale of 50 µA (d.c.) in series withthe ionization probe. A faulty position of the electrodecan lead to a reduction in the ionization current and causea safety cut-out of the burner due to a flame detection fai-lure. In this case, check the position of the electrode, itselectric connection and the earthing of the burner. Theionization current is normally > 20 µA.
REMOVING THE FIRING HEAD
IONIZATION CURRENT
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCHUnscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feedpressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for L.P.G.nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCHUnscrew screws A and B and remove cover C.- Set the pressure switch to the minimum byturning regulator D to position 1. - Start the burner and keep in low flame running, while checking that combustion is cor-rect. Through a small cardboard, progressively obstruct the air intake until to obtain aCO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressureport E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase theadjustment value of the air pressure switch until to have the burner lockout. Remove theobstruction from the air intake, screw on the cover C and start the burner by pressing thecontrol box rearm button.
Note: The pressure measured at pressure port E must be within the limits of the pressu-re switch working range. If not, loose the locking nut of screw F and gradually turn thesame: clockwise to reduce the pressure; counterclockwise to increase. At the end tighten thelocking nut.
2,55
10 15
50
25
35
30
4045
20
0,4
0,6 0,9
3,0
1,5
2,1
1,8
2,42,7
1,2
I
L
MN
A
B
CD
E
F
GH
gas pressure switch
air pressure switch
22 23
LANDIS LFL 1.622
Fotocellula
min 70 µA
Microamperometro fondo scala 1000 µA
PHOTORESISTOR
Microamperometerfull scale 1000 µA
pag.7
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
VL
VR
A
RPR
VS
OIL DELIVERY ADJUSTMENTThe diagram illustrates the fuel feeding system of these types of burners, which incorpora-tes a by-pass nozzle with oil flow regulation on its return pipe. The oil supply isvaried by acting on the nozzle through the pressure in the return line. Max. oil supplyis therefore reached when the pressure in the pump line is about 22 bar and the returnline is fully closed; min. oil supply when the return line is fully open. Relevant pres-sure readings in the return line are as follows:
Pump pressure 22-25 bar.Max Burner output, return oil pressure:FLUIDICS nozzle : 16 ÷19 bar.BERGONZO nozzle : 20 ÷24 bar.
Min Burner output, return oil pressure:FLUIDICS nozzle : 6 ÷9 barBERGONZO nozzle : 4 ÷8 bar
+-
OPERATION OF BURNER WITH LIGHT-OIL FUEL Once having installed the burner, check the following items:- The burner power feeding and the main line protection fuses- The correct length of pipes and that the same are sealed.- The type of fuel, which must be suitable for burner.- The connection of boiler’s thermostats and all the safeties.- The motor rotation direction.- The correct calibration of the motor’s thermal protection.When all the above mentioned conditions are checked and accomplished, it is possible to go on with burner’s tests.Power the burner. The control box feeds the ignition transformer and the burner’s motor at the same time, whichwill run a prepurging of the combustion chamber for about 20 sec.At the end of prepurging, the control box opens solenoid valves and the burner starts. After a safety interval of 5seconds and a correct ignition, the control box turns off the ignition transformer and, 10 seconds later, sets themotorised air damper to its maximum opening (High flame). In case of faulty ignition, the control box switches theburner into safety condition within 5 second. In such a case, the manual rearming of the burner shall not take placebefore 30 seconds have elapsed from the burner’s safety shutdown. In order to obtain an optimal combustion, it isnecessary adjust the LOW - HIGH flame air flow, according to the instruction given further on. During such aphase, it will be possible to manually switch between HIGH and LOW flame and viceversa, through the High/Lowflame switch. At the end of the adjusting phase, leave the switch in position AUTO.
0
12
0 - STOP1 - GASOLIO2 - GAS
LIGHT-OIL
HYDRAULIC CIRCUIT1 - Hose 2 - Oil filter3 - Oil cockA - Suction R - ReturnVS - Safety oil valveVL - Working oil valveVR - Return oil valve PR - Oil pressure switch
1
1
2 3
1) Remove the cap A of the pres-sure regulating valve TV.
2) Loosen the fixing nut B anduse an allen wrench on the screwC to adjust the delivery oil pres-sure. To increase the pressureturn clockwise, to decrease thepressure turn anticlockwise.
3) Tighten the nut B and payattention not to turn also theadjusting screw.
4) Screw on the cap A, back toits previous position.
pag.8
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
SUNTEC T.......
