FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant | Pillows | Mortar | FR Batts FR Collars | FR Access Panels | Pipe Wraps FyreWrap Duct Wrap | FR Downlight Covers Fire Door Hardware | Fire rated Board and Systems Cable Coating FYREBOX for multiple and mixed services Fight Fire With

Transcript of FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720...

Page 1: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

FyreFLEX®Fire Rated Sealant

tfire.com.au 010720

TECHNICAL GUIDE SERVICE PENETRATIONS

Trafalgar fire stopping range includes:

Sealant | Pillows | Mortar | FR Batts

FR Collars | FR Access Panels | Pipe Wraps

FyreWrap Duct Wrap | FR Downlight Covers

Fire Door Hardware | Fire rated Board and Systems

Cable Coating

FYREBOX for multiple and mixed services

Fight Fire With

Page 2: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FyreFLEX®Fire Rated Sealant

Page 2 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

Product Manual – Service Penetrations

Compliance Overview 3

Product Overview 4

Technical Specifications 5

Order & Install Specifications 6

General Installation notes 7

Metal pipe penetrations 8

- Plasterboard walls 8

- HEBEL and SPEEDPANEL walls 10

- Concrete and Masonry walls 12

- Concrete floors 14

Cable penetrations 15

- Plasterboard walls 15

- HEBEL and SPEEDPANEL walls 17

- Concrete and Masonry walls 19

- Concrete floors 21

Blank penetrations 21

TWrap installation 22

- Metal pipes and TWrap 22

- Metal pipes and TWrap 23

Special applications 24

FyrePEX or FyreFLEX? 25

ContentsPage

Page 3: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FyreFLEX®Fire Rated Sealant

Page 3 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

Under the building code NCC, a Deemed to Satisfy (DTS) solution is one that satisfies the performance requirements set out in section C of volume one. Section C specifically deals with the fire protection of openings in fire barriers (i.e. service penetrations in fire rated walls and floors).

Section C3.15 – Openings for Service Installations

Where any service penetrates an internal fire barrier that has a set Fire Resistance Level (FRL) with respect to integrity and insulation, the installation must comply with the following:

a) A Fire Tested System – An identical prototype, installed in the same wall or floor system that has beentested/approved to the fire testing standard AS1530.4 and AS4072.1 which has achieved an FRL of equal to orgreater than that required by the fire barrier.

For example, if the site has a -/90/90 plasterboard wall system with an electrical cable penetration, the product used to seal the cables must have been fire tested at an approved laboratory WITH electrical cables IN the same wall type AND fire tested for at least 90 minutes without failing the integrity or insulation criteria.

ComplianceOverview

Fire Assessment Reports

Fire testing is a timely and expensive process, and it is

impossible to test every single possible service configuration

‘identically’ in a practical sense.

Under the building code C3.15(a)(i)(B) a testing authority is

permitted to write a formal assessment confirming the fire

performance (FRL) of the penetration. The guidelines for

what can and can’t be included in a formal assessment are

outlined in AS4072.1.

Our FyreFLEX fire assessment report FCO 1579 is written by

expert Fire Engineers from a NATA approved laboratory

which provides evidence of compliance under the NCC. The

report summaries the decades of fire test data for FyreFLEX

Sealant, and allows for a large range of practical

applications. Trafalgar products installed in a plasterboard wall, being fire tested at the CSIRO

Approvals update Trafalgar are proud to announce that our latest update of report FCO 1579 for FyreFLEX Sealant will now include greater cable and metal pipe penetration coverage in Hebel and SPEEDPANEL walls, as well as our new TWrap insulation wrap systems.

TWrap is a 25mm thick foil blanket that can be used to wrap around service penetrations to insulate the penetration for up to 3 hours (-/180/180) and replaces the FyreWRAP 450mm insulation system. See page 22 for more information.

Page 4: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 4 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

FYREFLEX AND INSULATION PERFORMANCE:

FyreFLEX sealant can achieve an FRL up to -/240/120 on small bundles of cables in

certain fire barriers, however larger cables and metallic pipes will reduce the

insulation rating (i.e. increase in heat rise) under fire conditions. When this occurs,

TWrap is required to be wrapped around the services for a certain length to achieve

better insulation performance. For more information, refer to page 22 of this

document or call the Trafalgar Technical team on 1800 888 714.

