Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC...
Transcript of Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC...
![Page 1: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/1.jpg)
Gary Kenny Maine Public Utilities Commission
New England Pipeline Safety Seminar
Mt. Snow, Vermont October 21, 2015
![Page 2: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/2.jpg)
The Issues Butt Fusions Electrofusion Mechanical Tees Installation by Horizontal Directional
Drilling Improper Pipe Handling Exposed Plastic Pipe
![Page 3: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/3.jpg)
Butt Fusions Inadequate Qualification and Resulting Poor Quality Joints A 2014 investigation, in New York State, revealed
that six companies were not destructively testing hydraulic butt fusion samples during the qualification process [NY Rule and §192.285(b)(iii)].
When requalified, 91 workers with one company failed the destructive testing module. This may impact over 800,000 fusions made back to 2002.
![Page 4: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/4.jpg)
Butt Fusions (Continued) As of May 2015, 173 in-service fusions, of that
company, were examined. Of those, 72 failed visual inspections. Of those, 63 were destructively tested and eight failed.
When all companies are considered, there may be nearly one million in-service fusions impacted.
In May 2015 the NY PSC Ordered an extensive remediation program.
![Page 5: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/5.jpg)
Questionable Beads
![Page 6: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/6.jpg)
Butt Fusions (Continued) Lack of Understanding of Interfacial Fusion Pressure (IFP)
IFP is the allowable range of pressure that’s required between the faces of the pipes being joined, during the fusion process, to result in an adequate fusion;
IFP is constant for all sizes and wall thicknesses of pipes of the same type; and
The gauge pressure on hydraulic fusion machines varies with: The pipe diameter and wall thickness; The hydraulic piston area; and The hydraulic pressure (drag) required to move the pipe
being joined.
![Page 7: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/7.jpg)
Hand Pump Hydraulic Fusion Machine
![Page 8: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/8.jpg)
Hydraulic Pressure Gauge
![Page 9: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/9.jpg)
Butt Fusions Inadequate Cooling Time for Rough Handling
This is a problem noted with all types of fusion. It’s sometimes not recognized by field personnel: That Rough Handling requires additional cooling
time after the pipe may be removed from the clamps; and
What constitutes Rough Handling? Pulling, Installation in Trench, Etc.
![Page 10: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/10.jpg)
Electrofusion Couplings Inadequate Preparation Conventional Tie-In Applications
Inadequate Cooling Time for Rough Handling Alignment – If you need to use the backhoe
bucket to align the pipes, the electrofusion will likely fail.
![Page 11: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/11.jpg)
Coupling – Left End
![Page 12: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/12.jpg)
Coupling – Right End
![Page 13: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/13.jpg)
Fusion Failed After Equipment Used to Align Pipes
![Page 14: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/14.jpg)
Coupling Preparation at Tie-Ins Where the coupling is slid entirely over the
end of one pipe; That pipe must be prepared over the entire
length of the coupling.
![Page 15: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/15.jpg)
Electrofusion Couplings Is the pipe adequately prepared for this coupling?
It Depends!
![Page 16: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/16.jpg)
Electrofusion
Tees Improper Clamps Inadequate Preparation Inadequate Cooling Time for Rough Handling
![Page 17: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/17.jpg)
A Tee that Failed During Pressure Testing
![Page 18: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/18.jpg)
Location of Tee Failure
![Page 19: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/19.jpg)
Sidewinder – Not Approved for Electrofusion Tees
![Page 20: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/20.jpg)
Mechanical Tee - Installation Depend on the threads of the cutter’s sleeve to hold them
on the main
![Page 21: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/21.jpg)
Horizontal Directional Drilling Cross Bores Inadequate Weak Links
Lack of Pull Through to Inspect for Damage
Not Knowing What Else is Underground
![Page 22: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/22.jpg)
Cross Bore of a Sewer Lateral
![Page 23: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/23.jpg)
Cross Bore of a Culvert
![Page 24: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/24.jpg)
Damage from a Mechanical Snake
![Page 25: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/25.jpg)
Weak Link (Breakaway)
![Page 26: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/26.jpg)
Pipe in a Casing?
![Page 27: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/27.jpg)
No, a Gas Main Installed by HDD in a Drain Line
![Page 28: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/28.jpg)
Improper Pipe Handling Dragging Pipe
Lack of Care when Placing Pipe in Ditch
![Page 29: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/29.jpg)
Damaged Beads Are an Indication to Look Closer
![Page 30: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/30.jpg)
This is What You May Find
![Page 31: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/31.jpg)
Pipe Was Dragged After Fusion
![Page 32: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/32.jpg)
Exposed Plastic Pipe Most Often Found on Propane Systems In tank domes
Plastic Pipe Used for Regulator Vent Piping Must be PVC that’s rated for UV exposure –
gray electrical conduit
![Page 33: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/33.jpg)
Exposed PE Pipe in a Tank Dome
![Page 34: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/34.jpg)
How Do These Issues Occur? The Cause of Plastic Pipe Issues is ________.
a. lack of an adequate qualification process b. lack of adequate training for operator and
contractor personnel c. failure to follow procedures d. lack of adequate inspection e. rogue employees f. All of the above
![Page 35: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/35.jpg)
What Can Be Done To Prevent These Issues?
Better Training Mandatory for all, not just for those that fail the OQ test. Minimum experience levels for trainers.
Third Party (Independent) Qualification Examiners
Proctoring of written and/or on-line tests. Individual hands-on testing.
More Thorough Inspection by Operators
![Page 36: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/36.jpg)
Distribution Integrity Management Program (DIMP)
If there is a potential that the threat of inferior pipe joining may exist, it must be included as a threat in the DIMP written plan; however
The inclusion of inferior pipe joining in the DIMP plan IS NOT an alternative to removing all known defects from new construction!
![Page 37: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/37.jpg)
Suggested References Keynote speech given by MPUC Chairman,
Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s Future?!
May 15, 2015 NY PSC Order Requiring Local Distribution Companies to Follow and Complete Remediation Plans as Modified by this Order and to Implement New Inspection Protocols
![Page 38: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/38.jpg)
Questions
![Page 39: Gary Kenny Maine Public Utilities Commission Oct 2015/Plast… · Keynote speech given by MPUC Chairman, Mark Vannoy, at the October 8, 2015 conference, Natural Gas: Energy for Maine’s](https://reader034.fdocuments.us/reader034/viewer/2022042712/5f8b1f11eb5c342d3d066928/html5/thumbnails/39.jpg)
Thank You!