PRIMING AND ADJUSTMENT OF OIL PUMP1 - INLET 2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT4 - VACUUM GAUGE PORT 5 -6 - TO NOZZLE
VERIFY:- That piping system is perfectly sealed;- That the use of hoses is avoided whenever is possible (use copperpipes preferably);- That depression is not greater than 0,45 bar, to avoid pump’scavitation;- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 22-25 bar during the testing of burners. Before starting the burner,bleed the air in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump pri-ming. Start the burner and check the pump feeding pressure. In case the pump priming does not takeplace during the first prepurging, with a consequent, subsequent lock-out of the burner, rearm the burner’slock-out to restart, by pushing the button on the control box. If, after a successful pump priming, the bur-ner locks-out after the prepurging, due to a fuel pressure drop in the pump, rearm the burner’s lock-out torestart the burner. Do never allow the pump working without oil for more than three minutes. Note: befo-re starting the burner, check that the return pipe is open. An eventual obstruction could damage the pumpsealing device.
1
2
6
34
PRESSURE REGULATING VALVE ADJUSTMENT
A
B
C
B
A
pag.9
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
pag.10
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
pag.11
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
A - Reset keyB - Operating lamps (orange=light-oil; green= gas)C - Selector switch: 0 = Loking of devoices for operating at intermediate outputs = Operation at max. output = Operation at min. outputAUTO = Automatic operation
D - ON/OFF switchE - Fuse holderF - Selector: 0 = STOP 1 = Light-oil operation 2 = Gas operationG - Termal lock-out lampH - Modulating unit RWF 40
0I
0
AUTO
0
OIL GAS
OIL GAS
RESET
K6
RWF 40
PGMPGM EXITEXIT
E
H
F
C
A
D
BG
DESCRIPTION OF CONTROL PANEL
MAINTENANCEYEARLY CHECKSThe burner’s periodical check (firing head, electrodes etc.) must be carried out by authorised personnel one or two times peryear, depending on the utilisation. Before going on with the maintenance controls of the burner, it should be advisable to checkits general conditions, according to the following steps:Unplug the burner; close the fuel cock; shut down the gas supply; remove burner’s cover and clean the fan and air intake; cleanthe firing head and check the electrode’s position; reassemble all the parts; check the connection’s sealing; check the chimney;start the burner and check the combustion flue (CO2 = 9.5 ÷ 9.8; O = lower than 75 ppm).
BEFORE EVERY INTERVENTION CHECK:
POSITION OF IGNITION ELECTRODES
3 ÷ 4 mm
5 ÷ 6 mm
NOZZLE CLEANING AND REPLACEMENT
Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to notdamage the electrodes. Fit the new nozzle with the same care.Note: Always check the position of electrodes after having replaced the nozzle (see illustration). A wrongposition could cause ignition troubles.
pag.12
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
The electric system is duly powered and the burner is plugged in. The gas pressure must be the suitable one and the gas cock open. The control devices must be properly connected. When all the above conditions are met, start the burner by pressing the lockout enable pushbutton. Check the burner’s cycle.
THE BURNER DOES NOT START:Check the ON/OFF switch, the thermostats, the motor and the gas pressure. The master switch is in position “0”. Fuses are blown out. The control box is faulty.
THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE:Check the fan and the air pressure. Check the air pressure switch. Control box faulty. Ignition transformer faulty. Check the ignition cable. Electrodes are dirty or in wrong position. Nozzles are clogged or worn. Filters are clogged. Light-oil pressure is too low. Combustion air’s flow rate too high related to nozzle output.
THE BURNER RUNS THE PREPURGING BUT DOES NOT IGNITE:Check the position of the electrodes; check the ignition cable; Check the ignition transformer; Check the control box.
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER THE SAFETY TIME:Check phase and neutral for a correct connection. Check gas solenoid valve. Check the position of ionisation probe and its connection. Check the control box. Check nozzles (clogged or worn). The photoresistor does not detect the flame. The filters are clogged. Light-oil pressure too low. Combustion air’s flow rate too high related to nozzle output.
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER FEW MOMENTS:Check gas governor and gas filter. Check gas pressure through a manometer. Check ionization value (min. 70 µA).
THE BURNER DOES NOT SWITCHES TO HIGH FLAME:Manual selector switch in wrong position. Faulty control box. High flame solenoid valve’s coils faulty.Air damper’s jacket faulty or wrongly adjusted.
pag.13
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
RWF 40 MICROPROCESSOR REGULATOR
Display:analog input 1(actual value)
Display: Set point SP1
Decrease value
Programming key
Manual operation
Auxiliary contact
Increase value
EXIT key.
Burner operation
Reduce powerCLOSE/1st Stage
Increase powerOPEN/2nd Stage
Two-stage operation
Description of display and keys on the RWF 40 microprocessor regulatorThe figure shows the normal display indicating
the actual value and the programmed setpoint, and equally important,
gives the meaning of thesingle keys and indicator Leds.