APPLICATION:

• Plumbing: Copper and steel pipework

• Electrical: Power cable bundles or trays

• Comms: Data cables bundles or trays

• Fire: TPS fire cables and steel sprinkler pipes

• Builders: Control and expansion joints

FEATURES: • NCC 2022 ready - Tested and approved in

accordance with AS1530.4-2014 and AS4072.1

• Non-toxic

• Water based allowing easy clean-up.

• Excellent adhesion properties

• Tested and compliant in single layer

plasterboard, Hebel and SPEEDPANEL walls and

FyreBOARD Maxilite

• Approved for use in both walls and floors

FyreFLEX Sealant is a water based, low VOC and environmentally friendly fire-rated sealant with

intumescent properties which makes it perfect for fire stopping cable and metal pipe penetrations through

fire rated barriers.

FyreFLEX is the one of the most fire tested sealants in the market with more than 30 fire and acoustic

tests, and assessments spanning over 30 years. FyreFLEX has been approved for use in a large range of

control joint or firestopping applications required under the National Construction Code (NCC).

Penetrations tested in Hebel, SPEEDPANEL, FyreBOARD Maxilite, Plasterboard and concrete fire barriers

Product Overview

Page 5: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 5 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

To maintain market leadership, Trafalgar stay up to date with the latest technologies and trends in passive fire protection and contemporary construction techniques.

We are 75 years strong and still innovating!

Cable bundle penetrations

PRODUCT DESCRIPTION

Fire Rating Service and barrier dependent (refer to tables below) refer to below tables.

Movement Capabilities

FyreFLEX has a ± 10% movement capability

Colour

White – for service penetrations and easy painting Grey – Colour matched to concrete or blockwork

Testing Tested and approved to AS1530.4-2014 and AS4072.1 in accordance with the National Construction Code (NCC).

Installation

FyreFLEX Sealant must be applied to the gaps around service penetrations to the correct depth. See below for service specific requirements.

TWrap may be required for insulation performance.

Safety Non-Toxic, low VOC. Please refer to product MSDS for full safety information

Shelf Life 24 months from date of manufacture.

Also Available

For PVC conduits, insulated pipes or PEX piping, Trafalgar FyrePEXTM HP Sealant should be used. Contact Trafalgar for more information.

Cable tray penetrations

Metal pipe penetrations with TWrap

Technical Specifications

Page 6: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 6 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

FyreFLEX Sealant

Product Product Code Size Description Box Qty

FyreFLEX Cartridges FyreFLEX 300W FyreFLEX 300G

300mL cartridge White Grey

20

FyreFLEX Sausages FyreFLEX 600W FyreFLEX 600G

600mL sausage White Grey

18

FyreFLEX Pails FyreFLEX 10W FyreFLEX 10G

10L White Grey

n/a

TWrap 300 TWrap Roll – 300mm 300mm wide x 25mm thick x 7620mm long

Foil faced insulation

blanket 2

TWrap 600 TWrap Roll – 600mm 600mm wide x 25mm thick x 7620mm long

Foil faced insulation

blanket 1

Cable ties Cable Tie SS 12 x 521 4.6mm wide x 521mm

long Stainless steel

cable tie 25

Cable ties Cable Tie SS 12 x 910 4.6mm wide x 910mm

long Stainless steel

cable tie 25

Foil tape Premium Reinforced

Tape 95mm wide, 50 length

meter roll Re-enforced

aluminium tape 1x

SEALANT APPLICATION: Install FyreFLEX in accordance to installation details provided in the tables on pages 7 to 13 for the service and fire barrier specific approved systems.

1. Surfaces to be sealed must be clean, dry and free from dust, dirt, grease and other contamination.

2. Cut both the cartridge tip and applicator nozzle to the required diameter and angle, screw nozzle onto

cartridge.

