HARDWARE MANUAL FX 1N SERIES PROGRAMMABLE CONTROLLERS

Transcript of FX1N PLC Hw Manual

Page 1: FX1N PLC Hw Manual

HARDWARE MANUAL

FX1N SERIES PROGRAMMABLE CONTROLLERS

Page 2: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

Foreword

• This manual contains text, diagrams and explanations which will guide the reader in the correct installationand operation of the FX1N Series Programmable Controllers. It should be read and understood beforeattempting to install or use the unit.

• Further information can be found in the FX Series Programming Manual II.

• If in doubt at any stage of the installation of an FX1N Series Programmable Controller always consult aprofessional electrical engineer who is qualified and trained to the local and national standards which apply tothe installation site.

• If in doubt about the operation or use of FX1N Series Programmable Controller please consult the nearestMitsubisi Electric distributor.

• This manual is subject to change without notice.

Page 3: FX1N PLC Hw Manual

i

FX1N Series Pro grammable Controllers

Hardware Manual

FX1N Series Programmable Controllers

Manual number : JY992D89301

Manual revision : B

Date : June 2000

Page 4: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

ii

FX 1N.

e of the FX1N. The manual has The definition of such a person

n and construction of automaticnual should be of a competentstandards required to fulfill thatpects of safety with regards to

competent nature, trained and fulfill that job. These engineersf the completed product. Thisd documentation for the saidrdance with established safety

ed to use that product in a safe safety practices. The operatorsnected with the actual operation

arty constructed device whichal.

Guidelines for the safety of the user and protection of the

This manual provides information for the installation and usbeen written to be used by trained and competent personnel.or persons is as follows;

a) Any engineer who is responsible for the planning, desigequipment using the product associated with this manature, (trained and qualified to the local and national role). These engineers should be fully aware of all asautomated equipment.

b) Any commissioning or service engineer must be of aqualified to the local and national standards required toshould also be trained in the use and maintenance oincludes being completely familiar with all associateproduct. All maintenance should be carried out in accopractices.

c) All operators of the completed product should be trainand co-ordinated manner in compliance to establishedshould also be familiar with documentation which is conof the completed equipment.

Note : The term ‘completed equipment’ refers to a third pcontains or uses the product associated with this manu

Page 5: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

iii

ill be used to highlight points ofafety and protect the integrity ofncountered, its associated note will now be listed with a brief

d property damage.

physical and property damage.

nt of software.

ftware element should be aware

Note’s on the symbols used in this manual

At various times through out this manual certain symbols winformation which are intended to ensure the users personal sthe equipment. Whenever any of the following symbols are emust be read and understood. Each of the symbols useddescription of its meaning.

Hardware warnings

Software warning

1) Indicates that the identified danger WILL cause physical an

2) Indicates that the identified danger could POSSIBLY cause

3) Indicates a point of further interest or further explanation.

4) Indicates special care must be taken when using this eleme

5) Indicates a special point which the user of the associate soof.

6) Indicates a point of interest or further explanation.

Page 6: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

iv

sponsible for any consequential of this equipment.

intended only as an aid totsubishi Electric will accept noillustrative examples.

his equipment, you must satisfy

material for the correct operation

Description

nual for FX1S, FX1N, FX2N andrammable Logic Controllers

g the RS422 interface board

g the RS485 interface board

g the RS232 interface board

g the variable potentiometer input

g the special adapter board

g the display module 5DM

• Under no circumstances will Mitsubishi Electric be liable redamage that may arise as a result of the installation or use

• All examples and diagrams shown in this manual areunderstanding the text, not to guarantee operation. Miresponsibility for actual use of the product based on these

• Owing to the very great variety in possible application of tyourself as to its suitability for your specific application.

Associated Manuals

The following manuals are recomended as esential reference of a FX1N series Programmable Logic controller.

Manual Name Manual Number

FX Programming Manual II JY992D88101 Programming maFX2NC series Prog

FX1N-422-BD Suplementary JY992D84101 Instruction regardin

FX1N-485-BD Users JY992D84201 Instruction regardin

FX1N-232-BD Users JY992D84401 Instruction regardin

FX1N-8AV-BD JY992D84601 Instruction regardinboard

FX1N-CNV-BD JY992D84701 Instruction regardin

FX1N-5DM Users JY992D84901 Instruction regardin

Page 7: FX1N PLC Hw Manual

v

.................................ii

................................1-1

...................................... 1-6

...................................... 1-7

...................................... 1-8

...................................... 1-9......................................... 1-11......................................... 1-13.................................... 1-14

................................2-1

...................................... 2-1

...................................... 2-4

FX1N Series Programmable Controllers

Table of Contents

Guideline .............................................................

1. Introduction............................................................1.1 World Specification. .......................................................1.2 Model Name ..................................................................1.3 Serial Numbers .............................................................1.4 Configuration .................................................................

1.4.1 Input/Output Points and Current Consumption ..............1.4.2 Rules of Expansion ........................................................

1.5 EEProm Back up Data...................................................

2. Terminal layouts ....................................................2.1 Main units ......................................................................2.2 FX2N and FX0N Extension blocks .................................

Page 8: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

vi

................................3-1

...................................... 3-2

...................................... 3-4

...................................... 3-5

...................................... 3-6

...................................... 3-7

...................................... 3-8

.................................... 3-10

.................................... 3-11

.................................... 3-12......................................... 3-12......................................... 3-13

................................4-1...................................... 4-1...................................... 4-1...................................... 4-1...................................... 4-2...................................... 4-3...................................... 4-4...................................... 4-4

3. Installation Notes...................................................3.1 Product Outline..............................................................3.2 FX1N RUN/STOP Control ..............................................3.3 General Specifications...................................................3.4 PLC Mounting Arrangements ........................................3.5 DIN Rail Mounting .........................................................3.6 Direct Mounting ............................................................3.7 Termination at Screw Terminals ....................................3.8 Wiring Techniques.........................................................3.9 Installing Optional Units .................................................

3.9.1 Special Function Boards ................................................3.9.2 FX1N-5DM Display Module ............................................

4. Power Supply ........................................................4.1 Wiring Techniques.........................................................4.2 Wiring Cautions .............................................................4.3 Power Supply ................................................................4.4 Power Requirements ....................................................4.5 Example Wiring .............................................................4.6 Service Power supply ....................................................4.7 Earthing / Grounding .....................................................

Page 9: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

vii

................................5-1

...................................... 5-1........................................... 5-2........................................... 5-3........................................... 5-4........................................... 5-5...................................... 5-6........................................... 5-6........................................... 5-7

................................6-1

...................................... 6-1........................................... 6-2........................................... 6-3........................................... 6-3........................................... 6-4........................................... 6-4...................................... 6-5

5. Inputs.....................................................................5.1 24V DC input Specifications ..........................................

5.1.1 Typical Wiring .................................................................5.1.2 Input Circuit Connection .................................................5.1.3 Diodes and Inputs Connected in Series .........................5.1.4 Resistors andInputs Connected in Parallel ....................