Configuration level
User Level
Normal display
Parameters level
PGM
PGM
PGM
PGM PGMPGM
PGM PGM
PGM PGM
min 2s
min 2s
min 2s
Exit
PROGRAMMING LEVELS
pag.14
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
SETTING PARAMETERSWhen the burner is ignited all displays of the regulator light up. The set point display will blink for about 10 seconds. The valuein the upper field of the display (red) indicates the actual value. The value in the lower field of the display (green) indicates the setpoint currently programmed. CHANGING THE SET POINTTo change the set point, proceed as follows: ---- Press the PGMPGM button to access the user level. SP1* will appear in the lower display---- Change the value of set point SP1 using the t and s keys.▼e ▲. ---- After a 2 second delay the value set is stored automatically – Toreturn to normal display press EXITEXIT. ** The value of SP1 depends on the value set previously in configuration level C111.SETTING PID PARAMETERSPID parameters are factory set to standard mean values. The operation of the regulator can be self-adapted to suit the system byactivating the “tunE” function. The regulator will set the PID parameters automatically. To activate the “tunE” function proceedas follows: ---- With the burner in operation, press PGM PGM + ▼. ---- the caption “tunE*” will blink in the display. – When “tunE” stopsblinking, the self-adaptation routine has been completed. ---- Confirm the computed parameters by pressing the ▲ key for 2 seconds. ** The “tunE” function cannot be activated in Manual mode, or when the burner is off. The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-ve action time dt and the integral action time rt. To change parameters Pb1, dt and rt, proceeds as follows: ---- Press the PGMPGM button to access the parameters level. ---- To move fromone parameter to the next, press PGMPGM . ---- When Pb1 is displayed, the value can be increased or decreased using the s and t keys. ----Confirm the changed parameters by pressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored auto-matically. ---- Press PGMPGM to access the next parameter. ---- When dt is displayed, repeat the procedure described above. ---- Press PGMto access the next parameter. ---- When rt is displayed, repeat the procedure above. ---- To return to normal display press EXITEXIT. DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFFThe regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicatesthe upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows: ---- Pressthe PGMPGM key to access the parameters level. ---- To move from one parameter to the next, press PGMPGM . ---- When HYS1 is displayed(burner ignition differential-stage II), increase or decrease the value using the ▼ and ▲ keys. ---- Confirm the changed parameters bypressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored automatically. ---- Press PGMPGM to access thenext parameter. ---- When HYS2 is displayed (burner shutoff differential-stage II), repeat the procedure described above. ---- PressPGMPGM to access the next parameter. ---- When HYS3 is displayed (upper shutoff differential) repeat the procedure described above. ---- To return to normal display press EXITEXIT.
MANUAL/AUTOMATIC MODETo access “MANUAL” mode, press and hold EXITEXIT for at least 5 seconds. Manual mode can only be selected when the burner isin operation. It is deactivated automatically when the burner shuts off. When the LED above the hand symbol is alight, the regu-lator is in manual mode and the position of the servocontrol can be changed using the ▼ and ▲ keys. The LEDS on the front ofthe regulator indicate whether the servocontrol OPEN or CLOSE command is currently active. Pressing the ▼ key the servocon-trol OPENS. Pressing the ▲ key the servocontrol CLOSES. To select automatic mode press and hold EXITEXIT for at least 5 seconds.The LED above the hand symbol goes out and the regulator reverts to automatic.
CLIMATIC COMPENSATIONThe RWF 40 regulator can be set with the set point interlocked to the external probe. To select this operating mode, proceed asfollows: ---- Connect the required probe as in the wiring diagram. ---- Change the regulator settings. When using an external probethe regulator must be set as follows: ---- Press the PGMPGM key to access the configuration level. When the caption C111 (XXXX) isdisplayed, use the ▲ key to access the second figure (XXXX). Use the ▼ key to select the type of probe (XX3X). ---- Confirm thechange of parameters by pressing PGMPGM. If this is not done within 2 seconds, the value is stored automatically ---- Press PGMPGM toaccess the configuration level. When the display reads C112 (XXXX), use the ▲ key to access the second figure (XXXX). Press the▼ key to set the type of probe (XX3X). ---- Confirm the changed parameters by pressing PGMPGM. ---- If confirmation is not givenwithin 2 seconds the value will be stored automatically. ---- To return to normal display press EXITEXIT. To establish the heating curve, proceed as follows: ---- Press PGMPGM to access the parameters level. ---- Press PGMPGM to move from one parameter to the next. ---- When the letter H isdisplayed (heating curve gradient), increase or decrease the value using the ▼ and ▲ keys. ---- Confirm the changed parameters bypressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored automatically. ---- To return to normal display press EXITEXIT.