3. To achieve a clean finish, apply masking tape either side of the penetration to prevent sealant exuding onto

unwanted areas.

4. Apply sealant with applicator gun ensuring good surface contact is achieved by forcing sealant into the

opening to be sealed. Ensure that the correct depth of sealant is applied as required for the specific

installation - refer to tables on pages 6 to 21. Backing rod can be used to achieve the correct depth if required

(PE or other material).

5. Finish with a fillet or ‘cove’ of FyreFLEX sealant to the perimeter of the service – refer to tables below for

appropriate fillet sizes per penetration.

6. If necessary, tool within 5 minutes of application using a spatula dipped in soapy water, applying sufficient

pressure to ensure good contact of the sealant against the joint surfaces.

7. Remove masking tape. After use wash any tools in warm water and wash hands after use.

NOTE: TWrap may can be used to achieve higher insulation values – refer to pages 22-23 or contact Trafalgar for further information.

Order & Install Specifications

Page 7: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 7 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

General installation notes

1. Separation distances between FyreFLEX penetrationsCable and pipe penetrations that have been sealed with FyreFLEX sealant can be installed as close as 50mm apart, as measured from the edge of each aperture as shown (approved via assessment, reference FCO 1579c).

2. Measuring annular gaps and fill depths

This product manual refers to annular gaps as the space between the edge of the penetration and the closest edge of the service. It can be calculated simply as follows:

𝐴𝑛𝑛𝑢𝑙𝑎𝑟 𝐺𝑎𝑝 =𝑂𝑝𝑒𝑛𝑖𝑛𝑔 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟 − 𝑃𝑖𝑝𝑒 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟

2

Filling FyreFLEX Sealant to the right depth is important to maintain performance of the system, and miminise overuse of material. Trafalgar recommends the use of foam backing rod (combustible or otherwise) to set the right depth of sealant.

Examples:

50mm 50mm

Measuring 20mm annular gap Measuring 70mm fill depth

General Installation

Page 8: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 8 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

COPPER PIPES THROUGH PLASTERBOARD WALL SYSTEMS - APPROVALS

Wall system (minimum spec)

Pipe size (Type B)

Annular gap Fire stopping Fillet

TWrap length

FRL

Single layer 13mm plaster, both sides of a

64mm stud

DN25 5mm

FyreFLEX sealant to depth of plaster

50x50mm

300mm -/60/60

DN50 5mm 300mm -/60/60

DN100 5mm 450mm -/60/60

Single layer 16mm plaster, both sides of a

64mm stud

DN20 5mm

FyreFLEX sealant to depth of plaster

50x50mm

300mm -/90/90

DN50 5mm 300mm -/90/90

DN100 5mm 600mm -/90/90

Double layer 13mm plaster, both sides of a

64mm stud

DN25 15mm

FyreFLEX sealant to depth of plaster

15x15mm

300mm -/120/120

DN50 15mm 300mm -/120/120

DN100 15mm 600mm -/120/120

DN150 15mm 1100mm

& 300mm*

-/120/120

*Indicates as second layer of TWrap located at the base of the penetration, on both sides of the wall

STEEL PIPES THROUGH PLASTERBOARD WALL SYSTEMS - APPROVALS

Wall system (minimum spec)

Pipe size Annular

gap Fire stopping Fillet TWrap length

FRL

Single layer 13mm plaster, both sides of a

64mm stud

NB50 5mm FyreFLEX sealant to

depth of plaster 50x50mm

300mm -/60/60

NB100 5mm 400mm -/60/60

Single layer 16mm plaster, both sides of a

64mm stud

NB50 5mm FyreFLEX sealant to

depth of plaster 50x50mm

300mm -/90/90

NB100 5mm 400mm -/90/90

Double layer 13mm plaster, both sides of a

64mm stud

NB50 15mm

FyreFLEX sealant to depth of plaster

15x15mm

300mm -/120/120

NB100 15mm 400mm -/120/120

NB150 15mm 900mm

+ 300mm*

-/120/120

*Indicates as second layer of TWrap located at the base of the penetration, on both sides of the wall

