GAS TEC LB1360 27.05.2004 Multicalor 700.1 MD Multicalor 800.1 MD Multicalor 1000.1 MD Multicalor 1200.1 MD Light oil / Natural Gas 300 mbar MODELS techniques for energy saving GAS / LIGHT-OIL DUAL BURNERS

Transcript of GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360...

Page 1: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

G A S T E C

LB1360

27.05.2004

Multicalor 700.1 MDMulticalor 800.1 MDMulticalor 1000.1 MDMulticalor 1200.1 MD Light oil / Natural Gas 300 mbar

MODELS

techniques for energy saving

GAS / LIGHT-OIL DUAL BURNERS

Page 2: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.2

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

mbar

2000 3000 4000 5000 6000 7000 8000 9000 10000

10

12

14

16

1000

18

20

22

-2

11000

0

2

4

6

8

0

24

26

28

30

12000 kW13000

32

34

36

Multicalor 700.1 MD

Multicalor 800.1 M

D

Multicalor 1000.1 M

D

Multicalor 1200.1 M

D

WORKING FIELDS

Burner output

Bac

kpre

ssur

e in

com

bust

ion

cham

ber

E D - D1

G

CBA

F I

L

M

H

N

O

SUNTECSUNTECSUNTEC

OVERALL DIMENSIONS

Models Multicalor 700.1 MD 800.1 MD 1000.1 MD 1200.1 MDThermal power max. kW 7.250 8.500 10.500 13.100

kcal/h 6.250.000 7.327.500 9.052.000 11.293.100Thermal power min. kW 1.500 2.000 2.500 2.700

kcal/h 1.290.000 1.724.000 2.155.000 2.327.600Max. capacity (Natural Gas) Nm3/ h 729 855 1.056 1.318Min. capacity (Natural Gas) Nm3/ h 150 201 251 272Max. light oil flow rate kg/h 613 718 887 1.107Min. light oil flow rate kg/h 126 169 211 228Gas pressure mbar 300 300 300 300Voltage 50 Hz V 230/400 230/400 230/400 230/400Motor kW 15 18,5 22 37Rpm N° 2800 2800 2800 2800Fuels: Nat. Gas LHV = 35,9 Mj/Nm3 = 8.570 kcal/Nm3; Light Oil LHV = 10.200 kcal/kg max. 1,5° at 20 °C

D = Short headD1= Long head

MODELS A B C D D1 E F G H I L M N OMulticalor 700.1 1215 585 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 800.1 1285 655 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 1000.1 1315 685 630 570 - 1420 420 800 480 460 460 M20 195 232Multicalor 1200.1 1425 795 630 570 - 1420 450 800 480 460 460 M20 195 232

Page 3: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.3

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

CONNECTION TO THE GAS PIPELINE Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verifythat the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gaugeconnector, then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats tothe desired temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end ofthe test the burner will be enabled to run the start-up sequence.

ELECTRICAL CONNECTIONSAll burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral forauxiliary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors onburner as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtai-ning in the country in question.

BURNER START-UPBefore starting the burner, make sure it is mounted correctly. Then check connections are correct according to thediagram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make surevoltage corresponds to burner plate data. The connection diagram and start-up cycle are shown separately. Forwiring from control box to burner, see the enclosed connection diagram. Pay particular attention to neutral andphase connections : never exchange them!. Vent air and impurities of gas pipe. Check gas pressure conforms to thelimits stated on the burner plate when connecting a master gauge to the test port provided on the burner. Blowermotor starts and pre-purging begins. Since pre-purging has to be carried out with the max.air delivery, the burner control circuit turns the air damper to the max. delivery position bythe air servocontrol in approximately 30 seconds time. When the servocontrol is fully open,a signal to the electronic control unit starts the 66 seconds pre-purge cycle. At the end ofthe prepurging time, the air servocontrol gets to the Low Flame position so that burnerignition is ensured at min. output. Simultaneously the ignition transformer receives voltageand after 3 seconds (pre-ignition) opens the pilot gas valve. Fuel flows to the combustion head and ignites. Twoseconds after pilot gas valves have opened, the ignition transformer is excluded from the circuit. In case of no igni-tion the burner goes to lock-out within two seconds. After 6 sec. open the working gas valve, governed by the gasfiring butterfly valve.Now the burner is operating at the min. firing rate (about 30% of the max. firing rate). The airservocontrol runs at the Low Flame position and in case the temperature control has to be set at the max. output itgoes to a fully open position of air damper and butterfly valve. During the burner-off periods the air damper closesup fully.

0

12

0 - STOP1 - GASOLIO2 - GAS

LIGHT-OIL

ADJUSTING THE COMBUSTION PROCESSIMPORTANT: to obtain the right adjustment of the combustion and thermal capacity it is important to analyzethe reducts of combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment isdone simultaneously, together with the analysis of the products of combustion, making sure that the measuredvalues are suitable and that they comply with current safety standards. On this matter, please refer to the table andfigure below.THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.

NOTE: ALL SAFETY DEVICES (AIR PRESSURE SWITCH, MINIMUM GAS PRESSURE SWITCH, GAS SOLE-NOID VALVES AND GAS GOVERNOR) SHALL BE DULY SEALED AFTER CALIBRATION AND BUR-NER START UP BY ECOFLAM’S TECHNICIANS.

Page 4: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

CALCULATING THE BURNER CAPACITYTo calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters)on the counter and the time of the reading in seconds.Proceed with the calculation using the following formula: x f = kWe

sec

e = Litres gassec = Time in secondG20 = 34,02G30 = 116G31 = 88

f

pag.4

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTORRemove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key providedfor. Description:

I - High flame operating opening position adjusting cam (Light-Oil /Gas)II - Limit switch for the air damper position at burner’s shut downIII - Ignition flame opening position adjusting cam (Gas). IV - Ignition flame opening position adjusting cam(Light-Oil)V - Low flame operating opening position adjusting cam (Gas)VI - Low flame operating opening position adjusting cam (Light-Oil)VII - Not used camVIII - Not used cam

Manual change

The control box starts the burnerfan, to carry out the prepurging ofthe combustion chamber, andcheks the vent air pressure throughthe air pressure switch. At the endof prepurging, the ignition tran-sformer cuts-in and generates aspark between the electrodes. Atthe same time the two gas valvesopen (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out,is granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gaslack or a major pressure drop, the minimum air pressure switch shuts down the burner.