pag.15
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
PROBE CONNECTION DIAGRAMS
SPH
60
80
100
0
20
40
SPL
120
140
160
20 15 10 5 0 -20-15-10-517.5 12.5 7.5 2.5 -2.5 -17.5-12.5-7.5
0.20.40.60.811.21.41.61.822.22.42.62.833.23.43.63.84
External temperature (iC)
Hea
tin
g c
urv
e g
rad
ien
t (H
)
PARAMETERIZATION
Bo
iler
tem
per
atu
re s
et p
oin
t (i
C)
Cod.S704
Cod. S721Cod.S731
S731/1S731/2S731/3S731/4
Cod.S720/1
Connection for probeQAE2..(passive probe)Water probeConfiguration codeC111 = 9XXX
Connection for probeFT-TP/..(passive probe)(Degusa probe)Configuration codeC111 = 5XXX
Connection for probe QBE620-P..(active probes)Configuration code C111 = GXXXS731 - 0…4 bar / 0…400 kPa QBE620-P4 S731/1 - 0…10 bar / 0…1 MPa QBE620-P10 S731/2 - 0…16 bar / 0…1.6 Mpa QBE620-P16 S731/3 - 0…25 bar / 0…2.5 MPa QBE620-P25 S731/4 - 0…40 bar / 0…4 MPa QBE620-P40
Connection for probeQAC22 (passive probe)Configuration code C111 = XX3XC112 = XX1X
1 2 3 4
RWF 40
B M
G1+ M1
QAE22A
1 2 3 4
RWF 40
B M
B9 M9
QAC2..
1 2 3 4
RWF 40
GL M
G+ M1
OBE620-P..U1
G- U1
pag.16
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
- Situation - The number 1999 blinks in the display as the actual value, with the set point value displayed normally.
- Cause - The real value is not being measured. This means that the upper or lowerlimit of the measurement range on analog input 1 (real value) has been exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probeis faulty, the regulator will not indicate the real value of the physical quantity monitored. This will result in automatic shutdown (failsafe), deactivation of theself-adapt function and inhibition of manual operation. The response of the auxiliary contact will depend on the configuration of parameter C113.
- Situation - The number 1999 blinks in the display as the actual value, with tAshowing in the set point field.
- Cause - The external temperature is not being measured. This means that theupper or lower limit of the measurement range on analog input 3 (real value) hasbeen exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probeis faulty, the regulator will not indicate the real value.
- Situation - The number 1999 blinks in the display as the actual value, with SP .Eshowing in the set point field.
- Cause - The external set point value is not being measured. This means that theupper or lower limit of the measurement range on analog input 2 (real value) hasbeen exceeded.
- Remedy - Check the electrical connections and the external set point signal. If theprobe is faulty, the regulator will not indicate the real value of the physical quantitymonitored. This will result in automatic shutdown (failsafe), deactivation of the self-adapt function and inhibition of manual operation.
ERROR/FAULT INDICATIONNUMBERS BLINKING IN DISPLAY
Analog input 1 (actual value)Pt1000, 2-wire, Landis & Staefa IEC 751
5FT-TP/… (passive probe)
Ni1000, 2-wire, Landis & Staefa9QAE2 … (passive probe - water probe)
Standard Signal DC 0…10 V QBE620P…(active probe - pressure probe) G
C111 – C112 INPUT CONFIGURATION INDICATIONS
Analog Input 3 (external temperature)No function (probe not active) 0External probe Pt 1000, 2-wire,
1QAC22 (passive probe)
AUXILIARY CONTACT, TYPE OF REGULATOR, SET POINT “SP1”BLOCK C112. Parameter configuration
Set point “SP1”Set point SP1 - data input from keys 0Set point SP1 - interlocked to external probe (configure) 1
pag.17
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
A
Insert the RWF 40 regulator through the relative opening in the electrical panel (A). Insert the fixing anchors and screws into the slots, and secure the unit to the panel (B). To open the regulator, squeeze the cover from the ends as shown, and lift out (C).
WHEN REPLACEMENT IS NECESSARY, PROCEED AS SHOWN IN FIGURES A-B-C BELOW
B C
pag.18
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
Parameter Display Ecoflam setting Ecoflam setting Ecoflam setting (passive probe) (passive probe) (active probe)
QAE22 FT-TP/1000 QBE620-P...Limit value of limit comparator AL 0 0 0Switching differential for limit comparator HYSt 0 0 0Proportional band Pb.1 8 8 1Derivative time dt 20 20 3Integral action time rt 80 80 15Dead band (neutral zone) db 0.5 0.5 0.5Actuator running time (sec.) tt 25 25 25Switch-on threshold burner / stage II HYS1 -2 -2 -0.2Switch-off level stage II HYS2 0 0 0Upper switch-off threshold HYS3 5 5 0.5Response threshold q 0 0 0Heating curve slope H 2 2 2Parallel displacement P 0 0 0
PARAMETERS
Parameter Display Ecoflam setting(passive probe) (active probe) QBE620-P...