Metal Pipe Penetrations

Page 9: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 9 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

METAL PIPES THROUGH PLASTERBOARD WALL SYSTEMS – INSTALLATION DETAILS

v

Full depth of plaster

Single and double-layer plasterboard walls

Fillet (HxW)

Metal Pipe PenetrationsP l a s t e r b o a r d

TWrap for insulation performance

TWrap for insulation performance – refer to page 22 for installation requirements

Page 10: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 10 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

COPPER PIPE PENETRATIONS THROUGH PROPRIETARY WALL SYSTEMS - APPROVALS

Wall system (minimum spec)

Pipe size (Type B)

Annular gap

Fire stopping Fillet TWrap length

FRL

75mm AAC panel (single caged -/90/90

wall)

Hebel, Walsc, etc

DN50 5mm

FyreFLEX sealant to depth of the panel (75mm)

15x15mm

300mm -/90/90

DN100 5mm 600mm -/90/90

DN150 7.5mm 1050mm -/90/90

75mm ACC panel (double caged -/120/120 wall)

Hebel, Walsc, etc

DN50 5mm FyreFLEX sealant as above, plus 60mm FyreBOARD

Maxilite to thicken one side of the wall, with 100mm

overlaps around the pipe.

15x15mm

300mm -/120/120

DN100 5mm 600mm -/120/120

DN150 7.5mm 1100mm

+ 300mm*

-/120/120

78mm SPEEDPANEL wall systems

DN50 7.5mm FyreFLEX sealant to depth of the panel (78mm)

Plus 60mm FyreBOARD Maxilite to thicken one side

of the wall, with 100mm overlaps

30x30mm

300mm -/120/120

DN100 7.5mm 600mm -/120/120

DN150

7.5mm 900mm -/120/90

7.5mm 1100mm

+ 300mm*

-/120/120

*Indicates as second layer of TWrap located at the base of the penetration, on both sides of the wall

STEEL PIPE PENETRATIONS THROUGH PROPRIETARY WALL SYSTEMS – APPROVALS

Wall system (minimum spec)

Pipe size Annular

gap Fire stopping Fillet

TWrap length

FRL

75mm AAC panel (single caged -/90/90

wall)

Hebel, Walsc, etc

NB50 5mm

FyreFLEX sealant to full depth of the panel (75mm)

15x15mm

300mm -/90/90

NB100 5mm 450mm -/90/90

NB150 5mm 1050mm -/90/90

75mm ACC panel (double caged -/120/120 wall)

Hebel, Walsc, etc

NB50 5mm FyreFLEX sealant to full depth

of the panel (75mm)

15x15mm

300mm -/120/120

NB100 5mm FyreFLEX sealant as above, plus 60mm FyreBOARD

Maxilite to thicken one side of the wall, with 100mm

overlaps around the pipe.

450mm -/120/120

NB150 5mm 900mm + 300mm*

-/120/120

78mm SPEEDPANEL wall systems

NB50 7.5mm FyreFLEX sealant to full depth of the panel (78mm)

30x30mm

300mm -/120/120

NB100 7.5mm 450mm -/120/120

NB150 7.5mm

FyreFLEX sealant as above, plus 60mm FyreBOARD

Maxilite to thicken one side of the wall, with 100mm

overlaps around the pipe.

900mm -/120/90

900mm + 300mm*

-/120/120

*Indicates as second layer of TWrap located at the base of the penetration, on both sides of the wall

Metal Pipe PenetrationsMetal Pipe Penetrations

Page 11: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 11 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

METAL PIPES THROUGH PROPRIETARY WALL SYSTEMS – INSTALLATION DETAILS

Fillet (H x W)

Full depth fill

AAC walls – direct wall sealSPEEDPANEL and AAC walls thickened with

FyreBOARD Maxilite for 2-hour FRL’s

100mm

FyreBOARD Maxilite fixed with 10g x 100mm plasterboard screws in each

corner, 25mm from the edges

TWrap for insulation performance – refer to page 22 for installation details

Metal Pipe Penetrations

Page 12: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 12 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