LANDIS & STAEFA, Model LFL1.622 OPERATING CYCLERef. Descriptiont1 Duration Waiting time for confirmationt2 of air pressuret3 Preventilation timet4 Safety timet5 Pressurizing time

Time for enabling operation of the main gas valve on minimum capacity

t6 Time for enabling operation of the main gas valve on maximum capacity

Duration

8”66”2”4”

10”

10”

Rivelazionedi fiamma

Spia di blocco

Valvola gas

Serranda aria

Serranda gas

Trasformatoredi accensione

Pressostato aria

Motore ventilatore

Pressostato gas

0min

100%

t1 t2

t4

t3

t6t5

Ciclo di funzionamento normaleCiclo di funzionamento

in mancanza di fiamma all'accensionet1 t2

t4

t3

Consensomin./max. potenza

Gas manostat

Fan motor

Air Switch

Ignition transformer

Gas valve

Min/max capacity enabling device

Air damper

Gas damper

Flame detector

Cut-out pilot lamp

Normal operating cycleOperating cycle in the event of

ignition failureNormal operating cycle

Page 5: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.5

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

+

--

Part. 1

Part. 2

Part. 3

-

+

-COMMUTATORE

0

AUTO

0 = bloccaggio degli apparati per il funzionamento in una posizione intermadia = funzionamento alla massima potenza = funzionamento alla minima potenza AUTO = funzionamento automatico

ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GASPosition the selector placed on the control panel on position 2 and proceed as follows: Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gasflow, as established by analyzing the combustion process.

ADJUSTING THE MAXIMUM CAPACITY OF THE GASPosition the selector, situated on the control panel, on position 1 and proceed as follows:Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in thegovernor.

ADJUSTING THE MAXIMUM AIR FLOW RATE Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;The correct air flow as established by analyzing the combustion process.

ADJUSTING THE INTERMEDIATE BURNER CAPACITY Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment ismade as outlined below. Repeat the operation for the other cam points.Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the positionof the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.

AIR ADJUSTMENT

operating elements locked in an intermediatepositionoperation on maximum capacity operation on minimum capacity automatic operation

SELECTOR

SETTING THE FIRING HEAD

+-

Page 6: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.6

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

The ionization current is checked by inserting a microam-meter with an end of scale of 50 µA (d.c.) in series withthe ionization probe. A faulty position of the electrodecan lead to a reduction in the ionization current and causea safety cut-out of the burner due to a flame detection fai-lure. In this case, check the position of the electrode, itselectric connection and the earthing of the burner. Theionization current is normally > 20 µA.

REMOVING THE FIRING HEAD

IONIZATION CURRENT

ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCHUnscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feedpressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for L.P.G.nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw up cover M

ADJUSTMENT OF THE AIR PRESSURE SWITCHUnscrew screws A and B and remove cover C.- Set the pressure switch to the minimum byturning regulator D to position 1. - Start the burner and keep in low flame running, while checking that combustion is cor-rect. Through a small cardboard, progressively obstruct the air intake until to obtain aCO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressureport E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase theadjustment value of the air pressure switch until to have the burner lockout. Remove theobstruction from the air intake, screw on the cover C and start the burner by pressing thecontrol box rearm button.

Note: The pressure measured at pressure port E must be within the limits of the pressu-re switch working range. If not, loose the locking nut of screw F and gradually turn thesame: clockwise to reduce the pressure; counterclockwise to increase. At the end tighten thelocking nut.

2,55

10 15

50

25

35

30

4045

20

0,4

0,6 0,9

3,0

1,5

2,1

1,8

2,42,7

1,2

I

L

MN

A

B

CD

E

F

GH

gas pressure switch

air pressure switch

22 23

LANDIS LFL 1.622

Fotocellula

min 70 µA

Microamperometro fondo scala 1000 µA

PHOTORESISTOR

Microamperometerfull scale 1000 µA

Page 7: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.7

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

VL

VR

A

RPR

VS

OIL DELIVERY ADJUSTMENTThe diagram illustrates the fuel feeding system of these types of burners, which incorpora-tes a by-pass nozzle with oil flow regulation on its return pipe. The oil supply isvaried by acting on the nozzle through the pressure in the return line. Max. oil supplyis therefore reached when the pressure in the pump line is about 22 bar and the returnline is fully closed; min. oil supply when the return line is fully open. Relevant pres-sure readings in the return line are as follows:

Pump pressure 22-25 bar.Max Burner output, return oil pressure:FLUIDICS nozzle : 16 ÷19 bar.BERGONZO nozzle : 20 ÷24 bar.

Min Burner output, return oil pressure:FLUIDICS nozzle : 6 ÷9 barBERGONZO nozzle : 4 ÷8 bar

+-

OPERATION OF BURNER WITH LIGHT-OIL FUEL Once having installed the burner, check the following items:- The burner power feeding and the main line protection fuses- The correct length of pipes and that the same are sealed.- The type of fuel, which must be suitable for burner.- The connection of boiler’s thermostats and all the safeties.- The motor rotation direction.- The correct calibration of the motor’s thermal protection.When all the above mentioned conditions are checked and accomplished, it is possible to go on with burner’s tests.Power the burner. The control box feeds the ignition transformer and the burner’s motor at the same time, whichwill run a prepurging of the combustion chamber for about 20 sec.At the end of prepurging, the control box opens solenoid valves and the burner starts. After a safety interval of 5seconds and a correct ignition, the control box turns off the ignition transformer and, 10 seconds later, sets themotorised air damper to its maximum opening (High flame). In case of faulty ignition, the control box switches theburner into safety condition within 5 second. In such a case, the manual rearming of the burner shall not take placebefore 30 seconds have elapsed from the burner’s safety shutdown. In order to obtain an optimal combustion, it isnecessary adjust the LOW - HIGH flame air flow, according to the instruction given further on. During such aphase, it will be possible to manually switch between HIGH and LOW flame and viceversa, through the High/Lowflame switch. At the end of the adjusting phase, leave the switch in position AUTO.

