UR Series, Type-G60 Relay Test Report
Job Number:Customer: Location:
Relay ID:
Nameplate Data
Model #: Firmware Version: Boot Version:Serial #: Instruction Booklet:Ratings: CT / PT Ratio:
System Setup
Current Banks Voltage Banks5 5Ratio-F1 : 5 Ratio-F5 : 5 Bank F5: Phase Secondary = V Secondary = V
5 5Ratio-M1 : 5 Ratio-M5 : 5 Bank M5: Phase Secondary = V Secondary = V
Ibase = Amps
Electrical Tests
Inputs / Outputs
Minimum PickUp Time Delay
Phase Current
Phase Voltage
Generator Unbalance Function = CT Bank =
LevelINOM = pu x Pickup = 1.500 A [ I2 ]
STG1 Pickup = x Pickup = 3.000 A [ I2 ]
K-Value = x Pickup = 4.000 A [ I2 ]TMIN = s TMAX = s K-RESET
STG2 Pickup = x Pickup = 0.700 A [ I2 ]
DELAY = s x Pickup = 1.400 A [ I2 ]
+ Note: Neutral IOC is adjusted by 6.25% for I1 restraint. *Note: This function is disabled, not used, or zero time delay.
*
**
1.00 A
* NA *OV2 Disabled ** NA
10.00 Sec 10.0 s
[data below]
F1
*
*OV1 Disabled *
5.00 ( 0.280 pu)
Enabled
GEN UNBAL Settings Test Current [Negative Sequence]
*
40.00 ( 0.800 pu)0.20
Stage 2 [Alarm]
7.00%10.00
Stage 1 [TRIP]
0.80010.00%
* * NADisabled
Aux Voltage
OV2 DisabledNeutral Voltage
Volts per HertzV/Hz 2 DisabledV/Hz 1 Disabled
UV2
OV1
Neg Seq Volt OV
Check all voltage/current inputs (magnitude and polarity); use metering to view. Pass
*
Ground Current
Neutral Current
1.133.32
[Removed]
120V ac; 5Amp, 125V dc logic
F1
G60-D00-VFH-F8A-H6N-M8A-P6CAALC02000081
Disabled8.0 pu
*
[Name Removed]Gen/Cubicle:
800 NA
Bank
TOC1
CategoryIOC1
1601-0110-E2 (GEK-106411A)
Confirm
IOC2
ΑφSetting ExpectedElementF1 0.00 s40.00 A *
**40.0 A
*
[data below]
NATOCNA
TOC
1.20 pu 6.00 A
0.90 puDisabled
0.20 pu F1
108.00 V
IOC1 + Disabled
108.0 V
TOC1
F5**
1.00 A*
---
CT = 800:5, PT = 120:1
*
*
Pass
NA
[data below]
TOC[data below][data below]
Project:
800
[Location Removed]
40.0 AΒφ Setting Measured
CG02-107B, GT-1 2CG02-107B_G60
40.0 A
CoGen Installation
Auxiliary
Cφ
120120
Measured
Check all digital inputs. -AND- Check all output contacts.
Phase
800 NA
IOC1 DisabledTOC1UV1
0.80 puOV1 DisabledUV2 96.00 VF5
**
*
*
*
7.503.75
*
*TOC
( 0.300 pu) 180.0 s
---
*
[data below][data below]
*
[data below]*
*TOC
(3ph Delta)(3ph Delta)
TOC [data below]
*
* *
*
NA*
TOCTOC95.9 VNA
TOC
71.1 s180.0 s
TimeExpected Measured
Time
6.01 A 6.01 A 6.01 A*
71.1 s( 0.600 pu)
DisabledUV1 Disabled
Disabled
180.0010.00
240.0 s
NA NA
*NA
10.0 s
40.0 s240 s
40.0 s
2.50 ( 0.140 pu) 10.00 Sec
Power Technical Services, Inc. 1323 Butterfield Road; Suite 106
Downers Grove, IL 60515CG02-107B_G60, GT-1.xls
Page 1 of 4
Sample
![Page 2: G60 Tested](https://reader035.fdocuments.us/reader035/viewer/2022081721/552eb1885503464a778b4a9f/html5/thumbnails/2.jpg)
UR Series, Type-G60 Relay Test Report (cont)
Relay ID:
Electrical Tests (Cont)
Time-OverCurrentElement Curve & Time Dial
Curve = x =Phase TOC1 TDM = x =
Reset = x =Curve = x =
Neutral TOC1 TDM = x =Reset = x =Curve = x =
Ground TOC1 TDM = x =Reset = x =Curve = x =
Phase UV1 TDM = x =Reset = x =Curve = x =
Phase UV2 TDM = x =Reset = x =Curve = x =
Aux UV1 TDM = x =Reset = x =Curve = x =
Aux UV2 TDM = x =Reset = x =Curve = x =TDM = x =Reset = x =Curve = x =TDM = x =Reset = x =
reach Vφ-φ V φ-φ V φ-φ V φ-φRCA A A A A
Comp Limit Ω Ω Ω Ω° ° ° °
+ ° A A A ADirection − ° A A A A
Sec Secreach Vφ-φ V φ-φ V φ-φ V φ-φRCA A A A A
Comp Limit Ω Ω Ω Ω° ° ° °
+ ° A A A ADirection − ° A A A A
Sec Secreach Vφ-φ V φ-φ V φ-φ V φ-φRCA A A A A
Comp Limit Ω Ω Ω Ω° ° ° °
+ ° A A A ADirection − ° A A A A
Sec Sec
**Note: Z = Vφ-φ/2I If Phase Distance has Quadrillateral Charactoristic, ATTACH Quad datasheet:
If Power Swing settings enabled, Attach PTS' Out-Of-Step Relay datasheet:
*Note: This function is disabled, not used, or zero time delay.