5.2 AC110V Input Extension Block......................................5.2.1 Input Circuit Connection .................................................5.2.2 Programming Caution ....................................................

6. Outputs..................................................................6.1 Output Specifications.....................................................

6.1.1 Relay Output Example ...................................................6.1.2 Reliability Tests ..............................................................6.1.3 Response Times ............................................................6.1.4 Transistor Output Example.............................................6.1.5 Japanese Model Transistor Output ................................

6.2 Applying Safe Loads......................................................

Page 10: FX1N PLC Hw Manual

FX1N Series Programmable Controllers

viii

................................7-1...................................... 7-1...................................... 7-2...................................... 7-3...................................... 7-3...................................... 7-4...................................... 7-5...................................... 7-6...................................... 7-7...................................... 7-8.................................... 7-11

7. Diagnostics............................................................7.1 Preliminary Checks........................................................7.2 ERROR LED ON (CPU ERROR) ..................................7.3 Common Errors .............................................................7.4 Maintenance ..................................................................7.5 Operation and Error Flags .............................................7.6 PLC Status Registers ...................................................7.7 Error Registers ..............................................................7.8 Error Codes ...................................................................7.9 Instruction List ...............................................................7.10 Device List ....................................................................

Page 11: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 12: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

Page 13: FX1N PLC Hw Manual

Introduction 1.

1-1

the FX1N Series Programmable

RY

DIMENSIONSmm (inches)

WEIGHTkg (lbs)

0 z

90(3.6)

90(3.5)

75(3.0)

0.45 (0.99)

90(3.6)

0.45(0.99)

130(5.2)

0.65(1.44)

175(7.0)

0.80(1.77)

FX1N Series Programmable Controllers

1. Introduction

This manual covers the hardware installation instructions forLogic Controller.

MODELINPUT OUTPUT POWE

SUPPLQTY TYPE QTY TYPE

FX1N-14MR-ES/UL 8

24V DCSink /

Source

6(8)

Relay

100-24VAC

+10%-15%

50/60H

FX1N-24MR-ES/UL14

(16)10

(16)

FX1N-40MR-ES/UL 24 16

FX1N-60MR-ES/UL36

(40)24

Page 14: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-2

nt.

.95'')8 (0.31'')

DIN rail

mounting

slot

UNITS: mm (inches)

Main unit outline

Please see the previous page for each units width measureme

N X14

24V Y7

Y6Y0

FX1N-24M R

X0 X2

X1 X3 X5

X4

X7

X6

X11

X10

S/S X13

X12

X15

L

0V

Y11COM 2 COM 4

Y10Y5

Y4

Y2Y1

COM 0 COM 1 COM 3

Y3

POW ER

ERROR

IN

OUT

0 1 2 3

0 1 2 3

RUN

4 5 6 7

4 5 6 7

1110

131110 12

14 15

W

W - 8 (0.31'')

82(3.20'')

90(3.54'')

75 (2

2 - 4.5 (0.18'')

Page 15: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-3

RY

DIMENSIONSmm (inches)

WEIGHTkg (lbs)

z 150 (5.9)

90(3.5)

87(3.4)

0.75 (1.65)

z

150(5.9)

0.65(1.4)

182(7.2)

0.85(1.9)

z220(8.7)

1.00(2.2)

Powered Extension units

MODELINPUT OUTPUT POWE

SUPPLQTY TYPE QTY DEVICE

FX0N-40ER-ES/UL 24

24V DCSink /Source

16 Relay

100-240VAC+10%,-15%

50/60H

FX0N-40ET-DSS/UL 24 16 Transistor(Source)

24VDC+20%-15%FX0N-40ER-DSS 24 16 Relay

FX2N-32ER-ES/UL 16 16 Relay 100-240VAC+10%,-15%

50/60H

FX2N-32ET-ESS/UL 16 16 Transistor(Source)

FX2N-48ER-ES/UL 24 24 Relay

FX2N-48ER-DS 24 24 Relay24VDC+20%-30%

FX2N-48ET-ESS/UL 24 24 Transistor(Source)

100-240VAC+10%,-15%

50/60HFX2N-48ER-UA1/UL 24 110VAC 24 Relay

Page 16: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-4

DIMENSIONSmm (inches)

MASS (WEIGHT)kg (lbs)

43(1.7)

90(3.5)

87(3.4)

0.2(0.44)

70(2.8)

0.3(0.66)

40(1.6)

90(3.5)

87(3.4)

0.3(0.66)

Extension blocks

MODELINPUT OUTPUT

QTY TYPE QTY DEVICE TYPE

FX0N-8EX-UA1/UL 8110V AC

inputs- - -

FX0N-8EX-ES/UL 8 24V DCSink/

Source

- - -

FX0N-8ER-ES/UL 4 4Relay

-

FX0N-8EYR-ES/UL - - 8 -

FX0N-8EYT-ESS/UL - - 8 Transistor Source

FX0N-16EX-ES/UL 1624V DC

Sink/Source

- - -

FX0N-16EYR-ES/UL - - 16 Relay -

FX0N-16EYT-ESS/UL - - 16 Transistor Source

FX2N-16EX-ES/UL 1624V DC

Sink/Source

- - -

FX2N-16EYR-ES/UL - - 16 Relay -

FX2N-16EYT-ESS/UL - - 16 Transistor Source

Page 17: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-5

PPLYDIMENSIONSmm (inches)

MASS (WEIGHT)kg (lbs)ernal

V DC

mA*143

(1.7)

90(3.5)

87(3.4)

0.2(0.44)mA*1

0mA

55(2.1) 0.3(0.66)

5mA

0mA

0mA

0mA43

(1.7)

0.2(0.44)

0mA 0.5(1.1)

mA*1 43(1.7)

87(3.4) 0.2(0.44)

0mA 75(3.0)

75(3.0) 0.3(0.66)

*1: Internal 24V DC*2: The value depends on the switch setting.

Special function blocks

MODEL DESCRIPTION

NUMBEROF I/O POWER SU

I O Internal5V DC

Ext24

FX2N-2DA Digital to analog converter - 8 - 30mA 85

FX2N-2AD Analog to digital converter - 8 - 20mA 50

FX2N-4DA Digital to analog converter - 8 - 30mA 20

FX2N-4AD Analog to digital converter - 8 - 30mA 5

FX2N-4AD-PT PT 100 probe interface - 8 - 30mA 5

FX2N-4AD-TC Thermo-couple interface - 8 - 30mA 5

FX2N-32CCL CC-Link Interface block - 8 - 130mA 5

FX2N-16LNK-MMELSEC-I/O LINK Remote I/O system mas-ter block

*2 8 *2 200mA 9

FX0N-3A Analog / Digital converter - 8 - 30mA 90

FX2N-8AD Analog input block - 8 - 50mA 8

Page 18: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-6

1.1 World Specification.

Input Sink / Source

World spec models : SINK / SOURCE.Japanese models : ALWAYS SINK.

OutputsTransistor

World spec models : ALWAYS SOURCE.Japanese models : ALWAYS SINK.