COPPER PIPES THROUGH CONCRETE/MASONRY WALL SYSTEMS - APPROVALS

Wall system (minimum spec)

Pipe size (Type B)

Annular gap Fire stopping Fillet

TWrap length

FRL

90mm thick Concrete/masonry

DN25 5mm FyreFLEX sealant to

13mm depth on both sides

50x50mm

300mm -/60/60

DN50 5mm 300mm -/60/60

DN100 5mm 450mm -/60/60

96mm thick Concrete/masonry

DN20 5mm FyreFLEX sealant to

16mm depth on both sides

50x50mm

300mm -/90/90

DN50 5mm 300mm -/90/90

DN100 5mm 600mm -/90/90

116mm thick Concrete/masonry

DN25 15mm

FyreFLEX sealant to 26mm depth on

both sides 15x15mm

300mm -/120/120

DN50 15mm 300mm -/120/120

DN100 15mm 600mm -/120/120

DN150 15mm 1100mm

& 300mm*

-/120/120

*Indicates as second layer of TWrap located at the base of the penetration, on both sides of the wall

Metal Pipe PenetrationsC o n c r e t e W a l l a n d F l o o r

Concrete/Masonry walls

Fillet (H x W)

Fill depth

TWrap for insulation performance – refer to page 22 for installation details

Page 13: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 13 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

COPPER AND STEEL PIPES IN FLOOR SYSTEMS – APPROVALS

Pipe material Concrete thickness

(min.) Size

Annular gap

Depth of sealant

Fillet TWrap

(top side only)

FRL

Copper (Type B)

175mm DN50 20mm 50mm

30x30mm

300mm -/240/120

120mm DN100 20mm 60mm

750mm -/120/120

175mm 800 +

500mm* -/180/180

120mm DN150 20mm 60mm 800mm -/120/120

Steel

175mm NB50 20mm 50mm

30x30mm

300mm -/240/120

120mm NB100 20mm 60mm

600mm -/120/120

175mm 800 +

500mm* -/180/180

175mm NB150 20mm 50mm 600mm -/240/120

600mm + 300mm*

-/240/180

*Indicates as second layer of TWrap located at the base of the penetration

COPPER AND STEEL PIPES IN FLOOR SYSTEMS – INSTALLATION DETAILS

Concrete floors

Fillet (H x W)

Fill depth

TWrap for insulation performance – refer to page 22 for installation details

Metal Pipe Penetrations

Page 14: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 14 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH PLASTERBOARD WALL SYSTEMS – APPROVALS

Wall system (minimum

spec)

Cable type

Approved cable construction

Max bundle

size

Annular gap Fill depth Fillet

TWrap length

FRL

Single layer 13mm

plaster, both sides of a

64mm stud

Cable bundles

TPS cables, 2.5mm2

5x

5mm Depth of

plasterboard 50x50mm

Wrap Free

-/60/60 CAT6 data

cables 5x

Three-core and Earth 19mm OD

16mm2 3x

Single layer 16mm

plaster, both sides of a

64mm stud

Cable bundles

TPS cables 2.5mm2

5x

5mm Depth of

plasterboard 50x50mm

Wrap Free

-/90/90 CAT6 data

cables 5x

Three-core and Earth 19mm OD

16mm2 3x

Double layer 13mm

plaster, both sides of a

64mm stud

Cable bundles

TPS cables 2.5mm2 CAT6

cables 5x 5mm

Depth of plasterboard

30x30mm Wrap Free

-/120/120

TPS cables 2.5mm2

10x 20mm 30x30mm 300mm -/120/120

CAT6 data cables

10x 20mm 30x30mm 300mm -/120/120

Three-core and Earth up to

16mm2* 8x 30mm 30x30mm 300mm -/120/120

Single core cables up to

630mm2* 1x 20mm 50x50mm 300mm -/120/120

Three-core and Earth up to

180mm2 cables* 1x 20mm 50x50mm 300mm -/120/120

Cable trays

300mm wide* 1x 20mm 50x50mm 300mm -/120/120

*Based off AS1530.4-2014 appendix D1 standard cable sets, applies to copper core PVC and XLPE sheathed power cables.