** *
12.6 s
(3ph Delta)
*
50.0 s
(3ph Delta)
Instantaneous 0.20 NA0.500.75 NA NA * * *
( 0.90 pu = 108.00 V)
OFF
Volts / Hertz 12.00 NA
Voltage
Max Torque Angle
1.50 NA NA*NA *
*
Timed
Circle
Z1 *
Z2 *
Z3 *
NA
1.10 NA NA *
0.537 s
12.5 s
Αφ
DelayCheck
OFF
Max Torque AngleImpedance** Current @ MTA
Circle Check
0.50
Current @ MTA
*
0.80Inverse Time
Impedance**
DelayVoltage
0.20
Timed
0.500.20
1.0
0.50
Max Torque Angle
0.343 s
NA
2.00 A
6.00 A
1.968 s3.00 A
Project:
10.0
6.03.0
Test Current2.0
Instantaneous
3.0IAC Very Inv
---
50.3 s*
---20.0 s
2.0
3.06.0
4.0
Time1.312 s
Gen/Cubicle:
86.40 V
IAC Very Inv 2.0
ΒφExpected
1.96 s0.82 s
Inverse Time
0.36 s
NA
---
*
0.80
---
(3ph Delta)
(3ph Delta)
NA
NANA
0.35 s24.00 A0.54 s
12.00 A18.00 A
1.35 s
Cφ1.35 s
20.0 s54.00 V21.60 V76.80 V
0.35 s0.35 s0.54 s 0.54 s
2CG02-107B_G60
Measured Time
1.35 s
48.00 V5.00 s 5.04 s (3ph Delta)
CG02-107B, GT-1
0.340 s0.806 s
NA
---1.27 s (3ph Delta)2.01 s2.00 s
Instantaneous 1.25 s19.20 V
1.00
CoGen Installation
NANA
0.75 NA ** * ** *
NA
**
* * *NA
NA NA *
Cφ - AφBφ - Cφ
---
Aφ - Bφ
Current @ MTA
Zone Parameter Expected Values
Impedance**
OFF Voltage
Check Circle
Phase Distance (for Mho Charactoristic Only; if Quad, see Attached)
Delay
1.50 NA1.10 NA
NA
Volts / Hertz 2
Instantaneous
1.5Timed
Instantaneous
( 1.20 pu = 6.00 A)
( 0.80 pu = 96.00 V)
( 0.20 pu = 1.00 A)
0.20
NA * *
**
NA NA
* *
*NA * * *
Timed 2.00 NA NA * * *
Power Technical Services, Inc. 1323 Butterfield Road; Suite 106
Downers Grove, IL 60515CG02-107B_G60, GT-1.xls
Page 2 of 4
Sample
![Page 3: G60 Tested](https://reader035.fdocuments.us/reader035/viewer/2022081721/552eb1885503464a778b4a9f/html5/thumbnails/3.jpg)
UR Series, Type-G60 Relay Test Report (cont)
Relay ID:
Electrical Tests (Cont)
Test Voltage measured:test current used.