Page 19: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-7

I/O. Only FX2NC.

spec.

nese spec.

spec.

spec., DC source transistor

pply World spec.

upply World spec., DC source

pply, AC inputs

red product

1.2 Model Name

Notes on model name

F X 1 N - 2 4 M T - - D S S /

C)

A)B)

D)

G)F)E)

A) PLC type : FX1N

B) Total number of I / O channels

C)

Unit type

M MPU - main unit

E Powered extension unit

EX Extension block, input

EY Extension block, output

D)

Output type

R Relay

T Transistor

E) T Terminal style

F)

Features

Omit AC, Japanese

D 24V DC Japa

DS 24V DC World

DSS 24V DC World

ES AC Power Su

ESS AC Power Stransistor

UA1 AC Power Su

G) UL CE,UL registe

Page 20: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-8

1.3 Serial Numbers

Notes on serial numbers1) Production year

2) Production month

3) Production serial number

S E R I A L N O . : 0 6 3 2 6 73)1)

2)e.g. 0=2000 1=2001 1 - 9 = Jan - Sept

X = OctY = NovZ = Dec

Page 21: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-9

G

J

FX2N-16EX-ES/ULFX2N-16EYR-ES/ULFX2N-16EYT-ESS/UL

FX0N-8EX-ES/ULFX0N-8EX-UA1/ULFX0N-8ER-ES/ULFX0N-8EYR-ES/ULFX0N-8EYT-ESS/ULFX0N-16EX-ES/ULFX0N-16EYR-ES/ULFX0N-16EYT-ESS/UL

K

FX2N-2DAFX2N-4DAFX2N-2ADFX2N-4ADFX2N-4AD-PTFX2N-4AD-TCFX2N-32CCLFX2N-16LNK-MFX0N-3A

I

L/UL

L/ULL/UL

/UL

FX2N-8AD

1.4 Configuration

Schematic system

B

FX1N-5DMFX1N-EEPROM-8L

FX1N-14MR-ES/ULFX1N-24MR-ES/ULFX1N-40MR-ES/ULFX1N-60MR-ES/UL

FX1N-14MT-ESS/ULFX1N-24MT-ESS/ULFX1N-40MT-ESS/ULFX1N-60MT-ESS/UL

FX1N-232-BDFX1N-422-BDFX1N-485-BDFX1N-CNV-BDFX1N-8AV-BD

A

C

1

2

3

D

RS 422/RS 232 CONVERTERFX-232AW(C)

FX-10DU-E FX-40DU-ESFX-20DU-E FX-40DU-TK -ESFX-25DU-E FX-50DU-TKS-EFX-30DU-E

F930GOT F940GOTFX-10DM-E

F

FX-10P-E FX-20P-E

H

MELSEC MEDOCFX-PCS/AT-EEMELSEC MEDOC PLUS

FX-PCS/WIN-E

E

FXON-232ADP*FXON-485ADP**used withFX1N-CNV-BD

1

FX0N-40ER-ES/UFX0N-40ET-ESSFX0N-40ER-DS

FX2N-32ER-ES/UFX2N-32ET-ESSFX2N-48ER-ES/U

4

FX2N-48ER-UA1FX2N-48ER-DSFX2N-48ET-ESS

GX Developer-FX

Page 22: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-10

Configuration notesA MPU-Main unit (Main Processing Unit)

B FX1N Memory cassette or Display Module

C FX1N Expansion boards

D FX0N Network adapters

E Programming cables

F Programming software

G HMI devices, F900GOT, FX-DU Series

H Dedicated programming tools

I Powered extension units

J Extension blocks

K Special function blocks

Memory port

Extension board port

Programming port

MPU bus port

Page 23: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-11

s types of FX series extensionction block current consumption.

k should occupy 16 input/output

1.4.1 Input/Output Points and Current Consumption

The following tables show the input/output points of varioublocks, and special function blocks, along with the special fun.

*1:8 points are used for actual input/output, however, this blocpoints.

Extension blocks

MODEL INPUTX

OUTPUTY TOTAL

FX0N-8ER-ES/UL 4(8) 4(8) 16*1

FX0N-8EX-ES/UL 8 - 8

FX0N-8EX-UA1/UL 8 - 8

FX0N-8EYR-ES/UL - 8 8

FX0N-8EYT-ESS/UL - 8 8

FX0N-16EX-ES/UL 16 - 16

FX0N-16EYT-ESS/UL - 16 16

FX0N-16EYR-ES/UL - 16 16

FX2N-16EX-ES/UL 16 - 16

FX2N-16EYR-ES/UL - 16 16

FX2N-16EYT-ESS/UL - 16 16

Page 24: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-12

OUTPUTY TOTAL

- 8

8 16

- 8

- 8

- 8

- 8

- 8

- 8

- 8

- 8

*2 *2

- -

- -

*2:The value depends on the switch setting.

Special function block Function adapters

MODEL CURRENT CONSUMPTION5V DC

INPUTX X/Y

FX0N-3A 30mA - 8

FX0N-16NT 20mA 8 -

FX0N-32NT-DP 170mA - 8

FX2N-2AD 20mA - 8

FX2N-4AD 30mA - 8

FX2N-4AD-PT 30mA - 8

FX2N-4AD-TC 30mA - 8

FX2N-2DA 30mA - 8

FX2N-4DA 30mA - 8

FX2N-32CCL 130mA - 8

FX2N-16LNK-M 200mA *2 8

FX0N-232ADP 200mA - -

FX0N-485ADP 30mA - -

Page 25: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-13

s or upto 32 points of I/O whenfunction blocks when used iny 8 special function blocks when

pecial function blocks.

S/UL

-ES/UL

1.4.2 Rules of Expansion

The FX1N Series can be expanded by 2 special function blockused on its own. It can also be expanded by 4 special conjunction with an FX0N extension unit (2+2), or expanded bused in conjunction with an FX2N extension unit (2+6).

The maximum for an FX1N system is 128 points of I/O and 8 s

Y7COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y1 Y3 COM5 Y524+COM Y0 Y1 Y2 Y4 Y6 Y0 Y2 Y4 Y6

X7X3 X5N X0 X2 X4 X6L

COM COM X1

POWER

OUT

0 7654321

IN

0 1 2 3 4 5 6 7

X1X0 X2

X3X4

X5 X7X6

X1X0 X2

X3X4

X5 X7X6

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7 POWER

OUT

4 765

3210

RD

SD

POWER

24+ X1 X3 X5 X7X0 X2 X4 X6

X0X1

X2 X4 X6X3 X5 X7

POWER

7

7

0

IN

1

1

2

2

3

3

4

4

5

5

6

60

FX0N-16EX

FX0N-40ER

FX0N-8EYR

FX0N-232ADP

X000~X043 X050~X057

Y000~Y027 X060~X067

X070~X117

Y030~Y047 Y050~Y057

POWER

ERROR

IN

OUT

0 1 2 3

0 1 2 3

RUN

4 5 6 7

4 5 6 7

1716

373534 36

10 11 12 13 14 15 16 17

40 41 42 43

14 1510 11 12 13

272524 2620 21 22 23

30 31 32 33

272624 2520 21 22 23

COM2 Y5Y6

24+Y0 Y2Y1

COM0 COM1 COM3Y3Y4

Y17Y11

COMX10

X13 X43X42X12L N X0 X2

X1 X3 X5X4

X7X6

X11 X15X14 X16

X21X20

X23 X25X24

Y7Y10

Y27Y12 Y14

COM7COM4

X27X26

X31X30

X33X32

X35X34

X37X36

X41X40

Y16Y15

Y20 Y22Y21

Y24 Y26COM6

X17

FX1N-60MR

COMY13 COM5 Y23 Y25

X22

FX0N-232ADP FX1N-60MR-ES/UL FX0N-16EX-E

FX0N-40ER-ES/UL FX0N-8EYR

Page 26: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Introduction 1.