0

12

0 - STOP1 - GASOLIO2 - GAS

LIGHT-OIL

HYDRAULIC CIRCUIT1 - Hose 2 - Oil filter3 - Oil cockA - Suction R - ReturnVS - Safety oil valveVL - Working oil valveVR - Return oil valve PR - Oil pressure switch

1

1

2 3

Page 8: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

1) Remove the cap A of the pres-sure regulating valve TV.

2) Loosen the fixing nut B anduse an allen wrench on the screwC to adjust the delivery oil pres-sure. To increase the pressureturn clockwise, to decrease thepressure turn anticlockwise.

3) Tighten the nut B and payattention not to turn also theadjusting screw.

4) Screw on the cap A, back toits previous position.

pag.8

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

SUNTEC T.......

PRIMING AND ADJUSTMENT OF OIL PUMP1 - INLET 2 - RETURN

3 - BLEED AND PRESSURE GAUGE PORT4 - VACUUM GAUGE PORT 5 -6 - TO NOZZLE

VERIFY:- That piping system is perfectly sealed;- That the use of hoses is avoided whenever is possible (use copperpipes preferably);- That depression is not greater than 0,45 bar, to avoid pump’scavitation;- That check valve is suitably designed for the duty;

The pump pressure is set at a value of 22-25 bar during the testing of burners. Before starting the burner,bleed the air in the pump through the gauge port. Fill the piping with light-oil to facilitate the pump pri-ming. Start the burner and check the pump feeding pressure. In case the pump priming does not takeplace during the first prepurging, with a consequent, subsequent lock-out of the burner, rearm the burner’slock-out to restart, by pushing the button on the control box. If, after a successful pump priming, the bur-ner locks-out after the prepurging, due to a fuel pressure drop in the pump, rearm the burner’s lock-out torestart the burner. Do never allow the pump working without oil for more than three minutes. Note: befo-re starting the burner, check that the return pipe is open. An eventual obstruction could damage the pumpsealing device.

1

2

6

34

PRESSURE REGULATING VALVE ADJUSTMENT

A

B

C

B

A

Page 9: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.9

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

Page 10: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.10

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

Page 11: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.11

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

A - Reset keyB - Operating lamps (orange=light-oil; green= gas)C - Selector switch: 0 = Loking of devoices for operating at intermediate outputs = Operation at max. output = Operation at min. outputAUTO = Automatic operation

D - ON/OFF switchE - Fuse holderF - Selector: 0 = STOP 1 = Light-oil operation 2 = Gas operationG - Termal lock-out lampH - Modulating unit RWF 40

0I

0

AUTO

0

OIL GAS

OIL GAS

RESET

K6

RWF 40

PGMPGM EXITEXIT

E

H

F

C

A

D

BG

DESCRIPTION OF CONTROL PANEL

MAINTENANCEYEARLY CHECKSThe burner’s periodical check (firing head, electrodes etc.) must be carried out by authorised personnel one or two times peryear, depending on the utilisation. Before going on with the maintenance controls of the burner, it should be advisable to checkits general conditions, according to the following steps:Unplug the burner; close the fuel cock; shut down the gas supply; remove burner’s cover and clean the fan and air intake; cleanthe firing head and check the electrode’s position; reassemble all the parts; check the connection’s sealing; check the chimney;start the burner and check the combustion flue (CO2 = 9.5 ÷ 9.8; O = lower than 75 ppm).

BEFORE EVERY INTERVENTION CHECK:

POSITION OF IGNITION ELECTRODES

3 ÷ 4 mm

5 ÷ 6 mm

NOZZLE CLEANING AND REPLACEMENT

Use only the suitable box wrench provided for this operation to remove the nozzle, taking care to notdamage the electrodes. Fit the new nozzle with the same care.Note: Always check the position of electrodes after having replaced the nozzle (see illustration). A wrongposition could cause ignition troubles.

Page 12: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.12

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

The electric system is duly powered and the burner is plugged in. The gas pressure must be the suitable one and the gas cock open. The control devices must be properly connected. When all the above conditions are met, start the burner by pressing the lockout enable pushbutton. Check the burner’s cycle.

THE BURNER DOES NOT START:Check the ON/OFF switch, the thermostats, the motor and the gas pressure. The master switch is in position “0”. Fuses are blown out. The control box is faulty.

THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE:Check the fan and the air pressure. Check the air pressure switch. Control box faulty. Ignition transformer faulty. Check the ignition cable. Electrodes are dirty or in wrong position. Nozzles are clogged or worn. Filters are clogged. Light-oil pressure is too low. Combustion air’s flow rate too high related to nozzle output.

THE BURNER RUNS THE PREPURGING BUT DOES NOT IGNITE:Check the position of the electrodes; check the ignition cable; Check the ignition transformer; Check the control box.

THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER THE SAFETY TIME:Check phase and neutral for a correct connection. Check gas solenoid valve. Check the position of ionisation probe and its connection. Check the control box. Check nozzles (clogged or worn). The photoresistor does not detect the flame. The filters are clogged. Light-oil pressure too low. Combustion air’s flow rate too high related to nozzle output.

THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER FEW MOMENTS:Check gas governor and gas filter. Check gas pressure through a manometer. Check ionization value (min. 70 µA).

THE BURNER DOES NOT SWITCHES TO HIGH FLAME:Manual selector switch in wrong position. Faulty control box. High flame solenoid valve’s coils faulty.Air damper’s jacket faulty or wrongly adjusted.