Cable PenetrationsPlasterboardWall

Page 15: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 15 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH PLASTERBOARD WALL SYSTEMS – APPROVALS

Fillet (H x W)

Full depth of plaster

Double layer plasterboard walls Single layer plasterboard walls

Full depth of plaster

Fillet (H x W)

TWrap for insulation performance – refer to page 23 for installation details

Small cable bundles don’t require additional TWrap

Cable Penetrations Concrete wallsand floors

Page 16: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 16 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH PROPRIETARY WALL SYSTEMS – APPROVALS

Wall system (minimum

spec)

Cable type

Approved cable construction

Max bundle

size

Annular gap Fill depth Fillet

TWrap length

FRL

75mm Hebel double cage

AAC wall

Cable bundle

TPS cables, 2.5mm2

4x 5mm

Full depth of panel

30 x 30 Wrap Free

-/90/90

CAT6 data cables

4x 5mm 30 x 30 Wrap Free

-/90/90

Three-core and Earth up to

16mm2* 8x 20mm 50x50 300mm -/120/120

Single core cables up to

630mm2* 1x 20mm 50x50 300mm -/120/120

Three-core and Earth up to

180mm2 cables* 1x 20mm 50x50 300mm -/120/120

Cable tray

300mm wide* 1x 20mm 50x50 300mm -/120/120

78mm SPEEDPANEL

walls

Cable bundle

TPS cables, 2.5mm2

6x 5mm

Full depth of panel

30x30 Wrap Free

-/120/120

CAT6 data cables

6x 5mm 30x30 Wrap Free

-/120/120

Three-core and Earth up to

16mm2* 8x 20mm 50x50 300mm -/120/120

Single core cables up to

630mm2* 1x 20mm 50x50 300mm -/120/120

Three-core and Earth up to

180mm2 cables* 1x 20mm 50x50 300mm -/120/120

Cable tray

300mm wide* 1x 20mm 50x50 300mm -/120/120

*Based off AS1530.4-2014 appendix D1 standard cable sets, applies to copper core PVC and XLPE sheathed power cables.

Cable Penetrations Concrete wallsand floors

Page 17: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 17 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH PROPRIETARY WALL SYSTEMS – INSTALLATION DETAILS

Fillet (H x W)

Full depth fill

AAC panel walls SPEEDPANEL wall

Fillet (H x W)

Full depth fill

Small cable bundles don’t require additional TWrap

TWrap for insulation performance – refer to page 23 for installation details

Cable Penetrations Concrete wallsand floors

Page 18: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 18 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH CONCRETE AND MASONRY WALL SYSTEMS – APPROVALS

Wall system Cable type

Approved cable construction

Max bundle

size

Annular gap Fill depth Fillet

TWrap length

FRL

Concrete or Masonry

walls minimum

96mm thick

Cable bundles

TPS cables 2.5mm2

5x

5mm 16mm depth on both sides

50x50mm Wrap Free

-/90/90 CAT6 data

cables 5x

Three-core and Earth 19mm OD

16mm2 3x

Concrete or Masonry

walls minimum

116mm thick

Cable bundles

TPS cables 2.5mm2 CAT6

cables 5x 5mm

30mm depth on both sides

30x30mm Wrap Free

-/120/120

TPS cables 2.5mm2

10x 20mm 30x30mm 300mm -/120/120

CAT6 data cables

10x 20mm 30x30mm 300mm -/120/120

Three-core and Earth up to

16mm2* 8x 30mm 30x30mm 300mm -/180/120

Single core cables up to

630mm2* 1x 20mm 50x50mm 300mm -/180/120

Three-core and Earth up to 180mm2*

1x 20mm 50x50mm 300mm -/180/120

Cable trays

300mm wide* 1x 20mm 50x50mm 300mm -/180/120

Concrete or Masonry

walls minimum

140mm thick

Cable bundles

21mm OD data cables

6x

25mm 140 mm 50x50mm Wrap Free

-/240/120 Cable trays

100mm wide, 6x 21mm OD

power cables 1x

*Based off AS1530.4-2014 appendix D1 standard cable sets, applies to copper core PVC and XLPE sheathed power cables.