1-14

wn, before the data is lost.

ys, and requires 30 minutes to

1.5 EEProm Back up Data

FX1N existing data will be kept for 5 minutes during power do

The capacitor backed memory will retain programs for 10 darecharge upon power up.

Page 27: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Terminal layouts 2.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 28: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Terminal layouts 2.

Page 29: FX1N PLC Hw Manual

Terminal layouts 2.

2-1

FX1N product range. ed to aid the creation of wiring

X4

M R -E S/U L

X5

2 Y3

3

CO M3

X7X6

Y5CO M4

X12X13X11

X10X15

X14

Y6Y4

Y10Y7 Y11

X1N-24M

FX1N Series Programmable Controllers

2. Terminal layouts

The following selection of terminal layouts are taken from the Note: All layouts are diagrammatic only and are only intenddiagrams.

2.1 Main units

S/S X1N X0 X4

FX1N-14MR-ES/UL

X5

0V Y0 Y1 Y2 Y3

X3X2

24V COM0 COM1 COM3COM2

LX7

X6

Y4COM4 COM5

Y5

S /S X1N X0

FX 1N-24

0V Y0 Y1 Y

XX2

24V CO M0 CO M1 CO M2

L

FX1N-14M F

Page 30: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Terminal layouts 2.

2-2

24X25

X26X27

Y1615 Y17

X3130 X32

X33X34

X35X40

X41X42

X43

Y20 Y22Y21 Y23O M6

Y24 Y26Y25 Y27CO M7

X36X37

S /S X1N X0 X4

FX 1N-40M R -ES /U L

X5

0V Y0 Y1 Y2Y3

X3X2

24V CO M0 CO M1 CO M3CO M2

LX7

X6

Y5 CO M4

X12X13X11

X10X15

X14

Y6Y4 Y14Y7 Y11

X20X21X17

X16X23

X22 X

Y10 Y12Y13 CO M5 Y

FX1N-40M

S /S X1N X0 X4

FX 1N-60M R -E S/U L

X5

0V Y0 Y1 Y2Y3

X3X2

24V CO M0 CO M1 CO M3CO M2

LX7

X6

Y5 CO M4

X12X13X11

X10X15

X14

Y6Y4 Y14Y7 Y11

X20X21X17

X16X23

X22 X24X25

X26X27

Y10 Y12Y13 CO M5

Y16Y15 Y17

X

C

FX1N-60M

Page 31: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Terminal layouts 2.

2-3

X5

X7

FX

2N -16EY

R-E

S/U

L

FX

2N -16EY

T-E

SS

/UL

X3

X1

X0

X5

X6

X3

X1

S/S

X7

X4

X2

X0

X6

X4

X2

Y5

Y7

Y3

Y1

Y0

Y5

Y6

Y3

Y1

CO

M1

Y7

Y4

Y2

Y0

Y6

Y4

Y2

CO

M2

Y5

Y7

Y3

Y1

Y0

Y5

Y6

Y3

Y1

+V

0Y

7Y

4Y

2Y

0Y

6Y

4Y

2+

V1

+V 0 Y1 Y3Y0 Y2 Y4 Y6

F X 0N-16EYT -E SS /U L

Y5 Y7

Y0 Y2 Y4 Y6

+V 1

+V 2 Y1 Y3 Y5 Y7+V 3

2.2 FX2N and FX0N Extension blocks

S/S

X1

X3

X0

X2

CO

M1

X5

X7

X4

X6

FX

0N -8EX

-ES

/UL

Y1

Y3

Y0

Y2

Y5

Y7

Y4

Y6

FX

0N -8EY

R-E

S/U

L

CO

M2

Y1

Y3

Y0

Y2

Y5

Y7

Y4

Y6

FX

0N -8EY

T-E

SS

/UL

+V

0+

V1

X1

X3

X0

X2

Y1

Y3

Y0

Y2

FX

0N -8ER

-ES

/UL

S/S

CO

M1

X1

X3

X0

X2

X5

X7

X4

X6

FX

0N -8EX

-UA

1/UL

CO

M1

FX

2N -16EX

-ES

/UL

S /S X 1 X 3X 0 X 2 X 4 X 6

F X 0N-16EX -E S /U L

X 5 X 7

X 1 X 3 X 5 X 7X 0 X 2 X 4 X 6

CO M1 Y1 Y3Y0 Y2 Y4 Y6

F X 0N-16EYR -ES /U L

Y5 Y7

Y0 Y2 Y4 Y6

CO M2

CO M3 Y1 Y3 Y5 Y7CO M4

Page 32: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Terminal layouts 2.

2-4

MEMO

Page 33: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation notes 3.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 34: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation notes 3.

Page 35: FX1N PLC Hw Manual

Installation Notes 3.

3-1

fe and easy. When the productsally, they must be installed in atalled in accordance to the local

FX1N Series Programmable Controllers

3. Installation Notes

The installation of FX1N products has been designed to be saassociated with this manual are used as a system or individusuitable enclosure. The enclosure should be selected and insand national standards.

Page 36: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-2

p cover removed

POWER

ERROR

IN

OUT0 1 2 3

0 1 2 3

RUN

4 5 6 7

4 5 6 7

1110

131110 12

14 15

FX1N-24MR

X0 X2X1 X3 X5

X4X7

X6X11

X10S/S X13

X12X15

X14N

Y7 Y11Y10Y5

Y4Y0 Y2Y1 Y3 Y6

COM1 COM2 COM3 COM4

12

13

3.1 Product Outline

Features of the FX 1N PLC

➁ ➂

➉ ➈

To

X0 X2X1 X3 X5

X4X7

X6X11

X10S/S X13

X12X15

X14L N

0V24V Y7 Y11

Y10Y5Y4

Y0 Y2Y1COM0

Y3

POWER

ERROR

IN

OUT

0 1 2 3

0 1 2 3

RUN

4 5 6 7

4 5 6 7

1110

131110 12

14 15

Y6

FX1N-24MR

COM1 COM2 COM3 COM4

L

0V24V COM0

11

15

14

Page 37: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-3

d from VR1. Lower pot D8031

Features table1 Top cover

2 Direct mounting holes (4.5 mm diameter)

3 I/O terminal block securing screws

4 Input terminals (24V DC) and power supply terminals

5 Input LED status indicators

6 Expansion port cover

7 PLC status indicators (POWER, RUN, ERROR)

8 Output LED status indicators

9 DIN rail mounting clip

10 Output terminals and power supply source terminals

11 Optional equipment connector

12 Expansion port

13 Run/Stop switch

14 Programming port

15Variable analog potentiometers. Upper pot, D8030 rearead from VR2

Page 38: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-4

ort.