Page 13: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.13

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

RWF 40 MICROPROCESSOR REGULATOR

Display:analog input 1(actual value)

Display: Set point SP1

Decrease value

Programming key

Manual operation

Auxiliary contact

Increase value

EXIT key.

Burner operation

Reduce powerCLOSE/1st Stage

Increase powerOPEN/2nd Stage

Two-stage operation

Description of display and keys on the RWF 40 microprocessor regulatorThe figure shows the normal display indicating

the actual value and the programmed setpoint, and equally important,

gives the meaning of thesingle keys and indicator Leds.

Configuration level

User Level

Normal display

Parameters level

PGM

PGM

PGM

PGM PGMPGM

PGM PGM

PGM PGM

min 2s

min 2s

min 2s

Exit

PROGRAMMING LEVELS

Page 14: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.14

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

SETTING PARAMETERSWhen the burner is ignited all displays of the regulator light up. The set point display will blink for about 10 seconds. The valuein the upper field of the display (red) indicates the actual value. The value in the lower field of the display (green) indicates the setpoint currently programmed. CHANGING THE SET POINTTo change the set point, proceed as follows: ---- Press the PGMPGM button to access the user level. SP1* will appear in the lower display---- Change the value of set point SP1 using the t and s keys.▼e ▲. ---- After a 2 second delay the value set is stored automatically – Toreturn to normal display press EXITEXIT. ** The value of SP1 depends on the value set previously in configuration level C111.SETTING PID PARAMETERSPID parameters are factory set to standard mean values. The operation of the regulator can be self-adapted to suit the system byactivating the “tunE” function. The regulator will set the PID parameters automatically. To activate the “tunE” function proceedas follows: ---- With the burner in operation, press PGM PGM + ▼. ---- the caption “tunE*” will blink in the display. – When “tunE” stopsblinking, the self-adaptation routine has been completed. ---- Confirm the computed parameters by pressing the ▲ key for 2 seconds. ** The “tunE” function cannot be activated in Manual mode, or when the burner is off. The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-ve action time dt and the integral action time rt. To change parameters Pb1, dt and rt, proceeds as follows: ---- Press the PGMPGM button to access the parameters level. ---- To move fromone parameter to the next, press PGMPGM . ---- When Pb1 is displayed, the value can be increased or decreased using the s and t keys. ----Confirm the changed parameters by pressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored auto-matically. ---- Press PGMPGM to access the next parameter. ---- When dt is displayed, repeat the procedure described above. ---- Press PGMto access the next parameter. ---- When rt is displayed, repeat the procedure above. ---- To return to normal display press EXITEXIT. DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFFThe regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicatesthe upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows: ---- Pressthe PGMPGM key to access the parameters level. ---- To move from one parameter to the next, press PGMPGM . ---- When HYS1 is displayed(burner ignition differential-stage II), increase or decrease the value using the ▼ and ▲ keys. ---- Confirm the changed parameters bypressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored automatically. ---- Press PGMPGM to access thenext parameter. ---- When HYS2 is displayed (burner shutoff differential-stage II), repeat the procedure described above. ---- PressPGMPGM to access the next parameter. ---- When HYS3 is displayed (upper shutoff differential) repeat the procedure described above. ---- To return to normal display press EXITEXIT.

MANUAL/AUTOMATIC MODETo access “MANUAL” mode, press and hold EXITEXIT for at least 5 seconds. Manual mode can only be selected when the burner isin operation. It is deactivated automatically when the burner shuts off. When the LED above the hand symbol is alight, the regu-lator is in manual mode and the position of the servocontrol can be changed using the ▼ and ▲ keys. The LEDS on the front ofthe regulator indicate whether the servocontrol OPEN or CLOSE command is currently active. Pressing the ▼ key the servocon-trol OPENS. Pressing the ▲ key the servocontrol CLOSES. To select automatic mode press and hold EXITEXIT for at least 5 seconds.The LED above the hand symbol goes out and the regulator reverts to automatic.

CLIMATIC COMPENSATIONThe RWF 40 regulator can be set with the set point interlocked to the external probe. To select this operating mode, proceed asfollows: ---- Connect the required probe as in the wiring diagram. ---- Change the regulator settings. When using an external probethe regulator must be set as follows: ---- Press the PGMPGM key to access the configuration level. When the caption C111 (XXXX) isdisplayed, use the ▲ key to access the second figure (XXXX). Use the ▼ key to select the type of probe (XX3X). ---- Confirm thechange of parameters by pressing PGMPGM. If this is not done within 2 seconds, the value is stored automatically ---- Press PGMPGM toaccess the configuration level. When the display reads C112 (XXXX), use the ▲ key to access the second figure (XXXX). Press the▼ key to set the type of probe (XX3X). ---- Confirm the changed parameters by pressing PGMPGM. ---- If confirmation is not givenwithin 2 seconds the value will be stored automatically. ---- To return to normal display press EXITEXIT. To establish the heating curve, proceed as follows: ---- Press PGMPGM to access the parameters level. ---- Press PGMPGM to move from one parameter to the next. ---- When the letter H isdisplayed (heating curve gradient), increase or decrease the value using the ▼ and ▲ keys. ---- Confirm the changed parameters bypressing PGMPGM. ---- If confirmation is not given within 2 seconds the value will be stored automatically. ---- To return to normal display press EXITEXIT.