QAE22 FT-TP/1000 -P4 -P10 -P16 -P25 -P40Analog input 1, 2 and 3; setpoint changeover / shift C111 9030 5030 G000 G000 G000 G000 G000Limit comparator; controller type; setpoint 1; locking C112 0010 0010 0010 0010 0010 0010 0010Unit address; decimal place / unit, signal for out-of-range C113 0110 0110 0110 0110 0110 0110 0110Measured value range start analog input 1 SCL 0 0 0 0 0 0 0Measured value range analog input 1 SCH 100 100 4 10 16 25 40Measured value range analog input 2 SCL2 0 0 0 0 0 0 0Measured value range analog input 2 SCH2 0 0 0 0 0 0 0Lower setpoint limit SPL 60 60 0 0 0 0 0Upper setpoint limit SPH 88 88 4 10 16 25 40Actual value correction,analog input 1 OFF1 0 0 0 0 0 0 0Actual value correction,analog input 2 OFF2 0 0 0 0 0 0 0Actual value correction,analog input 3 OFF3 0 0 0 0 0 0 0Filter time constant for digital filter, dF1 1 1 0 0 0 0 0analog input 1
CONFIGURATION
pag.19
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
3M
MV
W1
V1U
1
U2
V2W
2
QBE6
20-P
GLM
U1
TP
LINE
LOAD
M1
LAN
DIS
RW
F 40
LN
QQ1
4Y2
Y1Q1
3G+
G-B9
U1G1
+M9
- +
TP
3M
182
1LA
NDIS
LFL 1
.622
104
36
58
79
1412
1113
1615
1732
2220
1921
2423
31
0001
0203
0405
0607
0809
A
0001
0203
0405
0607
0809
B C D E
A B C D E
IND.
MO
DIFI
CA
SOST
.DA
SOST
.IL
IND.
MO
D.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA
-FIR
MA
DATA
FIRMA
CONT
ROLL
ATO
DESC
RIZI
ONE
MO
DIFI
CA
DISE
GNAT
O
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE. A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONT
ROLL
O D
I TEN
UTA
APPA
RECC
HIAT
URA
UFF.T
ECNI
CO-S
ETTO
RE EL
ETTR
ICO
DENO
MIN
AZIO
NE
SIST
. RIV
ELAZ
.CO
DICE
MO
TORI
DUTT
ORE
S.p.A.
PAGI
NA D
I
12
SA
BEM
4314
1M
ULTI
CALO
R 10
00.1
MD
LAND
IS S
QM
50.
481A
2
LAND
IS L
FL 1
.622
DUNG
S VD
K 20
0-A
UV06
-05-
2004FM
P95 96KM
P RS
TN
O
Q
HLB
S1R1
1011
85
67
9T1
N
FMV95 96
SAgG
12
30
SAM
A
12
30
FMV97 98
HLB
T
GAS (
2)
GASO
LIO (1
)
COM
MUT
ATO
RE A
LTA-
BASS
A FI
AMM
ASW
ITCH
HIG
H-LO
W F
LAM
E
CONM
UTAD
OR
ALTA
-BAJ
A LL
AMA
pos 2
: BAS
SA F
IAM
MA/
LOW
FLA
ME/
1re
ALLU
RE/B
AJA
LLAM
A
INTE
RRRU
PTEU
R 2m
e-1r
e AL
LURE
pos 3
: AUT
OM
ATIC
O/A