ters.

eripheral.

e RUN-input terminal. Please

is determined by the most

STOP is made from a personal STOP then back to RUN to

ction RUN INPUT

TERMINALFX1N MPU STATUS

RUN

RUN

STOP

RUN

3.2 FX1N RUN/STOP Control

RUN or STOP of the FX1N can be controlled by:

The RUN/STOP switch mounted next to the programming p

A standard input (X0 to X17) defined by the system parame

Remotely from a personal computer or other programming p

Note :The FX1N RUN/STOP switch works in parallel with threfer to the table below.During remote operation the FX1N RUN/STOP statusrecently operated control.E.g. If the RUN/STOP switch is in RUN and a remotecomputer the RUN/STOP switch must be switched toswitch the MPU back to RUN mode.

S/S

R U N

0V 24V X0

RUN/STOP sele RUN/STOP

SWITCH

Run input terminal

Page 39: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-5

tion

ation

ation

mm Half Amplitude

/s2 Accelerationes (80 min in each direction)

mm Half Amplitude

/s2 Accelerationes (80 min in each direction)

ration, Action Time: 11 msction X, Y, and Z

sted by noise simulator

ints, terminals and ground

oints, terminals and ground

3.3 General Specifications

Item Descrip

Operating Temperature 0 to 55 °C (32 to 131 °F)

Storage Temperature -20 to 70 °C (-4 to 158 °F)

Operating Humidity 35 to 85% Relative Humidity, No condens

storage Humidity 35 to 90% Relative Humidity, No condens

Vibration Resistance - Direct Mounting

Conforms to IEC 68-2-6; 10 - 57 Hz: 0.75

57 - 150 Hz: 9.8 m Sweep Count for X, Y, Z: 10 tim

Vibration Resistance - DIN rail Mounting

Conforms to IEC 68-2-6; 10 - 57 Hz: 0.035

57 -150 Hz: 4.9 m Sweep Count for X, Y, Z: 10 tim

Shock Resistance Conforms to IEC 68-2-27: 147m/s2 Accele 3 times in each dire

Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, te

Dielectric Withstand Voltage 1500 V AC > 1 min, tested between all po

Insulation Resistance 5 MΩ > at 500 V DC, tested between all p

Ground Class D (100 Ω or less)

Page 40: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-6

ever mount them to the floor or

X0N-65EC

1N

PU

Fun

ctio

n bl

ock

Fun

ctio

n bl

ock

A

A

,FX 2N

sions A

0m m (1.97 inches)

A

3.4 PLC Mounting Arrangements

To prevent a rise in temperature, mount the units to walls. Nceiling of an enclosure.

Below (left) Single row arrangement Below (right) Double row arrangement using extension cable F

(650mm (25.59 inches); supplied separately).

FXCA

FX 0N

ExtenblockA

A

> 5A

FX 1N

C P U

Fun

ctio

n bl

ock

Fun

ctio

n bl

ock

A

A

AA

> 50m m (1.97 inches)A

Page 41: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-7

wing conditions: excessive or r rain, excessive heat, regular

it during installation e.g. cut e the protective paper band, to

22). To release, pull the spring

Caution

• Units should not be installed in areas subject to the folloconductive dust, corrosive or flammable gas, moisture oimpact shocks or excessive vibration.

• Take special care not to allow debris to fall inside the unwires, shavings etc. Once installation is complete removprevent overheating.

3.5 DIN Rail Mounting

Units can be snap mounted to 35mm DIN rail (DIN EN 500loaded clips away from the rail and slide the unit up and off.

Page 42: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-880(3

.15)

90(3

.54)

FX0N-16E

UNITS: mm (inches)

3.6 Direct Mounting

POWERS

P G 0O O GT D P

RR

F R C EP P L R

A

80(3

.15)

90(3

.54)*

4(0.16)

∅ = 4.5mm (0.18)

UNITS: mm (inches)

1IN 0

7

23456

POWER

1IN 0

7

23456

20(0.79)

80(3

.15)

90(3

.54)

40(1.57)

COM1 Y1 COM2 Y5 Y7Y0 Y2 Y4 Y6

Y0COM3

Y2 Y6Y3 COM4 Y7

POWER

7

7

0

OUT

1

1

2

2

3

3

4

4

5

5

6

60

Y3

Y1 Y5Y4

70(2.76)60(2.36)

FX2N-16E

Page 43: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-9

EL A

NT-DP

43(1.69)

2ADP

5ADP

Side view

MODEL A MODEL A MOD

FX2N-4DA

55(2.16)

FX2N-2DA

43(1.69)

FX0N-32

FX2N-4AD FX2N-2AD FX0N-23

FX2N-4AD-PT FX2N-32CCL FX0N-48

FX2N-4AD-TC FX2N-16LNK-M FX0N-8E

FX0N-3A FX0N-8E

87(3.42)*

9(0.35)

FX0N-232ADP is 68(2.68)

UNITS: mm (inches)

Page 44: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-10

2N product should be fitted withscrews should be tightened toprevent a loose connection from

3.7 Termination at Screw Terminals

Cables terminating at a screw terminal of an FX0N, FX1N or FXinsulated crimp terminals, see example shown. Terminals between 0.5 to 0.8 Nm. Screw terminals must be secured to causing a malfunction

.

To suit M3 (0.12in)screw terminals

Max.6.2mm0.24 in

Max.6.2mm0.24 in

Page 45: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-11

easy. If during the installation ofontact a professional electrician the installation site.

output signals or allow them to

w them to share the same arated or insulated with regard

nce consideration for voltage

s far as possible from equipment.

3.8 Wiring Techniques

The wiring of FX1N products has been designed to be safe andthese products or associated products concern is felt, please cwho is trained to the local and national standards applicable to

Wiring cautions

• Do not run input signals in the same multicore cable asshare the same wire.

• Do not lay I/O signal cables next to power cables or allotrunking duct. Low voltage cables should be reliably septo high voltage cabling.

• Where I/O signal lines are used over an extended distadrop and noise interference should be made.

• Always ensure that mounted units and blocks are kept ahigh-voltage cables, high-voltage equipment and power

Page 46: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-12

cial function board to the FX1N

l unit, please see the relevant

special function board. Only onerds.

quipment board. r port.

r.

B).

crews C).

removing section D)’ to expose)

w E).

3.9 Installing Optional Units

3.9.1 Special Function Boards

The following is a generic explanation of how to install a spePLC. For greater detail and specifications of each optionaproducts manual.

Always make sure the power is turned off, before installing a board can be used at one time, do not try to stack multiple boa

A) Special function or optional eB) Optional equipment connectoC) M3 screw to secure board. D) Top cover for board. E) M3 screw to secure top coveNote: Do not remove this screw.