Page 15: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.15

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

PROBE CONNECTION DIAGRAMS

SPH

60

80

100

0

20

40

SPL

120

140

160

20 15 10 5 0 -20-15-10-517.5 12.5 7.5 2.5 -2.5 -17.5-12.5-7.5

0.20.40.60.811.21.41.61.822.22.42.62.833.23.43.63.84

External temperature (iC)

Hea

tin

g c

urv

e g

rad

ien

t (H

)

PARAMETERIZATION

Bo

iler

tem

per

atu

re s

et p

oin

t (i

C)

Cod.S704

Cod. S721Cod.S731

S731/1S731/2S731/3S731/4

Cod.S720/1

Connection for probeQAE2..(passive probe)Water probeConfiguration codeC111 = 9XXX

Connection for probeFT-TP/..(passive probe)(Degusa probe)Configuration codeC111 = 5XXX

Connection for probe QBE620-P..(active probes)Configuration code C111 = GXXXS731 - 0…4 bar / 0…400 kPa QBE620-P4 S731/1 - 0…10 bar / 0…1 MPa QBE620-P10 S731/2 - 0…16 bar / 0…1.6 Mpa QBE620-P16 S731/3 - 0…25 bar / 0…2.5 MPa QBE620-P25 S731/4 - 0…40 bar / 0…4 MPa QBE620-P40

Connection for probeQAC22 (passive probe)Configuration code C111 = XX3XC112 = XX1X

1 2 3 4

RWF 40

B M

G1+ M1

QAE22A

1 2 3 4

RWF 40

B M

B9 M9

QAC2..

1 2 3 4

RWF 40

GL M

G+ M1

OBE620-P..U1

G- U1

Page 16: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.16

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

- Situation - The number 1999 blinks in the display as the actual value, with the set point value displayed normally.

- Cause - The real value is not being measured. This means that the upper or lowerlimit of the measurement range on analog input 1 (real value) has been exceeded.

- Remedy - Check the electrical connections and the state of the probe. If the probeis faulty, the regulator will not indicate the real value of the physical quantity monitored. This will result in automatic shutdown (failsafe), deactivation of theself-adapt function and inhibition of manual operation. The response of the auxiliary contact will depend on the configuration of parameter C113.

- Situation - The number 1999 blinks in the display as the actual value, with tAshowing in the set point field.

- Cause - The external temperature is not being measured. This means that theupper or lower limit of the measurement range on analog input 3 (real value) hasbeen exceeded.

- Remedy - Check the electrical connections and the state of the probe. If the probeis faulty, the regulator will not indicate the real value.

- Situation - The number 1999 blinks in the display as the actual value, with SP .Eshowing in the set point field.

- Cause - The external set point value is not being measured. This means that theupper or lower limit of the measurement range on analog input 2 (real value) hasbeen exceeded.

- Remedy - Check the electrical connections and the external set point signal. If theprobe is faulty, the regulator will not indicate the real value of the physical quantitymonitored. This will result in automatic shutdown (failsafe), deactivation of the self-adapt function and inhibition of manual operation.

ERROR/FAULT INDICATIONNUMBERS BLINKING IN DISPLAY

Analog input 1 (actual value)Pt1000, 2-wire, Landis & Staefa IEC 751

5FT-TP/… (passive probe)

Ni1000, 2-wire, Landis & Staefa9QAE2 … (passive probe - water probe)

Standard Signal DC 0…10 V QBE620P…(active probe - pressure probe) G

C111 – C112 INPUT CONFIGURATION INDICATIONS

Analog Input 3 (external temperature)No function (probe not active) 0External probe Pt 1000, 2-wire,

1QAC22 (passive probe)

AUXILIARY CONTACT, TYPE OF REGULATOR, SET POINT “SP1”BLOCK C112. Parameter configuration

Set point “SP1”Set point SP1 - data input from keys 0Set point SP1 - interlocked to external probe (configure) 1

Page 17: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.17

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

A

Insert the RWF 40 regulator through the relative opening in the electrical panel (A). Insert the fixing anchors and screws into the slots, and secure the unit to the panel (B). To open the regulator, squeeze the cover from the ends as shown, and lift out (C).

WHEN REPLACEMENT IS NECESSARY, PROCEED AS SHOWN IN FIGURES A-B-C BELOW

B C

Page 18: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.18

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

Parameter Display Ecoflam setting Ecoflam setting Ecoflam setting (passive probe) (passive probe) (active probe)

QAE22 FT-TP/1000 QBE620-P...Limit value of limit comparator AL 0 0 0Switching differential for limit comparator HYSt 0 0 0Proportional band Pb.1 8 8 1Derivative time dt 20 20 3Integral action time rt 80 80 15Dead band (neutral zone) db 0.5 0.5 0.5Actuator running time (sec.) tt 25 25 25Switch-on threshold burner / stage II HYS1 -2 -2 -0.2Switch-off level stage II HYS2 0 0 0Upper switch-off threshold HYS3 5 5 0.5Response threshold q 0 0 0Heating curve slope H 2 2 2Parallel displacement P 0 0 0

PARAMETERS

Parameter Display Ecoflam setting(passive probe) (active probe) QBE620-P...

QAE22 FT-TP/1000 -P4 -P10 -P16 -P25 -P40Analog input 1, 2 and 3; setpoint changeover / shift C111 9030 5030 G000 G000 G000 G000 G000Limit comparator; controller type; setpoint 1; locking C112 0010 0010 0010 0010 0010 0010 0010Unit address; decimal place / unit, signal for out-of-range C113 0110 0110 0110 0110 0110 0110 0110Measured value range start analog input 1 SCL 0 0 0 0 0 0 0Measured value range analog input 1 SCH 100 100 4 10 16 25 40Measured value range analog input 2 SCL2 0 0 0 0 0 0 0Measured value range analog input 2 SCH2 0 0 0 0 0 0 0Lower setpoint limit SPL 60 60 0 0 0 0 0Upper setpoint limit SPH 88 88 4 10 16 25 40Actual value correction,analog input 1 OFF1 0 0 0 0 0 0 0Actual value correction,analog input 2 OFF2 0 0 0 0 0 0 0Actual value correction,analog input 3 OFF3 0 0 0 0 0 0 0Filter time constant for digital filter, dF1 1 1 0 0 0 0 0analog input 1

CONFIGURATION

Page 19: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.19

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

3M

MV

W1

V1U

1

U2

V2W

2

QBE6

20-P

GLM

U1

TP

LINE

LOAD

M1

LAN

DIS

RW

F 40

LN

QQ1

4Y2

Y1Q1

3G+

G-B9

U1G1

+M9

- +

TP

3M

182

1LA

NDIS

LFL 1

.622

104

36

58

79

1412

1113

1615

1732

2220

1921

2423

31

0001

0203

0405

0607

0809

A

0001

0203

0405

0607

0809

B C D E

A B C D E

IND.