UTO
MAT
IC/A
UTO
MAT
IQUE
/AUT
OM
ATIC
O
pos 1
: ALT
A FI
AMM
A/HI
GH F
LAM
E/2m
eALL
URE/
ALTA
LLA
MA
YVG
1SP
Gm
inYV
GS
TP
STC
NS TR
50 H
z 400
V
TP
STS
SAL
1314
FU
Z
YVg3
YVg1
YVg2
pos 0
: ARR
ESTO
/ ST
OP
KA2
HLG
HLg
SAM
A
12
30
6
KA1
UV
TV
SPA
YVG
P
11N1M
23
LAND
IS SQ
M 50
.481A
2
133
222
121
2125
1615
424
514
717
2726
1/2
KMV2
FMV
KMV3
KMV1
KMV3
KMV1
KMV1
KMV2
KTav
v
MP
UV
W
FMP
RS
TN
50 H
z 400
V
Q
T NSR
PE PE
SAsb
locc
o
REV
4.0
HLB
14DU
NGS
VDK 2
00-A
13
BLACK 31BLUE
BROWN
YELLOW-GREEN
N N
S3B4
T2T1
S3B4
T2T1
L1 L1
20-0
5-20
04
pag.20
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
TELE
RRUP
TOR
MOT
OR V
ENTI
LATO
RCO
NTAC
TEUR
MOT
EUR
VENT
ILATE
URRE
MOT
E CON
TROL
SWIT
CH (F
AN M
OTOR
)
EMPA
LME M
OTOR
BOM
BACO
NTAC
TEUR
MOT
EUR
POM
PEPO
MP
REM
OTE C
ONTR
OL SW
ITCH
CONT
ATTO
RE M
OTOR
E VEN
TILA
TORE
KMV1
FILT
RO D
E PRO
TECI
ON A
NTID
ISTU
RBIO
FILT
RE A
NTIP
ARAS
ITES
RELA
ISRE
LAY
FUSI
BLE
FUSI
BLE
MOT
OR V
ENTI
LADO
RM
UTEU
R VE
NTILA
TEUR
MOT
OR FA
N
MOT
OR B
OMBA
MOT
EUR
POM
PEOI
L PUM
P M
OTOR
TRAN
SFOR
MAD
ORTR
ANSF
ORM
ATEU
R D'
ALLU
MAG
EIG
NITI
ON TR
ANSF
ORM
ER
FOTO
CELU
LACE
LLUL
E UV
UV C
ELL
RELE
' TER
MIC
O M
OTOR
VEN
TILA
DOR
RELA
IS TH
ERM
IQUE
MOT
EUR
VENT
ILATE
URM
OTOR
THER
MAL
REL
AY (F
AN M
OTOR
)
RELE
' TER
MIC
O M
OTOR
BOM
BARE
LAIS
THER
MIQ
UE M
OTEU
R PO
MPE
MOT
OR P
UMP
THER
MAL
REL
AY
ESPI
A GA
SLA
MPE
DE G
AZGA
S LAM
P
ESPI
A DE
BLO
QUEO
LAM
PE D
E SEC
URIT
ELO
CK-O
UT LA
MP
RELA
ISRE
LAY
ESPI
A GA
SOLE
OTE
MOI
N M
AZOU
TOI
L LAM
P
CONT
ATTO
RE M
OTOR
E POM
PA
LAM
PADA
GAS
OLIO
LAM
PADA
GAS
LAM
PADA
DI B
LOCC
O
RELE
' TER
MIC
O M
OTOR
E VEN
TILA
TORE
RELE
' TER
MIC
O M
OTOR
E POM
PA
FOTO
CELL
ULA
TRAS
FORM
ATOR
E
MOT
ORE V
ENTI
LATO
RE
MOT
ORE P
OMPA
FUSI
BILE
KMP
RELE
'
KA2
RELE
'
HLg
HLG
HLB
FMV
FMP
UVTVMV
RELE
'
RELE
'
MP
KA1
FUSE
FU
ELEC
TROV
ALVU
LA G
AS D
E 1^
LLAM
A
ELEC
TROV
ALVU
LA G
AS P
ILOTO
ELEC
TROV
ANNE
GAZ
PILO
TEPI
LOT F
LAM
E SOL
ENOI
D GA
S VAL
VEEL
ETTR
OVAL
VOLA
GAS
PILO
TA
ELET
TROV
ALVO
LA G
ASOL
IO
ELET
TROV
ALVO
LA G
AS D
I SIC
UREZ
ZA
ELET
TROV
ALVO
LA G
ASOL
IO
PRES
OSTA
TO G
AS D
E MIN
IMA
POT.