• Remove base unit top cover.

• Plug board A) into connector

• Fix board to base unit using s

• Attach top cover for board D)connector etc. (if applicable

• Secure top cover with M3 scre

A)

B)

C)

D)

D)'E)

Note

C)

Page 47: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-13

5DM.

nual.

C)

3.9.2 FX1N-5DM Display Module

Always make sure the power is turned off, before installing the

A) Top cover for DMB) Optional equipment connector.C) M3 screw to secure top cover.

• Remove the base unit top cover.

• Attach the top cover for DM A), andsecure with screw C) (if 5DM is to bepermanently mounted)

• Plug in the 5DM at connector B)

For further information please refer to the FX1N-5DM users ma

B)

A)

Page 48: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Installation Notes 3.

3-14

MEMO

Page 49: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Power supply 4.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 50: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Power supply 4.

Page 51: FX1N PLC Hw Manual

Power Supply 4.

4-1

easy. If during the installation ofontact a professional electrician the installation site.

signals or allow them to share the

share the same trunking duct. Loward to high voltage cabling.

e consideration for voltage drop

“L” terminal and the “Neutral” cableire to the “N” terminal, the user might

FX1N Series Programmable Controllers

4. Power Supply

4.1 Wiring Techniques

The wiring of FX1N products has been designed to be safe andthese product or associated products concern is felt, please cwho is trained to the local and national standards applicable to

4.2 Wiring Cautions

• Do not run input signals in the same multicore cable as outputsame wire.

• Do not lay I/O signal cables next to power cables or allow them tovoltage cables should be reliably separated or insulated with reg

• Where I/O signal lines are used over an extended distancand noise interference should be made.

4.3 Power Supply

When wiring AC supplies the “Live” cable should be connected to theshould be connected to the “N” terminal. Do NOT connect the “Live” wreceive a dangerous shock on powerup.

Page 52: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Power Supply 4.

4-2

FX1N-40M FX1N-60M, 50-60Hz PLC will continue operation.LC will shut down.

250V 3.15A (3A) s

32W 35W

*1 Includes the input current (7 or 5 mA per point).

4.4 Power Requirements

FX1N-14M FX1N-24MPower supply 100 - 240V AC +10%, -15%Max. allowable momentary power failure period

10ms; If less than 10ms, the If 10ms or more, the P

Fuse (size) rating 250V 1A

In-rush current100V AC - Max. 15A for 5m200V AV - Max. 25A for 5ms

Power consumption *1 29W 30W

Page 53: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Power Supply 4.

4-3

ly 100 - 240V AC +10% -15%

ector or Fuse

stop

ly switch

pilot indicator

ly for loads

resistor 100Ω or less (class3)

4.5 Example Wiring

AC /D CConverter

24V D C

Extens ion b lock

Extens ion b lock

M C

PL

M C

M C M C

L

N

24V0V

Power supp50 - 60 Hz

Circuit prot

Emergency

Power supp

Power ON

Power supp

Grounding

Fuse

Main unit

Breaker

Page 54: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Power Supply 4.

4-4

its own and, when used with

t. Ground resistance must be not be connected to the same ut if a proper ground cannot be rounded.

4.6 Service Power supply

The FX1N can supply 24V DC at 400mA when used onextension or special function blocks.

4.7 Earthing / Grounding

Use a cable at least 0.2mm2 (AWG24) to ground equipmenless than 100Ω (class 3). Note that the ground cable must ground as the power circuits. Grounding is recommended bprovided, the PLC will still operate correctly without being g

Page 55: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 56: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

Page 57: FX1N PLC Hw Manual

Inputs 5.

5-1

0N, FX2N Extension block

0%

24V DC, 5mA

>3.5mA

---

ler

it

FX1N Series Programmable Controllers

5. Inputs

5.1 24V DC input Specifications

FX1N main unit,extension block FX

X0 X7 X10 ∞Input voltage 24V DC ±1

Input current 24V DC, 7mA 24V DC, 5mA

Input switching current

OFF ON >4.5mA >3.5mA

ON OFF <1.5mA

Response time 10ms

Variable response time X000-X007 0-15ms

Circuit isolation Photocoup

Operation indication LED is l

Page 58: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-2

S/S X0 X1 X2

**M

5.1.1 Typical Wiring

Service supply

PNP Sensor

NPN Sensor

Input Device Contact

FX1N main unit

24V 0V S/S X0 X1 X2

PNP

FX1N-**M

FX1N-Source

24V 0V

NPN

FX1N-

FX1N-Sink

Page 59: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-3

24V

X24V DC

0VS/S

S/S)

S /S

X

S ink

4.3 kΩ

5.1.2 Input Circuit Connection

FX1N Main unit

FX2N and FX0N Extension blocks

24V

X24V DC

0VS/S

Source (-ve S/S) Sink (+ve

S /S

X

Source

24V D C±10%

4.3 kΩ

24V D C±10%

Page 60: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-4

FX0N, FX2NExtention block

X

S/S

5.1.3 Diodes and Inputs Connected in Series

Vdrop across the diode Max. 4VNo more than 2 LEDs should be connected in series.

24V

X

0V

S/S

FX 1N

Page 61: FX1N PLC Hw Manual

FX Inputs 5.

5.1.

e stated value, then add

is greater than the stated

1N Series Programmable Controllers

4 Resistors and Inputs Connected in Parallel

Parallel resistance Rp: FX1N = 15kΩ. If resistance Rp is less than thRb. See equation 1 for Rb calculation.Alternatively; Current leakage: FX1N = 1.5mA. If the current leakage value, then add Rb. See equation 2 for Rb calculation.

Parall el LED

Rb ≤4Rp

15 - RpEqn 1 :

Rb ≤6

I - 1.5Eqn 2 :

24V

X

0V

S/S

Rp

Rb

5-5

Page 62: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-6

0-60Hz

kΩ/60Hz

/50Hz 6.2mA 110V AC/60Hz

V 1.7mA

D is lit

5.2 AC110V Input Extension Block

5.2.1 Input Circuit Connection

FX0N-8EX-UA1/UL

Input voltage 85-132V AC 5

Input impedance 21kΩ/50HZ 18

Input current 4.7mA 100V AC

OFF ON/ON OFF; input switching current 80V 3.8mA/30

Response time 25ms

Circuit isolation / Operation indication Photocoupler/LE

X0

COM1

85-132 V AC50/60 Hz

X1

X2

Page 63: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-7

routines are not suitable for use also not suitable.

5.2.2 Programming Caution

When using 110V AC units, high speed counter and interrupt due to the long 'ON/OFF' times. The following instructions are

FNC 52 MTR

FNC 56 SPD

FNC 72 DSW

Page 64: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Inputs 5.

5-8

MEMO

Page 65: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 66: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

Page 67: FX1N PLC Hw Manual

Outputs 6.