MO

DIFI

CA

SOST

.DA

SOST

.IL

IND.

MO

D.

PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.

DATA

-FIR

MA

DATA

FIRMA

CONT

ROLL

ATO

DESC

RIZI

ONE

MO

DIFI

CA

DISE

GNAT

O

DATA

FIRMA

COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE. A TERMINE DI LEGGE E' VIETATO RIPRODURRE O

CONT

ROLL

O D

I TEN

UTA

APPA

RECC

HIAT

URA

UFF.T

ECNI

CO-S

ETTO

RE EL

ETTR

ICO

DENO

MIN

AZIO

NE

SIST

. RIV

ELAZ

.CO

DICE

MO

TORI

DUTT

ORE

S.p.A.

PAGI

NA D

I

12

SA

BEM

4314

1M

ULTI

CALO

R 10

00.1

MD

LAND

IS S

QM

50.

481A

2

LAND

IS L

FL 1

.622

DUNG

S VD

K 20

0-A

UV06

-05-

2004FM

P95 96KM

P RS

TN

O

Q

HLB

S1R1

1011

85

67

9T1

N

FMV95 96

SAgG

12

30

SAM

A

12

30

FMV97 98

HLB

T

GAS (

2)

GASO

LIO (1

)

COM

MUT

ATO

RE A

LTA-

BASS

A FI

AMM

ASW

ITCH

HIG

H-LO

W F

LAM

E

CONM

UTAD

OR

ALTA

-BAJ

A LL

AMA

pos 2

: BAS

SA F

IAM

MA/

LOW

FLA

ME/

1re

ALLU

RE/B

AJA

LLAM

A

INTE

RRRU

PTEU

R 2m

e-1r

e AL

LURE

pos 3

: AUT

OM

ATIC

O/A

UTO

MAT

IC/A

UTO

MAT

IQUE

/AUT

OM

ATIC

O

pos 1

: ALT

A FI

AMM

A/HI

GH F

LAM

E/2m

eALL

URE/

ALTA

LLA

MA

YVG

1SP

Gm

inYV

GS

TP

STC

NS TR

50 H

z 400

V

TP

STS

SAL

1314

FU

Z

YVg3

YVg1

YVg2

pos 0

: ARR

ESTO

/ ST

OP

KA2

HLG

HLg

SAM

A

12

30

6

KA1

UV

TV

SPA

YVG

P

11N1M

23

LAND

IS SQ

M 50

.481A

2

133

222

121

2125

1615

424

514

717

2726

1/2

KMV2

FMV

KMV3

KMV1

KMV3

KMV1

KMV1

KMV2

KTav

v

MP

UV

W

FMP

RS

TN

50 H

z 400

V

Q

T NSR

PE PE

SAsb

locc

o

REV

4.0

HLB

14DU

NGS

VDK 2

00-A

13

BLACK 31BLUE

BROWN

YELLOW-GREEN

N N

S3B4

T2T1

S3B4

T2T1

L1 L1

20-0

5-20

04

Page 20: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.20

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

TELE

RRUP

TOR

MOT

OR V

ENTI

LATO

RCO

NTAC

TEUR

MOT

EUR

VENT

ILATE

URRE

MOT

E CON

TROL

SWIT

CH (F

AN M

OTOR

)

EMPA

LME M

OTOR

BOM

BACO

NTAC

TEUR

MOT

EUR

POM

PEPO

MP

REM

OTE C

ONTR

OL SW

ITCH

CONT

ATTO

RE M

OTOR

E VEN

TILA

TORE

KMV1

FILT

RO D

E PRO

TECI

ON A

NTID

ISTU

RBIO

FILT

RE A

NTIP

ARAS

ITES

RELA

ISRE

LAY

FUSI

BLE

FUSI

BLE

MOT

OR V

ENTI

LADO

RM

UTEU

R VE

NTILA

TEUR

MOT

OR FA

N

MOT

OR B

OMBA

MOT

EUR

POM

PEOI

L PUM

P M

OTOR

TRAN

SFOR

MAD

ORTR

ANSF

ORM

ATEU

R D'

ALLU

MAG

EIG

NITI

ON TR

ANSF

ORM

ER

FOTO

CELU

LACE

LLUL

E UV

UV C

ELL

RELE

' TER

MIC

O M

OTOR

VEN

TILA

DOR

RELA

IS TH

ERM

IQUE

MOT

EUR

VENT

ILATE

URM

OTOR

THER

MAL

REL

AY (F

AN M

OTOR

)

RELE

' TER

MIC

O M

OTOR

BOM

BARE

LAIS

THER

MIQ

UE M

OTEU

R PO

MPE

MOT

OR P

UMP

THER

MAL

REL

AY

ESPI

A GA

SLA

MPE

DE G

AZGA

S LAM

P

ESPI

A DE

BLO

QUEO

LAM

PE D

E SEC

URIT

ELO

CK-O

UT LA

MP

RELA

ISRE

LAY

ESPI

A GA

SOLE

OTE

MOI

N M

AZOU

TOI

L LAM

P

CONT

ATTO

RE M

OTOR

E POM

PA

LAM

PADA

GAS

OLIO

LAM

PADA

GAS

LAM

PADA

DI B

LOCC

O

RELE

' TER

MIC

O M

OTOR

E VEN

TILA

TORE

RELE

' TER

MIC

O M

OTOR

E POM

PA

FOTO

CELL

ULA

TRAS

FORM

ATOR

E

MOT

ORE V

ENTI

LATO

RE

MOT

ORE P

OMPA

FUSI

BILE

KMP

RELE

'

KA2

RELE

'

HLg

HLG

HLB

FMV

FMP

UVTVMV

RELE

'

RELE

'

MP

KA1

FUSE

FU

ELEC

TROV

ALVU

LA G

AS D

E 1^

LLAM

A

ELEC

TROV

ALVU

LA G

AS P

ILOTO

ELEC

TROV

ANNE

GAZ

PILO

TEPI

LOT F

LAM

E SOL

ENOI

D GA

S VAL

VEEL

ETTR

OVAL

VOLA

GAS

PILO

TA

ELET

TROV

ALVO

LA G

ASOL

IO

ELET

TROV

ALVO

LA G

AS D

I SIC

UREZ

ZA

ELET

TROV

ALVO

LA G

ASOL

IO

PRES

OSTA

TO G

AS D

E MIN

IMA

POT.