Center V V V VRadius A A A A
Ω Ω Ω Ω° °
+ 40 ° A A (Test Angle = 251.9 deg)
− 40 ° A A (Test Angle = 288.1 deg)
Sec SecCenter V V V VRadius A A A A
Ω Ω Ω Ω° °
+ 40 ° A A (Test Angle = 251.4 deg)
− 40 ° A A (Test Angle = 288.6 deg)
Sec Sec
Phase VT Connection:
V V V VA A A A Test Voltage measured:
SMIN - 1 VA VA VA VASMIN - 2 ° ° ° °
RCA + 50 ° I ÷ cos(50°) = A A A A Test current used:Calib − 50 ° I ÷ cos(50°) = A A A A
Sec Sec Sec Sec (Connect to A-ph)
V V V VA A A A
SMIN - 1 VA VA VA VASMIN - 2 ° ° ° °
RCA + ° I ÷ cos( °) = A A A ACalib − ° I ÷ cos( °) = A A A A
Sec Sec Sec Sec
Stator Differential
CT Set FormulaPICKUP x Ibase ÷ Ratio
PICKUP x Ibase ÷ Ratio
Slope 1 = BREAK 1 = pu Slope 2 = BREAK 2 = pu [Current Banks F1 and M1 .]
Slope Curve ActionLine End Current [Bank-F1]Neutral End Current [Bank-M1] Low Slope disabled:Normalized Op Current, Iop [pu] PICKUP > (BREAK 1
[ Ir > PICKUP/Slope ] Normalized Restraint, Ir [pu] × Slope) [ Ir < BREAK 1 ] SLOPE = Id / Ir = (Ir - Iop) / Ir
Line End Current [Bank-F1]Neutral End Current [Bank-M1]Normalized Op Current, Iop [pu]
[ Ir > BREAK 2 ] Normalized Restraint, Ir [pu]SLOPE = Id / Ir = (Ir - Iop) / Ir
*Note: This function is disabled, not used, or zero time delay.
Delta
Current (at RCA + Calib, ref = ph-ph)
Stage 1 Stage 2
phase-phase
0.5660
1-phaseMeasured
PT Input :
CT Bank :
0.570
5.00
5.005.06
Expected Measured
1-phase
Expected Measured Expected Measured
4.163180.0
phase-phase
0.52
60.05.68
Offset Reach
5.090.567
5.105.00
5.120.5638
0.50
8.67270.0
4.254.25
60.04.00
ExpectedMax Reach
6.10270.0
6.046.04
5.706.077
Loss of Excitation
269.56.11
Zone Parameter
0 pu12 pu
Slope 260.00 A * - too high * - too high
Calculate2.4 pu 0 pu 0 pu
80%
9.98% 10.03%
Measure 12.00 A* - too high
1.014 pu1.13 pu 1.127 pu 1.127 pu 1.127 pu
Slope 15.63 A 5.634 A 5.634 A
Calculate1.01 pu 1.014 pu 1.014 pu
10% 10.01%
Βφ Cφ
Measure 5.06 A 5.070 A 5.072 A 5.069 A5.634 A
Values
Line EndNeut End
F1 0.5 A
Bank Expected
PICKUP = 0.100
M1 0.5 A 0.50 A 0.50 A 0.50 A
10% 1.25 80% 10.00
Minium Pickup
Element / Settings
13.8612.15
Stage 1Check
Max Torque Angle
Current @ 270° (lag)
300.0
0.50 A 0.50 A 0.50 ACφΑφ Βφ
Parameter
60.0 5.00
Impedance**
0.7214.163180.0
10.0
Measured PickUp
Expected Measured ValuesParameter / Formula Αφ
pu
Current @ 270° (lag)
Voltage
Phase-Phase Voltage
Impedance**
LinearityCheck
Stage 2
Delay
CircleCheck
Max Torque Angle
Circle
0.06
8.6174.02
10.08.3
Delay
269.54.294.25
6.050.0860.0
** Note: For single-phase-current testing, reach is 1/3 the specified value.
Z = Vφ-n/I = reach
Time DelayCheck
1.141.10
10.0
1.120
0.7204.16180
10.00.721
300.0
1.120
Appearent Power
30.0Phase-Phase Voltage
0.004
Dir Power 1 0.720Phase-Phase Voltage
Appearent Power
10.0
4.16F5
0.004 180
Time Delay
F1 Max Torque Angle (ref = ph-ph)
0180 1.120
Dir Power 2 *
OFF Max Torque Angle (Ref: Vph-n)
PT Input :F5
CT Bank :F1
Current (at RCA + Calib)OFF
NA LinearityNA
1.141.1030.0
1.120
CG02-107B, GT-1 2CG02-107B_G60
Slope Check
Sensitive Directional Power
Project: CoGen Installation Gen/Cubicle:
Power Technical Services, Inc. 1323 Butterfield Road; Suite 106
Downers Grove, IL 60515CG02-107B_G60, GT-1.xls
Page 3 of 4
Sample
![Page 4: G60 Tested](https://reader035.fdocuments.us/reader035/viewer/2022081721/552eb1885503464a778b4a9f/html5/thumbnails/4.jpg)
UR Series, Type-G60 Relay Test Report (cont)
Relay ID:
Electrical Tests (Cont)(Test using 1-ph to Gnd) : 5 : 5
RGF #1 : RGF #2 : RGF #3 : RGF #4 :
pu pu ; pu pu
PICKUP x Ibase ÷ Ratio
PICKUP x Ibase ÷ Ratio
Slope 1 = Slope 2 = Slope 3 = Slope 4 =
Line End CT, IN
Ground CT, IG
Normalized IN [pu] 0 0 0 0Normalized IG [pu] 1 0 0 0S = (IG-IN) ÷ (IG+IN)Pickup Delay
Dropout Delay
Frequency FunctionsElement
UF 1UF 2UF 3UF 4UF 5UF 6OF 1OF 2OF 3OF 4
Synchro-Check SynchCheck 1: SynchCheck 2:Category
V1V2
Max Volt Volts V (sec) Volts V (sec)Max Angle Angle deg Angle degMax Freq Freq Hz Freq Hz