PRES
SOST
AT G
AZ P
RESS
ION
MIN
GAS P
RESS
URE S
WIT
CH M
INPR
ESSO
STAT
O GA
S DI M
INIM
ASP
Gmin
YVGP
YVg2
YVg1
YVGS
THER
MOS
TAT C
HAUD
IERE
TERM
OSTA
TO C
ALDE
RA
TERM
OSTA
TO D
I SIC
UREZ
ZA
COM
MUT
ATOR
E GAS
OLIO
-GAS
INTE
RRUP
TEUR
MAZ
OUT-
GAS
CONM
UTAD
OR G
ASOL
EO-G
AS
TERM
OSTA
TO D
E SEG
URID
AD
COM
MUT
ATOR
E MAN
UALE
-AUT
OMAT
ICO
SWIT
CH (M
ANUA
L-AU
TOM
ATIC
))IN
TERR
UPTE
UR M
ANUE
L-AU
TOM
ATIQ
UECO
NMUT
ADOR
MAN
UAL-
AUTO
MAT
ICO
THER
MOS
TAT D
E SEC
URIT
E
ELEC
TROV
ANNE
GAZ
PET
ITE A
LLUR
EFI
RST S
TAGE
GAS
SOLE
NOID
VAL
VEEL
ETTR
OVAL
VOLA
GAS
DI P
RIM
A FI
AMM
AYV
G1
SAM
A
SAFE
TY TH
ERM
OSTA
T
SWIT
CH (O
IL-GA
S)SA
gG
STS
PRES
SOST
AT A
IRPR
ESOS
TATO
AIR
E
TERM
OSTA
TO C
ALDA
IABO
ILER
THER
MOS
TAT
STC
INTE
RRUP
TOR
GENE
RAL C
ON FU
SIBL
EIN
TERR
UPTE
UR G
ENER
AL A
VEC
FUSI
BLE
MAI
N SW
ITCH
WIT
H FU
SE
ANTJ
AMM
ING
FILT
ERFI
LTRO
ANT
IDIS
TURB
O
INTE
RRUT
TORE
GEN
ERAL
E CON
FUSI
BILE
ZQ
INTE
RRUT
TORE
DI L
INEA
INTE
RRUP
TEUR
DE L
IGNE
INTE
RRUP
TOR
DE LI
NEA
WOR
KING
SWIT
CH
PRES
SOST
ATO
ARIA
AIR
PRES
SURE
SWIT
CHSP
A
SAL
HLBT
ESPI
A DE
BLO
QUEO
REL
E TER
MIC
OLA
MPE
DE T
HERM
AL D
E SEC
URIT
ETH
ERM
AL LO
CK-O
UT LA
MP
LAM
PADA
DI B
LOCC
O TE
RMIC
O
PAGI
NA D
I
CONT
ATTO
RE M
OTOR
E VEN
TILA
TORE
KMV2
CONT
ATTO
RE M
OTOR
E VEN
TILA
TORE
KMV3
REM
OTE C
ONTR
OL SW
ITCH
(FAN
MOT
OR)
CONT
ACTE
UR M
OTEU
R VE
NTILA
TEUR
TELE
RRUP
TOR
MOT
OR V
ENTI
LATO
R
REM
OTE C
ONTR
OL SW
ITCH
(FAN
MOT
OR)
CONT
ACTE
UR M
OTEU
R VE
NTILA
TEUR
TELE
RRUP
TOR
MOT
OR V
ENTI
LATO
R
EXTR
A SA
FETY
GAS
SOLE
NOID
VAL
VEEL
ECTR
OVAN
NE G
AZ D
E SEC
URIT
EEL
ECTR
OVAL
VULA
GAS
DE S
EGUR
IDAD
YVg3
ELET
TROV
ALVO
LA G
ASOL
IOOI
L SOL
ENOI
D VA
LVE
ELCT
ROVA
NNE M
AZOU
TEL
ECTR
OVAL
VULA
DE G
ASOL
EO
OIL S
OLEN
OID
VALV
EEL
CTRO
VANN
E MAZ
OUT
ELEC
TROV
ALVU
LA D
E GAS
OLEO
OIL S
OLEN
OID
VALV
EEL
CTRO
VANN
E MAZ
OUT
ELEC
TROV
ALVU
LA D
E GAS
OLEO
0001
0203
0405
0607
0809
A
0001
0203
0405
0607
0809
B C D E
A B C D E
IND.
MO
DIFI
CA
SOST
.DA
SOST
.IL
IND.
MO
D.
PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.
DATA
-FIR
MA
DATA
FIRMA
CONT
ROLL
ATO
DESC
RIZI
ONE
MO
DIFI
CA
DISE
GNAT
O
DATA
FIRMA
COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE. A TERMINE DI LEGGE E' VIETATO RIPRODURRE O
CONT
ROLL
O D
I TEN
UTA
APPA
RECC
HIAT
URA
UFF.T
ECNI
CO-S
ETTO
RE EL
ETTR
ICO
DENO
MIN
AZIO
NE
SIST
. RIV
ELAZ
.CO
DICE
MO
TORI
DUTT
ORE
S.p.A.
BEM
4314
1M
ULTI
CALO
R 10
00.1
MD
LAND
IS S
QM
50.4
81A2
LAND
IS L
FL 1
.622
DUNG
S VD
K 20
0-A
UV06
-05-
2004
(0° )
VIII:
CAM
MA
NON
UTILI
ZZAT
A
CAM
MA
DI R
EGOL
AZIO
NE A
RIA
PER
FIAM
MA
DI A
CCEN
SION
E GAS
OLIO
CAM
MA
DI R
EGOL
AZIO
NE A
RIA
PER
FIAM
MA
DI A
CCEN
SION
E GAS
CAM
MA
DI R
EGOL
AZIO
NE A
RIA
PER
BASS
A FI
AMM
A GA
SOLIO
CAM
MA
DI R
EGOL
AZIO
NE A
RIA
PER
BASS
A FI
AMM
A GA
S
CAM
MA
DI R
EGOL
AZIO
NE A
LTA
FIM
MA
( GAS
-GAS
OLIO
)CA
MM
A DI
REG
OLAZ
IONE
ARI
A CH
IUSU
RA TO
TALE
CAM
MA
NON
UTILI
ZZAT
A
(0°)
II:
(25°
) V:
(15°
) IV:
(15°
) III:
(0°)
VII:
(25°
) VI:
(70°
) I:
0
I
00
IIIII
IV
0
VVI
IVI
0
VIII
2/2
pag.21
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
MU
LT
ICA
LO
R 1
000.