PRES

SOST

AT G

AZ P

RESS

ION

MIN

GAS P

RESS

URE S

WIT

CH M

INPR

ESSO

STAT

O GA

S DI M

INIM

ASP

Gmin

YVGP

YVg2

YVg1

YVGS

THER

MOS

TAT C

HAUD

IERE

TERM

OSTA

TO C

ALDE

RA

TERM

OSTA

TO D

I SIC

UREZ

ZA

COM

MUT

ATOR

E GAS

OLIO

-GAS

INTE

RRUP

TEUR

MAZ

OUT-

GAS

CONM

UTAD

OR G

ASOL

EO-G

AS

TERM

OSTA

TO D

E SEG

URID

AD

COM

MUT

ATOR

E MAN

UALE

-AUT

OMAT

ICO

SWIT

CH (M

ANUA

L-AU

TOM

ATIC

))IN

TERR

UPTE

UR M

ANUE

L-AU

TOM

ATIQ

UECO

NMUT

ADOR

MAN

UAL-

AUTO

MAT

ICO

THER

MOS

TAT D

E SEC

URIT

E

ELEC

TROV

ANNE

GAZ

PET

ITE A

LLUR

EFI

RST S

TAGE

GAS

SOLE

NOID

VAL

VEEL

ETTR

OVAL

VOLA

GAS

DI P

RIM

A FI

AMM

AYV

G1

SAM

A

SAFE

TY TH

ERM

OSTA

T

SWIT

CH (O

IL-GA

S)SA

gG

STS

PRES

SOST

AT A

IRPR

ESOS

TATO

AIR

E

TERM

OSTA

TO C

ALDA

IABO

ILER

THER

MOS

TAT

STC

INTE

RRUP

TOR

GENE

RAL C

ON FU

SIBL

EIN

TERR

UPTE

UR G

ENER

AL A

VEC

FUSI

BLE

MAI

N SW

ITCH

WIT

H FU

SE

ANTJ

AMM

ING

FILT

ERFI

LTRO

ANT

IDIS

TURB

O

INTE

RRUT

TORE

GEN

ERAL

E CON

FUSI

BILE

ZQ

INTE

RRUT

TORE

DI L

INEA

INTE

RRUP

TEUR

DE L

IGNE

INTE

RRUP

TOR

DE LI

NEA

WOR

KING

SWIT

CH

PRES

SOST

ATO

ARIA

AIR

PRES

SURE

SWIT

CHSP

A

SAL

HLBT

ESPI

A DE

BLO

QUEO

REL

E TER

MIC

OLA

MPE

DE T

HERM

AL D

E SEC

URIT

ETH

ERM

AL LO

CK-O

UT LA

MP

LAM

PADA

DI B

LOCC

O TE

RMIC

O

PAGI

NA D

I

CONT

ATTO

RE M

OTOR

E VEN

TILA

TORE

KMV2

CONT

ATTO

RE M

OTOR

E VEN

TILA

TORE

KMV3

REM

OTE C

ONTR

OL SW

ITCH

(FAN

MOT

OR)

CONT

ACTE

UR M

OTEU

R VE

NTILA

TEUR

TELE

RRUP

TOR

MOT

OR V

ENTI

LATO

R

REM

OTE C

ONTR

OL SW

ITCH

(FAN

MOT

OR)

CONT

ACTE

UR M

OTEU

R VE

NTILA

TEUR

TELE

RRUP

TOR

MOT

OR V

ENTI

LATO

R

EXTR

A SA

FETY

GAS

SOLE

NOID

VAL

VEEL

ECTR

OVAN

NE G

AZ D

E SEC

URIT

EEL

ECTR

OVAL

VULA

GAS

DE S

EGUR

IDAD

YVg3

ELET

TROV

ALVO

LA G

ASOL

IOOI

L SOL

ENOI

D VA

LVE

ELCT

ROVA

NNE M

AZOU

TEL

ECTR

OVAL

VULA

DE G

ASOL

EO

OIL S

OLEN

OID

VALV

EEL

CTRO

VANN

E MAZ

OUT

ELEC

TROV

ALVU

LA D

E GAS

OLEO

OIL S

OLEN

OID

VALV

EEL

CTRO

VANN

E MAZ

OUT

ELEC

TROV

ALVU

LA D

E GAS

OLEO

0001

0203

0405

0607

0809

A

0001

0203

0405

0607

0809

B C D E

A B C D E

IND.

MO

DIFI

CA

SOST

.DA

SOST

.IL

IND.

MO

D.

PROPRIETA' RISERVATA DELLA DITTA ECOFLAM S.p.A.

DATA

-FIR

MA

DATA

FIRMA

CONT

ROLL

ATO

DESC

RIZI

ONE

MO

DIFI

CA

DISE

GNAT

O

DATA

FIRMA

COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE. A TERMINE DI LEGGE E' VIETATO RIPRODURRE O

CONT

ROLL

O D

I TEN

UTA

APPA

RECC

HIAT

URA

UFF.T

ECNI

CO-S

ETTO

RE EL

ETTR

ICO

DENO

MIN

AZIO

NE

SIST

. RIV

ELAZ

.CO

DICE

MO

TORI

DUTT

ORE

S.p.A.