6-1

Transistor Output

5-30V DC

A/1 point, 0.8A/COM

12W/24V DC

1.5W/24V DC

------------------

ms; < 5µs (Y0,Y1 only)

I > 0.2A); <5µs (Y0,Y1 only)

PhotoCoupler

0.1mA/30V DC

energized

FX1N Series Programmable Controllers

6. Outputs6.1 Output Specifications

Description Relay Output

Switched voltages (resistive load)

≤ 250V AC, ≤ 30V DC

Rated current / N points (resistive load)

2A/1 point, 8A/COM 0.5

Max. Inductive load 80VA

Max. lamp load (tungsten load)

100W (1.17A/85V AC, 0.4A/250V AC)

Minimum loadWhen supply voltage < 5V DC allow at least 2mA flow

Response time (approx.)

OFF ON

10ms < 0.2

ON OFF

10ms < 0.2ms (

Circuit isolation By Relay

Open circuit current leakage

----------------

Operation indication LED is lit when coil is

Page 68: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

6-2

Do not use this terminal

Fuse

Surge absorbing Diode.

Exte rna l Mechan ica lInterlock

Emergency Stop

Noise suppressor 0.1µFcapacitor + 100-120ΩresistorContactor

Valve

Incandescent Lamp

DC Power Supply

AC Power Supply

6.1.1 Relay Output Example

Typical Relay

CO M0 Y0 Y1 Y2 Y3CO M1 CO M2 Y4 Y5

M C1 M C2

M C 2 M C 1

Page 69: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

6-3

ON/OFF test cycle. Please note relay contacts service life. Thenoid valve is 500,000 operations

figure below. If a response time'dummy' resistor and ensure the

01 are high speed responsee following characteristics:

5 - 24V DC, 100kHz maximum

response is required, a currentmust be used.

80VA0.8A/100V AC0.4A/240V AC

200,000

S-K180,S-K400

6.1.2 Reliability Tests

The test results in the table below were gathered from a 1 secthat the over current induced by in-rush greatly reduces therated life for an inductive AC load such as a contactor or soleat 20VA.

6.1.3 Response TimesOFF times increase as the load current decreases.For improved response times use a 'dummy' resistor, see theof 0.5 ms or better is required when using 'light loads' use a signal line has a current greater than 60mA/24V DC

Y000 and Y0outputs with th

10 - 100mA atoutput signal.

If a high speedof 10 - 100mA

20VA 35VA

Load capacity0.2A/100VAC0.1A/200VAC

0.35A/100V AC0.17A/240V AC

Life of contact (cycles) 3,000,000 1,000,000

Example load (Mitsubishi contactor) S-K10 ~ S-K95 S-K100 ~ S-K150

5 to 24VY

+V

Dummy load Load

10 to 100mA

DummyLoad

Page 70: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

6-4

Do not use this terminal

Emergency Stop

Fuse

External Mechanical Interlock

Output Terminal Y0

Output Terminal Y1

DC Power Supply

6.1.4 Transistor Output Example

6.1.5 Japanese Model Transistor Output

+V0 Y0 Y1 Y2 Y3+V1 +V2 Y4 Y5

M C1 M C2

M C 2 M C 1

CO M0 Y0 Y1 Y2 Y3CO M1 CO M2 Y4 Y5

M C1 M C2

M C 2 M C 1

Page 71: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

6-5

output, see previous figures. irection control of a motor),

PLC's sequencing alone. rcuits. (See preceding figure.)

6.2 Applying Safe Loads

Ensure all loads are applied to the same side of each PLC Loads which should NEVER simultaneously operate (e.g. dbecause of a safety critical situation, should not rely on theMechanical interlocks MUST be fitted to all safety critical ci

Page 72: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Outputs 6.

6-6

MEMO

Page 73: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

1 INTRODUCTION

2 TERMINAL LAYOUTS

3 INSTALLATION NOTES

4 POWER SUPPLY

5 INPUTS

6 OUTPUTS

7 DIAGNOSTICS

Page 74: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

Page 75: FX1N PLC Hw Manual

Diagnostics 7.

7-1

orrectly.

own load a small it has been written

rcibly turn ON/OFF

k the previously are complete take

any live or

FX1N Series Programmable Controllers

7. Diagnostics

7.1 Preliminary Checks

Check power supply, ground and I/O cables are wired c

Turn the power supply on. Check the power LED is lit. Dtest program into the PLC. Verify the program to ensureto the PLC correctly. Using the programming device, foeach output. Check the output LEDs for operation.

Put the PLC into RUN. Check the RUN LED is lit. Checdown loaded program works correctly. Once all checksthe PLC out of run and turn OFF the power supply.

During this testing stage take extreme care not to touchhazardous parts.

POWERRUN

ERROR

POWERRUN

ERROR

POWERRUN

ERROR

Page 76: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-2

s the memory cassette been talled or removed while the units s still been powered?

ramming error. Ensure the earth/ correctly rewired.

A

PC M/C PC M/C

7.2 ERROR LED ON (CPU ERROR)

FaultERROR LED ON

RemedyReset PLC. Power OFF,ON and trigger RUN input.

Possible results

LED OFFHainsha

LED is lit

Remedy

Possible results

LED is litPower OFF

Disconnect earth/ground terminal

LED is flashing

Check for progground cable is

Power ON

RemedyPossible program/scan time error. Check D8012 for program scan time, (units 0.2 ms must be less than 0.2 s, i.e data value <2000).

Possible resultsD8012 > D8000

POWERRUN

ERROR

A

B

PC M/C

B

Page 77: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-3

ting range.

by one program scan.

ue to vibration).

7.3 Common Errors

- Corroded contact points at some point in an I/O line.

- An I/O device has been used outside its specified opera

- An input signal occurs in a shorter time period that taken

7.4 Maintenance

- Check interior temperature of the panel.

- Check panel air filters if fitted.

- Check for loosening of terminals or mounting facilities (d

Page 78: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-4

Parallel link error

Parameter error

Syntax error

Program (circuit) error

Program execution error

Execution error latch

9)

9)

9)

PC hardware error

7.5 Operation and Error Flags

M8063(ref. D8063)

M8064(ref. D8064)

M8065(ref. D8065, D806

M8066(ref. D8066, D806

M8067(ref. D8067, D806

M8068(ref. D8068)

M8061(ref. D8061)

M8004(ref. 8004)

M8035

M8036

M8037

M8039(ref. D8039)

Error occurance(ON when M8060-7 are ON)

Forced RUN mode

Forced RUN signal

Forced STOP signal

Constant scan mode

Page 79: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-5

7.6 PLC Status Registers

02H =EEPR O M protect sw itch O FF0AH =EEPR O M protect sw itch O N10H =M PU m em ory

D8000(defau lt 200m s)

D8001

D8002

D8003

D8004

W atchdog tim er

PLC vers ion

26100 = FX 1N Vers ion 1 .0026 = FX 1N, 100 = Vers ion 1 .00

M em ory capac ity

0008=8K s teps

M em ory type

Error flag num ber8060=M 8060, (8060-8068)