Cable Penetrations Concrete wallsand floors

Page 19: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 19 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

Concrete and Masonry walls – some approvals required sealant to the full depth of the wall

CABLE PENETRATIONS THROUGH CONCRETE AND MASONRY WALL SYSTEMS – INSTALLATION DETAILS

Fillet (H x W)

One side fill depth fill

Fillet (H x W)

Full depth fill

Small cable bundles don’t require additional TWrap

TWrap for insulation performance – refer to page 23 for installation details

Cable PenetrationsHebel and SPEEDPANEL

Page 20: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 20 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH CONCRETE FLOOR SYSTEMS – INSTALLATION DETAILS

Floor slab Cable type

Approved cable construction

Max bundle

size

Annular gap Fill depth Fillet

TWrap length

FRL

Concrete slabs

Minimum 120 mm thick

Cable Bundle

Three-core and Earth up to

16mm2* 8x 20mm

70mm

50x50mm 300mm -/90/90

Three-core and Earth up to 180mm2*

1x 20mm 50x50mm 300mm -/90/90

CAT6 data cables

30x 20mm 70mm

40x40mm Wrap Free

-/120/120

TPS 2.5mm2 30x 20mm 40x40mm Wrap Free

-/120/120

Three-core and Earth up to

16mm2* 8x 30mm

70mm

30x30mm 450mm -/120/120

Single core cables up to

630mm2* 1x 20mm 50x50mm 450mm -/120/120

Three-core and Earth up to 180mm2*

1x 20mm 50x50mm 450mm -/120/120

Cable trays

300mm wide** 1x 20mm 50x50mm 300mm -/90/90

300mm wide* 1x 20mm 50x50mm 450mm -/120/120

Concrete slabs

Minimum 175 mm thick

Cable Bundle

41mm OD Single core power

cables 1x 20mm 100mm 50x50

Wrap Free

-/240/90

Three-core and Earth up to

16mm2* 8x 30mm

60mm

30x30mm 450mm -/180/180

Single core cables up to

630mm2* 1x 20mm 50x50mm 450mm -/180/180

Three-core and Earth up to 180mm2*

1x 20mm 50x50mm 450mm -/180/180

Cable Trays

300mm wide* 1x 20mm 50x50mm 450mm -/180/180

*Based off AS1530.4-2014 appendix D1 standard cable sets, applies to copper core PVC and XLPE sheathed power cables.**Based off AS1530.4-2014 appendix D1 standard cable sets, excluding single core cables.

Cable PenetrationsHebel and SPEEDPANEL

Page 21: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 21 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CABLE PENETRATIONS THROUGH CONCRETE FLOOR SYSTEMS – INSTALLATION DETAILS

Blank penetrations

SYSTEM DIAGRAM FRL

• Blank penetration

• Walls and floors

• Max 56mmdiameter in

concrete floors.

• Maximum 50mmdiameter in 2-hourplasterboard walls

Concrete floor 100mm fill depth

-/240/180

Concrete floor 140mm fill depth

-/240/240

2-hour plaster wall-/120/120

Concrete floor penetrations

Fillet (H x W)

Fill depth

CAT6 and TPS cables do not require TWrap for -/120/120. For cables that do require TWrap, refer to page 23

Cable PenetrationsHebel and SPEEDPANEL

Page 22: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 22 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

TWRAP INSTALLATION FOR INCREASED INSULATION PERFORMANCE

TWrap is a 25mm fully encapsulated wrap that can be applied to service penetration treated with FyreFLEX

sealant to increase the insulation performance which reduces the temperature rise on the service during fire

conditions.

For example, if a 150mm steel pipe was sealed in a concrete floor that requires 2-hour FRL, the addition of

TWrap will increase the FRL from -/120/- to -/120/120 when wrapped for 600mm off the slab.

TWrap must be installed on both sides of a wall penetration and is tested on the top side only for floor

penetrations and is fixed around services simply with 4.6mm wide steel cable ties or straps 50mm from each

end, and then at 150mm centres between.