BEM

4314

1M

ULTI

CALO

R 10

00.1

MD

LAND

IS S

QM

50.4

81A2

LAND

IS L

FL 1

.622

DUNG

S VD

K 20

0-A

UV06

-05-

2004

(0° )

VIII:

CAM

MA

NON

UTILI

ZZAT

A

CAM

MA

DI R

EGOL

AZIO

NE A

RIA

PER

FIAM

MA

DI A

CCEN

SION

E GAS

OLIO

CAM

MA

DI R

EGOL

AZIO

NE A

RIA

PER

FIAM

MA

DI A

CCEN

SION

E GAS

CAM

MA

DI R

EGOL

AZIO

NE A

RIA

PER

BASS

A FI

AMM

A GA

SOLIO

CAM

MA

DI R

EGOL

AZIO

NE A

RIA

PER

BASS

A FI

AMM

A GA

S

CAM

MA

DI R

EGOL

AZIO

NE A

LTA

FIM

MA

( GAS

-GAS

OLIO

)CA

MM

A DI

REG

OLAZ

IONE

ARI

A CH

IUSU

RA TO

TALE

CAM

MA

NON

UTILI

ZZAT

A

(0°)

II:

(25°

) V:

(15°

) IV:

(15°

) III:

(0°)

VII:

(25°

) VI:

(70°

) I:

0

I

00

IIIII

IV

0

VVI

IVI

0

VIII

2/2

Page 21: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.21

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

MU

LT

ICA

LO

R 1

000.

1 M

D

4

8939

28

29

33

37

3857

3

1

5

42

3130

32

2

6

10

11

53

54

0°15

°30

°45

°

60°75° 90°

PG

ME

XIT

0I

0

AU

TO

0OIL

GA

S

OIL

GA

S

RE

SE

T

21 19 20

FIND

ER

FIND

FIND

FIND

ERFI

NDER

137 12

1516 17

18

K6

RW

F 4

0PG

MP

GM

EX

ITE

XIT

2322

40

2524

1427

35

3436

4948

5547

46

5153

44

5051

45

4152

58

Page 22: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.22

techniques for energy savingLB1360 MULTICALOR 700.1÷1200.1 MD

TC = SHORT HEAD TL = LONG HEAD

Multicalor 1000.1 MDN° DESCRIPTION code

1 - AIR PRESSURE SWITCH DG 10 U Q112/22 - AIR INTAKE SET GRPA1003 - WIELAND PLUG 6 pin E2264 - COVER BFC09255/0385 - GLASS BFC020046 - PEED WINDOM FRAME BFC020067 - MOTOR 22 kW M170/618 - FAN RG-630 BFV10401/0019 - AIR CONVEYOR BFC0826010 - CONVEYOR RING BFC08258/03811 - AIR INTAKE GRCA63012 - CONTROL BOX BASE LANDIS A40113 - CONTROL BOX LANDIS LFL1.622 A11314 - IGNITION TRANSFORMER BRAHMA T8 T10115 - REMOTE CONTROL SWITCH AEG LS15K.00 R621/516 - REMOTE CONTROL SWITCH (PUMP) AEG LS11K.00 R621/417 - MOTOR THERMAL RELAY AEG B18K-320 R521/1618 - MOTOR THERMAL RELAY (PUMP) AEG R521/519 - MAIN SWITCH cod.40100I1509 R102020 - RESET BUTTON C5559AL R102121 - SELECTOR R1020/522 - LAMP Elettrospring EL/N-SC4 E151023 - FUSE SUPPORT FUSIT FH-B528 E802/224 - RELÉ BASE Finder 5532 R905

Finder 5534 R90625 - RELÉ Finder 5532 R711

Finder 5534 R71226 - TIMER AEG SDE R52727 - UV CELL LANDIS QRA 2 A20528 - IGNITION CABLE TC BFE01403/329 - IGNITION ELECTRODES SET E612/130 - PIPE TC31 - ROD TC32 - GAS FIRING HEAD33 - FRONT DISC34 - OIL FIRING HEAD35 - COIL EL011 V52336 - CONNECTOR WITH RECTIFIER V1119/0737 - INNER ASSEMBLY TC38 - BLAST TUBE TC BFB07022/10339 - GASKET ISOMART BFG04059/140 - ANTIJAMMING FILTER S132/441 - AIR DAMPER MOTOR LANDIS SQM50.481A2 M212/9142 - SILENCER BAA1100143 - OIL PUMP SUNTEC T5C105 P1481/0444 - COUPLING MP501/445 - PUMP MOTOR 4 kW ABB M147/9146 - OIL VALVE LUCIFER 121 V175147 - COIL LUCIFER 3541 V52248 - OIL VALVE PARKER PM133IV V175/949 - COIL PARKER ZB 14 V516/150 - OIL FILTER 70501/03 S107/551 - HOSES TN 18X1500 S90252 - MANOMETER CEWAL R1/4 D50-40BAR S601/153 - PILOT GAS VALVE DUNGS SV-DLE 507 V1994/2154 - COIL DUNGS55 - OIL VALVE SUNTEC TV40011 P148156 - NOZZLE BERGONZO kg/h 65057 - MODULATING UNIT LANDIS RWF 40 E1215

Page 23: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

pag.23

LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving

NOTE :

Page 24: GAS / LIGHT-OIL DUAL BURNERS - Ecoflam · 2016-01-12 · pag.2 techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD mbar 2000 3000 4000 5000 6000 7000 8000 9000 10000 10

La ECOFLAM S.p.A si riserva il diritto di apportare ai prodotti quelle modifiche che riterrà necessarie o utili, senza pregiudicarne le caratteristiche principali.

Ecoflam S.p.A.via Roma, 64 - 31023 RESANA (TV) - Italy - tel. 0423/715345 r.a.telefax 0423/715444 (Italy 480009 - Export 480873, 715538).http://www.ecoflam.it - e-mail: [email protected]

ECOFLAM S.p.A. reserves the right to make any adjustments, without prior notice, which it considers necessary or usefulto its products, without affecting their main features.