Page 80: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-6

7.7 Error Registers

D8061

D8063

D8064

D8065

D8066

D8067

D8068

D8069

Error code for PLC hardware error

Error code for parallel link fault

Parameter error code

Syntax error code

Program (circuit) error code

Program execution error code

Latched stepnumber of execution error

Step number of errors associatedwith error flags M8065-M8067

Page 81: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-7

Check both power andcommunications connections

No errorParity/overrun/framing errorCharacter errorData sum check errorData format errorCommand errorWatchdog timer error

7.8 Error Codes

D8061 Check cable connections

No error0000RAM error6101Operation circuit error6102I/O bus error (M8069 = ON)6103

D8062Check the programmer / PCconnections

No error0000Parity/overrun/framing error6201Character error6202Data sum check error6203Data format error6204Command error6205

D8063

0000630163026303630463056306

Page 82: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-8

6 7 8 9

FEND WDT FOR NEXT

V BCD BIN

C WAND WOR WXOR

L SFWR SFRD

SPD PLSY PWM PLSR

ALT RAMP

FROM TO

D VRSC PID

S ZRN PLSV DRVI DRVA

TRD TWR HOUR

RD3A WR3A

> LD< LD≠ LD≤AND≠ AND≤ AND≥

≤ OR≥

7.9 Instruction List

0 1 2 3 4 5

000 Program Flow CJ CALL SRET IRET EI DI

010 Transfers, Comp CMP ZCP MOV BMO

020 + - x /, Logics ADD SUB MUL DIV INC DE

030 Shift SFTR SFT

040 Data Operation ZRST DECO ENCO

050 High Speed REF MTR HSCS HSCR

060 Handy Instructions IST ABSD INCD

070 FX I/O Devices DSW SEGL

080 FX Ser Devices RS PRUN ASCI HEX CCD VRR

150 Positioning AB

160 Real Time Clock TCMP TZCP TADD TSUB

170 Special Comms

220

In-line Compare

LD= LD

230 LD≥ AND= AND> AND<

240 OR= OR> OR< OR≠ OR

Page 83: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-9

Symbol FNC No D P

P

PID 88PLSR 059PLSV 157PLSY 057

PRUN 081

PWM 058

R

RAMP 067REF 050RD3A 176RS 080

S

SEGL 074SFRD 039SFTL 035

SFTR 034

SFWR 038SPD 056SRET 002SUB 021

Symbol FNC No D P Symbol FNC No D P

A

ABS 155E

EI 004ABSD 062 ENCO 042ADD 020

F

FEND 006ALT 066 FOR 008

AND 232-238 FROM 078

ASCI 082

H

HEX 083

BBCD 018 HOUR 169BIN 019 HSCR 054BMOV 015 HSCS 053

C

CALL 001

I

INC 024CCD 084 INCD 063CJ 000 IRET 003CMP 010 IST 060

D

DEC 025 L LD 224-230

DECO 041M

MOV 012DI 005 MTR 052DIV 023 MUL 022DRVA 159 N NEXT 009DRVI 158 O OR 240-246DSW 072

Page 84: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-10

ZZCP 011ZRN 156ZRST 040

Symbol FNC No D P

T

TADD 162V

VRRD 085TCMP 160 VRSC 086TO 079

W

WAND 026TRD 166 WDT 007TSUB 163 WOR 027TWR 167 WR3A 177TZCP 161 WXOR 028

Symbol FNC No D P Symbol FNC No D P

Page 85: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-11

Remarksrovided by built in EEPROM memory

128, dependent on user selectionInputs 128, Outputs 128)

M0 to M383

M384 to M1535

From the range M8000 to M8255

S0 to S999

S0 to S9

T0 to T199

T200 to T245

T246 to T249

T250 to T255

7.10 Device List

Item SpecificationProgram capacity 8K steps P

I/O configurationMax hardware I/O configuration points

(Max. software addressable

Auxiliaryrelay

(M coils)

General 384 points

Latched 1152 points (subset)

Special 256 points

State relays(S coils)

Latched 1000 points

Initial 10 points (subset)

Timers (T)

100 msRange: 0.1 to 3,276.7 s

200 points

10 msRange: 0.01 to 327.67 s

46 points

1 msRange: 0.001 to 32.767 s

4 point

100 msrenentive

Range: 0.1 to 3,276.7 s6 points

Page 86: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-12

C0 to C15Type: 16 bit up counter

C16 to C199Type: 16 bit up counter

C200 to C219Type: 32 bit bi-directional counter

C220 to C234Type: 32 bit bi-directional counter

C235 to C240

C241 to C245

C246 to C250

C251 to C255

Remarks

Counters (C)

General Range: 1 to 32,767 counts

16 points

Latched 184 points (subset)

General Range: -2,147,483,648 to

+2,147,483,647 counts20 points

Latched 15 points (subset)

High speedcounters (C)

1 phase Range: -2,147,483,648 to +2,147,483,647 counts

Select upto four 1 phase counters with a combined counting frequency of

5kHz or less.Alternatively select one 2 phase or A/B

phase counter with a counting frequency of 2kHz or less.

Note all counters are latched

1 phasec/w start

reset input2 phase

A/B phase

Item Specification

Page 87: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-13

D0 to D127Type: 16 bit data storage register pair

for 32 bit deviceD128 to D7999

Type: 16 bit data storage register pair for 32 bit device

1000 to D7999 set by parameter in 14 blocks of 500 program steps

Type: 16 bit data storage registerData is move from external setting

potentiometers to registersD8030 and D8031)

From the range D8000 to D8255Type: 16 bit data storage register

V and ZType: 16 bit data storage register

P0 to P127

I00 to I50(rising trigger = 1,falling trigger = 0)

N0 to N7 to +32,767 to +2,147,483,647 to FFFFto FFFFFFFF

Remarks

Dataregisters (D)

General 128 points

Latched 7872 points (subset)

File 7000 pointsD

Externallyadjusted

Range: 0 to 2552 points

Special 256 points (inclusive of D8013, D8030 and D8031)

Index 16 points

Pointers (P)

For usewith CALL

128 points

For use withinterrupts

6 points

Nest levels 8 points for use with MC and MCR

ConstantsDecimal K 16 bit: -32,768

32 bit: -2,147,483,648Hexadeci-

mal H16 bit: 0000

32 bit: 00000000

Item Specification

Page 88: FX1N PLC Hw Manual

FX1N Series Programmable Controllers Diagnostics 7.

7-14

Page 89: FX1N PLC Hw Manual

Under no circumstances will MITSUBISHI ELECTRIC be liable or responsible for any consequential damage thatmay arise as a result of the installation or use of this equipment.All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guar-antee operation. MITSUBISHI ELECTRIC will accept no responsibility for actual use of the product based on theseillustrative examples.Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitabilityfor your specific application.

FX1N Series Programmable Controllers

Page 90: FX1N PLC Hw Manual

HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX: J24532 CABLE MELCO TOKYOHIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN

JY992D89301B(MEE0006)

Effective June. 2000Specification are subjectto change without notice.

HARDWARE MANUALFX1N SERIES PROGRAMMABLE CONTROLLERS