FyreWrap 38mm may be substituted for TWrap when installed at the correct lengths specified in the above

service specific tables.

TWRAP INSTALLATION FOR METAL PIPES

TWrap Installation

Page 23: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 23 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

1. Cable TraysBefore wrapping, cable trays require loose TWrap infill material to be packed around the cables and into any voids between the cable tray and the services as shown below. Note this is NOT required for wrapping individual bundles of cables.

2. Cable bundles

Some smaller bundles of cables won’t need any TWrap at all – look for the Wrap Free notes in the tables above.

The ones that do need TWrap can be simply wrapped with TWrap for the correct length and strapped in place with 4.6mm cable ties 50mm from each end, and at 150mm centres between them.

TWRAP INSTALLATION FOR CABLE PENETRATIONS

Cable Trays with one width of TWrap Cable Trays extended length TWrap

TWrap Installation

Page 24: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 24 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

CONTROL/EXPANSION JOINTS AND HEAD OF WALL DETAILS

FyreFLEX has a proud history of use as a control/expansion joint filler and is tested &

approved for many applications such as:

- Joint protection in masonry/concrete walls

- Joint protection in concrete floors

- Plasterboard wall T-junctions

- Deflection heads

- 10% movement flexibility

- UV Stable

For a full list of installation specifications and fill depths please refer to the separate

FyreFLEX Control Joint datasheet.

Special Applications

Page 25: FyreFLEX® - Fire Rating Solutions€¦ · FyreFLEX® Fire Rated Sealant tfire.com.au 010720 TECHNICAL GUIDE SERVICE PENETRATIONS Trafalgar fire stopping range includes: Sealant |

1800 888 714 tfire.com.au

FYREFLEX®Fire Rated Sealant

Page 25 of 25FYREFLEX® is a Registered trademark of Trafalgar Group Pty Ltd

Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order. The information contained in this brochure was correct at the time of print. E&OE. Published 01/05/20

Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order.The information contained in this brochure was correct at the time of print. E&OE. Published 01.05.18

Trafalgar reserves the right to change specifications without notice. Please check with your supplier at the time of order.The information contained in this brochure was correct at the time of print. E&OE. Published 01.05.18

FYREFLEX OR FYREPEX?

MULTIPLE SERVICES?

The building code (NCC) requires certain separation distances

between service penetrations (up to 200mm) so when there

is not enough room to achieve this with the above products,

Trafalgar FYREBOX™ is the best, compliant solution! Visit

www.fyrebox.com.au for more details.

MULTIPLE SERVICES?

What is the service?

Bare copper or steel pipe

Cables or Cable Trays

Water/Gas PEX pipe

Air-con services (pair coil + cables)

PVC or HDPE piping

FYREFLEX® Sealant FYREPEX® Sealant FYRECHOKE™ Collars

Trafalgar FYREPEX® HP Sealant is a new intumescent based sealant that expands with the heat of a fire, which

enables it to be used with plastic (PEX), or insulated copper piping. As the sealant expands, it actively crushes the

pipe to block off the penetration for up 2 hours during a fire.

Trafalgar FYREFLEX® Sealant is an acrylic based sealant that has been around for decades and is a tried and true

method of fire stopping bare metal pipes and cables, through a variety of different wall and floor types - nothing

has changed with this product.

Choosing the right product for your application will largely depend on the penetrating services. As a general guide,

use the following flowchart:

For specific product approvals and installation instructions for these and other products, download the technical

manuals from www.tfire.com.au or get in contact with our technical team on 1800 888 714.

MULTIPLE SERVICES?For specific product approvals and installation instructions for these and other products,

download the technical manuals from www.tfire.com.au or get in contact with our technical team on 1800 888714.

MULTIPLE SERVICES?

The building code requires certain separation distances between service penetrations (up to 200mm) so when there is not enough room to achieve this with the above products, Trafalgar FYREBOX™ is the best, compliant solution! Visit www.fyrebox.com.au for more details.

FyreFLEX orFYREPEX