**Note: Functional Testing may be performed only if operating conditions permit.
CommentsTest Equipment & Calibration Date:
Other Comments:
Relay Tested By: Date: Attach print-out of relay settings: Functional Tests By: Date:
Time Delay
Gnd CT Ratio
40%NA
**
39.78% *
800
FormulaActionRestd Gnd Fault #1 Restd Gnd Fault #2 Restd Gnd Fault #3
Expected
Line CT Ratio
NA
*0.00 s * NA * NA * NA *0.10 s NA NA0.12 s * *
*NA*
NANANA NA
NA**
Measured**
Measured**
NANA
Calculate0.43 pu
NA
**
NA
NA
NANA
1.00 pu0.431 pu1.000 pu
NANA
Formula
Expected Measured
*NANA
Minium Pickup
CT
Measured Expected
Line End 0.500 A
40%Ground 0.500 A 0.499 A
Measure 2.14 A 2.154 A5.000 A5.00 A
Enabled Disabled
NA
Restd Gnd Fault #3
0.100
Disabled
0.500 A
Restd Gnd Fault #1
NA
Restd Gnd Fault #4
Disabled
800
*
Restd Gnd Fault #4Expected
PICKUP 1 =
**
Expected Measured Expected Measured Expected Measured* *
Measured
PICKUP 2 = PICKUP 3 = PICKUP 4 =
Restd Gnd Fault #2Expected
K.P.Rolley 10/13/03
Yes
*
GENERATOR TRIP for NON-DIFF faults - Operates for all faults, except Differential.
3x Doble F-2253
Generator Trip "Functional test" performed during start-up testing, prior to first run.
DO Delay0.00 s
PickUp PU Delay
**61.0 Hz
*1.10 s *0.00 s1.00 s
*NoNoNo
**
DO Delay*
PickUp
*
PU Delay1.10 s
***
*
Yes 59.0 Hz0.10 pu
*
0.00 sYes
*
0.10 pu*0.60 s
59.003 Hz58.002 Hz
*
61.99 Hz*
0.60 s*
60.99 Hz
**
Enabled FALSE Disabled
** *
TRUE
*
*NA
Measured
*
CG02-107B, GT-1
Specified
NoNo
58.0 Hz
NoYesYes
Min V(A)
*
Enabled
0.50 s 0.00 s
-29.5 deg
Min V(A)11.9 V11.9 V
*
62.0 Hz
Yes
20 140.4 V
*Note: This function is disabled, not used, or zero time delay.
SYNCHRO-CHECK - Operates on Synchro-Check or Dead-Bus/Live-Line.
59.83 Hz 60.17 Hz+30.5 deg
P5 Flex Logic
P2 Flex Logic
P4 Flex Logic
Specified
YesGENERATOR TRIP for DIFF faults - Operates only for Differential faults. Yes
LIVE
*
Yes
Logic Elements
Tested
Output Functional Tested**
DEAD
95.8 VLow
LIVE
Project: CoGen Installation Gen/Cubicle:
36.8 V 95.9 V
High(Dead) (Live) *
*
Low High
2CG02-107B_G60
*
Output Control
300.17
Flex Logic
*
TRIP OUTPUT - Operates for programmed faults.YesBREAKER FAILURE simulation - Operates if Breaker doesn't trip after 200msec.
Yes YesYes
0.30 pu
NoK.P.Rolley 10/13/03
P1 Flex Logic Yes
P3 Flex Logic
100.5 V
0.80 pu0.80 pu
Specified35.8 V0.30 puD
EAD
1.00 s0.50 s
**
**
*
Output & Logic Checks
Slope Check
Restricted Ground Fault
Power Technical Services, Inc. 1323 Butterfield Road; Suite 106
Downers Grove, IL 60515CG02-107B_G60, GT-1.xls
Page 4 of 4