1 M
D
4
8939
28
29
33
37
3857
3
1
5
42
3130
32
2
6
10
11
53
54
0°15
°30
°45
°
60°75° 90°
PG
ME
XIT
0I
0
AU
TO
0OIL
GA
S
OIL
GA
S
RE
SE
T
21 19 20
FIND
ER
FIND
FIND
FIND
ERFI
NDER
137 12
1516 17
18
K6
RW
F 4
0PG
MP
GM
EX
ITE
XIT
2322
40
2524
1427
35
3436
4948
5547
46
5153
44
5051
45
4152
58
pag.22
techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD
TC = SHORT HEAD TL = LONG HEAD
Multicalor 1000.1 MDN° DESCRIPTION code
1 - AIR PRESSURE SWITCH DG 10 U Q112/22 - AIR INTAKE SET GRPA1003 - WIELAND PLUG 6 pin E2264 - COVER BFC09255/0385 - GLASS BFC020046 - PEED WINDOM FRAME BFC020067 - MOTOR 22 kW M170/618 - FAN RG-630 BFV10401/0019 - AIR CONVEYOR BFC0826010 - CONVEYOR RING BFC08258/03811 - AIR INTAKE GRCA63012 - CONTROL BOX BASE LANDIS A40113 - CONTROL BOX LANDIS LFL1.622 A11314 - IGNITION TRANSFORMER BRAHMA T8 T10115 - REMOTE CONTROL SWITCH AEG LS15K.00 R621/516 - REMOTE CONTROL SWITCH (PUMP) AEG LS11K.00 R621/417 - MOTOR THERMAL RELAY AEG B18K-320 R521/1618 - MOTOR THERMAL RELAY (PUMP) AEG R521/519 - MAIN SWITCH cod.40100I1509 R102020 - RESET BUTTON C5559AL R102121 - SELECTOR R1020/522 - LAMP Elettrospring EL/N-SC4 E151023 - FUSE SUPPORT FUSIT FH-B528 E802/224 - RELÉ BASE Finder 5532 R905
Finder 5534 R90625 - RELÉ Finder 5532 R711
Finder 5534 R71226 - TIMER AEG SDE R52727 - UV CELL LANDIS QRA 2 A20528 - IGNITION CABLE TC BFE01403/329 - IGNITION ELECTRODES SET E612/130 - PIPE TC31 - ROD TC32 - GAS FIRING HEAD33 - FRONT DISC34 - OIL FIRING HEAD35 - COIL EL011 V52336 - CONNECTOR WITH RECTIFIER V1119/0737 - INNER ASSEMBLY TC38 - BLAST TUBE TC BFB07022/10339 - GASKET ISOMART BFG04059/140 - ANTIJAMMING FILTER S132/441 - AIR DAMPER MOTOR LANDIS SQM50.481A2 M212/9142 - SILENCER BAA1100143 - OIL PUMP SUNTEC T5C105 P1481/0444 - COUPLING MP501/445 - PUMP MOTOR 4 kW ABB M147/9146 - OIL VALVE LUCIFER 121 V175147 - COIL LUCIFER 3541 V52248 - OIL VALVE PARKER PM133IV V175/949 - COIL PARKER ZB 14 V516/150 - OIL FILTER 70501/03 S107/551 - HOSES TN 18X1500 S90252 - MANOMETER CEWAL R1/4 D50-40BAR S601/153 - PILOT GAS VALVE DUNGS SV-DLE 507 V1994/2154 - COIL DUNGS55 - OIL VALVE SUNTEC TV40011 P148156 - NOZZLE BERGONZO kg/h 65057 - MODULATING UNIT LANDIS RWF 40 E1215
pag.23
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
NOTE :
La ECOFLAM S.p.A si riserva il diritto di apportare ai prodotti quelle modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche principali.
Ecoflam S.p.A.via Roma, 64 - 31023 RESANA (TV) - Italy - tel. 0423/715345 r.a.telefax 0423/715444 (Italy 480009 - Export 480873, 715538).http://www.ecoflam.it - e-mail: [email protected]
ECOFLAM S.p.A. reserves the right to make any adjustments, without prior notice, which it considers necessary or usefulto its products, without affecting their main features.